WARNING:
Improper installation, adjustment, alteration, service or
maintenance can cause injury, property damage, or loss
of life. Refer to this manual. For assistance or additional
information consult an authorized installer, service agency
or the gas supplier.
FOR YOUR SAFETY:
Do not store or use gasoline or other fl ammable vapours and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by an authorized
installer, service agency or the gas supplier.
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FOR YOUR SAFETY:
What to do if you smell gas:
Do not try to light any applianceDo not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
01/03/08
REGENCY GAS FIREPLACE INSERT
TO THE NEW OWNER
Congratulations! You are the owner of a state-of-the-art Gas Insert by FPI.
The L234 Direct Vent Gas Insert has been designed to provide you with all the warmth and charm
of a fi replace, at the fl ick of a switch. The L234-NG and L234-LP have been approved by Warnock
Hersey for both safety and effi ciency.
As it also bears our own mark, it promises to provide you with economy, comfort and security for
many trouble free years to follow. Please take a moment now to acquaint yourself with these
instructions and the many features of your FPI Fireplace.
This is a copy of the labels that accompany each
L234 Gas Insert. We have printed a copy of the
contents here for your review. The safety label
is located on a plate inside the base of the unit
visible when the bottom louver is opened. Ensure
that the safety label is attached to the unit.
NOTE: FPI units are constantly being
improved. Check the label on the unit and
if there is a difference, the label on the unit
is the correct one.
INSTALLATION
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfi tter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, fl exible
connectors shall not exceed 36 inches in
length.
For the State of Massachusetts, the appliances individual manual shut-off must be a
t-handle type valve.
The State of Massachusetts requires the
installation of a carbon monoxide alarm in
accordance with NFPA 720 and a CO alarm
with battery back up in the same room where
the gas appliance is installed.
4
Regency® L234 Direct Vent Gas Insert
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
INSTALLATION
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
Regency® L234 Direct Vent Gas Insert5
UNIT & FACEPLATE DIMENSIONS
INSTALLATION
6
Regency® L234 Direct Vent Gas Insert
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The FPI Direct Vent Gas Insert must be installed
in accordance with these instructions. Carefully
read all the instructions in this manual fi rst. Consult the building authority having jurisdiction to
determine the need for a permit prior to starting
the installation.
NOTE: Failure to follow the instructions could
cause a malfunction of the heater which could
result in death, serious bodily injury, and/or
property damage. Failure to follow these
instructions may also void your fi re insurance
and/or warranty.
FOR YOUR SAFETY
This appliance requires air for proper combustion.
Always provide adequate combustion and
ventilation air. Follow instructions and information
in CSA B149.1 (in Canada) or the National Fuel
Gas Code ANS Z223.1/NFPA (in the USA),
regarding requirements for combustion and
ventilation air.
GAS PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut off valve during any pressure testing
of the gas supply piping system at test pressures
equal to or less than
1/2 psig. (3.45 kPa).
SPECIFICATIONS
At pressures over 1/2 psig, the pipe to the unit
must be disconnected.
Gas Input Capacity:
Natural Gas 23,500 Btu/h
Propane 21,500 Btu/h
Min. Input:
Natural Gas 12,500 Btu/h
Propane 11,000 Btu/h
Fuels: Approved for use with both natural gas,
and propane. Approved as is for use at 0' to
4,500' (0-1370m).
Electrical: 120V A.C. system.
Circulation Fan: Variable speed, 127 CFM.
Log Set: Ceramic fi bre, 6 per set.
Vent System: 3" co-linear aluminum fl ex
or 2" intake with 3" exhaust.
INSTALLATION INTO A
SOLID FUEL BURNING
FIREPLACE OR
FACTORY BUILT
FIREPLACE
The L234 Gas Inserts have been tested and
approved to be vented into any masonry
fireplace or approved solid fuel burning
factory built fi replace that will allow the insert
to physically fi t into the fi rebox. Refer to the
"Minimum Fireplace Opening" section.
If the factory built fi replace* height is too low
for your Insert, you may remove the smoke
baffl e plate and damper from the factory
built fi replace as long as these items are
saved and are reinstalled in the event that
the Insert is removed. NOTE: Any alterations
made to the listed solid fuel burning factory
built fi replace may void the listing of the
fi replace. Cutting any sheet-metal parts of
the fi replace, in which the gas fi replace insert
is to be installed, is prohibited.
If the factory-built fi replace has no gas
access hole(s) provided, an access hole of
1.5" (37.5mm) or less may be drilled through
the lower sides or bottom of the fi rebox in
a proper workmanship like manner. This
access hole must be plugged with noncombustible insulation after the gas supply
line has been installed.
The fi replace and fi replace chimney must
be clean and in good working order and
constructed of non-combustible materials
and chimney cleanouts must fi t properly.
Refractory, glass doors, screen rails, screen
mesh, and log grates can be removed
from the fi replace before installing the gas
fi replace insert. Smoke shelves, shields
and baffl es may be removed if attached by
mechanical fasteners. A tight seal between
the gas fi replace insert fl ue collar and the
fi replace chimney must be made to prevent
heat loss.
*Check with your local inspector before
commencing with this installation.
Installer must mechanically attach the supplied
label to the inside of the fi rebox of the fi replace
into which the gas fi replace insert is installed.
"WARNING: This fi replace has been converted
for use with a gas fi replace insert only and
cannot be used for burning wood or solid fuels
unless all original parts have been replaced,
and the fi replace re-approved by the authority
having jurisdiction."
BEFORE YOU START
Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of
the following:
General Safety Information
1) The appliance installation must conform
with local codes or in the absence of local
codes, with CAN/CSA B149.1 (in Canada)
or the National Fuel Gas Code ANSI Z223.1
NFPA 54 in the U.S.A. This appliance should
be installed by a qualifi ed gas fi tter technician
only.
2) Installation and repair should be done
by a qualifi ed service person.
3) The appliance should be inspected
before use and at least annually by
a professional service person. More
frequent cleaning may be required due
to excessive lint from carpeting, bedding
material, animal hair, etc. It is imperative
that control compartments, burners
and circulating air passageways of the
appliance be kept clean.
4) See general construction and assembly
instructions. This appliance may only be
installed in a vented, noncombustible
fi replace.
5) This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) Always connect this appliance to a vent
system vent that is run (or routed) to the
outside of the building envelope. Never vent
to another room or inside a building. Make
sure that the vent is properly sized and is
of adequate height to provide the proper
draft.
7) Inspect the venting system annually for
blockage and any signs of deterioration.
8) Any glass removed for servicing must be
replaced prior to operating the appliance.
9) WARNING: Failure to position the parts
in accordance with the diagrams in
this manual or failure to use only parts
specifi cally approved with this appliance
may result in property damage or
personal injury.
10) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fi replace.
INSTALLATION
Regency® L234 Direct Vent Gas Insert7
INSTALLATION
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
aaaaa
a
a
a
a
a
a
a
a
a
a
aaaaaaaaaa
11) Due to high temperatures, the appliance
should be located out of high traffi c areas
and away from furniture and draperies.
Children and adults should be alerted to
the hazards of high surface temperatures,
especially the fi replace glass, and should
stay away to avoid burns or clothing
ignition. Young children should be carefully
supervised when they are in the same
room as the appliance. Clothing or other
fl ammable material should not be placed
INSTALLATION
on or near the appliance.
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
INSTALLATION
CHECKLIST
Before installing vent system ensure that the
damper plate is open and secure to prevent the
damper plate from falling down and crushing
the liner.
8) Install standard and optional features.
Refer to the following sections where
applicable:
a. Brick Panels
b. Log Installation
c. Faceplate
d. Hearth Trim
e. Backing Plate
f. Remote Control (brick panels are
mandatory with remote control option)
g. Wall Thermostat
9) Final check. Refer to the "Final Check"
section. Before leaving this unit with the
customer, the installer must ensure that the
appliance is fi ring correctly. This includes:
a) Clocking the appliance to ensure the
correct fi ring rate.
b) Adjusting the primary air, if required,
to ensure that the fl ame does not
carbon. Refer to the "Gas Insert
Aeration System" section.
c) Ensuring that the appliance is venting
correctly.
MINIMUM FIREPLACE
OPENING
The minimum fi replace opening for the L234
gas fi replace insert is shown in the following
diagrams:
The FPI Gas Insert is installed as listed
below.
1) Check all clearances to combustibles.
Refer to the following sections where
applicable:
a. Minimum Clearances to Combustibles.
b. Combustible Mantel Clearances
c. Mantel Clearances
2) Make the gas connection. Refer to the "Gas
Connection" section.
3) Install the 3" x 3" or 3" x 2" fl ue liner to the
sliding connector plate. Refer to the "Flue
Liner Installation" section.
4) Slide the unit half way into the fi replace.
5) Pull the vent connector plate through the
tapered brackets and fasten to the front
plate. Refer to the "Flue Liner Installation"
section.
No electrical power supply is required for the gas
control to operate. A 120 Volt AC power cord is
hooked up to the fan. Plug the 3 wire cord into
a suitable receptacle. Do not cut the ground terminal off under any circumstances. When
connected with 120 volts, the appliance must
be electrically grounded in accordance with
local codes, current version of the Canadian
Electrical Code CSA C22.1 (in Canada) or in
the absence of local codes, with the National
Electrical Code ANSI/NFPA 70.
WARNING:
Electrical Grounding Instructions
This appliance is equipped with
a three pronged (grounding) plug
for your protection against shock
hazard and should be plugged
directly into a properly grounded
three-prong receptacle. Do not cut
or remove the grounding prong
from this plug.
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
Regency® L234 Direct Vent Gas Insert
INSTALLATION
MINIMUM CLEARANCES TO
COMBUSTIBLES
Unless otherwise stated the clearances listed below are Minimum distances
to combustible materials. Please Note: A major cause of chimney
related fi res is due to a failure to maintain required clearances (air
space) to combustible materials. It is of the greatest importance
that this insert and vent system be installed only in accordance with
these instructions.
Side Walls A 8" (203 mm)*
Ceiling B 56" (1422 mm)
Min. Mantel Height C 21" (533 mm) see Diagram 1
Max. Mantel Depth D 12" (305 mm) see Diagram 1
Alcove Width E 60" (1524 mm)
Alcove Depth F 36" (914 mm)
Hearth Height G 1-1/2" (38 mm)
Hearth Width H 28" (686 mm)
Hearth Depth I 12" (305 mm)
* Alcove side wall must have a min. of 8" clearance.
COMBUSTIBLE MANTEL
CLEARANCES
Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from top of door frame
are shown in the diagram below. Mantel may be installed anywhere in the
shaded area or higher.
Note: A non-combustible mantel may be installed at a lower
height.
Note: Ensure the paint that is used on the mantel and the facing is
“heat resistant” or the paint may discolour.
INSTALLATION
Diagram 1
INSTALLATION WITH NON-COM-
BUSTIBLE HEARTH IN FRONT
12" Max.
Mantel
Faceplate
Hearth
G
Regency® L234 Direct Vent Gas Insert9
D
To p o f
Door Frame
Existing or
Non-Combustible Hearth
12” Min.
C
INSTALLATION WITH COMBUSTIBLE
FLOORING IN FRONT
12" Max.
Mantel
Faceplate
4” min
D
To p o f
Door Frame
C
No hearth required if the unit
is raised 4" (102mm) or more.
Combustible
Flooring
INSTALLATION
VENTING
THE APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY
FLUE SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE.
This appliance is designed to be attached to two 3" (76mm) co-linear
aluminium fl ex running the full length of the chimney. The fl ue length
must be a minimum length of 8' (2.44m) and a maximum of 35' (10.7m).
Periodically check that the vent is unrestricted.
Masonry chimneys may take various contours which the fl exible liner will
INSTALLATION
accommodate. However, keep the fl exible liner as straight as possible,
avoid unnecessary bending.
INSTALLATION WITH 3" & 3" LINERS
Part # Description
948-305 3" Flex - 35 ft. (intake & exhaust)
946-529 FPI Co-linear DV Vertical Termination Cap & Flashing
Vent Run
8' to 20'1"3/16"
20' to 35'3/4"3/16"
NOTE: See instructions in the "Vent Restrictor Positon"
section on positioning of the vent restrictor.
Vent Restrictor
Position
Burner Aeration
Setting
The L234 is also approved for use with a 2" liner for air intake and a 3" liner
for exhaust. This would be suitable for a Class A wood burning chimney
with a minimum 6" round fl ue.
The chimney must be lined with one 2" diameter liner for intake and one
3" diameter liner for exhaust. The minimum vent length is 8' and maximum
is 35'.
INSTALLATION WITH 3" & 2" LINERS
Part # Description
948-305 3" Flex - 35 ft. (exhaust)
948-316 2" Flex - 35 ft. (intake)
946-582 FPI Co-linear DV Vertical Termination Cap, Flashing &
2" Collar
Vent Run
8' to 20'1"3/16"
20' to 35'1"1/8"
NOTE: See instructions in the "Vent Restrictor Positon"
section on positioning of the vent restrictor.
Vent Restrictor
Position
Burner Aeration
Setting
Alternative Approved Venting Components*
980 Vertical Termination Cap
991 High Wind Cap
923GK 3" Co-linear Adaptor with fl ashing
In areas of consistently high winds, we recommend using the Simpson
Dura-Vent System (923GK adapter and 991 high-wind cap).
The Air Intake pipe must be attached to the inlet air collar of the termination
cap.
*NOTE: Simpson Duravent can only be used with 3" and 3" liners.
10
Regency® L234 Direct Vent Gas Insert
INSTALLATION
CONVERTING FROM 3" & 3" VENTING TO 3" & 2"
1) Remove the top plate from the unit by undoing the screw at the front
of the fi rebox and slide out towards the back of the unit.
2) Remove the 3" collar from the top plate by undoing the 4 screws.
NOTE: The screws are secured from the underside of the top plate.
VENT RESTRICTOR POSITION
The Vent Restrictor plate is located on the inside top of the fi rebox.
To change the vent restrictor position, refer to the instructions below;
1) Remove the glass door.
2) Remove brick panels if installed.
3) Remove the 4 screws that hold the vent restrictor plate in place.
4) Adjust the vent restrictor plate to the required vent restrictor
position.
INSTALLATION
Underside of Top Plate
3) Secure the 2" collar to the top plate using 4 screws in place of the 3"
collar.
4) Re-install the top plate to the unit.
1"
›
‹
Factory Set at 1"
5) Once the vent restrictor plate is in the required position, secure using
the 4 screws removed from step 3.
6) Re-install brick panels if removed.
7) Re-install glass door.
3/4"
›
‹
Adjusted to 3/4"
Top Plate with 2" Collar shown on Unit
Regency® L234 Direct Vent Gas Insert11
INSTALLATION
FLUE LINER
INSTALLATION
1) Cut the fl ex liner as required.
2) Mark the end of one liner with an "E" to indicate Exhaust.
3) Connect the other end of the above liner to the exhaust side of the
termination cap, seal connection with high temperature silicone.
INSTALLATION
Secure with gear clamp or screws.
4) Connect the 2nd liner to the inlet side of the cap, seal connection
with high temperature silicone. Secure with gear clamp or screws.
5) Install fl ashing.
6) Insert both liners into chimney, passing through the damper open-
ing.
7) Install termination cap.
8) Connect the marked end of the liner to the exhaust collar of the
vent connector plate marked with an "E", seal connection with high
temperature silicone. Secure with gear clamp or screws.
GAS CONNECTION
GAS CONNECTION WARNING:
Only persons licensed to work with gas piping may
make the necessary gas connections to this appliance.
1) When the appliance is to be installed into either an existing masonry
chimney system or factory built fi replace, thoroughly clean the
chimney before installation.
2) A 3/8" NPT gas supply pipe must be brought near the inlet hole.
The valve inlet is on the right side of the unit.
3) Locate the center point where the vent will pass through the chimney
above the appliance. Move the appliance into the exact location
where it is to be installed. Ensure that the Insert is level.
NOTE: This unit is equipped with a heat sensor thermodisc which
will prevent the blower from operating until the unit reaches the
correct temperature.
9) Connect the 2nd liner to the intake collar, seal connection with high
temperature silicone. Secure with gear clamp or screws.
10) Align vent connector plate with guides on unit.
11) Slide unit into masonry opening, while ensuring that the slots at the
rear of the connector plate mates up with the hold down plate on
the unit.
12) Secure with screw.
NOTE:
1) Final gas connection should be made after unit is in place to avoid
damage to the liner when pushing the unit into position.
2) Mill-pac may be used instead of high tempture silicone and screws
may be used instead of gear clamps at connections of liner to inlet
and vent collars.
GAS INSERT
AERATION SYSTEM
The burner aeration is factory set but may need adjusting due to either
the local gas supply or altitude. Open the air shutter for a blue fl ame
or close for a more yellow fl ame.
Minimum Air Shutter Openings
Vent Run
8' to 20'
3" x 3"
20' to 35'
8' to 20'
3" x 2"
20' to 35'
CAUTION: Carbon will be produced if the air shutter is closed too much.
Note: Any damage due to carboning resulting from improperly setting
the aeration controls is NOT covered under warranty.
Burner Aeration
Setting
NG: 3/16"
LP: 3/16"
NG: 3/16"
LP: 3/16"
NG: 3/16"
LP: 3/16"
NG: 1/8"
LP: 1/8"
12
Note: Aeration Adjustment should only be performed by an authorized
FPI Installer at the time of installation or service.
Regency® L234 Direct Vent Gas Insert
INSTALLATION
GAS PIPE
PRESSURE TESTING
The appliance must be isolated from the gas supply piping system by closing
its individual manual shut-off valve during any pressure testing of the gas
supply piping system at test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator built into the gas control,
and should be checked at the pressure test point.
NOTE: To properly check gas pressure, both inlet and manifold
pressures should be checked using the valve pressure ports
on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise
with a 1/8" wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16"
ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with the unit burning and
the setting should be within the limits specifi ed on the safety label.
6) When fi nished reading manometer, turn off the gas valve, disconnect
the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver.
Note: Screw should be snug, but do not over tighten.
SIT VALVE DESCRIPTION
1) Gas on/off knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Manifold (Outlet) Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection Point
2
INOUT
6
1
5
INSTALLATION
4
3
Regency® L234 Direct Vent Gas Insert13
INSTALLATION
LP Conversion instructions for BEFORE UNIT INSTALLATION.
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER, IF IN DOUBT DO NOT DO THIS CONVERSION!!
LP Conversion Kit Contains:
INSTALLATION
Qty. Part # Description
1 910-037 LP Pilot Orifi ce
1 904-163 Orifi ce #54
1 904-529 5/32" Allen Key
1 918-590 LP Conversion Decal
1 908-528 Red Propane Label
1 918-688 Instruction Sheet
CONVERSION KIT #536-969 FROM NG TO LP
1) Open the left and right side faceplate
panels.
2) Turn off the gas supply.
3) Remove the bottom louver by pulling out.
4) Remove the glass door.
a) Pull off the left side spring hook that
holds the door in place. While holding the
hook turn it upside down and place it into
the middle opening on the top side mounting
bracket. Repeat for right side
Spring Hook
.
Top Mounting Bracket
b) Swing the door out 45 degrees and lift up
and out.
5) Remove the logs if installed.
6) Remove the brick panels if installed.
7) Remove the burner by undoing the 3
screws.
Burner Removed
8) Remove the burner tray by undoing the 4
screws.
Burner Tray Removed
14
Regency® L234 Direct Vent Gas Insert
INSTALLATION
9) Remove burner orifi ce with a 1/2" wrench
and discard.
10) Install the new LP burner orifi ce stamped
#54 and tighten.
11) Pull off the pilot cap to expose the pilot
orifi ce.
13) From the valve remove the black protec-
tion cap by hand from the high-low knob
(Fig.1).
Fig. 1
14) Insert the allen key
into the hexagonal
key-way of the screw
(Fig. 2), rotate it
counter-clockwise
until it is free and
extract it.
Fig.2
WARNING!
Do not overtighten the screw.
Recommended to
grip the wrench by the short side.
18) Verify that if the conversion is from NG to
LPG, the screw must be re-assembled
with the red o-ring visible (Fig. 5).
Red o-ring visible
LPG Configuration
Fig.5
19) Re-assemble the black protection cap
(Fig. 6).
INSTALLATION
12) Unscrew the pilot orifi ce with the supplied
allen key and replace it with the LP pilot orifi ce
in the kit and re-install the pilot cap.
15) Check that the screw is clean and if
necessary remove dirt.
16) Flip the screw (Fig. 3).
Fig.3
17) Using the allen key as shown in Fig.4,
rotate the screw clockwise until snug, do
not overtighten.
Fig. 6
WARNING!
Also check that the pilot and main
burner injectors
are appropriate for the gas type.
20) Attach the label "This unit has been con-
verted to Propane" near or on top of the
serial # decal.
21) Replace yellow "Natural Gas" label with red
"LPG" label.
22) Reverse steps 8) to 1).
NOTE: Before re-installing the burner,
check the LP areation settings.
23) Check the inlet and outlet pressures.
24) Check operation of fl ame control.
25) Check for proper fl ame appearance.
Fig.4
Regency® L234 Direct Vent Gas Insert15
INSTALLATION
OPTIONAL BRICK PANEL INSTALLATION
NOTE: Brick Panels are mandatory when using Optional Remote
1) Carefully remove the brick panels from the box and unwrap them.
2) Insert the back brick panel by carefully placing it against the back
wall of the fi rebox and rest it on the rear log tray.
INSTALLATION
Back Brick Panel
Rear Log Tray
3) Slide the right side brick panel into position and secure in place using
the brick clip. Repeat for left side.
Brick Clip
Completed Brick Panel Installation
Right Side Brick Panel
16
Regency® L234 Direct Vent Gas Insert
INSTALLATION
CONTOUR OR CONTEMPORARY FACEPLATE
Faceplate Contents List:
1 Faceplate (Contour or Contemporary)
1 Louver (Contour or Contemporary)
4 Screws (10-24 x 1/2" Pan Head Phillips Black)
2 Wire Clips
1 Cable Tie
Faceplate Installation:
1) Place the 4 10-24 x 1/2" screws into the faceplate mounting brackets
as identifi ed in diagram 1.
4) Place the 2 wire clips on the inside of the right faceplate panel as
INSTALLATION
shown in diagram 3.
Diagram 3
5) From the right side of the unit connect the red female ON/OFF valve
connectors to the ON/OFF switch located on the right faceplate
panel. See diagram 4.
Diagram 1
2) Open the left and right side faceplate panels of the faceplate.
3) Mount the faceplate onto the unit by aligning the 4 key hole slots in
the faceplate with the screws installed to the mounting brackets on
the unit. Tighten screws to secure. See diagram 2.
Faceplate shown on unit
without left and right
side panels to show
keyhole mounting.
ON/OFF Connectors
Diagram 4
Diagram 2
Regency® L234 Direct Vent Gas Insert17
INSTALLATION
6) Peel off the tape from the velcro strips and mountthe DC Sparker
to the velcro on the inside of the right faceplate panel as shown
in diagram 5. Install batteries into the DC Sparker (batteries are
included with packaged manual).
NOTE: The DC Sparker comes with the unit. It is cable tied to
the top left side mounting bracket.
INSTALLATION
Diagram 5
7) From the right side of the unit connect the black electrode wire to the
DC Sparker as shown in diagram 6.
9) Close the right side faceplate panel.
10) Remove the remote receiver bracket from the left side of the unit by
undoing the 2 screws. See diagram 8.
Remote Receiver
Bracket
DC Sparker
Diagram 8
11) Remove the grommet from the bracket on the left side of the unit.
See diagram 9.
Diagram 6
8) Secure the loose wires into the wire clips above and to the bottom
left of the DC Sparker as shown in diagram 7.
18
Electrode Wire
Diagram 9
12) From the left side faceplate panel expose the fan wires from the
sleeve and connect them to the wires from the unit as shown in
diagram 10.
Diagram 10
Grommet
Regency® L234 Direct Vent Gas Insert
INSTALLATION
13) Tuck the wires completely into the sleeve and place the supplied
cable tie to the end of it as shown in diagram 11.
Diagram 11
14) Place the grommet removed from step 10 over the sleeve (see
diagram 12) and put back in place (see diagram 13).
NOTE: Ensure connectors are tucked in behind the mounting bracket
to allow the side faceplate panel to close easily.
17) Fit the bottom louver into the slots at the bottom of the fi rebox as
shown in diagram 14.
INSTALLATION
Diagram 14
Completed Faceplate Installation:
Diagram 12
Contemporary Faceplate
Diagram 13
15) Re-install the remote receiver bracket (reverse step 10).
16) Close the left side faceplate panel.
Contour Faceplate
Regency® L234 Direct Vent Gas Insert19
INSTALLATION
OPTIONAL BACKING PLATE
INSTALLATION
Backing Plate Contents List:
9 Screws (#8 x 1/2" Type B Black)
1 Backing Plate
Backing Plate Assembly:
Backing Plate Installation:
Attach Top Backing Plate to Faceplate
1) Remove the faceplate (Contour or Contemporary) from the unit if
already installed.
2) Lay the faceplate on its front, on a soft surface to prevent
scratching.
3) Attach the top piece of the backing plate to the faceplate using 5
screws provided as shown in diagram 1.
Rear View of Faceplate
Customize Backing Plate:
The Backing Plate can be adjusted to custom fi t an installation by trimming
the inside of the top, corner and side pieces as shown in the diagram
below. The dotted lines shown are only an example of where you can
cut. Cuts can be made beyond these marks as required.
Trim the backing plate using a metal cutting blade. No cut edges will be
exposed once installation is complete.
NOTE: In place of where any existing screw holes are cut, new holes
will need to be drilled for attachment.
The inside of the backing plate
may be cut as required using a
metal cutting blade.
Do not cut the outside edges.
Diagram 1
Attach Faceplate & Top Backing Plate to Unit
4) Place the 4 10-24 x 1/2" screws into the faceplate mounting brackets
as identifi ed in diagram 2. Screws are provided with faceplate
packaging.
20
Rear View of
Backing Plate
Diagram 2
Regency® L234 Direct Vent Gas Insert
INSTALLATION
5) Open the left and right side faceplate panels of the faceplate.
6) Mount the faceplate onto the unit by aligning the 4 key hole slots in
the faceplate with the screws installed to the mounting brackets on
the unit. Tighten screws to secure. See diagram 3.
Faceplate shown on unit
without left and right
side panels to show
keyhole mounting.
Diagram 3
Attach Left & Right Corner Backing Plate
9) Place the right side corner backing plate over the top and right side
backing plate. Push in place to secure, see diagram 5. Repeat for
left side.
Diagram 5
Completed Backing Plate Installation:
INSTALLATION
Attach Left & Right Backing Plate to Faceplate
7) Align the screw holes on the left and right side backing plate with
the oblong openings in the faceplate and secure in place using a
minimum of 2 screws on each side as shown in diagram 4.
Faceplate shown on unit without left and
right side faceplate panels to show mounting
of left and right side backing plate.
Diagram 4
8) Close the left and right side faceplate panels.
Regency® L234 Direct Vent Gas Insert21
INSTALLATION
Hearth Trim Contents List:
4 Screws (10-24 x 1/2" Truss Head)
1 Hearth Trim
Customize Hearth Trim:
INSTALLATION
a) The Hearth Trim can be adjusted to custom fi t an installation by
pulling apart the top piece from the bottom piece.
b) Cut the top of the bottom piece of the hearth trim to the appropriate
height using a metal cutting blade.
NOTE: The tab bends at the back of the top piece of the hearth trim
should be used as the measuring point to the hearth to measure the
height required.
c) Reattach the top piece of the hearth trim to the cut bottom piece by
fi tting in place.
OPTIONAL HEARTH TRIM
Hearth Trim Installation:
1) Open the left and right side faceplate panels.
2) Align the screw holes on the hearth trim with the screw holes on the
fl anges on the left and right side faceplate. Secure in place using 2
screws on each side as shown in diagram 1.
3) Close the left and right side faceplate panels.
Faceplate shown without left
and right side panels to show
mounting of hearth trim.
Diagram 1
Completed Hearth Trim Installation:
22
Regency® L234 Direct Vent Gas Insert
LOG SET INSTALLATION
INSTALLATION
Read the instructions below carefully and refer to the images.
Dangerous operating conditions may occur if the logs are not
positioned in their correct locations. If the logs are broken
do not use the unit until they are replaced. Broken logs can
interfere with the pilot operation.
Log kit (Part # 536-930) contains the following pieces:
a) 2-711 Rear Log
b) 2-712 Center Log
c) 2-713 Left Log
d) 2-714 Front Log
e) 2-715 Top Left Log
f) 2-716 Top Right Log
g) Embers (supplied with packaged manual)
h) 946-669 Platinum Embers (supplied with packaged manual)
2-711
2-713
2-715
2-716
INSTALLATION
2-711
3) Place log 2-714 on the base of the fi rebox in front of the burner.
2-712
2-714
1) Carefully remove the logs from the box and unwrap them. The logs are fragile, handle with care - do not force into position.
2) Fit log 2-711 into the pins on the rear log tray.
2-711
2-714
4) Fit log 2-712 into the pins on the middle of the burner.
2-712
Regency® L234 Direct Vent Gas Insert23
INSTALLATION
6) Place log 2-715 into the pin on log 2-712 and rest the right end of
the log on the notch in log 2-713.
2-712
INSTALLATION
5) Fit the left side of log 2-713 into the pin on log 2-714 and rest the
right side of the log on the burner plate pushing it against the tab.
2-713
2-714
2-713
2-715
2-712
Notch
2-713
Tab
2-712
24
Regency® L234 Direct Vent Gas Insert
INSTALLATION
7) Place embers on the right side of the burner as shown.8) Fit log 2-716 into the pin on log 2-712.
2-716
2-712
INSTALLATION
Right side of Burner
Also place a few embers along the burner tube next to log 2-713.
Separate platinum embers and place on and around the embers.
Avoid stacking platinum embers.
2-713
Regency® L234 Direct Vent Gas Insert25
INSTALLATION
Completed Log Set Installation
INSTALLATION
2-7152-712
2-711
2-713
2-714
2-716
26
Regency® L234 Direct Vent Gas Insert
WIRING DIAGRAMS
INSTALLATION
This heater does not require a 120V A.C. supply for operation. However,
a 120V A.C. power supply is needed for the fan/blower operation.
Caution: Ensure that the wires do not touch any hot
surfaces and are away from sharp edges.
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation.
WARNING: Electrical Grounding Instructions
This appliance is equipped with a three pronged
(grounding) plug for your protection against shock
hazard and should be plugged directly into a properly
grounded three-prong receptacle. Do not cut or remove
the grounding prong from this plug.
INSTALLATION
Regency® L234 Direct Vent Gas Insert27
INSTALLATION
OPTIONAL REMOTE
CONTROL
IMPORTANT
Due to the extreme heat this gas insert
emits, brick panels are required to be
installed in the unit when using either
remote control option.
INSTALLATION
Use of FPI Remote Control Kit #910-399 or
#910-368 is approved for this unit. Use of other
systems may void your warranty.
The remote control kit comes with a hand held
transmitter, a receiver and a wall mounting
plate.
Refer to Remote Control manual for complete
user setup and operation instructions.
Remote Receiver Installation
1) Remove the control switch from the remote
receiver by gently pulling out.
Control
Switch
Remote
Receiver
4) Re-install the control switch and the battery
pack (with batteries).
5) Remove the peel off from the velcro on the
receiver bracket on the left side of the unit.
6) Secure the receiver to the velcro on the
recevier bracket.
Receiver
Receiver Bracket
7) Run the receiver wires under the base of the
fi rebox to the left side of the unit.
OPTIONAL WALL
THERMOSTAT
A wall thermostat may be installed if desired,
follow the wiring diagram below. Note: the wires
are connected to the "TH" on the gas valve. Use
the table below to determine the maximum wire
length. FPI offers an optional programmable
thermostat but any 250-750 millivolt rated nonanticipator type thermostat that is CSA, ULC
or UL approved may be used.
It is recommended that the thermostat be
installed on an interior wall.
CAUTION
Do not connect the millivolt
wall thermostat wires
to the 120V wires.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire Size Max. Length
14 GA.
16 GA.
18 GA.
20 GA.
22 GA.
50 Ft.
32 Ft.
20 Ft.
12 Ft.
9 Ft.
2) Remove the spring loaded battery pack by
pushing in and then pulling out.
Battery
Pack
3) Remove the receiver from the bracket and
discard the bracket.
Bracket
Receiver
8) Connect the reciever wires to the valve.
9) Secure the loose wires under the fi rebox
in the wire clips located on the base of the
fi rebox.
FINAL CHECK
Before leaving this unit with the customer, the
installer must ensure that the appliance is fi ring
correctly. This includes:
1) Clocking the appliance to ensure the
correct fi ring rate (rate noted on label) at
15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15 min. to stabilize.
3) Check for proper draft.
CAUTION
Any alteration to the product that
causes sooting or carboning that
results in damage to the exterior
facia is not the responsibility of
the manufacturer.
28
Regency® L234 Direct Vent Gas Insert
OPERATING INSTRUCTIONS
FIRST FIRE
The fi rst fi re in your insert is part of the paint
curing process. To ensure that the paint is
properly cured, it is recommended that you
burn your fi replace for at least four (4) hours
the fi rst time you use it with the fan on. When
fi rst operated, the unit will release an odour
caused by the curing of the paint, the burning
off of any oils remaining from manufacturing.
Smoke detectors in the house may go off at
this time. Open a few windows to ventilate the
room for a couple of hours.
The glass panel may require cleaning after the
unit has cooled down.
DO NOT ATTEMPT TO CLEAN THE
GLASS WHILE IT IS HOT.
Note: When the glass is cold and the
appliance is lit, it may cause
condensation and fog the glass.
This condensation is normal and
will disappear in a few minutes as
the glass heats up.
DO NOT BURN THE APPLIANCE
WITHOUT THE GLASS FRONT IN
PLACE.
During the fi rst few fi res, a white fi lm
may develop on the glass front as part
of the curing process. The glass should
be cleaned or the fi lm will bake on and
become very diffi cult to remove. Use a
non-abrasive cleaner and NEVER clean
the glass while it is hot.
OPERATING
INSTRUCTIONS
1) Read and understand these instructions
before operating this appliance.
2) Check to see that all wiring is correct and
enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the door frame is
properly positioned. Never operate the
appliance with the glass removed.
5) Verify that the venting and cap are
unobstructed.
6) Ensure that the brick panels, if used, are
installed.
7) Verify log placement. If the pilot cannot be
seen when lighting the unit, the logs have
been incorrectly positioned.
8) The unit should never be turned off, and on
again without a minimum of a 60 second
wait.
LIGHTING
PROCEDURE
IMPORTANT
Prior to igniting or reigniting the
pilot, remove the glass door.
NOTE: For all propane units and units
equipped with electric spark boxes,
see "Copy of Lighting Plate Instructions" section for more details.
3) Turn gas control knob counterclockwise
so indicator points to the "PILOT" position.
Depress the gas control knob fully. Depress
the ignitor button several times until the
pilot lights. After approximately one minute,
release the gas control knob. The pilot fl ame
should continue to burn. If the pilot does not
remain lit, repeat operation allowing a longer
period before releasing gas control knob.
4) When the pilot stays lit, turn the gas knob
further counterclockwise to the "ON"
position.
5) Reinstall the glass door (refer to the "Standard
Flush Door" section).
6) Use the switch, thermostat or remote control
to turn on the unit.
7) Rotate the fl ame height regulator to adjust
the fl ame height higher or lower.
SHUTDOWN
PROCEDURE
1) Use the switch, thermostat or remote control
to turn off the main burner.
2) Turn the main gas control clockwise to the
"OFF" position to turn off the pilot.
3) Turn off all electric power to appliance if
service is to be performed.
OPERATION
Only when the pilot holds, without pressure
being applied to the control knob, should you
reinstall the glass door. The unit must not be
operated with the glass door removed.
IMPORTANT: Gas on/off knob cannot be
turned from "PILOT" to "OFF" unless it is
partially depressed.
1) Turn burner OFF using "ON/OFF" switch.
2) Turn gas control knob so indicator points
to "OFF" position and allow 5 minutes for
any gas in the combustion chamber to
escape.
Regency® L234 Direct Vent Gas Insert29
OPERATING INSTRUCTIONS
OPERATION
COPY OF LIGHTING INSTRUCTION PLATE
AUTOMATIC
CONVECTION
FAN OPERATION
The fan operates automatically. Turn the knob
on the left side of the faceplate to adjust to the
desired speed. The fan will turn on as the insert
comes up to operating temperature. After the
unit has been turned off and the unit has been
cooled to below useful heat output range, the
fan will shut off automatically.
NORMAL OPERATING
SOUNDS OF
GAS APPLIANCES
It is possible that you will hear some sounds
from your gas appliance. This is perfectly normal
due to the fact that there are various gauges
and types of steel used within your appliance.
Listed below are some examples. All are normal operating sounds and should not be considered
as defects in your appliance.
Blower:
FPI gas appliances use high tech blowers to
push heated air farther into the room. It is not
unusual for the fan to make a "whirring" sound
when ON. This sound will increase or decrease
in volume depending on the speed setting of
your fan speed control.
Gas Inlet
Gas Inlet
OFF
Burner Tray:
The burner tray is positioned directly under the
burner tube(s) and logs and is made of a different
gauge material from the rest of the fi rebox and
body. Therefore, the varying thicknesses of steel
will expand and contract at slightly different
rates which can cause "ticking" and "cracking"
sounds. You should also be aware that as there
are temperature changes within the unit. These
sounds will likely re-occur. Again, this is normal
for steel fi reboxes.
Blower Thermodisc:
When thermally activated switch turns ON, it
will create a small "clicking" sound. This is the
contact switch closing.
Pilot Flame:
While the pilot fl ame is on it will make a slight
"whisper" sound.
Gas Control Valve:
As the gas control valve turns ON and OFF, a
dull clicking sound may be heard. This is normal
operation of a gas regulator or valve.
Unit Body and Firebox:
Different types and thicknesses of steel will
expand and contract at different rates resulting in
some "cracking" and "ticking" sounds which will
be heard throughout the cycling process.
30
Regency® L234 Direct Vent Gas Insert
MAINTENANCE
MAINTENANCE
INSTRUCTIONS
1) Always turn the gas valve to the off position
before cleaning. For relighting, refer to
lighting instructions. Keep the burner and
control compartment clean by brushing and
vacuuming at least once a year.
When cleaning the logs, use a clean soft
paint brush as the logs are fragile and easily
damaged.
2) Clean (never when unit is hot) appliance,
door and louvers with a damp cloth. Never
use an abrasive cleaner. The fi nishes on
louvers and doors may be scratched if
abrasives are used to clean them. The
heater is fi nished in a heat resistant paint
and should only be refi nished with heat
resistant paint (not with wall paint). FPI uses
StoveBrite Paint - Metallic Black #6309.
3) Make a periodic check of the burner for
proper position and condition. Visually
check the fl ame of the burner periodically,
making sure the fl ames are steady: not
lifting or fl oating. If there is a problem, call
a qualifi ed service person.
4) The appliance and venting system must be
inspected before use, and at least annually,
by a qualifi ed fi eld service person, to ensure
that the fl ow of combustion and ventilation
air is not obstructed.
During the annual service call, the burners
should be removed and cleaned from the
burner tray.
5) Keep the area near the appliance clear and
free from combustible materials, gasoline
and other fl ammable vapours and liquids.
WARNING: CHILDREN AND ADULTS
SHOULD BE ALERTED TO THE
HAZARDS OF HIGH SURFACE
TEMPERATURE AND SHOULD STAY
AWAY TO AVOID BURNS OR CLOTHING
IGNITION. YOUNG CHILDREN SHOULD
BE CAREFULLY SUPERVISED WHEN
THEY ARE IN THE SAME ROOM AS
THE APPLIANCE.
CAUTION: ANY SAFETY SCREEN OR
GUARD REMOVED FOR SERVICING
AN APPLIANCE MUST BE REPLACED
PRIOR TO OPERATING THE
APPLIANCE.
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED
ON OR NEAR THE APPLIANCE.
6) Each time the appliance is lit, it may cause
condensation and fog the glass. This
condensation and fog is normal and will
disappear in a few minutes as the glass heats
up.
Never operate the appliance without the
glass properly secured in place or with
the door open.
7) Do not use this appliance if any part has been
under water. Immediately call a qualifi ed
service technician to inspect the appliance
and to replace nay part of the control system
and any gas control which has been under
water.
8) Periodically check the pilot fl ames. Correct
fl ame pattern has three strong blue fl ames: 1
fl owing around the thermopile and 1 around
the thermocouple, and 1 fl owing across the
front of the burner.
Note: If you have an incorrect fl ame pattern,
contact your FPI dealer for further
instructions.
Front Burner Tube
Top view of pilot fl ame
Incorrect fl ame pattern will have small, probably
yellow fl ames, not coming into proper contact with
the rear of the burner or thermopile.
Front Burner Tube
Top View of pilot fl ame
GENERAL VENT
MAINTENANCE
Conduct an inspection of the venting system
semi-annually. Recommended areas to inspect
as follows:
1) Check the Venting System for corrosion in
areas that are exposed to the elements.
These will appear as rust spots or streaks, and
in extreme cases, holes. These components
should be replaced immediately.
2) Remove the Termination Cap, and shine a
fl ashlight down the Vent. Remove any bird
nests, or other foreign material.
3) Check for evidences of excessive
condensation, such as water droplets forming
in the inner liner, and subsequently dripping
out the joints. Continuous condensation can
cause corrosion of caps, pipe, and fi ttings.
It may be caused by having excessive
lateral runs, too many elbows, and exterior
portions of the system being exposed to
cold weather.
4) Inspect joints to verify that no pipe
sections or fi ttings have been disturbed,
and consequently loosened. Also check
mechanical supports such as Wall Straps,
or plumbers' tape for rigidity.
LOG REPLACEMENT
The unit should never be used with broken logs.
Turn off the gas valve and allow the unit to cool
before opening door to carefully remove the
logs. The pilot light generates enough heat to
burn someone. If for any reason a log should
need replacement, you must use the proper
replacement log. The position of these logs
must be as shown in the diagram under Log
Installation.
NOTE: Improper positioning of logs may
create carbon build-up and will alter the unit’s
performance which is not covered under
warranty.
MAINTENANCE
GLASS GASKET
If the glass gasket requires replacement use
a tadpole gasket for the Flush Front (Part #
936-155).
DOOR GLASS
Your FPI insert is supplied with high temperature,
5 mm Neoceram ceramic glass that will withstand
the highest heat that your unit will produce. Do
not abuse the glass by striking the surface or by
slamming the door shut.
If your glass requires cleaning, we recommend
using an approved glass cleaner available at
all authorized dealers. Do not use abrasive
materials. Do not clean the glass when hot.
In the event that you break your glass by
impact, purchase your replacement from an
authorized FPI dealer only, do not use substitute
materials. Follow our step-by-step instructions
for replacement. Warning: Wear gloves when
removing damaged or broken glass.
Caution: Do not operate appliance with
glass panels removed, cracked or broken.
Replacement of the glass should be done by
a licensed or qualifi ed service person.
Regency® L234 Direct Vent Gas Insert31
MAINTENANCE
FAN REPLACEMENT
1) Unplug the power source.
2) Open the left and right side faceplate
panels.
3) Remove the bottom louver by pulling out.
4) Remove the glass door.
a) Pull off the left side spring hook that holds
the door in place. While holding the hook turn
it upside down and place it into the middle
opening on the top side mounting bracket.
Repeat for right side
Spring Hook
.
b) Swing the door out 45 degrees and lift up
and out.
5) Remove the logs.
6) Remove brick panels, if installed.
7) Remove the burner by undoing the 3
screws.
8) Remove the burner tray by undoing the 4
screws.
Burner Tray Removed
MAINTENANCE
Top Mounting Bracket
9) Remove the rear log tray by undoing the 3
screws.
Burner Removed
Rear Log Tray Removed
32
Regency® L234 Direct Vent Gas Insert
MAINTENANCE
10) Remove the fan cover plate by undoing the
12 screws that hold it in place.
Fan Cover Plate Removed
12) Remove the 2 screws that hold the fan bracket
in place.
13) Remove the fan by sliding the fan forward
and lift up and out.
15) Replace the fan.
NOTE: Bend the connector clips down before
re-installing the fan cover plate.
Connector Clips
16) Reverse steps 14 - 1.
11) Unplug the fan connector wires.
14) Remove the ground screw which holds the
ground wire.
MAINTENANCE
Ground Wire
Regency® L234 Direct Vent Gas Insert33
MAINTENANCE
VALVE REPLACEMENT
1) Open the left and right side faceplate
panels.
2) Remove the bottom louver by pulling out.
3) Remove the glass door.
a) Pull off the left side spring hook that holds
the door in place. While holding the hook turn
it upside down and place it into the middle
opening on the top side mounting bracket.
Repeat for right side.
Spring Hook
b) Swing the door out 45 degrees and lift up
and out.
4) Remove the logs.
5) Remove brick panels, if installed.
6) Remove the valve shield by undoing the 2
screws.
7) Disconnect the gas connection to the
valve.
8) Disconnect the ignitor wire from the DC
Sparker.
9) Disconnect the valve wires from the DC
Sparker.
DC Sparker Wires
MAINTENANCE
Top Mounting Bracket
10) Unplug the 2 connectors from the valve.
Valve Shield
34
Regency® L234 Direct Vent Gas Insert
MAINTENANCE
11) Remove the burner by undoing the 3
screws.
Burner Removed
13) Remove the rear log tray by undoing the 3
screws.
Valve Removed
15) Replace the valve.
16) Reverse steps 14 - 1.
Rear Log Tray Removed
12) Remove the burner tray by undoing the 4
screws.
Burner Tray Removed
14) Remove the 12 screws that hold the valve
tray to the fi rebox and carefully pull out.
MAINTENANCE
Regency® L234 Direct Vent Gas Insert35
PARTS LIST
MAIN ASSEMBLY
Part # Description Part # Description
1) 940-355/P Glass
536-539 Door Frame Assembly
536-540 Door Frame Assembly with Glass
2) 948-463 Burner Assy - NG/LP
3) 536-092 Log Tray Middle
4) 536-014 Log Tray Rear
5) 536-011 Fan Access Plate
6) 536-107 Gasket - Fan Access Plate
7) 536-517/P Fan Assembly 120 V
910-215/P Fan Motor 120 V
910-794 Power Cord
910-985 Wire Harness (Faceplate) - Black
910-986 Wire Harness (Faceplate) - Red
910-692 Wire Fan to Power Cord Ground
910-142 Fan Auto On/Off Thermodisc
536-522 Baffl e Plate Assembly
536-901 Brick Panel Set - Standard Brown
536-902 Brick Panel Set - Standard Red
9) * Brick Panel - Right
10) * Brick Panel - Left
11) * Brick Panel - Back
511-031 Brick Clip
910-073 Battery Holder - DC Sparker
910-074 DC Sparker - Switch
910-478 Valve - S.I.T. - Natural Gas / Propane
* Valve Tray
536-106 Thermal Insulation
* Insulation Hold Down Bracket
* Louver Hold Down - Top
536-109 Gasket - Valve Tray
536-930 Complete Log Set
* Bottom Log
* Center Top Log
* Front Log
* Left Log
* Right Log
* Top Left Log
* Rear Log
* Top Right Log
918-667 Manual
* Not available as a replacement part.
12) 536-523 Flue Adaptor Assembly
13) * Valve Shield
14) 536-091 Pilot Hood
15) 910-038 Pilot Assy- 3 Flame - S.I.T. - NG
910-039 Pilot Assy - 3 Flame - S.I.T. - LP
904-430 Orifi ce #42 - NG
904-163 Orifi ce #54 - LP
936-170 Orifi ce Gasket
Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit
thoroughly before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of a
Excalibur Product. This warranty is not transferable.
The Warranty: Limited Lifetime
The combustion chamber, heat exchanger, burner tubes/pans, logs, brick panels and gold plating (against defective manufacture only) are covered under the Limited Lifetime
Warranty for fi ve (5) years for parts and subsidized labour* and parts only thereafter.
Glass is covered for lifetime against thermal breakage only, parts and subsidized labour* for fi ve (5) years and parts only thereafter from date of purchase.
External casting, surrounds and grills are covered against cracks and warps resulting from manufacturer defects, parts and subsidized labour* for three (3) years from the date
of purchase and parts only thereafter.
Special Finishes - One year on brushed nickel and antique copper full screens and doors. You can expect some changes in color as the product "ages" with constant heating
and cooling. FPI warranties the product for any manufacturing defects on the original product. However, the manufacturers warranty does not cover changing colors and marks,
ie. fi nger prints, etc applied after the purchase of the product. Damage from the use of abrasive cleaners is not covered by warranty.
Electrical and mechanical components such as blowers, switches, wiring, thermodiscs, FPI remote controls, spill switches, thermopiles, thermocouples, pilot assembly components,
and gas valves are covered for two years parts and one year subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are considered repairs and
continue as if new with appliance. ie. twelve (12) months from original purchase date of appliance with a minimum of three (3) months coverage from date of replacement.
FPI venting components are covered parts and subsidized labour* for three (3) years from date of purchase.
Simpson Dura-Vent venting components (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.
Repair/replacement parts purchased by the consumer from FPI after the original coverage has expired on the unit will carry a 90 day warranty, valid with a receipt only. Any
item shown to be defective will be repaired or replaced at our discretion. No labor coverage is included with these parts.
Conditions:
Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI's option, through an accredited distributor or agent provided
that the defective part be returned to the distributor or agent Transportation Prepaid, if requested.
Porcelain/Enamel - Absolute perfection is either guaranteed nor commercially possible. Any chips must be reported and inspected by an authorized dealer within three days of
installation. Reported damage after this time will be subject to rejection.
It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated
for manufacturer defect.
The authorized selling dealer is responsible for all in-fi eld service work carried out on your Regency product. FPI will not be liable for results or costs of workmanship from
unauthorized service persons or dealers.
At all times FPI reserves the right to inspect product in the fi eld which is claimed to be defective.
All claims must be submitted to FPI by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer name,
purchase date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim.
At no time will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufactured.
ie. as products evolve, fi eld modifi cations or upgrades will not be performed.
FPI will not be liable for travel costs for service work.
Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.
Embers, rockwool, gaskets, door handles and paint are not covered under the terms of this warranty policy.
Any unit which shows signs of neglect or misuse is not covered under the terms of this warranty policy.
The warranty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, negligence
or accident, spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by mechanical
systems such as furnaces, fans, clothes dryer, etc.
Freight damage to stoves and replacement parts is not covered by warranty and is subject to a claim against the freight carrier by the dealer.
FPI will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.
Performance problems due to operator error will not be covered by this warranty policy.
Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from FPI, may nullify your warranty
on this product.
Any alteration to the unit which causes sooting or carboning that results in damage to the interior / exterior facia is not the responsibility of FPI.
* Subsidy according to job scale as predetermined by FPI.
Regency® L234 Direct Vent Gas Insert39
FPI fi replaces are designed with reliability and simplicity
in mind. In addition, our internal Quality Assurance Team
carefully inspects each unit thoroughly before it leaves
our door.
FPI Fireplace Products International Ltd. is pleased to extend
this Limited Lifetime Warranty to the original purchaser of
a FPI Product.
See the inside back cover for details.
Register your Regency® online at
http://www.regency-fi re.com
Installer: Please complete the following information
Dealer Name & Address: ______________________________________________