WARNING:
If the information in these instructions are not followed exactly,
a fi re or explosion may result causing property damage,
personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed
installer, service agency or the gas supplier.
919-271
Tested by:
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
Installer
Homeowner: Please keep these instructions for future reference.
: Please complete the details on the back cover
and leave this manual with the homeowner.
www.regency-fi re.com
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
08/19/13
Page 2
MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
®
This Regency
standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88-2009 / CSA 2.33-2009 and GAS-FIRED APPLIANCES FOR
USE AT HIGH ALTITUDES CAN / CGA 2.17-M91.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home,
where not prohibited by local codes.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria
for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home
Standard in Canada.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence
of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA
70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1
in Canada.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as
applicable to local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the
National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
product has been tested and listed by Warnock Hersey/Intertek as a Direct Vent Wall Furnace to the following
This appliance can only be used with the type of gas indicated on the rating plate.
This appliance is not convertible for use with other gases.
Ensure that structural members are not cut or weakened during installation.
This appliance may be installed as an OEM installation in a manufactured home (USA only) or mobile home and must be
installed in accordance with the manufacturer's instruction and the Manufactured Home Construction and Safety Standard,
Title 24 CFR, Part 3280, in the Untied States, or the Standard for Installation in Mobile Homes, CAN/CSA Z240 MH, in
Canada.
2
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 3
To the New Owner:
Congratulations!
You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The HZ40E has been
designed to provide you with all the warmth and charm of a fi replace at the fl ick of a switch. The
model HZ40E has been approved by Warnock Hersey/Intertek for both safety and effi ciency . As
it also bears our own mark, it promises to provide you with economy, comfort and security for
many trouble free years to follow. Please take a moment now to acquaint yourself with these
instructions and the many features of your Regency
®
Fireplace.
Regency Horizon Gas Inserts Video
Regency Horizon™ HZ40E-2 Gas Fireplace
3
Page 4
TABLE OF CONTENTS
SAFETY DECAL
Copy of Safety Decal .....................................................5
REQUIREMENTS
MA Code - CO Detector.................................................6
INSTALLATION
Important Message ......................................................8
Before You Start ............................................................8
General Safety Information............................................8
The Warranty: Limited Lifetime ...................................67
4
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 5
SAFETY LABEL
This is a copy of the label that accompanies
each HZ40E-NG2 and HZ40E-LP2 Direct Vent
Gas Fireplace. We have printed a copy of the
contents here for your review.
®
NOTE: Regency
improved. Check the label on the unit and if
there is a difference, the label on the unit is the
correct one.
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1.
This appliancemust be installed inaccordance with theStandard CAN/CSAZ240 MH, MobileHousing, in Canada,or with the ManufacturedHome Construction andSafety Standard,Title 24 CFR,Part 3280,in
the UnitedStates, orwhen such astandard isnot applicable,ANSI/NCSBCS A225.1/NFPA 501A, ManufacturedHome InstallationsStandard orANSIA119.2ou NFPA501C Standardfor Recreational Vehicles
This applianceis only foruse with the typeof gas indicatedon the ratingplate and may beinstalled inan aftermarket, permanentlylocated, manufactured (mobile) homewhere not prohibitedby local codes.See
owner's manualfor details.This appliance isnot convertiblefor use withother gases,unless a certifiedkit isused.
Installer l'appareilselon lescodes ou règlementslocaux, ou,en l'absence detels règlements,selon lescodes d'installationANSI Z223.1,National Fuel GasCode ouCSA-B149.1 envigueur.
Installer l'appareil selon la norme CAN/CSA-Z240, Série MM, Maison mobiles ou CAN/CSA-Z240 VC, Véhicules de camping, ou la norme 24 CFR Part 3280, Manufactured Home Construction and Safety
Standard. Si cesnormes ne sont pas pertinentes,utilisez la normeANSI/NCSBCS A225.1/NFPA501A, Manufactured Home InstallationsStandard, ouANSI A119.2 ou NFPA501C Standard for Recreational
Vehicles.
Cet appareildoit être utilize uniquement avecle type de gaz indiqué surla plaque signalétique. Cetappareil peut être installédans une maison préfabriquée ou mobile(É.-U. seulement) installée àdemeure si
les règlementslocaux lepermettent. Voirla notice del'utilisateur pourplus de renseignements.Cet appareiln'est pasconvertible pourune utilisation avecd'autres gaz,sauf siune troussecertifié est utilisé.
This ventedgas fireplaceheater is notfor usewith air filters.Ne pasutiliser defiltre à airavec cefoyer au gazà évacuation.
FOR USEWITH GLASSDOORS CERTIFIED WITHTHE APPLIANCEONLY
Fan (Part # 256-917)
Electrical supply / Électrique 115VAC, 1.13 A, 60Hz.
NOT FOR USE WITH SOLID FUELS. /
units are constantly being
COPY OF SAFETY DECAL
Listed:
VENTED GAS FIREPLACE HEATER /
Certified for/Certifi e pour:
Tested to:
ANSI Z21.88-2009/CSA 2.33-2009
MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE.
APPAREIL FONCTIONNANT AU NATURAL GAS
CONCU POUR ETRE POELE: Mod le HZ40E-NG2
Pression d'allimentation minimum
Pression à la tubulure d' chappement lev e
Grandeur de l'injecteur
D bitmaximum selon
Calorifique
é
l'altitude
ÉÉ
QUIP A L'UISINE POUR GAZ PROPANE
CONCU POUR ETRE POELE: Mod le HZ40E-LP2
Pression d'allimentation minimum
Pression à la tubulure d' chappement lev e
Grandeur de l'injecteur
D bitmaximum selon
Calorifique
é
l'altitude
ééé
ééé
POUR UTILISATION UNIQUEMENTAVECLES PORTES ENVERRE CERTIFIÉESAVEC L'APPAREIL
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
Serial No./ No de serie
412
Minimum Clearances to Combustibles /
é
é
FPI Fireplace Products International Ltd. Delta, BC, Canada
Degagement Minimum De Materiaux Combustibles
Side Walls
A8” (203mm)
B
D
C
DOOR SEAL: Please
check that the door is
A
E
properly sealed
Ceiling
F
B 22” (559mm)
Min. Mantel Height
C17" (432mm)
Max. Mantel Depth
D13” (330mm)
Alcove Width
E84" (1524mm)
Alcove Depth
F36" (2134mm)
(See Instruction Manual for
detailed instructions)
Made in Canada/ Fabrique au Canada
919-270
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfi tter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, fl exible con-
nectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appliances individual manual shut-off must be a
t-handle type valve.
The State of Massachusetts requires the
installation of a carbon monoxide alarm in
accordance with NFPA 720 and a CO alarm
with battery back up in the same room where
the gas appliance is installed.
Regency Horizon™ HZ40E-2 Gas Fireplace
5
Page 6
REQUIREMENTS
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
MA Code - CO Detector
(for the State of Massachusetts only)
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
6
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 7
49-5/16"
45-5/8"
39-13/16"
DIMENSIONS
18-5/16"
16-1/2"1-7/16"
(318mm)
1
36
"
1
4
13
"
4
42"
16-7/8"
33-3/16"
31"
10"
(1092mm)
(972mm)
(1238mm)
(902mm)
(388mm)
4
1
15
(522mm)
(600mm)
(327mm)
(914mm)
Regency Horizon™ HZ40E-2 Gas Fireplace
7
Page 8
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The Gas Fireplace must be installed in accordance
with these instructions. Carefully read all the
instructions in this manual fi rst. Consult the "authority
having jurisdiction" to determine the need for a permit
prior to starting the installation. It is the responsibility
of the installer to ensure this fi replace is installed
in compliance with manufacturers instructions and
all applicable codes.
BEFORE YOU START
Safe installation and operation of this appliance
requires common sense, however, we are required
by the Canadian Safety Standards and ANSI
Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD
BE DONE BY AN AUTHORIZED
SERVICE PERSON. THE APPLIANCE
SHOULD BE INSPECTED BEFORE
USE AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON.
MORE FREQUENT CLEANING MAY
BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, BEDDING
MATERIAL, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS
AND CIRCULATING AIR PASSAGEWAYS
OF THE APPLIANCE BE KEPT CLEAN.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE
IN THE SAME AREA AS THE APPLIANCE. TODDLERS, YOUNG CHILDREN
AND OTHERS MAY BE SUSCEPTIBLE
TO ACCIDENTAL CONTACT BURNS. A
PHYSICAL BARRIERS IS RECOMMENDED IF THERE ARE AT RISK INDIVIDUAL
IN THE HOUSE. TO RESTRICT ACCESS
TO A FIREPLACE OR STOVE, INSTALL
AN ADJUSTABLE SAFETY GATE TO
KEEP TODDLERS, YOUNG CHILDREN
AND OTHER AT RISK INDIVIDUALS OUT
OF THE ROOM AND AWAY FROM HOT
SURFACES.
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED
ON OR NEAR THE APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local codes or, in the absence of local codes, with
the current Canadian or National Gas Codes,
CAN1-B149 or ANSI Z223.1 Installation Codes.
2) The appliance when installed, must be
electrically grounded in accordance with local
codes, or in the absence of local codes with the
current National Electrical Code, ANSI/NFPA 70
or CSA C22.1 Canadian Electrical Code.
11) Under no circumstance should this
appliance be modified. Parts that have
to be removed for servicing should be
replaced prior to operating this appliance.
12) Installation and any repairs to this appliance
should be done by a qualifi ed service person.
A professional service person should be called
to inspect this appliance annually. Make it a
practice to have all of your gas appliances
checked annually.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid fuels
(wood, paper, cardboard, coal, etc.) be used in
this appliance.
15) The appliance area must be kept clear and free
of combustible materials, (gases and other fl ammable vapours and liquids).
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS
APPLIANCE CORRECTLY WILL VOID
YOUR WARRANTY AND MAY CAUSE A
SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE
ALERTED TO THE HAZARDS OF HIGH
SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND
SHOULD STAY AWAY TO AVOID BURNS
OR CLOTHING IGNITION.
3) See general construction and assembly
instructions. The appliance and vent should be
enclosed.
4) This appliance must be connected to the
specifi ed vent and termination cap to the outside
of the building envelope. Never vent to another
room or inside a building. Make sure that the
vent is fi tted as per Venting instructions.
5) Inspect the venting system annually for blockage
and any signs of deterioration.
6) Venting terminals shall not be recessed into a
wall or siding.
7) Any safety glass removed for servicing must be
replaced prior to operating the appliance.
8) To prevent injury, do not allow anyone who is
unfamiliar with the operation to use the fi replace.
9) Wear gloves and safety glasses for protection
while doing required maintenance.
10) Be aware of electrical wiring locations in walls
and ceilings when cutting holes for termination.
8
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 9
INSTALLATION
INSTALLATION
CHECKLIST
1) Locate appliance
a) Room location (Refer to "Locating Your Gas
fi replace" section)
b) Clearances to Combustibles (Refer to
"Clearances" section)
c) Mantel Clearances (Refer to "Mantel
Clearances" section)
d) Framing & Finishing Requirements (Refer
to "Framing & Finishing" section)
e) Venting Requirements (Refer to "Venting"
section)
2) Position nailing strips (Refer to "Unit Assembly
Prior to Installation).
3) Slide unit into place.
4) Remove installation access panel.
5) Install vent (Refer to "Venting Arrangement"
sections).
6) Make gas connections (Refer to "Gas Line
Installation section).
7) Make electrical connections to receptacle
supplied with unit (recommended).
8) Install 4 AA batteries into receiver/switch box
or use optional AC power adaptor.
9) T est the pilot (Refer to "Pilot Adjustment" section).
10) T est Gas Pressure (Refer to "Gas Pipe Pressure
Testing" section).
11) Install standard and optional features. Refer to
the following sections:
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label 26,000 Btu/h
(NG), 25,500 Btu/h (LP) after burning appliance
for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow the
unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your fi replace,
ensure that the clearances are met.
2) The appliance must be installed on a fl at, solid,
continuous surface For example a wood, metal
or concrete fl oor or in a raised (on the wall) ap-
plication. The appliance must be installed on
a metal or wood panel extending the full width
and depth of the appliance.
3) The HZ40E Direct Vent Gas Fireplace can be
installed in a recessed position or framed out
into the room as in A, B, C and D.
See Diagram 1.
4) This appliance is Listed for bedroom
installations using the standard Remote
(thermostat system). Some areas may have
further requirements, check local codes before
installation.
5) The HZ40E Direct Vent Gas Fireplace
is approved for alcove installations, see
"Clearances" section for details.
6) We recommend that you plan your installation
on paper using exact measurements for
clearances and fl oor protection before actually
installing this appliance. Have an authorized
inspector, dealer , or installer review your plans
before installation.
Note: For vent terminations refer to "Exterior
Vent Termination Locations" section.
HEATWAVE
DUCT SYSTEM
OPTIONAL KIT #946-556
The HeatWave Air Duct Kit increases the
effectiveness of your fi replace by dispersing warm
air from the fi replace to remote locations in the same
room or other rooms in your home.
Up to two kits may be installed on the fi replace. Please Note: Only 1 HeatWave kit may be oper-
ated at one time. This includes the internal blower
option as well.
a) Glass Crystals/ Optional Ceramic
Stones
b) Optional Firebox Base Pebbles
c) Optional Refl ective Panels
d) Optional Fan
e) Faceplate
f) Remote Control or Wall Thermostat
and 10ft. wire harness.
12) Reinstall installation access panel.
13) Final check.
Before leaving this unit with the customer, the
installer must ensure that the appliance is fi ring
correctly and operation fully explained to customer.
Regency Horizon™ HZ40E-2 Gas Fireplace
Diagram 1
A) Flat on Wall
B) Flat on Wall Corner
C) Recessed into Wall/Alcove
D) Corner
The HeatWave Duct Kit has different
clearance and framing requirements, check
the HeatWave manual for details.
OPTIONAL
HEAT RELEASE KIT
#946-570
The Heat Release Kit expels warm air from the
fi replace to the outside of the building, allowing
the fi replace to be operated with less heat entering
the room. The kit may be used on either the left
or right side.
9
Page 10
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fi replace and vent system be installed only in accordance with these instructions.
The top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may NOT be
Caution Requirements
recessed into combustible construction.
Clearance:DimensionMeasured From:
A: Mantel Height (min.)17" (330mm)Top of Fireplace Opening
B: Sidewall (on one side)8" (203mm)Side of Fireplace Opening
E: Alcove Width84" (2134mm)Sidewall to Sidewall (Minimum)
F: Alcove Depth36" (914mm)Front to Back Wall (Maximum)
G: From Floor27" (686mm)Top of Fireplace Opening
Note:0"No hearth required
22" (559mm)Top of Fireplace Opening
if these clearances (air space) to combustible materials are not
Fire hazard is an extreme risk
adhered to. It is of greatest importance that this fi replace and vent
system be installed only in accordance with these instructions.
Passing through wall/
floor/ceiling - when
fi restop is used.
WARNING
The HeatWave Duct Kit and the Heat
Release Kit have different clearance
and framing requirements, check the
HeatWave and Heat Release manual
for details.
1-1/2"
D
F
A
G
E
B
Installed Close
to Floor
Installed close
to ceiling.
E
F
Alcove
10
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 11
MANTEL CLEARANCES
INSTALLATION
Due to the extreme heat this fi replace emits, the
mantel clearances are critical. Combustible mantel
clearances from top of front facing are shown in the
diagram on the right.
Note: Ensure the paint that is used on the mantel
and the facing is "high quality" or the paint
may discolour.
26
20
10
0
To Unit
Base
14
13"
22”
27”
(330mm)
1"
(559mm)
To p o f
Fireplace
Opening
21264810
(25mm)
17”
Combustible Material
Metal Stud
(On Edge)
Facing
Non-combustible
Standoff
Combustible mantel leg clearances as per diagram:
MANTEL LEG
Allowable mantel
legp rojection
Regency Horizon™ HZ40E-2 Gas Fireplace
MANTEL LEG CLEARANCES
7”
5-11/16”(144m
Non-Combustibl
4"
1.5" (38mm)
7-1/8” (181mm)
10”(203mm)
13”( 279mm)
m)
e
11
Page 12
INSTALLATION
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The nailing Strips must be correctly positioned and attached before unit is
slid into position.
NAILING STRIPS
The nailing strips come attached to the unit. There is 1 plate on each side, 1
on the top. There also two on the bottom.
The top and side nailing strips are secured to the framing. The bottom
nailing strips are
Framing depth measurement is noted with the nailing strips
IMPORTANT NOTE
set as far forward on the fi rebox as possible. The nailing
strips can be adjusted back up to 1-1/2” to allow for varying
thicknesses in non-combustible material & wall fi nishes.
INST ALLATION ACCESS P ANEL
The unit is equipped with a removable access panel for pre-fi nish installation
of optional components - this panel is located on the lower front face.
1) Remove lower front face nailing strips (2 screws per nailing strip).
2) Remove 8 screws to remove access panel.
3) Easier access to gas connection with panel removed.
4) Install any optional components with access panel removed.
5) Reinstall access panel with 8 screws and lower front face nailing strips
(2 screws per strip) - prior to installing any facing material
Note: Access panel is no longer usable once facing material installed.
FRONT FACE NAILING STRIP
INSTALLATION
Nailing Strips
Installation Access Panel
Lower front nailing strips
Required when the combined facing/fi nishing material is 1/2".
If using material which is thicker than 1/2", the nailing strips are not
required and should be removed and discarded.
1) The 5 front nailing strips are only used if the facing/fi nishing material
is a combined 1/2" in thickness. This enables the facing and fi nishing
materials to be securely fastened to a solid surface.
2) Follow instructions on non-combustible facing installation for predrilling holes prior to attaching the noncombustible material supplied
with this unit.
3) The side/top nailing strips which are attached to this unit will also need
to be adjusted. See Framing and fi nishing in this manual.
* Framing depth measurement is noted with the nailing strips set as far forward on the fi rebox as possible.
The nailing strips can be adjusted back up to 1” to allow for varying thicknesses in non-combustible
material & wall fi nishes.
rywallor
other facing
Metal Stud (Header)
H
Note: All other framing may
be of wood construction.
D
A
Metal Stud
B
on edge
F
Finished Floor
Non-Combustible
Facing
G
Flex or Rigid Pipe
C1
C
E
C2
J
K
I
L
Regency Horizon™ HZ40E-2 Gas Fireplace
13
Page 14
INSTALLATION
WALL MOUNT ON / OFF SWITCH AND BATTERY COMPARTMENT INSTALLATION
AND/OR RECEIVER INSTALLATION
REQUIRED FOR ALL INSTALLATIONS - INCLUDING PROFLAME REMOTE CONTROLS
IMPORTANT INSTALLATION NOTE:
The Receiver must be placed inside the supplied (Low Voltage)
junction type wall box and installed into the wall only.
DO NOT INSTALL WITHIN THE CONFINES OF THE FIREPLACE.
Remote Receiver Installation
1. Install the low voltage junction box to the framing, at desired location within 10 ft. from fi replace.
2. Feed the 12 pin connector through the opening at back of junction box.
3. Connect the 12 pin connector to the back of the receiver.
4. Install the Receiver in the Low Voltage Junction box.
5. Insert the 4 AA type batteries in the battery compartment with the correct polarity.
6. Place the slider into the cover plate.
7. Put the Receiver switch in the “OFF” position, to allow correct lineup for slider switch.
8. Make sure the Receiver and cover plate words “ON” and “UP” are on the same side.
9. Align the slider with the switch on the Receiver and couple the switch into the slider.
10. Align the screw holes.
11. Using the two (2) screws provided secure the cover plate to the Receiver.
Optional Profl ame Receiver
Slider Switch
Wall Plate
Low Voltage Junction Box
J-Box
Receiver
14
10 ft. wire harness with
12 pin connector
Diagram 1
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 15
INSTALLATION
NON-COMBUSTIBLE REQUIREMENTS
* Installation of the Receiver must be completed before installing non-combustible facing.
All three pieces (top, 2 sides) are now supplied to meet the non combustible requirements. Previously only the top was supplied.
Metal Stud (header)
Calcium silicate board is a high - grade material
with cement, quartz, natural and selected
minerals as the main raw materials. It is widely
used for partitions and ceilings in buildings.
It is fi re proof and earthquake proof.
If fi nishing the wall above the unit with materials
such as tile, brick, marble, etc. non-combustible
board available from the building supply store
can be used.
Note: Calcium Silicate is 1/2' thick
Metal Stud
(252mm)
20"
(508mm)
(351mm)
13-13/16”
10"
Non-combustible
5-11/16"
(144mm)
51-5/16" (1303mm)
Non-combustible
Material
Non-combustible
May be combustible (ie. 1/2” drywall)
on edge
Metal Stud
(859mm)
33 -13/16"
Non-combustible
NON-COMBUSTIBLE FACING INSTALLATION
Caution: The non-combustible board supplied with this unit can
be damaged if dropped or struck. Handle with care.
1) Using drywall screws - secure non combustible material
around unit, framing and top nailing strip every 6 inches.
Important Note: To avoid cracking the board - pre-drill holes prior to
securing to unit/ framing.
2) Wipe any debris/dust from the non combustible
material and drywall.
3) Prior to securing it is mandatory to prime the facing and edges
using a quality primer. This will ensure proper adhesion of both the
tape and mud. The supplied board is very porous.
Failure to follow this procedure will result in cracked seams.
4) Tape the seams using a mesh type tape.
5) Mud seams as normal. We recommend using a
product called Durabond high strength compound - for the fi rst coat.
This product can be found at any hardware store.
Mud must be cured as per manufacturer’s recommendations.
6) Prime wall for a second time for proper adhesion of paint
7) Paint walls using a high quality paint which will withstand
the high temperatures being emitted from this appliance.
Non-combustible board
shipped with unit.
Non-combustible board
shipped with unit.
Non-combustible board-faces and edges
MUST BE PRIMED.
Regency Horizon™ HZ40E-2 Gas Fireplace
15
Page 16
INSTALLATION
FRAMING & FINISHING
1) Frame in the enclosure for the unit with framing material.
IMPORTANT: The framed opening must be of non-combustible
material.
Note: When constructing the framed opening, please ensure there
is access to install the gas lines when the unit is installed.
2) For exterior walls, insulate the enclosure to the same degree as the
rest of the house, apply vapour barrier and drywall, as per local installation codes. (Do not insulate the fi replace itself.)
WARNING: Failure to insulate and add vapor barriers to the inside
of the exterior wall will result in operational and performance
problems including, but not limited to: excessive condensation
on glass doors, poor fl ame package, carbon, blue fl ames etc.
These are not product related issues.
3) The unit does not have to be completely enclosed in a chase. You
must maintain clearances from the vent to combustible materials: See
"Clearances" section. Combustible materials can be laid against the
side and back standoffs and the stove base.
4) Non-combustible material (ie. tile, slate, etc) may be brought up to and
overlap the unit (top and bottom) ensuring that the maximum thickness
does not go beyond the 1-1/2" as shown in the diagram below. The
faceplate will not be able to be mounted if fi nished material is beyond
1-1/2".
5) If material such as brick, stone, etc extends past the faceplate depth (1-1/2"),
when fi nishing around the faceplate, the minimum opening dimensions noted
below must be adhered to ensuring for the removal of the faceplate and for
the safe operation of this appliance.
NOTE: Spacing of 1" around the completed surround must be adhered to.
52-3/4"
27-5/8"
Unit shown with 4 piece faceplate
47- 1/16”
1/2" required
between faceplate
+ fi nished wall
”
9/16
24-
Unit shown with inner and outer door frame
39-13/16”
16-7/8”
IMPORTANT: 1/2" gap required between faceplate and fi nished wall when
using 4 pce. Faceplate (Part # 256-924, 256-926, 256-927)
16
Unit shown with inner door frame only
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 17
FRAMING & FINISHING
INSTALLATION
Finished
Material
Nailing Strip
Position
1/2"1"
1"1/2"
1-1/2"0" (fl ush)
Nailing Strip
1” Forward
Unit
Nailing Strip
½” Forward
Unit
Nailing Strip
Flush w/unit
Factory Set
Note:
Depending on the material used for fi nishing, the nailing
strips must be set accordingly so that the fi nished material
is always at the 1-1/2" edge of the fl ange.
Metal Stud
10"
(252mm)
Unit
NON-COMBUSTIBLE REQUIREMENTS
Metal Stud (header)
51-5/16" (1303mm)
20"
(508mm)
(351mm)
13-13/16”
Non-combustible
Non-combustible
Material
Non-combustible
May be combustible (ie. 1/2” drywall)
on edge
Metal Stud
(859mm)
33 -13/16"
Non-combustible
(144mm)
Regency Horizon™ HZ40E-2 Gas Fireplace
5-11/16"
17
Page 18
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
1
Minimum Clearance Requirements
A
Clearance above grade, veranda, porch, deck, or balcony12"(30cm)12"(30cm)
B
Clearance to window or door that may be opened 12"(30cm)9" (23cm)
C
Clearance to permanently closed window**
D
Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm)
from the center line of the terminal (check with the local code)
E
Clearance to unventilated soffi t19"(48cm)19"(48cm)
F
Clearance to outside corner: with AstroCap Termination Cap.7"(18cm)7"(18cm)
Clearance to outside corner: with all other approved Termination Caps.13"(33cm)13"(33cm)
G
Clearance to inside corner: with AstroCap Termination Cap 7"(18cm)7"(18cm)
Clearance to inside corner: with all other approved Termination Caps.13"(33cm)13"(33cm)
H
Clearance to each side of center line extended above meter/regulator assembly 36"(90cm)
J
Clearance to service regulator vent outlet36"(90cm)*
K
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance12"(30cm)9" (23cm)
L
Clearance to a mechanical air supply inlet #3' (91cm) above if within 10' (3m) horizontally.72"(1.8m)36"(90cm)
M
Clearance above paved sidewalk or a paved driveway located on public property 84"(2.1m)
N
Clearance under veranda, porch, deck, or balcony 12"(30cm)
1
In accordance with current CSA B149.1, Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
┼
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor
Clearance in accordance with local installation codes and the requirements of the gas supplier
*
a
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
b
3 feet (91cm) above - if within 10 feet (3m) horizontally
Canada
19"(48cm)19"(48cm)
a
┼
‡
USA
*
*
*
2
b
18
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 19
INSTALLATION
4” X 6-5/8” RIGID PIPE
CROSS REFERENCE CHART ONLY
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Chimney Conversion Kit A (USA only)46DVA-KCAN/AN/AN/AN/ATM-4CA6
Chimney Conversion Kit B (USA only)46DVA-KCBN/AN/AN/AN/ATM-4CA7
Chimney Conversion Kit C (USA only)46DVA-KCCN/AN/AN/AN/ATM-4CA8
Chimney Conversion Kit Masonry
(USA only)
Wall Firestop46DVA-WFSN/AN/AN/AN/ATM-4TR
Colinear Flex Connectors46DVA-ADFN/AN/AN/AN/AN/A
FPI
946-506/PVent Guard (Optional) for AstroCap946-205Vinyl Siding Shield for Riser Vent Terminal
510-994Rigid Pipe Adaptor (Must use with all rigid piping)946-208/PVent Guard (Optional) for Riser Vent Terminal
640-530/PRiser Vent Terminal946-523/PAstroCap Horizontal Cap
946-605Starter Collar Increaser 4” x 6-5/8” to 5” x 8”946-206Vinyl Siding Standoff for AstroCap
Note: When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection: Use this table to determine offset pipe lengths.
Pipe Length
(L)
0” (0mm)4-7/8” (124mm)13-7/8” (340mm)Simpson Direct Vent Pro: www.duravent.com
Note: Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination.
Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.
Run (X)Rise (Y)
46DVA-KMCN/AN/AN/AN/AN/A
4” x 6-5/8” VentingFor specifi c instructions on venting components - visit the
manufacturers website listed below.
20
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 21
VENT RESTRICTOR POSITION
Vent restriction is required for certain venting installations, see the diagrams in the "Venting
Arrangements" section to determine if they are required for your installation.
The Vent Restrictor plate is located on the inside top of the fi rebox.
To set the vent restriction as indicated in the venting arrangements diagrams, refer to the following instructions;
1) Remove the glass door - see instructions in this manual.
2) Remove the screws that hold the vent restrictor plate in place.
3) Adjust the vent restrictor plate to the required vent restrictor position as per the diagrams shown.
4) Once the vent restrictor plate is in the required position, secure with screws.
INSTALLATION
Set 0
(Factory set)
VENT RESTRICTOR
AT 3"
Regency Horizon™ HZ40E-2 Gas Fireplace
Set 1
VENT RESTRICTOR
AT 2"
Set 2
VENT RESTRICTOR
AT 1-1/2"
Set 3
VENT RESTRICTOR
AT 1"
21
Page 22
INSTALLATION
VENTING INTRODUCTION
The HZ40E uses the "balanced fl ue" technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws
outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These fl ue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel
or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.
VENTING ARRANGEMENT FOR HORIZONTAL TERMINATIONS
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o (two 45o elbows equal one 90o elbow). (Not including
the starting 45o elbow at the fl ue collar when using rigid venting.)
Note: Must use optional rigid pipe adapter (Part# 510-994) when using Rigid Pipe Venting Systems.
Horizontal (Feet)
18
16
0
2
4
614
816
1018
1220
14
Vent Restrictor
on Set 1
12
10
Vent Restrictor
8
6
on Set 0
Factory Set)
(
Vertical Height (Feet) from Centreline
4
2
0
VENT RESTRICTOR SETTING:
Vent restrictor factory set at Set 0.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 0 to Set 1 if required.
Note: For horizontal terminations the Regency Direct Vent Flex System may be used for installations with a maximum continuous vent
length of up to 10 feet. If longer runs are required, rigid pipe must be used.
• Maintain clearances to combustibles as listed in "Clearances" section
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.
• A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.
• Flex system can only be used up to 10 feet - otherwise rigid venting must be used.
36-1/4” (921mm)
Minimum Height
Requirement
22
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 23
INSTALLATION
HORIZONTAL TERMINATIONS
FLEX VENT 4" X 6-7/8"
These venting systems, in combination with the HZ40E Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Warnock
Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination
Locations" section.
Regency® Direct Vent (Flex) System Termination Kits includes all the parts needed to install the HZ40E using a fl exible vent.
1) Liner sections should be continuous without any
joints or seams.
2) 4” fl exible inner liner (Kit length)
3) spring spacers
4) thimble
5) AstroCap termination cap
6) screws
7) tube of Mill Pac
8) plated screws
9) S.S. screws #8 x 1-1/2” drill point
2) Only Flex pipe purchased from Regency® may be
used for Flex installations
3) Horizontal vent must be supported every 3 feet.
4) Regency® Direct Vent System (Flex) is only approved
for horizontal terminations.
5) Flex system can only be used up to a maximum
continuous vent length of up to 10 feet. If longer
runs are required, rigid pipe must be used.
Vent Guard
(Part #946-506/P)
Regency Horizon™ HZ40E-2 Gas Fireplace
23
Page 24
INSTALLATION
/
HORIZONTAL TERMINATIONS
RIGID PIPE 4" X 6-5/8"
The minimum components required for a basic horizontal
termination are:
1 Horizontal Termination Cap
1 45o Elbow
1 Rigid Pipe Adaptor (510-994)
1 Wall Thimble
1 Length of pipe to suit wall thickness
(see chart)
Wall thickness is measured from the back standoffs to the inside
mounting surface of termination cap. For siding other than vinyl
furring strips may be used, instead of the vinyl siding standoff, to
create a level surface to mount the vent terminal. The Terminal
must not be recessed into siding. Measure the wall thickness
including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl
siding), measure to outside surface of wall without siding and
add 2 inches.
Flat Wall Installation
Wall Thickness
(inches)
4" - 5-1/2"6"
7" - 8-1/2"9"
10" - 11-1/2"12"
9" - 14-1/2'11" - 14-5/8" Adj. Pipe
15" - 23-1/2"17" - 24" Adj. Pipe
Vent Length Required
(inches)
Standoff (Optional)
Adj.Pipe Length
o
45 Elbow
Rigid Pipe Adapter
Vinyl Siding
Horizontal
Termination Cap
Vent Guard
(Part #946-506
Wall Thimble
WARNING:
Do not combine venting components from
different venting systems.
TM
However use of the the AstroCap
Riser is acceptable with all systems.
This product has been evaluated by Intertek
for using a Rigid Pipe Adaptor in conjunction
with Duravent Direct-Vent, Selkirk Direct-T emp,
Ameri Vent Direct Venting, ICC Excel Direct
and Security Secure Vent systems. Use of
these systems with the Rigid Pipe adaptor is
deemed acceptable and does not affect the
Intertek WHI listing of components.
The FPI AstroCap
American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, ICC Excel, Selkirk Direct-Temp. AstroCapTM is a proprietary trademark of FPI
Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
24
TM
and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent,
and FPI
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 25
INSTALLATION
HORIZONTAL TERMINATIONS
RIGID PIPE 4" X 6-5/8"
The diagrams below shows examples of horizontal termination arrangements using one, two, or three 90o elbows (two 45o elbows equal one 90o elbow)
1) A maximum of three 90o elbows are permitted (not including the starting 45o elbow at the fl ue collar when using rigid venting).
2) Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.
• Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems.
• A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.
• Flex system can only be used up to 10 feet - otherwise rigid venting must be used.
Straight Out Horizontal Venting
Maximum 36"(914mm)
Minimum 6"(152mm)
Diagram 1
center
of hole
C
L
height
(Rigid)
Min.
36-1/4" (743mm)
C
L
Regency Horizon™ HZ40E-2 Gas Fireplace
Please note the minimum centerline for
basic install shown above.
With these options,
maximum total pipe
length is 28 feet with
minimum of 12 feet
total vertical and
maximum 9 feet total
horizontal.
Please note
minimum 1 foot
between 90o elbows
is required.
H1
H
V
V1
Regency Horizon™ HZ40E-2 Gas Fireplace
27
Page 28
INSTALLATION
L
S
O
VERTICAL TERMINATIONS
The minimum components required for a basic vertical
termination are:
RIGID PIPE 4" X 6-5/8"
1 Vertical Termination Cap
1 45o Elbow
1 Rigid Pipe Adaptor (510-994)
1 Ceiling Firestop
1 Flashing
1 Storm Collar
1 Length of pipe to suit wall thickness
(see chart)
Galvanized pipe is desirable above the roofl ine due to its higher
corrosion resistance. Continue to add pipe sections through the
fl ashing until the height of the vent cap meets the minimum height
requirements specifi ed in Dia. 4 or local codes. Note that for steep
roof pitches, the vertical height must be increased. A poor draft, or
down drafting can result from high wind conditions near big trees
or adjoining roof lines, in these cases, increasing the vent height
may solve the problem.
Roof Pitch Minimum Vent Height
Feet Meters
fl at to 7/12 2 0.61
over 7/12 to 8/12 2 0.61
over 8/12 to 9/12 2 0.61
over 9/12 to 10/12 2.5 0.76
over 10/12 to 11/12 3.25 0.99
over 11/12 to 12/12 4 1.22
over 12/12 to 14/12 5 1.52
over 14/12 to 16/12 6 1.83
over 16/12 to 18/12 7 2.13
over 18/12 to 20/12 7.5 2.29
over 20/12 to 21/12 8 2.44
Vertical Terminal
Storm Collar
Flashing
Ceiling Firestop
Pipe Length
Standoff(
Adj.Pipe
o
45Elbow
Rigid Pipe Adapter
Vinyl
WARNING:
Do not combine venting components from different venting systems.
However use of the the AstroCapTM and FPI Riser is acceptable with all systems.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction
with Duravent Direct-Vent, Selkirk Direct-T emp, Ameri Vent Direct Venting, ICC Excel Direct
and Security Secure Vent systems. Use of these systems with the Rigid Pipe adaptor is
deemed acceptable and does not affect the Intertek WHI listing of components.
The FPI AstroCap
American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, ICC Excel, Selkirk Direct-Temp. AstroCapTM is a proprietary trademark of FPI
Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
28
TM
and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent,
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 29
INSTALLATION
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
6
8
2
0
4
101216
18
14
20
VENTING ARRANGEMENT FOR VERTICAL TERMINATIONS
Vertical Venting with One(1) 90o Elbows (1 - 90
The shaded area in the diagram shows all allowable combinations
of straight vertical and offset to vertical terminations, using one
90o elbow, with Rigid Pipe Venting Systems.
o
Two 45
starting 45o elbow at the fl ue collar.
• Vent must be supported at offsets.
• Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed in the
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever
• Must use optional rigid pipe adaptor (Part# 510-994)
• Refer to the "Vent Restrictor Position" section for
elbows equal to one 90o elbow, not including the
"Clearances" section.
passing through a wall.
when using rigid pipe vent systems.
details on how to change the vent restrictor from the
factory setting of Set 0 to Set 1 or Set 2 if required.
o =
2 - 45o)
Horizontal (Feet)
18
Maximum: 40 ft. (12.2m)
Vent Restrictor on Set 3
Vent Restrictor on Set 2
Vertical Height (Feet)
Minimum length of pipe
between elbows 12” (305mm)
Vent Restrictor on Set 1
Minimum
8’6” (2.6m)
(921mm)
Min. 36-1/4”
Max. 10’ (3m)(centerline to centerline)
Maximum: 27 ft. (8.2m)
Regency Horizon™ HZ40E-2 Gas Fireplace
29
Page 30
INSTALLATION
VERTICAL TERMINATION
WITH CO-LINEAR FLEX SYSTEM
THE APPLIANCE MUST NOT BE
CONNECTED TO A CHIMNEY FLUE SERV-
ING A SEPARATE SOLID FUEL
BURNING APPLIANCE.
This appliance is designed to be attached to
two 3" (76mm) co-linear aluminium fl ex running
the full length of the chimney. See the "Venting
Arrangements - Vertical Terminations" Section for
minimum and maximum heights.
Required Parts:
Part # Description
946-529 Co-linear DV Vertical
Termination Cap
948-305 3" Flex - 35 ft.
946-563 Co-Axial to Co-Linear Adapter Kit
which contains the following:
Co-linear Flex Adapter Outer Pipe
Inner Pipe Adapter
510-994 Rigid Pipe Adaptor
46DVA-E45 45o Elbow
Alternate Approved Caps
46DVA-VC Vertical Termination Cap
46DVA-VCH High Wind Cap
46DVA-GK
3" Co-linear Adapter with fl ashing
Masonry chimneys may take various contours which the fl exible liner will accommodate. However, keep the fl exible liner as straight as possible, avoid unnecessary bending.
The Air Intake pipe must be attached to the inlet air collar of the termination cap.
Co-linear DV
Vertical Termination
Cap # 946-529
A maximum
of two certified
joiner kits
may be used
per length.
Flex Liner
#948-305
35 ft (11m)
Exhaust
Flue
Pipe Length
Rigid Pipe Adapter
# 510-994
Outer
Pipe
with Kit#
946-563
o
45 Elbow
Air Intake
Co-Linear
Flex
Adapter
with Kit#
946-563
Inner Pipe
Adapter
with Kit#
946-563
30
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 31
VERTICAL TERMINATIONS
RIGID PIPE 4" X 6-5/8"
INSTALLATION
• Two 45
• Vent must be supported at offsets.
• Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.
• Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems.
o
elbows equal to one 90o elbow. Maximum of four 45o elbows allowed, not including the starting 45o elbow at the fl ue collar.
Vertical Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
OptionVHV + V 1
A)1' Min. 4' Max.2' Min.
B)2' Min. 5' Max.3' Min.
C)3' Min. 6' Max.4' Min.
D)4' Min. 7' Max.5' Min.
E)5' Min. 8' Max.6' Min.
Restrictor Position - Set 0 (factory setting)Restrictor Position - Set 0 (factory setting)
With these options,
maximum total pipe
length is 30 feet with
minimum of 6 feet total
vertical and maximum 8
feet total horizontal.
Please note minimum
1 foot between 90o
elbows is required.
Vertical Venting with Two (2) 90o Elbows
OptionH + H1V
A)2' Max.2' Min.
B)3' Max.3' Min.
C)4' Max.4' Min.
D)5' Max.5' Min.
E)6' Max.6' Min.
One 90o elbow = Two 45o elbows.
With these options, maximum
total pipe length is 30 feet
with minimum of 6 feet total
vertical and maximum 6 feet
total horizontal.
Please note minimum 1
foot between 90o elbows is
required.
Regency Horizon™ HZ40E-2 Gas Fireplace
For additional vertical venting with
o
2 x 90
elbows, refer to "Rigid Pipe
Venting Arrangements" Section.
31
Page 32
INSTALLATION
Vertical Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option H V H + H1 V + V1A) 1' Max. 1' Min. 3' Max. 3' Min.
B) 2' Max. 2' Min. 4' Max. 5' Min.
C) 3' Max. 3' Min.' 5' Max. 7' Min.
D) 4' Max. 4' Min. 6' Max. 9' Min.
E) 5' Max. 5' Min. 7' Max. 11' Min.
Restrictor Position - Set 0 (factory setting)
With these options, max. total
pipe length is 30 feet with min.
of 11 feet total vertical and
max. 7 feet total horizontal.
Please note min. 1 foot
between 90o elbows is
required.
Vertical Venting with Three (3) 90o Elbows
One 90
Option V H + H1 V + V1 A) 2' Min. 3' Max. 4' Min.
B) 3' Min. 4' Max. 6' Min.
C) 4' Min. 5' Max. 7' Min.
D) 5' Min. 6' Max. 8' Min.
E) 6' Min. 7' Max. 9' Min.
F) 7' Min. 8' Max. 10' Min.
o
elbow = Two 45o elbows.
With these options, max. total
pipe length is 30 feet with min.
of 10 feet total vertical and
max. 8 feet total horizontal.
Please note min. 1 foot
between 90o elbows is
required.
Restrictor Position - Set 0 (factory setting)
32
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 33
8' (2.4m) Min.
Horizontal Distance (Feet)
Vertical Height (feet)
2’ (51mm) max.
35
36-1/4”
(921mm)
35' (10.7m) Max.
Vent Restrictor
Set 2
16' Max.
Vent Restrictor Set 1
Restrictor Set 1
Restrictor Set 2
INSTALLATION
VENTING ARRANGEMENTS - VERTICAL TERMINATIONS
with Co-linear Flex System for both
Residential & Manufactured Homes
into Masonry Fireplaces
35
Set 2
Vent Restrictor
V
Vertical Height (feet)
Horizontal Distance (Feet)
Vent Restrictor
Vent Restrictor
Set 2
' (10.7m) Max.
16' Max. Vent
35
8' (2.4m) Min.
”
36-1/4
(921mm)
Set 1
Vent Restrictor
35
Restrictor Set 2
Restrictor Set 1
Vertical Height (feet)
2’ (51mm) max.
Horizontal Distance (Feet)
Vent Restrictor
Set 2
Combined max. of.35' (10.7m) Max.
Combined min. of 8’ (2.4m).
6’ (152mm) max.
36-1/4”
(921mm)
16' Max.
Vent Restrictor Set 1
Combined max. of
Regency Horizon™ HZ40E-2 Gas Fireplace
The shaded area in the diagrams show
the allowable vertical terminations when
using two- 3" co-linear aluminium fl ex
and 4 x 6-5/8" rigid pipe.
33
Page 34
INSTALLATION
UNIT INSTALLATION
WITH HORIZONTAL
TERMINATION
4" X 6-5/8"
VENTING
(Rigid Vent Systems)
Minimum Vent Clearances
to Combustibles
* Clearances noted below must be maintained;
except when passing through a wall, ceiling or at the
termination where the use of a fi restop or wall thimble
reduces clearance to 1-1/2" (38mm).
Below are the recommended framing dimensions
(inside measurements) for the 4" x 6-5/8"
rigid vent terminations - for use with a fi restop or
wall thimble.
Recommended Framed Opening
Size
Vent SizeFraming Size
4" x 6 - 5/8"10" x 10"
Install the vent system according to the
manufacturer's instructions included with the
components.
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are in
the way when the venting system is attached.
If this is the case, you may want to adjust the
location of the unit. Rough in the gas preferably
on the right side of the unit and the electrical
(junction block is on the left side) on the left.
2) Direct Vent pipe and fi ttings are designed with
special twist-lock connections to connect the
venting system to the appliance fl ue outlet. A
twist-lock appliance adaptor is required.
3) In conjunction with the Approved V ent system,
install the adaptor after the unit is set in its
desired location. Put a bead of high temperature
silicone inside the outer section of the adapter
and a bead of Mill Pack on the inner collar. Slip
the adapter over the existing inner and outer
fl ue collar. Fasten to the outer collar only with
the 3 supplied screws (drilling pilot holes will
make this easier).
4) Level the fi replace and fasten it to the framing
using nails or screws through the top and side
nailing strips.
5) Assemble the desired combination of pipe and
elbows to the appliance adaptor and twist-lock
for a solid connection.
Note: For best results and optimum performance
with each approved venting system, it is
highly recommended to apply “Mill-Pac”
sealant (supplied) to every inner pipe
connection. Failure to do so may result
in drafting or performance issues not
covered under warranty. Silicone (red
RTV) is optional.
Horizontal runs of vent must be supported every
3 feet (0.9meter). Wall straps are available for
this purpose.
6) Mark the wall for a square hole.-see chart to left
for size. The center of the square hole should
line up with the center-line of the horizontal pipe.
Cut and frame the square hole in the exterior
wall where the vent will be terminated. See
diagram 2 for center line requirements.
If the wall being penetrated is constructed of
non-combustible material, i.e. masonry block
or concrete, an 8" (203mm) diameter hole is
acceptable.
Note:
a) The horizontal run of vent must be level, or
have a 1/4 inch rise for every 1 foot of run
towards the termination. Never allow the
vent to run downward. This could cause
high temperatures and may present the
possibility of a fi re.
b) The location of the horizontal vent
termination on an exterior wall must meet
all local and national building codes,
center
of hole
C
L
C
L
height
(Rigid)
Min.
36-1/4" (743mm)
Diagram 2
7) Ensure that the pipe clearances to combustible
materials are maintained (Diagram 5). Install
the termination cap.
Note: If installing termination on a vinyl siding
covered wall, a vinyl siding standoff or
furring strips must be used to ensure
that the termination is not recessed into
the siding.
Diagram 5
The four wood screws provided should be
replaced with appropriate fasteners for stucco,
brick, concrete, or other types of sidings.
8) Before connecting the horizontal run of vent pipe
to the vent termination, slide the Wall Thimble
over the vent pipe. The wall thimble is required
for all horizontal terminations.
9) Slide the appliance and vent assembly towards
the wall carefully inserting the vent pipe into the
vent cap assembly. It is important that the vent
pipe extends into the vent cap suffi cient distance
so as to result in a minimum pipe overlap of
1-1/4 inches (32mm). Secure the connection
between the vent pipe and the vent cap.
10) Install wall thimble in the center of the framed
hole and attach with wood screws (Diagram 7).
Diagram 7
Diagram 1
34
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 35
INSTALLATION
UNIT INSTALLATION
WITH HORIZONTAL
TERMINATION
4" X 6-5/8"
VENTING
(Flex Vent Systems)
Minimum Vent Clearances
to Combustibles
* Clearances noted below must be maintained;
except when passing through a wall, ceiling or at the
termination where the use of a fi restop or wall thimble
reduces clearance to 1" (25mm).
Below are the recommended framing dimensions
(inside measurements) for the 4" x 6-5/8" rigid
vent terminations - for use with a fi restop or wall
thimble.
Recommended Framed Opening
Size
Vent SizeFraming Size
4" x 6 - 5/8"10" x 10"
1) Locate the unit in the framing, rough in the gas
(preferably on the right side of the unit). Locate
the centerline of the termination and mark wall
accordingly. Cut an square hole in the wall - see
chart (inside dimension).
NOTE: Horizontal sections must be supported
at intervals not exceeding 3 feet (0.9
meter). (Flame picture and performance
will be affected by sags in the liner).
4) Separate the 2 halves of the wall thimble and
securely fasten the one with the tabs to the
outside wall making sure that the tabs are on
top and bottom. Fasten the other thimble half
to the inside wall. The thimble halves slip inside
each other and can be adjusted for 2 x 4 or 2
x 6 walls.
5) Slip the assembled liner and termination
assembly through the thimble making sure the
termination cap faces up (there are markings
on the cap indicating which way is up). This
will position the termination cap with proper
down slope for draining water. Fasten the cap
to the outer wall with the 4 supplied screws.
6) Pull the centre inner and outer fl ex liner out
enough to slip over the fl ue collars of the fi replace. (You may wish to cut the liner shorter
to make it more workable.) Do not bend liner
more than 90
collars a minimum of 1-3/8".
7) Apply Mill Pac over the fi replace inner fl ue
collar and slip the inner fl ex liner down over it
and attach with 3 supplied screws.
8) Do the same with the outer fl ue collar and outer
fl ex liner.
9) Apply a bead of silicone between the thimble
and termination and around the outer edge of
the terminal at the wall in order to keep the
water out.
o
. The liners must slip over the
ASTROCAP
DIMENSIONS (946-523/P)
11”
(294mm)
11”
(294mm)
of hole
C
L
C
L
(921mm)
36-1/4”
Min.
Using Flex System
Note: If installing termination on a siding cov-
ered wall, a vinyl siding standoff or vinyl
furring strips must be used to ensure that
the termination is not recessed into the
siding.
2) Level the fi replace and fasten it to the framing
using nails or screws through the nailing strips.
3) Assemble the vent assembly by applying Mill
Pac to the inner fl ue collar of the termination and
slipping the inner fl ex liner over it at least 1-3/8"
(35mm). Fasten with the 3 screws (drilling pilot
holes will make this easier). Apply Mill Pac or
high temperature silicone to the outer fl ex pipe
and slip it over the outer fl ue collar of the vent
terminal at least 1-3/8"(35mm) and fasten with
the 3 screws.
IMPORTANT: Do not locate termination hood
where excessive snow or ice buildup may
occur. Be sure to check vent termination
area after snow falls, and clear to prevent
accidental blockage of venting system. When
using snow blowers, make sure snow is not
directed towards vent termination area.
Screws
(3 per
connection)
4" (102mm) dia. flue pipe
with spring spacer
6-7/8" (173mm)
dia. air intake
Wall Thimble 2 pieces
(10" (254mm)
Outer Diameter)
2”x4”or2”x6”
Termination
Cap
Screws
(4 per
connection)
Regency Horizon™ HZ40E-2 Gas Fireplace
35
Page 36
INSTALLATION
UNIT INSTALLATION
WITH VERTICAL
TERMINATION
4" X 6-5/8" VENTING
(Rigid Vent Systems)
1) Maintain the 1-1/2" clearances (air spaces) to
combustibles when passing through ceilings,
walls, roofs, enclosures, attic rafter, or other
nearby combustible surfaces. Do not pack
air spaces with insulation.
Check "Venting" Sections for
the maximum vertical rise of the
venting system and the maximum
horizontal offset limitations.
2) Set the gas appliance in its
desired location. Drop a plumb
bob down from the ceiling to the
position of the appliance fl ue
exit, and mark the location where
the vent will penetrate the
ceiling. Drill a small hole
at this point. Next, drop a
plumb bob from the roof to
the hole previously drilled
in the ceiling, and mark the
spot where the vent will penetrate the roof.
3) A Firestop spacer must be installed in the fl oor
or ceiling of every level. To install the Firestop
spacer in a fl at ceiling or wall, cut a 10 inch
square hole. Frame the hole as shown in
Diagram 2 and install the fi restop.
Diagram 1
4) Assemble the desired lengths of pipe and
elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position
and sealed.
NOTE: For best results and optimum performance with each approved venting system, it is
highly recommended to apply “Mill-Pac” sealant
(supplied) to every inner pipe connection. Failure
to do so may result in drafting or performance
issues not covered under warranty. Silicone (red
RTV) is optional.
5) Cut a hole in the roof centered on the small
drilled hole placed in the roof in Step 2. The hole
should be of suffi cient size to meet the minimum
requirements for clearance to combustibles
of 1-1/2". Slip the fl ashing under the shingles
(shingles should overlap half the fl ashing) as
per Diagram 3.
Diagram 4
Roof Pitch
fl at to 7/1220.61
over 7/12 to 8/1220.61
over 8/12 to 9/1220.61
over 9/12 to 10/122.50.76
over 10/12 to 11/123.250.99
over 11/12 to 12/1241.22
over 12/12 to 14/1251.52
over 14/12 to 16/1261.83
over 16/12 to 18/1272.13
over 18/12 to 20/127.52.29
over 20/12 to 21/1282.44
7) Ensure vent is vertical and secure the base of
the fl ashing to the roof with roofi ng rails, slide
storm collar over the pipe section and seal with
a mastic.
8) Install the vertical termination cap by twistlocking it.
Note: Any closets or storage spaces, which the
vent passes through must be enclosed.
Minimum Vent Height
Feet Meters
Note: All vertical terminations are vented
using 4" x 6-5/8" venting and rigid pipe
adaptor #510-994.
Diagram 2
Diagram 3: The upper half of the fl ashing is installed
under the roofi ng material and not nailed down
until the chimney is installed. This allows for small
adjustments.
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic to
avoid obstructions, it is important to
support the vent pipe every 3 feet, to
avoid excessive stress on the elbows,
and possible separation. Wall straps
are available for this purpose.
Galvanized pipe is desirable above the roofl ine
due to its higher corrosion resistance. Continue
to add pipe sections through the fl ashing until the
height of the vent cap meets the minimum height
requirements specifi ed in Dia. 4 or local codes.
Note that for steep roof pitches, the vertical
height must be increased. A poor draft, or down
drafting can result from high wind conditions
near big trees or adjoining roof lines, in these
cases, increasing the vent height may solve
the problem.
36
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 37
INSTALLATION
HZ40E-NG2 SYSTEM DATA
Min. Supply
Pressure
Manifold Pressure3.5" WC (0.87 kpa)
Orifi ce Size #40 DMS
Maximum Input26,000 Btu/h
Minimum Input18,000 Btu/h
5" WC (1.25 kpa)
(7.61 kW)
(5.28 KW)
HZ40E-LP2 SYSTEM DATA
Min. Supply Pressure11" WC (2.73 kpa)
Manifold Pressure10" WC (2.49 kpa)
Orifi ce Size #53 DMS
Maximum Input25,500 Btu/h
Minimum Input21,000 Btu/h
(7.47 kW)
(6.15 KW)
HIGH ELEVATION
This unit is approved for altitude 0 to 4500 ft. (CAN1
2.17-M91).
PILOT ADJUSTMENT
Periodically check the pilot fl ames. Correct fl ame
pattern has two strong blue fl ames: 1 fl owing
around the fl ame sensor and 1 fl owing across
the burner (it does not have to be touching the
burner).
Burner
Flame Sensor
Pilot
Note: If you have an incorrect fl ame pattern,
contact your Regency® dealer for further
instructions.
Incorrect fl ame pattern will have small, probably
yellow fl ames, not coming into proper contact
with the rear burner or fl ame sensor.
Ignitor
GAS PIPE PRESSURE
TESTING
880 S.I.T. VALVE
DESCRIPTION
1) Pilot adjustment
2) Outlet Pressure Tap
3) Inlet Pressure Tap
4) Pilot Outlet
5) Main Gas Outlet
6) Main Gas Inlet
3
2
1
GAS LINE
INSTALLATION
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.
When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and fl ex connectors are
usually considered to meet this requirement.
NOTE: A shutoff / dante valve should be supplied in or near the unit (or as per local codes)
for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detector.
Do not use open fl ame for leak testing.
The appliance must be isolated from the gas supply piping system by closing its individual manual
shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa). Disconnect
piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1) Make sure the unit is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a
1/8" wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4) Turn the unit on with the remote or wall switch
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits specifi ed on the safety label.
6) When fi nished reading manometer, turn off
the unit, disconnect the hose and tighten the
screw (clockwise) with a 1/8" fl at screwdriver.
Note: Screw should be snug, but do not over
tighten.
6
4
5
AERA TION ADJUSTMENT
The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude. Open the air shutter for a blue fl ame or
close for a more yellow fl ame.
Minimum Air Shutter Opening:
NG 1/8"
NG with Logs 1/8
NG with Stones 1/8”
LP 3/8"
LP with Logs Full open
LP with Stones Full open
Note: Any damage due to carboning resulting
from improperly setting the aeration
controls is NOT covered under warranty.
Regency Horizon™ HZ40E-2 Gas Fireplace
37
Page 38
INSTALLATION
AC POWER ADAPTOR INSTALLATION (FOR SUREFIRE SYSTEMS)
An optional AC power adaptor may be installed as a constant power source for the SureFire system.
This will avoid battery leakage and power drainage. 4-AA Battery pack may be re-installed into receiver during power outages.
NOTE: For all Gas Fireplaces 120 volt power must be brought to the receptacle box inside the ERWWRPRIWKH¿UHER[(provided with the unit).
All Freestanding Gas Stoves & Gas Inserts will need a receptacle box located outside / near the unit
NOTE: AC power adaptor is not required when using GTMF Remote
IMPORTANT: Recommend removing the 4-AA batteries in the SureFire receiver.
so that the AC Power Adaptor can be plugged in.
INSTALL AC ADAPTOR WITH SUREFIRE WALL SWITCH ONLY - (WITHOUT REMOTE)
1) Locate “DC Supply” tag on wire harness. For location in unit
see remote installation page in owners manual.
2) Connect the male end from AC adaptor to the female end
tagged “DC Supply” on wiring harness in unit.
3)
Plug AC adaptor into 120V wall outlet (or into 120V receptacle if
LQVWDOOHGLQVLGHWKHJDV¿UHSODFH¿UHER[
4) Neatly tuck any loose AC Power Adaptor wires neatly underneath /
inside the appliance.
INSTALL AC ADAPTOR WITH SUREFIRE PROFLAME GT / GTM REMOTE
This method also applies for models, HZ30E - HZ40E - L390E - HZI390E
1) Connect the male end of the AC adaptor to the female end of the
wire adaptor (supplied with AC adaptor) together as shown
Wire adaptor
2)
Locate FCM - COM connector on the Remote wire harness -
(keep wires away from the heat as much as possible).
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 39
INSTALLATION
WIRING DIAGRAM
This heater does not require a 120V A.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/thermostat will
continue to operate. However, a 120V A.C. power supply is needed for the fan/blower operation.
(Do not cut the ground terminal off under any circumstances.)
NOTE: Even if the fan is not purchased with the unit, it is still a good idea to bring power to the receptacle box (provided with the unit) in case the
fan is installed at a later date.
PROFLAME SYSTEM GT
885
Proflame System
Configuration
886 GTMF
Wire Diagram
SureFire™ Switch
Optional AC Adaptor
Optional AC Adaptor
PROFLAME SYSTEM GTM
Proflame System
Configuration
885
886 GTMF
Wire Diagram
SureFire™ Switch
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation.
Regency Horizon™ HZ40E-2 Gas Fireplace
Caution: Ensure that the wires do not touch any
hot surfaces and are away from sharp edges.
39
Page 40
INSTALLATION
PROFLAME SYSTEM GTMF WITH OPTIONAL FAN
Proflame System
Configuration
885
886 GTMF
Wire Diagram
SureFire™ Switch
120V AC
60 Hz
Neutral
Live
Black
Ground
Black
Caution: Ensure that the wires do not touch any
hot surfaces and are away from sharp edges.
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation.
White
Green
Black
Fan
Fan
Black
Red
Fan Thermodisc
(normally open)
Ground
40
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 41
OPTIONAL FAN WIRING DIAGRAM
~
~
WITHOUT PROFLAME GTMF SYSTEM
INSTALLATION
Lockwasher
Star washer
#8 Ground Lug
(for mobile home)
Nut
Fan
ground wire
Electrical Connection Alternative Scheme "A",
Power at Stove
Wall Junction Box
Wire Nuts
*Speed Control
Switch with
lead wires
(Regency)
120V AC
60 Hz
Neutral
Live
Fan
Black
Ground
Black
White
Green
Black
Black
Fan Thermodisc
(normally open)
Electrical Connection Alternative Scheme "B",
Power at Switch
Wall Junction Box
*Speed Control
Switch with lead wires
Ground
Fan
Red
14 AWG wire
*Wire Clamp
*Receptacle Box
inside stove
*Receptacle
(dedicated use
by stove fan only)
Copper Ground
120 Volts
60 Hz
White (Neutral)
Black (Hot)
14 AWG wire
Black (Hot)
120 Volts
60 Hz
Wire Nuts
* = supplied with fan kit
Other parts are to be supplied
by electrician or installer
White (Neutral)
Copper Ground
Wire
Wire Nuts
14 AWG wire
*Receptacle Box
inside stove
*Receptacle
(dedicated use
by unit fan only)
Black
White
Ground
*Wire Clamp
Caution: Ensure that the wires do not touch any
hot surfaces and are away from sharp edges.
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation.
Regency Horizon™ HZ40E-2 Gas Fireplace
41
Page 42
INSTALLATION
Optional
REMOTE CONTROL
Use the Regency® Remote Control approved for this unit. Use of other systems
may void your warranty.
The remote control comes with a hand held transmitter.
*Profl ame GT remote control 946-700
RF remote, ON/OFF Thermostat, ON/OFF Flame Control
Large blue backlit LCD screen with temperature display receiver.
*Profl ame GTM remote control 946-701.
RF remote, ON/OFF Thermostat, ON/OFF Flame Control
Large blue backlit LCD screen with temperature display receiver.
**Profl ame GTMF remote control 946-702.
RF remote, ON/OFF Thermostat, ON/OFF Flame Control
ON/OFF fan control with 3-stage adjustment. Requires a fan (if not included),
to be installed for fan function to operate.
*Must also chose one of the following which enables the fl ame to be turned
down using the remote control:
*Modulator Surefi re NG 946-693
*Modulator Surefi re LP 946-694
Large blue backlit LCD screen with temperature display receiver.
(Included with Unit)
RECEIVER WALL SWITCH
1) Run the supplied 10' of the wire harness through the right or left side gas
inlet opening- connect the ON/OFF wire harness. Be careful not to damage
wire.
2) Choose a convenient location on the wall to install the receiver and the
receptacle box (protection from extreme heat is very important). Run wires
from the fi replace to that location.
3) Connect the wire to the receiver wall switch and install into the low voltage
receptacle box.
42
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 43
GTMF REMOTE INSTALLATION
r
INSTALLATION
120 Volt AC power is needed for the fan. The fan can be hard wired if desired.
The receptacle box should be installed on the right hand side of the unit
by a qualifi ed electrician. The neutral (wider) slot of the polarized receptacle
should be at the top.
Unit must be grounded at all times. Do not cut the ground terminal off
under any circumstances.
Note: Follow instructions below - if unit has not yet been installed - otherwise
skip to existing installtions section.
1) Remove 8 screws to remove front access panel.
2) Remove 2 top screws and loosen 2 bottom screws to remove side access
panel.
INTO EXISTING INSTALLATIONS
1) Shut off the gas and power supply to the unit.
2) Remove the faceplate or door frame - see instruction in manual.
3) Remove the glass door.
a) Remove the 3 screws shown below at the bottom of the glass
door.
b) Swing the door out 45o from the bottom and lift up and out.
4) Remove the inner panels - reverse of "Inner panel Installation" in the
installation manual.
3) Install fan control module (FCM) into bracket on the inside of the panel,
plug the (FCM) into the outlet in the unit - reinstall the panel with 4 screws
from step 2.
5) Remove the burner tray cover by lifting up and out as shown below.
* Prior to removing burner - remove crystals, pebbles, spa stones and inne
panels - if installed.
4) Proceed to Step 11.
Regency Horizon™ HZ40E-2 Gas Fireplace
43
Page 44
INSTALLATION
5) Loosen 2 screws at the back of the burner to release it.
6) Remove the burner by sliding it to the right - then lift out.
8) Once the top panel is removed - the left side panel will be accessible.
Remove 3 screws from the left side access panel in locations shown
below.
Note: Some components have been removed for illustration purposes.
9) Install the fan control module (FCM) through the opening created by the
removed left side access panel.
7) Remove the left access plate by removing 8 screws - see locations below.
Left side access
10) Install the fan control module (FCM) into the bracket as shown below.
44
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 45
11) Locate the digital fi rebox control box.
12) Plug the fan power cord into the fan control module in the outlet marked
fan. Plug in the FCM wire (from the digital fi rebox control box wire har-ness) into the location on the fan control module marked com
INSTALLATION
FCM Wire
Com
13) See Profl ame remote instructions for coding remote to receiver as well
as operating instructions.
14) Reverse steps 2-1 for new installations.
Reverse steps 8 - 1 for existing installations.
Regency Horizon™ HZ40E-2 Gas Fireplace
45
Page 46
INSTALLATION
OPTIONAL FAN INSTALLATION
120 Volt AC power is needed for the fan switch and blower. The fan can be
hard wired if desired. The receptacle box should be installed on the left
hand side of the unit by a qualifi ed electrician. The neutral (wider) slot of the
polarized receptacle should be at the top see page 41 for wiring diagram).
Unit must be grounded at all times. Do not cut the ground terminal off
under any circumstances.
Follow these instructions before the initial installation into the framing. If
installing the optional fan into an exiting installation - follow instructions on
the next two pages.
1) Remove lower front face nailing strips (2 screws per nailing strip).
2) Remove 8 screws to remove front access panel.
3) Slide the fan assembly through the front access panel - slide all the way
back to the back of the two tabs.
5) Connect one of the black wire to the Black wires from the power cord.
(light blue connector). Connect the other end to one spade on the thermodisc.
6) Connect the red wire end to the other open spade one the thermodisc.
Connect the other end of the red wire to the black wire from the fan motor.
7) Connect the white wire from the fan motor to the black wire on the power
cord.(dark blue connector).
8) Slide in the thermodisc to the clip in the location shown below.
Thermodisc clip
9) Secure the ground wire from the fan assembly, also secure the ground
wire from the power cord to the stud on the back left near the fan.
Ground Lug
Tabs
4) Secure the fan to the fl oor of the unit with 2 screws, in locations show
below.
46
10) Plug the fan into the receptacle located in the lower left front corner at
the base of the unit.
NOTE: If installing the fan with a GTMF remote - please see GTMF remote
instructions in the manual.
TO REMOVE THE FAN
1) Turn the power off.
2) Reverse the above instructions.
Maintenance: The sealed bearings are lubricated, there is no need to lu-
bricate them further. (Extra lubricant will cause more lint and dust buildup
- causing the bearings to prematurely fail).
Regular cleaning and vacuuming of the fan area will add to the life of the
motor.
IMPORTANT:
These fans collect a lot of dust from within your home. Ensure you
maintain these fan motors on a regular basis by vacuuming
the fan blades and housing using a soft brush nozzle.
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 47
INSTALLATION
p
OPTIONAL FAN INSTALLATION - INTO EXISTING INSTALLATIONS
120 Volt AC power is needed for the fan switch and blower. The fan can be
hard wired if desired. The receptacle box should be installed on the left
hand side of the unit by a qualifi ed electrician. The neutral (wider) slot of the
polarized receptacle should be at the top (see page 41 for wiring diagram).
Unit must be grounded at all times. Do not cut the ground terminal off
under any circumstances.
1) Shut off the gas and power supply to the unit.
3) Remove the faceplate or door frame by lifting it up off the glass door.
Faceplate
(4pc style
shown)
4) Remove the glass door.
a) Remove the 3 screws shown below at the bottom of the glass
door.
Glass Door
7) Loosen 3 screws at the back of the burner to release it.
8) Remove the burner by sliding it to the right - then lift out.
b) Swing the door out 45o from the bottom and lift up and out.
5) Remove the inner panels - reverse of "Inner panel Installation" in the
installation manual.
6) Remove the burner tray cover by lifting up and out as shown below.
9) Remove the left access plate by undoing the 8 screws - see locations
below.
Location of screws on access plate
10) Remove the left access plate by undoing the 8 screws - see locations
below.
* Prior to removing burner - remove crystals, pebbles, spa stones and inner
anels - if installed.
Regency Horizon™ HZ40E-2 Gas Fireplace
47
Page 48
INSTALLATION
10) Maneouver fan through left access panel opening.
11) To complete fan installation - follow steps 2- 7 on previous page.
NOTE: The right access panel wasremoved to allow easier access to secure
the right screw on the fan base.
12) Reverse steps 9-1 to complete install.
48
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 49
INNER PANEL INSTALLATION
INSTALLATION
Handling Instructions
Black Enamel Panels
• Black Enamel panels must be inspected for scratches and
dimples prior to installation. All claims to be recorded at this time.
Claims for damage after installation will not receive consideration.
• Black Enamel panels will discolor a little during normal operation.
This is normal and should not be considered a defect.
All hand and fi nger marks MUST be cleaned off with a soft cloth.
*
Use an ammonia based cleaner (ie. glass cleaner) to remove any
fi ngerprints before applying heat to the unit.
Failure to do this will result in burn stain on panels which you
will be unable to remove. Not protected by product warranty.
1) Remove the faceplate and glass door if already installed - see
manual for instructions.
2) Remove 4 screws to remove top heat defl ector.
7) Install the left side enamel panel - secure in position with the panel
clip and two tighten two screws loosened in step 2, as shown in the
diagram below.
8) Install the right side enamel panel - secure in position with the panel
clip and two screws loosened in step 4.
3) Remove installed factory panels.Loosen 2 screws (do not remove) on panel clip securing side panel,
Slide panel clip down away from screws.
Remove side panel.
panel clip
4) Repeat on opposite side.
5) Remove back panel.
6) Install the back enamel panel fi rst. Tilt the panel forward - position
the bottom of the panel fi rst. Use care not to scratch or mar the panel
on the pilot shield.
9) Reinstall heat defl ector.
10) Reinstall glass door - reinstall faceplate.
Final Install
Regency Horizon™ HZ40E-2 Gas Fireplace
49
Page 50
INSTALLATION
GLASS CRYSTALS OR OPTIONAL STONES
INSTALLATION ON BURNER
Spread the Glass Crystals or Stones evenly over the burner. Ensure the crystals/stones do not overlap excessively as this will affect the fl ame pattern.
IMPORTANT NOTE:
Only the supplied approved Glass Crystals and Stones are to be used with these fi replaces. Use of any other type of glass crystals or stones can
alter the unit's performance, any damage caused by the use of any unapproved glass or stones will not be covered under warranty.
When using Ceramic Spa/Volcanic Stones DO NOT cover burner ports or pilot light that lead to pilot fl ame.
PTO30 / Plateau Series 10 lbs1 Box Volcanic Stones
PTO6020 lbs2 Boxes Volcanic Stones
NOTE: * Glass Crystals are not supplied with the unit. Must purchase separately - see quantities above.
Glass Crystals are available in 1lb and 5lb bags.
Note: 1 Spa stone package contains 70 stones.
** Recommended - use only 40 of the 70 spa stones on the HZ30E burner.
*** Recommended - use only 24 of the 70 spa stones on the HZI234E burner.
OPTIONAL PEBBLES / GLASS CRYSTAL INSTALLATION FOR FIREBOX BASE (AROUND BURNER)
There are 2 optional packages to choose from to cover the fi rebox base:
1) Natural River Pebbles
2) Glass Crystals (4 colors available)
Spread the pebbles / crystals evenly on the exposed base of the fi rebox. Pebbles are NOT to be placed anywhere on the burner or over top of
the Glass Crystals or optional Stones.
IMPORTANT NOTE: Only the supplied and approved pebbles / glass crystals are to be used with these fi replaces. Use of any other type of pebbles,
50
glass crystals or other material can create a danger and will void the warranty.
HZI390E /HZI390PB3 lbs1 package (3 x bags pebbles)
HZI234E2 lbs1 package (3 x bags pebbles)
HZO42 / HZO42 (AUS)3 lbs1 package (3 x bags pebbles)
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 51
INSTALLATION
For Units HZ54E, , HZ42ST, HZ42STE, HZI234E, HZ42E, HZ42,
Glass Crystals shown on Burner
HZ30E,
HZO42, HZO42 (AUS) PTO30, PTO60, Plateau Series
Glass Crystals shown surrounding the Burner
Optional Spa Stones + Glass Crystals shown on burner.
For Units HZ54E, HZ42ST, HZ42STE, HZI234E, HZ42, HZ42E,
HZ30E
Natural River Pebbles shown surrounding the a Horizon Burner
Glass Crystals shown on Burner and Firebox Floor
For Units HZI390E, HZI540E
Regency Horizon™ HZ40E-2 Gas Fireplace
DO NOT block pilot area with glass crystals
51
Page 52
INSTALLATION
OPTIONAL DRIFTWOOD LOG SET INSTALLATION
Read the instructions below carefully and refer to the images. If the logs are broken do not use the unit until they are replaced. Broken
logs can interfere with pilot operation.
Improper positioning of the logs may create carbon build-up and can alter the unit's performance which is not covered under warranty.
*Satin black paint is included if touch ups are required.
1 Rear Log
2 Left Log
3Right Log
4 Left Cross Log
5 Right Cross Log
6Front Left Log Piece
7Front Right Log Piece
Lava embers
Pilot Hood - HZ54E only
Log placement template - one each HZ54E /HZ40E
1
4
3
5
6
6. Clip on log guides - position approximately 5" on either side of the
pilot hood.
Log guides
2
7. Install Rear Log (1), by positioning cut out over pilot hood.
7
1. S hut off gas and electr ical supply, allow unit to cool to room temperature.
2. Remove fl ush glass door (see manual).
3. Carefully remove the logs from the packaging and unwrap them.
The logs are fragile, handle with care -never force into position.
4. Ensure glass crystals are installed on the burner.
HZ54E = 2lbs HZ40E=1.5lbs
5.HZ54E only- Remove existing pilot hood - replace with pilot hood
provided with log set.
HZ54E - existing Pilot
Hood
52
HZ54E - new Pilot
Hood
8. Push the rear log gently back, until it hits the log guides.
1
Log 1 in position
9. Place log placement template on the front fl oor of the unit.
Ensure L and R sides are in the correct position. Secure template in
place with magnets (supplied) on each side.
HZ40E - log placement template -
shown in place.
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 53
INSTALLATION
10. Position Left Log (2) by matching the log and template profi les exactly.
1
2
HZ54E shown - Left Log (2) positioned to match
template profi le.
11. Position Right Log (3) by matching the log and template profi les exactly.
1
3
HZ54E shown - Right Log (3) positioned to match
template profi le.
12. Position Left Cross Log (4) on Log 1, match up pin landing as per
reference below, rest bottom of Log 2 on Log 3 plus match log profi le
with template profi le.
15. Place Front Left log piece on fi rebox fl oor as shown.
2
6
HZ54E shown - Left Log Piece(6)
16. Place Right Log piece on fi rebox fl oor as shown.
7
4
HZ54E shown - Right Log Piece(7)
17. If desired, install additional crystals on fi rebox fl oor, in and around
installed logs.
18. Install lava embers - spread evenly over glass.
HZ54E pin landing
HZ40E pin landing
4
1
2
HZ54E shown - Left Cross Log (4) positioned to
13. Position Right Log (5) by lining pin on Logs 1 with pin landing on Log
3, match bottom of Log 5 and template profi le.
14. Carefully remove log placement template.
match template profi le.
1
Match pin and pin landing
5
Logs 1 and 3.
3
Lava embers on glass crystals
19. Reverse steps 1 and 2.
20. Adjust aeration settings - see unit manual for settings.
HZ54E shown - Completed Install
HZ40E shown - Completed Install
Regency Horizon™ HZ40E-2 Gas Fireplace
53
Page 54
INSTALLATION
GLASS DOOR INSTALLATION
The glass door comes with a black frame.
1) To install the frame and glass door, simply hook the top door fl ange onto
the top of the unit and swing the door towards the unit, Diagram 1.
Note: Be careful that the glass gasket does not roll up; there must be a gap
between the gasket and the door lip to ensure that the door sits
securely on the unit. See Diagram 2.
2) With the door in proper position - secure with 2 screws in locations shown
in Diagram 3.
Diagram 3
3) Install cover plates over each screw with 2 magnets each as shown below.
Hook top of
door onto
top flange
Flush
Door
Diagram 1
Cover Plate
Magnet
Diagram 4
Cover Plates Installed
Diagram 5
54
Diagram 2
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 55
OPTIONAL MESH GLASS GUARD
INSTALLATION
1) Remove left side and right side door frame screws.
2) Using existing door frame screw, install lower mesh mounting brackets
on left side and right side, as shown.
3) Install mesh screen, fl ush side facing out.
4) Install left side and right side top mounting clips approximately 3" from
each side.
NOTE: Clips should line up with the edge of the outer edge of the glass
door fl ange - see glass door install for illustration.
Lower mesh mounting brackets
Regency Horizon™ HZ40E-2 Gas Fireplace
Mesh mounting clips
5) Install faceplate - refer to faceplate installation instructions in manual.
55
Page 56
INSTALLATION
1) If installing optional mesh glass guard - See optional "Mesh Glass
Guard" installation instructions.
2) Install brackets onto the back of the faceplate - 3 screws for each
bracket in locations shown below.
3) To install the 4 pc. faceplate - hook brackets (located on back of
faceplate) over the two middle tabs on the glass door frame.
If thicker fi nishing materials are used - the faceplate may be
adjusted out - up to 1/2".
4 PIECE FACEPLATE INSTALLATION
Hook bracket over
these tabs
+1/2"
+1/4"
Use fi rst notch in bracket
for standard installation
Important: 1/2" gap required between faceplate and
fi nished wall when using part #256-924, 256-926, 256927 (4 pc. faceplate).
Final Install
56
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 57
INSTALLATION
INNER AND OUTER DOOR FRAME INSTALLATION
Note: HZ40E only - if installing optional mesh glass guard See optional mesh glass guard instruction in the manual.
1) Install 4 magnets onto 4 corners of glass frame prior to installing
the inner door frame.
2) Install the inner door frame - fi t it over the glass door frame.
Glass Door
Inner Door Frame
3) Install the outer door frame to the unit by hooking the left and right side
mounting brackets into the mounting slots at the side of the fi rebox
as shown below. It is recommended that you use the fi rst mounting
slot (the one closest to the door frame overlay) out of the 3 so that
the faceplate and door frame overlay are fl ush with one another.
NOTE: There are 3 mounting slots available, this is to accommodate
any fi nishing that protrudes slightly beyond the faceplate.
Bracket in Unit
Tab on Faceplate
918-905a
Regency Horizon™ HZ40E-2 Gas Fireplace
Completed inner door
frame and faceplate
installation
Note: Inner door frame may be installed by itself, or with the outer
door frame.
The outer door frame cannot be installed by itself - if install-
ing the outer door frame - the inner door frame must also be
installed.
1
08/24/11
57
Page 58
OPERATING INSTRUCTIONS
OPERATING
INSTRUCTIONS
1) Read and understand these instructions before
operating this appliance.
2) Check to see that all wiring is correct and
enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the glass door frame
is properly positioned. Never operate the
appliance with the glass removed.
5) Verify that the venting and cap are unobstructed.
6) The unit should never be turned off, and on
again without a minimum of a 60 second wait.
FIRST FIRE
The FIRST FIRE in your heater is part of the paint
curing process. To ensure the paint is properly
cured, it is recommended you burn your fi replace
for at least four (4) hours the fi rst time.
When fi rst operated, the unit will release an odour
caused by the curing of the paint and the burning
off of any oils remaining from manufacturing. Smoke
detectors in the house may go off at this time. Open
a few windows to ventilate the room for a couple of
hours. The glass may require cleaning.
NOTE: When the glass is cold and the appliance
is lit, it may cause condensation and fog
the glass. This condensation is normal and
will disappear in a few minutes as the glass
heats up.
DO NOT A TTEMPT TO CLEAN THE GLASS
WHILE IT IS STILL HOT!
LIGHTING
PROCEDURE
IMPORTANT
To ignite or reignite the pilot, you
must fi rst remove the glass door.
1) Press and release on ON/OFF button once
on the remote control or ON/OFF switch.
2) After approximately 4 seconds the spark
ignition system will spark for 60 seconds to
light the main burner.
3) The unit will turn on.
Note: The fi rst try for ignition will last approxi-
mately 60 seconds. If there is no fl ame ignition
(rectifi cation) the board will stop sparking for
approximately 35 seconds. After wait time
, the board will start second try for ignition
by sparking for approximately 60 seconds .
If there is still no positive ignition the board
will go into lock out.
The system will need to be reset as follows:
a) Turn the system off using ON/OFF switch
or press ON/OFF button - if using optional
remote.
b) After approximately 2 seconds turn on ON/
OFF switch or press ON/OFF button if using
optional remote.
c) Repeat step 2.
If the appliance will not operate, follow the
instructions "To Turn Off Gas to Appliance"
and call your service technician or gas
supplier.
NORMAL OPERATING
SOUNDS OF
GAS APPLIANCES
It is possible that you will hear some sounds from
your gas appliance. This is perfectly normal due to
the fact that there are various gauges and types
of steel used within your appliance. Listed below
are some examples. All are normal operating sounds and should not be considered as defects
in your appliance.
Burner Tray:
The burner tray is positioned directly under the
burner and is made of a different gauge material
from the rest of the fi rebox and body. Therefore, the
varying thicknesses of steel will expand and contract
at slightly different rates which can cause "ticking"
and "cracking" sounds. You should also be aware
that as there are temperature changes within the
unit these sounds will likely re-occur. Again, this is
normal for steel fi reboxes.
Pilot Flame:
While the pilot fl ame is on it can make a very slight
"whisper" sound.
Gas Control Valve:
As the gas control valve turns ON and OFF, a
dull clicking sound may be audible, this is normal
operation of a gas regulator or valve.
Unit Body/Firebox:
Different types and thicknesses of steel will expand
and contract at different rates resulting in some
"cracking" and "ticking" sounds will be heard
throughout the cycling process.
Blower Thermodisc:
When this thermally activated switch turns ON it will
create a small "clicking" sound. This is the switch
contacts closing and is normal.
DO NOT BURN THE UNIT WITHOUT THE
GLASS DOOR IN PLACE.
During the fi rst few fi res, a white fi lm
may develop on the glass front as part of
the curing process. The glass should be
cleaned after the unit has cooled down
or the fi lm will bake on and become very
diffi cult to remove. Use a non-abrasive
cleaner and DO NOT ATTEMPT TO
CLEAN THE GLASS WHILE IT IS HOT.
58
58
SHUTDOWN
PROCEDURE
1) Turn the wall mounted switch or remote to
the "OFF" position.
2) Press "OFF" on the remote control.
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 59
OPERATING INSTRUCTIONS
COPY OF LIGHTING PLATE INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
This appliance must be installed in accordance with local codes, if any;
if none, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or
WARNING: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life. Improper installation, adjustment,
alteration, service or maintenance can cause injury or property damage. Refer to the owner’s
information manual provided with this appliance. For assistance or additional information
consult a qualified installer, service agency or gas supplier.
AVERTISSEMENT. Quiconque ne respecte pas à la lettre les instructions dans la présente notice
risquede déclencher un incendie ou une explosion entraînant des dommages, des blessures ou
la mort.
Une installation, d'ajustement, de modifi cation, de service ou d'entretien peut provoquer
des blessures ou des dommages matériels. Reportez-vous au manuel du propriétaire de
l'information fournie avec cet appareil. Pour obtenir de l'aide ou des informations supplémentaires consulter un installateur qualifi é, une agence de service ou fournisseur de gaz.
A) This appliance is equipped with an ignition device which automatically lights the pilot.
Do not try to light the pilot by hand.
B) BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the fl oor
because some gas is heavier than air and will settle on the fl oor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance.
- Do not touch any electric switch, do not use any phone in your building.
- Immediately call your gas supplier from a neighbours phone. Follow the gas supplier ’s instructions.
- If you cannot reach your gas supplier, call the fi re department.
C) Do not use this appliance if any part has been under water. Immediately call a qualifi ed service
technician to inspect the appliance and replace any part of the control system and any
gas control which has been underwater.
A) Cet appareil est muni d’un dispositif d’allumage qui allume automatiquement la veilleuse.
Ne tentez pas d’allumer la veilleuse manuellement.
B) AVANT DE FAIRE FONCTIONNER, renifl ez tout autour de l’appareil pour déceler une odeur
de gaz. Renifl ez près du plancher, car certains gaz sont pluslourds que l’air et peuvent
s’accumuler au niveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le
bâtiment.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les
instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur, appelez le service des incendies
C) N’utilisez pas cet appareil s’il a été plongé dansl’eau, même partiellement. Faites inspecter l’appareil par un tech-
nicien qualifi é et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l’eau.
CAUTION: Hot while in operation. Do not touch. Severe Burns may result. Due to high surface
temperatures keep children, clothing and furniture, gasoline and other liquids having fl ammable
vapors away. Keep burner and control compartment clean. See installation and operating
instructions accompanying appliance.
1) Turn on ON/OFF switch
2) After approximately 4 seconds the spark ignition system will spark for 60 seconds to light the main
burner.
3) The unit will turn on.
Note: The fi rst attempt to ignition will last approximately 60 seconds. If there is no fl ame ignition (rectifi ca-
s
tion) the board will stop sparking for approximately 35 seconds. After this wait time, the board will start a
second try for ignition by sparking for approximately 60 seconds. If there is still no positive ignition after the
second attempt the board will go into lock out.
The system will need to be reset as follows (after going into lock out mode):
a) Wait 5 minutes - turn the system off using ON/OFF switch.
b) After approximately 2 seconds turn on ON/OFF switch or press ON/OFF button if using optional
c) Unit will repeat step 2.
1) Appuyez le bouton ON / OFF
2) Attendre 4 secondes. Le système d’allumage produira des étincelles pendant 60 secondes afi n d’amorcer
3) Les fl ammes s’allumeront.
Remarque : Au premier allumage, le système tente d’allumer les fl ammes pendant 60 secondes. Si l’essai est
infructueux, le système fait une pause de 35 secondes. C’est ce qu'on appelle l'étape de rectifi cation. Ce délai
écoulé, le système tente à nouveau d'allumer les fl ammes en produisant des étincelles pendant 60 secondes.
Si les fl ammes ne s’allument toujours pas, le système se met en mode verrouillage.
Il faut alors le réinitialiser en suivant les étapes ci-dessous (pour le déverrouiller) :
a) Attendre 5 minutes et éteindre l’appareil en réglant l’interrupteur à la position « OFF »;
b) Attendre 2 secondes et rallumer le système à l’aide de l’interrupteur ou de la télécommande.
c) L'unité répétera l'étape 2.
1) Turn off ON/OFF switch
2) If service is to be performed - you must disconnect power to the unit, from the battery pack, refer to
Appuyez sur le bouton ON / OFF
1)
2) Si le service est effectuée, vous devez débrancher l'appareil, du bloc-piles, voir le manuel d'instruction
remote.
le brûleur principal.
manual.
pour plus de détails.
Natural Gas and Propane Installation Codes, CSA B149.1.
LIGHTING INSTRUCTIONS
TO TURN OFF GAS APPLIANCE
INSTALLATION
Regency Horizon™ HZ40E-2 Gas Fireplace
DO NOT REMOVE THIS INSTRUCTION PLATE
918-628b
5959
Page 60
MAINTENANCE
MAINTENANCE
INSTRUCTIONS
1) Always turn off the gas and electrical supply
before cleaning. For relighting, refer to lighting
instructions. Keep the burner and control
compartment clean by brushing and vacuuming
at least once a year.
2) Clean appliance and door with a damp cloth
(never when unit is hot). Never use an abrasive
cleaner. The glass should be cleaned with a gas
fi replace glass cleaner. The glass should be
cleaned when it starts looking cloudy.
3) The faceplate is fi nished in a heat resistant
paint and should only be refi nished with heat
resistant paint. Regency® uses StoveBright
Paint - Metallic Black #6309.
Note: Faceplates and inner panels made from
stainless steel will naturally change color
over time.
4) Make a periodic check of burner for proper
position and condition. Visually check the fl ame
of the burner periodically, making sure the fl ames
are steady; not lifting or fl oating. If there is a
problem, call a qualifi ed service person.
5) The appliance and venting system must be
inspected before use, and at least annually, by
a qualifi ed fi eld service person, to ensure that
the fl ow of combustion and ventilation air is not
obstructed.
Note: Never operate the appliance without the
glass properly secured in place.
GLASS GASKET
If the glass gasket requires replacement use a
tadpole glass gasket (Part # 936-159).
GLASS DOOR
Your Regency® fi replace is supplied with high
temperature 5mm-Ceramic glass. If your glass
requires cleaning, we recommend using an
approved glass cleaner available at all authorized
dealers. Do not use abrasive materials.
CAUTION & WARNINGS:
* Do not clean when the glass is hot.
* The use of substitute glass will void all product
warranties.
* Care must be taken to avoid breakage of the
glass.
* Do not strike or abuse the glass.
* Do not operate this fi replace without the glass
front or with a cracked or broken glass front.
* Wear gloves when removing damaged or broken
glass.
* Replacement of the glass panel(s) should be
done by a licensed or qualifi ed service per son.
GLASS REPLACEMENT
In the event that you break your glass by impact,
purchase your replacement from an authorized
Regency® dealer only.
Replacement neo-ceramic glass
(Part # 940-361/P) is shipped with gasket.
GENERAL VENT
MAINTENANCE
Conduct an inspection of the venting system semiannually. Recommended areas to inspect as follows:
1) Check the Venting System for corrosion in areas
that are exposed to the elements. These will
appear as rust spots or streaks, and in extreme
cases, holes. These components should be
replaced immediately.
2) Remove the Cap, and shine a fl ashlight down the
Vent. Remove any bird nests, or other foreign
material.
3) Check for evidences of excessive condensation,
such as water droplets forming in the inner
liner, and subsequently dripping out the joints,
Continuous condensation can cause corrosion
of caps, pipe, and fi ttings. It may be caused
by having excessive lateral runs, too many
elbows, and exterior portions of the system
being exposed to cold weather.
4) Inspect joints, to verify that no pipe sections or
fi ttings have been disturbed, and consequently
loosened. Also check mechanical supports such
as Wall Straps, or plumbers' tape for rigidity.
6) Do not use this appliance if any part has been
under water. Immediately call a qualifi ed service
technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.
7) In the event this appliance has been serviced
check that the vent-air system has been properly
resealed & reinstalled in accordance with the
manufacturer's instructions.
8) Verify operation after servicing.
CAUTION: Wear gloves when removing
damaged or broken glass.
WARNING: Do not operate the
appliance with the glass panels
removed, cracked or broken.
Replacement of the glass panels
should be done by a licensed or
qualifi ed service person.
60
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 61
V ALVE ASSEMBLY REPLACEMENT
MAINTENANCE
1) Turn the unit off and allow it to cool down to room temperature.
2) Shut off thegas and power supply to the unit.
3) Remove the faceplate or door frame -see instruction in this manual.
4) Remove the glass door.
a) Remove the 3 screws shown below at the bottom of the glass
door.
b) Swing the door out 45o from the bottom and lift up and out.
5) Remove the inner panels - reverse of "Inner panel Installation" in this
manual.
6) Remove the burner tray cover by lifting up and out as shown below.
8) Remove the burner by sliding it to the right - then lift out.
9) Remove the valve access plate by undoing the 8 screws - see locations
below.
* Prior to removing burner - remove crystals, pebbles, spa stones and inner
panels - if installed.
7) Remove 3 screws on the burner to release it - locations shown below.
10) Disconnect the inlet gas line and remove the valve assembly.
256-934 Outer Door Frame Black
256-936 Outer Door Frame Bold
256-947 Outer Door Frame Stainless
256-944 Inner Door Frame Black
256-946 Inner Door Frame Bold
256-947 Inner Door Frame Stainless
256-951 Verona Glass Surround Pure Black
256-953 Verona Glass Surround Classic Grey
256-955 Verona Glass Surround Chocolate Brown
256-917 Fan Kit
256-929 Mesh Guard
256-930 Log Set
Part # Description
946-700 GT Remote Control
946-701 GTM Remote Control
946-702 GTMF Remote Control
946-693 Modulator NG
946-694 Modulator LP
1 pound bag of glass crystals
946-675 Black Refl ective Crystals
946-676 Copper Crystals
946-677 Starfi re Crystals946-678 Cobalt Blue Crystals
5 pound bag of glass crystals
946-775 Black Refl ective Crystals
946-776 Copper Crystals
946-777 Starfi re Crystals946-778 Cobalt Blue Crystals
946-672 Natural River Pebbles
946-674 Ceramic Spa Stones
10
Regency Horizon™ HZ40E-2 Gas Fireplace
11
63
Page 64
NOTES
64
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 65
NOTES
Regency Horizon™ HZ40E-2 Gas Fireplace
65
Page 66
NOTES
66
Regency Horizon™ HZ40E-2 Gas Fireplace
Page 67
WARRANTY
Regency® Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly
before it leaves our facility. Regency® Fireplace Products is pleased to extend this limited lifetime warranty to the original purchaser of a Regency® Product. This warranty is
not transferable.
The Warranty: Limited Lifetime
The combustion chamber, heat exchanger, burner tubes/pans, logs, glass crystals, ceramic spa stones, pebbles, brick panels and gold plating (against defective manufacture only) are
covered under the Limited Lifetime Warranty for fi ve (5) years for parts and subsidized labour* and parts only thereafter.
Glass is covered for lifetime against thermal breakage only, parts and subsidized labour* for fi ve (5) years and parts only thereafter from date of purchase.
External casting, surrounds and grills are covered against cracks and warps resulting from manufacturer defects, parts and subsidized labour* for three (3) years from the date of purchase
and parts only thereafter.
Special Finishes - One year on stainless steel panels, nickel overlays,nickel faceplates, brushed nickel and antique copper full screens and doors. You can expect some changes in color
as the product "ages" with constant heating and cooling. Regency warranties the product for any manufacturing defects on the original product. However, the manufacturers warranty does
not cover changing colors and marks, ie. fi nger prints, etc applied after the purchase of the product. Damage from the use of abrasive cleaners is not covered by warranty.
Electrical and mechanical components such as blowers, switches, wiring, thermodiscs, Regency® remote controls, spill switches, thermopiles, thermocouples, pilot assembly components,
and gas valves are covered for two years parts and one year subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are considered repairs and continue
as if new with appliance. ie. twelve (12) months from original purchase date of appliance with a minimum of three (3) months coverage from date of replacement.
Regency venting components are covered parts and subsidized labour* for three (3) years from date of purchase.
Simpson Dura-Vent venting components (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.
Repair/replacement parts purchased by the consumer from Regency
shown to be defective will be repaired or replaced at our discretion. No labor coverage is included with these parts.
Conditions:
Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at Regency's option, through an accredited distributor or agent provided that
the defective part be returned to the distributor or agent Transportation Prepaid, if requested.
Porcelain/Enamel - Absolute perfection is either guaranteed nor commercially possible. Any chips must be reported and inspected by an authorized dealer within three days of installation.
Reported damage after this time will be subject to rejection.
It is the general practice of Regency
manufacturer defect.
The authorized selling dealer is responsible for all in-fi eld service work carried out on your Regency® product. Regency will not be liable for results or costs of workmanship from unauthorized
service persons or dealers.
At all times Regency reserves the right to inspect product in the fi eld which is claimed to be defective.
All claims must be submitted to Regency® by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer name, purchase
date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim.
At no time will Regency® be liable for any consequential damages which exceed the purchase price of the unit. Regency® has no obligation to enhance or modify any unit once manufactured.
ie. as products evolve, fi eld modifi cations or upgrades will not be performed.
®
Regency
Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.
Embers, rockwool, gaskets, door handles and paint are not covered under the terms of this warranty policy.
Any unit which shows signs of neglect or misuse is not covered under the terms of this warranty policy.
The warranty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, negligence or accident,
spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by mechanical systems such as furnaces,
fans, clothes dryer, etc.
Freight damage to stoves and replacement parts is not covered by warranty and is subject to a claim against the freight carrier by the dealer.
Regency will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.
Performance problems due to operator error will not be covered by this warranty policy.
Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from Regency
this product.
Any alteration to the unit which causes sooting or carboning that results in damage to the interior / exterior facia is not the responsibility of Regency® .
* Subsidy according to job scale as predetermined by FPI.
will not be liable for travel costs for service work.
®
to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to Regency and evaluated for
®
after the original coverage has expired on the unit will carry a 90 day warranty, valid with a receipt only. Any item
®
, may nullify your warranty on
Regency Horizon™ HZ40E-2 Gas Fireplace
67
Page 68
Register your Regency® warranty online
www.regency-fi re.com
Reasons to register your product online today!
• View and modify a list of all your registered products.
• Request automatic email notifi cation of new product updates.
• Stay informed about the current promotions, events, and special
offers on related products.
Installer: Please complete the following information
Dealer Name & Address: ______________________________________________
___________________________________________________________________
Installer: ___________________________________________________________
Phone #: ___________________________________________________________
Date Installed: ______________________________________________________
Serial No.: __________________________________________________________