These gas appliances have been tested in
accordance with AS4553-2000, NZS 5262
and have been certifi ed by the Australian
Gas Association for installation and operation as described in these Installation and
Operating Instructions.
Your unit should be serviced annually by
an authorised service person.
PLEASE KEEP THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause
injury or property damage. Refer to this
manual. For assistance or additional information consult an authorised installer,
service agency or the gas supplier.
FOR YOUR SAFETY
Do not store or use gasoline or other fl am-
mable vapours and liquids in the vicinity of
this or any other appliance.
Installation and service must be performed
by an authorised installer, service agency or
the gas supplier.
918-448b
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appli-
ance
Do not touch any electri-
cal switch: do not use any
phone in your building.
Immediately call your gas
supplier from a neighbour's
phone. Follow the gas supplier's instructions.
If you cannot reach your
gas supplier, call the fi re
department.
06/23/08
Page 2
REGENCY
GAS INBUILT FIREPLACE
TO THE NEW OWNER
Congratulations! You are the owner of a state-of-the-art Gas Inbuilt Fireplace by FPI. The Regency
Gas Fireplace Series of appliances has been designed to provide you with all the warmth and
charm of a fi replace, at the fl ick of a switch. The model IG35 of this series has been approved
by Australian Gas Association for both safety and effi ciency. As it also bears our own mark, it
promises to provide you with economy, comfort and security for many trouble free years to follow.
Please take a moment now to acquaint yourself with these instructions and the many features of
your Regency Fireplace.
UNIT DIMENSIONS
2
Regency IG35 Gas Inbuilt Fireplace
Page 3
TABLE OF CONTENTS
REGENCY GAS FIREPLACE INSERT
DATA BADGE
Data Badge....................................................................5
INSTALLATION
Important Message ........................................................5
For Your Safety ..............................................................5
Before You Start ............................................................5
This is a copy of the label that accompanies
each Regency IG35 Gas Inbuilt fi replace. We
have printed a copy of the contents here for
your review.
DATA BADGE NOTE: Regency units are constantly being improved. Check the label on the
unit and if there is a difference, the label on the
unit is the correct one.
(Australia Only)
4
Regency IG35 Gas Inbuilt Fireplace
Page 5
INSTALLATION
IMPORTANT
MESSAGE
The Regency Gas Fireplace must be installed
in accordance with these instructions. Carefully
read all the instructions in this manual fi rst.
Note: Failure to follow these instructions
could cause a malfunction of the
heater which could result in death,
serious bodily injury, and/or property damage. Failure to follow these
instructions may also void your fi re
insurance and/or warranty.
FOR YOUR SAFETY
This appliance requires air for proper combustion. Always provide adequate combustion and
ventilation air. Follow instructions and information in the current AS5601-2004, NZS 5261
or local codes. Consult the "authority having
jurisdiction" to determine the need for a permit
prior to starting the installation.
MATERIALS REQUIRED
A 240 Volt AC power cord is hooked up to the
unit. Plug 3 wire cord into a suitable receptacle.
Do not cut the ground terminal off under any
circumstances.
When connected with 240 volts, the appliance
must be electrically grounded in accordance
with local codes.
This unit is polarity sensitive and will not operate if polarity is incorrect.
BEFORE YOU START
Installation is to be carried out ONLY by an
authorised person.
1) The appliance shall be installed in accord-
ance with the manufacturer's installation
instructions, local gas fi tting regulations,
municipal building codes, water supply
regulations, electrical wiring regulations,
with AS5601-2004. (AGA gas installation
code) NZS 5261(New Zealand)
2) Installation and repair should be done
ONLY by an authorised person.
3) The appliance should be inspected before
use and at least annually by an authorised
service person. More frequent cleaning may
be required due to excessive lint from carpeting, bedding material, etc. It is imperative
that control compartments, burners and
circulating air passageways of the appliance
be kept clean and free from excessive lint
from carpeting.
4) See general construction and assembly
instructions. This appliance may only be installed in a fl ued, non-combustible fi replace.
The appliance and fl ue should be enclosed
when installed or passing through a living
area, where children may come in contact
with it.
This appliance can also be installed into the
approved Zero Clearance Kit #486-900 in a
combustible situation.
5) Always connect this space heater to a chimney and fl ue to the outside of the building
envelope. Never fl ue to another room. Make
sure that the fl ue is properly sized and is
of adequate height to provide the proper
draft.
6) Inspect the fl ueing system annually for
blockage and any signs of deterioration.
7) Any safety glass removed for servicing
must be replaced prior to operating the appliance.
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fi replace.
INSTALLATION
CHECKLIST
The Regency Gas Insert is installed as listed
below.
1) Unit Location - refer to "Clearances to
Combustibles" section.
2) Make the gas connections. Refer to "Gas
Connections" section.
3) Install the fl ue or liner to the fl ue collar. Refer
to "Flueing" section.
4) Slide the unit into the fi replace.
5) Test gas pressure, refer to "Gas Pipe Pres-
sure Testing" section. Check aeration, refer
to "Aeration Settings" section.
6) Test for fl ue spillage, refer to "Test for Flue
Spillage" section.
7) Install the optional brick panels. Refer to
"Optional Brick Panels" section.
8) Install the log set. Refer to "Log Set installation" section.
9) Assemble and install the faceplate and trim
and louvres. Refer to "Faceplate, Trim &
Louvre" section.
10) Optional Premium Flush Front installation.
Refer to "Premium Flush Front Installation"
section.
11) Final check: Before leaving this unit with the
customer, the installer must ensure that the
appliance is fi ring correctly. This includes:
a) Clocking the appliance to ensure the
correct fi ring rate.
b) Adjusting the primary air, if required,
to ensure that the fl ame does not car-
bon.
c) Ensuring that the appliance is fl ueing
correctly. Refer to "Test for Flue Spillage"
section.
Regency IG35 Gas Inbuilt Fireplace
9) Installer must mechanically attach the supplied label to the inside of the fi rebox of the fi replace into which the gas fi replace insert
is installed.
"WARNING: This fi replace has been converted
for use with a gas fi replace insert only and
cannot be used for burning wood or solid fuels
unless all original parts have been replaced,
and the fi replace re-approved by the authority
having jurisdiction."
5
Page 6
INSTALLATION
MINIMUM FIREPLACE
DIMENSIONS
The minimum fi replace dimensions for the
Regency gas space heater are shown in the
following diagrams:
MINIMUM
CLEARANCES TO
COMBUSTIBLES
The minimum fi replace clearances for the
Regency gas space heater are shown in the
following diagrams:
From Unit:
Sides A 250 mm
Ceiling B 1220 mm
Mantel C see Mantel
Clearances
From Surround (660 mm x 1016 mm):
Sides D 96 mm
Ceiling E 1066 mm
Max. Mantle Depth G 305 mm
Hearth Height H 0 mm
Hearth Depth I 300 mm*
Hearth Width J 1100 mm
Min. Alcove Width K 1262 mm
Max. Alcove Depth L 915 mm
* NOTE: No hearth required with screen. Floor
fi nishing material must not be any higher then
the base of the fi replace.
Mantel Clearances
Note: A non-combustible mantel may be
installed at a lower height if the framing is made of metal studs covered
with a non-combustible board.
GAS CONNECTION
Premium Flush Front Framing
When installing the Premium Flush Front, the
walls surrounding the zero clearance kit must
be made of non-combustible material. See
Diagram below.
GAS CONNECTION WARNING:
Only persons licensed to work
with gas piping may make the
necessary gas connections to this
appliance.
1) If the appliance is to be installed into an
existing chimney system or Zero Clearance
Box, thoroughly clean the masonry or factory
built fi replace.
2) The gas connection is 1/2" BSP.
3) Locate the center point where the fl ue will
pass through the chimney above the appliance. Move the appliance into the exact
location where it is to be installed. Ensure
that the Insert is level.
CAUTION: If the glass is removed for servicing, it must be replaced and closed prior to
operating the appliance.
6
Regency IG35 Gas Inbuilt Fireplace
Page 7
INSTALLATION
FLUEING
THE APPLIANCE MUST NOT BE CONNECTED
TO A CHIMNEY FLUE SERVING A SEPARATE
SOLID FUEL BURNING APPLIANCE.
This appliance is designed to attach to a 100
mm diameter twin skin or listed gas fuel type
fl ue liner running the full length of the chimney. A
minimum fl ue height of 1.5 m. is recommended.
The Regency Inbuilt Fireplace incorporates
its own internal draft diverter, so no additional
external draft diverter is required.
Periodically check that the fl ue is unrestricted
and an adequate draft is present when the unit
is in operation.
Before installing fl ue system ensure that the
damper plate is open and secure to prevent the
damper plate from falling down and crushing
the liner.
Install to AS5601-2004,(Australia) NZS 5261
(New Zealand).
Combustion and Ventilation Air
WARNING: This appliance needs
fresh air for safe operation and must
be installed with provisions for adequate combustion and ventilation
air available to the room in which it
is to be operating.
Air for combustion is drawn in through the front
of the unit, therefore, the front of the unit must
be kept clear of any obstructions.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 3.45 kPa (14" w.c.).
The manifold pressure is controlled by a
regulator built into the gas control, and should
be checked at the pressure test point.
Note: To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" (# 3) and/or "OUT" (# 4)
pressure tap(s), turning counterclockwise
with a 1/8" wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" (8mm) ID
hose.
4) Seal and or check the pilot outlet (# 8)
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specifi ed on the safety
label.
6) When fi nished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8"
fl at screwdriver. Screw should be snug,
but do not over tighten.
S.I.T. Valve Description
1) On-Off Solenoid Valve EV1
2) On-Off Solenoid Valve EV2
3) Inlet Pressure Test Point
4) Outlet Pressure Test Point
5) Connection for Pressure Regulator/
Combustion Chamber Compensation
6) Pressure Regulator for Minimum and
Maximum Outlet Pressure
7) Gas Outlet Pressure Electric Modulator
8) Pilot Outlet
9) Main Gas Outlet
10) Side Outlet
Regency IG35 Gas Inbuilt Fireplace
7
Page 8
g
INSTALLATION
System Data
IG35
IG35-NG: For 0 to 610 meters altitude
IG35-LPG: For 0 to 610 meters altitude
IG35-ULPG: For 0 to 610 meters altitude
Burner Inlet Orifi ce Sizes:
NG LPG ULPG
Burner #33 #51 #53
Electrical: 240 V. 50Hz.
Circulation: High/Off/LO speed fan,
150/89 CFM.
Log Set: Ceramic fi ber, 7 per set.
TEST FOR FLUE
SPILLAGE
A " spillage" test must be made before the
installed unit is left with the customer. Follow
the procedure below:
1) Start all exhaust fans in the home and then
close all external doors and windows in the
house.
2) Light the unit and set controls to maximum.
Turn fan off.
3) After fi ve minutes, test that there is a “pull” on
the fl ue by placing a smoke match, cigarette
or similar device which gives off smoke, in
both sides of the unit. See diagram 1.
OPTIONAL
BRICK PANEL
1) Unwrap the brick panels from the protective
wrapping.
2) Remove the glass front and log set if already
installed.
3) Place the rear brick panel fl at against the
back of the unit, by carefully slipping it between the back wall of the fi rebox and the
rear log tray.
4) Remove the screw on the inside top left and
right side of the fi rebox.
Left Side
of Firebox
Rem ove
screw
5) Slide the left and right side brick panels in
place and secure using the brick retaining
clips provided and the screws removed in
step 4 as shown in the diagram below.
Aeration Setting
NG 15mm fully open
LPG 15mm fully open
ULPG 15mm fully open
AERATION SETTINGS
The burner aeration is factory set but may need
adjusting due to either the local gas supply, air
supply or altitude. This adjustment is performed
by the installer. (Close the aeration for a more
yellow fl ame, or open it to make the fl ame
bluer).
NG: 15mm fully open
LPG: 15mm fully open
ULPG: 15mm fully open
Note: Any damage due to carboning result-
ing from improperly setting the aeration controls is NOT covered under
warranty.
Diagram 1
The smoke should be drawn into the unit. If the
smoke is still not drawn into the spill tube, turn
the unit off and check for the cause of the lack
of draft. If necessary, rectify.
For wind turbulent sites, a wind cap may remedy the problem. These caps are not included
with the standard fl ue kit and will need to be
purchased separately.
Back
brick
panel
Screw
Brick
Retainin
Clip
Side
brick
panel
8
Regency IG35 Gas Inbuilt Fireplace
Page 9
INSTALLATION
Conversion Kit #486-968 for NG to LPG Model
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!
Conversion Kit 486-968 Contains:
Qty. Part # Description
1 904-645 Burner Orifi ce #51
1 908-528 Red "LPG" label
1 918-590 Label "Converted to LPG"
1 918-541 Instruction Sheet
1) Shut off the gas supply and unplug the power
cord.
2) Remove the front door.
3) Remove logs.
4) Remove the rear log tray by removing the 2
screws. (Log tray must be rotated to clear
the burner.)
7) Remove burner orifi ce with a 1/2" wrench
and discard. Use a wrench to hold on to the
elbow behind the orifi ce.
8) Reinstall new burner orifi ce LPG stamped
#51 and tighten.
9) Stick the conversion label "This unit has
been converted to LPG" over top of the serial
number decal.
10) Replace the yellow "NG" label with the red
"LPG" label.
11) Carefully pull out the control box.
NOTE: The control box is held in place with
velcro.
12) Remove the heat shield from the control
box by removing the 2 screws.
13) Remove the control box cover by undoing the
3 screws. Maneuver through antenna.
Antenna
Control Box
Cover
14) Remove the jumper using a plier.
Jumper Location
5) Remove the grate.
6) Remove the burner and adjust the aeration
setting to 15 mm fully open.
Jumper
Heat Shield
15) Reverse steps 13, 12, 11, 6, 5, 4, 3 & 2.
Regency IG35 Gas Inbuilt Fireplace
9
Page 10
INSTALLATION
16) Turn on gas supply and plug in power
cord.
17) Adjusting the Outlet Pressure
All the adjustments must be carried out
in the following order:
Remove the modulator plastic cap (A) using
needle nose pliers.
Maximum pressure: Turn the unit ON to
its highest input rating. Screw in the nut (B)
to increase the outlet pressure and screw it
out to decrease it. Use a 10 mm wrench.
NOTE: The outlet pressure must be set to
maximum 2.61 kPa.
Minimum pressure: Remove one of the
cables connected to the electric modulator.
While holding the nut (B) with a wrench,
screw in the screw (C) to increase the
pressure and screw it out to decrease it.
Use a screwdriver 6 x 1 blade.
NOTE: The outlet pressure must be set to
minimum 0.75 kPa.
Cable
Electric
Modulator
After carrying out all adjustments, block
the setting screws with paint, taking care
not to obstruct the breather orifi ce of the
pressure.
Put back the modulator plastic cap.
WARNING: To ensure the correct opera-
tion of the modulator it is necessary that
the plastic cap (A) is returned to its original
location.
A
B
18) At the end of all setting and adjustment
operations, check electrical installation and
gas leaks.
19) Check operation of fl ame control.
C
20) Check for proper fl ame appearance and
glow on logs.
Installer Notice:
These instructions must be left
with the appliance.
10
Regency IG35 Gas Inbuilt Fireplace
Page 11
INSTALLATION
Conversion Kit #486-967 for NG to ULPG
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!
Conversion Kit 486-967 Contains:
Qty. Part # Description
1 904-345 Burner Orifi ce #53
1 918-273 Red "ULPG" label
1 918-272 Label "Converted to ULPG"
1 918-542 Instruction Sheet
1) Shut off the gas supply and unplug the power
cord.
2) Remove the front door.
3) Remove logs.
4) Remove the rear log tray by removing the 2
screws. (Log tray must be rotated to clear
the burner.)
7) Remove burner orifi ce with a 1/2" wrench
and discard. Use a wrench to hold on to the
elbow behind the orifi ce.
8) Reinstall new burner orifi ce ULPG stamped
#53 and tighten.
9) Stick the conversion label "This unit has
been converted to ULPG" over top of the
serial number decal.
10) Replace the yellow "NG" label with the red
"ULPG" label.
11) Carefully pull out the control box.
NOTE: The control box is held in place with
velcro.
12) Remove the heat shield from the control
box by removing the 2 screws.
13) Remove the control box cover by undoing the
3 screws. Maneuver through antenna.
Antenna
Control Box
Cover
14) Remove the jumper using a plier.
Jumper Location
5) Remove the grate.
6) Remove the burner and adjust the aeration
setting to 15 mm fully open.
Jumper
Heat Shield
15) Reverse steps 13, 12, 11, 6, 5, 4, 3 & 2.
Regency IG35 Gas Inbuilt Fireplace
11
Page 12
INSTALLATION
16) Turn on gas supply and plug in power
cord.
17) Adjusting the Outlet Pressure
All the adjustments must be carried out
in the following order:
Remove the modulator plastic cap (A) using
needle nose pliers.
Maximum pressure: Turn the unit ON to
its highest input rating. Screw in the nut (B)
to increase the outlet pressure and screw it
out to decrease it. Use a 10 mm wrench.
NOTE: The outlet pressure must be set to
maximum 2.61 kPa.
Minimum pressure: Remove one of the
cables connected to the electric modulator.
While holding the nut (B) with a wrench,
screw in the screw (C) to increase the
pressure and screw it out to decrease it.
Use a screwdriver 6 x 1 blade.
NOTE: The outlet pressure must be set to
minimum 0.75 kPa.
Cable
Electric
Modulator
After carrying out all adjustments, block
the setting screws with paint, taking care
not to obstruct the breather orifi ce of the
pressure.
Put back the modulator plastic cap.
WARNING: To ensure the correct opera-
tion of the modulator it is necessary that
the plastic cap (A) is returned to its original
location.
A
B
18) At the end of all setting and adjustment
operations, check electrical installation and
gas leaks.
19) Check operation of fl ame control.
C
20) Check for proper fl ame appearance and
glow on logs.
Installer Notice:
These instructions must be left
with the appliance.
12
Regency IG35 Gas Inbuilt Fireplace
Page 13
INSTALLATION
LOG SET
INSTALLATION
Read the instructions below carefully and
refer to the diagrams. If logs are broken
do not use the unit until they are replaced.
Log kit #730-935 contains the following:
a) 02-65 Rear Log
b) 02-56 Middle Left Log
c) 02-44 Front Left Log
d) 02-46 Left Top Log
e) 02-45 Front Right Log
f) 02-47 Center Log
g) 02-48 Middle Right Log
h) Embers 902-151
i) Lava 902-154
Log kit #486-930 contains the following:
a) 02-50 Side Log
b) 02-52 Side Log
c) Embers 902-151
d) Lava 902-154
The "02" refer numbers (i.e. 02-65) are
molded into the rear of each log.
3) Place Rear Log A)02-65 on the two pins on
the rear log support.
A)02-65
4) Place the Middle Left Log B)02-56 on the
two pins from the rear left side.
B)02-56
7) Place the Left Top Log D)02-46 on the pin
on Log B)02-56 and on top of the cutout
on Log A)02-65.
A)02-65
D)02-46
C)02-44
8) Place Front Right Log E)02-45 on the two
pins as shown.
B)02-56
E)02-45
Installation of Kit 730-935:
1) Carefully remove the logs from the box and
unwrap them. The logs are fragile, handle
with care - do not force into position.
2) Sprinkle the embers on the front, left and
right sides of the fi rebox base.
5) Place lava rock in front of middle left log as
shown in the picture.
9) Place the lava rock in the area between
the left and right logs, leaving a space in
the middle for log (F) 02-47.
Ensure that the lava rocks are not placed
directly over the burner ports.
6) Place Front Left Log C)02-44 onto the 2
front pins as shown.
Lava Rock
C)02-44
Embers
Regency IG35 Gas Inbuilt Fireplace
Embers
13
Page 14
INSTALLATION
10) Place the notch in Center Log F)02-47 over
Log E)02-45 and across the cutout on Log
A)02-65.
F)02-47
CutoutNotch
11) Position notch in Front Right Log G)02-48
on Log F)02-47 and push the bottom right
edge against the bracket on the burner
tray.
A)02-65
G)02-48
A)02-65
E)02-45
Installation of Kit 486-930:
1) Carefully remove the logs from the box and
unwrap them. The logs are fragile, handle
with care - do not force into position.
2) Sprinkle the embers on the front, left and
right sides of the fi rebox base.
3) Place Side Log 02-50 on the right side of
the grate on the fi rebox base.
Position log as desired ensuring the log
DOES NOT interfere with the fl ame. Possible
positioning shown in diagrams below.
02-50
4) Place Side Log 02-52 on the left side of the
grate on the fi rebox base.
Position log as desired ensuring the log
DOES NOT interfere with fl ame. Possible
positioning shown in diagrams below.
02-52
Example 1
E)02-45
F)02-47
Notch
G)02-48
E)02-45
Side View
Bracket
The bottom right edge of Log G)02-48 must
sit snugly against the bracket
12) Test fi re to ensure proper light off. Ensure
fl ame fl ows smoothly from one end of the
burner to the other. If there is any fl ame
hesitation, check the area for any blockage
of the burner port.
Example 1
Example 2
Example 3
02-52
Example 2
02-50
02-52
Example 3
02-50
5) Test fi re to ensure proper light off. Ensure
fl ame fl ows smoothly from one end of the
burner to the other. If there is any fl ame
hesitation, check the area for any blockage
of the burner port.
14
Regency IG35 Gas Inbuilt Fireplace
Page 15
INSTALLATION
FACEPLATE,
TRIM & LOUVER
INSTALLATION
1) Lay the faceplate panels fl at, face down on
something soft so they don't scratch.
2) Take the top faceplate and align the holes
in it with the holes in the side panels. Using the screws provided, attach from the
top of the panel (the holes in the top panel
are slightly larger than the holes in the side
panel to facilitate easier installation).
4) Connect the fan harness to the fan switch.
5) Connect the valve harness to the valve on/off
switch.
6) Tuck the wires into the faceplate to keep
them away from the inbuilt fi replace using
the clip provided. Attach the clip to the rear
of the faceplate to ensure that the wires do
not touch the side of the unit.
7) The power cord should be run behind the
faceplate panel.
10) Push the Regency logo plate into the two
holes in the bottom left corner of the faceplate.
11) Place the 2 hinges for the bottom louver
in position and secure using 4 screws per
hinge.
12) Place the bottom louver in position and
secure it with 6 screws.
Diagram 1
Hint: Don't tighten the trim to the bottom
of the faceplate side panels with the screws
provided. See diagram 1.
3) Using the connectors provided, join the left
side trim to the top trim. Connect the right
side trim to the top trim.
8) Place the trim on the assembled faceplate
panels and secure it with the side screws.
9) Attach the faceplate panels* to the inbuilt
fi replace body using 4 black screws.
13) Install the safety screen by inserting the 4
screen brackets into the 4 slots.
Screen
Bracket
Slots
14) Install the top louver by sliding the 2 bracket
clips into the brackets located on top of the
unit.
Diagram 2
Rear View: Trim Assembly
Regency IG35 Gas Inbuilt Fireplace
Side
Screws
15
Page 16
INSTALLATION
PREMIUM FLUSH FRONT INSTALLATION
1) Unplug the power source.
2) Remove the glass door.
ECS Manual Control Switch Installation:
3) Remove the heat shield from the left side of the faceplate by undoing
the 2 screws. See diagram 1.
Left Side
Heat Shield
Diagram 1
4) Unplug the CAT5 cable from the ECS manual switch included with
the unit. See diagram 2.
Washer
Phenolic Spacer
Split Lock Washer
Nut
Diagram 3
ECS Manual Switch
Diagram 4
7) Run the thermodisc wires thru the hole in the heat shield.
Then place the grommet over the sleeve and tuck into the hole in the
and nuts securing the manual control switch to separate the manual
control switch keypad. See diagram 2.
Manual Control
Switch Keypad
Control Switch
Diagram 2
6) Place the ECS manual control switch key pad on the outside of the
opening in the faceplate and the control switch to the inside of the
faceplate.
Align the holes and secure in place using the 2 bolts, washers,
phenolic spacers, split lock washers and nuts. See diagram 3 for
sequence. Diagram 4 shows ECS manual control switch mounted
on faceplate.
Bolts
CAT5 Cable
Receptacle
Grommet
Diagram 5
16
Regency IG35 Gas Inbuilt Fireplace
Page 17
INSTALLATION
8) Secure with 2 Phillips Head Screws as shown.
See Diagram 6 inset
Diagram 6
12) Partially mount the heat shield to the left side of the faceplace and
connect the CAT5 cable to the ECS manual control switch. See
diagram 9.
Faceplate
Diagram 9
Diagram 7
9) Bring faceplate close to unit.
10) Run thermodisc wires from top of heat defl ector through
left side of faceplate. See Diagram 7.
11) Place the cable ties thru the cable tie holders in the heat shield loosely
to secure loose wires.
Run the CAT5 cable from the unit thru the cable ties on the heat
shield and tighten cable ties. Ensure not to overtighten. Cut excess
cable tie. See diagram 8.
CAT5 Cable
13) Secure the heat shield to the faceplate using 2 screws. See diagram
10. NOTE: Screws are secured from the front.
Diagram 10
Diagram 8
Regency IG35 Gas Inbuilt Fireplace
17
Page 18
INSTALLATION
Thermodisc Installation:
14) Install the heat defl ector to the unit by fi tting the tabs into the tab
brackets located on the underside of the fi rebox. See diagram 11.
Diagram 12 shows defl ector completely installed.
Tab into Tab Bracket
16) Secure the faceplate in place
using 2 screws on the left and
right side. Diagram 14 shows
mounting on right side.
Diagram 11
Diagram 12
Heat Defl ector
Faceplate Installation:
15) Completely mount the faceplate to the unit. .See diagram 13.
Diagram 14
Wiring:
17) Remove the wire harness from the valve. See diagram 15.
Wire Harness
Diagram 15
18) Undo the wire clip to the right side of the valve. See diagram 16.
Valve
18
Diagram 16
Diagram 13
Regency IG35 Gas Inbuilt Fireplace
Page 19
INSTALLATION
19) Carefully lift off the ignition module from the velcro and slightly bring
forward. Remove the wire harness connected to the ignition module
as shown in diagram 17.
Wire Harness
Removed
Diagram 17
20) Discard the complete wire harness that was connected to the valve
and ignition module.
21) Take the wire harness included with the kit and connect one end of
the wire harness to the ignition module (in place of the one removed),
see diagram 18 .
Place the ignition module back on the velcro at the base of the fi rebox.
Ensure to run the loose wires from the wire harness in behind the
bracket on the left side of the ignition module. See diagram 19.
Ignition
Module
22) Connect the other end of the new wire harness to the valve, in place
of the one removed in step 16. See diagram 20.
Diagram 20
23) Disconnect the red split wires from the wire harness as shown in
diagram 21.
Diagram 18
Diagram 19
Bracket
Diagram 21
24) Feed the remaining thermodisc wires thru the opening on the bottom
of the left side of the fi rebox and run them in behind the bracket to
the left of the valve. See diagram 22.
Connect the 2 wires from the thermodisc to the appropriate wire on
the harness; female to male, male to female.
Bracket
Diagram 22
Regency IG35 Gas Inbuilt Fireplace
19
Page 20
INSTALLATION
25) Secure all loose wires in the wire clip to the right side of the valve.
See diagram 23.
Diagram 23
Louver Installation:
26) Secure the hinge bracket and hinge to the outside of the fi rebox fl ange
on the left and right side as shown using 2 screws on each side. See
diagram 24.
Screen Door Installation:
28) Re-install the glass door.
29) Install the screen by placing the hooks (2 on each side) into the slots
on the inside of the faceplate. Once in place, push down on the screen
to secure. See diagram 26.
Hinge Bracket
Diagram 24
27) Align the bottom louver hinge tab screw holes with hinge screw holes
and secure using 3 screws on each side. See diagram 25.
Bottom Louver
Diagram 25
Hinge
Diagram 26
30) Close the bottom louver.
31) Plug in the power source.
NOTE:
The fan should run at least on low speed to prevent the unit
from overheating which will cause automatic shutdown via the
thermodisc safety switch.
20
Regency IG35 Gas Inbuilt Fireplace
Page 21
INSTALLATION
REMOTE CONTROL
Use the Regency Remote Control Kit approved
for this unit. Use of other systems may void
your warranty.
The remote control kit comes with a hand held
transmitter and a wall mounting plate.
1) Choose a convenient location to mount
the hand held transmitter, protection from
extreme heat is very important.
By usiing the wall mounting plate to house the
transmitter, the remote can also be used as a
wall thermostat.
Caution: Ensure that the wires do not
touch any hot surfaces and are away
from sharp edges.
FINAL CHECK
Before leaving this unit with the customer, the
installer must ensure that the appliance is fi ring
correctly. This includes:
1) Clocking the appliance to ensure the correct fi ring rate (rate noted on label) at 15
minutes.
2) If required, adjusting the primary air to
ensure that the fl ame does not carbon.
First allow the unit to burn for 15 min. to
stabilize.
3) Check for proper draft.
CAUTION
Any alteration to the product that
causes sooting or carboning that
results in damage to the exterior
facia is not the responsibility of the
WIRING
This unit is polarity sensitive and will
not operate if polarity is incorrect.
STANDARD WIRING
Regency IG35 Gas Inbuilt Fireplace
21
Page 22
INSTALLATION
WIRING WITH PREMIUM FLUSH FRONT OPTION
WARNING:
Electrical Grounding Instructions
This appliance is equipped with a three
pronged (grounding) plug for your
protection against shock hazard and
should be plugged directly into a properly grounded three-prong receptacle.
Do not cut or remove the grounding
prong from this plug.
CAUTION:
Label all wires prior to disconnection
when servicing controls.
Wiring errors can cause improper
and dangerous operation.
22
Regency IG35 Gas Inbuilt Fireplace
Page 23
OPERATING INSTRUCTIONS
OPERATING
INSTRUCTIONS
Before operating this appliance, proceed through
the following check list.
1) Read and understand these Instructions
before operating this appliance.
2) Check to see that all wiring is correct and
enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass door is in place. Never
operate the appliance with the door glass
removed.
5) Verify that all fl ueing and the cap is unob-
structed.
6) Verify log placement.
7) The unit should never be turned off and on
again without a minimum of a 60 second
wait.
8) When lighting the appliance, the inside of
the glass may fog up. This will burn off after
a few minutes of operation.
LIGHTING
INSTRUCTIONS
1) Plug the power cord into a power outlet.
2) Press and release the ON/OFF switch once
to start the unit. The LED will be lit.
3) After approximately 8 seconds the spark
ignition system will spark for 8 seconds to
light the main burner.
4) If the main burner does not light, repeat step
2 to restart the unit.
FIRST FIRE
The FIRST FIRE in your heater is part of the
paint curing process. To ensure that the paint
is properly cured, it is recommended that you
burn your fi replace for at least four (4) hours the fi rst time you use it with the fan on.
When fi rst operated, the unit will release an
odour caused by the curing of the paint and the
burning off of any oils remaining from manufacturing. Smoke detectors in the house may go off
at this time. Open a few windows to ventilate
the room for a couple of hours. The glass may
require cleaning.
NOTE: The main burner will always start on
"HIGH" and resume it's last setting after
20 seconds of operation.
NOTE: When the glass is cold and the appliance
is lit, it may cause condensation and fog
the glass. This condensation is normal
and will disappear in a few minutes as
the glass heats up.
DO NOT ATTEMPT TO CLEAN THE
GLASS WHILE IT IS STILL HOT!
DO NOT BURN THE APPLIANCE WITHOUT THE GLASS FRONT IN PLACE.
FAN OPERATION
Set the fan speed on the control panel at the top
rear of the unit to adjust to the desired speed.
Pressing and releasing the plus (+) FAN button
will change the fan speed as follows:
OFF -> LOW -> MEDIUM -> HIGH -> OFF,
etc.
Pressing and releasing the minus (-) FAN button
will be the reverse of the above.
ADJUSTING FLAME
HEIGHT
There are six fl ame settings that can be adjusted
by pressing and releasing the plus (+) and minus
(-) FLAME button.
The FLAME setting button is located on the
control panel at the top rear of the unit.
SUMMARY OF
CONTROLS
On/Off Button
If the unit is switched off, pressing and releasing
this button once will switch the unit on. The unit
will resume its last settings.
If the unit is switched on, pressing and releasing
this button once will switch the unit off.
Flame:
Increase - If the unit is switched on, pressing
and releasing the fl ame plus (+) button once will
increase the fl ame height to the next available
high setting.
Decrease - If the unit is switched on, pressing
and releasing the fl ame minus (-) button once
will decrease the fl ame height to the next avail-
able low setting.
Fan:
Increase - If the unit is switched on, pressing
and releasing the fan plus (+) button once will
increase the fan speed to the next available
high setting.
Decrease - If the unit is switched on, pressing
and releasing the fan minus (-) button once will
decrease the fan speed to the next available
low setting.
SHUTDOWN
INSTRUCTIONS
1) Press the ON/OFF switch once.
2) The LED will fl ash.
3) Turn off all electric power to the appliance
if service is to be performed.
Regency IG35 Gas Inbuilt Fireplace
23
Page 24
OPERATING INSTRUCTIONS
COPY OF LIGHTING INSTRUCTION PLATE
FOR YOUR SAFETY READ BEFORE LIGHTING
This appliance must be installed in accordance with local codes, if any; if not,
follow the current CAN1-B149/ANSI Z 223.1 (Australia: AS5601-2004, New Zealand: NZS 5261)
WARNING: If you do not follow these instructions exactly, a fi re or explosion may result
causing property damage, personal injury or loss of life. Improper installation, adjustment,
alteration, service or maintenance can cause injury or property damage. Refer to the
owner’s information manual provided with this appliance. For assistance or additional
information consult a qualifi ed installer, service agency or gas supplier.
A) BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the fl oor because some
gas is heavier than air and will settle on the fl oor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electric switch, do not use any
phone in your building
- Immediately call your gas supplier from a neighbors
phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the
fi re department.
CAUTION: Hot while in operation. Do not touch. Severe Burns may result. Due to high
surface temperatures keep children, clothing and furniture, gasoline and other liquids
having fammable vapors away. Keep burner and control compartment clean. See installation
and operating instructions accompanying appliance.
LIGHTING INSTRUCTIONS
STOP! Read the safety information above on this label.
1) Plug the power cord into a power outlet.
2) Press and release the ON/OFF switch once to start
the unit. The LED will be lit.
TO TURN OFF GAS APPLIANCE
1) Press the ON/OFF switch once.
2) The LED will fl ash.
You may shut off the pilot during prolonged non use periods to conserve fuel.
DO NOT REMOVE THIS INSTRUCTION PLATE
B) Do not use this appliance if any part has been under water.
Immediately call a qualifi ed service technician to inspect
the appliance and to replace any part of the control system
and any gas control which has been under water.
This appliance needs fresh air for safe operation and
must be installed so there are provisions for adequate
combustion and ventilation air.
3) After approximately 8 seconds the spark ignition
system will spark for 8 seconds to light the main
burner.
4) If the main burner does not light, repeat step 2 to
restart.
3) Turn off all electric power to the unit if service is
to be performed.
918-247b
NORMAL OPERATING
SOUNDS OF
GAS APPLIANCES
It is possible that you will hear some sounds
from your gas appliance. This is perfectly normal
due to the fact that there are various gauges
and types of steel used within your appliance.
Listed below are some examples. All are normal operating sounds and should not be considered
as defects in your appliance.
Blower:
Regency gas appliances use high tech blowers
to push heated air farther into the room. It is not
unusual for the fan to make a "whirring" sound
when ON. This sound will increase or decrease
in volume depending on the speed setting of
your fan speed control.
Burner Tray:
The burner tray is positioned directly under the
burner tube(s) and logs and is made of a different gauge material from the rest of the fi rebox
and body. Therefore, the varying thicknesses of
steel will expand and contract at slightly different
rates which can cause "ticking" and "cracking"
sounds. You should also be aware that as there
are temperature changes within the unit these
sounds will likely re-occur. Again, this is normal
for steel fi reboxes.
Gas Control Valve:
As the gas control valve turns ON and OFF, a
dull clicking sound may be audible, this is normal
operation of a gas regulator or valve.
Unit Body/Firebox:
Different types and thicknesses of steel will
expand and contract at different rates resulting
in some "cracking" and "ticking" sounds will be
heard throughout the cycling process.
24
WARNING:
DO NOT SPRAY AEROSOLS IN THE VICINITY OF
THIS APPLIANCE WHILE IN OPERATION.
Regency IG35 Gas Inbuilt Fireplace
Page 25
MAINTENANCE
MAINTENANCE
INSTRUCTIONS
Any maintenance required accessing the
glass door of the unit must be performed
by an authorized service person.
1) Always unplug the power cord before
cleaning. For relighting, refer to lighting
instructions. Keep the burner and control
compartment clean by brushing and vacuuming at least once a year. When cleaning
the logs, use a soft clean brush as the logs
are fragile and easily damaged.
2) Clean glass (never when unit is hot), appliance, louvres, and door with a damp cloth.
Never use an abrasive cleaner. The gold
louvres (and optional gold door) may be
scratched if abrasives are used to clean
them.
The heater is fi nished in a heat resistant
paint and should only be refi nished with
heat resistant paint (not with wall paint).
Regency uses StoveBright Paint - Metallic
Black #6309.
3) Make a periodic check of burner for proper
position and condition. Visually check the
fl ame of the burner periodically, making sure
the fl ames are steady; not lifting or fl oating.
If there is a problem, call an authorized
service person.
4) The appliance and fl ueing system must be
inspected before use, and at least annually, by an authorized fi eld service person,
to ensure that the fl ow of combustion and
ventilation air is not obstructed.
During the annual service call, the burners
should be removed from the burner tray
and cleaned. Replace the embers - do not
block the burner ports.
CAUTION: ANY SAFETY SCREEN
OR GUARD REMOVED FOR SERVICING AN APPLIANCE MUST BE
REPLACED PRIOR TO OPERATING THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT
BE PLACED ON OR NEAR THE
APPLIANCE.
DO NOT USE THIS APPLIANCE
IF ANY PART HAS BEEN UNDER
WATER. IMMEDIATELY CALL AN
AUTHORIZED SERVICE TECHNI
CIAN TO INSPECT THE APPLIANCE AND TO REPLACE ANY
PART OF CONTROL SYSTEM AND
ANY GAS CONTROL WHICH HAS
BEEN UNDER WATER.
6) Verify proper operation after servicing.
LOG REPLACEMENT
The unit should never be used with broken logs.
Unplug the power cord and allow the unit to cool
before opening door to carefully remove the logs.
If for any reason a log should need replacement,
you must use the proper replacement log. The
position of these logs must be as shown in the
diagram under Log Installation.
Note: Improper positioning of logs may
create carbon build-up and will alter
the unit’s performance which is not
covered under warranty.
DOOR GLASS
REPLACEMENT
Your Regency stove is supplied with high temperature, 5 mm Neoceram ceramic glass that
will withstand the highest heat that your unit will
produce. In the event that you break your glass
by impact, purchase your replacement from an
authorised Regency dealer only, and follow our
step-by-step instructions for replacement.
WARNING: do not operate appliance with the glass front removed,
cracked or broken. Replacement
of the glass should be done by
a licensed or authorised service
person.
Flush Glass Replacement
Slide old glass out of the side frames and
replace with new glass.
GLASS GASKET
If the glass gasket requires replacement use
7/8" fl at glass gasket (Part # 936-243).
5) Keep the area near the appliance clear and
free from combustible materials, gasoline
and other fl ammable vapours and liquids.
WARNING: CHILDREN AND
ADULTS SHOULD BE ALERTED
TO THE HAZARDS OF HIGH
SURFACE TEMPERATURE AND
SHOULD STAY AWAY TO AVOID
BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN
THEY ARE IN THE SAME ROOM
AS THE APPLIANCE.
Regency IG35 Gas Inbuilt Fireplace
25
Page 26
MAINTENANCE
FAN MAINTENANCE
To Remove Fan:
1) Turn the unit off and allow it to cool to room temperature,
2) Unplug or disconnect power source to stove.
3) Open the bottom louvre.
4) Remove the ECS harness from the back clip.
Back Clip
5) Remove the 2 screws that secure the fan in place.
6) Pull out the ECS box.NOTE: The ECS box is held in place with velcro.
7) Carefully slide the fan to the front, rotate it 45 degrees and slide it out
simultaneously with the ECS box.
Resistor Con-
nectors
8) Disconnect all the connectors from the fan and resistor.
Fan
Connectors
Fan Ground
Cable
9) Remove the fan ground cable.
10) Pull out the fan tray.
11) Remove the 3 screws from the back of the fan tray to remove the
fan.
12) Reverse the above steps to install the new fan.
26
Regency IG35 Gas Inbuilt Fireplace
Page 27
MAINTENANCE
REMOVING
VALVE TRAY
1) Unplug or disconnect the power source to
the stove.
2) Shut off the gas supply and remove the gas
connection from the valve.
3) Remove the top louvre.
4) Remove the safety screen.
5) Remove the screen door.
6) Remove the logs.
7) Remove the brick panels.
8) Remove the rear log tray.
9) Remove the grate.
10) Remove the burner.
11) Remove the glass door holder by removing 4
screws on the front and 2 on the bottom.
13) Remove the valve cover plate by removing
the 3 screws.
Valve Cover
14) Remove all the wire connectors from the
valve and spark ignitor.
16) Remove the valve tray assembly.
17) To replace the valve tray assembly, simply
reverse the above steps.
Glass Door
Holder
12) Remove the fi rebox base plate by removing
11 screws which hold it in place.
15) Remove the 2 screws which secure the
valve tray. Use a long Philips screwdriver
for easy access.
486-574/P Valve Assembly - NG
486-576/P Valve Assembly - LPG
52) 910-080 SIGMA Valve 845
53) 910-190 Piezo Ignitor and nut
54) * Valve Heat Shield
56) * Pilot Bracket
60) 486-048 Grate Assembly
62) 486-535 Burner Assembly - NG/LPG
63) 910-034 Pilot Assy (NG) - 3 fl ame convertible top910-035 Pilot Assy (LPG) - 3 fl ame convertible top
69) 730-935 Log Set
486-930 Log/Ember Package
86) 910-386 Thermocouple
87) 910-341 Thermopile
92) * Rear Log
93) * Left Top Log
94) * Center Log
95) * Middle Right Log
96) * Middle Left Log
97) * Front Right Log
98) * Front Left Log
*Not available as a replacement part.
Regency IG35 Gas Inbuilt Fireplace
29
Page 30
PARTS LIST
FACEPLATE ASSEMBLY
Part # Description Part # Description
87) 910-140 Fan HI/OFF/LOW Switch
88) 910-246 Burner ON/OFF Switch
486-918 Faceplate & Trim Complete - Regular
91) * Faceplate Side Right - Regular
92) * Faceplate Top - Regular
93) * Faceplate Side Left - Regular
Trims Packaged - Regular
94) * Faceplate Trim Right - Regular
95) * Faceplate Trim Top - Regular
96) * Faceplate Trim Left Assy - Regular
176) 486-926 Hearth Trim 2" - Regular
180) 486-928 Hearth Trim 4" - Regular
181) 486-929 Flush Screen Door
*Not available as a replacement part.
PREMIUM FLUSH FRONT ASSEMBLY
Part # Description
486-916 Premium Flush Front - Black
486-949 Wiring
486-932 Flue Free Kit
910-987 Thermodisc
200) * Screen
201) * Heat Defl ector
202) * Heat Shield
*Not available as a replacement part.
30
Regency IG35 Gas Inbuilt Fireplace
Page 31
WARRANTY
Regency® fi replace products are designed with reliability and simplicity in
mind. In addition, our internal Quality Assurance Team carefully inspects
each unit thoroughly before it leaves our door. Regency
is pleased to extend this limited lifetime warranty to the original purchaser
of a Regency® Product.
The Warranty: Lifetime
Covered under the agreement are the following components:
Combustion chamber, heat exchanger, burner tubes, logs, embers,
glass (thermal breakage) and all gold plating (against defective manufacture).
The above will be covered for parts and labour for the fi rst fi ve years
and parts only thereafter.
Electrical components such as blowers, switches, wiring, thermodiscs,
remote control, thermopiles, thermocouples and gas valves are covered
for one year from the date of purchase.
Conditions:
All installations must be performed by an authorised gas fi tter and installed
according to all applicable local and national codes. Also, all service
work must be carried out by an authorised gas service person. It is the
responsibility of the installer to ensure that the appliance is fi ring as per
rating plate. Any part or parts of this unit which in our judgement show
evidence of such defect will be repaired or replaced at Regency®'s option,
through an accredited distributor or agent provided that the defective
part be returned to the distributor or agent Transportation Prepaid, if
requested. In areas where there is not an approved service agent or the
closest approved service agent is situated more than twenty-fi ve (25)
kilometres from the installation, Australian Heating Distributors are not
obliged to arrange warranty repairs and travel and/or additional labour
charges will apply.
®
Industries Ltd.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door
or glass gasketing or trim. It does not cover installation and operational
related problems such as over-fi ring, downdrafts or spillage caused by
environmental conditions, nearby trees, buildings, hilltops, mountains,
inadequate fl ueing or ventilation, excessive offsets, negative air pres-
sures caused by insuffi cient make up air, mechanical systems such as
furnaces, fans, clothes dryers etc.
The warranty does not extend to any part or parts which show evidence
of misuse or abuse, neglect, accident or lack of maintenance.
Products made by other manufacturers and used in conjunction with the
operation of this appliance without authorization from Regency
nullify your warranty on this product.
Regency® Industries Ltd., shall in no event be liable for any special,
indirect consequential damages of any nature whatsoever which are in
excess of the original purchase price of the product. Any alteration to
the unit which causes sooting or carboning that results in damage to the
exterior facia is not the responsibility of Regency® Industries Ltd.
General:
It is essential that all submitted claims provide all of the necessary
information including purchase date, serial #, type of unit and part or
parts requested.
®
, may
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.