40003Maximum Value (Hi word)
40004Maximum Value (Lo word)
40005Minimum Value (Hi word)
40006Minimum Value (Lo word)
40007Total Value (Hi word)
40008Total Value (Lo word)
40009Setpoint 1 Value (Hi word)
40010Setpoint 1 Value (Lo word)
40011Setpoint 2 Value (Hi word)
40012Setpoint 2 Value (Lo word)
40013Setpoint 3 Value (Hi word)
40014Setpoint 3 Value (Lo word)
40015Setpoint 4 Value (Hi word)
40016Setpoint 4 Value (Lo word)
40017Setpoint 1 Band/Dev. Value (Hi word)
40018Setpoint 1 Band/Dev. Value (Lo word)
40019Setpoint 2 Band/Dev. Value (Hi word)
40020Setpoint 2 Band/Dev. Value (Lo word)
40021Setpoint 3 Band/Dev. Value (Hi word)
40022Setpoint 3 Band/Dev. Value (Lo word)
40023Setpoint 4 Band/Dev. Value (Hi word)
40024Setpoint 4 Band/Dev. Value (Lo word)
40031Input Offset Value (Hi word)
40032Input Offset Value (Lo word)
REGISTER NAMELOW LIMIT HIGH LIMIT
N/AN/AN/ARead Only
-199999999999N/ARead/Write
-199999999999N/ARead/Write
-199999999 999999999N/ARead/Write
-199999999999100Read/WriteActive List (A or B)
-199999999999200Read/WriteActive List (A or B)
-199999999999300Read/WriteActive List (A or B)
-199999999999400Read/WriteActive List (A or B)
-1999999999990Read/WriteActive List (A or B). Applicable only for Band or Deviation Setpoint Action.
-1999999999990Read/WriteActive List (A or B). Applicable only for Band or Deviation Setpoint Action.
-1999999999990Read/WriteActive List (A or B). Applicable only for Band or Deviation Setpoint Action.
-1999999999990Read/WriteActive List (A or B). Applicable only for Band or Deviation Setpoint Action.
N/AN/AN/ARead Only
-1999999999990Read/Write
FACTORY
SETTING
ACCESSCOMMENTS
Process value of present input level. This value is affected by Input Type,
Resolution, Scaling, & Offset Value. (Relative Value = Absolute Input Value +
Offset Value)
Status of Setpoint Outputs. Bit State: 0 = Off, 1 = On. Bit 3 = S1, Bit 2 = S2, Bit
1 = S3, Bit 0 = S4.
Outputs can only be activated/reset with this register when the respective bits
in the Manual Mode Register (MMR) are set.
Bit State: 0 = Auto Mode, 1 = Manual Mode
Bit 4 = S1, Bit 3 = S2, Bit 2 = S3, Bit 1 = S4, Bit 0 = Linear Output
Bit State: 1 = Reset Output, bit is returned to zero following reset processing;
Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4
Linear Output Card written to only if Linear Output is in Manual Mode.(MMR bit
0 = 1)
Gross value of present Input level. This value is affected by Input Type,
Resolution, Scaling, but not affected by Offset Value
Input Offset Value plus the Input Absolute Value equals the Relative Input
Value (standard meter value).
REGISTER
ADDRESS
INPUT PARAMETERSSEE MODULE 1 FOR PARAMETER DESCRIPTIONS
List AList B Input Scaling Points Parameters
40101 40201 Number of Scaling Points2162Read/WriteNumber of Linearization Scaling Points
40102 40202 ReservedN/AN/AN/AN/A
40103 40203 Scaling Pt.1 Input Value (Hi word)
40104 40204 Scaling Pt.1 Input Value (Lo word)
40105 40205 Scaling Pt.1 Display Value (Hi word)
40106 40206 Scaling Pt.1 Display Value (Lo word)
thruthruScaling Pts. 2 thru 15 Values…………
40163 40263 Scaling Pt.16 Input Value (Hi word)
40164 40264 Scaling Pt.16 Input Value (Lo word)
40165 40265 Scaling Pt.16 Display Value (Hi word)
40166 40266 Scaling Pt.16 Display Value (Lo word)
List AList B Setpoint Values
40167 40267 Setpoint 1 Value (Hi word)
40168 40268 Setpoint 1 Value (Lo word)
40169 40269 Setpoint 2 Value (Hi word)
40170 40270 Setpoint 2 Value (Lo word)
40171 40271 Setpoint 3 Value (Hi word)
40172 40272 Setpoint 3 Value (Lo word)
40173 40273 Setpoint 4 Value (Hi word)
40174 40274 Setpoint 4 Value (Lo word)
40175 40275 Setpoint 1 Band/Dev. Value (Hi word)
40176 40276 Setpoint 1 Band/Dev. Value (Lo word)
40177 40277 Setpoint 2 Band/Dev. Value (Hi word)
40178 40278 Setpoint 2 Band/Dev. Value (Lo word)
40179 40279 Setpoint 3 Band/Dev. Value (Hi word)
40180 40280 Setpoint 3 Band/Dev. Value (Lo word)
REGISTER NAMELOW LIMIT HIGH LIMIT
-1999999999990Read/Write1 = 1 in least signicant digit (Input Range dependant)
-1999999999990Read/Write1 = 1 display unit (disregard decimal point)
-1999999999990Read/Write1 = 1 in least signicant digit (Input Range dependant)
-1999999999990Read/Write1 = 1 display unit (disregard decimal point)
-199999999999100Read/Write1 = 1 display unit (disregard decimal point)
-199999999999200Read/Write1 = 1 display unit (disregard decimal point)
-199999999999300Read/Write1 = 1 display unit (disregard decimal point)
-199999999999400Read/Write1 = 1 display unit (disregard decimal point)
-1999999999990Read/WriteApplicable only for Band or Deviation Setpoint Action.
-1999999999990Read/WriteApplicable only for Band or Deviation Setpoint Action.
-1999999999990Read/WriteApplicable only for Band or Deviation Setpoint Action.
Registers 40107-40162 and 40207-40262 hold values for Scaling Points 2 thru
15, and follow the same ordering as Scaling Point 1.
REGISTER
ADDRESS
40181 40281 Setpoint 4 Band/Dev. Value (Hi word)
40182 40282 Setpoint 4 Band/Dev. Value (Lo word)
USER INPUT / FUNCTION KEYSSEE MODULE 2 FOR PARAMETER DESCRIPTIONS
40301User Input Active State010Read/Write0 = Active Low, 1 = Active High
40302User Input 1 Action0280Read/Write
40303User Input 2 Action0280Read/WriteSame as User Input 1 Action
40304User F1 Key Action0170Read/Write
40305User F2 Key Action0170Read/WriteSame as User F1 Key Action
40306User F1 Second Action0170Read/WriteSame as User F1 Key Action
40307User F2 Second Action0170Read/WriteSame as User F1 Key Action
0 = _ 7 = G 14 = O 21 = V 28 = 4 35 = e 42 = r
1 = A 8 = H 15 = P 22 = Y 29 = 5 36 = g 43 = u
2 = b 9 = I 16 = Q 23 = Z 30 = 6 37 = h 44 = 3 = C 10 = J 17 = R 24 = 0 31 = 7 38 = i 45 = °
4 = d 11 = K 18 = S 25 = 1 32 = 8 39 = n 46 =
5 = E 12 = L 19 = t 26 = 2 33 = 9 40 = o
6 = F 13 = N 20 = U 27 = 3 34 = c 41 = q
40403Hysteresis Value1650002Read/Write1 = 1 Display Unit
40404On Time Delay0327500Read/Write1 = 0.1 Second
40405Off Time Delay0327500Read/Write1 = 0.1 Second
40406Output Logic010Read/Write0 = Normal, 1 = Reverse
40487Transmit Delay025010Read/Write1 = 0.001 Second
40488Abbreviated Transmission (RLC only)010Read/Write0 = No, 1 = Yes (Not used when communications type is Modbus)
40489Print Options (RLC only)0151Read/Write
40490Load Serial Settings010Read/Write
ANALOG OUTPUT PARAMETERSSEE MODULE 8 FOR PARAMETER DESCRIPTIONS
40491Type021Read/Write0 = 0-20 mA, 1 = 4-20 mA, 2 = 0-10 V
40492Assignment090Read/Write0=NONE, 1=rEL, 2=AbS, 3=tOtAL, 4=HI, 5=LO, 6=S1, 7=S2, 8=S3, 9=S4
40493Analog Low Scale Value (Hi word)
40494Analog Low Scale Value (Lo word)
40495Analog High Scale Value (Hi word)
40496Analog High Scale Value (Lo word)
40497Update time01000Read/Write0 = Max update rate, 1 = 0.1 Second
40498Probe Failure Action (TC or RTD only)010Read/Write0 = Low Scale, 1 = High Scale (only applies for TC or RTD input)
FACTORY SERVICE
40501-40506Factory Service RegistersN/AN/AN/ARead/WriteFactory Use Only - Do Not Modify
41001-41010Slave IDN/AN/AN/ARead Only
41101-41116GUID/ScratchN/AN/AN/ARead/WriteReserved (may be used in future RLC software)
REGISTER NAMELOW LIMIT HIGH LIMIT
099
1247Modbus: 1-247
-1999999999990Read/WriteDisplay value that corresponds with 0 V, 0 mA or 4 mA output
-19999999999910000Read/WriteDisplay value that corresponds with 10 V or 20 mA output
FACTORY
SETTING
247Read/Write
ACCESSCOMMENTS
0 = No Change, 1 = Green, 2 = Orange, 3 = Red, 4 = Grn/Org, 5 = Red/Org,
6 = Red/Grn, 7 = Line 1 Color
RLC Protocol: 0-99
0 = No, 1 = Yes (Not used when communications type is Modbus) Bit 0 – Print
Input Value, Bit 1 – Print Total Value, Bit 2 – Print Max & Min Values,
Bit 3 – Print Setpoint Values
Changing 40481-40487 will not update the PAX2A until this register is written
with a 1. After the write, the communicating device must be changed to new
PAX2A settings and this register returns to 0.