MODEL RLY6/RLY6A - SINGLE PHASE DIN RAIL MOUNT SOLID STATE RELAY
INTEGRATED HEAT SINK
OPTICALLY ISOLATED
SOLID STATE SWITCHING
SINGLE PHASE OUTPUT RATING: 25 A (RLY6) or 40 A (RLY6A)
SWITCHING: 24 TO 660 VAC
CONTROL SIGNAL: 4 TO 32 VDC
ZERO VOLTAGE TURN-ON
MOUNTS ON DIN RAIL OR DIRECTLY TO PANEL
4000 VOLT ISOLATION
BUILT-IN SNUBBER
LED “ON” INDICATOR
CAGE CLAMP TERMINATIONS
R
UL Recognized Component, File #E191578
LR 702877
GENERAL DESCRIPTION
The RLY60000 is a solid state relay that switches load currents up to 25 A; the RLY6A000 switches load currents up to 40 A. These units feature a zero voltage turn-on detector to minimize radiated RFI when switching. An internal snubber guards against false triggering of the output related to high dv/dt applications. A low level DC control signal of 4 to 32 VDC is all that is needed for the switching operation. These units, highlighted by the inverse-parallel SCR output, provide a greatly increased operational life over mechanical relays by avoiding the usual relay contact problems such as: arcing, bouncing, and mechanical failure.
The RLY6/RLY6A can be directly controlled by logic/SSR drive output or sourcing output of Red Lion Controls products.
RLY6, 25 Amp DIMENSIONS In inches (mm)
3.94
(100)
1.18 (30)
3.15 (80)
.26 (6)
TOP VIEW
4
Control
­4-28 VDC
RED LION CONTROLS
MADE IN U.S.A.YORK, PA.
SOLID STATE RELAY
RLY60000
48-660 VAC
25 Amp Output
2
3 +
M2447B
3.43
1
.71 (18)
(87)
RLY6A, 40 Amp DIMENSIONS In inches (mm)
3.94
(100)
2.36 (60)
3.15 (80)
.31 (8)
TOP VIEW
4
3
Control
+
­4-32 VDC
MADE IN U.S.A.
YORK, PA.
SOLID STATE RELAY
M3058X
RLY6A000
24-660 VAC
40 Amp Output
21
1.73 (44)
3.43 (87)
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators not equipped with safeguards. To do so, can be potentially harmful to persons or equipment in the event of a fault to the unit.
CAUTION: Risk of Danger.
Read complete instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
SPECIFICATIONS
OUTPUT SPECIFICATIONS
1. OPERATING VOLTAGE RANGE: 24 to 660 VAC
2. OPERATING FREQUENCY RANGE: 47 to 63 Hz
3. MAXIMUM CONTINUOUS LOAD CURRENT: (See Safe Operating Conditions)
RLY6: 25 A RLY6A: 40 A
4. SURGE CURRENT: RLY6:
Non-Repetitive 1 Cycle: 250 A Non-Repetitive 1 Second: 100 A
RLY6A:
Non-Repetitive 1 Cycle: 250 A Non-Repetitive 1 Second: 150 A
5. MIN. LOAD CURRENT: 100 mA
6. LEAKAGE CURRENT @ V
7. OVER VOLTAGE RATING: 1400 PIV
8. VOLTAGE DROP @ I
9. POWER DISSIPATION AT FULL LOAD:
RLY6: 25.0 Watts RLY6A: 48.0 Watts
RMS
RMS
OUT
PEAK
PEAK
PEAK
PEAK
(Max.): 8 mA
OUT
: 1.5 VAC
Operating Load
08
RLY6 25 A Derating Curve
SPECIFICATIONS (Cont’d)
10. I2T FUSING: 1035 A2S (For Fusing Purposes, T = 8.3 msec.)
11. Dv/Dt @ V
(Max.): 500 V/µsec
OUT
INPUT SPECIFICATIONS
1. CONTROL VOLTAGE RANGE: 4 to 32 VDC
2. TURN-ON VOLTAGE (MIN.): 4 VDC
3. TURN-OFF VOLTAGE (MAX.): 1 VDC
4. REVERSE VOLTAGE PROTECTION: -75 VDC
5. INPUT CURRENT (MAX.): 8 mA
GENERAL SPECIFICATIONS
1. ISOLATION (INPUT TO OUTPUT TO BASE): 4000 V
2. CAPACITANCE INPUT TO OUTPUT: 3 pf
3. OPERATING TEMPERATURE RANGE: -40°C to +80°C
RMS
SAFE OPERATING CONDITIONS
The relay must always operate within the “Safe Operating Area” of the
Derating Curve Figure. Operations outside the Safe Operating Area will shorten the life of, or cause permanent damage to, the relay. The ambient temperature should be measured 1" (25 mm) below the relay (when mounted to a vertical surface) and with all of the associated equipment operating.
30
20
10
0
Operating Load
-40 -30 -20 -10 01020304050607080
Current (Amps RMS)
50
40
30
Safe Operating Area
Ambient Temperature (C°)
RLY6A 40 A Derating Curve
SCHEMATIC
Control Voltage
+
3
Zero
voltage
detect
­4 2
1
Snubber
Load
or
Load
A.C.
Line
FUSING
Devices such as electromechanical circuit breakers and slow blow fuses cannot react quickly enough to protect this relay in a shorted condition. Fast “semiconductor fuses” with appropriate I2T ratings are strongly recommended.
MECHANICAL INTERRUPT SWITCH
The off-state leakage current of the power unit is 8 mA maximum. The voltage level of the output will rise proportional to the resistance of the load due to this leakage current. Full line voltage can be measured when the output is connected to a high resistance load and the power unit is in the off-state.
A mechanical interrupt switch is recommended between both sides of the line voltage and the load. The switch should be opened when servicing any part of the output wiring. When measuring the off-state output voltage of the unit for correct operation, load the output of the RLY6/RLY6A with a small resistance (approximately 100 ohms).
WIRING GUIDELINES
The controlling device and the relay load should NEVER share the same power feed. It is recommended that this relay be installed as close as possible to the load to keep the power cable runs short. The control voltage can run over distances in excess of 200 feet with shielded cable. If using shielded cable, connect the shield to the minus “-” terminal of the control signal at one end only.
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBERS
RLY6 25 A Single Phase Din Rail Mount Solid State Relay RLY60000
RLY6A 40 A Single Phase Din Rail Mount Solid State Relay RLY6A000
Do not dispose of unit in trash - Recycle
20
10
Current (Amps RMS)
Safe Operating Area
0
-40 -30 -20 -10 01020304050607
Ambient Temperature (C°)
It is strongly recommended that a 0.18" (4.6 mm) clearance is maintained on all four sides of the relay. If the relays are mounted against each other, then the end relays must be derated by additional 10% (of the Derating Curve) and the middle relays by 20%.
In small enclosures, adequate ventilation must be provided to assure proper safe operating temperature. Accumulation of dust and dirt on the heat sink fins will also affect heat dissipation. In extreme dust and dirt conditions, the relay must be derated by additional 20%.
Red Lion Controls Headquarters 20 Willow Springs Circle York PA 17406 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839
Red Lion Controls
Europe
Softwareweg 9
NL - 3821 BN Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
The Company warrants the products it manufactures against defects in materials and
0
workmanship for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims
all liability for any afrmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon
personal injuries, deaths, property damage, lost prots, and other matters which Buyer,
its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers
and limitations contained herein and relies on no other warranties or afrmations.
Red Lion Controls
India 201-B, 2nd Floor, Park Centra Opp 32 Mile Stone, Sector-30
Gurgaon-122002 Haryana, India
Tel +91 984 487 0503
LIMITED WARRANTY
Red Lion Controls
China
Unit 302, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113 3688
Fax +86 21 6113 3683
Loading...