MODEL RLY7 - THREE PHASE DIN RAIL MOUNT SOLID STATE RELAY
INTEGRATED HEAT SINK
OPTICALLY ISOLATED
SOLID STATE SWITCHING
25 A THREE PHASE OUTPUT RATING
24 TO 660 VAC SWITCHING
4 TO 32 VDC CONTROL SIGNAL
ZERO VOLTAGE TURN-ON
MOUNTS ON DIN RAIL OR DIRECTLY TO PANEL
4000 VOLT ISOLATION
BUILT-IN SNUBBER
LED “ON” INDICATOR
CAGE CLAMP TERMINATIONS
Bulletin No. RLY7-E
Drawing No. LP0472
Released 03/13
UL Recognized Component,
File #E191578
GENERAL DESCRIPTION
The RLY7 is a three phase solid state relay that switches load currents up to
25 A. The unit features a zero voltage turn-on detector to minimize radiated RFI
when switching. An internal snubber guards against false triggering of the
output related to high dv/dt applications. A low level DC control signal of 4 to
32 VDC is all that is needed for the switching operation. This unit, highlighted
by the inverse-parallel SCR output, provides a greatly increased operational life
over a mechanical relay by avoiding the usual relay contact problems such as:
arcing, bouncing, and mechanical failure.
The RLY7 can be directly controlled by logic/SSR drive output or sourcing
output of Red Lion Controls products.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators
not equipped with safeguards. To do so, can be potentially harmful to persons
or equipment in the event of a fault to the unit.
DIMENSIONS In inches (mm)
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
SPECIFICATIONS
OUTPUT SPECIFICATIONS
1. Operating Voltage Range: 24 to 660 VAC
2. Operating Frequency Range: 47 to 63 Hz
3. Maximum Continuous Load Current: 25 Amps (3 pole), 35 Amps (2 pole)
(See Safe Operating Conditions)
5. Min. Load Current: 100 mA
6. Leakage Current @ V
7. Peak Blocking Voltage: 1400 VAC
8. Voltage Drop @ I
9. I2T Fusing: 1350 A2sec
(For Fusing Purposes, T = 8.3 msec.)
10. Dv/Dt @ V
OUT
TOP VIEW
(Max.): 10 mA
OUT
: 3 VAC
OUT
(Max.): 1000 V/µsec
4.84
(123)
2.95
(75)
R
(L1)
3 PHASE SOLID STATE RELAY
(T1)
U
S
(L2)
RED LION CONTROLS
MODEL: RLY7
PART: RLY70000
25 AMP, AT 24-660 VAC
(T2)
V
3.54 (90)
YORK, PA.
T
(L3)
+
-
3.15
4-32
VDC
(80)
INPUT
M2448
(T3)
W
3.43
(87)
.14 (3.5)
.91 (23.1)1.73 (43.9)
INPUT SPECIFICATIONS
1. Control Voltage Range: 4 to 32 VDC
2. Turn-on Voltage (Min.): 4 VDC
3. Turn-off Voltage (Max.): 1 VDC
4. Input Current (Max.): 15 mA
GENERAL SPECIFICATIONS
1. Isolation (Input to Output to Base): 4000 V
2. Operating Temperature Range: 0°C to 40°C
RMS
SAFE OPERATING CONDITIONS
The relay must always operate within the “Safe Operating Area” of the
Derating Curve Figure. Operations outside the Safe Operating Area will shorten
the life of, or cause permanent damage to, the relay. The ambient temperature
should be measured 1" (25 mm) below the relay (when mounted to a vertical
surface) and with all of the associated equipment operating.
It is strongly recommended that a 1" (25 mm) clearance is maintained on all
four sides of the relay. If the relays are mounted against each other, then the end
relays must be derated by an additional 10% (of the Derating Curve) and the
middle relays by 20%.
Derating Curve
40
30
20
10
Operating Load
0
Current (Amps RMS)
20 30 40 50 60 70 80
Safe
Operating
Area
Ambient Temperature (C°)
FUSING
Devices such as electromechanical circuit breakers and slow blow fuses
cannot react quickly enough to protect this relay in a shorted condition. Fast
“semiconductor fuses” with appropriate I2T ratings are strongly recommended.
MECHANICAL INTERRUPT SWITCH
The off-state leakage current of the power unit is 10 mA maximum. The
voltage level of the output will rise proportional to the resistance of the load due
to this leakage current. Full line voltage can be measured when the output is
connected to a high resistance load and the power unit is in the off-state.
A mechanical interrupt switch is recommended between the line voltage and
the load. The switch should be opened when servicing any part of the output
wiring. When measuring the off-state output voltage of the unit for correct
operation, load the output of the RLY7 with a small resistance (approximately
100 ohms).
WIRING GUIDELINES
The controlling device and the relay load should NEVER share the same
power feed. It is recommended that this relay be installed as close as possible to
the load to keep the power cable runs short. The control voltage can run over
distances in excess of 200 feet with shielded cable. If using shielded cable,
connect the shield to the minus “-” terminal of the control signal at one end only.
L1
L2
L3
N
ControlControl Control
L2L1 L3
T2T1 T3
T1 T3T2
L3L2L1
L1 L2 L3
T2 T3T1
In small enclosures, adequate ventilation must be provided to assure proper
safe operating temperature. Accumulation of dust and dirt on the heat sink fins
will also affect heat dissipation. In extreme dust and dirt conditions, the relay
must be derated by an additional 20%.
SCHEMATIC
Control
LINE
L3L2L1
T3T1 T2
Voltage
Zero
voltage
detector
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBER
RLY7 Three Phase Din Rail Mount Solid State Relay RLY70000
Do not dispose of unit in trash - Recycle
Star or Wye connection
with neutral
Star or Wye connection
without neutral
Delta
Connection
THREE PHASE HEATING APPLICATION
This application shows a Model TCU Temperature Controller regulating
the temperature of a drying kiln. The TCU has an SSR Drive Output
Module installed. This module controls the three phase relay directly.
L1
L2
L3
+
-
L1 L2 L3
T1 T2 T3
KILN
MODEL TCU WITH
SSR DRIVE OUTPUT
Control
1
2
3
4
5
6
7
8
+
9
10
-
11
12
13
14
15
16