These gas appliances have been tested
in accordance with AS4553-2000, NZS
5262 and have been certified by the
Australian Gas Association for
installation and operation as described
in these Installation and Operating
Instructions.
Your unit should be serviced
annually by an authorised service
person.
PLEASE KEEP THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause
injury or property damage. Refer to this
manual. For assistance or additional information consult an authorized installer, service agency or the gas supplier.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this
or any other appliance.
Installation and service must be performed
by an authorized installer, service agency or
the gas supplier.
918-318a
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical
switch: do not use any
phone in your building.
Immediately call your gas
supplier from a neighbour's
phone. Follow the gas supplier's instructions.
If you cannot reach your
gas supplier, call the fire
department.
05/26/06
To the New Owner:
Congratulations! You are the owner of a state-of-the-art Regency Rear Flued Room Sealed Freestanding Gas Stove by FPI
Fireplace Products International. The Regency Gas Series of hand crafted appliances has been designed to provide you
with all the warmth and charm of a woodstove, at the flick of a switch. The models FG37-NG, and F37-LPG of this series
has been approved by Warnock Hersey for both safety and efficiency. As it also bears our own mark, it promises to provide
you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint
yourself with these instructions and the many features of your Regency Rear Flued Room Sealed Freestanding Gas Stove.
2FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater
FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater3
DATA PLATE
This is a copy of the label that accompanies
each REGENCY Rear Flued Room Sealed Freestanding Gas Stove. We have printed a copy of
the contents here for your review. The data
plate is located on the inside of the drop down
pedestal door.
NOTE: Regency units are constantly being
improved. Check the label on the unit and if there
is a difference, the label on the unit is the correct
one.
(Australia Only)
4FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater
INSTALLATION
IMPORTANT:
SAVE THESE
INSTRUCTIONS
The REGENCY Rear Flued Room Sealed Freestanding Gas Stove must be installed in accordance AG601 and NZS 5261 and with these
instructions. Carefully read all the instructions
in this manual first. Consult the building authority
having jurisdiction to determine the need for a
permit prior to starting the installation.
Note: Failure to follow the instructions
could cause a malfunction of the
heater which could result in death,
serious bodily injury, and/or property damage. Failure to follow these
instructions may also void your
fire insurance and/or warranty.
SPECIFICATIONS
Fuels:FG37-NG is approved for use with
NG.
FG37-LPG is approved for use with
liquefied petroleum gases (LPG).
Safe installation and operation of this appliance
requires common sense, however, please be
aware of the following:
INSTALLATION AND REPAIRS
SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THIS APPLIANCE SHOULD BE INSTALLED,
REPAIRED, INSPECTED BEFORE
USE AND AT LEAST ANNUALLY
BY AN AUTHORIZED SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO
EXCESSIVE LINT FROM CARPETING, ETC. IT IS IMPERATIVE THAT
THE CONTROL COMPARTMENT,
BURNERS AND CIRCULATING AIR
PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES,
THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND
AWAY FROM FURNITURE AND
DRAPERIES.
WARNING: FAILURE TO INSTALL
THIS APPLIANCE CORRECTLY
WILL VOID YOUR WARRANTY AND
MAY CAUSE A SERIOUS HOUSE
FIRE.
CHILDREN AND ADULTS SHOULD
BE ALERTED TO THE HAZARDS OF
HIGH SURFACE TEMPERATURES,
ESPECIALLY THE FIREPLACE
GLASS, AND SHOULD STAY AWAY
TO AVOID BURNS OR CLOTHING
IGNITION.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN
THEY ARE IN THE SAME ROOM AS
THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE
PLACED ON OR NEAR THE APPLIANCE.
1) Provide adequate clearances for servicing, proper operation and around the air
openings into the combustion chamber.
2) The appliance must be installed on a flat,
solid, continuous surface (e.g. wood, metal, concrete). This may be the floor, or it can
be raised up on a platform to enhance its
visual impact. The appliance may be installed on carpeting, tile, wood flooring or
other combustible material, because the
appliance's metal pedestal base extends
the full width and depth of the appliance.
The REGENCY Rear Flued Room Sealed
Freestanding Gas Stove can be installed in
a wide variety of ways and will fit nearly
any room layout. It may be installed in a
recessed position, framed out into the room,
or across a corner.
3) The REGENCY Rear Flued Room Sealed
Freestanding Gas Stove is approved for
manufactured home installations, see pages 6 to 9 for the required flue arrangements.
If installed into a manufactured home the
unit must be bolted down to the floor.
4) We recommend that you plan your installation on paper using exact measurements
for clearances and floor protection before
actually installing this appliance. Have an
authorized building inspector review your
plans before installation.
GENERAL SAFETY
INFORMATION
1) The appliance shall be installed in accordance with the manufacturer's installation
instructions, local gas fitting regulations,
municipal building codes, water supply regulations, electrical wiring regulations, with
AS5601-2004 (AGA gas installation code)
NZS 5261 (New Zealand)
2) Installation and repair should be done
ONLY by an authorised person.
3) DO NOT CONNECT TO MASONARY FLUE.
4) This appliance must be connected to
the specified flue and termination cap
to the outside of the building envelope. Never flue to another room or
inside a building. Make sure that the
flue is fitted as per Flueing instructions.
5) Inspect the flueing system annually for
blockage and any signs of deterioration.
6) Flueing terminals shall not be recessed into
a wall or siding.
7) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fireplace.
9) Wear gloves and safety glasses for protection while doing required maintenance.
10) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for
termination.
11) Under no circumstances should this appliance be modified. Parts that have to be
removed for servicing should be replaced
prior to operating this appliance.
12) Installation and any repairs to this appliance
should be done by an authorised service
person. An authorised service person
should be called to inspect this appliance
annually. Make it a practice to have all of
your gas appliances checked annually.
13) Do not slam shut or strike the glass door.
FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater5
INSTALLATION
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
15) The appliance area must be kept clear and
free of combustible materials, (gases and
other flammable vapours and liquids).
INSTALLATION
CHECKLIST
1) Check Clearances to Combustibles (page
6), location of unit (page 6) and fluing
requirements (pages 6-9).
2) Install fluing: Check all fluing requirements,
pages 8-12.
3) Make gas connections, page 12. Test the
pilot. Must be as per diagram, pages 15 &
22.
4) If necessary, convert from NG to LPG (page
13).
5) Install log set, page 15.
LOCATING YOUR
REGENCY GAS STOVE
When selecting a location for your stove, ensure that the clearances listed above are met as
well as ensuring that there is adequate accessibility for servicing and proper operation.
For Flu Termination requirements, see page 7.
This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
This appliance is Listed for Alcove installations,
maintain minimum Alcove clearances as follows, minimum ceiling height of 1.7m, minimum
width of 1.0m and a maximum depth of 0.9m.
Use the minimum clearances shown in the
diagrams below:
FG37-NG & FG37-LPG Clearances
A Side Wall to Unit190 mm
B Back Wall to Unit76 mm
E Side Wall to Unit114 mm
FG37-NG & FG37-LPG
Reference Dimensions
C Floor to Flue Centerline635 mm
D Side Wall to Flue Centerline 521 mm
6) Install Front Door Front, page 16.
7) Test Gas Pressure, page 17.
8) Install Louvres, page 17.
9) Install optional Remote Control, page 18.
10) Final check, page 18.
Before leaving this unit with the customer, the
installer must ensure that the appliance is firing
correctly and operation fully explained to
customer.
This includes:
1) Clocking the appliance to ensure the cor-
rect firing rate (rate noted on label) after
burning appliance for 15 minutes.
2) If required, adjusting the primary air to
ensure that the flame does not carbon. First
allow the unit to burn for 15-20 min. to
stabilize.
CAUTION: Any alteration to the product
that causes sooting or carboning that
results in damage is not the responsibility of the manufacturer.
A ) Cross Corner
B)Flush with Wall/Alcove
C) Flat on Wall Corner
D) Flat on Wall
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance
and the chimney connector. The farthest
distance is correct if the two clearances
do not coincide. For example, if the appliance
is set as indicated in one of the diagrams but the
connector is too close, move the stove until the
correct clearance to the connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type
of installation with another in order to
achieve closer clearances.
Minimum ceiling height
is 914 mm from top of
unit.
COMBUSTION AND
VENTILATION AIR
The combustion air from this appliance is drawn
from outside the building through the outer flue.
Extra provision for combustion air inside
the room is not required.
This unit can be installed on a solid combustible
surface like a wood floor. This unit can also be
installed directly on carpeting or vinyl when the
bottom pedestal cover plate (provided with unit)
is installed.
6FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater
INSTALLATION
EXTERIOR FLUE TERMINATION LOCATIONS
Minimum clearances required for balanced flue terminals or
the flue terminals of outdoor appliances
according to AS5601-2004 (AGA gas installation code) or NZS 5261 (New Zealand)
Minimum
a Below eaves, balconies or other projections:
- Appliances up to 50 MJ/h input300
- Appliances over 50 MJ/h input500
b From the ground or above a balcony300
c From a return wall or external corner500
d From a gas meter (M)1000
e From an electricity meter or fuse box (P)500
fFrom a drain or soil pipe150
g Horizontal from any building structure (unless appliance is approved
for closer installation) or obstruction facing a terminal500
h From any other flue terminal, cowl or combustion air intake500
jHorizontally from an openable window, door, or non-mechanical air inlet, or
any other opening into a building, with the exception of sub-floor ventilation
(see also Note (I)):
- Appliances up to 150 MJ/h input500
- Appliances over 150 MJ/h input1500
k Vertically below an openable window, door, or non-mechanical air inlet,
or any other opening into a building, with the exception of sub-floor ventilation
(see also Note (I)): see table below
Clearance (mm)
Clearance 'k' in mm
Space Heaters All Other Appliances
Up to 50 MJ/hUp to 50 MJ/h inputOver 50 MJ/h inputOver 150 MJ/h input
input to 150 MJ/h input
15050010001500
NOTES:
(I) For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases.
(II) All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest
par to of the terminal.
(III) Prohibited area below electricity meter or fuse box extends to ground level.
(IV)A flue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on
at least two sides and a free flow of air at the appliance is achieved.
FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater7
INSTALLATION
FLUING
The Regency Room Sealed System (Horizontal
Termination Kit (946-110) and the Vertical Termination with the Co-linear Flex System in
combination with the REGENCY Room SealedRear Freestanding Gas Stoves (FG37-NG and
FG37-LPG) have been approved and listed as
Room Sealed heater systems by Australian
Gas Association.
The Horiz. Termination Kit (946-110) includes
everything required for a straight through the
wall installation, or add a 45
installation.
IMPORTANT
Read all instructions carefully before starting
the installation. Failure to follow these instructions may create a fire or other safety hazard,
and will void the warranty. Be sure to check the
fluing and clearance to combustible requirements on pages 6 to 9. Consult your local
building codes before beginning installation.
The location of the termination cap must conform to the requirements in the Exterior Flue
Terminal Locations diagram on page 7.
o
elbow for a corner
FLUING
INSTALLATION
PRECAUTIONS
The Regency Room Sealed System and the
Vertical Termination with the Co-linear Flex
System are engineered products that have
been designed and tested for use with the
FG37-NG, and FG37-LPG. The Regency warranty will be voided and serious fire, health or
other safety hazards may result from any of the
following actions:
1) Installation of any damaged Room Sealed
component
2) Unauthorized modification of the Room
Sealed System
3) Installation of any component part not manufactured or approved by Regency Industries Ltd.
4) Installation other than as instructed by Regency Industries Ltd.
Warning: Always maintain required
clearances (air spaces) to nearby
combustibles to prevent a fire hazard. Do not fill air spaces with insulation.
The minimum clearance requirements between
the outer wall of the flue pipe and nearby
combustible surfaces is 30mm. Be sure to
check the flue termination clearance requirements from decks, windows, soffits, gas regulators, air supply inlets and public walkways
as specified on page 7 and in your local building
codes.
The gas appliance and flue system
must be flued directly to the outside
of the building, and never be attached to a chimney serving a separate solid fuel or gas-burning appliance.
Each Room Sealed gas appliance must use its
own separate flue system. Common flue systems are prohibited.
SAFETY
PRECAUTIONS FOR
THE INSTALLER
1) Wear gloves and safety glasses for protection.
2) Exercise extreme caution when using ladders or on roof tops.
3) Be aware of electrical wiring locations in
walls and ceilings.
PLANNING YOUR FLUING INSTALLATION
See page 7 for Exterior Flue Termination
requirements.
When planning your installation, it will be necessary to select the proper length of flue pipe
for your particular requirements. Determine the
minimum clearance to combustibles from the
rear of the unit to the wall. It is also important to
note the wall thickness. Before cutting the flue
hole through the wall ensure that ALL flue and
termination clearances (see page 7) will be met.
NOTE: Ensure compliance with the outside
flue terminal location before cutting hole as
both dimensions must be met.
*If this is an outside corner, the minimum distance between the flue and the outside corner
is 12" (30cm). See "F" on the diagram on page 7.
For corner installation, Restrictor must
be set at 1-1/4" (32mm) open.
For straight rear installation, Restrictor must be set at 1-1/8" (29mm) open.
8FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater
INSTALLATION
Vent Restrictor
Vent
Restrictor
Plate
Vent Restrictor
(fully open)
Vent
Restrictor
Plate
44.5mm44.5mm
32mm32mm
FLUING ARRANGEMENTS - VERTICAL TERMINATIONS
FOR BOTH RESIDENTIAL & MANUFACTURED HOMES/MOBILE HOMES
Vertical Terminations
with Co-linear Flex System
The shaded area in the diagram shows the allowable vertical
terminations installed in a masonry chimney. All vertical flue
installations require the Flue Restrictor to be set to 32mm open. All
Vertical Flue Terminals must be Simpson Dura Vent (Abey Australia)
DV 980 MAS (Australian Modified.)
Straight Vertical Terminations
9
8
7
6
5
4
216mm
9.1m Max.
Vertical Terminations
using Dura-Vent Fluing System
The shaded areas in the two diagrams below show all allowable
combinations of straight vertical and offset to vertical runs with
vertical terminations. Maximum one 90o elbow. All vertical and
offset to vertical flue installations require Flue Restrictor to be set to 32mm
open. If the flue is ENCLOSED in a chase (min. size 229mm x 229mm)
maintain a 32mm clearance to combustibles. All Vertical Flue Terminals
must be Simpson Dura Vent (Abey Australia) DV 980 MAS (Australian
Modified.)
Offset to Vertical Terminations
If connecting to a Dura-Vent system, the Adapter to Dura-Vent #
640-994 is required.
3
Vertical Height (meters)
1
1
2
1
Horizontal Distance (meters)
1
3.2m Min.
2
Flue Restrictor Position
To set the Flue restriction
as indicated in the diagram,
simply loosen the screws
and push the flue restrictor
plate to the correct position.
Tighten the screws.
FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater9
INSTALLATION
RESIDENTIAL AND MANUFACTURED HOMES/
MOBILE HOMES INSTALLATIONS
You will require the following components with your new Regency Rear Flued Room Sealed Freestanding Gas Stove. Please review your product
to make sure you have everything you need. In the event that you are missing any part, contact your dealer.
Note: These are the minimum pieces required.
Other parts may be required for your particular installation.
1946-2016-5/8" dia. x 18" (168mm dia. x 457mm) Black Pipe
1946-2074" dia. x 18" (102mm dia. x 457mm) Aluminum Flue
1946-584Astro Riser Vent Terminal
1946-202Wall Penetration Heat Shield for Heat Sensitive walls
(Wall Thimble) (2 pcs)
1640-545Decorative Wall Trim (Black)
1948-128Tube Mill-Pac
Screws
and 4" (102mm) Aluminum Flue
Terminal
Heat Shield*
* Simpson Dura-Vent components
HORIZONTAL INSTALLATIONS
1) Set the unit in its desired location. Check to
determine if wall studs are in the way when
the fluing system is attached. If this is the
case, you may want to adjust the location
of the unit.
2) Assemble the desired combination of pipe
and elbow to the appliance adapter with
pipe seams oriented down. Offset the pipe
seams as double seams in one place will
cause the outer pipe to take an oval shape.
Kit comes complete with 18" (457mm) of
straight flue - 6-5/8" (168mm) dia. black
outer pipe and 4" (102mm) dia. inner flue.
3) With the pipe attached to the stove, slide the
stove into its correct location, and mark the
wall for a 9-1/2" (241mm) (inside dimensions) round hole. The center of the round
hole should line up with the centerline of the
horizontal pipe, as shown in diagram 1. Cut
and frame the 9-1/2 (241mm) round hole in
the exterior wall where the flue will be
terminated. If the wall being penetrated is
constructed of non-combustible material,
i.e. masonry block or concrete, a 7" (178mm)
diameter hole is acceptable.
Note:
a) The horizontal run of flue should have
a 1/4 inch (6mm) rise for every 1 foot
(305mm) of run towards the termination. Never allow the flue to run downward. This could cause high temperatures and may present the possibility of
a fire.
b) The location of the horizontal flue termi-
nation on an exterior wall must meet all
local and national building codes, and
must not be blocked or obstructed. For
External Flue Terminal Locations, see
diagram on page 7.
Diagram 1
c) Snorkel Terminations:
For installations requiring a vertical rise
on the exterior of the building, Astro
Riser Vent Terminations as shown in
Dia. 2 is available. Follow the same
installation procedures as used for
standard Horizontal Termination.
NEVER install the Astro Riser vent upside down.
Diagram 2
*Dia 2: Local codes or regulations may require
different clearances.
10FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.