Red Lion SNUB User Manual

0.90 (23)
0.33 (8.5)
0.75 (19)
4.00 (102)
(AWG 20 WIRE)
A
A
Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net
R-C SNUBBER NOISE AND ARC SUPPRESSOR
GENERAL DESCRIPTION
DIMENSIONS In inches (mm)
[All Dimensions are nominal]
SPECIFICATIONS
1. R-C Value: 0.1 μf, 47 1/2 Watt (±30%)
2. Max. Line Voltage: 250 V rms or 250 VDC
3. Frequency: DC to 62 Hz
4. Peak Pulse Voltage: 1200 V max.
UL recognized component
(Okaya Electric America, Inc. PN# XEB0471, UL-1414, File # E47474)
Bulletin No. SNUB-B Drawing No. LP0349 Released 12/11
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBER
SNUB R-C Snubber Inductive Load Suppressor SNUB0000
Do not dispose of unit in trash - Recycle
APPLICATION
The R-C snubber inductive load suppressor should be applied as shown below. Placing the suppressor across the contact in many cases can work as well, but for maximum effect, it is best to place the suppressor directly
CONTACT
POWER
C OR DC
250V (MAX.)
INDUCTIVE
LOAD
R-C
SNUBBER
Preferred Application Alternate Application
across the load. All inductive loads in a system should be suppressed in this manner to avoid mutual interference. The suppressors are effective in both AC and DC circuits.
* CONTACT
POWER
C OR DC
250V (MAX.)
R-C
SNUBBER
* Use a snubber across all contacts in the load circuit.
INDUCTIVE
LOAD
Red Lion Controls Headquarters 20 Willow Springs Circle York PA 17406 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839
Red Lion Controls
Europe
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
54, Vishvas Tenement
GST Road, New Ranip,
Ahmedabad-382480 Gujarat, India
Tel +91 987 954 0503
Fax +91 79 275 31 350
Red Lion Controls
China
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683