Red Lion PAX2A Technical Data

PAX2A Modbus Register Table 4/15/13 LP0931A
REGISTER
ADDRESS
FREQUENTLY USED REGISTERS
40002 Input Relative Value (Lo word)
40003 Maximum Value (Hi word) 40004 Maximum Value (Lo word) 40005 Minimum Value (Hi word) 40006 Minimum Value (Lo word) 40007 Total Value (Hi word) 40008 Total Value (Lo word) 40009 Setpoint 1 Value (Hi word) 40010 Setpoint 1 Value (Lo word) 40011 Setpoint 2 Value (Hi word) 40012 Setpoint 2 Value (Lo word) 40013 Setpoint 3 Value (Hi word) 40014 Setpoint 3 Value (Lo word) 40015 Setpoint 4 Value (Hi word) 40016 Setpoint 4 Value (Lo word) 40017 Setpoint 1 Band/Dev. Value (Hi word) 40018 Setpoint 1 Band/Dev. Value (Lo word) 40019 Setpoint 2 Band/Dev. Value (Hi word) 40020 Setpoint 2 Band/Dev. Value (Lo word) 40021 Setpoint 3 Band/Dev. Value (Hi word) 40022 Setpoint 3 Band/Dev. Value (Lo word) 40023 Setpoint 4 Band/Dev. Value (Hi word) 40024 Setpoint 4 Band/Dev. Value (Lo word)
40025 Setpoint Output Register (SOR) 0 15 N/A Read/Write
40026 Manual Mode Register (MMR) 0 31 0 Read/Write
40027 Reset Output Register 0 15 0 Read/Write
40028 Analog Output Register (AOR) 0 4095 0 Read/Write
40029 Input Absolute Value (Hi word)
40030 Input Absolute Value (Lo word)
40031 Input Offset Value (Hi word) 40032 Input Offset Value (Lo word)
REGISTER NAME LOW LIMIT HIGH LIMIT
N/A N/A N/A Read Only
-199999 999999 N/A Read/Write
-199999 999999 N/A Read/Write
-199999999 999999999 N/A Read/Write
-199999 999999 100 Read/Write Active List (A or B)
-199999 999999 200 Read/Write Active List (A or B)
-199999 999999 300 Read/Write Active List (A or B)
-199999 999999 400 Read/Write Active List (A or B)
-199999 999999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Setpoint Action.
-199999 999999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Setpoint Action.
-199999 999999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Setpoint Action.
-199999 999999 0 Read/Write Active List (A or B). Applicable only for Band or Deviation Setpoint Action.
N/A N/A N/A Read Only
-199999 999999 0 Read/Write
FACTORY
SETTING
ACCESS COMMENTS
Process value of present input level. This value is affected by Input Type, Resolution, Scaling, & Offset Value. (Relative Value = Absolute Input Value + Offset Value)
Status of Setpoint Outputs. Bit State: 0 = Off, 1 = On. Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4. Outputs can only be activated/reset with this register when the respective bits in the Manual Mode Register (MMR) are set.
Bit State: 0 = Auto Mode, 1 = Manual Mode Bit 4 = S1, Bit 3 = S2, Bit 2 = S3, Bit 1 = S4, Bit 0 = Linear Output
Bit State: 1 = Reset Output, bit is returned to zero following reset processing; Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4
Linear Output Card written to only if Linear Output is in Manual Mode.(MMR bit 0 = 1)
Gross value of present Input level. This value is affected by Input Type, Resolution, Scaling, but not affected by Offset Value
Input Offset Value plus the Input Absolute Value equals the Relative Input Value (standard meter value).
REGISTER
ADDRESS
INPUT PARAMETERS SEE MODULE 1 FOR PARAMETER DESCRIPTIONS
40081 Input Range 0 26 10 Read/Write
40082 Temperature Scale (TC or RTD only) 0 1 1 Read/Write 0 = °C, 1 = °F 40083 Ice Point Compensation (TC only) 0 1 1 Read/Write 0 = Off, 1 = On 40084 ADC Conversion Rate (samples/sec) 0 5 0 Read/Write 0 = 5, 1 = 10, 2 = 20, 3 = 40, 4 = 80, 5 = 160 40085 Decimal Point 0 4 2 Read/Write 0 = 0, 1 = 0.0, 2 = 0.00, 3 = 0.000, 4 = 0.0000 40086 Rounding Factor 0 6 0 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20, 5 = 50, 6 = 100 40087 Digital Input Filter 0 250 10 Read/Write 1 = 0.1 Second 40088 Filter Band 0 250 10 Read/Write 1 = 1 display unit 40089 Input Scaling Points in List Function 0 1 0 Read/Write 0 = No, 1 = Yes
List A List B Input Scaling Points Parameters 40101 40201 Number of Scaling Points 2 16 2 Read/Write Number of Linearization Scaling Points 40102 40202 Reserved N/A N/A N/A N/A 40103 40203 Scaling Pt.1 Input Value (Hi word) 40104 40204 Scaling Pt.1 Input Value (Lo word) 40105 40205 Scaling Pt.1 Display Value (Hi word) 40106 40206 Scaling Pt.1 Display Value (Lo word)
thru thru Scaling Pts. 2 thru 15 Values
40163 40263 Scaling Pt.16 Input Value (Hi word) 40164 40264 Scaling Pt.16 Input Value (Lo word) 40165 40265 Scaling Pt.16 Display Value (Hi word) 40166 40266 Scaling Pt.16 Display Value (Lo word)
List A List B Setpoint Values 40167 40267 Setpoint 1 Value (Hi word) 40168 40268 Setpoint 1 Value (Lo word) 40169 40269 Setpoint 2 Value (Hi word) 40170 40270 Setpoint 2 Value (Lo word) 40171 40271 Setpoint 3 Value (Hi word) 40172 40272 Setpoint 3 Value (Lo word) 40173 40273 Setpoint 4 Value (Hi word) 40174 40274 Setpoint 4 Value (Lo word) 40175 40275 Setpoint 1 Band/Dev. Value (Hi word) 40176 40276 Setpoint 1 Band/Dev. Value (Lo word) 40177 40277 Setpoint 2 Band/Dev. Value (Hi word) 40178 40278 Setpoint 2 Band/Dev. Value (Lo word) 40179 40279 Setpoint 3 Band/Dev. Value (Hi word) 40180 40280 Setpoint 3 Band/Dev. Value (Lo word)
REGISTER NAME LOW LIMIT HIGH LIMIT
-199999 999999 0 Read/Write 1 = 1 in least signicant digit (Input Range dependant)
-199999 999999 0 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 0 Read/Write 1 = 1 in least signicant digit (Input Range dependant)
-199999 999999 0 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 100 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 200 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 300 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 400 Read/Write 1 = 1 display unit (disregard decimal point)
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
FACTORY
SETTING
ACCESS COMMENTS
0 = 250µA 6 = 2V 12 = 1KΩ 18 = TC-R 24 = RTD 392 1 = 2.5mA 7 = 10V 13 = 10KΩ 19 = TC-S 25 = RTD 672
2 = 25mA 8 = 25V 14 = TC-T 20 = TC-B 26 = RTD 427 3 = 250mA 9 = 100V 15 = TC-E 21 = TC-N 4 = 2A 10 = 200V 16 = TC-J 22 = TC-C
5 = 250mV 11 = 100Ω 17 = TC-K 23 = RTD 385
Registers 40107-40162 and 40207-40262 hold values for Scaling Points 2 thru 15, and follow the same ordering as Scaling Point 1.
REGISTER
ADDRESS
40181 40281 Setpoint 4 Band/Dev. Value (Hi word) 40182 40282 Setpoint 4 Band/Dev. Value (Lo word)
USER INPUT / FUNCTION KEYS SEE MODULE 2 FOR PARAMETER DESCRIPTIONS
40301 User Input Active State 0 1 0 Read/Write 0 = Active Low, 1 = Active High
40302 User Input 1 Action 0 28 0 Read/Write
40303 User Input 2 Action 0 28 0 Read/Write Same as User Input 1 Action
40304 User F1 Key Action 0 17 0 Read/Write
40305 User F2 Key Action 0 17 0 Read/Write Same as User F1 Key Action 40306 User F1 Second Action 0 17 0 Read/Write Same as User F1 Key Action 40307 User F2 Second Action 0 17 0 Read/Write Same as User F1 Key Action
DISPLAY PARAMETERS SEE MODULE 3 FOR PARAMETER DESCRIPTIONS 40331 Line 1 Display Color 0 2 0 Read/Write 0 = Green, 1 = Red, 2 = Orange 40332 Display Intensity Level 0 4 4 Read/Write 0 = Min.(off), 4 = Max. 40333 Display Contrast Level 0 15 7 Read/Write 40334 Line 1 Display 0 8 1 Read/Write 0 = None, 1 = Input, 2 = Total, 3 = Hi, 4 = Lo, 5 = S1, 6 = S2, 7 = S3, 8 = S4 40335 Units Mnemonic 0 1 0 Read/Write 0 = Off, 1 = List
40336 Units Digit 1 (Left) 0 46 0 Read/Write
40337 Units Digit 2 (Center) 0 46 0 Read/Write Same selections as Digit 1 40338 Units Digit 3 (Right) 0 46 0 Read/Write Same selections as Digit 1 40339 Line 2 Input Display Access 0 2 0 Read/Write 0=LOC, 1=d-rEd, 2=d-Ent 40340 Line 2 Totalizer Display Access 0 2 0 Read/Write 0=LOC, 1=d-rEd, 2=d-Ent 40341 Line 2 Maximum (Hi) Value Access 0 2 0 Read/Write 0=LOC, 1=d-rEd, 2=d-Ent 40342 Line 2 Minimum (Lo) Value Access 0 2 0 Read/Write 0=LOC, 1=d-rEd, 2=d-Ent 40343 Line 2 List Selection Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE 40344 Line 2 Setpoint 1 Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE 40345 Line 2 S1 Band/Dev. Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE 40346 Line 2 Setpoint 2 Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE 40347 Line 2 S2 Band/Dev.Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE 40348 Line 2 Setpoint 3 Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE 40349 Line 2 S3 Band/Dev.Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE 40350 Line 2 Setpoint 4 Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE
REGISTER NAME LOW LIMIT HIGH LIMIT
-199999 999999 0 Read/Write Applicable only for Band or Deviation Setpoint Action.
FACTORY
SETTING
ACCESS COMMENTS
0 = NO 8 = d-tot 16 = r-HL 24 = r-4 1 = PLOC 9 = r-tot1 17 = dISP 25 = r-34 2 = rEL 10 = r-tot2 18 = d-LEV 26 = r-234 3 = d-rEL 11 = E-tot 19 = Color 27 = r-ALL 4 = d-HLd 12 = d-HI 20 = LISt 28 = Print 5 = A-HLd 13 = r-HI 21 = r-1 6 = SYNC 14 = d-Lo 22 = r-2 7 = bAt 15 = r-Lo 23 = r-3
0 = NO 5 = r-HI 10 = r-1 15 = r-234 1 = rEL 6 = r-Lo 11 = r-2 16 = r-ALL 2 = d-rEL 7 = r-HL 12 = r-3 17 = Print 3 = bAt 8 = d-LEV 13 = r-4 4 = r-tot 9 = LISt 14 = r-34
0 = _ 7 = G 14 = O 21 = V 28 = 4 35 = e 42 = r 1 = A 8 = H 15 = P 22 = Y 29 = 5 36 = g 43 = u 2 = b 9 = I 16 = Q 23 = Z 30 = 6 37 = h 44 = ­3 = C 10 = J 17 = R 24 = 0 31 = 7 38 = i 45 = ° 4 = d 11 = K 18 = S 25 = 1 32 = 8 39 = n 46 = 5 = E 12 = L 19 = t 26 = 2 33 = 9 40 = o 6 = F 13 = N 20 = U 27 = 3 34 = c 41 = q
REGISTER
ADDRESS
40351 Line 2 S4 Band/Dev.Value Access 0 5 0 Read/Write 0=LOC, 1=d-rEd, 2=d-ENt, 3=P-rEd, 4=P-ENt, 5=HidE 40352 Reserved N/A N/A N/A N/A 40353 Reserved N/A N/A N/A N/A 40354 Reserved N/A N/A N/A N/A 40355 Reserved N/A N/A N/A N/A 40356 Line 2 Display Color Access 0 3 0 Read/Write 0=LOC, 1=P-rEd, 2=P-ENt, 3=HidE 40357 Line 2 Display Intensity Level Access 0 3 0 Read/Write 0=LOC, 1=P-rEd, 2=P-ENt, 3=HidE 40358 Line 2 Display Contrast Level Access 0 3 0 Read/Write 0=LOC, 1=P-rEd, 2=P-ENt, 3=HidE 40359 Line 2 Zero (Tare) Display Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40360 Line 2 Batch Input to Totalizer Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40361 Line 2 Reset Totalizer Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40362 Line 2 Reset Max (Hi) Display Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40363 Line 2 Reset Min (Lo) Display Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40364 Line 2 Reset Max and Min Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40365 Line 2 Reset Alarm 1 Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40366 Line 2 Reset Alarm 2 Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40367 Line 2 Reset Alarm 3 Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40368 Line 2 Reset Alarm 4 Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40369 Line 2 Reset Alarm 3 and 4 Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40370 Line 2 Reset Alarm 2, 3 and 4 Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40371 Line 2 Reset All Alarms (1-4) Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40372 Line 2 Print Request Access 0 2 0 Read/Write 0=LOC, 1=P-ENt, 2=HidE 40373 Line 2 Security Code Value 0 250 0 Read/Write
SECONDARY PARAMETERS SEE MODULE 4 FOR PARAMETER DESCRIPTIONS 40381 Max (Hi) Capture Value Assignment 0 1 0 Read/Write 0 = Relative, 1 = Absolute 40382 Max (Hi) Capture Delay Time 0 32750 10 Read/Write 0 = Max Update Rate, 1 = 0.1Sec 40383 Min (Lo) Capture Value Assignment 0 1 0 Read/Write 0 = Relative, 1 = Absolute 40384 Min (Lo) Capture Delay Time 0 32750 10 Read/Write 0 = Max Update Rate, 1 = 0.1Sec 40385 Display Update (readings per second) 0 4 0 Read/Write 0 = 1, 1 = 2, 2 = 5, 3 = 10, 4 = 20
TOTALIZER PARAMETERS SEE MODULE 5 FOR PARAMETER DESCRIPTIONS 40391 Totalizer Decimal Point 0 4 3 Read/Write 0 = 0, 1 = 0.0, 2 = 0.00, 3 = 0.000, 4 = 0.0000 40392 Totalizer Time Base 0 3 1 Read/Write 0 = Second, 1 = Minute, 2 = Hour, 3 = Day 40393 Totalizer Scale Factor 1 65000 1000 Read/Write 1 = 0.001 40394 Totalizer Reset at Power Up 0 1 0 Read/Write 0 = No, 1 = Yes 40395 Totalizer Low Cut Value (Hi word) 40396 Totalizer Low Cut Value (Lo word)
SETPOINT PARAMETERS SEE MODULE 6 FOR PARAMETER DESCRIPTIONS
Setpoint 1
40401 Assignment 0 3 0 Read/Write 0 = None, 1 = Rel, 2 = Abs, 3 = Total
40402 Action 0 10 0 Read/Write
40403 Hysteresis Value 1 65000 2 Read/Write 1 = 1 Display Unit 40404 On Time Delay 0 32750 0 Read/Write 1 = 0.1 Second 40405 Off Time Delay 0 32750 0 Read/Write 1 = 0.1 Second 40406 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse
REGISTER NAME LOW LIMIT HIGH LIMIT
-199999 999999 -199999 Read/Write
FACTORY
SETTING
ACCESS COMMENTS
0=No, 1=Ab-HI, 2=Ab-LO, 3=AU-HI, 4=AU-LO, 5=dE-HI, 6=dE-LO, 7=bANd, 8=bNdIn, 9=totLo, 10=totHI
REGISTER
ADDRESS
40407 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 40408 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 40409 Annunciator 0 3 1 Read/Write 0 = Off, 1 = Normal, 2 = Reverse, 3 = Flash
40410 Color 0 7 0 Read/Write
40411 Probe Failure Action (TC or RTD only) 0 1 0 Read/Write 0 = Off, 1 = On (only applies for TC or RTD input)
Setpoint 2
40421 Assignment 0 3 0 Read/Write 0 = None, 1 = Rel, 2 = Abs, 3 = Total
40422 Action 0 10 0 Read/Write
40423 Hysteresis Value 1 65000 2 Read/Write 1 = 1 Display Unit 40424 On Time Delay 0 32750 0 Read/Write 1 = 0.1 Second 40425 Off Time Delay 0 32750 0 Read/Write 1 = 0.1 Second 40426 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 40427 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 40428 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 40429 Annunciator 0 3 1 Read/Write 0 = Off, 1 = Normal, 2 = Reverse, 3 = Flash
40430 Color 0 7 0 Read/Write
40431 Probe Failure Action (TC or RTD only) 0 1 0 Read/Write 0 = Off, 1 = On (only applies for TC or RTD input)
Setpoint 3
40441 Assignment 0 3 0 Read/Write 0 = None, 1 = Rel, 2 = Abs, 3 = Total
40442 Action 0 10 0 Read/Write
40443 Hysteresis Value 1 65000 2 Read/Write 1 = 1 Display Unit 40444 On Time Delay 0 32750 0 Read/Write 1 = 0.1 Second 40445 Off Time Delay 0 32750 0 Read/Write 1 = 0.1 Second 40446 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 40447 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 40448 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 40449 Annunciator 0 3 1 Read/Write 0 = Off, 1 = Normal, 2 = Reverse, 3 = Flash
40450 Color 0 7 0 Read/Write
40451 Probe Failure Action (TC or RTD only) 0 1 0 Read/Write 0 = Off, 1 = On (only applies for TC or RTD input)
Setpoint 4
40461 Assignment 0 3 0 Read/Write 0 = None, 1 = Rel, 2 = Abs, 3 = Total
40462 Action 0 10 0 Read/Write
40463 Hysteresis Value 1 65000 2 Read/Write 1 = 1 Display Unit 40464 On Time Delay 0 32750 0 Read/Write 1 = 0.1 Second 40465 Off Time Delay 0 32750 0 Read/Write 1 = 0.1 Second 40466 Output Logic 0 1 0 Read/Write 0 = Normal, 1 = Reverse 40467 Reset Action 0 2 0 Read/Write 0 = Auto, 1 = Latch1, 2 = Latch2 40468 Standby Operation 0 1 0 Read/Write 0 = No, 1 = Yes 40469 Annunciator 0 3 1 Read/Write 0 = Off, 1 = Normal, 2 = Reverse, 3 = Flash
REGISTER NAME LOW LIMIT HIGH LIMIT
FACTORY
SETTING
ACCESS COMMENTS
0 = No Change, 1 = Green, 2 = Orange, 3 = Red, 4 = Grn/Org, 5 = Red/Org, 6 = Red/Grn, 7 = Line 1 Color
0=No, 1=Ab-HI, 2=Ab-LO, 3=AU-HI, 4=AU-LO, 5=dE-HI, 6=dE-LO, 7=bANd, 8=bNdIn, 9=totLo, 10=totHI
0 = No Change, 1 = Green, 2 = Orange, 3 = Red, 4 = Grn/Org, 5 = Red/Org, 6 = Red/Grn, 7 = Line 1 Color
0=No, 1=Ab-HI, 2=Ab-LO, 3=AU-HI, 4=AU-LO, 5=dE-HI, 6=dE-LO, 7=bANd, 8=bNdIn, 9=totLo, 10=totHI
0 = No Change, 1 = Green, 2 = Orange, 3 = Red, 4 = Grn/Org, 5 = Red/Org, 6 = Red/Grn, 7 = Line 1 Color
0=No, 1=Ab-HI, 2=Ab-LO, 3=AU-HI, 4=AU-LO, 5=dE-HI, 6=dE-LO, 7=bANd, 8=bNdIn, 9=totLo, 10=totHI
REGISTER
ADDRESS
40470 Color 0 7 0 Read/Write
40471 Probe Failure Action (TC or RTD only) 0 1 0 Read/Write 0 = Off, 1 = On (only applies for TC or RTD input)
SERIAL COMMUNICATIONS PARAMETERS SEE MODULE 7 FOR PARAMETER DESCRIPTIONS 40481 USB Mode 0 1 0 Read/Write 0 = Conguration, 1 = Port 40482 Type 0 2 2 Read/Write 0 = RLC Protocol (ASCII), 1 = Modbus RTU, 2 = Modbus ASCII 40483 Baud Rate 0 5 5 Read/Write 0=1200, 1=2400, 2=4800, 3=9600, 4=19200, 5=38400 40484 Data Bits 0 1 1 Read/Write 0 = 7 Bits, 1 = 8 Bits 40485 Parity 0 2 0 Read/Write 0 = None, 1 = Even, 2 = Odd
40486 Address
40487 Transmit Delay 0 250 10 Read/Write 1 = 0.001 Second 40488 Abbreviated Transmission (RLC only) 0 1 0 Read/Write 0 = No, 1 = Yes (Not used when communications type is Modbus)
40489 Print Options (RLC only) 0 15 1 Read/Write
40490 Load Serial Settings 0 1 0 Read/Write
ANALOG OUTPUT PARAMETERS SEE MODULE 8 FOR PARAMETER DESCRIPTIONS 40491 Type 0 2 1 Read/Write 0 = 0-20 mA, 1 = 4-20 mA, 2 = 0-10 V 40492 Assignment 0 9 0 Read/Write 0=NONE, 1=rEL, 2=AbS, 3=tOtAL, 4=HI, 5=LO, 6=S1, 7=S2, 8=S3, 9=S4 40493 Analog Low Scale Value (Hi word) 40494 Analog Low Scale Value (Lo word) 40495 Analog High Scale Value (Hi word) 40496 Analog High Scale Value (Lo word) 40497 Update time 0 100 0 Read/Write 0 = Max update rate, 1 = 0.1 Second 40498 Probe Failure Action (TC or RTD only) 0 1 0 Read/Write 0 = Low Scale, 1 = High Scale (only applies for TC or RTD input)
FACTORY SERVICE
40501-40506 Factory Service Registers N/A N/A N/A Read/Write Factory Use Only - Do Not Modify
41001-41010 Slave ID N/A N/A N/A Read Only
41101-41116 GUID/Scratch N/A N/A N/A Read/Write Reserved (may be used in future RLC software)
REGISTER NAME LOW LIMIT HIGH LIMIT
0 99 1 247 Modbus: 1-247
-199999 999999 0 Read/Write Display value that corresponds with 0 V, 0 mA or 4 mA output
-199999 999999 10000 Read/Write Display value that corresponds with 10 V or 20 mA output
FACTORY
SETTING
247 Read/Write
ACCESS COMMENTS
0 = No Change, 1 = Green, 2 = Orange, 3 = Red, 4 = Grn/Org, 5 = Red/Org, 6 = Red/Grn, 7 = Line 1 Color
RLC Protocol: 0-99
0 = No, 1 = Yes (Not used when communications type is Modbus) Bit 0 – Print Input Value, Bit 1 – Print Total Value, Bit 2 – Print Max & Min Values, Bit 3 – Print Setpoint Values
Changing 40481-40487 will not update the PAX2A until this register is written with a 1. After the write, the communicating device must be changed to new PAX2A settings and this register returns to 0.
RLC-PAX2A <a><b><0100h><0020h><0020h><0010h> <a> = SP Card Status. “0”-No Card, “2”-Dual SP, “4”-Quad SP <b> = Linear Card Status. “0”-Not Installled, “1”-Installed <0100h> = Version Number (1.00 or higher) <0020h><0020h> = 32 Register Writes, 32 Register Reads (Max.) <0010h> = 16 Register GUID/Scratch