Regency HZ33CE User Manual

Regency HZ33CE
Owners &
Installation Manual
Gas Fireplace
MODEL: HZ33CE-NG Natural Gas
HZ33CE-LP Propane
WARNING: If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
919-120a
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
HZ33CE Video
www.regency-fi re.com
FOR YOUR SAFETY What to do if you smell gas:
Do not try to light any appliance Do not touch any electrical switch:
do not use any phone in your building.
Immediately call your gas supplier
from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
11/13/13
To the New Owner:
Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The HZ33CE has been designed to provide you with all the warmth and charm of a fi re at the fl ick of a switch. The model HZ33CE has been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and
the many features of your Regency
®
Fireplace.
Horizon Benefi ts Video HZ33CE Video
2
Regency HZ33CE Gas Fireplace
MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regency® product has been tested and listed by Warnock Hersey as a Direct Vent Wall Furnace to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88 - 2009 / CSA 2.33 - 2009 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN / CGA 2.17-M91.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable to local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home, where not prohibited by local codes.
This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used. (Kit # 434-972).
Ensure that structural members are not cut or weakened during installation.
Regency HZ33CE Gas Fireplace
3
TABLE OF CONTENTS
SAFETY LABEL
Copy of Safety Decal .....................................................5
REQUIREMENTS
MA Code - CO Detector.................................................6
DIMENSIONS
Unit Dimensions ............................................................7
4 sided faceplate Dimensions........................................7
Mantel Dimensions ........................................................7
INSTALLATION
Important Message ......................................................8
Before You Start ............................................................8
General Safety Information............................................8
Installation Checklist ......................................................9
Locating Your Gas Fireplace .........................................9
Clearances ..................................................................10
Mantel Clearances.......................................................11
Mantel Leg Clearances................................................11
Framing & Finishing.....................................................12
Tile Finish ............................................................12
Clean Finish .........................................................13
Framing Dimensions....................................................14
Venting Introduction .....................................................15
Exterior Vent Termination Requirements .....................16
Regency® Direct Vent fl ex System ..............................17
Rigid Pipe Venting Systems ........................................18
4" X 6-5/8" RigiD Pipe Cross Reference Chart ............19
Rigid Pipe Venting Arrangements ...............................21
Vertical Termination with Co-Linear Flex System ........22
Venting Arrangements - Vertical Terminations ............23
Unit installation with Horizontal termination .................28
Unit installation with Vertical Termination ....................29
Gas Line Installation ....................................................29
Pilot Adjustment ...........................................................30
High Elevation .............................................................30
886 S.I.T. Valve Description .........................................30
Gas Pipe Pressure Testing ..........................................30
Conversion from NG to LP ..........................................31
Wiring Diagrams .........................................................35
Profl ame system GT ...................................................35
Profl ame system GTM ................................................36
Installing the Optional Fan (Prior to unit installation) ...38
Optional fan Wiring Diagram ......................................39
Installing the Optional Fan (installed unit) ...................39
Optional Wall Thermostat ...........................................41
Battery Installation .......................................................41
Optional Remote Control .............................................41
Wall Switch ..................................................................41
Aeration Adjustment ....................................................41
Optional Refl ective Panel Installation ..........................42
Glass Crystals AND optional stones ............................43
Installation On Burner and Firebox Floor.....................43
Optional Spa Stones Installation .................................43
Optional log set Installation .........................................44
Glass screen guard and Glass Door installation .........47
Standard Flush Door and screen.................................47
Optional 4-sided faceplate installation .................48
Optional mantel installation ..................................49
OPERATING INSTRUCTIONS
Operating Instructions .................................................50
First Fire ......................................................................50
Lighting Procedure ......................................................50
Shutdown Procedure ...................................................50
Normal Operating Sounds of Gas Appliances .............50
Copy of Lighting Plate Instructions ..............................51
MAINTENANCE
Maintenance Instructions.............................................52
General Vent Maintenance ..........................................52
Glass Door...................................................................52
Glass Replacement .............................................52
V alve Tray Replacement ..............................................53
PARTS LIST
Main Assembly ............................................................54
Accessories .................................................................55
WARRANTY
The Warranty: Limited Lifetime ...................................59
4
Regency HZ33CE Gas Fireplace
SAFETY LABEL
This is a copy of the label that accompanies each HZ33CE Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review.
®
NOTE: Regency
units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
COPY OF SAFETY DECAL
Duplicate S/N
Listed:
VENTED GAS FIREPLACE HEATER
Certified for/Certifi e pour:
4001172
Tested to:
ANSI Z21.88-2009/CSA 2.33-2009
MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE.
CAN/CGA-2.17-M91(R2009)
NATURAL GAS: Model HZ33CE-NG
Model/Modele:
HZ33CE
Minimum supply pressure Manifold pressure high Manifold pressure low Orifice size
-NG
Minimum input Maximum input Altitude
5" WC (1.25 kPa)
3.5" WC (0.87 kPa)
1.6" WC (0.39 kPa) # 47 DMS 12,000 Btu/h (3.51 kW) 17,000 Btu/h (4.98 kW) 0-4500 ft/pi (0-1372 m)
PROPANE: Model -LPHZ33CE
Model/Modele:
HZ33CE
Minimum supply pressure Manifold pressure high Manifold pressure low Orifice size
-LP
Minimum input Maximum input Altitude
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1. This appliancemust be installedin accordance with the Standard CAN/CSAZ240 MH,Mobile Housing, in Canada, or withthe Manufactured HomeConstruction and SafetyStandard, Title 24CFR, Part 3280,in the United States,or whensuch a standardis notapplicable, ANSI/NCSBCSA225.1/NFPA501A, Manufactured HomeInstallations Standard This appliance is onlyfor use with the type of gasindicated on the rating plate and maybe installed in an aftermarket, permanently located,manufactured (mobile) home where notprohibited by local codes. See owner's manualfor details. Installer l'appareilselon lescodes ou règlementslocaux, ou,en l'absence detels règlements,selon les codesd'installation ANSIZ223.1, NationalFuel Gas Codeou CSA-B149.1en vigueur. Installer l'appareilselon la normeCAN/CSA-Z240,Série MM, Maisonmobiles ou CAN/CSA-Z240VC, Véhiculesdecamping, ou lanorme 24 CFRPart 3280,Manufactured Home Constructionand Safety Standard. Si cesnormes nesont pas pertinentes,utilisez lanorme ANSI/NCSBCSA225.1/NFPA501A, Manufactured HomeInstallations Standard. Cet appareil doitêtre utilize uniquement avec letype de gaz indiqué surla plaque signalétique. Cet appareilpeut être installé dans unemaison préfabriquée ou mobile (É.-U.seulement) installée à demeure siles règlements locauxle permettent.Voir lanotice de l'utilisateurpour plusde renseignements. Cetappareil nepeut pas êtreutilisé avecd'autres gaz saufsi unetrousse de conversioncertifiée estfournie.
This ventedgas fireplaceheater is notfor usewith air filters. Nepas utiliser defiltre àair avec cefoyer augaz à évacuation.
For usewith glassdoors certified withthe applianceonly
Fan (Part# 432-917)
11" WC (2.73 kPa) 10" WC (2.49 kPa)
6.4" WC (1.59 kPa) # 56 DMS 12,500 Btu/h (3.66 kW) 15,000 Btu/h (4.39 kW) 0-4500 ft/pi (0-1372 m)
CANADA and U.S.A.é
APPAREIL FONCTIONNANT AU NATURAL GAS CONCU POUR ETRE POELE:
Pression d'allimentation minimum Pression a la tubulure d' chappement lev e Pression a la tubulure d' chappement basse Grandeur de l'injecteur D bit Califorique minimum selon
é
D bit Caliorfique maximum selon
é
l'altitude
APPAREIL FONCTIONNANT AU PROPANE CONCU POUR ETRE POELE:
Pression d'allimentation minimum Pression a la tubulure d' chappement lev e Pression a la tubulure d' chappement basse Grandeur de l'injecteur D bit Califorique minimum selon
é
D bit Caliorfique maximum selon
é
l'altitude
Pour utilisationuniquement avecles portes enverre certifiéesavec l'appareil
ééé é
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUELS.
NE PAS UTILISER AVEC DUCOMBUSTIBLE SOLIDE.FOYER AU GAZ À ÉVACUATION -
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
Minimum Clearances to Combustibles
Modéle -NG
HZ33CE
Modéle -LP
HZ33CE
ééé é
Degagement Minimum De Materiaux Combustibles
Ceiling
A
C
DOOR SEAL: Please check that
the door is properly sealed
(See Instruction Manual for Detailed Instructions)
Electrical supply/ Électrique115VAC,1.13A, 60Hz.
Made in Canada / Fabrique au Canada
406
Serial No./ No de serie
406
0" Clearance to combustibles from:
Sides, bottom and rear of unit *Top - 3-1/2" (89mm) non-combustible material required above unit.
Wall
Ceiling Clearances from Top Opening of Unit:
(A) 30" (762mm)
Side Wall Clearance from Side Opening of Unit:
B) 9"(229mm)
Floor Clearance:
Floor
FPI Fireplace Products International Ltd.
C) 0”
Alcove Clearances
D)E)Min. Width 84" (1219mm)
Max. Depth 36" (914mm)
Delta, BC, Canada
919-119
For the State of Massachusetts, installation and repair must be done by a plumber or gas fi tter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, fl exible con­nectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appli­ances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.
Regency HZ33CE Gas Fireplace
5
REQUIREMENTS
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
MA Code - CO Detector
(for the State of Massachusetts only)
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
6
Regency HZ33CE Gas Fireplace
16"
3
m
407mm
23"
584mm
DIMENSIONS
UNIT DIMENSIONS
34-9/16" [878mm]
16"
(406mm)
26"
660mm
29-7/16"
747mm
4 SIDED FACEPLATE DIMENSIONS
543mm
21-3/8"
3"
(76mm)
NAILING STRIP
29-1/4"
742mm
MANTEL DIMENSIONS
26-1/16"
(662mm)
2-1/2"
[64mm]
29-1/4"
742mm
42-5/16"
(1074mm)
Regency HZ33CE Gas Fireplace
6-3/8"
(162mm)
36-3/4"
(933mm)
2"
(51mm)
47-9/16"
9"
(229mm)
(1207mm)
29-9/16"
(750mm)
52-1/8"
(1324mm)
9"
(229mm)
21-1/2"
(545mm)
35-1/2"
(901mm)
5-1/8"
(130mm)
5"
(127mm)
8-1/8"
(206mm)
(76
7
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The HZ33CE™ Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fi replace is installed in compliance with manufacturers instructions and all applicable codes.
BEFORE YOU ST ART
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPE­CIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME AREA AS THE APPLI­ANCE. TODDLERS, YOUNG CHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO ACCIDENTAL CONTACT BURNS. A PHYSICAL BARRIERS IS RECOMMEND­ED IF THERE ARE AT RISK INDIVIDUAL IN THE HOUSE. TO RESTRICT ACCESS TO A FIREPLACE OR STOVE, INSTALL AN ADJUSTABLE SAFETY GATE TO KEEP TODDLERS, YOUNG CHILDREN AND OTHER AT RISK INDIVIDUALS OUT OF THE ROOM AND AWAY FROM HOT SURFACES.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
ANY SAFETY SCREEN, GUARD, OR BARRIER REMOVED FOR SERVICING THE APPLIANCE, MUST BE REPLACED PRIOR TO OPERATING THE APPLIANCE.
IF THE BARRIER BECOMES DAMAGED, THE BARRIER SHALL BE REPLACED WITH THE MANUFACTURER'S BARRIER FOR THIS APPLIANCE.
GENERAL SAFETY
INFORMATION
1. The appliance installation must conform with
local codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CAN1-B149 or ANSI Z223.1 Installation Codes.
2. The appliance when installed, must be electri-
cally grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Canadian Electrical Code.
3. See general construction and assembly in-
structions. The appliance and vent should be enclosed.
4. This appliance must be connected to the speci-
fi ed vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fi tted as per Venting instructions.
5. Inspect the venting system annually for blockage
and any signs of deterioration.
6. Venting terminals shall not be recessed into a
wall or siding.
7. Any safety glass removed for ser vicing must be replaced prior to operating the appliance.
8. To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fi replace.
9. Wear gloves and safety glasses for protection while doing required maintenance.
10. Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.
11. Under no circumstances should this appliance be modifi ed. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
12. Installation and any repairs to this appliance should be done by an authorized service per­son. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
13. Do not slam shut or strike the glass door.
14. Under no circumstances should any solid fuels
(wood, paper, cardboard, coal, etc.) be used in this appliance.
15. The appliance area must be kept clear and free of combustible materials, (gases and other fl ammable vapours and liquids).
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
8
Regency HZ33CE Gas Fireplace
INSTALLATION
INSTALLATION
CHECKLIST
1. Locate appliance:
a) Room location (Refer to "Locating Your
Gas fi replace" section)
b) Clearances to Combustibles (Refer to
"Clearances" section)
c) Mantle Clearances (Refer to "Mantel
Clearances" section)
d) Framing & Finishing Requirements
(Refer to "Framing & Finishing" section)
e ) Venting Requirements (Refer to "Venting"
section)
2. Assemble Top and Side Standoffs (Refer to
"Unit Assembly Prior to Installation).
3. Slide unit into place.
4. Install vent (Refer to "Venting Arrangement"
sections).
5. Make gas connections (Refer to "Gas Line
Installation section).
6. Test the pilot (Refer to "Pilot Adjustment"
section).
7. Test Gas Pressure (Refer to "Gas Pipe Pres-
sure Testing" section).
8. Install 4 AA batteries in the battery pack or
optional AC power adaptor.
9. Install standard and optional features. Refer
to the following sections:
This includes:
1. Clocking the appliance to ensure the correct
fi ring rate (rate noted on label), after burning appliance for 15 minutes.
2. If required, adjusting the primar y air to ensure
that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
LOCATING YOUR
GAS FIREPLACE
1. When selecting a location for your fi replace,
ensure that the clearances are met.
2. The appliance must be installed on a fl at,
solid, continuous surface For example a wood, metal or concrete fl oor or in a raised (on the wall) application. The appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
3. The HZ33CE Gas Fireplace can be installed
in a recessed position or framed out into the room as in A, B, C and D. See Diagram 1.
A) Flat on Wall
4. This appliance is Listed for bedroom
installations when used with a listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
5. The HZ33CE Gas Fireplace is approved for
alcove installations, see "Clearances" section for details.
6. We recommend that you plan your installation
on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.
Note: For vent terminations refer to "Exterior
Vent T ermination Locations" section.
a) Optional Refl ective Panels b) Glass Crystals or Optional Ceramic Stones c) Remote Control or Wall Thermostat
d) Optional Fan Assembly e) Optional 4 sided Faceplate f) Optional Mantel
10. Wall Mounted ON/OFF Switch: Use the toggle wall switch supplied with the
manual package. Use of a “decor” switch
causes higher resistance which is a problem
on gas fi replaces.
11. Final check.
Before leaving this unit with the customer, the installer must ensure that the appliance is fi ring correctly and operation fully explained to customer.
Diagram 1
B) Flat on Wall Corner C) Recessed into Wall/Alcove D) Corner
Regency HZ33CE Gas Fireplace
9
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fi replace and vent system be installed only in accordance with these instructions.
The top, back and sides of the fi replace are defi ned by
Caution Requirements
standoffs. The metal ends of the standoff may NOT
be recessed into combustible construction.
C
F
G
Fire hazard is an extreme risk
WARNING
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fi replace and vent
system be installed only in accordance with these instructions.
C
Clearance: Dimension Measured From:
A: *Front Floor Clearance (min.) B: *Sidewall (on one side)
C: *Ceiling (room and/or alcove)
D: Alcove Width E: Alcove Depth F: Mantel G: Mantel Clearances
10
0" Underside of Unit
9" (229mm) Side Opening of Unit
30" (762mm) Top Opening of Unit
84" (1219mm) Sidewall to Sidewall (Minimum)
36" (914mm) Front to Back Wall (Maximum)
12" (305mm)
15-3/4" (400mm)
From Top Opening of Unit
Close to Ceiling
Flue Clearances
Horizontal - Top 2-1/2"
Horiztonal - Side 1-1/2"
Horiztonal - Bottom 1-1/2"
Vertical (Flex Vent) 1-1/2"
Vertical (Rigid) 1-1/4"
Regency HZ33CE Gas Fireplace
MANTEL CLEARANCES
INSTALLATION
Due to the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel
clearances from top of front facing are shown in the diagram on the right.
Note: A non-combustible mantel may be
installed at a lower height if the framing is made of metal studs covered with a non-combustible board.
Note: Ensure the paint that is used on the mantel
and the facing is "heat resistant" or the paint may discolour.
12
16
14
12
10
15-3/4" (400mm)
8
6
4
2
0
Mantel Clearances
6
810
12" (305mm)
7-1/2"(191mm)
0” - 3-1/2" (89mm)
13-3/4"(349mm)
24-1/4"(616mm)
to floor
4
2
11-3/4"(298mm)
Top opening of Unit
0
Drywall
Non-combustible material
3"(76mm)
Standoff
MANTEL LEG CLEARANCES
Combustible mantel leg clearances from side of unit as per diagram:
Top View
Side opening of Unit
Side View
0-3
6-3/4"
Allowable mantel leg projection
9"
Regency HZ33CE Gas Fireplace
11
INSTALLATION
FRAMING & FINISHING
1. There are 8 (eight) side nailing strips and one top nailing strip available on the unit. One set of four (4) are for a clean fi nish installation, the other set are
for a tile fi nish installation as they are set back 1/2" (13mm). The top nailing strip is adjustable to 1/2" (13mm).
2. Bend the required four (4) nailing strips to 90º.
3. Attach top nailing strip with one (1) screw (located at the back of the nailing strip). Adjust to required position, flush or back 1/2" and tighten screw.
Adjustable Top
Nailing Strip
Nailing strip for
Clean Finish (set
ush with unit)
Nailing strip for
Nailing strip for
Tile Finish (set
back 1/2")
Tile Finish (set
back 1/2")
Nailing strip for
Clean Finish (set
ush with unit)
1. Frame in the enclosure for the unit with framing material.
Note: When constructing the framed opening, please ensure there is access to install the gas lines when the unit is installed.
2. For exterior walls, insulate the enclosure to the same degree as the rest of the house; apply vapour barrier and drywall, as per local installation codes. (Do not insulate the fi replace itself.)
WARNING: Failure to insulate and add vapor barriers to the inside of the exterior wall will result in operational and performance problems
including, but not limited to: excessive condensation on glass doors, poor fl ame package, carbon, blue fl ames etc. These are not product related issues.
3. The unit does not have to be completely enclosed in a chase. You must maintain clearances from the vent to combustible materials: See "Clearances"
section. Combustible materials can be laid against the side and back standoffs and the stove base.
4. Tile Finish Option 1: Drywall may be installed onto the unit as shown below to create a surface to apply fi nishing materials such as tile, slate, etc.
Drywall cannot extend beyond the metal surface of the unit.
5. Tile Finish Option 2: If applying a non-combustible fi nishing material (tile,slate,etc) the material can be installed directly onto the metal surface (clean front) of the unit in the area shown below.
TILE FINISH
Combustible Material
21-3/8"
[542mm]
Non-combustible Finishing Material (ie. tile)
Ensure finished material is brought to lip
Non-combustible Material (3-1/2" x 34-9/16")
Nailing Strip
-1/2" back from unit face
Supplied with Unit
12
29-7/16"
747mm
Non-combustible Finishing Material (ie. tile)
1-1/2
(38mm)
Combustible Material
Regency HZ33CE Gas Fireplace
INSTALLATION
CLEAN FINISH
6. If applying a non-combustible facing it may be installed over the metal surface (clean front) of the unit in the area shown below.
1/2" DRYWALL
3-1/2"
NON COMBUSTIBLE BOARD SUPPLIED WITH UNIT
34-9/16"
878mm
33-7/16"
[849mm]
Combustible and Non-combustible Facing and Finishing
Materials around unit.
[89mm]
WOOD STUD
DO NOT EXTEND DRYWALL ONTO METAL SURFACE OF UNIT.
NON-COMBUSTIBLE FACING
FOR CLEAN LOOK (ie. PAINTED FINISH)
1/2" DRYWALL
Non-combustible Finishing Material
Ensure finished material is brought to lip
Non-combustible Finishing Material
Combustible
Material
Non-combustible Material (3-1/2" x 34-9/16")
Nailing Strip
-flush with unit
1-1/2
(38mm)
Combustible Material
Supplied with Unit
NOTE: The 3-1/2" x 34-9/16" non combustible material supplied with this unit can be replaced if trying to achieve a clean fi nish. A large piece of non com-
bustible material (ie. 4' x 8' x 1/2") can be used to eliminate taped seams on or near unit.
7. Non-combustible material (ie. tile, slate, etc.) may be brought up to the edge of the glass door of the unit. Minimum clearances must be adhered to, this
will assure ease of glass door removal and access to the lower panel.
NOTE: Non-combustible fi nishing materials may be of any thickness desired.
NON COMBUSTIBLE BOARD SUPPLIED WITH UNIT
No Combustible
Materials in this Area
3-1/2" [89mm]
5-3/16"
[132mm]
No Combustible
Materials in this Area
[849mm]
33-7/16"
[542mm]
NO FACING OR
21-3/8"
FINISHING MATERIAL
IN THIS AREA
29-7/16"
2-1/2"
[64mm]
747mm
34-9/16"
878mm
Minimum Clearances for Finishing Materials
IMPORTANT FINISHING DETAIL NOTE:
Before placing unit into fi nal position - it is important to know the total thickness / height of fi nished hearth (tile, carpet, etc.) The base of the fi replace, 4 sided faceplate or mantel should be level or higher than the fi nished hearth height.
J Style trim or metal corner bead may be used to finish edges
29-7/16"
747mm
Trim materials
Note: All non-combustible facing material should butt up cleanly
to the fl anges around the fi rebox opening.
Rough edges may be visible from an angle.
To maintain a clean fi nished edge - facing material edges
may be fi nished with a J-style trim or metal cornerbead (both materials available at your local building or hardware store).
IMPORTANT: Materials used must be NON-COMBUSTIBLE.
21-3/8"
[542mm]
Regency HZ33CE Gas Fireplace
13
INSTALLATION
DETAILN
SCALE 1 : 6
2X4 HEADER
N
Non-combustible
Header
(steel stud
on edge)
FRAMING DIMENSIONS
M
H
I
NOTE: If this is an outside corner, the
minimum distance between the vent and the outside corner is 6" (15cm) with AstroCap termination cap or 12" (30cm) with Rigid Vent termination cap.
(For example Dura-Vent)
Framing Dimensions Description HZ33CE
G Framing Width 35"(889mm)
H Framing Height * 31-3/4" (806mm)
I Framing Rise from Floor 0" (when not using a surround)
J * For Finish with Tile
Surround
K Corner Wall Length 38-15/16" (988mm)
L Corner Facing Wall Width 55-1/2" (1410mm) M Framed Chase Ceiling* 36" (914mm) Rigid 32" (812mm) Flex
N
O
P Gas Connection Inset* 7-3/16" (183mm)
Q Gas Connection Width* 3" (76mm)
G
J
J
Floor
K
O
L
P
Q
3-5/16" min (when using 4 sided Faceplate)
Framing Depth Vertical Horizontal
Vent Centerline Height* 30" (762mm) Rigid 26" (660mm) Flex
Gas Connection Height* 1 1/2" (38mm)
19-3/4" (502mm) Rigid / 16" (406mm) Flex
Opening for gas
connection
2" min (when using Mantel)
22-3/4" (578mm) Vertical Rise
N
I
14
* Measured from base of unit.
Regency HZ33CE Gas Fireplace
INSTALLATION
VENTING INTRODUCTION
The HZ33CE uses the "balanced fl ue" technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
There are 5 vent systems approved for use with the HZ33CE: the Regency® Direct Vent Flex System for Horizontal Terminations only and the Simpson Dura-Vent, Selkirk Direct-Temp, Amerivent Direct Vent and Security Secure Vent Systems for Horizontal and Vertical Terminations (see following "Venting" Sections for more details).
Note: These fl ue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited. (See "Rigid Pipe Venting System" for more details and exceptions).
NOTE: Ensure compliance with the outside vent terminal location before cutting hole as both dimensions must be met.
Regency HZ33CE Gas Fireplace
15
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
1
Minimum Clearance Requirements
A Clearance above grade, veranda, porch, deck, or balcony 12"(30cm) 12"(30cm)
B Clearance to window or door that may be opened 12"(30cm) 9" (23cm)
C Clearance to permanently closed window **
D Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm)
from the center line of the terminal (check with the local code)
E Clearance to unventilated soffi t 15"(38cm) 15"(38cm)
F Clearance to outside corner: with AstroCap Termination Cap. 6"(15cm) 6"(15cm)
Clearance to outside corner: with all other approved Termination Caps. 12"(30cm) 12"(30cm)
G Clearance to inside corner: with AstroCap Termination Cap 6"(15cm) 6"(15cm)
Clearance to inside corner: with all other approved Termination Caps. 12"(30cm) 12"(30cm)
H Clearance to each side of center line extended above meter/regulator assembly 36"(90cm)
J Clearance to service regulator vent outlet 36"(90cm) *
K Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance 12"(30cm) 9" (23cm)
L Clearance to a mechanical air supply inlet
#3' (91cm) above if within 10' (3m) horizontally.
M Clearance above paved sidewalk or a paved driveway located on public property 84"(2.1m)
N Clearance under veranda, porch, deck, or balcony 12"(30cm)
1
In accordance with current CSA B149.1, Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor
Clearance in accordance with local installation codes and the requirements of the gas supplier
*
a
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
b
3 feet (91cm) above - if within 10 feet (3m) horizontally
Canada
18"(46cm) 18"(46cm)
a
72"(1.8m) 36"(90cm)
USA
*
*
*
2
b
16
Regency HZ33CE Gas Fireplace
INSTALLATION
REGENCY® DIRECT VENT FLEX SYSTEM
Horizontal Terminations Only
This venting system, in combination with the HZ33CE-4 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the "Exterior Vent Terminal Locations" Section .
Regency® Direct Vent Flex Termination Kit (Part # 946-513. includes all the parts needed to install the HZ33CE with a maximum run of 2 feet. If installing the HZ33CE-4 with a continuous vent length of more than 2 ft (.6m) to a maximum of 10 ft. (3.0m) use Kit # 946-515 (4 ft) or 946-516 (10 ft) or
see "Rigid Pipe Venting Systems" Section for alternate venting arrangements.
AstroCap Flex Kits
1
6-7/8" dia. fl exible liner (kit length)
2
4" dia. fl exible liner (kit length)
3
spring spacers (3.
4
thimble (2.
5
AstroCap termination cap (1.
6
screws (12.
7
tube of Mill Pac (1.
8
plated screws (8.
9
screws #8 x 1-1/2" drill point, stainless steel (4.
Notes:
1. Liner sections should be continuous without any joints or seams.
2. Only Flex pipe purchased from Regency® may be used for Flex installations.
MINIMUM
RIGID PIPE CENTER-LINE
Alternate
Horizontal
Termination
Caps
MINIMUM
FLEX KIT CENTER-LINE
Wherever necessary due to external location of cap, the AstroCap can be replaced with the FPI Riser Vent T er­mination Cap.
Note: - Unit must be raised by 1".
Regency HZ33CE Gas Fireplace
17
INSTALLATION
RIGID PIPE VENTING SYSTEMS
Horizontal or Vertical Terminations
The minimum components required for a basic horizontal termination are:
1 AstroCap Horizontal Termination Cap 1 45o Elbow 1 Rigid Pipe Adaptor 1 Wall Thimble 1 Length of pipe to suit wall thickness (see chart)
For siding other than vinyl, furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal must not be recessed into siding.
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2 inches.
Alternate
Horizontal
Termination
Caps
Vertical
Terminal
Storm Collar
Flashing
Ceiling Firestop
Pipe Length
o
90 Elbow
Pipe Length
Pipe Length
Vinyl Siding
Standoff (Optional)
Horizontal
Termination Cap
# 946-523/P
Wall Thimble
Adj.Pipe Length
11" - 14-5/8”
Horizontal
Termination Cap
#946-523/P
Vinyl Siding
Standoff (Optional)
Wall Thimble
19-3/4"
(502mm)
27"
(686mm)
o
45 Elbow
Rigid Pipe Adapter
# 510-994
Flat Wall Installation
Max. Wall Vent Length
Thickness (inches) Required (inches)
7 - 1/4" 6" 10 - 1/4" 9" 13 - 1/4" 12" 8 -1/4" 3" to 7" Slip 3" to 14-1/2 " Slip
13 - 1/4"
WARNING:
Do not combine venting components from different venting systems.
Exception: However, use of the the AstroCap and FPI Riser is acceptable with all systems.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Duravent Direct-Vent , Selkirk Direct-Temp, Ameri Vent Direct venting and Security Secure Vent systems. Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of components.
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
TM
18
The FPI AstroCap American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, Selkirk Direct-Temp. AstroCapTM is a proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
TM
and FPI Riser Vent terminal are cer tifi ed for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent,
Regency HZ33CE Gas Fireplace