Regency L965E-NG, HZ965E-LP, HZ965E-NG, L965E-LP, Liberty L965E Owners & Installation Manual

...
Page 1
Regency L965E / HZ965E
Gas Fireplace
Owners &
Installation Manual
Liberty L965E
Horizon HZ965E
MODELS: L965E-NG L965E-LP HZ965E-NG HZ965E-LP
WARNING: If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
www.regency-fi re.com
FOR YOUR SAFETY What to do if you smell gas: Do not try to light any appliance Do not touch any electrical switch:
do not use any phone in your building.
Immediately call your gas supplier
from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
919-088a
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
01/17/14
Page 2
SAFETY
FOR SAFE INSTALLATION AND OPERATION OF YOUR “Regency” HEATER, PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
All Regency gas-fi red appliances must be installed in accordance with their instructions. Carefully read all the instructions in this manual fi rst. Consult the building authority having jurisdiction to determine the need for a permit prior to commencing the installation.
NOTE: Failure to follow these instructions could cause a malfunction of the fi replace, which could result in death, serious bodily injury, and/or property damage.
Failure to follow these instructions may also void your fi re insurance and/or warranty.
GENERAL
Installation and repair should be done by a qualifi ed service person. The appliance should be inspected before the fi rst use and, at least, annually by a qualifi ed service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative the control compartments, burners and circulating air passageways of the appliance be kept clean.
Due to high temperatures, the appliance should be located out of high traffi c areas and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burn or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance, Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fi replace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other fl ammable materials should not be placed on or near the appliance.
To prevent injury, if the pilot or pilot and burners have gone out on their own, open the glass door and wait 5 minutes to air out before attempting to re-light the fi replace.
Always keep the area around these appliances clear of combustible material, gasoline and other fl ammable liquids and vapours.
These appliances should not be used as a drying rack for clothing or for hanging Christmas stockings/ decorations.
Due to the paint curing on the fi replace, a faint odor and slight smoking will likely be noticed when the fi replace is fi rst used. Open a window until the smoking stops.
Always connect this gas fi replace to a vent system and vent to the outside of the building envelope. Never vent to another room or inside the building. Make sure the specifi ed vent pipe is used, properly sized and of adequate height to provide suffi cient draft. Inspect the venting system annually for blockage and signs of deterioration.
WARNING: Failure to position the parts in accordance with the diagrams in this booklet, or failure to use only parts specifi cally approved with this appliance, may result in property damage or personal injury.
WARNING: Do not operate with the glass front removed, cracked or broken. Replacement of the glass should be done by a licensed or qualifi ed service person.
Never use solid fuels such as wood, paper, cardboard, coal, or any fl ammable liquids, etc., in this appliance.
Do not use this heater if any part has been under water. Immediately call a qualifi ed service technician to inspect the heater and to replace any part of the control or gas control systems that have been under water.
Do not abuse the glass by striking it or slamming the door shut.
FOR YOUR SAFETY
• Installation and service must be performed by a qualifi ed installer, service agency or gas supplier.
This installation must conform to local codes or, in the absence of local codes, to the current CAN/CSA-B149.1 Natural Gas and Propane Installation Code (Canada) or National Fuel Gas Code ANSI Z223.1.2 (USA)
• To prevent injury, do not allow anyone who is unfamiliar with the fi replace to operate it.
2
WARNING
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW
CHILDREN TO TOUCH
GLASS.
Regency L965E / HZ965E Gas Fireplace
Page 3
TABLE OF CONTENTS
Dimensions: 5
Rating Label Location: 5
Copy of the safety label 6
INSTALLATION 7
Introduction: 7
Non-Combustible Material Zone: 7
Framing: 8
Internal chase: 8
External chase: 9
Corner framing: 10
Framing for sidewalls and mantel: 11
Typical Framing - Raised Hearth: 12
Installation of Fireplace Facing: 13
Receiver installation 14
Allowable vent confi gurations: 15
Vent Termination Restrictions: 16
Approved Vent Parts: 17
Installation of Flue Restrictor: 18
TV Installation Above Unit: 19
Planning Your Installation: 20
Assembly of the Unit: 20
Securing unit into Position: 20
Installation Of Non-combustible Wall And Hearth Board: 21
Installation Of Venting And Terminations: 21
Horizontal Installation: 22
Vertical Termination Installation: 23
Heat Distribution Kit installation 26
Power vent Kit installation 30
Door Removal and Installation: 38
Gas Hook-Up: 39
Electrical Hook-Up: 39
LP Gas Conversion: 40
Glass Burner Removal/installation: 43
Glass Crystal installation : 44
Optional Spa Stones Installation 44
Refl ective panel installation / Removal: 45
Brick panel installation / Removal: 46
Log Burner / Ember Bed removal / Installation 47
Log set installation: 47
Full screen door / screen Installation 50
Finishing trim: 51
START-UP & OPERATION 52
Normal Sounds During Operation: 52
Remote Control Operations: 52
Technical Data 52
System Description: 52
Wall Mounting The Receiver: 54
Operating Procedure: 54
Smart Thermostat (Transmitter Operation) 55
Remote Flame Control 55
Remote Actuated Accent Lights 55
Key lock 56
Low Battery Power Detection 56
Manual Bypass Of The Remote System 56
Split Valve Operation 56
Air Shutter Adjustment: 57
Diagnostic ash codes: 57
Wiring Harness 58
Air Intake
Lighting Instruction Label: 59
Light Bulb Replacement 60
: 59
CLEANING / ANNUAL SERVICE 60
Cleaning The Glass: 60
Replacing Glass: 60
Burner & Firebox Cleaning: 60
TROUBLESHOOTING 61
Appendix A - Optional Reduced Ceiling Height Installation 63
Warranty 66
Liberty Gas
Inserts Benefi ts
Horizon Gas
Inserts Benefi ts
Regency L965E / HZ965E Gas Fireplace
Liberty L965E Horizon HZ965E
33
Page 4
REQUIREMENTS
DIRECT VENT ONLY: This type is identifi ed by the prefi x DV. This appliance draws all of its air for combustion from outside
the dwelling, through a specially designed vent pipe system. This appliance has been tested and approved for installations from 0 feet to 4500 feet (1372 m) above sea level.
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas Association guidelines
which state: the sea level rated input of Gas Designed Appliances installed at elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level. Refer also to National Fuel Gas Code, ANSI Z223.1/ NFPA 54, local authorities, or codes which have jurisdiction in your area regarding the de-rate guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certifi ed high altitude rating shall
be reduced at the rate of 4% for each additional 1000 feet (305 m). Refer also to CSA-B149.1 Natural Gas and Propane Installation Code, local authorities, or codes which have jurisdiction in your area regarding the de-rate guidelines.
This appliance has been tested by INTERTEK TESTING SERVICES NA LTD. and found to comply with the established VENTED GAS FIREPLACE HEATER standards in CANADA and the USA as follows:
VENTED GAS FIREPLACE HEATER (L965E/HZ965E; NG/LPG)
TESTED TO: ANSI Z21.88a-2009/CSA 2.33a-2009 VENTED GAS FIREPLACE HEATERS
CAN/CGA 2.17-M91 GAS FIRED APPLIANCES FOR HIGH ALTITUDES
CSA P.4.1-02 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY
This Regency L965E/HZ965E Fireplace:
• Has been certifi ed for use with either natural or propane gases. (See rating label.)
• Is not for use with solid fuels.
• Is approved for bedroom or bed sitting room. (IN CANADA: must be installed with a listed wall thermostat. IN USA: see current ANSI Z223.1 for installation instructions.)
• Must be installed in accordance with local codes. If none exist, use current installation code CAN/ CSA-B149.1 Natural Gas and Propane Installation Code (Canada in Canada or ANSI Z223.1/NFPA 54 in the USA.
• Must be properly connected to an approved venting system and not connected to a chimney fl ue serving a separate solid-fuel burning appliance.
• The fl ow of combustion and ventilation air not be obstructed.
IMPORTANT NOTICE (Regarding fi rst fi re up): When the unit is turned on for the fi rst time, it should be turned onto high without the fan on for
the fi rst 4 hours. This will cure the paint, logs, gasket material and other products used in the manufacturing process. It is advisable to open a window or door, as the unit will start to smoke and can irritate some people. After the unit has gone through the fi rst burn, turn the unit off including the pilot, let the unit get cold then remove the glass door and clean it with a good gas fi replace glass cleaner, available at your local Regency dealer.
4
Regency L965E / HZ965E Gas Fireplace
Page 5
DIMENSIONS:
5-1/4" 5-1/4"
(133mm)
(133mm)
18-3/4" 18-3/4"
(476mm)
(476mm)
DIMENSIONS
Figure 1. Dimensions of the Firebox.
RATING LABEL LOCATION:
The Rating and Lighting instruction label is located below the door frame, underneath the fi rebox attached to a chain. To access the label, slide the plate forward out from under the fi rebox. Always return it when fi nished.
ELECTRICAL HOOK-UP:
An electrical junction box is provided and fastened to the right side of the fi replace. Power needs to be brought to the electrical junction box. The power for the various control components are all provided from the fan control module. Install the provided electric outlet and cover and plug the the fan control module into it. See the Rating Label for the listed electrical requirements.
When installed, the L965E/HZ965E, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
See Page 39.
52-5/16"
52-5/16" (1329mm) (1329mm)
Regency L965E / HZ965E Gas Fireplace
Figure 2. Rating/Lighting Label Location.
5
Page 6
SAFETY LABEL
COPY OF THE SAFETY LABEL
DO NOT REMOVE THIS LABEL / N'ENLEVEZ PAS CETTE ETIQUETTE
Manufactured in Canada for / Fabriqué dans le Canada pour:
WH-
VENTED GAS FIREPLACE HEATER ENVIRO MODEL: FOYER AU GAZ A EVACUATION MODELE ENVIRO:
L965E
NAT: (Natural Gas) LPG (Propane)
TESTED TO / TESTÉE SELON LES NORMES: ANSI Z21.88-2009/CSA 2.33-2009 VENTED GAS FIREPLACE HEATERS / FOYER AU GAZ EVACUATION; CAN/CGA 2.17-M91 GAS FIRED APPLIANCES FOR HIGH ALTITUDES / LES APPAREILS BRULANT GAZ POUR UTILISATION EN HAUTES ALTITUDES; Can/CSA P.4.1-02 (R2006) TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY / LA METHODE D'ESSAI POUR MESURER L'EFFICACITE DE CHEMINEE ANNUELLE.
INPUT (ENTRÉE): NAT: 0-4500 FT (1372 M) LPG: 0-4500 FT (1372 M) MAX: 48,000 BTU (14.07 .Wh) MAX: 48,000 BTU (14.07 .Wh) MIN: 16,000 BTU (4.68 .Wh) MIN: 17,000 BTU (4.98 .Wh) MANIFOLD PRESSURE (PRESSION D’ADMISSION): NAT: 3.5 in. WC (0.87kPa) / 1.6 in. WC (0.40kPa) LPG: 10 in. WC (2.48kPa) / 6.4 in. WC (1.59kPa) MINIMUM GAS SUPPLY PRESSURE: (PRESSION MINIMALE D'ALIMENTATION DE GAZ PERMISE) NAT: 5 in. Wc (1.24kPa) LPG: 12 in. Wc (2.98kPa) ORIFICE SIZE: (DIMENSIONS DE L’ORIFICE) NAT: Left # 45 DMS, Right # 41 DMS LPG: Left # 55 DMS, Right # 53 DMS PILOT ORIFICE SIZE: (DIMENSIONS DE PILOTER L’ORIFICE) NAT: # 62 DMS LPG: Left # 35 DMS
ELECTRICAL RATING:(EXIGENCES ÉLECTRIQUES) Fan type circulator (Ventilateur circulaire): 120V AC 60hz/ Less than 7Amp CLEARANCES TO COMBUSTIBLES: (DISTANCE OBLIGATOIRE DES COMBUSTIBLES) Stove side (Côté de poêle): 4 inches (10.2cm), Back (Arriére): 4 inches (10.2cm), Ceiling from bottom of unit (Du fond d'unité au Plafond): 80” inches (203.2cm), From fireplace frame to side wall (Du frome de la cheminée au mur latéral): 10" (25.5 cm), From base of the unit to shelf, header, or 12" (30.5cm) mantel (De la base de l'unité à une étagère, un en-tête, ou un 12" manteau de cheminée): 52.25" (133cm) VENT PIPE CLEARANCES:(ESPACES LIBRES DE VENTILATION) See manufacturer’s listing, label and installation instructions. Verifeez l’identifaction, l’etiquette et les instructionsd’installation du fabricant. This appliance must be properly connected to a venting system in accordance with the manufacturer's installation instructions. Cet appareil doit être convenablement connecté à un système donner vent conformément aux instructions d'installation du fabricant.
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUELS.
BEDROOM OR BEDSITTING ROOM (IN CANADA with a listed wall thermostat). THIS APPLIANCE MUST BE PROPERLY CONNECTED TO A VENTING SYSTEM IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. FOR DIRECT DISCHARGE WITHOUT DUCT CONNECTION. This appliance must be installed as per manufacturers installation instructions and in accordance with local codes if any. If none exist, use current installation code CAN/CSA B149.1 in Canada or ANSI Z223.1/NFPA 54 in the USA. This vented gas fireplace is not for use with air filters. FOR USE WITH GLASS DOORS CERTIFIED WITH THE APPLIANCE ONLY. This appliance is only for use with the type(s) of gas indicated on the rating plate. A conversion kit is available for this appliance. This appliance is not convertible for use with other gases, unless a certified kit is used.
WARNING: Do not operate the appliance until all sections have been assembled and installed in accordance with the manufacturers instructions. FOYER AU GAZ A EVACUATION - NE PAS EMPLOYER AVEC DES COMBUSTIBLES SOLIDES.
appareil peut être installé dans une chambre à coucher ou un studio. Cet appareil doit être branché correctement à un système de conduits. Uniquement pour l'échappement direct sans raccord de conduit.Cet appareil doit être installé selon les directives d'installation du manufacturier et selon les codes locaux, s'il y a lieu. Autrement, employez le code d'installation en vigueur au Canada CAN/CSA B149.1. Ne pas utilliser de filtre a air avec ce foyer au gaz a evacuation. POUR L'USAGE AVEC PORTES VITREES A CERTIFIE AVEC L'APPAREIL SEULEMENT. Cet apperareil doit etre utilise uniquement avec le type de gaz indique sur la plaque. Cet appareil ne peut etre converti a d’autres gaz sauf si une trouse de conversion certifee est utilisee.
assemblees et installees selon les instructions du fabricant.
MOBILE HOME: May be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. See owner's manual for details. This appliance must be installed in accordance with the current Standard for Mobile Homes, CAN/CSA Z240, or the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or when such standard is not applicable, the current Standard for Fire Safety Criteria for Manufactured Home Installations, sites, and Communitties, ANSI/NFPA 501A. LA MAISON MOBILE :
pour Maisons Mobiles, le BOITE/CSA Z240, ou les Normes de Construction et de Sureté des Maisons Pré-fabriquées (Titre 24 CFR, la Partie 3280). Quand ces Normes ne sont pas en vigueur, il faut suivre les criteres pour la sureté (contre les increndies) et pour la construction des Maisons Pré-fabriquées, leurs sites, ANSI/NFPA 501A, et des communautées aux Instructions du manufacturier.
MANUFACTURED BY (FABRIQUE PAR) : SHERWOOD INDUSTRIES LTD. 6782 OLDFIELD RD. SAANICHTON, BC, CANADA
CAUTION
flammable vapors away.
ADVERTISSEMENT: Ne pas utiliser l’appareil tant que toutes les sections n’ont pas ete
Peut être installé dans une maison mobile. Cet appareil doit être installé conformement aux Normes actuelles
: Hot while in operation. Do not touch. Keep children, clothing, furniture, or gasoline and other liquids having
ATTENTION
Sections of the venting system have not been installed.
: Très chaud quand allumé. Ne touchez pas, les brûlures sévères peuvent résulter.
FPI Fireplace Products International Ltd. Delta, BC, Canada
HZ965E
%
Certified for use in Canada & USA
Certifié pour installation au
Canada et aux Etats-Unis.
MAY BE INSTALLED IN
919-087
75
16354
Cet
Tenez loin des enfants, des vêtements, des meubles,de l’essence ou d’autres fluides produisant des vapeurs inflammables.
J F M A M J J A S O N D 2012 2013 2014 2015
DATE OF MANUFACTURE: DATE DE FABRICATION:
6
Figure 3. Rating Label.
Regency L965E / HZ965E Gas Fireplace
Page 7
INSTALLATION
PLANNING YOUR INSTALLATION
INTRODUCTION:
This section of the technical manual is for the use of qualifi ed technicians only. Fireplace placement, hearths, facings, mantles, and venting terminations will be covered, as well as the gas and electric systems. There are several installation safety guidelines that must be adhered to. Please carefully read the safety precautions at the front of this manual.
Warning: Clearances must be suffi cient to allow access for maintenance and service.
If installing a Power Vent Kit (706-922) or a Heat Distribution Kit (706-921), refer to the instructions included with the kits to aid in your planning.
NON-COMBUSTIBLE MATERIAL ZONE:
This installation guide will show you many options for installing your new L965E/HZ965E Some options include external chases, internal chases, rock facing and corner installations. No matter what direction your installation takes, this illustration shows an area where no combustible building products may go. This illustration applies to any and all installations for the L965E /HZ965E and should be used as the fi rst reference before any others. Failure to comply with this requirement can lead to elevated operating temperatures, degradation of materials or even result in fi re. If you are unclear about any details contained here, consult with your retailer prior to installation.
24"
(610mm)
**52-5/16" (1329mm)
27-3/4"
(705mm)
11 "
(279mm)
Regency L965E / HZ965E Gas Fireplace
Figure 4. Non-Combustible Material Zone.
When Installing a TV above the unit.
7
Page 8
INSTALLATION
FRAMING:
INTERNAL CHASE:
63"
(1600mm)
to centerline
Figure 5. Typical Framing for Internal Chase - General.
24"
(610mm)
Min. Chase Depth
44-3/4"
(1137mm)
Minimum
52-5/16"
(1329mm)
Minimum
52-5/16"
(1329mm)
To Header
NOTE:
Framing chase depth is 26-1/2” when using the heat distribution kit.
Internal ceiling clearance is 90” when using the heat distribution kit.
8
Figure 6. Typical Framing for Internal Chase - Detailed.
Regency L965E / HZ965E Gas Fireplace
Page 9
EXTERNAL CHASE:
Non-Combustible Facing and Hearth Protector Dimensions:
Facing (supplied) 1 Top = 46” x 19” 2 Sides = 32-15/16 x 4-9/16”
Hearth Protector (supplied) 46” x 12”
NOTE: No hearth is required if the unit is raised a
minimum of 18” off the fl oor.
INSTALLATION
Hearth Protector
63"
(1600mm)
to centerline
Figure 7. Typical Framing for External Chase - General.
24"
(610mm)
Min. Chase Depth
44-3/4"
(1137mm)
Minimum
52-5/16"
(1329mm)
To Header
Figure 8. Typical Framing for External Chase - Detailed.
Regency L965E / HZ965E Gas Fireplace
9
Page 10
INSTALLATION
CORNER FRAMING:
Figure 9. Typical Framing for Corner - General.
64”
(1626mm)
44-3/4"
(1137mm)
Minimum
5
Height from Base
2-5/16"(1329mm)
Minimum to
Header/Shelf
of Unit
10
Figure 10. Typical Framing for Corner - Detailed.
Regency L965E / HZ965E Gas Fireplace
Page 11
FRAMING FOR SIDEWALLS AND MANTEL:
0
2
Non-combustible
26
20
10
14
12
64810
10" (254mm)
4"
(102mm)
No Mantel
Here
18-1/2”
0
Mantel Trim
(max. of 1-1/4")
Facing
INSTALLATION
The mantel’s maximum overhang is 10” (254mm) at the minimum height of 52¼” (1327mm) measured from the base of the fi replace.
The mantel can extend 1” (25.4mm) further for every 1” (25.4mm) of height it is installed over the minimum height, as shown in Figure 12.
Non-combustible mantels and mantel legs are not limited to these dimensions.
Mantel temperatures are monitored during testing and can reach 117°F (47°C) above room temperatures. Make sure the fi nish on your mantel is suitable for temperatures of this range.
A wood trim can overhang a maximum of 1-1/4”deep and 14-1/2” in height from the top of the unit as shown in fi gures 11 and 12.
33-1/4”
To Unit
Base
Top of Fireplace Opening
Figure 11. Mantel Clearances
44-3/4"(1 137mm )
Minimum
Framing Width
Figure 12. Typical Framing for Sidewalls & Mantel - Detailed.
Regency L965E / HZ965E Gas Fireplace
51-3/4" (1314mm)
Minimum
Fireplace Base to
Combustible Mantel
11
Page 12
INSTALLATION
TYPICAL FRAMING - RAISED HEARTH:
Warning: Failure to follow these guidelines may result in elevated operating temperatures, an inability to remove or install the door.
A non-combustible Hearth Insulation Board is required to be installed between any non-combustible hearth covering and any combustible fl oor­ing beneath.
The design of the unit is such that the fi replace must be raised by the same distance as any additional hearth covering or riser that are added in front of the fi replace. Figure 14 shows a raised hearth made of a wooden construction hearth riser (B), covered with the insu­lation board provided and then covered with non­combustible slate (A). The thickness of the riser (B) is 4” (102mm). The thickness of the slate (A) is 2” (52mm). A+B=C which is 6” (152mm). In summary, the fi replace must be raised by the same thickness of any material added in front of the fi replace. If the raised hearth is deeper or wider than the Insulation Board provided with the unit, additional non-combustible materials such as Backer Board (cement board) can be used to build up to the same thickness as the Insulation Board. All header, ceiling or shelf dimensions are measured from the fl oor that the fi replace sits on. Failure to maintain minimum installation dimensions can lead to elevated temperatures, fi re or personal injury. For optional Reduced Ceiling Height installations, see Appendix A.
The insulation board supplied with this unit is 46”width x 12” depth x 1/2” thick.
Any additional material such as marble must be the same width and depth as the insulation board.
Figure 13. Typical Framing for a Raised Hearth - General.
Non-combustible
Hearth Pad
Figure 15. Fireplace Section for a Raised
12
Hearth - WARNING.
52-5/16"(1329mm)
Minimum to
Combustible
Header Height
from Base of Unit
Figure 14. Typical Framing for a Raised Hearth - Detailed.
Regency L965E / HZ965E Gas Fireplace
Page 13
INSTALLATION OF FIREPLACE FACING:
INSTALLATION
Figure 16. Typical Facing for the Fireplace - General.
There are three (3) options for installing facing to your fi replace installation. Care must be taken to ensure proper clearances are maintained.
Failure to maintain this clearance will lead to elevated operating temperatures and possible discoloration of materials.
Three (3) possible installations include:
1) For fi replace facing less than 1” thick (total facing and non-combustible board combined) with an optional front installed.
2) For fi replace facing greater than 1” thick with an optional front installed.
3) For any fi replace facing without an optional front installed.
Figure 17. Option 1 - Fireplace Facing Less
Than 1” (25.4mm) Thick.
NOTE: REQUIRES 5/8”(16mm)_AIR GAP
Figure 18. Option 2 - Fireplace Facing More Than 1” (25.4mm) Thick With Optional Front
Installed.
NOTE: REQUIRES 3/4”(19mm) AIR GAP
Figures 17 to 19 highlight the relationships between the fi replace, optional front, and facing installed.
Regency L965E / HZ965E Gas Fireplace
Figure 19. Option 3 - Any Fireplace Facing
Without Optional Front Installed.
13
Page 14
INSTALLATION
RECEIVER INSTALLATION
Figure 22. Receiver Installation.
The Receiver is the heart of the remote control system. You need to access this receiver after installation to change the batteries (for operation during a power failure), to program a new remote / receiver combination and to operate a manual override should you lose your remote control or the batteries in the remote control lose their power.
The Receiver is connected to the fi replace with a wire harness that has a maximum length of 8 ft (2.4m). The connection point on the fi replace is on the right side of the unit, where the gas valve and electronic ignition module is located. Because of the 8 ft (2.4m) limitation in the wiring harness, the receiver needs to be mounted to the right side of the fi replace. An electrical box is provided for the receiver. Mount this electrical box as you would any electrical outlet or switch box. Thread the cable and connector through the back of the electrical box and connect it to the rear of the receiver. Secure the receiver into the electrical box. Once the facing of the fi replace installation is complete, install the receiver cover, supplied with the unit as shown. The receiver cover also functions as a switch plate and allows for access to the program button, critical for remote control operation.
Review the section in this manual regarding the remote control operations for more information on the functions of the receiver.
14
Regency L965E / HZ965E Gas Fireplace
Page 15
INSTALLATION
ALLOWABLE VENT CONFIGURATIONS:
The vent chart, in Figure 23, illustrates the vent confi gurations that have been tested and approved for use with this appliance. 45˚ elbows are acceptable for this installation and may be used instead of 90˚ elbows. You may use two (2) 45˚ elbows for every 90˚ elbow shown in this chart.
This appliance is also approved for use with 5” x 8” fl ex venting. Only use fl exible venting that is approved for this appliance. Flex vent runs must comply with the same limitations as the rigid vent chart shown here. Flexible vent runs greater than 10’ total are not permitted. When using the fl exible vent system, part # 946-601 5” x 8” fl ex pipe adaptor must be used to adapt from rigid venting to fl ex venting. This must be attached to the appliance prior to attaching fl ex venting.
The restrictor settings shown in Figure 23, are recommended. Installation factors such as altitude, prevailing weather conditions such as temperature or wind, or the number of elbows used may affect your fi nal restrictor settings. Insuffi cient restriction may cause pilot outages or reduced effi ciencies. Too much restriction may lead to elevated operating temperatures, poor fl ame appearances, sooting or carbon deposits building up on burner effects or window glass.
Only use the restrictors supplied with this appliance.
Table 1: Vent Restrictor Sizes.
%
Restriction
40%
50%
60%
70%
80%
Ø of Flue
Restrictor
3.878”
(98.5mm)
3.540”
(89.9mm)
3.166”
(80.4mm)
2.742”
(69.6mm)
2.239”
(56.9mm)
Figure 23. Allowable Vent Confi gurations Chart.
Regency L965E / HZ965E Gas Fireplace
15
Page 16
INSTALLATION
VENT TERMINATION RESTRICTIONS:
NOT FOR POWER VENT SYSTEM - IF USING POWER VENT - SEE PAGE 37.
N
O
D
E
C
B
L
F
Fixed
Closed
Openable
B
B
Openable
Fixed
Closed
H
G
G
M
B
A
J
I
Termination Cap
Figure 24. Vent Termination Restrictions, refer to Table 2.
Table 2: Vent termination clearances, refer to Figure 24.
Letter Canadian Installation
A 12 in (30 cm) Clearance above grade, verandah, porch, deck, or
B 12 in (30 cm) 9 in (23 cm) Clearance from window or door that may be opened.
C 12 in (30 cm)* Clearance from permanently closed window (to prevent
D 19¼ in (49 cm) Vertical clearance to ventilated soffi t located above the
E 19¼ in (49 cm) Clearance to unventilated soffi t.
F 17¼ in (44 cm)* Clearance to outside corner.
G 17¼ in (44 cm) Clearance to inside corner.
H 3 ft (91 cm) within a height
of 15 ft (4.5 m) above the meter/regulator assembly
I 3 ft (91 cm) 3 ft (91 cm)* Radial clearance around service regulator vent outlet.
J 12 in (30 cm) 9 in (23 cm) Clearance to non-mechanical air supply inlet to building,
K 6 ft (1.83 m) 3 ft (91 cm) above if within 10
L 7 ft (2.13 m
M 19¼ in (49 cm)
N 12 in (30 cm)* Clearance horizontally to any surface (such as an exte-
O 12 in (30 cm) Clearance above roof line for vertical terminations.
1
)t
Air Supply Inlet
US Installation
3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly*
ft (3 m) horizontally
7 ft (2.13 m)
+
G
2
*t
Gas Meter
balcony.
condensation).
terminal, within a horizontal distance of 2 ft (60 cm) from center line of terminal.
Clearance to each side of center line extended above meter/regulator assembly.
or the combustion air inlet to any other appliance.
Clearance to mechanical air supply inlet.
Clearance above paved sidewalk or paved driveway located on public property.
Clearance under verandah, porch, deck, or balcony.
rior wall) for vertical terminations.
Restriction Zone
(Termination not allowed)
Description
K
A
1
In accordance with the current CSA B149, Natural Gas and Propane Installation Code.
2
In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.
* These numbers are only estimates. Clearance in accordance with installation codes and the requirements of the gas supplier. t
A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings and it serves both dwellings.
+
Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
NOTE: Venting terminals shall not be recessed into walls or siding.
16
Regency L965E / HZ965E Gas Fireplace
16
Page 17
APPROVED VENT PARTS:
Table 3: Vent part numbers (Must state if galvanized or black wanted, PART NUMBERS).
INSTALLATION
Part Description
6” Pipe Length
9” Pipe Length
12” Pipe Length
24” Pipe Length
36” Pipe Length
48” Pipe Length
60” Pipe Length
8 ½” Pipe Extension
16” Pipe Extension
Simpson Duravent
Security Chim.
58DVA-06 SV5L6 5D7 5DT-06 5D6 TC-5DL6
58DVA-09 5DT-09
58DVA-12 SV5L12 5D12 5DT-12 5D12 TC-5DL1
58DVA-24 SV5L24 5D2 5DT-24 5D24 TC-5DL2
58DVA-36 SV5L36 5D3 5DT-36 5D36
58DVA-48 SV5L48 5D4 5DT-48 5D48 TC-5DL4
58DVA-60
58DVA-08A SV5LA12(12”)
58DVA-16A SV5LA24(24”)
American
Metal
5D7A
5D12A
5D16A 5D26A
Selkirk Int. Metal-Fab EXCELDirect
5DT-AJ12 5DAL
Flexible Length, 36” TC-5DLF
12” Adjustable Length TC-5DLT
45° Elbow
90° Elbow
Roof Flashing
Storm Collar
Ceiling Firestop
Wall Firestop
Wall Thimble
Horiz. Square Termination
Horiz. Round Termination
58DVA-E45 SV5E45 5D45L 5DT-EL45 5D45L TE-5DE45
58DVA-E90 SV5E90 5D90L 5DT-EL90 5D90L TE-5DE90
58DVA-F6
SV5F /
SV5FA / SV5FB
5DF12
5DT-AF6
5DT-AF12
5DF
XF-6EF / XF-6EFA
/XF-6EFB
58DVA-SC SV5FC 5DSC 5DT-SC 5DSC TM-SC
58DVA-FS SV5BF 5DFSP 5DT-FS TM-5CS
58DVA-WFS 5DFS
58DVA-WT SV5RMS 5DWT 5DT-WT 5DWT TM-5WT
58DVA-HC-* SV5CHC 5DHCS 5DT-HC 5DHT TM-5HT/TM-5DHT
5DHC
Horizontal Sconce Termination
Vert. Termination, High Wind
Vinyl Siding Standoff
Flex Venting 5” and 8”
*Several color choices
IMPORTANT: This chart covers the major components for each of these manufacturers only. Refer to the manufacturers’ catalogue for further details on roof fl ashings and other installation items
The L965E/HZ965E fi replace has been tested and certifi ed for use with AMERICAN METAL PRODUCTS “AMERIVENT DIRECT”, SIMPSON DURAVENT TYPE GS PIPE FOR GAS STOVES. SECURITY CHIMNEY’S “SECURE VENT DIRECT VENT SYSTEM”, SELKIRK “DIRECT­TEMP VENT SYSTEM”, and EXCELDIRECT “ICC“ kits are available for horizontal and vertical venting. When planning an installation, it will be necessary to select the proper length of vent pipe for the particular requirements. WARNING: Do not mix parts from different vent manufacturers’ systems. EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a Direct Vent GS starting collar in conjunction with Secure Vent, Direct-Temp, and Ameri Vent Direct venting systems. Use of these systems with the Direct Vent GS starting collar is deemed acceptable and does not affect the Intertek WH listing of the appliance.
58DVA-VCH SV5CGV 5DVC 5DT-VT 5DVT
58DVA-VSS SV5VS 5DHVS 5DT-VS 5DVS TM-VSS
Durafl ex
Regency L965E / HZ965E Gas Fireplace
17
Page 18
INSTALLATION
Manufacturer Trade Name Nominal Sizes
Table 4: Approved Vent Manufacturers
American Metal Products AmeriVent Direct
Security Chimneys International LTD Secure Vent
Selkirk Metalbestos Direct-Temp
Simpson Dura-Vent Direct Vent GS
EXCELDirect ICC
INSTALLATION OF FLUE RESTRICTOR:
Figure 25: Installation of Flue Restrictor.
6) Re-install the Light Covers, Firebox Liners, Burners and log sets and the Glass Door.
7) Run the unit for ½ hour to check for proper operations and fl ame appearance.
5” x 8”
5” x 8”
5” x 8”
5” x 8”
5” x 8”
Flue Restrictors are necessary to keep the fi replace running at its intended effi ciency. They are also required to counteract the effect that taller vertical vent runs may have on the appliance. The additional venting action that tall vertical vent systems may have can result in poor pilot and/ or burner operations and possibly nuisance shut downs. Generally, the vent restriction may be less than what is shown in the vent chart, but not greater. The vent restrictor size is shown in percentages, meaning that a 40% restrictor restricts the vent 40% from its fully un-restricted vent size.
1) Remove the Glass Door; refer to DOOR REMOVAL AND INSTALLATION.
2) Remove the Burner and/or Log Set; refer to BURNER REMOVAL AND INSTALLATION.
3) Remove the Refl ective or Brick Panels; refer to REFLECTIVE OR BRICK PANEL INSTALLATION.
4) Refer to the Vent Chart (Figure 23) for selection
of the appropriate Restrictor.
5) Using the two (2) ¼” T-20 screws provided with
the restrictor, fasten the Restrictor into the Flue Outlet as shown in Figures 25 & 26. Make sure the diagonal holes line up with the diagonal holes located in the Flue Outlet Box Use a powered driver to drive the screw in. Be careful not to over-torque the screw and strip the threads.
18
Figure 26: Installation of Flue Restrictor -
Close-Up.
Regency L965E / HZ965E Gas Fireplace
Page 19
INSTALLATION
TV INSTALLATION ABOVE UNIT:
During the development of the L965E/HZ965E, we took into consideration that in some installations TV’s or fl at panel monitors may be located above the mantel. Although we can not anticipate every possible installation variable, we took time to evaluate the suitability of the installation of a TV or Plasma display above the mantel. We carried out testing to evaluate what possible operating temperatures that may be experienced when the appliance was installed in an internal chase. A mantel was installed with the maximum overhang at the minimum allowable installation height, with a full 13” (330mm) shelf installed over the unit (see section NON-COMBUSTIBLE MATERIAL ZONE).
The area above the mantel, within 4 inches (102mm) of the wall was measured under maximum operating conditions and found to not exceed 120°F (49°C). Variations of mantel overhangs, shelf depths or ceiling heights will affect this temperature. Please refer the TV owner’s manual for information on acceptable operating conditions. Care must be taken to evaluate your specifi c installation and operating conditions when deciding to install electronic equipment above or near this appliance when it is in operation. Always consult your TVs owner’s manual to ensure that this application is an approved installation.
SEE NOTE BELOW
Figure 27: Installation of TV Above the Unit.
IMPORTANT: Temperature acceptance levels in TV’s vary greatly. Before installing any electronic appliance above this fi replace, fi rst
verify temperature requirements from the TV manufacturer. See temperatures above for guidance. Regency will not be responsible for heat damage to electronic appliances.
Regency L965E / HZ965E Gas Fireplace
19
Page 20
INSTALLATION
QUALIFIED INSTALLERS ONLY
PLANNING YOUR INSTALLATION:
Prior to starting your venting installation, refer to the section on Allowable Vent Confi gurations to make sure your plans fall into the allowable limits of horizontal and vertical installations.
When planning your installation, it will be necessary to select the proper length of vent pipe for your particular requirements. For horizontal installations, refer to the section on Clearances to Combustibles to determine the minimum clearance from the rear of the appliance to the wall. It is also important to note the wall thickness. Select the amount of vertical rise desired for “vertical-to- horizontal” type installations. To determine the length of vent pipe required for vertical installations, measure the distance from the appliance fl ue outlet to the ceiling, the ceiling thickness, the vertical rise in an attic or second story, and allow for suffi cient vent height above the roofl ine. For two-story applications, fi restops are required at each fl oor level. If an offset is needed in the attic, additional pipe and elbows will be required.
ASSEMBLY OF THE UNIT:
Left and Right
Facing Support
1. Using eight (8) T-20 screws provided, install the facing supports right and left as well as the heat shield in the middle, as shown in Figure 28.
2. Using eight (8) T20 screws provided, attach both back stand-offs, as shown in Figure 29.
Figure 28: Installation of Supports & Heat
shield.
SECURING UNIT INTO POSITION:
Once the unit is in its fi nal position, confi rm that you have access to power, gas supply, that your non-combustible zone requirements are met, that you meet all the minimum vent requirements, and that your planned vent terminal location will meet all of the vent termination clearances. Secure the unit to the fl oor, with at least four (4) wood screws, two (2) on either side of the unit’s bottom nailing fl ange. Secure the side stand-offs to the framing members using four (4) wood screws, one (1) for each stand-off and to the header, one (1) wood screw for each facing support.
Figure 29: Installation of Back Stand-Offs.
20
Figure 30: Securing the Unit.
Regency L965E / HZ965E Gas Fireplace
Page 21
QUALIFIED INSTALLERS ONLY
INSTALLATION OF NON-COMBUSTIBLE WALL AND HEARTH BOARD:
Install the non-combustible wall board and hearth protector provided with the unit. The side boards are interchangeable and are secured with facing screws (¾” screws provided), three (3) to each side of the unit and three (3) to each side frame member. The top board is secured with three (3) facing screws along the top frame (header), three (3) along the top nailing fl ange of the unit and two (2) on each vertical frame member. Also secure the top wall board to the heat shield behind it with two (2) screws and each facing support upright with two (2) screws. See the section on hearth installation for installing the hearth protector, required with the installation of this unit. All the screws required to attach the wall board sides and top to the unit have corresponding holes already located on the units nailing fl anges, facing supports and heat shield.
INSTALLATION OF VENTING AND TERMINATIONS:
Read all instructions carefully before starting the installation. Failure to follow these instructions may create a fi re or other safety hazard, and will void the warranty.
INSTALLATION PRECAUTIONS:
• Do not install any damaged venting or vent components.
• Do not modify any vent or termination component.
• Do not install any vent component that is not an approved vent component for this appliance.
• Do not use any instructions other that those included in this manual or those included by the vent component manufacturer with the venting. When there are discrepancies between the two, this manual will be considered the fi nal authority.
Consult your local building codes before beginning the installation.
INSTALLATION
Non-Combustible Hearth Protection
Figure 31: Installation of Wall & Hearth Board.
Figure 32: Typical Minimum Vent Confi gurations
- Horizontally Terminated.
Regency L965E / HZ965E Gas Fireplace
Figure 33: Typical Vent Confi gurations
- Vertically Terminated.
21
Page 22
INSTALLATION
WARNING
Always maintain required clearances (air spaces) to nearby combustibles to prevent a fi re hazard. Do not fi ll air spaces with insulation. Unless
stated otherwise, clearances on horizontal vent sections are 2” (51mm) to combustible materials. Clearances to vertical vent sections are 1” (25mm) to combustible clearances.
The fi replace and vent system must be vented directly to the outside of the building. Each direct vent fi replace must use its own separate vent
system. Common vent systems are prohibited.
The fl ow of combustion and ventilation air not be obstructed.
HORIZONTAL INSTALLATION:
Step 1. Set the fi replace in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is
Step 2. Direct Vent pipe and fi ttings are designed with special twist-lock connections. Assemble the desired combination of pipe and elbows to the appliance.
Notes:
(1) Twist-lock procedure: Four (4) indentations, located on the female ends of pipes and fi ttings, are designed to slide straight onto the male ends of adjacent
(2) Horizontal runs of vent must be supported every 3 feet (915mm). Wall Straps are available for
(3) Sealant is only necessary on the outer tube of the GS Pipe. Run a 1.25 inch (3mm) wide bead of
Step 3. With the adaptor and pipe attached to the fi replace, slide the fi replace into its correct
Notes:
(1) Any horizontal run of vent must have a ¼ inch (6mm) rise for every 1 foot (305mm) of run towards
(2) The location of the horizontal vent termination on an exterior wall
Step 4. For a Square Horizontal Vent Termination, place the vent cap
Notes:
(1) The four (4) wood screws provided should be replaced with
(2) For buildings with vinyl siding, a Vinyl Siding Standoff should be installed between the vent cap and the wall (see Figure 37). Attach the Vinyl Siding Standoff
the case, you may want to adjust the location of the appliance.
See the sections on TYPICAL FRAMING - INTERNAL CHASE, EXTERNAL CHASE or CORNER INSTALLATION for some of the possible vent pathway options. All installations must fall within the Allowable Vent Confi gurations shown in Figure 20.
pipes and fi ttings, by orienting the four pipe indentations so they match and slide into the four (4) entry slots on the male ends. Push the pipe sections completely together, then twist-lock one section clockwise approximately one-quarter turn, until the two (2) sections are fully locked.
this purpose.
sealant around the male end of the outer sleeve, as shown in Figure 34, and twist-lock the pipes or fi ttings together.
location, and mark the wall for a square hole of the appropriate size. Use 11”x11” (280x280mm) square hole for 8” x 5” pipe. The center of the square hole should line up with the centerline of the horizontal pipe, as shown in Figure 35. Cut and frame the square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, a hole with zero clearance to the pipe is acceptable.
the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fi re.
must meet all local and national building codes, and must not be easily blocked or obstructed. Termination clearances must comply with the VENT TERMINATION RESTRICTIONS section.
in the center of the square hole and attach to the exterior wall with the four wood screws provided (refer to Figure 36). Before attaching the Vent Termination to the exterior wall, run a bead of non-hardening sealant around its outside edges, so as to make a seal between it and the wall. If you are using a Round Horizontal Vent Termination, place an exterior Wall Firestop over the square hole. Run a bead of non-hardening sealant around the edges of the Wall Firestop, and attach the Wall Firestop to the wall with the four wood screws provided. The arrow on the vent cap should be pointing up. Ensure that proper clearances to combustible materials are maintained.
Figure 36: Fastening Horizontal
Termination Cap in Place.
appropriate fasteners for stucco, brick, concrete, or other types o f sidings.
to the Horizontal Vent Termination. The Vinyl Siding Standoff prevents excessive heat from possibly melting the vinyl siding material. Note that the Square Horizontal Vent Termination bolts onto the fl at portion of the Vinyl Siding Standoff, (Shaded area shown in Figure 37), so that an air space will exist between the wall and the Vent Termination.
Figure 34: Twist-Lock Connection.
Figure 35: Horizontal Venting and Cut
Away.
22
Regency L965E / HZ965E Gas Fireplace
Page 23
Figure 38: Installation of Vent Pipe to
Termination.
INSTALLATION
Figure 39: Installation of Wall Firestop.
Figure 37: Installation of Vinyl Siding Standoff.
VERTICAL TERMINATION INSTALLATION:
Step 1. Maintain clearances between venting and combustible building materials as stated earlier in this section. Do not
Step 2. Set the fi replace in its desired location. Drop a plum bob down from the ceiling to the
Step 3. To install the Ceiling Firestop in a fl at ceiling, cut a square hole in the ceiling 11” x 11”
Step 4. Assemble the desired lengths of galvanized Pipe and Elbows necessary to reach from
pack air spaces with insulation. Check with the Allowable Vent Confi gurations page when planning your installation to ensure the vertical and horizontal elements of your installation are within these limits.
position of the appliance fl ue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters, or other framing will obstruct the venting system. You may wish to relocate the appliance, or to offset, to avoid cutting load bearing members.
(280x280mm) square for 8” x 5” pipe, centered on the hole drilled in Step 2. Frame the hole as shown in Figure 40.
the Appliance Adaptor up through the Ceiling Firestop. Ensure that all Pipe and Elbow connections are in their fully twist-locked position.
Figure 40: Installation of Ceiling Firestop.
Regency L965E / HZ965E Gas Fireplace
23
Page 24
INSTALLATION
Step 5. Cut a hole in the roof centered on the small drill hole placed
in the roof in Step 2. The hole should be of suffi cient size to meet the minimum requirements for clearance to combustibles, as specifi ed earlier. Continue to assemble lengths of Pipe and Elbows necessary to reach from the Ceiling Firestop up through the roof line.
Notes: (1) If an offset is necessary in the attic to avoid obstructions, it is important
to support the vent pipe every 3 feet, to avoid excessive stress on the Elbows, and possible separation. Wall Straps are available for this purpose (see Figure 41).
(2) Whenever possible, use 45° Elbows, instead of 90° Elbows. The 45°
Elbow offers less restriction to the fl ow of fl ue gases and intake air.
Step 6. Slip the fl ashing over the Pipe Section(s) protruding through
the roof. Use a non-hardening sealant between the Flashing and the roof to prevent water leakage. Secure the base of the Flashing to the roof with roofi ng nails. Ensure the roofi ng material overlaps the top edge of the Flashing as shown in Figure 42. Verify that you have at least the minimum clearance to combustibles at the roofl ine.
Step 7. Continue to add Pipe Sections until the height of the Vent Cap
meets the minimum building code requirements described by your local codes. In the absence of local codes, make sure the terminal is 2 feet (610mm) above anything within 10 feet (3046mm) of the vent (refer to Figure 44 & Table 5 for clearances for different pitches). Note that for steep roof pitches, the vent height must be increased. In high wind conditions, nearby trees, adjoining roofl ines, steep pitched roofs, and other similar factors can result in poor draft, or down-drafting. In these cases, increasing the vent height may solve this problem.
Step 8. Slip the Storm Collar over the Pipe, and push it down to the top
of the Flashing, as shown in Figure 42. Use the non-hardening sealant above and below the joint between the Storm Collar and the Pipe.
Step 9. Twist lock the Vent Cap.
Figure 41: Vertical
Installation Using High
Wind Cap.
Notes: (1) For multi-story vertical installations, a Ceiling Firestop is required at
any subsequent fl oors (as shown in Figure 43). The opening should be cut and framed in the same manner as the opening in Step 3 (see Figure 40).
(2) Any occupied areas above the fi rst fl oor, including closets and storage
spaces, which the vertical vent passes through, must be enclosed. The enclosure may be framed and sheet rocked with standard construction materials, however minimum allowable clearances between the outside of the vent pipe must be maintained. Do not fi ll any of the required air spaces with insulation.
24
Figure 42: Installation of Flashing & Vertical
Termination.
Figure 43: Installation of
Ceiling Fire Stops.
Regency L965E / HZ965E Gas Fireplace
Page 25
Table 5: Minimum ‘H’ for Figure 44.
Roof Pitch Minimum Height (H)
Feet Meters
Flat to 7/12 1 0.3
Over 7/12 to 8/12 1.5 0.46
Over 8/12 to 9/12 2 0.61
Over 9/12 to 10/12 2.5 0.76
Over 10/12 to 11/12 3.25 0.99
Over 11/12 to 12/12 4 1.22
Over 12/12 to 14/12 5 1.52
Over 14/12 to 16/12 6 1.83
Over 16/12 to 18/12 7 2.13
Over 18/12 to 20/12 7.5 2.29
Over 20/12 to 21/12 8 2.44
VENTING ARRANGEMENTS - HORIZONTAL TERMINATION (FLEX):
Regency® Direct Vent System
INSTALLATION
Figure 44: Height of Vertical Termination;
Reference Table 5.
These venting systems, in combination with the HZ965/L965, have been tested and listed as a direct vent system by Warnock Hersey. The
location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.
FPI Direct Vent (Flex) System T ermination Kits include all the parts needed to install the HZ965/L965, using a fl exible vent.
FPI Kit # Length Contains:
#946-615 4 Feet 1) 8” fl exible liner (Kit length)
#946-618 6 Feet
#946-616 10 Feet
2) 5” fl exible liner (Kit length)
3) spring spacers
4) thimble
5) AstroCap termination cap
6) screws
7) tube of Mill Pac
8) plated screws
9) S.S. screws #8 x 1-1/2” drill point
10) vinyl siding standoff
Rigid pipe adaptor
(Part # 946-601)
Regency L965E / HZ965E Gas Fireplace
(standard with unit)
25
Page 26
INSTALLATION
HEAT DISTRIBUTION KIT INSTALLATION:
Please ensure that your Heat Distribution Kit has not been damaged.
IMPORTANT: When installing the Heat Distribution Kit, the framing clearances are different. See fi gure 12 on page 29. Clearances must be maintained.
1. Remove the rear standoff and the duct cover plate from the back of the unit.
Rear of the Unit
Duct Cover Plate
Rear Standoff
Figure 2: Remove the duct cover.
2. Insert the hot air duct and the hot air duct angle into the
cut out (refer to Figure 3). Secure the ducts to the back of the fi replace through the pre-drilled holes with hex head
Rear of the Unit
Hot Air Duct Angle
Hot Air Duct
Figure 3: Install the hot air ducts.
Item Description
1 Hot Air Duct
2 Hot Air Duct Angle
3 Fireplace Vent Duct
4 Fan Bezel
5 Front Access Cover
6Fan
7 Fan Housing Assembly
8 Fan Housing Mounting Bracket
9 5” Round Flex Line Air Duct
NOTE:
The supply grill not supplied with unit.
Figure 1: Heat Distribution Kit’s Parts Diagram.
screws.
3. Cover the hot air duct opening with the Fireplace Vent Duct (refer to Figure 4). Push the vent duct kit against the back of the fi replace and secure it in place with fi ve (5) ¼” HWH self drilling screws.
26
Regency L965E / HZ965E Gas Fireplace
Page 27
Fireplace
Vent Duct Collar
Hot Air Duct Opening
Rear of the Unit
Fireplace Vent Duct
(57mm)
2"
41/16"
(103mm)
21/4"
1
/4"
18
(464mm)
133/4"
(349mm)
INSTALLATION
21/4"
(57mm)
1
5
(129mm)
81/16"
(105mm)
/16"
3
Min 8 (222mm)
Figure 4: Install the vent duct kit.
TYP 16"
(406mm)
3
/8"
Min 14
(365mm)
/4"
Fan Cut Out
2"x4" Wall Stud
Hot Air Duct
Figure 5: Fan housing overall dimensions.
(305mm)
3
/4"
12"
Ceiling
3
/4"
1
(44mm)
2x4 Wall Stud
Fan Housing
C
L
1
(44mm)
Fan Housing
1
17
/4"
(438mm)
Fan Mounting Brackets
Figure 7: Mounting fan housing.
4. With the “FIGURE 5: FAN HOUSING OVERALL DIMENSIONS.” and “FIGURE 6: M
INIMUM INSTALLATION CLEARANCES FOR FAN.”
Cut a opening for the fan in the wall board; minimum 14” by 8”. It cannot be less than 12” from the ceiling and 1¾” between fan housing to the closest stud or combustible materials. Do not install in front of the vent.
Figure 6: Minimum Installation Clearances for Fan.
5. Mount and secure the fan housing assembly to the framing members or to the 2x4 wall studs using the mounting brackets and screws provided in the
kit (refer to Figure 7).
Note: The brackets have a guided fl ange which provides the minimum spacing required between the fan housing and 2x4 wall studs or combustible materials.
6. Wire the fan (refer to Figure 8)
a) Feed the 110-120 VAC electrical service wires through the strain relief and through the service hole on the bottom of the fan housing. b) Secure the service wires to the strain relief. c) Use the wire nut to join the wires to the service wire. d) Secure the service ground wire to the ground screw on the cover plate.
Regency L965E / HZ965E Gas Fireplace
27
Page 28
INSTALLATION
Fan Housing
Ground
Cover Plate
Strain Relief
Figure 8: Wiring fan.
e) Secure the cover plate to the back of the fan hous­ing with screws f) Secure the service wires to the strain relief f) For wiring options see Figure 9.
8. Attach the 5” Aluminum Flex Vent to the Fireplace Vent Duct Collar with sheet metal screws or a vent strap and run the vent to the Fan Housing Vent Duct Collar. The Fan Housing Vent Duct can be installed through the rear or the bottom of the Fan Housing as shown in Figure 10.
Figure 9: Fan wiring options.
Fan Housing
Vent Duct Collar
IMPORTANT: Maintain a minimum of 2” (51mm) clearance between the fl ex lines and combustible materials. Optional Note: An 8ft (2.4m) 5” Aluminum Flex Vent is provided. An extra 5” aluminum fl ex run can be added using a coupling provided by the installer. An extra 12’ in length can be added making the total run 20’, which is the maximum allowable.
9. Attach the fan bezel to the fan cut out and secure the fan bezel to the wall board with screws.
10. Cover the cut out with a fan grille.
When installed, the Power Vent Kit, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
WARNING: Electrical Grounding Instructions This appliance is equipped with a three-prong (grounding) plug for your pro­tection against shock hazard and should be plugged directly into a properly
grounded three-prong receptacle. Do not cut or remove the grounding prong
from this plug.
Periodic examination of venting systems should be done by a qualifi ed agency.
28
5" Aluminum
Flex Vent
Fireplace
Duct Collar
Figure 10: Optional install with two (2) heat distribution kits.
143/8" (365mm)
8” X 14” grille is required-purchased separately.
Figure 11: Install fan bezel & grille.
Regency L965E / HZ965E Gas Fireplace
Vent
Fan Grille
(Not Supplied)
Fan Housing
83/4
"
(222mm)
Fan Bezel
Page 29
60"
(1524mm)
Chase Minimum Width
26 1/2"
(610mm)
Chase Minimum
Depth
INSTALLATION
44 3/4"
(1137mm)
Minimum
A
**
52 5/16" (1329mm) to Header
** Minimum Height from the base of the unit.
90"
(2286mm)
to Internal
Ceiling
Figure 12: Installation Clearances with Heat Distribution Kit.
Regency L965E / HZ965E Gas Fireplace
29
Page 30
INSTALLATION
POWER VENT KIT INSTALLATION:
Please ensure that your Power Vent Kit has not been damaged.
1. Plan out the venting and wiring installation. Important notes to consider when planning where the venting will be installed:
Minimum horizontal vent run allowed with no rise
is 1 foot (305mm).
• Horizontal vent runs less than 8 feet (2.44m) require a 60% restrictor. Refer to the Owner’s Manual on how to install a restrictor.
• Maximum vent run is 100 feet (30.5m) (H1 + V + H2 + H3 + H4 + H5 + H6), refer to Figure 2.
• Maximum below-grade installation is 8 feet (2.4m) (V).
• Multi-elbow installations are possible up to a maximum of six 90°.
• See Figure 4a for the typical overall dimensions with a minimum horizontal vent installed.
• Refer to Figure 19 and Table 1 for vent termination clearances and restrictions.
• Approved vent systems are as follow when using 4” x 6-5/8” pipe. Simpson duravent, Security Chimney, American Metal,
Selkirk Int. Metal Fab., Excel Direct.
Item Description
1 5”x8” to 4”x6” Vent Reducer*
2 4”x6” Wall Thimble
3 Power Vent Assembly
4 Power Vent Control Box
* Item not included
Figure 1: Power Vent Kit’s Parts Diagram.
5"x8" to 4"x6
Vent Reducer
5"x8"
o
90
Elbow
5
/8"
H1
90
4"x6
o
Elbow
5
/8"
V
Power Vent
H6
H2
H5
H4
H3
Figure 2: Below-grade installation with maximum number of elbows.
30
Regency L965E / HZ965E Gas Fireplace
Page 31
INSTALLATION
5" x 8" to
4" x 6
Vent Reducer
5" x 8"
90o
Elbow
Power Vent Control Box
5
/8"
1ft (305mm)
4” x 6-5/8” vent
4" x 6" Vent
Wall
Thimble
2" x 4"
Wall Stud
Wall
Board
1
14
/8"
(359mm)
97/16"
(240mm)
Power
Vent
141/2"
(368mm)
141/2"
(368mm)
391/16" (992mm)
Figure 5: Thimble framing dimensions.
44" (1.11m)
Figure 4 Typical overall dimensions with minimum horizontal
• 50 feet (15.25m) of cable is supplied with this kit, if more venting is required, use 706-033 - 100 feet (30.5m) PVK CABLE and connect it as shown on the wiring diagram in Figure 4.
• Allow for an extra 24”-30” (60-75cm) of cable at the PVK control box for future servicing.
2. Reduce the venting size from 5” x 8” to 4” x 6-5/8 with a vent reducer, see Figure 1.
3. Using the dimensions in Figures 4 & 5, frame an opening for the thimble of 14½” x 14½” (368mm x 368mm).
4. Insert a 2 ft (61cm) length of the power vent electrical cord through the bushing on the bottom left of the inner thimble, shown in Figure 6.
5. Secure the inner thimble to the wall board with screws.
6. Insert the rest of the power vent electrical cord through the bushing on the right bottom of the outer thimble, refer to Figure 7
vent installed.
Regency L965E / HZ965E Gas Fireplace
31
Page 32
INSTALLATION
Wall Board
Screw
Vents
Inner Thimble
Wall Board
Outer Thimble
Power Vent
Electrical Cord
Bushing
Inner Thimble
Power Vent Electrical Cord
Bushing
Screw
Figure 6: Install the inner thimble and the power
vent cords.
7. Assemble the outer thimble to the inner thimble and secure the outer thimble to the wall board with screws.
8. Remove power vent case cover from power vent assembly by removing 4 x 5/16” screws (2 per side). Pull the top of power vent and then push downward on power vent case cover to clear exhaust assembly
Figure 7: Install the outer thimble.
9. Insert the power vent electrical cord through the Strain Relief on the bottom right of the power vent assembly, refer to Figure 8.
10. Align the power vent assembly with the direct vent pipe that is protruding through the thimble.
11. Secure the power vent assembly in place with screws as seen in Figure 8.
Figure 8: Install the power vent.
Figure 9: Securing cord with the Strain Relief.
32
Regency L965E / HZ965E Gas Fireplace
Page 33
INSTALLATION
Power Vent Case Cover
Exhaust
Cut-Out
Figure 10: Fan and vacuum switch wired.
12. Secure the cord to the Power Vent Assembly with the Strain Relief as shown in Figure 9.
13. Connect the wires to the fan, vacuum switch, and ground according to the wiring diagram in Figure 17. Secure the green ground wire as shown in Figure
9. Route the wires as shown in Figure 10 to prevent them from getting pinched.
14. Align the exhaust defl ector with the exhaust cut out on the bottom of the power vent cover and install, refer to Figure 8, 11 and 12. Ensure that the rubber vacuum hose does not kink when installed.
Figure 11: Install the power vent cover case.
Power Vent
Screw
Vacuum Switch
Power Vent
Assembly
15 Secure the cover to the power vent assembly with screws to the left and right sides of the assembly.
16. Remove the protective cover from the PVK Control Box Velcro and secure the power vent control box to the side as shown in Figure 1a.
Figure 12: Cover is installed to the power vent
assembly.
Figure 13: Removing Access Cover.
Regency L965E / HZ965E Gas Fireplace
33
Page 34
INSTALLATION
17. When using the 50-1970 Power Vent Kit, there is no need to have the unit set to continuous pilot, connect the 9V clip of the PVK to the 9V clip of the unit.
a) Remove the Access Cover from inside the fi rebox by removing all ten (10) T-20 screws (see Figure 13).
b) Disconnect the connection to the Standing Pilot
Switch as shown in Figure 14.
c) Disconnect the TH wires from under the valve
and plug in the two (2) orange wires as shown in Figure 15.
d) Disconnect the 3/16” connector from the valve
and connect the two (2) blue wires as shown in Figure 16.
18. Plug the power cord from the PVK Control Box into the top outlet of the Electric Box on the side of the unit as shown in Figure 17.
19. Reinstall the Side Access Cover and continue
with the appliance
Figure 14: Disconnecting Standing Pilot
Switch.
Figure 15
Installation steps as shown in the Instruc­tion Manual. When installed, the Power Vent Kit, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
: Disconnecting TH Wire & Connecting
Orange Wires.
Figure 17: Plugging PVK into Electric Box.
WARNING: Electrical Grounding Instructions
This appliance is equipped with a three-prong (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug. Periodic examination of venting systems should be done by a qualifi ed agency.
Figure 16: Changing Valve Wiring.
34
Regency L965E / HZ965E Gas Fireplace
Page 35
INSTALLATION
SILICONE NOTES:
Installer should apply outdoor silicone to the powervent cover on the areas shown below as a preventative measure to help keep water from getting
inside.
SILICONE THESE AREAS
Regency L965E / HZ965E Gas Fireplace
SILICONE THESE AREAS
35
Page 36
INSTALLATION
August 25, 2009
50-1970 WESTGATE
BLACK
CN1 MOLEX
1Red
2Red
3Black
4Green
5Blue
6White
7Orange
8 Green
9 Yellow
Star Washer
GREEN (Ground)
RED
WHITE
:
ALL SPADE CONNECTORS
NEED TO BE SPACED 1"
NOTE
APART.
BROWN
1/4" Male Spades
3" (Insulated)
GRAY
ONG
BLUE
BRN
ONG
GRAY
BRN
BLUE
4"
RED
PCB
BROWN
GREEN
BLUE IN
N.O.SW
WHITE
BLUE OUT
ORANGE
GREEN
(Ground)
BLACK
C-11974 (2ft)
Molex Mini-fit 2
WHITE
IPI/CPI
C-11817
(1ft)
BLUE OUT
3/16" Spades
(0.187)
(50ft)
C-11896
BLUE IN
ONG
BROWN
N.O.SW
(Vacuum)
MOTOR
BLACK
BLOWER
3/16" Female Spade
(0.187)
P M
SIT 885 Valve
Fan Control Module
S
Pilot
GROUND
2 ft
FCM-COM
I
Figure 18: Wiring Schematic Diagram.
COM
TRIGGER
ONG
TH
WHT
GRN
6-prongs
snap
9V clip
6-prongs
snap
TPTH
TH
receptacle
36
Split Flow
WHT
GRN
BATTERY
COM
SPLIT FLOW
DFC
CN1
23456789
CN1 Molex 9 ways female connector
1
DC receptacle Coaxial female
DFC-SUPPLY
Regency L965E / HZ965E Gas Fireplace
SIT - DFC
S-Receiver
Page 37
FOR POWER VENT SYSTEM ONLY
IF NOT USING POWER VENT - SEE CHART ON PAGE 16.
INSTALLATION
N
O
D
E
C
B
L
F
Fixed
Closed
Openable
B
B
Openable
Fixed
Closed
H
G
G
M
B
A
J
I
Termination Cap
Figure 19. Vent Termination Restrictions, refer to Table 1.
Table 1: Vent termination clearances, refer to Figure 19.
Letter Canadian Installation
A 24 in (60 cm) Clearance above grade, verandah, porch, deck, or balcony.
B 12 in (30 cm) 9 in (23 cm) Clearance from window or door that may be opened.
C 12 in (30 cm)* Clearance from permanently closed window (to prevent
D 4 in (10 cm) Vertical clearance to ventilated soffi t located above the terminal,
E 4 in (10 cm) Clearance to unventilated soffi t.
F 12 in (30 cm)* Clearance to outside corner.
G 4 in (10 cm) Clearance to inside corner.
H 3 ft (91 cm) within a height
of 15 ft (4.5 m) above the
meter/regulator assembly
I 3 ft (91 cm) 3 ft (91 cm)* Radial clearance around service regulator vent outlet.
J 12 in (30 cm) 9 in (23 cm) Clearance to non-mechanical air supply inlet to building, or the
K 6 ft (1.83 m) 3 ft (91 cm) above if within 10
L 7 ft (2.13 m
M 19¼ in (49 cm)
1
3 ft (91 cm) within a height
of 15 ft (4.5 m) above the
meter/regulator assembly*
)t
Air Supply Inlet
US Installation
ft (3 m) horizontally
7 ft (2.13 m)
+
2
*t
Gas MeterG
condensation).
within a horizontal distance of 2 ft (60 cm) from center line of terminal.
Clearance to each side of center line extended above meter/ regulator assembly.
combustion air inlet to any other appliance.
Clearance to mechanical air supply inlet.
Clearance above paved sidewalk or paved driveway located on public property.
Clearance under verandah, porch, deck, or balcony.
Restriction Zone
(Termination not allowed)
Description
K
A
1
In accordance with the current CSA B149, Natural Gas and Propane Installation Code.
2
In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.
* These numbers are only estimates. Clearance in accordance with installation codes and the requirements of the gas supplier. t
A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings and it serves both dwellings.
+
Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
NOTE: Venting terminals shall not be recessed into walls or siding.
Regency L965E / HZ965E Gas Fireplace
37
Page 38
INSTALLATION
DOOR REMOVAL AND INSTALLATION:
1) The fi replace door hangs on two (2) hooks on the top of the fi rebox. The two (2) door latches at the bottom of the fi rebox hook over the tabs on the bottom of the door frame.
2) Lower the door latch tool underneath the door frame. Catch the lower door latch
with the door latch tool (see Figure 45) and pull it out slightly, then down. Once the lower door latch clears the tab on the bottom of the door frame, release it inwards and then remove the door latch tool. Refer to Figures 47 & 48.
3) Pull the Door Frame at the bottom forward about 2” (5cm), then lift the Door
Frame upwards to clear the Upper Door Hooks. Refer to Figures 48 & 49.
4) Lift the Door Frame away, being careful that the glass panel is secure within the
Door Frame.
Large hooked end for
removing the door.
Figure 45: Door Latch /Air Adjustment Tool.
Slots on other end
is for Air Shutter
Adjustment Levers
Figure 48: Door Latch Locations.
38
Figure 47: Door Latch Tool in Place. Figure 46: Door Latch Locations.
Figure 49: Top Door Hook.
Regency L965E / HZ965E Gas Fireplace
Page 39
GAS HOOK-UP:
The L965E/H965E are equipped from the factory with a 1/2” SAE 45º male gas fitting. This fitting will fit commonly used flexible gas supply lines.
If your local code requires you to use only rigid pipe for gas supply, remove the flare fitting provided. The gas line is fastened to an MPT flare fitting.
You can then use a common union to provide the gas connection to the appliance. The dimension shown in Figure 50 are for your convenience if you have to hard pipe directly to the unit.
NOTES:
This appliance and it’s main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressure in excess of 1/2 psi (3.5 kPa).
Isolate this appliance from the gas supply piping system by closing its the equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
INSTALLATION
ELECTRICAL HOOK-UP:
An electrical junction box is provided and fastened to the right side of the fi replace. Power needs to be brought to the electrical junction box. The power for the various control components are all provided from the fan control module. Install the provided electric outlet and cover and plug the the fan control module into it. See the Rating Label for the listed electrical requirements.
When installed, the L965E/HZ965E, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
WARNING
Electrical Grounding Instructions
This appliance is equipped with a three-prong (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
Figure 50: Location of Gas Hook-Up.
NOTE:
Electrical box is located inside this panel-shown outside to show location.
Figure 51: Location of Electrical Hook-Up.
Regency L965E / HZ965E Gas Fireplace
39
Page 40
INSTALLATION
LP GAS CONVERSION:
WARNING: This conversion kit shall be installed by a qualifi ed service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fi re, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualifi ed service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specifi ed in the manufacturer’s instructions supplied with the kit.
1. Ensure all the components of the conversion kit are accounted for. There should be a pilot orifi ce, left & right for the glass tray orifi ces, left & right for the log burner orifi ces, regulator diaphragm, servo regulator, and conversion label.
2. If the unit has already been connected to a gas supply, shut off the gas supply to the unit.
3. If the unit has been run, shut off and allow cooling to room temperature.
4. Remove the fi replace door. (see DOOR REMOVAL AND INSTALLATION).
5. Remove the burner, glass crystals and fi rebox liners. (see each applicable section in this manual),
6. The pilot hood is held in with spring pressure. Remove the hood by pulling it directly up from the pilot assembly (Figure 52).
7. Insert a 5/32” or 4mm Allen wrench into the top of the pilot orifi ce. Remove it by rotating it counter-clock wise until it is free of the pilot assembly (Figure 53).
8. Ensure that the pilot orifi ce you are about to install is the correct orifi ce. LP orifi ces have a groove cut around the top of the orifi ce. See Figure 54 for help to identify these parts. The orifi ce size is stamped into the orifi ce. The correct orifi ce sizes for the L965E/HZ965E are LPG - 35 and NG - 62.
Figure 52: Removing the hood.
Figure 53: Removing the Pilot
Orifi ce.
Figure 54: Identifying the Orifi ce.
40
Figure 55: Removing the Gas Orifi ces.
Regency L965E / HZ965E Gas Fireplace
Page 41
9. Install the correct orifi ce and replace the pilot hood. The pilot hood has an indexing notch which must be align with the pilot base. Ensure the pilot hood is properly located and that the spring holding the pilot hood is properly engaged. Delayed ignition may be the result of an improperly installed pilot hood.
10. Using a socket wrench, remove both gas burner orifi ces from the orifi ce mounting brackets at the rear fl oor of the fi rebox (Figure 55).
11. Use only the gas burner orifi ces that were included in
the LP gas conversion kit supplied by the manufacturer. The correct orifi ce sizes for the L965E/HZ965E are shown in Table 6.
INSTALLATION
Figure 56: Removing the Right Burner
Support.
Figure 57: Removing Access
Cover.
Table 6: Correct Orifi ce Sizes for the L965E/HZ965E
Burner Left (front) Right (rear)
Glass Tray NG 45 41
Glass Tray LP 55 53
Log Burner NG 45 41
Log Burner LP 55 53
12. Using a T-20 driver, remove the Right Burner Support (Figure 56).
13. Remove the Valve Access Cover by removing all ten (10) T-20 screws (Figure 57).
14. Using a T-20 safety driver, remove the two (2) screws that hold the fl ame modulator from the gas valve (Figure 58).
15 Remove the rubber regulator diaphragm that is situated between the servo regulator and the valve
body and replace with the one provide in the LP conversion kit.
16. Install the LP fl ame modulator, with the new longer T-20 screws, included in the LP conversion kit.
17. If the fuel delivery pressure or the manifold pressure is to be verifi ed, it can be done at this stage. a. Loosen the pressure tap screw. b. Place a ¼” silicone tube over either pressure port on the valve (refer to Figure 59). Attach the tube to
a mono meter. c. Install a burner in the fi rebox (see burner installation section) d. Being careful to route the silicone tube away from the burner, test fi re the unit for only long enough to establish the pressure reading. e. Check your inlet gas pressure by measuring the pressure at the inlet pressure tap on the valve. Inlet pressure should be a minimum of 12”
WC for LPG. If the pressure reads less than this, have a licensed gas fi tter determine and rectify the reason for the reduced supply pressure. f. Check your manifold pressure by measuring the pressure at the manifold pressure tap on the valve. The manifold pressure with the appliance
operating at its high setting should be between 9.5” WC and 10.5” WC. If your pressure reads outside of this range, make sure that your LP
conversion regulator has been properly installed. If it has, call your dealer to arrange for a replacement valve to be installed. Turn off the fuel
supply to do not operate this unit until the valve has been replaced.
g. Make sure to close the test pressure point taps after testing.
18. Re-install the Valve Access Cover, making sure that the wire harness is carefully tucked back into the valve compartment and that the pilot tube, igniter lead and fl ame proving wire are routed through the provisions in the Valve Access Cover and the Firebox opening.
19. Re-install the Right Burner Support.
20. Re-connect the fuel supply to the unit.
21. Re-install the Fireplace Panel Set, Burner, Burner Trim Kit, Grate, Logs or Glass Burner and Front Door.
22. Once the unit is re-assembled and started, use a gas leakage detector to check for any fuel leakage. Check around the entire valve assembly, particularly around the gas regulator and fl ame modulator. Make sure that the LP regulator has been properly installed and is not leaking any fuel.
23. Once the supply pressure and the manifold pressure have been confi rmed, you can check the units rating by confi rming the correct orifi ce sizes are installed. This can be done by using a quality orifi ce gauge and referring to the chart above for the correct offi ce sizing. The rating is listed on the rating plate located under the fi rebox, attached to the unit with a cable.
Figure 58: Modulator Screws.
Regency L965E / HZ965E Gas Fireplace
41
Page 42
INSTALLATION
24. Fire the unit to ensure correct operation and fl ame picture. Ensure the Split Valve and Flame Modulation works as described in the operations section of this manual.
25. Check the pilot fl ame that it is the correct size and orientation. The pilot fl ame can be adjusted with the adjustment provision on the front face of the valve. This is located just up and to the left of the regulator motor. It is clearly marked on the valve. Adjusting the screw in or out will raise or lower the pilot fl ame height. The correct pilot fl ame should resemble Figure 60.
The ignition sequence should be as follows:
a) Press the ON button on the remote control. b) The receiver should beep, to indicate the command has been received. c) Within a 2-3 second of the beep, the ignitor should begin to spark. The ignitor will
spark at intervals of 1 second(s). d) The main valve will open 4-6 seconds after the pilot is lit. e) Within 4 seconds of the main valve opening, all of the burner ports should light and
remain burning.
26. To complete the LP conversion of this appliance, place the “LP Converted” sticker, supplied with the LP conversion kit on the rating plate indicating that this unit has been converted to operate on LP gas.
Figure 59: Pressure Test Points.
42
Figure 60: Relationship between ignitor and burner.
Regency L965E / HZ965E Gas Fireplace
Page 43
GLASS BURNER REMOVAL/INSTALLATION:
INSTALLATION
1) Removal the front panel of the burner by removing 2 screws in the locations
shown in Figure 61 and Figure 62.
Figure 61: Front Panel Screw Locations
Figure 62: Removing Front Panel
Screws
2) After the screws are removed, lift out the front panel as shown in Figure 63.
4) Carefully pull the burner forward (see Figure 65) away from the
mixing tubes. When clear of the mixing tubes, lift the burner up and out.
Figure 65: Move Burner away from Mixing Tubes
5) To install, reverse steps.
Figure 63: Lift Out Front Panel
3) Remove the 4 screws on the burner in locations shown in Figure 64.
Figure 64: Burner Screw Locations
Regency L965E / HZ965E Gas Fireplace
43
Page 44
INSTALLATION
GLASS CRYSTAL / STONES INSTALLATION :
Evenly spread the Glass Crystals or optional Ceramic Spa Stones over the burner. Ensure the crystals (or stones) do not overlap too much as this will effect the fl ame pattern.
IMPORTANT NOTE:
Only the supplied approved Glass Crystals and Ceramic Spa Stones are to be used with these fi replaces. Use of any other type of glass crystals or stones can alter the unit's performance, any damage caused by the use of any unapproved glass or stones will not be covered under warranty.
When using Ceramic Spa Stones DO NOT cover burner ports or pilot light that lead to pilot fl ame. Ensure the crystals or stones do not overlap excessively as this will effect the fl ame pattern.
BURNER PACKAGES
Unit *Glass Crystals **Ceramic Spa Stones
HZ965 12 lbs 140 spa stones NOTE: * Glass Crystals are available in 1lb and 5lb bags.
**Each Ceramic Spa stone package contains 70 stones.
1) Start Crystals on back Burner and
3) Work Crystals downwards to front
NOTE: Correct fi nal glass installation of Crystals as shown in step 4 and 5. The Burner and Firebox Floor should not be visible when the fl ame is out.
Figure 69 Figure 70
4) Crystals shown spread evenly over
edge of Firebox Floor
Figure 67Figure 66 Figure 68
Firebox Floor
the burner and fi rebox base.
OPTIONAL SPA STONES INSTALLATION (AROUND BURNER)
2) Work Crystals downwards to front of Burner and Firebox Floor
Figure 71
5) Ensure Crystals do not block the front of the pilot hood and fl ame to
light the burner.
Figure 72 Figure 73
NOTE: Spa Stones are NOT to be placed anywhere on the Pilot assembly area.
Glass Crystals to be installed on the burner and fi rebox fl oor prior to installing stones.
44
Regency L965E / HZ965E Gas Fireplace
Page 45
INSTALLATION
REFLECTIVE PANEL INSTALLATION / REMOVAL:
Before installation, panels must be handled and cleaned as per instructions noted below:
Black Enamel Panels
Black Enamel panels must be inspected for scratches and dimples prior to installation. All claims to be recorded at this time.
Claims for damage after installation will not receive consideration.
Black Enamel panels will discolor a little during normal operation. This is normal and should not be considered a defect.
All hand and fi nger marks MUST be cleaned off with a soft cloth.
*
Use an ammonia based cleaner (ie. glass cleaner) to remove any fi ngerprints before applying heat to the unit. Failure to do this will result in burn stain on panels which you will be unable to remove. Not protected by product warranty.
1. Install the Rear Porcelain Panel by placing it behind the burner. Use cau­tion- do not scratch the panel.
Figure 74: Rear Porcelain Panel
2. Install the Left Refl ective Panel; it should be fl ush with the outer edge of
the fi rebox (see Figure 76).
With panel in position, slide panel clip in until it touches the panel, tighten
panel clip screws as shown in Figure 75.
Figure 76: Panel /Unit Alignment.
3. Install the Top Panel by placing it on top of the Rear Panel and behind the
Left Panel (see Figure 77). Hold with one hand then place right side panel.
Figure 77: Upper Rear Porcelain Panel
4. Repeat same procedure in Step 2 to install Right Side Panel.
5. To remove panels, reverse steps.
Figure 75: Side Porcelain Panel and Panel
Clip
Regency L965E / HZ965E Gas Fireplace
Figure 78: Final Install
45
Page 46
INSTALLATION
BRICK PANEL INSTALLATION / REMOVAL:
1) Loosen screws securing Brick Panel Clip shown in Figure 76 and slide Clip away from wall of unit.
4) Slide the upper back panel in behind the left side panel and on top of the lower back panel as shown in Figure 79.
Figure 76: Brick Clip
2) 6OLGHWKHORZHUEDFNSDQHOLQ¿UVWDQGUHVWLWRQWKHUHDUZDOO
support bracket as shown in Figure 77.
Figure 77: Lower Back Brick Panel
3) Slide Left Brick Panel in between wall of unit and Brick Clip as shown
LQDQG)LJXUH)URQWHGJHRISDQHOPXVWEHÀXVKZLWK¿UHER[HGJH
side panel will now hold rear panel up against back wall.
Slide Panel Clip until it is snug against the Left Side Brick Panel and
retighten screw to secure clip.
Figure 79: Upper Back Brick Panel
5) Follow directions from Step 3 to install Right Side Panel to complete installation.
Figure 80: Right Side Brick Panel
Figure 78: Left Brick Panel
46
Figure 81: Completed Install
6) To remove Brick Panels, reverse steps.
Regency L965E / HZ965E Gas Fireplace
Page 47
LOG BURNER / EMBER BED REMOVAL / INSTALLATION:
1. Pull the burner away from the mixing tubes.
2. Lift the burner up and out of the unit.
3. Reverse steps to reinstall.
Note: Use caution when lifting, burner is heavy - do not drop.
INSTALLATION
Figure 79: Burner Removal
LOG SET INSTALLATION:
Read the instructions below carefully and refer to the images. If the logs are broken do not use the unit until they are replaced. Broken logs can interfere with pilot operation.
Improper positioning of the logs may create carbon build-up and can alter the unit's performance which is not covered under warranty.
*Satin black paint is included if touch ups are required.
D
B
F
H
F
C
Regency L965E / HZ965E Gas Fireplace
A
Completed Install
E
G
47
Page 48
INSTALLATION
LOG SET INSTALLATION:
1) Place Log A on the Ceramic Log Burner as shown in Figure 86.
A
Figure 86: Log A
2) Identify locator on Log B as shown in Figure 87.
4) Identify locator on Log A as shown in Figure 89.
A
Figure 89: Log A Locator
5) Position Log C on Log A using Locator as shown in Figure 90.
B
Locator
Figure 87: Log B Locator
3) Line up Locator on Log B with Locator on Log A as shown in Figure 88.
B
A
Figure 88: Log B Position
C
A
Figure 90: Log C Position
6) Identify locator on Log D and opposing Locator on Log B as shown in
Figure 91. Place Log D gently on Log B.
D
B
48
Figure 91: Log D Locator
Regency L965E / HZ965E Gas Fireplace
Page 49
INSTALLATION
7) Identify locator on Log E and opposing Locator on the Ceramic Log
Burner as shown in Figure 94. Place Log E gently on Burner.
E
Figure 92: Log F Locator
8) Identify locator on Log F and opposing Locator on the Ceramic Log
Burner as shown in Figure 94. Place Log F gently on Burner.
F
10) Identify locator on Log H and opposing Locator on Log B as
shown in Figure 92. Place Log H gently on Log B.
B
H
Figure 96: Log H Locator
11) Log H in position.
Figure 93: Log F Locator
9) Identify locator on Log G and opposing Locator on the Ceramic Log
Burner as shown in Figure 94. Place Log G gently on Burner.
G
Figure 94: Log G Locator
F
G
H
Figure 97: Log H Position
Figure 95: Log F and G position
Regency L965E / HZ965E Gas Fireplace
49
Page 50
INSTALLATION
FULL SCREEN DOOR / SCREEN INSTALLATION
Both the full screen door and screen both install onto the front of the unit using two(2) tabs, one on each side. These tabs secure the front to the fi replace, allowing for easy removal for service access.
Install the front by lifting it parallel to the fi replace with the mounting bracket tabs pointing towards the fi replace. Slide the tabs all the way into the slots
between the Glass Door Frame and the drywall fl anges of the fi replace. Pull down on each corner to make sure the tab is engaged with the hanger.
IMPORTANT: Ensure that the minimum gap required between the Optional Front and wall of the unit is maintained (refer to Figure 99). Not maintain­ing the proper gap will cause the unit to run at elevated temperatures and result in an unsafe condition
The face should be cleaned before the fi replace is turned on for the fi rst time.
Figure 97: Location on unit to install Full Screen or Screen.
Figure 98: Line up Tabs with slot on Unit
Figure 96: Optional Front Installed.
The arched full screen door unit uses four(4) tabs, two on each side. These tabs secure the front to the fi replace, allowing for easy removal for service access. Note: There are three (3) slots on each tab 1/2" apar t to allow adjustment
depending on the thickness of the fi nishing material.
Arched Screen Doors
Figure 99: Optional Front
50
Installed.
Regency L965E / HZ965E Gas Fireplace
Page 51
FINISHING TRIM:
Finishing trim is supplied with the unit for use if the unit is installed up from fl oor level.
The trim will cover the gap between the unit and the non combustible materials.
INSTALLATION
Figure 100: Top View - exposed non combustible materials
1. Slide trim into position over exposed non combustible materials.
Non combustible
materials
Trim piece
Figure 102: Completed Trim install
Figure 101: Top View - Sliding trim into place
Regency L965E / HZ965E Gas Fireplace
51
Page 52
OPERATING INSTRUCTIONS
START-UP & OPERATION
NORMAL SOUNDS DURING OPERATION:
Table 1: Normal Sounds
Component Sound & Reason
Fascia Creaking when heating up or cooling down.
Burner Light pop or poof when turned off; this is more common with LP units.
Pilot Flame Quiet whisper while the pilot fl ame in on.
Gas Control Valve Dull click when turning on or off, this is the valve opening and closing.
REMOTE CONTROL OPERATIONS:
The Profl ame GTMFS is a modular remote control system that directs the functions of the L965E / HZ965E. The Profl ame GTMFS is confi gured to control the on/off main burner operation, its fl ame levels and provides on/off and Smart thermostatic control of the appliance. The system controls a remotely actuated 120V/60Hz power outlet, fan speed through six (6) levels and has a constantly powered 120V/60Hz power outlet.
WARNING
THE TRANSMITTER AND RECEIVER ARE RADIO FREQUENCE DEVICES. PLACING THE RECEIVER IN OR NEAR METAL MAY SEVERELY REDUCE THE SIGNAL RANGE.
ATTENTION!
- TURN “OFF” THE MAIN GAS SUPPLY OF THE APPLIANCE DURING INSTALLATION OR MAINTENANCE OF THE RECEIVER.
- PLACE THE RECEIVER’S 3 POSITION SLIDER SWITCH IN THE “OFF” POSITION DURING INSTALLATION OR MAINTENANCE.
- TURN “OFF” MAIN GAS SUPPLY TO THE APPLIANCE PRIOR TO REMOVING OR REINSERTING THE BATTERIES IN THE RECEIVER.
- DURING APPLIANCE INSTALLATION/MAINTENANCE OR IN CASE OF REMOTE CONTROL MALFUNCTION TURN OFF THE FAN CONTROL MODULE USING THE “ON/OFF” MAIN POWER SWITCH ON THE FRONT PANEL OF THE FCM.
TECHNICAL DATA
Transmitter (Remote Control): Supply voltage 4.5 V (three 1.5 V AAA batteries) Ambient temperature ratings 0 - 50 °C (32 - 122 °F)
Receiver: Supply voltage 6.0 V (four 1.5 V AA batteries)
Fan Control Module: Supply voltage/frequency: 120 V / 60 Hz Aux switched output: 120 V / 60 Hz / 2 A Fan speed output: 120 V / 60 Hz / 1 Art
SYSTEM DESCRIPTION:
The Profl ame Remote Control System consists of three (3) elements:
1. Profl ame Transmitter.
2. Profl ame Receiver and a wiring harness to connect the Receiver to the gas valve, stepper motor and Fan Control Module.
3. Profl ame Fan Control Module (FCM)
52
52
Regency L965E / HZ965E Gas Fireplace
Page 53
TRANSMITTER (Remote Control with LCD Display)
The Profl ame Transmitter uses a streamline design with a simple button layout and informative LCD display (Figure 99).
The Transmitter is powered by three (3) AAA type batteries. A Mode Key is provided to Index between the features and a Ther­mostat Key is used to turn on/off or index through Thermostat functions (Figure 103 & 104).
OPERATING INSTRUCTIONS
Figure 103: Profl ame Transmitter.
INSTALLATION
Figure 104: Profl ame Transmitter LCD Screen.
RECEIVER
The Profl ame Receiver (Figure 101) connects directly to the gas valve, stepper motor, DFC, and Fan Control Module with a wir ing harness. The Receiver is powered by 110 V and uses four (4) AA type batteries for backup. The Receiver accepts commands via radio frequency from the Transmitter to operate the appliance in accordance with the particular Profl ame system confi guration. The Receiver three (3) position slider switch can be set to one of three positions: ON (Manual Override), Remote (Remote control), or Off.
Figure 105: Profl ame Receiver.
FAN CONTROL MODULE
Fan Control Module (FCM) offers the added ability to control the fan speed through six (6) speeds, a remotely actuated 120V outlet and a constantly powered 120V outlet. The FCM provides DC power to the Receiver allowing the batteries to be used only when line power is interrupted or lost (see Figure 106).
Figure 106: Profl ame Fan Control Module.
Regency L965E / HZ965E Gas Fireplace
5353
Page 54
OPERATING INSTRUCTIONS
WALL MOUNTING THE RECEIVER:
The receiver can be placed inside a standard Junction type wall box either by itself or in combination with a light dimmer control. This installation can take place up to 8’ft (2.4m) from the appliance control valve.
1. Connect the wiring harness to the back of the Receiver.
2. Install the Receiver in the Junction box using the existing J box screws (Figure 59).
3. Insert the four (4) AA type batteries in the battery compartment with the correct polarity.
4. Place the slider into the cover plate.
5. Put the Receiver switch in the “OFF” position.
6. Make sure the Receiver and cover plate words “ON” and “UP” are on the same side.
7. Align the slider with the switch on the Receiver and couple the switch into the slider.
8. Align the screw holes.
9. Using the two (2) screws provided secure the cover plate to the Re­ceiver.
OPERATING PROCEDURE:
Initializing The System For The First Time
Figure 107: Wall Mounting the Receiver.
end of the paper clip into the hole marked “PRG” on the Receiver front cover.
The Receiver will “beep” three (3) times to indicate that it is ready to synchronize with a Transmitter. Install the three (3) AAA type batteries in the Transmitter battery bay, located on the base of the Transmitter. With the batteries already installed in the Transmitter, push the ‘ON’ button. The Receiver will “beep” four (4) times to indicate the Transmitter’s command is accepted and sets to the particular code of that Transmitter. The system is now initialized.
Install the four (4) AA batteries into the receiver battery bay. Note the polarity of the battery and insert into the battery bay as indicated on the Battery cover (+/-). Place the 3-position slider switch in the “Remote” position. Using the end of a paper clip, or other similar object, insert the
Temperature Indication Display
With the system in the “OFF” position, press the Thermostat Key and the Mode Key at the same time. Look at the LCD screen on the transmitter to verify that a °C or °F is visible to the right of the Room Temperature display.
Turn on the Appliance
Press the ON/OFF Key on the Transmitter. The Transmitter display will show all active Icons on the screen. A single “beep” from the Receiver will confi rm reception of the command and will commence to fi rst ignite the pilot light, followed by the main burner. This should take about 10 seconds to complete.
Turn off the Appliance
Press the ON/OFF Key on the Transmitter. The Transmitter LCD display will only show the room temperature and Icon (see Figure 61). A single “beep” from the Receiver confi rms reception of the command and both the pilot light (if the unit is not set to continuous pilot) and main burner will turn off.
Room Thermostat (Transmitter Operation)
The Remote Control can operate as a room thermostat. The thermostat can be set to a desired temperature to control the comfort level in a room. To activate this function, press the Thermostat Key. The LCD display on the Transmitter will change to show that the room thermostat is “ON” and the set temperature is now displayed . To adjust the set temperature, press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD screen of the Transmitter.
Figure 108: Remote Control Display in Fahrenheit and Celsius.
54
54
Regency L965E / HZ965E Gas Fireplace
Page 55
OPERATING INSTRUCTIONS
INSTALLATION
SMART THERMOSTAT (TRANSMITTER OPERATION)
The Smart Thermostat function adjusts the fl ame height in accordance to the difference between the set point temperature and the actual room temperatures. As the room temperature gets closer to the set point the Smart Function will modulate the fl ame down. To activate this function, press the Thermostat Key (until the word “SMART” appears to the right of the temperature bulb graphic (Figure 106). To adjust the set temperature, press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD screen of the Transmitter.
REMOTE FLAME CONTROL
The Profl ame GTMFS has six (6) fl ame levels. With the system on, and the fl ame level at the maximum in the appliance, pressing the Down Arrow Key once will reduce the fl ame height by one step until the fl ame is turned off. The Up Arrow Key will increase the fl ame height each time it is pressed. If the Up Arrow Key is pressed while the system is on but the fl ame is off, the fl ame will come on in the high position (refer to Figure 107). A single “beep” will confi rm reception of the command.
Figure 109: Remote Control Displays Set
Temperature.
REMOTE ACTUATED ACCENT LIGHTS
The L965E is shipped with two (2) fi rebox accent lights. They are connected to the auxiliary power outlet of the Profl ame Fan Control Module. The lights can be turned on or off using the Auxiliary function on your remote control. Press the Mode Key on the remote control until the Auxiliary Function icon is highlighted. Pressing the Up or Down arrow keys will turn the accent lights on or off. A single “beep” will confi rm the reception of the command
Figure 110: Remote Control’s Smart Flame Function.
Regency L965E / HZ965E Gas Fireplace
Figure 111: Remote Control’s Flame Levels.
5555
Page 56
OPERATING INSTRUCTIONS
KEY LOCK
This function will lock the keys to avoid unsupervised operation. To activate this function, press the MODE and UP keys at the same time and the a lock will appear (see Figure 109). To de­activate this function, press the MODE and UP Keys at the same time.
LOW BATTERY POWER DETECTION
Transmitter: The life span of the remote control batteries
depends on various factors: quality of the batteries used, the number of ignitions of the appliance, the number of changes to the room thermostat set point, etc. When the Transmitter batteries are low, a Battery Icon will appear on the LCD display of the Transmitter (see Figure110) before all battery power is lost. When the batteries are replaced this Icon will disappear.
Receiver: The life span of the Receiver batteries depends on
various factors: quality of the batteries used, the number of ignitions of the appliance, the number of changes to the room thermostat set point, etc. When the Receiver batteries are low, No “beep” will be emitted from the Receiver when it receives an On/Off command from the Transmitter. This is an alert for a low battery condition for the Receiver. When the batteries are replaced the “beep” will be emitted from the Receiver when the ON/OFF Key is pressed (See
The System For The First Time
).
Initializing
Figure 112: Remote Control with Aux for Accent Lights.
Figure 113: Remote Control
Locked.
Figure 114: Low Battery Indicator.
MANUAL BYPASS OF THE REMOTE SYSTEM
If the batteries of the Receiver or Transmitter are low or depleted, the appliance can be turned on manually by sliding the three position slider switch on the Receiver to the ON position. This will bypass the remote control feature of the system and the appliance main burner will come on.
SPLIT VALVE OPERATION
The split fl ow operation on the L965E/ HZ965E turns off the rear section of the burner, greatly reducing the heat output of the unit. If you’d like to have the fi replace on but would not like to have as much heat in the room, you can turn off this function. Press the bottom key of your remote repeatedly until the double fl ame icon is lit up (refer to Figure 115). By pressing the up or down key, turn the rear split valve to “on” or “off”. The rear fl ame on the burner will turn on and off. This does not affect the fl ame setting of the remaining fl ame. Turning off the rear section of this burner may result in an extinguishing “pop”, particularly if your fi replace is operating on propane gas
Figure 115: Split Valve Indicator.
WARNING: Fire Hazard. Can cause severe injury or death The Receiver causes ignition of the appliance. The appliance can turn on suddenly. Keep away from the appliance burner when operating the remote system or activating manual by pass of the remote system.
WARNING: Shock Hazard. Can cause severe injury or death. This device is powered by line voltage. Do Do not try to repair this device. In no way is the enclosure to be tampered with or opened. Disconnect from line voltage before performing any maintenance.
WARNING: Devices rated more than 5A shall not be connected to the OUT receptacle. Devices rated more than 1A shall not be connected to the FAN receptacle. Devices rated more than 2A shall not be connected to the AUX receptacle.
CAUTION: Property Damage Hazard. Excessive heat can cause property damage. The appliance can stay lit for many hours. Turn off the appliance if it is not going to be attended for any length of time. Always place the Transmitter where children cannot reach it.
56
56
Regency L965E / HZ965E Gas Fireplace
Page 57
OPERATING INSTRUCTIONS
INSTALLATION
AIR SHUTTER ADJUSTMENT:
The L965E/ HZ965E is setup to work with two (2) gas orifi ces. The orifi ce on the left (looking from the front) feeds the front burner while the right feeds the rear burner, which can also be switched off using the remote control. Each orifi ce has its own Air Shutter. The Air Shutter is connected to an Adjustment Lever that is accessible from the front and bottom of the fi rebox. These Air Shutters can be adjusted during the operation of the fi replace. This Figure 68 shows the fi replace with the door and the burners removed. This is to better show the Air Shutters and the Adjustment Levers. The Door/Air Shutter Tool (see Figure 116) has a small slots on one end. These slots can be used to engage the vertical section of the adjustment lever to move the klever forward or rearward. Moving the Lever towards you opens the Air Shutter, while moving it rearward, closes the Air Shutter. Air shutters should be adjusted so that the gas fl ame burns with a blue base and a bright yellow upper section. Air shutters set to closed will lead to a dirty fl ame which may lead to soot gathering on the logs and/or glass panel. Properly set Air Shutters will result in a very blue fl ame for the fi rst fi fteen (15) minutes of operations with the fl ame becoming more yellow as the unit comes up to operating temperature.
Table 2: Air Shutter Settings.
Left Right
Glass / Media Burner
LP Open Open
NG Open Open
Log Set/ Ember Bed Burner
Figure 116: Air Shutter Adjustment.
LP Open 1/8” (3mm) Open
NG Open 1/16” (2mm) Open
DIAGNOSTIC FLASH CODES:
1. Fail to ignite: If there is no positive ignition, the board will go into lock out and the LED will blink 3 times in intervals until the system is reset.
2. Low battery condition (<4V): the LED indicator will blink one (1) time in intervals.
3. Parasitic Pilot Flame: the LED indicator will blink two (2) times in intervals.
4. System Lock out: the LED indicator will blink three (3) times in intervals.
Additional Ignition Information
1. The Profl ame DFC Board will try two (2) times for ignition.
2. Each try for ignition will last approximately 60 seconds.
3. The wait time between the two tries is approximately 35 seconds.
Regency L965E / HZ965E Gas Fireplace
5757
Page 58
MAINTENANCE
WIRING HARNESS
58
Caution: Label all wires
prior to disconnection when servicing controls, Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Regency L965E / HZ965E Gas Fireplace
Page 59
LIGHTING INSTRUCTION LABEL:
MAINTENANCE
CAUTION:
CAUTION: Do not operate this fireplace with the glass removed, cracked or broken.
Replacement of the panel(s) should be done by a licensed or qualified person! This appliance needs fresh air for safe operation and must be installed with provisions for combustion and ventilation air. See installation and operating instructions manual. Keep burner and control compartment clean.
WARNING: Improper installation, adjustment, alteration, service or maintenance can
cause injury or property damage, or loss of life. Refer to owner's manual provided with this appliance. See installation and operating instructions accompanying appliance. Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
WARNING:
MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
A) This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.
B) BEFORE LIGHTING smell all around the appliance area for gas and next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS: Do not try to light any appliance. Do not touch any electrical switch: do not use any phone in your building. Immediately call your gas supplier from a neighbors' phone. Follow the gas suppliers instructions. If you cannot reach your gas supplier, call the fire department.
1. STOP! Read the safety information above on this label.
2. Read the owner's manual including the section on "Remote Control" operation.
3. Do not attempt to light the pilot by hand.
4. If you smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step.
5. Using the remote control, set thermostat to desired setting, or switch press the ON/OFF key on the remote. "ON" will be indicated on the display of the remote and an audible "beep" will be heard at the unit to idicate the command has been received.
Hot while operating. Do not touch. Severe burns may result. Keep children, clothing, furniture, gasoline or other flammable vapors away.
FOR YOUR SAFETY READ BEFORE OPERATING
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION
OPERATING INSTRUCTIONS
C) If any portion of this appliance does not operate as the instructions indicate, don't try to repair it, call a qualified service technician. Do not use tools. Force or attempted repair may result in a fire or explosion.
D) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
6. This appliance is equipped with a completely automatic ignition and lighting control. The control will attempt to light the pilot several timesif necessary. If it is unsuccessful, it will discontinue operations. If the appliance does not operate, follow the instructions "To Turn Off Gas To Appliance" and call your service technician or gas supplier.
Blue LCD Display
ON/OFF Key
THERMOSTAT Key
UP/DOWN Arrow Key
MODE Key
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat to lowest setting, or press the ON/OFF Key. "OFF" will be indicated on the display and an audible "Beep" will be heard at the unit to indicate the command has been received.
C-11800
Figure 117 Lighting Label.
AIR INTAKE
:
If for any reason, during the life of this appliance, any portion of the fresh air intake system including the vent termination, vent components or any portion of the air intake that transfers fresh combustion air from the starter collar on the top of the unit to the air intake at the bottom rear of the fi rebox is disassembled, it must be re-assembled as instructed in the installation portion of the manual. All air intake components must be re-sealed using high temperature sealant or ceramic gaskets as provided by the manufacturer or as shown in the vent installation area of the manual. This process should be completed by a qualifi ed hearth installation technician. Periodic examination of venting systems should be done by a qualifi ed agency.
Regency L965E / HZ965E Gas Fireplace
59
Page 60
MAINTENANCE
LIGHT BULB REPLACEMENT
The L965 comes with 2 accent lights in the rear of the fi replace. These are halogen lights that will need replacing from time to time, depending on use. They can be purchased from most hardware stores or speciality lighting stores. The bulb specifi cations are:
Halogen bulb 120V 50W GY6.36 (lower wattages may be used).
Before replacing the light bulbs, let the unit cool completely to room temperature. In order to replace this bulb, you need to remove the fi replace door, logs, burners and fi rebox liners. See each specifi c section in this manual for instructions on how to remove these components. The light is situated in a light cover that is located on the back wall of the fi rebox. To remove the light cover, lift the cover about ½” and pull towards you. Lift the old bulb from the socket and replace it with the new bulb. It’s best not to contact the bulb with your hands. Oils from your skin will diminish the bulbs life. Use paper or the wrapper that the bulb comes in to keep from touching the bulb. If you prefer, the bulb can be replaced with a lower wattage if you’d like to reduce the bulbs effects in the fi rebox. Re-assemble the various components in the reverse order. Ensure the light covers are replaced prior to operating the appliance.
CLEANING / ANNUAL SERVICE:
The
965/HZ965 cleaning, battery replacement, light replacement, venting inspection and inspection of the burner, log sets and fi rebox liners. The venting systems should be periodically examined by a qualifi ed agency.
CLEANING THE GLASS:
When the fi replace has cooled, remove the face of the fi replace along with the glass. See MAINTENANCE
ND SERVICE - GLASS DOOR REMOVAL. Check the gasket material on the back of the glass, making sure that
A it is attached and intact. During a cold start up, condensation will sometimes form on the glass. This is a normal condition with all fi replaces. However, this condensation can allow dust and lint to cling to the glass surface. Initial paint curing of the appliance can leave a slight fi lm behind the glass, a temporary problem. The glass will need cleaning about two weeks after installation. Use a mild glass cleaner and a soft cloth; abrasive cleaners will damage the glass and plated surfaces. Depending on the amount of use, the glass should require cleaning no more than two or three times a season. Do not clean the glass when it is hot.
REPLACING GLASS:
The glass in the fi replace is a high temperature ceramic. If the glass is damaged in any way, a factory replacement is required (see PARTS LIST - COMPONENTS). Wear gloves when handling damaged glass door assembly to prevent personal injury. When the glass door assembly is being transported, it must be wrapped in newsprint and tape and/or a strong plastic bag. Do not operate with the glass front removed, cracked or broken. Removal and replacement of the glass from the door must be done by a licensed or qualifi ed service person. The glass must be purchased from an authorized Regency dealer, part #50-2002.
No substitute materials are allowed.
will require maintenance, which can usually be planned on an annual basis. Service should include
Figure 118: Replacing Light Bulb.
BURNER & FIREBOX CLEANING:
The fl ow of combustion and ventilation air not to be obstructed. Periodic maintenance should include cleaning of the fi rebox, burner and log effects. Refer
to the sections on glass door removal, log and or burner installation to remove the glass door, log set (if equipped), burner trim pieces and burners. Using a vacuum with a soft brush attachment, clean out any dust, lint or debris from the fl oor of the fi rebox. Using a soft brush, gently remove any dirt or debris from the top surface of the burner. Using the same brush, gently brush away any carbon deposits that have built up on the surface of the logs. Re-install all of these components as shown in the setup / installation portion of this guide. Clean both surfaces of the window glass using commercial glass cleaner and clean soft cloths. Securely re-install the glass door onto the fi replace.
60
Regency L965E / HZ965E Gas Fireplace
Page 61
TROUBLESHOOTING
Problem Possible Cause Solution
Thermostat does not work
The pilot fl ame has gone out
The On/Off switch is turn to OFF
The thermostat is set too high · Set the thermostat to a lower temperature
· Turn it ON
· Check pilot assembly wiring
MAINTENANCE
No spark generation
No pilot fl ame ignition
Pilot will not remain lit
Spark develops near the pilot assembly or could occur onboard
No spark from the igniter
Air in the gas line
Pilot gas pressure dropout upon main burner gas valve opening
No gas fl ow out of the pilot burner
Problem with Flame Sensor circuit
· Check for broken or poor connection from the sparker to the electrode
· Check for the spark shorting or arcing at other locations
· Check for defective sparker and spark electrode
· See “no spark generation”
· It takes a while for all the air to purge out of the pilot before gas can reach the pilot and ignite
· Check gas mains supply and pressure
· Check gas valve wirings and connections to the board
· Check the pilot burner for obstruction
· Check the wirings and connections between the pilot assembly and the board
· Check the correct gas type settings on the valve and pilot burner assembly orifi ce
· Check for proper connection of the Flame Sensor to the DFC board
· Check pilot for full fl ame impingement around Flame Sensor
· If fl ame is too small, check gas pressure, adjust pilot rate screw, check pilot head for damage
· Ensure the ground wire is properly attached to the pilot mounting bracket
and that it is makes a good electrical connection.
Restrictor setting
The pilot light has gone out
Remote control does not work
No reaction to command
Regency L965E / HZ965E Gas Fireplace
The remote is too far away from the heater
The remote control receiver is turned “OFF”
One of the two remote control or receiver batteries are dead
Receiver or transmitter batteries are low
A maximum number of failed ignitions or fl ame restorations have been reached.
No communication between the remote control and the receiver
· Use the correct restrictor setting for the venting confi guration
· See “Pilot will not remain lit”
· Use the remote closer to the heater
· Check the remote control instructions
· Replace the batteries
· Replace the batteries
· Remove any possible blocking conditions. See “locking conditions”
· See how to reset the board from Lockout
· Reprogram the transmitter to the receiver.
· Follow the initializing system for the fi rst time
61
Page 62
MAINTENANCE
TROUBLESHOOTING
Problem Possible Cause Solution
Locking conditions
Main burners will not start
Reset the Profl ame DFC board
The pilot fl ame has gone out · See “Pilot will not remain lit”
The remote control is not working correctly · Replace the batteries
The thermostat is disconnected or set too high
Problem with thermopile circuit
· Turn the system off by pressing the ON/OFF button on the transmitter
· After approximately 2 seconds press the ON/OFF button on the transmitter again.
· In the manual fl ame control mode, use the down arrow button to reduce the fl ame to off, indicated by the word OFF displayed on the transmitter LCD screen.
· Wait approximately 2 seconds and press the up arrow button, the ignition sequence will start.
· With the transmitter off, move the slider switch on the receiver to the OFF position.
· Wait approximately 2 seconds and move the receiver slider switch to the ON position.
· Set the thermostat to a lower temperature
· Check gas line pressure
· Check wiring to thermostat for breaks
· Check for fl ame impingement on thermopile
Flame lifting
Blue Flames
Glass fogs up
Flames are burning “dirty” or sooting
Leak in vent pipe · Check for leaks in vent connections
Improper vent confi guration · Check vent confi guration with manual
· Check to see if terminal is on correctly
Terminal may be re-circulating fl ue gases
The heater has just been started · Normal during start up: fl ame will yellow as the fi replace heats up
Improper air shutter adjustment · Adjust air shutter – contact your dealer
Normal condition: after the appliance warms up the glass will be clear.
The logs or glasses are placed incorrectly
Improper air shutter adjustment
Incorrect rating input · Check manifold pressure and clock input rating for over-fi ring
· May need to install high wind termination cap.
· Contact dealer
**Due to additives in gas, glass may get hazy during operation** Clean as needed.
· Check log positioning
· Check level of glasses layout
· Increase primary air by opening the air shutter and/or by opening the
vent restrictor
· Check for proper venting and blockage of the vent termination
· See also “Burners will not remain lit”
62
Regency L965E / HZ965E Gas Fireplace
Page 63
INSTALLATION
APPENDIX A - OPTIONAL REDUCED CEILING HEIGHT INSTALLATION
The L965E/HZ965E can be installed with the reduced ceiling height as shown in this diagram. If you are limited by ceiling heights, particularly when installing a raised hearth, you can install the unit observing the clearances outline in this diagram. The main difference is the install depth is changed to 26½” (673mm) to compensate for the reduced vertical clearances. The width and framing dimensions remain unchanged to the regular installations shown earlier in this manual.
44-3/4" (1137mm)
**52-5/16" (1329mm)
Regency L965E / HZ965E Gas Fireplace
63
Page 64
PARTS LIST
64
Regency L965E / HZ965E Gas Fireplace
Page 65
PARTS LIST
Item Part Description
1 706-010 Glass Door Assembly
2 706-009 Door Tool
3 706-908 Panel Set - Porcelain
5 706-902 Brick Panel Set - Old town red
706-904 Brick Panel Set - Castlestone
706-905 Brick Panel Set - Ledgestone
7 706-525 Burner - Glass
8 706-530 Burner - Log / Ember Bed
9 706-930 Log Set
10 946-775 Glass Crystals - Black
946-776 Glass Crystals - Copper
946-777 Glass Crystals - Starfi re
946-778 Glass Crystals - Blue
12 50-1978 Refractory Burner Trim Black
13 706-574/P Valve Assembly - NG
706-576/P Valve Assembly - LP
911-084 Valve Only NG
911-085 Valve Only LP
14 911-030 Fan Controller Module
15 911-012 IPI Burner Controller
16 911-016 Remote Receiver
17 706-021 Transmitter
18 911-032 Wire Harness - Receiver
19 911-013 Wire Harness - IPI
20 911-006 Pilot Assembly - NG
911-007 Pilot Assembly - LP
22 706-026 Vent Restrictor Set
27 706-921
28 706-922
30 706-929
31 706-940
Regency Heat Distribution Kit
Power Vent Kit
Mesh Guard
Full Screen Doors
Item Part Description
36 706-969
37 706-968
38 910-100
39 910-101
910-432
706-005
911-037 Pilot Flame Sensor (Long Ceramic)
706-007
706-008
919-088 Manual
706-028
706-029
706-032
706-039
911-038
706-003
706-059
706-060
706-061
706-062
946-693
946-694
LPG Conversion Kit
NG Conversion Kit
Pilot Orifi ce (Injector) NG Threaded
Pilot Orifi ce (Injector) LP Threaded
Sit Pilot Tube W/end Ferules - 1 Pc
Light Bulbs Set Of 2 Part
Pilot Bypass Switch
Valve Access Panel Gasket
Halogen socket/bulb/wire
Main Orifi ce Tray Gasket
Light Bulb Cover (Specify Colour)
Door Gasket (20ft)
Spark Electrode W/ignitor Cable
Halogen Cycle (Pin Socket)
#55 Burner orifi ce - LP
#53 Burner orifi ce - LP
#45 Burner orifi ce - NG
#41 Burner orfi ce - NG
Stepper Motor - NG
Stepper Motor - LP
Regency L965E / HZ965E Gas Fireplace
65
Page 66
WARRANTY
Regency Fireplace Products is the manufacturer of the Regency line of heating products. At Regency, our commitment to the highest level of quality and customer service is the most important thing we do. Each Regency stove is built on a tradition of using only the fi nest materials and is backed by our Exclusive Lifetime Limited Warranty to the original purchaser. With Regency, you’re not just buying a fi replace or stove, you’re buying a company with years of unequalled performance and quality.
Limited Lifetime Warranty:
Under this warranty, Regency Fireplace Products covers the fi replace or stove body and accessories against defects in materials and workmanship, for part repair or replacement for seven (7) years and subsidized* labour for the fi rst three (3) years to the original purchaser. This Warranty covers: Firebox, Heat Exchanger, Steel Firebox Panels, Ceramic Logs & Panels, Burner, Ceramic Glass, Pedestals, Panels and Legs. Please see the exclusions and limitation section below as certain restrictions and exclusions apply to this warranty.
Limited Two (2) Year Warranty:
Under this warranty, Regency Fireplace Products covers: Gas Assembly, Pilot Assemblies, Flame Sensors, Flame Electrodes, Blower, Blower Control, Temperature Sensors, Remote Controls and Wire Harness against defects in materials and workmanship, for part repair or replacement for the fi rst two (2) years and subsidized* labour for the fi rst one (1) year to the original purchaser. Please see the exclusions and limitation section below as certain restrictions and exclusions apply to this warranty. *Subsidized according to job scale as predetermined by Regency.
To the Dealer
When fi lling out a warranty claim, please complete the following information on an offi cial warranty claim form: Customer information: Name, address and telephone number of purchaser and date of purchase. Dealer information: Date of installation, name of installer and dealer, serial number of the appliance, nature of complaint, defects or malfunction, description and part numbers of any parts replaced.
To the Distributor
Sign and verify that work and information are correct.
Exclusions and Limitations:
1. This Warranty does not cover tarnish, discoloration or wear on the plating or paint.
2. This Warranty excludes wear and tear or breakage caused by cleaning, moving or service on log set and panels.
3. A qualifi ed installer must install this stove or fi replace. This Limited Warranty covers defects in materials and workmanship only if the product has been installed in accordance with local building and fi re codes; in their absence, refer to the owner’s manual. If the product is damaged or broken as a result of any alteration, wilful abuse, mishandling, accident, neglect, or misuse of the product, the Limited Warranty does not apply.
4. The stove must be operated and maintained at all times in accordance with the instructions in the Owner’s Manual. If the unit shows signs of neglect or misuse, it is not covered under the terms of this Warranty policy. Performance problems due to operator error will not be covered by the Limited Warranty policy.
5. As this is a heating appliance, some changes in colour of surface fi nishes may occur. This is not a fl aw and as such is not covered under this warranty.
6. Some minor expansion, contraction, or movement of certain parts and resulting noise, is normal and not a defect and, therefore, is not covered under this Limited Warranty.
7. Misuse includes over-fi ring. Over-fi ring this appliance can cause serious damage and will nullify the Limited Warranty.
8. The Limited Warranty will cover glass thermal breakage only and will not cover misuse of the stove glass, including but not limited to glass that is struck, has surface contaminates or has had harsh or abrasive cleaners used on it.
9. This warranty does not cover products made or provided by other manufacturers and used in conjunction with the operation of this stove without prior authorization from Regency Fireplace Products The use of such products may nullify the Limited Warranty on this stove. If unsure as to the extent of this Limited Warranty, contact your authorized Regency dealer before installation.
10. Regency Fireplace Products will not be responsible for inadequate performance caused by environmental conditions.
11. The Limited Warranty does not cover installation and operational related problems caused by downdrafts or spillage
caused by environmental conditions. Environmental conditions include but are not limited to nearby trees, buildings, roof tops, wind, hills, mountains, inadequate venting or ventilation, excessive offsets, negative air pressures or other infl uences caused by mechanical systems such as furnaces, fans, clothes dryers etc.
66
Regency L965E / HZ965E Gas Fireplace
Page 67
WARRANTY
12. The Limited Warranty is void if: a) The stove has been operated in atmospheres contaminated by chlorine, fl uorine or other damaging chemicals. b) The stove is subject to submersion in water or prolonged periods of dampness or condensation. c) Any damage to the unit, combustion chamber or other components due to water, or weather damage which is the
result of, but not limited to, improper chimney/venting installation.
c) Salt air in coastal areas or high humidity can be corrosive to the fi nish; these environments can cause rusting.
Damage caused by salt air or high humidity is not covered by the Limited Warranty.
13. Exclusions to the Limited Warranty include: injury, loss of use, damage, failure to function due to accident, negligence, misuse, improper installation, alteration or adjustment of the manufacturer’s settings of components, lack of proper and regular maintenance, alteration, or act of God.
14. The Limited Warranty does not cover damage caused to the fi replace or stove while in transit. If this occurs, do not operate the stove and contact your courier and/or dealer.
15. Limited Warranty does not extend to or include fi rebox paint, door or glass gaskets with damage caused by normal wear and tear, or exterior paint discoloration or chipping, worn gaskets, etc.
16. The Limited Warranty does not include damage to the unit caused by abuse, improper installation, or modifi cation of the unit.
17. Damage to plated surfaces caused by fi ngerprints, scratches, melted items, or other external scores and residues left on the plated surfaces from the use of abrasive cleaners or polishes is not covered in this warranty.
18. The Limited Warranty does not cover tarnish, discoloration or wear on the plated surfaces.
19. The paint on the Metal Brick Liner may peel. This is due to the extreme conditions applied to the paint during normal usage. It is not a fl aw and is not covered under warranty.
20. Regency Fireplace Products is free of liability for any damages caused by the fi replace or stove, as well as inconvenience expenses and materials. The Limited Warranty does not cover incidental or consequential damages.
21. The Limited Warranty does not cover any loss or damage incurred by the use or removal of any component or apparatus to or from the Regency fi replace or stove without the express written permission of Regency Fireplace Products and bearing a Regency Fireplace Products label of approval.
22. Any statement or representation of Regency products and their performance contained in Regency advertising, packaging literature, or printed material is not part of the Limited Warranty.
23. The Limited Warranty is automatically voided if the fi replace or stove’s serial number has been removed or altered in any way. If the stove is used for commercial purposes, it is excluded from the Limited Warranty.
24. No dealer, distributor, or similar person has the authority to represent or warrant Regency products beyond the terms contained within the Limited Warranty. Regency Fireplace Products assumes no liability for such warranties or representations.
25. Regency Fireplace Products will not cover the cost of the removal or re-installation of the stove, hearth, facing, mantels, venting or other components.
26. Subsidized labour to replace or repair items under this Limited Warranty will be covered per our warranty service fee reimbursement schedule. Labour rates are set per component and as such total labour costs may not be covered.
27. Regency Fireplace Products is not liable for freight or labour on any stove replaced in-fi eld and is not liable for travel costs for service work. In the event of in-home repair work, the customer will pay any in-home travel fees or service charges required by the Authorized Dealer.
28. At no time will Regency Fireplace Products be liable for any consequential damages which exceed the purchase price of the unit. Regency Fireplace Products has no obligation to enhance or modify any stove once manufactured (example: as a stove evolves, fi eld modifi cations or upgrades will not be performed).
29. This Limited Warranty is applicable only to the original purchaser and it is non-transferable.
30. This warranty only covers Regency products that are purchased through an authorized Regency dealer.
31. If for any reason any section of the Limited Warranty is declared invalid, the balance of the warranty remains in effect and all other clauses shall remain in effect.
32. The Limited Warranty is the only warranty supplied by Regency Fireplace Products, the manufacturer of the stove. All other warranties, whether expressed or implied, are hereby expressly disclaimed and purchaser’s recourse is expressly limited to the Limited Warranty.
33. Regency Fireplace Products and its employees or representatives will not assume any damages, either directly or indirectly, caused by improper usage, operation, installation, servicing or maintenance of this stove.
34. Regency Fireplace Products reserves the right to make changes without notice. Please complete and mail the warranty registration card and have the installer fi ll in the installation data sheet in the back of the manual for warranty and future reference.
35. Regency Fireplace Products is responsible for stocking parts for a maximum of seven (7) years after discontinuing the manufacture or incorporation of the item into its products. An exception to this would be if an OEM supplier is not able to supply a part.
Regency L965E / HZ965E Gas Fireplace
67
Page 68
Register your Regency® warranty online
www.regency-fi re.com
Reasons to register your product online today!
• View and modify a list of all your registered products.
• Request automatic email notifi cation of new product updates.
• Stay informed about the current promotions, events, and special
offers on related products.
Installer: Please complete the following information
Dealer Name & Address: ___________________________________
________________________________________________________
Installer: ________________________________________________
Phone #: ________________________________________________
Date Installed: ___________________________________________
Serial No.: _______________________________________________