WARNING:
If the information in these instructions are not followed exactly,
a fi re or explosion may result causing property damage,
personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed
installer, service agency or the gas supplier.
919-271
Tested by:
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
Installer
Homeowner: Please keep these instructions for future reference.
: Please complete the details on the back cover
and leave this manual with the homeowner.
www.regency-fi re.com
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
08/19/13
MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
®
This Regency
standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88-2009 / CSA 2.33-2009 and GAS-FIRED APPLIANCES FOR
USE AT HIGH ALTITUDES CAN / CGA 2.17-M91.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home,
where not prohibited by local codes.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria
for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home
Standard in Canada.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence
of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA
70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1
in Canada.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as
applicable to local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the
National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
product has been tested and listed by Warnock Hersey/Intertek as a Direct Vent Wall Furnace to the following
This appliance can only be used with the type of gas indicated on the rating plate.
This appliance is not convertible for use with other gases.
Ensure that structural members are not cut or weakened during installation.
This appliance may be installed as an OEM installation in a manufactured home (USA only) or mobile home and must be
installed in accordance with the manufacturer's instruction and the Manufactured Home Construction and Safety Standard,
Title 24 CFR, Part 3280, in the Untied States, or the Standard for Installation in Mobile Homes, CAN/CSA Z240 MH, in
Canada.
2
Regency Horizon™ HZ40E-2 Gas Fireplace
To the New Owner:
Congratulations!
You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The HZ40E has been
designed to provide you with all the warmth and charm of a fi replace at the fl ick of a switch. The
model HZ40E has been approved by Warnock Hersey/Intertek for both safety and effi ciency . As
it also bears our own mark, it promises to provide you with economy, comfort and security for
many trouble free years to follow. Please take a moment now to acquaint yourself with these
instructions and the many features of your Regency
®
Fireplace.
Regency Horizon Gas Inserts Video
Regency Horizon™ HZ40E-2 Gas Fireplace
3
TABLE OF CONTENTS
SAFETY DECAL
Copy of Safety Decal .....................................................5
REQUIREMENTS
MA Code - CO Detector.................................................6
INSTALLATION
Important Message ......................................................8
Before You Start ............................................................8
General Safety Information............................................8
The Warranty: Limited Lifetime ...................................67
4
Regency Horizon™ HZ40E-2 Gas Fireplace
SAFETY LABEL
This is a copy of the label that accompanies
each HZ40E-NG2 and HZ40E-LP2 Direct Vent
Gas Fireplace. We have printed a copy of the
contents here for your review.
®
NOTE: Regency
improved. Check the label on the unit and if
there is a difference, the label on the unit is the
correct one.
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1.
This appliancemust be installed inaccordance with theStandard CAN/CSAZ240 MH, MobileHousing, in Canada,or with the ManufacturedHome Construction andSafety Standard,Title 24 CFR,Part 3280,in
the UnitedStates, orwhen such astandard isnot applicable,ANSI/NCSBCS A225.1/NFPA 501A, ManufacturedHome InstallationsStandard orANSIA119.2ou NFPA501C Standardfor Recreational Vehicles
This applianceis only foruse with the typeof gas indicatedon the ratingplate and may beinstalled inan aftermarket, permanentlylocated, manufactured (mobile) homewhere not prohibitedby local codes.See
owner's manualfor details.This appliance isnot convertiblefor use withother gases,unless a certifiedkit isused.
Installer l'appareilselon lescodes ou règlementslocaux, ou,en l'absence detels règlements,selon lescodes d'installationANSI Z223.1,National Fuel GasCode ouCSA-B149.1 envigueur.
Installer l'appareil selon la norme CAN/CSA-Z240, Série MM, Maison mobiles ou CAN/CSA-Z240 VC, Véhicules de camping, ou la norme 24 CFR Part 3280, Manufactured Home Construction and Safety
Standard. Si cesnormes ne sont pas pertinentes,utilisez la normeANSI/NCSBCS A225.1/NFPA501A, Manufactured Home InstallationsStandard, ouANSI A119.2 ou NFPA501C Standard for Recreational
Vehicles.
Cet appareildoit être utilize uniquement avecle type de gaz indiqué surla plaque signalétique. Cetappareil peut être installédans une maison préfabriquée ou mobile(É.-U. seulement) installée àdemeure si
les règlementslocaux lepermettent. Voirla notice del'utilisateur pourplus de renseignements.Cet appareiln'est pasconvertible pourune utilisation avecd'autres gaz,sauf siune troussecertifié est utilisé.
This ventedgas fireplaceheater is notfor usewith air filters.Ne pasutiliser defiltre à airavec cefoyer au gazà évacuation.
FOR USEWITH GLASSDOORS CERTIFIED WITHTHE APPLIANCEONLY
Fan (Part # 256-917)
Electrical supply / Électrique 115VAC, 1.13 A, 60Hz.
NOT FOR USE WITH SOLID FUELS. /
units are constantly being
COPY OF SAFETY DECAL
Listed:
VENTED GAS FIREPLACE HEATER /
Certified for/Certifi e pour:
Tested to:
ANSI Z21.88-2009/CSA 2.33-2009
MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE.
APPAREIL FONCTIONNANT AU NATURAL GAS
CONCU POUR ETRE POELE: Mod le HZ40E-NG2
Pression d'allimentation minimum
Pression à la tubulure d' chappement lev e
Grandeur de l'injecteur
D bitmaximum selon
Calorifique
é
l'altitude
ÉÉ
QUIP A L'UISINE POUR GAZ PROPANE
CONCU POUR ETRE POELE: Mod le HZ40E-LP2
Pression d'allimentation minimum
Pression à la tubulure d' chappement lev e
Grandeur de l'injecteur
D bitmaximum selon
Calorifique
é
l'altitude
ééé
ééé
POUR UTILISATION UNIQUEMENTAVECLES PORTES ENVERRE CERTIFIÉESAVEC L'APPAREIL
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
Serial No./ No de serie
412
Minimum Clearances to Combustibles /
é
é
FPI Fireplace Products International Ltd. Delta, BC, Canada
Degagement Minimum De Materiaux Combustibles
Side Walls
A8” (203mm)
B
D
C
DOOR SEAL: Please
check that the door is
A
E
properly sealed
Ceiling
F
B 22” (559mm)
Min. Mantel Height
C17" (432mm)
Max. Mantel Depth
D13” (330mm)
Alcove Width
E84" (1524mm)
Alcove Depth
F36" (2134mm)
(See Instruction Manual for
detailed instructions)
Made in Canada/ Fabrique au Canada
919-270
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfi tter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, fl exible con-
nectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appliances individual manual shut-off must be a
t-handle type valve.
The State of Massachusetts requires the
installation of a carbon monoxide alarm in
accordance with NFPA 720 and a CO alarm
with battery back up in the same room where
the gas appliance is installed.
Regency Horizon™ HZ40E-2 Gas Fireplace
5
REQUIREMENTS
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
MA Code - CO Detector
(for the State of Massachusetts only)
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
6
Regency Horizon™ HZ40E-2 Gas Fireplace
49-5/16"
45-5/8"
39-13/16"
DIMENSIONS
18-5/16"
16-1/2"1-7/16"
(318mm)
1
36
"
1
4
13
"
4
42"
16-7/8"
33-3/16"
31"
10"
(1092mm)
(972mm)
(1238mm)
(902mm)
(388mm)
4
1
15
(522mm)
(600mm)
(327mm)
(914mm)
Regency Horizon™ HZ40E-2 Gas Fireplace
7
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The Gas Fireplace must be installed in accordance
with these instructions. Carefully read all the
instructions in this manual fi rst. Consult the "authority
having jurisdiction" to determine the need for a permit
prior to starting the installation. It is the responsibility
of the installer to ensure this fi replace is installed
in compliance with manufacturers instructions and
all applicable codes.
BEFORE YOU START
Safe installation and operation of this appliance
requires common sense, however, we are required
by the Canadian Safety Standards and ANSI
Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD
BE DONE BY AN AUTHORIZED
SERVICE PERSON. THE APPLIANCE
SHOULD BE INSPECTED BEFORE
USE AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON.
MORE FREQUENT CLEANING MAY
BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, BEDDING
MATERIAL, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS
AND CIRCULATING AIR PASSAGEWAYS
OF THE APPLIANCE BE KEPT CLEAN.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE
IN THE SAME AREA AS THE APPLIANCE. TODDLERS, YOUNG CHILDREN
AND OTHERS MAY BE SUSCEPTIBLE
TO ACCIDENTAL CONTACT BURNS. A
PHYSICAL BARRIERS IS RECOMMENDED IF THERE ARE AT RISK INDIVIDUAL
IN THE HOUSE. TO RESTRICT ACCESS
TO A FIREPLACE OR STOVE, INSTALL
AN ADJUSTABLE SAFETY GATE TO
KEEP TODDLERS, YOUNG CHILDREN
AND OTHER AT RISK INDIVIDUALS OUT
OF THE ROOM AND AWAY FROM HOT
SURFACES.
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED
ON OR NEAR THE APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local codes or, in the absence of local codes, with
the current Canadian or National Gas Codes,
CAN1-B149 or ANSI Z223.1 Installation Codes.
2) The appliance when installed, must be
electrically grounded in accordance with local
codes, or in the absence of local codes with the
current National Electrical Code, ANSI/NFPA 70
or CSA C22.1 Canadian Electrical Code.
11) Under no circumstance should this
appliance be modified. Parts that have
to be removed for servicing should be
replaced prior to operating this appliance.
12) Installation and any repairs to this appliance
should be done by a qualifi ed service person.
A professional service person should be called
to inspect this appliance annually. Make it a
practice to have all of your gas appliances
checked annually.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid fuels
(wood, paper, cardboard, coal, etc.) be used in
this appliance.
15) The appliance area must be kept clear and free
of combustible materials, (gases and other fl ammable vapours and liquids).
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS
APPLIANCE CORRECTLY WILL VOID
YOUR WARRANTY AND MAY CAUSE A
SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE
ALERTED TO THE HAZARDS OF HIGH
SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND
SHOULD STAY AWAY TO AVOID BURNS
OR CLOTHING IGNITION.
3) See general construction and assembly
instructions. The appliance and vent should be
enclosed.
4) This appliance must be connected to the
specifi ed vent and termination cap to the outside
of the building envelope. Never vent to another
room or inside a building. Make sure that the
vent is fi tted as per Venting instructions.
5) Inspect the venting system annually for blockage
and any signs of deterioration.
6) Venting terminals shall not be recessed into a
wall or siding.
7) Any safety glass removed for servicing must be
replaced prior to operating the appliance.
8) To prevent injury, do not allow anyone who is
unfamiliar with the operation to use the fi replace.
9) Wear gloves and safety glasses for protection
while doing required maintenance.
10) Be aware of electrical wiring locations in walls
and ceilings when cutting holes for termination.
8
Regency Horizon™ HZ40E-2 Gas Fireplace
INSTALLATION
INSTALLATION
CHECKLIST
1) Locate appliance
a) Room location (Refer to "Locating Your Gas
fi replace" section)
b) Clearances to Combustibles (Refer to
"Clearances" section)
c) Mantel Clearances (Refer to "Mantel
Clearances" section)
d) Framing & Finishing Requirements (Refer
to "Framing & Finishing" section)
e) Venting Requirements (Refer to "Venting"
section)
2) Position nailing strips (Refer to "Unit Assembly
Prior to Installation).
3) Slide unit into place.
4) Remove installation access panel.
5) Install vent (Refer to "Venting Arrangement"
sections).
6) Make gas connections (Refer to "Gas Line
Installation section).
7) Make electrical connections to receptacle
supplied with unit (recommended).
8) Install 4 AA batteries into receiver/switch box
or use optional AC power adaptor.
9) T est the pilot (Refer to "Pilot Adjustment" section).
10) T est Gas Pressure (Refer to "Gas Pipe Pressure
Testing" section).
11) Install standard and optional features. Refer to
the following sections:
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label 26,000 Btu/h
(NG), 25,500 Btu/h (LP) after burning appliance
for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow the
unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your fi replace,
ensure that the clearances are met.
2) The appliance must be installed on a fl at, solid,
continuous surface For example a wood, metal
or concrete fl oor or in a raised (on the wall) ap-
plication. The appliance must be installed on
a metal or wood panel extending the full width
and depth of the appliance.
3) The HZ40E Direct Vent Gas Fireplace can be
installed in a recessed position or framed out
into the room as in A, B, C and D.
See Diagram 1.
4) This appliance is Listed for bedroom
installations using the standard Remote
(thermostat system). Some areas may have
further requirements, check local codes before
installation.
5) The HZ40E Direct Vent Gas Fireplace
is approved for alcove installations, see
"Clearances" section for details.
6) We recommend that you plan your installation
on paper using exact measurements for
clearances and fl oor protection before actually
installing this appliance. Have an authorized
inspector, dealer , or installer review your plans
before installation.
Note: For vent terminations refer to "Exterior
Vent Termination Locations" section.
HEATWAVE
DUCT SYSTEM
OPTIONAL KIT #946-556
The HeatWave Air Duct Kit increases the
effectiveness of your fi replace by dispersing warm
air from the fi replace to remote locations in the same
room or other rooms in your home.
Up to two kits may be installed on the fi replace. Please Note: Only 1 HeatWave kit may be oper-
ated at one time. This includes the internal blower
option as well.
a) Glass Crystals/ Optional Ceramic
Stones
b) Optional Firebox Base Pebbles
c) Optional Refl ective Panels
d) Optional Fan
e) Faceplate
f) Remote Control or Wall Thermostat
and 10ft. wire harness.
12) Reinstall installation access panel.
13) Final check.
Before leaving this unit with the customer, the
installer must ensure that the appliance is fi ring
correctly and operation fully explained to customer.
Regency Horizon™ HZ40E-2 Gas Fireplace
Diagram 1
A) Flat on Wall
B) Flat on Wall Corner
C) Recessed into Wall/Alcove
D) Corner
The HeatWave Duct Kit has different
clearance and framing requirements, check
the HeatWave manual for details.
OPTIONAL
HEAT RELEASE KIT
#946-570
The Heat Release Kit expels warm air from the
fi replace to the outside of the building, allowing
the fi replace to be operated with less heat entering
the room. The kit may be used on either the left
or right side.
9
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fi replace and vent system be installed only in accordance with these instructions.
The top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may NOT be
Caution Requirements
recessed into combustible construction.
Clearance:DimensionMeasured From:
A: Mantel Height (min.)17" (330mm)Top of Fireplace Opening
B: Sidewall (on one side)8" (203mm)Side of Fireplace Opening
E: Alcove Width84" (2134mm)Sidewall to Sidewall (Minimum)
F: Alcove Depth36" (914mm)Front to Back Wall (Maximum)
G: From Floor27" (686mm)Top of Fireplace Opening
Note:0"No hearth required
22" (559mm)Top of Fireplace Opening
if these clearances (air space) to combustible materials are not
Fire hazard is an extreme risk
adhered to. It is of greatest importance that this fi replace and vent
system be installed only in accordance with these instructions.
Passing through wall/
floor/ceiling - when
fi restop is used.
WARNING
The HeatWave Duct Kit and the Heat
Release Kit have different clearance
and framing requirements, check the
HeatWave and Heat Release manual
for details.
1-1/2"
D
F
A
G
E
B
Installed Close
to Floor
Installed close
to ceiling.
E
F
Alcove
10
Regency Horizon™ HZ40E-2 Gas Fireplace
MANTEL CLEARANCES
INSTALLATION
Due to the extreme heat this fi replace emits, the
mantel clearances are critical. Combustible mantel
clearances from top of front facing are shown in the
diagram on the right.
Note: Ensure the paint that is used on the mantel
and the facing is "high quality" or the paint
may discolour.
26
20
10
0
To Unit
Base
14
13"
22”
27”
(330mm)
1"
(559mm)
To p o f
Fireplace
Opening
21264810
(25mm)
17”
Combustible Material
Metal Stud
(On Edge)
Facing
Non-combustible
Standoff
Combustible mantel leg clearances as per diagram:
MANTEL LEG
Allowable mantel
legp rojection
Regency Horizon™ HZ40E-2 Gas Fireplace
MANTEL LEG CLEARANCES
7”
5-11/16”(144m
Non-Combustibl
4"
1.5" (38mm)
7-1/8” (181mm)
10”(203mm)
13”( 279mm)
m)
e
11
INSTALLATION
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The nailing Strips must be correctly positioned and attached before unit is
slid into position.
NAILING STRIPS
The nailing strips come attached to the unit. There is 1 plate on each side, 1
on the top. There also two on the bottom.
The top and side nailing strips are secured to the framing. The bottom
nailing strips are
Framing depth measurement is noted with the nailing strips
IMPORTANT NOTE
set as far forward on the fi rebox as possible. The nailing
strips can be adjusted back up to 1-1/2” to allow for varying
thicknesses in non-combustible material & wall fi nishes.
INST ALLATION ACCESS P ANEL
The unit is equipped with a removable access panel for pre-fi nish installation
of optional components - this panel is located on the lower front face.
1) Remove lower front face nailing strips (2 screws per nailing strip).
2) Remove 8 screws to remove access panel.
3) Easier access to gas connection with panel removed.
4) Install any optional components with access panel removed.
5) Reinstall access panel with 8 screws and lower front face nailing strips
(2 screws per strip) - prior to installing any facing material
Note: Access panel is no longer usable once facing material installed.
FRONT FACE NAILING STRIP
INSTALLATION
Nailing Strips
Installation Access Panel
Lower front nailing strips
Required when the combined facing/fi nishing material is 1/2".
If using material which is thicker than 1/2", the nailing strips are not
required and should be removed and discarded.
1) The 5 front nailing strips are only used if the facing/fi nishing material
is a combined 1/2" in thickness. This enables the facing and fi nishing
materials to be securely fastened to a solid surface.
2) Follow instructions on non-combustible facing installation for predrilling holes prior to attaching the noncombustible material supplied
with this unit.
3) The side/top nailing strips which are attached to this unit will also need
to be adjusted. See Framing and fi nishing in this manual.
* Framing depth measurement is noted with the nailing strips set as far forward on the fi rebox as possible.
The nailing strips can be adjusted back up to 1” to allow for varying thicknesses in non-combustible
material & wall fi nishes.
rywallor
other facing
Metal Stud (Header)
H
Note: All other framing may
be of wood construction.
D
A
Metal Stud
B
on edge
F
Finished Floor
Non-Combustible
Facing
G
Flex or Rigid Pipe
C1
C
E
C2
J
K
I
L
Regency Horizon™ HZ40E-2 Gas Fireplace
13
INSTALLATION
WALL MOUNT ON / OFF SWITCH AND BATTERY COMPARTMENT INSTALLATION
AND/OR RECEIVER INSTALLATION
REQUIRED FOR ALL INSTALLATIONS - INCLUDING PROFLAME REMOTE CONTROLS
IMPORTANT INSTALLATION NOTE:
The Receiver must be placed inside the supplied (Low Voltage)
junction type wall box and installed into the wall only.
DO NOT INSTALL WITHIN THE CONFINES OF THE FIREPLACE.
Remote Receiver Installation
1. Install the low voltage junction box to the framing, at desired location within 10 ft. from fi replace.
2. Feed the 12 pin connector through the opening at back of junction box.
3. Connect the 12 pin connector to the back of the receiver.
4. Install the Receiver in the Low Voltage Junction box.
5. Insert the 4 AA type batteries in the battery compartment with the correct polarity.
6. Place the slider into the cover plate.
7. Put the Receiver switch in the “OFF” position, to allow correct lineup for slider switch.
8. Make sure the Receiver and cover plate words “ON” and “UP” are on the same side.
9. Align the slider with the switch on the Receiver and couple the switch into the slider.
10. Align the screw holes.
11. Using the two (2) screws provided secure the cover plate to the Receiver.
Optional Profl ame Receiver
Slider Switch
Wall Plate
Low Voltage Junction Box
J-Box
Receiver
14
10 ft. wire harness with
12 pin connector
Diagram 1
Regency Horizon™ HZ40E-2 Gas Fireplace
INSTALLATION
NON-COMBUSTIBLE REQUIREMENTS
* Installation of the Receiver must be completed before installing non-combustible facing.
All three pieces (top, 2 sides) are now supplied to meet the non combustible requirements. Previously only the top was supplied.
Metal Stud (header)
Calcium silicate board is a high - grade material
with cement, quartz, natural and selected
minerals as the main raw materials. It is widely
used for partitions and ceilings in buildings.
It is fi re proof and earthquake proof.
If fi nishing the wall above the unit with materials
such as tile, brick, marble, etc. non-combustible
board available from the building supply store
can be used.
Note: Calcium Silicate is 1/2' thick
Metal Stud
(252mm)
20"
(508mm)
(351mm)
13-13/16”
10"
Non-combustible
5-11/16"
(144mm)
51-5/16" (1303mm)
Non-combustible
Material
Non-combustible
May be combustible (ie. 1/2” drywall)
on edge
Metal Stud
(859mm)
33 -13/16"
Non-combustible
NON-COMBUSTIBLE FACING INSTALLATION
Caution: The non-combustible board supplied with this unit can
be damaged if dropped or struck. Handle with care.
1) Using drywall screws - secure non combustible material
around unit, framing and top nailing strip every 6 inches.
Important Note: To avoid cracking the board - pre-drill holes prior to
securing to unit/ framing.
2) Wipe any debris/dust from the non combustible
material and drywall.
3) Prior to securing it is mandatory to prime the facing and edges
using a quality primer. This will ensure proper adhesion of both the
tape and mud. The supplied board is very porous.
Failure to follow this procedure will result in cracked seams.
4) Tape the seams using a mesh type tape.
5) Mud seams as normal. We recommend using a
product called Durabond high strength compound - for the fi rst coat.
This product can be found at any hardware store.
Mud must be cured as per manufacturer’s recommendations.
6) Prime wall for a second time for proper adhesion of paint
7) Paint walls using a high quality paint which will withstand
the high temperatures being emitted from this appliance.
Non-combustible board
shipped with unit.
Non-combustible board
shipped with unit.
Non-combustible board-faces and edges
MUST BE PRIMED.
Regency Horizon™ HZ40E-2 Gas Fireplace
15
INSTALLATION
FRAMING & FINISHING
1) Frame in the enclosure for the unit with framing material.
IMPORTANT: The framed opening must be of non-combustible
material.
Note: When constructing the framed opening, please ensure there
is access to install the gas lines when the unit is installed.
2) For exterior walls, insulate the enclosure to the same degree as the
rest of the house, apply vapour barrier and drywall, as per local installation codes. (Do not insulate the fi replace itself.)
WARNING: Failure to insulate and add vapor barriers to the inside
of the exterior wall will result in operational and performance
problems including, but not limited to: excessive condensation
on glass doors, poor fl ame package, carbon, blue fl ames etc.
These are not product related issues.
3) The unit does not have to be completely enclosed in a chase. You
must maintain clearances from the vent to combustible materials: See
"Clearances" section. Combustible materials can be laid against the
side and back standoffs and the stove base.
4) Non-combustible material (ie. tile, slate, etc) may be brought up to and
overlap the unit (top and bottom) ensuring that the maximum thickness
does not go beyond the 1-1/2" as shown in the diagram below. The
faceplate will not be able to be mounted if fi nished material is beyond
1-1/2".
5) If material such as brick, stone, etc extends past the faceplate depth (1-1/2"),
when fi nishing around the faceplate, the minimum opening dimensions noted
below must be adhered to ensuring for the removal of the faceplate and for
the safe operation of this appliance.
NOTE: Spacing of 1" around the completed surround must be adhered to.
52-3/4"
27-5/8"
Unit shown with 4 piece faceplate
47- 1/16”
1/2" required
between faceplate
+ fi nished wall
”
9/16
24-
Unit shown with inner and outer door frame
39-13/16”
16-7/8”
IMPORTANT: 1/2" gap required between faceplate and fi nished wall when
using 4 pce. Faceplate (Part # 256-924, 256-926, 256-927)
16
Unit shown with inner door frame only
Regency Horizon™ HZ40E-2 Gas Fireplace
FRAMING & FINISHING
INSTALLATION
Finished
Material
Nailing Strip
Position
1/2"1"
1"1/2"
1-1/2"0" (fl ush)
Nailing Strip
1” Forward
Unit
Nailing Strip
½” Forward
Unit
Nailing Strip
Flush w/unit
Factory Set
Note:
Depending on the material used for fi nishing, the nailing
strips must be set accordingly so that the fi nished material
is always at the 1-1/2" edge of the fl ange.
Metal Stud
10"
(252mm)
Unit
NON-COMBUSTIBLE REQUIREMENTS
Metal Stud (header)
51-5/16" (1303mm)
20"
(508mm)
(351mm)
13-13/16”
Non-combustible
Non-combustible
Material
Non-combustible
May be combustible (ie. 1/2” drywall)
on edge
Metal Stud
(859mm)
33 -13/16"
Non-combustible
(144mm)
Regency Horizon™ HZ40E-2 Gas Fireplace
5-11/16"
17
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
1
Minimum Clearance Requirements
A
Clearance above grade, veranda, porch, deck, or balcony12"(30cm)12"(30cm)
B
Clearance to window or door that may be opened 12"(30cm)9" (23cm)
C
Clearance to permanently closed window**
D
Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm)
from the center line of the terminal (check with the local code)
E
Clearance to unventilated soffi t19"(48cm)19"(48cm)
F
Clearance to outside corner: with AstroCap Termination Cap.7"(18cm)7"(18cm)
Clearance to outside corner: with all other approved Termination Caps.13"(33cm)13"(33cm)
G
Clearance to inside corner: with AstroCap Termination Cap 7"(18cm)7"(18cm)
Clearance to inside corner: with all other approved Termination Caps.13"(33cm)13"(33cm)
H
Clearance to each side of center line extended above meter/regulator assembly 36"(90cm)
J
Clearance to service regulator vent outlet36"(90cm)*
K
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance12"(30cm)9" (23cm)
L
Clearance to a mechanical air supply inlet #3' (91cm) above if within 10' (3m) horizontally.72"(1.8m)36"(90cm)
M
Clearance above paved sidewalk or a paved driveway located on public property 84"(2.1m)
N
Clearance under veranda, porch, deck, or balcony 12"(30cm)
1
In accordance with current CSA B149.1, Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
┼
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor
Clearance in accordance with local installation codes and the requirements of the gas supplier
*
a
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
b
3 feet (91cm) above - if within 10 feet (3m) horizontally
Canada
19"(48cm)19"(48cm)
a
┼
‡
USA
*
*
*
2
b
18
Regency Horizon™ HZ40E-2 Gas Fireplace
INSTALLATION
4” X 6-5/8” RIGID PIPE
CROSS REFERENCE CHART ONLY
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Chimney Conversion Kit A (USA only)46DVA-KCAN/AN/AN/AN/ATM-4CA6
Chimney Conversion Kit B (USA only)46DVA-KCBN/AN/AN/AN/ATM-4CA7
Chimney Conversion Kit C (USA only)46DVA-KCCN/AN/AN/AN/ATM-4CA8
Chimney Conversion Kit Masonry
(USA only)
Wall Firestop46DVA-WFSN/AN/AN/AN/ATM-4TR
Colinear Flex Connectors46DVA-ADFN/AN/AN/AN/AN/A
FPI
946-506/PVent Guard (Optional) for AstroCap946-205Vinyl Siding Shield for Riser Vent Terminal
510-994Rigid Pipe Adaptor (Must use with all rigid piping)946-208/PVent Guard (Optional) for Riser Vent Terminal
640-530/PRiser Vent Terminal946-523/PAstroCap Horizontal Cap
946-605Starter Collar Increaser 4” x 6-5/8” to 5” x 8”946-206Vinyl Siding Standoff for AstroCap
Note: When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection: Use this table to determine offset pipe lengths.
Pipe Length
(L)
0” (0mm)4-7/8” (124mm)13-7/8” (340mm)Simpson Direct Vent Pro: www.duravent.com
Note: Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination.
Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.
Run (X)Rise (Y)
46DVA-KMCN/AN/AN/AN/AN/A
4” x 6-5/8” VentingFor specifi c instructions on venting components - visit the
manufacturers website listed below.
20
Regency Horizon™ HZ40E-2 Gas Fireplace
VENT RESTRICTOR POSITION
Vent restriction is required for certain venting installations, see the diagrams in the "Venting
Arrangements" section to determine if they are required for your installation.
The Vent Restrictor plate is located on the inside top of the fi rebox.
To set the vent restriction as indicated in the venting arrangements diagrams, refer to the following instructions;
1) Remove the glass door - see instructions in this manual.
2) Remove the screws that hold the vent restrictor plate in place.
3) Adjust the vent restrictor plate to the required vent restrictor position as per the diagrams shown.
4) Once the vent restrictor plate is in the required position, secure with screws.
INSTALLATION
Set 0
(Factory set)
VENT RESTRICTOR
AT 3"
Regency Horizon™ HZ40E-2 Gas Fireplace
Set 1
VENT RESTRICTOR
AT 2"
Set 2
VENT RESTRICTOR
AT 1-1/2"
Set 3
VENT RESTRICTOR
AT 1"
21