E: Alcove Width84" (2134mm)Side wall to side wall (min.)
F: Alcove Depth36" (914mm)Front of Unit
G: To Enclosure Ceiling (min/max)0-3" (76mm)From top of enclosure
H: Convection Air outlet 120 sq. inches (min)* Top/front or side of enclosure
I: Enclosure Depth (min.)
J: Opening Height
K: To Ceiling (min) All 3 sides
L: Chase Enclosure (min.)
M: Clearance to Sprinkler Head (Min.)
Hearth0"No hearth required
** See mantel clearances chart in this section
* A minimum of 120 square inches of open area, not lower than 3" from top of enclosure, required for all
installations — this can be achieved by having an open area in front, each side, and/or above as shown
in the four diagrams on the next page.
DimensionMeasured From:
19" (483mm)
15-1/16" (383mm)
1-1/2"
63" (1600mm)
36" (914mm)
Minimum inside dimensions
Bottom/Top of Fireplace Opening
To Top of Ceiling
From base of unit/floor
Perpendicular from chase grill
Flue Clearances to
Combustibles
Horizontal - Top3"
Horizontal - Side 2"
Horizontal - Bottom2"
Vertical2"
Passing through wall/floor/
ceiling - when firestop is
used.
1-1/2"
E
F
Alcove
The HeatWave Duct Kit has
different clearance and framing
requirements, check the HeatWave
manual for details.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this replace and vent
system be installed only in accordance with these instructions.
M
Chase grill
Side view
Sprinkler
L
Page 3
City Series Power Vent
CB40EPV Gas Fireplace
CLEARANCES CB40EPV
H
K
I
L
A1
A
Floor to ceiling with top opening
G
C
D
J
B
H
I
L
A1
H
H
C
D
A
G
J
B
Low framing with vents in front/sides or top
G
H
H
G
G
H
I
A1
L
A
H
C
D
Full framing with low vents in front or sides
G
L
I
J
B
B
A
C
D
J
Full framing with vents in front or sides
Page 4
City Series Power Vent
CB40EPV Gas Fireplace
FRAMING DIMENSIONS CB40EPV
NOTE: Framing may be constructed of combustible material (ie. 2x4) and does not require steel studs. Two (2) optional steel stud kits may also
be purchased. These kits may be used in place of the conventional wood framing as shown below. It comes as a compact kit (flush to the
appliance on all sides)or an extended kit. The extended kit protrudes beyond each side of the appliance as shown on the front cover of
this manual. There is also an optional hearth kit which may be purchased as shown on the front cover of this manual. These kits are highly
recommended as it was designed specifically for the product to facilitate ease of installation. See instructions in this manual for details.
Note: A combined minimum of 120 square inches of open area is required for the convection air outlet to cool the enclosure. Ensure clearances
for Convection Air Outlets are met. See clearances CB40E in the unit manual as there are different methods as to how this can be achieved.
Note: Only basic framing dimensions are shown. The framing may also extend beyond the appliance on either side and also extend out front if a
hearth is desired. See clearance/finishing requirements for details.
Note: Unit is not load bearing. All finished materials must be supported by framing.
DescriptionCB40EPV
Maximum material
dimensions 2" x 4" for
Header studs (installed
on edge and flat)
Note: This appliance must be installed on
a solid surface such as a plywood floor
which must be the full width and depth of
the appliance.
Page 5
City Series Power Vent
CB40EPV Gas Fireplace
2126 4810
14
20
1/2" Drywall, wood, wood panel, etc.
MANTEL CLEARANCES CB40EPV
Due to the extreme heat this fireplace emits, the
mantel clearances are critical.
Combustible mantel clearances from top of front facing
are shown in the diagram on the right.
Note: Ensure the paint that is used on the mantel
and the facing is "high quality" or the paint
may discolour.
26
10
12" (305mm)
9
"
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram:
CB40E
MANTEL LEG
0
To
Bottom
Fireplace
Opening
of
15-1/16”
5-1/8"
Top o f
Fireplace
Opening
12"
8-1/2"
Page 6
City Series Power Vent
Horizontal (Feet)
Vertical (Feet)
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
8
Horizontal(Feet)
4
0
610
12
16181420
2224
32342826303638
Restrictor – Fully Open
2
72' overall length Max.
(shown with 5 - 90º elbows)
72' run (no rise)
72' overall length Max.
(shown with 5 - 90º elbows)
CB40EPV Gas Fireplace
VENTING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS
RIGID PIPE: MUST USE RIGID PIPE ADAPTOR 770-994 AND 946-606 PIPE REDUCER TO 4" X 6 5/8"
Note: Rigid pipe is approved for up to 72 feet.
Note: Flex pipe is approved for up to 40 feet using 2 X 946-756-- 20 foot flex kits.
The gas power vent system is designed to allow the installation of a gas appliance when typical vent configurations (shown in this manual) are
not possible.
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
-2
-3 Ft. max.
-4
-6
-8
0
8
610
4
2
16181420
12
72' overall length Max.
(shown with 5 - 90º elbows)
2224
72' overall length Max.
(shown with 5 - 90º elbows)
Restrictor – Factory Set @ 1"
Shown with 2 elbows (negative run 72')
32342826303638
72' run (no rise)
4046485054 56525860
4244
6264 666870
72
Important: Minimum overall vent run must be 4 feet.
Maximum total vent length = 72' maximum of six - 90° elbows permitted.
Maximum total negative vent length = 7'.
Note: Maximum length of 72 feet is based on overall length of combined
One 90° elbow = two 45° elbows.
chimney components.
Page 7
City Series Power Vent
Powervent Kit
(Part #946-535)
CB40EPV Gas Fireplace
HORIZONTAL TERMINATIONS
Rigid Pipe 4" x 6-5/8"
The minimum components required for a basic horizontal termination
are:
1 Power Vent Kit
1 Rigid Pipe Adaptor
1 Length of pipe to suit wall thickness and total vent run
(see Table 1)
Wall thickness is measured from the back standoffs to the inside mounting
surface of termination cap. Create a level surface to mount the vent terminal.
The Terminal must not be recessed into siding. Measure the wall thickness.
Flat Wall Installation
Wall Thickness
(inches)
4" - 5-1/2"6"
7" - 8-1/2"9"
10" - 11-1/2"12"
9" - 14-1/2'11" - 14-5/8" Adj. Pipe
15" - 23-1/2"17" - 24" Adj. Pipe
Vent Length Required
(inches)
o
90 Elbow
Adj.Pipe Length
Table 1
Pipe Length
Vent reducer(Part #946-606)
Rigid Pipe Adapter
Page 8
City Series Power Vent
CV40EPV / CB40EPV / CC40EPV
Gas Power Vent Installation CV40EPV / CB40EPV / CC40EPV - Rigid Vent
GAS POWER VENT INSTALLATION CB40EPV - RIGID VENT
The Power Vent System is a Direct Vent Te rminal designed to allow installation of gas appliances where typical vent confi gurations cannot be achieved.
These installation instructions must be used in conjunction with the appliance and appropriate Power Vent components installation instructions.
120 Volt power supply is required to operate this system.
Models Equipped with Surefi re Ignition
The Power Vent system can only be used with units that have been tested with the Regency Power Vent system.
Downward vertical vent runs are permitted with the Surefi re Ignition system. See vent confi guration in unit manual.
CB40EPV Gas Fireplace
Rigid Pipe Adaptor
(Required,sold separately)
CB40EPV Shown
4" x 6-5/8" Rigid pipe lengths
(sold separately)
Slip Section
(sold separately)
Power Vent Terminal
(946-535)
BX Cable
(sold separately)
Frame Assembly
(included w/Power Vent kit)
Power Vent frame
(adjustable depth)
(incl. with Power V ent
kit)
Power Vent trim
(incl. with Power V ent
kit)
946-535 Power Vent Kit with Vent Terminal
1510-994Rigid Pipe adaptorsold separately
1Power Vent Fa nincluded w/Power Vent kit
1Power Vent Frameincluded w/Power Vent kit
1911-250/P45' 5-wire BX cable orsold separately
1911-251/P90' 5-wire BX cablesold separately
amount required
for install
1946-535Power Vent Kitsold separately
4" x 6-5/8" Rigid Pipesold separately
Power vent frame
Power vent trim
Page 9
City Series Power Vent
CV40EPV / CB40EPV / CC40EPV
Gas Power Vent Installation CV40EPV / CB40EPV / CC40EPV - Flex Vent
The Power Vent System is a Direct Vent Te rminal designed to allow installation of gas appliances where typical vent confi gurations cannot be achieved.
CB40EPV Gas Fireplace
GAS POWER VENT INSTALLATION CB40EPV - FLEX VENT
These installation instructions must be used in conjunction with the appliance and appropriate Power Vent components installation instructions.
120 Volt power supply is required to operate this system.
Models Equipped with Surefi re Ignition
The Power Vent system can only be used with units that have been tested with the Regency Power Vent system.
Downward vertical vent runs are permitted with the Surefi re Ignition system. See vent confi guration in unit manual.
Max. 2 x 20' Flex kits (946-756)
(sold separately)
Power Vent Terminal
(946-535)
Frame Assembly
(included w/Power Vent kit)
CV40EPV Shown
BX Cable
(sold separately)
946-535 Power Vent Kit with Vent Terminal
2 Max. 946-75620' Flex Kitsold separately
1Power Vent Fa nincluded w/Power Vent kit
1Power Vent Frameincluded w/Power Vent kit
1911-250/P 45' 5-wire BX cable orsold separately
1911-251/P 90' 5-wire BX cablesold separately
1946-535Power Vent Kitsold separately
Power Vent frame
(adjustable depth)
(incl. with Power V ent
kit)
Power Vent trim
(incl. with Power V ent
kit)
Power vent frame
Power vent trim