PAX2A Modbus Register Table 4/15/13 LP0931A
REGISTER
ADDRESS
FREQUENTLY USED REGISTERS
40001 Input Relative Value (Hi word)
40002 Input Relative Value (Lo word)
40003 Maximum Value (Hi word)
40004 Maximum Value (Lo word)
40005 Minimum Value (Hi word)
40006 Minimum Value (Lo word)
40007 Total Value (Hi word)
40008 Total Value (Lo word)
40009 Setpoint 1 Value (Hi word)
40010 Setpoint 1 Value (Lo word)
40011 Setpoint 2 Value (Hi word)
40012 Setpoint 2 Value (Lo word)
40013 Setpoint 3 Value (Hi word)
40014 Setpoint 3 Value (Lo word)
40015 Setpoint 4 Value (Hi word)
40016 Setpoint 4 Value (Lo word)
40017 Setpoint 1 Band/Dev. Value (Hi word)
40018 Setpoint 1 Band/Dev. Value (Lo word)
40019 Setpoint 2 Band/Dev. Value (Hi word)
40020 Setpoint 2 Band/Dev. Value (Lo word)
40021 Setpoint 3 Band/Dev. Value (Hi word)
40022 Setpoint 3 Band/Dev. Value (Lo word)
40023 Setpoint 4 Band/Dev. Value (Hi word)
40024 Setpoint 4 Band/Dev. Value (Lo word)
40025 Setpoint Output Register (SOR) 0 15 N/A Read/Write
40026 Manual Mode Register (MMR) 0 31 0 Read/Write
40027 Reset Output Register 0 15 0 Read/Write
40028 Analog Output Register (AOR) 0 4095 0 Read/Write
40029 Input Absolute Value (Hi word)
40030 Input Absolute Value (Lo word)
40031 Input Offset Value (Hi word)
40032 Input Offset Value (Lo word)
REGISTER NAME LOW LIMIT HIGH LIMIT
N/A N/A N/A Read Only
-199999 999999 N/A Read/Write
-199999 999999 N/A Read/Write
-199999999 999999999 N/A Read/Write
-199999 999999 100 Read/Write Active List (A or B)
-199999 999999 200 Read/Write Active List (A or B)
-199999 999999 300 Read/Write Active List (A or B)
-199999 999999 400 Read/Write Active List (A or B)
-199999 999999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Setpoint Action.
-199999 999999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Setpoint Action.
-199999 999999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Setpoint Action.
-199999 999999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Setpoint Action.
N/A N/A N/A Read Only
-199999 999999 0 Read/Write
FACTORY
SETTING
ACCESS COMMENTS
Process value of present input level. This value is affected by Input Type,
Resolution, Scaling, & Offset Value. (Relative Value = Absolute Input Value +
Offset Value)
Status of Setpoint Outputs. Bit State: 0 = Off, 1 = On. Bit 3 = S1, Bit 2 = S2, Bit
1 = S3, Bit 0 = S4.
Outputs can only be activated/reset with this register when the respective bits
in the Manual Mode Register (MMR) are set.
Bit State: 0 = Auto Mode, 1 = Manual Mode
Bit 4 = S1, Bit 3 = S2, Bit 2 = S3, Bit 1 = S4, Bit 0 = Linear Output
Bit State: 1 = Reset Output, bit is returned to zero following reset processing;
Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4
Linear Output Card written to only if Linear Output is in Manual Mode.(MMR bit
0 = 1)
Gross value of present Input level. This value is affected by Input Type,
Resolution, Scaling, but not affected by Offset Value
Input Offset Value plus the Input Absolute Value equals the Relative Input
Value (standard meter value).
REGISTER
ADDRESS
INPUT PARAMETERS SEE MODULE 1 FOR PARAMETER DESCRIPTIONS
40081 Input Range 0 26 10 Read/Write
40082 Temperature Scale (TC or RTD only) 0 1 1 Read/Write 0 = °C, 1 = °F
40083 Ice Point Compensation (TC only) 0 1 1 Read/Write 0 = Off, 1 = On
40084 ADC Conversion Rate (samples/sec) 0 5 0 Read/Write 0 = 5, 1 = 10, 2 = 20, 3 = 40, 4 = 80, 5 = 160
40085 Decimal Point 0 4 2 Read/Write 0 = 0, 1 = 0.0, 2 = 0.00, 3 = 0.000, 4 = 0.0000
40086 Rounding Factor 0 6 0 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20, 5 = 50, 6 = 100
40087 Digital Input Filter 0 250 10 Read/Write 1 = 0.1 Second
40088 Filter Band 0 250 10 Read/Write 1 = 1 display unit
40089 Input Scaling Points in List Function 0 1 0 Read/Write 0 = No, 1 = Yes
List A List B Input Scaling Points Parameters
40101 40201 Number of Scaling Points 2 16 2 Read/Write Number of Linearization Scaling Points
40102 40202 Reserved N/A N/A N/A N/A
40103 40203 Scaling Pt.1 Input Value (Hi word)
40104 40204 Scaling Pt.1 Input Value (Lo word)
40105 40205 Scaling Pt.1 Display Value (Hi word)
40106 40206 Scaling Pt.1 Display Value (Lo word)
thru thru Scaling Pts. 2 thru 15 Values … … … …
40163 40263 Scaling Pt.16 Input Value (Hi word)
40164 40264 Scaling Pt.16 Input Value (Lo word)
40165 40265 Scaling Pt.16 Display Value (Hi word)
40166 40266 Scaling Pt.16 Display Value (Lo word)
List A List B Setpoint Values
40167 40267 Setpoint 1 Value (Hi word)
40168 40268 Setpoint 1 Value (Lo word)
40169 40269 Setpoint 2 Value (Hi word)
40170 40270 Setpoint 2 Value (Lo word)
40171 40271 Setpoint 3 Value (Hi word)
40172 40272 Setpoint 3 Value (Lo word)
40173 40273 Setpoint 4 Value (Hi word)
40174 40274 Setpoint 4 Value (Lo word)
40175 40275 Setpoint 1 Band/Dev. Value (Hi word)
40176 40276 Setpoint 1 Band/Dev. Value (Lo word)
40177 40277 Setpoint 2 Band/Dev. Value (Hi word)
40178 40278 Setpoint 2 Band/Dev. Value (Lo word)
40179 40279 Setpoint 3 Band/Dev. Value (Hi word)
40180 40280 Setpoint 3 Band/Dev. Value (Lo word)
REGISTER NAME LOW LIMIT HIGH LIMIT
-199999 999999 0 Read/Write 1 = 1 in least signicant digit (Input Range dependant)
-199999 999999 0 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 0 Read/Write 1 = 1 in least signicant digit (Input Range dependant)
-199999 999999 0 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 100 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 200 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 300 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 400 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
FACTORY
SETTING
ACCESS COMMENTS
0 = 250µA 6 = 2V 12 = 1KΩ 18 = TC-R 24 = RTD 392
1 = 2.5mA 7 = 10V 13 = 10KΩ 19 = TC-S 25 = RTD 672
2 = 25mA 8 = 25V 14 = TC-T 20 = TC-B 26 = RTD 427
3 = 250mA 9 = 100V 15 = TC-E 21 = TC-N
4 = 2A 10 = 200V 16 = TC-J 22 = TC-C
5 = 250mV 11 = 100Ω 17 = TC-K 23 = RTD 385
Registers 40107-40162 and 40207-40262 hold values for Scaling Points 2 thru
15, and follow the same ordering as Scaling Point 1.