Red Lion PAX2D Data Sheet

Dual Line Digital Input Panel Meter
Red Lion PAX®2 Series
PAX2D - Dual Line Digital Input Panel MeterMeter
With its dual display and digital input, the PAX2D delivers an ideal solution for applications that require two parameters to be visualized at the same time.
Line one consists of a 0.7" high 6 digit LCD display that can be programmed to show Counters A, B, or C; Rate A, B, or C; or the Hi or Lo values. The color can be tied to the setpoints; providing the operator with a visual display of changing conditions in the application. A second display line can be programmed for any of the above parameters as well. The meter also offers a programmable custom unit indicator for both displays.
PAX2D provides the maximum in application flexibility; by accepting inputs from proximity sensors, magnetic sensors, photo eyes, length sensors, rotary pulse generators, transistors or a plain switch.
2
3
1
7
6
1. Top Line: 6-Digit 0.7" (18 mm) Display
2. Programmable for Red, Orange or Green
3. Custom Unit Indicator
4. Tactile Feel Buttons
5. Setpoint Annunciators
6. Bottom Line: 9-Digit 0.35" (9 mm) Green Display
7. Built-In USB Port
5
4
PRODUCT HIGHLIGHTS
> Count, Dual Count, Rate, and Dual Rate
> Math Function Capability
> Universal Power Supply: 50 to 250 VAC
or 21.6 to 250 VDC
> Built-in USB Programming/Virtual Comms Port
> Setpoints: Dual or Quad Relay; Quad Sinking;
Quad Sourcing/SSR Drive; and Dual Triac/Dual SSR Drive
> Retransmitted Analog Output
> Communications: Modbus Protocol; RS232,
RS485, DeviceNet, and Profibus
FEATURES & BENEFITS
> Main display offers three programmable,
easy-to-read colors: red, orange and green
> The display color can be tied to the setpoints
> Second display line is a 0.35" high 9 digit,
green LCD
> The 9-digit display accommodates totalizing
applications that exceed the normal 6-digit displays
> Stock one meter for multiple applications
PAX2D - Dual Line Digital Input Panel Meter Specifications
(2.54)
(44.45)
3.60 (91.44)
4.14 (105)
0.10
1.75
3.60 (91.44)
DISPLAY
Negative image LCD Top Line: 6-digit, 0.71" (18 mm) tri-color backlight
(red, green or orange) Display range: -199,999 to 999,999
Bottom Line: 9 digit, 0.35" (8.9 mm) green backlight
Display range: -199,999,999 to 999,999,999
POWER CONNECTION
AC Power: 40 to 250 VAC, 50/60 Hz, 20 VA DC Power: 21.6 to 250 VDC, 8 W
SENSOR POWER
+18 VDC, ±5% @ 60 mA max., short circuit protected
ANNUNCIATORS
Backlight color: Red
1 - setpoint alarm 1 2 - setpoint alarm 2 3 - setpoint alarm 3 4 - setpoint alarm 4
Units Label: programmable units annunciators
KEYPAD
2 programmable function keys, 4 keys total
COUNTER DISPLAYS
6-digit (top line) or 9-digit (bottom line) Top Line Display Range: -199,999 to 999,999 Bottom Line Display Range: -199,999,999 to 999,999,999 Over Range Display: OUEr Under Range Display: UndEr Display Designators: CtA, Ctb, CtC (top line), A, b, C (bottom line) Maximum Count Rates: 50% duty cycle, count mode dependent If setpoints disabled: 35 KHz for all modes except Quadrature
x4 (32 KHz)
If setpoint(s) enabled: 20 KHz for any mode except Quadrature
x1 (19 KHz), Quadrature x2 (17 KHz) and Quadrature x4 (10 KHz)
RATE DISPLAYS
6-digit (top or bottom line) Rate A or Rate B Display Range: 0 to 999,999 Rate C, Rate Max (High) or Min (Low) Display Range:
-199,999 to 999,999 Over Range Display: OUEr Under Range Display: UndEr Display Designators: RtA, Rtb, RtC, Hi, Lo (top or bottom line) Maximum Frequency: 50 KHz Minimum Frequency: 0.001 Hz Display Update Time: 0.1 to 999.9 seconds Accuracy: ±0.01%
INPUT CAPABILITIES
The inputs accept pulses from a variety of sources including switch
contacts, TTL outputs, magnetic pickups and all standard RLC sensors. Inputs accept current sinking or current sourcing outputs and provide selectable input filtering for low frequency signals or switch contact debounce.
MEMORY
Nonvolatile memory retains all programmable
parameters and display values
INPUTS
Three programmable user inputs
All specifications are subject to change. Consult the company website for more information.
ENVIRONMENTAL
Operating Temperature Range: 0 to 50 °C Storage Temperature Range: -40 to 60 °C Operating and Storage Humidity: 0 to 85% max.
RH non-condensing
Altitude: Up to 2000 meters
CERTIFICATION & COMPLIANCE
Refer to EMC Installation Guidelines section of the bulletin for
additional information
CONNECTIONS
High compression cage-clamp terminal block
MECHANICAL
Construction: This unit is rated for NEMA 4X/IP65 indoor use; IP20 Touch
safe; Installation Category II, Pollution Degree 2; One piece bezel/case; Flame resistant; Synthetic rubber keypad; Panel gasket and mounting clip included
Weight: 8 oz. (226.8 g)
DIMENSIONS In inches (mm)
1.95
(49.53)
3.80 (96.52)
1.75
(44.45)
0.10
(2.54)
4.14 (105)
ORDERING INFORMATION
PART NUMBER MODEL DESCRIPTION
PAX2D000 PAX2D Dual Line Digital Input Panel Meter
PAXCDS10
PAXCDS20 Quad Setpoint Relay Output Card
PAXCDS30 Quad Setpoint Sinking Open Collector Output Card
PAXCDS40 Quad Setpoint Sourcing Open Collector Output Card
PAXCDS50 Dual Triac/Dual SSR Drive Digital Output Card
PAXCDS60 Quad Form C Relay Digital Output Card
PAXCDC10
PAXCDC1C
PAXCDC20 RS232 Serial Communications Card with Terminal Block
PAXCDC2C
PAXCDC30 DeviceNet Communications Card
PAXCDC50 Profibus-DP Communications Card
PAXCDL10 PAXCDL Analog Output Card
PAXCDS
PAXCDC
Dual Setpoint Relay Output Card
RS485 Serial Communications Card with Terminal Block
Extended RS485 Serial Communications Card with Dual RJ11 Connector
Extended RS232 Serial Communications Card with 9 Pin D Connector
Loading...