Regency B36XTCE User Manual

Regency Bellavista
B36XTCE
Gas Fireplace
Owners &
Installation Manual
MODEL: B36XTCE
Medium DV Gas Fireplace
WARNING: If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
Bellavista
B36XTCE Video
www.regency-fi re.com
FOR YOUR SAFETY What to do if you smell gas: Do not try to light any appliance Do not touch any electrical switch:
do not use any phone in your building.
Immediately call your gas supplier
from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
919-154
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
10/30/13
To the New Owner:
Congratulations!
®
Y ou are the owner of a state-of-the-art Gas Fireplace by REGENCY
. The Bellavista™ B36XTCE has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The Bellavista™ B36XTCE has been approved by Warnock Hersey/Intertek for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency® Fireplace.
Bellavista B36XTCE
2
Bellavista B36XT
Gas Fireplace Benefi ts
Regency B36XTCE Gas Fireplace
MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regency® product has been tested and listed by Warnock Hersey as a Direct Vent Wall Furnace to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88-2009 / CSA 2.33-2009 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN / CGA 2.17-M91.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable to local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home, where not prohibited by local codes.
This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
Ensure that structural members are not cut or weakened during installation.
Regency B36XTCE Gas Fireplace
3
TABLE OF CONTENTS
SAFETY LABEL
Copy of Safety Decal .....................................................5
REQUIREMENTS
MA Code - CO Detector.................................................6
DIMENSIONS
Unit Dimensions ............................................................7
INSTALLATION
Important Message ......................................................8
Before You Start ............................................................8
General Safety Information............................................8
Installation Checklist .....................................................9
Locating Your Gas Fireplace .........................................9
Clearances ..................................................................10
Mantel Clearances.......................................................11
Mantel Leg Clearances................................................12
Non- Combustible Requirements: ...............................12
Framing ......................................................................13
Framing & Finishing.....................................................14
Tile Finish ............................................................14
Clean Finish .........................................................14
Unit Assembly Prior to Installation ...............................16
Top Standoff Assembly ........................................16
Nailing strips ........................................................16
Venting Introduction .....................................................18
Vent Restrictor, Baffl e & Heat Defl ector Installation ....19
Exterior Vent Termination Requirements .....................20
4" X 6-5/8" Rigid Pipe .................................................21
5" X 8" Rigid Pipe ......................................................23
AstroCap XL & Rigid REAR VENT KIT for CORNER
INST ALLATIONS .........................................................28
RIGID PIPE 5" x 8" ..............................................28
venting arrangements For Horizontal TerminationS
29
RIGID PIPE 4" x 6-5/8" ........................................29
Horizontal terminations ................................................31
Two (2) 90o Elbows (Rigid Pipe 4" x 6 - 5/8") ..............31
Horizontal terminations ................................................31
Three (3) 90o Elbows (Rigid Pipe 4" x 6 - 5/8") ............31
venting arrangements For Vertical TerminationS .32
RIGID PIPE 4" x 6-5/8" ........................................32
Vertical terminations ...................................................33
Three (3) 90o Elbows (Rigid Pipe 4" x 6 - 5/8") ............33
venting arrangements ..........................................34
With Co-linear Flex System .................................34
Vertical Terminations ...........................................35
Co-linear Flex System Into Masonry Fireplaces .35
Unit Installation with Horizontal Termination ...............36
4" x 6-5/8" or 5" x 8" Venting ......................................36
Unit Installation with Horizontal Termination ...............37
Unit installation with Vertical Termination ....................38
Gas Line Installation ....................................................38
Pilot Adjustment ...........................................................39
High Elevation .............................................................39
886 S.I.T. Valve Description .........................................39
Gas Pipe Pressure Testing ..........................................39
Conversion from NG to LP ..........................................40
Brick panel installation .................................................42
Optional black enamel panel installation .....................43
Log set installation .......................................................44
Optional Fan installation ..............................................47
AC power adaptor installation (for surefi re systems) ...48
GT Remote installation ................................................49
Optional Wall Thermostat ...........................................50
Optional Remote Control .............................................50
Optional Wall Switch ....................................................50
GTM Remote installation .............................................51
GTMF Remote installation ...........................................53
Aeration Adjustment ....................................................56
Wiring diagram ............................................................56
PROFLAME SYSTEM WIRING diagram .....................56
Optional accent light Installation ..................................58
Mesh guard Installation ...............................................61
Flush glass door Installation ........................................62
OPERATING INSTRUCTIONS
Operating Instructions .................................................63
First Fire ......................................................................63
Lighting Procedure ......................................................63
Shutdown Procedure ...................................................63
Normal Operating Sounds of Gas Appliances .............63
Copy of Lighting Plate Instructions ..............................64
Maintenance Instructions.............................................65
Log Replacement ........................................................65
Bulb Replacement .......................................................65
Removing Valve ...........................................................66
Installing Valve .............................................................66
PARTS LIST
Main Assembly ............................................................67
Burner Assembly .........................................................69
WARRANTY
The Warranty: Limited Lifetime ...................................71
4
Regency B36XTCE Gas Fireplace
This is a copy of the label that accompanies each Bellavista™ B36XTCE Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review.
®
NOTE: Regency
units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
SAFETY LABEL
COPY OF SAFETY DECAL
Duplicate S/N
Listed:
VENTED GAS FIREPLACE HEATER /
4001172
Certified for/Certifi e pour: Tested to:
ANSI Z21.88-2009/CSA 2.33-2009
MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE.
é
CAN/CGA-2.17-M91(R2009)
NATURAL GAS: Model B36XTCE-NG
WC/C.E.
Minimum supply pressure Manifold pressure high Manifold pressure low Orifice size Minimum input Maximum input Altitude
5.0" (1.25 kPa) WC/C.E.
3.5" (0.87 kPa) WC/C.E.
1.6" (0.40 kPa)
#35 DMS 21,500 Btu/h (6.3 kW) 31 ,000 Btu/h (9.09 kW) 0-4500 ft/pi (0-1372 m)
PROPANE GAS: Model B36XTCE-LP
Minimum supply pressure Manifold pressure high Manifold pressure low Orifice size Minimum input Maximum input Altitude
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1. This appliancemust beinstalled in accordancewith theStandard CAN/CSAZ240 MH, MobileHousing, inCanada, or withthe Manufactured Home Constructionand SafetyStandard,Title24 CFR, Part3280, inthe United States,or whensuch a standardis notapplicable,ANSI/NCSBCS A225.1/NFPA501A, Manufactured Home InstallationsStandard orANSI A119.2 ou NFPA501C Standard for RecreationalVehicles This appliance is only foruse with the type of gas indicated on therating plateand may be installed inan aftermarket, permanently located, manufactured (mobile) home where notprohibited bylocal codes. See owner's manualfor details.This appliance is notconvertible foruse with othergases, unlessa certified kitis used.(Kit #576-972).
Fan Part# 576-917. Installer l'appareilselon lescodes ou règlementslocaux, ou,en l'absence detels règlements,selon les codesd'installation ANSIZ223.1, NationalFuel Gas Codeou CSA-B149.1en vigueur. Installer l'appareil selon la norme CAN/CSA-Z240, Série MM, Maison mobiles ou CAN/CSA-Z240 VC, Véhicules de camping, ou la norme 24 CFR Part 3280, Manufactured Home Construction and Safety Standard. Si ces normes ne sont pas pertinentes, utilisez la norme ANSI/NCSBCSA225.1/NFPA 501A, Manufactured Home Installations Standard, ou ANSIA119.2 ou NFPA 501C Standard for Recreational Vehicles. Cet appareildoit êtreutilize uniquement avec le typede gazindiqué surla plaque signalétique. Cet appareilpeut êtreinstallé dans une maison préfabriquée ou mobile(É.-U. seulement)installée à demeure si les règlements locauxle permettent.Voir lanotice de l'utilisateurpour plusde renseignements. Cetappareil nepeut pas êtreutilisé avecd'autres gaz saufsi unetrousse de conversioncertifiée estfournie.
This ventedgas fireplaceheater is notfor usewith air filters. Ne pasutiliser defiltre à airavec cefoyer au gazà évacuation. FOR USEWITH GLASSDOORS CERTIFIED WITHTHE APPLIANCEONLY
Electrical supply/Électrique 115VAC, 1.13 A, 60Hz. NOT FOR USE WITH SOLID FUELS. /
WC/C.E.
11" (2.74 kPa)
WC/C.E.
10" (2..49 kPa)
WC/C.E.
6.4" (1.60 kPa) #51 DMS 25,000 Btu/h (7.33 kW) 31 ,000 Btu/h (9.09 kW) 0-4500 ft/pi (0-1372 m)
NE PAS UTILISER AVEC DU COMBUSTIBLE SOLIDE.
CANADA and U.S.A.
APPAREIL FONCTIONNANT AU NATURAL GAS CONCU POUR ETRE POELE: Mod le B36XTCE-NG
Pression d'allimentation minimum Pression à la tubulure d' chappement lev e Pression à la tubulure d' chappement basse Grandeur de l'injecteur D bit minimum selon D bit maximum selon l'altitude
ÉÉ
CONCU POUR ETRE POELE: Mod le B36XTCE-LP
Pression d'allimentation minimum Pression à la tubulure d' chappement lev e Pression à la tubulure d' chappement basse Grandeur de l'injecteur D bit minimum selon D bit maximum selon l'altitude
FOYER AU GAZ À ÉVACUATION
ééé é
é
Calorifique
é
Calorifique
QUIP A L'UISINE POUR GAZ PROPANE
ééé é
é
Calorifique
é
Calorifique
POUR UTILISATION UNIQUEMENTAVECLES PORTESEN VERRE CERTIFIÉESAVECL'APPAREIL
FPI Fireplace Products International Ltd. Delta, BC, Canada
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
Minimum Clearances to Combustibles /
é
é
Degagement Minimum De Materiaux Combustibles
Ceiling
C
D
A
E
Floor
DOOR SEAL: Please
check that the door is
properly sealed
(See Instruction Manual for
detailed instructions)
410
Serial No./ No de serie
410
0" Clearance to combustibles from:
Sides, bottom and rear of unit *Top - 3-1/2" (89mm) non-combustible
Wall
material required above unit.
Mantel Clearances from
F
Fireplace Opening:
(A) Min. 15-1/2" (394mm)
Side Wall Clearance from Fireplace Opening
B) Min. 12” (305mm)
Ceiling from Top of Fireplace Opening:
C) 39” (991mm)
Mantel Depth:
D) Max. 12” (304mm)
Alcove Clearances:
E) Min. Width 84" (2134mm), F) Max. Depth 36" (914mm)
Made in Canada/ Fabrique au Canada
(on one side)
919-153
For the State of Massachusetts, installation and repair must be done by a plumber or gas fi tter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appli­ances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.
Regency B36XTCE Gas Fireplace
5
REQUIREMENTS
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
MA Code - CO Detector
(for the State of Massachusetts only)
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
6
Regency B36XTCE Gas Fireplace
23-5/8"
(599mm)
40-5/16"
(1024mm)
33"
(838mm)
40-5/8"
(1032mm)
UNIT DIMENSIONS
14-3/4"
3(375mm)
DIMENSIONS
21-13/16"
(529mm)
29-7/8"
(759mm)
32-7/8"
(759mm)
25-5/8"
(650mm)
4-1/8"
(105mm)
38-1/16"
8-5/8"
41-5/16"
(1049mm)
29-3/4"
(219mm)
(756mm)
(188mm)
3-1/4"
(79mm)
7-7/16"
1-1/2
(38mm)
1-1/4"
(32mm)
35-5/16'
33-1/8"
(840mm)
(895mm)
Regency B36XTCE Gas Fireplace
7
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The B36XTCE Gas Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fi replace is installed in compliance with manufacturers instructions and all applicable codes.
BEFORE YOU ST ART
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME AREA AS THE APPLI­ANCE. TODDLERS, YOUNG CHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO ACCIDENTAL CONTACT BURNS. A PHYSICAL BARRIERS IS RECOMMEND­ED IF THERE ARE AT RISK INDIVIDUAL IN THE HOUSE. TO RESTRICT ACCESS TO A FIREPLACE OR STOVE, INSTALL AN ADJUSTABLE SAFETY GATE TO KEEP TODDLERS, YOUNG CHILDREN AND OTHER AT RISK INDIVIDUALS OUT OF THE ROOM AND AWAY FROM HOT SURFACES.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
ANY SAFETY SCREEN, GUARD, OR BARRIER REMOVED FOR SERVICING THE APPLIANCE, MUST BE REPLACED PRIOR TO OPERATING THE APPLIANCE.
IF THE BARRIER BECOMES DAMAGED, THE BARRIER SHALL BE REPLACED WITH THE MANUFACTURER'S BARRIER FOR THIS APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CAN1-B149 or ANSI Z223.1 Installation Codes.
2) The appliance when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/NFP A 70 or CSA C22.1 Canadian Electrical Code.
7) Any safety glass removed for servicing must be replaced prior to operating the appliance.
8) To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fi replace.
9) Wear gloves and safety glasses for protection while doing required maintenance.
10) Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.
11) Under no circumstances should this appliance be modifi ed. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
12) Installation and any repairs to this appliance should be done by a qualifi ed service person. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid fuels
(wood, paper, cardboard, coal, etc.) be used in this appliance.
15) The appliance area must be kept clear and free of combustible materials, (gases and other ammable vapours and liquids).
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPE­CIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
8
3) See general construction and assembly instructions. The appliance and vent should be enclosed.
4) This appliance must be connected to the specifi ed vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fi tted as per Venting instructions.
5) Inspect the venting system annually for blockage and any signs of deterioration.
6) Venting terminals shall not be recessed into a wall or siding.
Regency B36XTCE Gas Fireplace
INSTALLATION
INSTALLATION
CHECKLIST
1) Locate appliance
a) Room location (Refer to "Locating Your
Gas fi replace" section)
b) Clearances to Combustibles (Refer to
"Clearances" section)
c) Mantle Clearances (Refer to "Combustible
Mantel Clearances" section)
d) Framing & Finishing Requirements (Refer
to "Framing & Finishing" section)
e) Venting Requirements (Refer to "V enting"
section)
2) Assemble Top Standoffs and Top Facing Support and Side Nailing Strips (Refer to "Unit Assembly Prior to Installation" Section). NOTE: Must be done before installing unit into place.
3) Install vent (Refer to "Venting" sections).
4) Make gas connections. Test the pilot. Must
be as per Diagram (Refer to "Pilot Adjustment " section).
Convert to propane if desired (Refer to "Gas
Line Installation" and "Conversion Kit from NG to LPG" sections).
5) Make electrical connections to receptacle supplied with unit (recommended).
This includes:
1) Clocking the appliance to ensure the correct
ring rate (rate noted on label 31,000 Btu/h, after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your replace,
ensure that the clearances are met.
2) The appliance must be installed on a fl at, solid, continuous surface For example a wood, metal or concrete fl oor or in a raised (on the wall) application. The appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
3) The B36XTCE Gas Fireplace can be installed in a recessed position or framed out into the room as in A, B, C and D. See Diagram 1.
4) This appliance is Listed for bedroom installations using the standard Remote (millivolt thermostat system). Some areas may have further requirements, check local codes before installation.
5) The B36XTCE Gas Fireplace are approved for alcove installations, see "Clearances" section for details.
6) We recommend that you plan your installation on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.
Note: For vent terminations refer to
"Exterior Vent T ermination Locations" section.
6) Install standard and optional features. Refer
to the following sections:
a. Install 4AA batteries into battery pack or
install optional AC power adaptor b. Inner Panels or Brick Panels (Optional) c. Log Set Installation d. Standard Flush Door e. Remote Control f. Wall Switch g. Wall Thermostat h. Fan Installation (Optional) i. Light Installation (Optional)
7) Final check.
Diagram 1
A) Flat on Wall B) Flat on Wall Corner C) Recessed into Wall/Alcove D) Corner
Regency B36XTCE Gas Fireplace
9
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fi replace and vent system be installed only in accordance with these instructions.
The top, back and sides of the fi replace are defi ned by
Caution Requirements
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
B36XTCE Clearance Requirements
Clearance: Dimension Measured From:
A: Mantel Height (min.) 15-1/2" (394mm) Top of Fireplace Opening B: Sidewall 12" (304mm) one side
C: Ceiling 39" (991mm) Top of Fireplace Opening D: Mantel Depth (max.) 12" (304mm) 23-1/2 " (570mm) from
E: Alcove Width 84" (2134mm) Wall to Wall (Minimum) F: Alcove Depth 36" (914mm) Front to Back Wall (Maximum) Notes: 0" No Hearth Required
C
Fire hazard is an extreme risk
WARNING
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fi replace and vent
system be installed only in accordance with these instructions.
Side of Fireplace Opening
only
Top of Fireplace Opening
C
10
D
F
A
E
E
Minimum Vent Clearances
E
F
Close to Ceiling
to Combustibles
F
Alcove
Horizontal Top 2" (51mm) Horizontal Side 1-1/2 " (38mm) Horizontal Bottom 1-1/2" (38mm) Vertical Vent 1-1/2" (38mm)
Regency B36XTCE Gas Fireplace
INSTALLATION
MANTEL CLEARANCES
Due to the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in
the Diagram on the right.
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board.
Mantel Clearances
14
12
6
810
4
0
2
24
12
12”
B
0
Inches
To Floor
Mantel Clearances B36XTCE
From Top of Fireplace Opening
Combustible
7”
Non-combustible
1"
Header
(steel stud)
on edge
C
D
3-1/2”
Non-combustible
Standoff
Top of
A
29-11/16"
(754mm)
Fireplace
Opening
ABCD
23-1/2"
(597mm)
20"
(508mm)
15-1/2"
(394mm)
Note: Ensure the paint that is used on the mantel and the facing is "High Quality" or the paint may discolour.
Regency B36XTCE Gas Fireplace
11
INSTALLATION
MANTEL LEG CLEARANCES
Top View
Side opening of fireplace
Mantel leg
1-1/2"
Mantel leg
3"
3.5”
6.5"
Allowable mantel leg
projection.
12"
NON- COMBUSTIBLE REQUIREMENTS:
40-5/8"
[1031mm]
Non combustible - supplied w/unit
No Combustible
Materials in this Area
3-1/2"
[89mm]
8-3/8"
[213mm]
[1057mm]
25-5/8"
41-5/8"
NO FACING OR
[651mm]
FINISHING MATERIAL
IN THIS AREA
4-1/8"
[105mm]
32-7/8"
3-7/8"
[98mm]
NOTE: The 3-1/2" x 40-5/8" non combustible material supplied with this unit can be replaced if trying to achieve a clean fi nish. A large piece of non
combustible material (ie. 4' x 8' x 1/2") can be used to eliminate taped seams on or near unit.
12
835mm
See framing dimensions on next page.
Regency B36XTCE Gas Fireplace
INSTALLATION
Q
FRAMING
Framing Dimensions Description B36XTCE
L Framing rise from fl oor
M Framing Width 41-1/4"(1048mm) N Framing Height 42" (1067mm) O (Rear Vent) Framing Depth - Rear Vent 23-7/8" (606mm) O (Top Vent) Framing Depth - Top Vent 23-7/8" (606mm) P (Top Vent) Corner Facing Wall Width 53-1/4" (1353mm) P (Rear Vent) Corner Facing Wall Width 57-7/8" (1470mm) AstroCapXL
Q (Top Vent) Corner Facing Wall Width 75-1/4" (1911mm) Q (Rear Vent) Corner Facing Wall Width 81-1/2" (2070mm) AstroCapXL
R (Rear Vent) Framed Chase Ceiling - Rear 41-1/2" (1054mm) R (Top Vent) Framed Chase Ceiling - Top 50-1/2" (1283mm) S (Rear Vent) Vent Centerline Height - Rear 26-1/2" (673mm) S (Top Vent) (5" x 8") Vent Centerline Height - Top 42-1/8" (1070mm) Flex 44-1/4" (1123mm) Rigid S (Top Vent) (4" x 6-5/8") Vent Centerline Height - Top - 49" (1245mm) Rigid T Gas Connection Height 1-1/2" (38mm) U Gas Connection Inset 7-3/8" (187mm) V Gas Connection Width 3-1/4" (82mm) W Non-combustible Height 3-1/2"" (89mm)
0" (when not using a surround)
1" min (when using Mantel)
66-1/8" (1670mm) - other approved caps
93-1/2" (2375mm) - other approved caps
** Important: Framing height requires consideration of the hearth depth. Dimension N = N + the thickness of the installed hearth.
R
Drywall
Non-combustible
Header
(steel stud
on edge)
N
L
M
(or other
facing)
W
Non-Combustible
Header
(steel stud) on edge
Non-Combustible Facing
11" (279mm)
dia. Hole through
wall Vent.
O
S
S
Regency B36XTCE Gas Fireplace
P
T
U
V
Opening for gas
connection
13
INSTALLATION
FRAMING & FINISHING
1. Frame in the enclosure for the unit with framing material.
Note: When constructing the framed opening, please ensure there is access to install the gas lines when the unit is installed.
2. For exterior walls, insulate the enclosure to the same degree as the rest of the house; apply vapour barrier and drywall, as per local installation codes. (Do not insulate the fi replace itself.)
WARNING: Failure to insulate and add vapor barriers to the inside of the exterior wall will result in operational and performance problems
including, but not limited to: excessive condensation on glass doors, poor fl ame package, carbon, blue fl ames etc. These are not product related issues.
3. The unit does not have to be completely enclosed in a chase. You must maintain clearances from the vent to combustible materials: See "Clearances"
section. Combustible materials can be laid against the side and back standoffs and the stove base.
4. Tile Finish Option 1: Drywall may be installed onto the unit as shown below to create a surface to apply fi nishing materials such as tile, slate, etc.
Drywall cannot extend beyond the metal surface of the unit.
5. Tile Finish Option 2: If applying a non-combustible fi nishing material (tile,slate,etc) the material can be installed directly onto the metal surface (clean front) of the unit in the area shown below.
TILE FINISH
Combustible Material
Non-combustible
Finishing Material (ie. tile)
Non-combustible Material (3-1/2" x 40-5/8")
Nailing Strip
-1/2" back from unit face
Supplied with Unit
[651mm]
32-7/8"
835mm
25-5/8"
Ensure finished material is brought to lip
Non-combustible Finishing Material (ie. tile)
1-1/2
Combustible Material
CLEAN FINISH
6. If applying a non-combustible facing it may be installed over the metal surface (clean front) of the unit in the area shown below.
NON-COMBUSTIBLE BOARD - SUPPLIED WITH UNIT
41-5/8"
[1054mm]
Combustible and Non-combustible Facing and Finishing
40-5/8"
[1032mm]
Materials around unit.
WOOD STUD
1/2" DRYWALL
DO NOT EXTEND DRYWALL ONTO METAL SURFACE OF UNIT.
NON-COMBUSTIBLE FACING
FOR CLEAN LOOK (ie. painted finish)
1/2" DRYWALL
Non-combustible Finishing Material
Ensure finished material is brought to lip
Non-combustible Finishing Material
Combustible
Material
Non-combustible Material (3-1/2" x 40-5/8")
Nailing Strip
1-1/2
Combustible Material
(38mm)
Supplied with Unit
-flush with unit
(38mm)
NOTE: The 3-1/2" x 40-5/8" non combustible material supplied with this unit can be replaced if trying to achieve a clean fi nish. A large piece of non com-
bustible material (ie. 4' x 8' x 1/2") can be used to eliminate taped seams on or near unit.
14
Regency B36XTCE Gas Fireplace
INSTALLATION
7. Non-combustible material (ie. tile, slate, etc) may be brought up to the edge of the glass door of the unit. Minimum clearances must be adhered to, this
will assure ease of glass door removal and access to the lower panel.
NOTE: Non-combustible fi nishing materials may be of any thickness desired.
40-5/8"
[1031mm]
Non combustible - supplied w/unit
No Combustible
Materials in this Area
NO FACING OR
3-1/2"
[89mm]
8-3/8"
[213mm]
[651mm]
25-5/8"
[1057mm]
41-5/8"
FINISHING MATERIAL
IN THIS AREA
4-1/8"
[105mm]
32-7/8"
3-7/8"
[98mm]
Minimum Clearances for Finishing Materials
835mm
IMPORTANT FINISHING DETAIL NOTE:
Before placing unit into fi nal position - it is important to know the total thickness / height of fi nished hearth (tile, carpet, etc.) The base of the fi replace, 4 sided faceplate or mantel should be level or higher than the fi nished hearth height.
Note: All non-combustible facing material should butt up cleanly
Rough edges may be visible from an angle.
To maintain a clean fi nished edge - facing material edges
may be fi nished with a J-style trim or metal cornerbead (both materials available at your local building or hardware store).
No Combustible
Materials in this Area
J Style trim or metal corner bead may be used to finish edges
32-7/8"
835mm
Trim materials
to the fl anges around the fi rebox opening.
[651mm]
25-5/8"
IMPORTANT: Materials used must be NON-COMBUSTIBLE.
Regency B36XTCE Gas Fireplace
15
INSTALLATION
UNIT ASSEMBLY PRIOR TO INSTALLATION
BEFORE YOU ST ART
The T op Nailing Support, the Side Nailing Strips, the 2 Top Standoffs and the Flue Collar must be correctly positioned and attached before the fi replace is moved into position.
TOP STANDOFF ASSEMBLY
The top standoffs are shipped in a fl at position and must be folded into shape and attached.
STANDOFF SLOT LOCATION
TopView
1) Take each standoff and bend into the correct shape. Bend up at the bend lines until the tab in the standoff and the pre-punched slots on the fi replace top line up. Be sure to use correct slots, they are marked.
NAILING STRIPS
1. There are 8 (eight) side nailing strips and one top nailing strip available on the unit. One set of four (4) are for a clean fi nish installation, the other set are
for a tile fi nish installation as they are set back 1/2" (13mm). The top nailing strip is adjustable to 1/2" (13mm).
2. Bend the required four (4) nailing strips to 90º.
3. Attach top nailing strip with one (1) screw (located at the back of the nailing strip). Adjust to required position, flush or back 1/2" and tighten screw.
Adjustable Top
Nailing Strip
Nailing strip for
Clean Finish (set
ush with unit)
Nailing strip for
Tile Finish (set
back 1/2")
B36XT/ B36XTE/ B36XTCE
B36X B36X
B36XT/ B36XTE/ B36XTCE
Nailing strip for
Tile Finish (set
back 1/2")
16
Nailing strip for
Clean Finish (set
ush with unit)
Regency B36XTCE Gas Fireplace
INSTALLATION
Intake Collar Assembly
w/gasket
The unit comes equipped as a rear vent unit. These instructions are to be used, only if the unit is going to be top vented.
Top Collar Assembly Kit
1 Intake Collar Assembly with Gasket 1 Intake Cover Plate with Gasket 1 Top/Rear Exhaust Assembly with Gasket 1 Heat Defl ector 1 Baffl e Plate 29 1/4" x 1/2" Screws (4 spares) 1 Restrictor 1 Intake Collar Gasket (spare) 1 Exhaust Assembly Gasket (spare)
1 Insulation Plate Cover 1 Insulation Filling
1) Remove the door assembly by releasing the adjustable latches and lifting up off the door frame assembly.
Note: This conversion must be done prior to the unit being placed in position.
Exhaust Assembly
w/ gasket
Intake Collar Assembly
w/gasket
Insulation cover
plate
Note: Components shown are installed on unit.
CONVERSION TO TOP VENT
Intake Cover Plate
w/gasket
Insulation fi lling
Adjustable Tension
Latch location
2) From inside the rebox, remove the top heat defl ector by removing 2 screws.
Heat Defl ector
Diagram 2
3) From inside the rebox, remove the baffl e plate by removing 4 screws
- remove top front screw fi rst. See Diagram 3.
Baffl e Plate
Diagram 3
Regency B36XTCE Gas Fireplace
Diagram 1
4) From the inside of the rebox, remove the exhaust assembly by removing the 8 screws. See Diagram 4.
Diagram 4
17
INSTALLATION
5) From the outside rear of the rebox, remove the intake collar assembly. Remove the 4 - 1/4" x 1/2" screws. See Diagram 5.
Diagram 9
Exhaust
Assembly
Intake Collar
Assembly
Diagram 5
6) From the outside top of the rebox - remove top insulation cover plate and insulation fi lling - by removing 4 screws. See Diagram 6.
Discard cover plate and insulation fi lling.
Diagram 6
7) From the outside top of the rebox - remove the intake cover plate by removing the 4 - 1/4" x 1/2 " screws. See Diagram 7.
9) From the outside top of the rebox, install the intake collar assembly . Secure with 4 - 1/4" x 1/2" screws. Ensure all screws are tight, but do not over tighten. All 4 screws must be used.
Exhaust
Assembly
Diagram 10
10) From the outside rear of the rebox, install the intake cover plate with 4 - 1/4" x 1/2" screws. Ensure all screws are tight, but do not over tighten. All 4 screws must be used.
Intake Collar
Assembly
Diagram7
Before proceeding to Step 8, inspect condition of all gaskets. DO NOT install parts with damaged gaskets. Replace if necessary
with spare gaskets supplied.
8) From the inside of the rebox, place the exhaust assembly into position as shown in Diagram 8 and secure with 8 - 1/4" x 1/2" screws (Diagram 9). Ensure all screws are tight, but do not over tighten.
All 8 screws must be used.
Diagram 8
18
Diagram 11
11) Set vent restrictor accordingly - see next page.
12) From inside the fi rebox, re-install the baf e plate and heat
defl ector - reverse steps 2 & 3.
VENTING
INTRODUCTION
The B36XTCE uses the "balanced fl ue" technology Co-Axial sys- tem. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion cham­ber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These fl ue pipes must not be connected to any other
appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.
Regency B36XTCE Gas Fireplace
INSTALLATION
VENT RESTRICTOR, BAFFLE & HEAT DEFLECTOR INSTALLATION
NOTE: THE VENT RESTRICTOR & BAFFLE MUST BE INSTALLED PRIOR TO OPTIONAL PANEL INSTALLATION.
1) Determine the venting con guration.
2) Remove top heat de ector and baf e plate (reverse of steps 5 & 6).
3) Go to venting arrangements section (in the manual) to determine if
a vent restrictor setting is required.
Note: The vent restrictor does not apply to rear vent applications.
4) Align the vent restrictor plate to the required vent restrictor position
as per the Diagrams shown.
5) Once the vent restrictor plate is in the required position, secure with 2 - 1/4" x 1/2" screws. Ensure all screws are tight, but do not over
tighten. (See Diagram 2).
Diagram 2 Vent restrictor installed on top exhaust assembly
6) From inside the fi rebox, install the baffl e plate with 4 - 1/4" x 1/2 " screws. Ensure all screws are tight, but do not over tighten.
Baffl e Plate
Note: If installing brick/optional panels, see brick/optional panel
instructions before proceeding to next step.
7) From inside the rebox, install the top heat de ector with 2 -
1/4" x 1/2" screws. Ensure all screws are tight, but do not over
tighten.
Heat Defl ector
Diagram 3
Diagram 4
Regency B36XTCE Gas Fireplace
19
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
1
Minimum Clearance Requirements
A Clearance above grade, veranda, porch, deck, or balcony 12"(30cm) 12"(30cm)
B Clearance to window or door that may be opened 12"(30cm) 9" (23cm)
C Clearance to permanently closed window **
D Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm)
from the center line of the terminal (check with the local code)
E Clearance to unventilated soffi t 19"(48cm) 19"(48cm)
F Clearance to outside corner: with AstroCap Termination Cap. 13"(33cm) 13"(33cm)
Clearance to outside corner: with all other approved Termination Caps. 13"(33cm) 13"(33cm)
G Clearance to inside corner: with AstroCap Termination Cap 11"(28cm) 11"(28cm)
Clearance to inside corner: with all other approved Termination Caps. 11"(28cm) 11"(28cm)
H Clearance to each side of center line extended above meter/regulator assembly 36"(90cm)
J Clearance to service regulator vent outlet 36"(90cm) *
K Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance 12"(30cm) 9" (23cm)
L Clearance to a mechanical air supply inlet #3' (91cm) above if within 10' (3m) horizontally. 72"(1.8m) 36"(90cm)
M Clearance above paved sidewalk or a paved driveway located on public property 84"(2.1m)
N Clearance under veranda, porch, deck, or balcony 12"(30cm)
1
In accordance with current CSA B149.1, Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor
Clearance in accordance with local installation codes and the requirements of the gas supplier
*
a
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
b
3 feet (91cm) above - if within 10 feet (3m) horizontally
Canada
24"(60cm) 24"(60cm)
a
USA
*
*
*
2
b
20
Regency B36XTCE Gas Fireplace
INSTALLATION
4" X 6-5/8" RIGID PIPE
CROSS REFERENCE CHART ONLY
Components from different Manufacturers may not be mixed. Not all Rigid Pipe components are available directly from FPI.
Description
6” Pipe Length-Galvanized 46DVA-06 4DT-6 N/A 4D6 SV4L6 TC-4DL6
6” Pipe Length-Black 46DVA-06B 4DT-6B N/A 4D6B SV4LB6 TC-4DL6B
7” Pipe Length-Galvanized N/A N/A 4D7 N/A N/A N/A
7” Pipe Length-Black N/A N/A 4D7B N/A N/A N/A
9” Pipe Length-Galvanized 46DVA-09 4DT-9 N/A N/A N/A N/A
9” Pipe Length-Black 46DVA-09B 4DT-9B N/A N/A N/A N/A
12” Pipe Length-Galvanized 46DVA-12 4DT-12 4D12 4D12 SV4L12 TC-4DL1
12” Pipe Length-Black 46DVA-12B 4DT-12B 4D12B 4D12B SV4LB12 TC-4DL1B
18” Pipe Length-Galvanized 46DVA-18 4DT-18 4D18 4D18 SV4LA TC-4DL18
18” Pipe Length-Black 46DVA-18B 4DT-18B 4D18B 4D18B SV4LA TC-4DL18B
24” Pipe Length-Galvanized 46DVA-24 4DT-24 4D24 4D24 SV4L24 TC-4DL2
24” Pipe Length-Black 46DVA-24B 4DT-24B 4D24B 4D24B SV4LB24 TC-4DL2B
36” Pipe Length-Galvanized 46DVA-36 4DT-36 4D36 4D36 SV4L36 TC-4DL3
36” Pipe Length-Black 46DVA-36B 4DT-36B 4D36B 4D36B SV4LB36 TC-4DL3B
48” Pipe Length-Galvanized 46DVA-48 4DT-48 4D48 4D48 SV4L48 TC-4DL4
48” Pipe Length-Black 46DVA-48B 4DT-48B 4D48B 4D48B SV4LB48 TC-4DL4B
60” Pipe Length-Galvanized 46DVA-60 4DT-60 N/A N/A N/A N/A
60” Pipe Length-Black 46DVA-60B 4DT-60B N/A N/A N/A N/A
Simpson
Direct Vent Pro
®
Selkirk
Direct Temp™
American Metal
Products®
Amerivent Direct
Metal-Fab™
Sure Seal
Security
Secure- Vent®
ICC Excel
Direct
Adjustable Length 3”-10”-Galvanized N/A N/A N/A 4DAL N/A TC-4DLT
Adjustable Length 3”-10”-Black N/A N/A N/A 4DALB N/A TC-4DLTB
Adjustable Length 7”-Galvanized N/A N/A 4D7A N/A N/A N/A
Adjustable Length 7”-Black N/A N/A 4D7AB N/A N/A N/A
Extension Pipe 8-1/2”-Galvanized 46DVA-08A N/A N/A N/A N/A N/A
Extension Pipe 8-1/2”-Black 46DVA-08AB N/A N/A N/A N/A N/A
Adjustable Length 12”-Galvanized N/A N/A 4D12A N/A SV4LA12 N/A
Adjustable Length 12”-Black N/A N/A 4D12A N/A SV4LBA12 N/A
Extension Pipe 16”-Galvanized 46DVA-16A N/A N/A N/A N/A N/A
Extension Pipe 16”-Black 46DVA-16AB N/A N/A N/A N/A N/A
45º Elbow-Galvanized 46DVA-E45 4DT-EL45 4D45L N/A N/A TE-4DE45
45º Elbow-Black 46DVA-E45B 4DT-EL45B 4DT-EL45B N/A N/A TE-4DE45B
45º Elbow Swivel-Galvanized See 46DVA-E45 N/A N/A 4D45L SV4E45 N/A
45º Elbow Swivel-Black See 46DVA-E45B N/A N/A 4D45LB SV4EB45 N/A
90º Elbow-Galvanized 46DVA-E90 4DT-EL90S 4DT-EL90S N/A N/A TE-4DE90
90º Elbow-Black 46DVA-E90B 4DT-EL90SB 4DT-EL90SB N/A SV4EBR90-1 TE-4DE90B
90º Elbow, Swivel-Galvanized See 46DVA-E90 N/A N/A 4D90L SV4E90-1 N/A
90º Elbow, Swivel-Black See 46DVA-E90B N/A N/A 4D90LB SV4EB90-1 N/A
90º Starter Elbow, Swivel-Galvanized N/A N/A N/A 4D90A N/A N/A
Adaptor* N/A N/A N/A 4D90L N/A N/A
Ceiling Support N/A 4DT-CS 4DFSP 4DSP SV4SD TE-4DE45
Cathedral Support Box 46DVA-CS 4DT-CSS 4DRSB 4DRS SV4CSB TE-4DE45B
Wall Support/Band 46DVA-WS 4DT-WS/B 4DWS 4DWS SV4BM N/A
Offset Support
Wall Thimble-Black 46DVA-WT 4DT-WT 4DWT 4DWT SV4RSM TE-4DE90
Wall Thimble Support/Ceiling Support 46DVA-DC N/A N/A N/A SV4PF TE-4DE90B
Firestop Spacer 46DVA-FS 4DT-FS 4DFSP 4DFS SV4BF N/A
Trim Plate-Black N/A 4DT-TP 4DFPB 4DCP SV4LA N/A
46DVA-ES (N/A - FPI)
4DT-OS N/A N/A SV4SU N/A
Regency B36XTCE Gas Fireplace
21
INSTALLATION
Description
Attic Insulation Shield 12” 46DVA-IS N/A@ FPI N/A 4DAIS12 N/A SV4RSA N/A
Attic Insulation Shield -
Basic Horizontal Termination Kit (A) Disc. 4DT-HKA 4DHTK2 4DHTKA SV-SHK N/A
Horizontal Termination Kit (B) 46DVA-KHA
Vertical Ter mination Kit Disc. 4DT-VKC 4DHTK 4DHTK SV-FK N/A
High Wind Vertical Cap 46DVA-VCH N/A N/A N/A N/A TM-4VT
High Wind Horizontal Cap 46DVA-HC N/A N/A N/A N/A TM-4DHT
Horizontal Square Termination Cap See
Vertical Ter mination Cap 46DVA-VC 4DT-HVC 4DVC 4DVT SV4CGV-1 TM-4VT
Storm Collar 46DVA-08A 4DT-SC 4DSC 4DSC SV4FC TM-SC
Adjustable Flashing 0/12-6/12 46DVA-F6 4DT-ST14 4D12S 4DST14 SV4STC14 TF-4FA
Adjustable Flashing 6/12-12/12 46DVA-FLA 4DT-ST36 4D36S 4DST36 SV4STC36 TF-4FB
Vinyl Siding Standoff 46DVA-VSS 4DT-VS N/A 4DVS SV4VS TM-VSS
Vinyl Siding Shield Plate N/A 4DT-VSP N/A N/A SV4VS N/A
Snorkel Termination 14” 46DVA-SNKL N/A N/A N/A N/A TM-4ST14
Snorkel Termination 36” N/A N/A N/A N/A N/A TM-4ST36
Cold Climates 36” N/A N/A 4DAIS12 N/A N/A TM-4AS
Simpson
Direct Vent Pro
(Changed Components)
46DVA-HC 4DT-HHC 4DHC 4DHT SV4CHC-1 TM-4HT
®
Selkirk
Direct Temp™
4DT-HKB 4DHTK1 4DHTKB SV-HK N/A
American Metal
Products®
Amerivent Direct
Metal-Fab™
Sure Seal
Security
Secure- Vent®
ICC Excel
Direct
Restrictor Disk N/A N/A N/A N/A N/A TM-4DS
Extended Vertical Ter mination Cap N/A N/A N/A N/A N/A N/A
Chimney Conversion Kit A (USA only) 46DVA-KCA N/A N/A N/A N/A TM-4CA6
Chimney Conversion Kit B (USA only) 46DVA-KCB N/A N/A N/A N/A TM-4CA7
Chimney Conversion Kit C (USA only) 46DVA-KCC N/A N/A N/A N/A TM-4CA8
Chimney Conversion Kit Masonry (USA only)
Wall Firestop 46DVA-WFS N/A N/A N/A N/A TM-4TR
Colinear Flex Connectors 46DVA-ADF N/A N/A N/A N/A N/A
FPI
946-506/P Vent Guard (Optional) for AstroCap 946-205 Vinyl Siding Shield for Riser Vent Terminal
510-994 Rigid Pipe Adaptor (Must use with all rigid piping) 946-208/P Vent Guard (Optional) for Riser Vent Terminal
640-530/P Riser Vent Terminal 946-523/P AstroCap Horizontal Cap
946-605 Starter Collar Increaser 4” x 6-5/8” to 5” x 8” 946-206 Vinyl Siding Standoff for AstroCap
Note: When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection: Use this table to determine offset pipe lengths.
Pipe Length
(L)
0” (0mm) 4-7/8” (124mm) 13-7/8” (340mm) Simpson Direct Vent Pro: www.duravent.com
6” (152mm) 8” (203mm) 16-1/2” (419mm) Selkirk Direct-Temp: www.selkirkcorp.com
9” (229mm) 10-1/8” (257mm) 18-5/8” (473mm) American Metal Products: www.americanmetalproducts.com
12” (305mm) 12-1/4” (311mm) 20-3/4” (527mm) Metal-Fab Sure Seal: www.mtlfab.com
24” (610mm) 20-5/8” (524mm) 29-1/8” (740mm) Security Secure Vent: www.securitychimneys.com
36” (914mm) 29” (737mm) 37-1/2” (953mm) Industrial Chimney Company: www.icc-rsf.com
48” (1219mm) 37-7/16” (951mm) 45-15/16” (1167mm)
Note: Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination. Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.
Run (X) Rise (Y)
46DVA-KMC N/A N/A N/A N/A N/A
4” x 6-5/8” Venting For specifi c instructions on venting components - visit the
manufacturers website listed below.
22
Regency B36XTCE Gas Fireplace