Red Lion PAX2A User Manual

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
1/8 DIN Analog Input Panel Meter Installation Guide
U
R
C
PROCESS CONTROL EQUIPMENT
US LISTED
L
3RSD
Drawing No. LP0900A
Effective 04/13
See the Red Lion website at www.redlion.net or the enclosed USB thumbdrive for a complete user manual
SPECIFICATIONS
POWER:
AC Power: 40 to 250 VAC, 50/60 Hz, 20 VA DC Power: 21.6 to 250 VDC, 8 W Isolation: 2300 Vrms for 1 min. to all inputs and outputs.
INPUT CAPABILITIES:
Current Input Ranges:
± 250 µADC ± 2.5 mADC ± 25 mADC ± 250 mADC ± 2 ADC
Voltage Input Ranges:
± 250 mVDC ± 2.0 VDC ± 10 VDC ± 25 VDC ± 100 VDC ± 200 VDC
Thermocouple Inputs:
Types: T, E, J, K, R, S, B, N, C (W5/W26) Max Continuous Overvoltage: 30 V
RTD Inputs:
Type: 3 or 4 wire, 2 wire can be compensated for lead wire resistance Excitation current: 100 ohm range: 136.5 µA ±10% 10 ohm range: 2.05 mA ±10% Max. continuous overload: 30 VDC Input Type:
100 ohm Pt alpha = .00385 100 ohm Pt alpha = .00392 120 ohm Nickel alpha = .00672 10 ohm Copper alpha = .00427
Resistance Inputs:
Max. continuous overload: 30 VDC
INPUT RANGE COMPLIANCE
100 ohm 0.175 V 999 ohm 1.75 V
9999 ohm 17.5 V
EXCITATION POWER: Jumper selectable
Transmitter Power: +18 VDC, ± 5% @ 50 mA max. Reference Voltage: + 2 VDC, ± 2%
Compliance: 1KW load min (2 mA max) Temperature Coefficient: 40 ppm/ºC max.
Reference Current: 1.05 mADC, ± 2%
Compliance: 10 KW load max.
USER INPUTS: Two programmable user inputs
Max. Continuous Input: 30 VDC Isolation To Sensor Input Common: Not isolated.
ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50 °C Storage Temperature Range: -40 to 60 °C Vibration to IEC 68-2-6: Operational 5-150 Hz, 2 g Shock to IEC 68-2-27: Operational 25 g (10 g relay) Operating and Storage Humidity: 0 to 85% max. RH non-condensing Altitude: Up to 2000 meters
CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A IEC/EN 61010-1
RoHS Compliant UL Listed: File #E179259 Type 4X Indoor Enclosure rating (Face only) IP65 Enclosure rating (Face only) IP20 Enclosure rating (Rear of unit)
CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm) Wire Gauge Capacity: One 14 AWG (2.55 mm) solid,
two 18 AWG (1.02 mm) or four 20 AWG (0.61 mm)
CONSTRUCTION: This unit is rated NEMA 4X/IP65 for indoor use only.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece bezel/ case. Flame resistant. Synthetic rubber keypad. Panel gasket and mounting clip included.
WEIGHT: 8 oz. (226.8 g)
DIMENSIONS In inches (mm)
1.95
(49.53)
3.80 (96.52)
1
2
3
4
0.10
(2.54)
Note: Recommended minimum clearance (behind the panel) for mounting clip
installation is 2.1" (53.4) H x 5.5" (140) W.
1.75
(44.45)
4.14 (105)
1
3.60 (91.44)
SAFETY SUMMARY
PANEL
LATCHING SLOTS
BEZEL
PANEL GASKET
PANEL LATCH
LATCHING TABS
PANEL MOUNTING SCREWS
All safety related regulations, local codes and instructions that appear in this literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Do not use this unit to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the unit.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION:
Risk of electric shock.
SETTING THE JUMPERS
The PAX2A controller has four jumpers that must be checked and/or changed prior to applying power. The following Jumper Selection Figures show an enlargement of the jumper area.
To access the jumpers, remove the meter base from the case by firmly squeezing and pulling back on the side rear finger tabs. This should lower the latch below the case slot (which is located just in front of the finger tabs). It is recommended to release the latch on one side, then start the other side latch.
Warning: Exposed line voltage exists on the circuit boards. Remove all
power to the meter and load circuits before accessing inside of the meter.
INPUT RANGE JUMPERS
METER INSTALLATION
The PAX2A meets NEMA 4X/IP65 requirements when properly installed. The unit is intended to be mounted into an enclosed panel. Prepare the panel cutout to the dimensions shown. Remove the panel latch from the unit. Slide the panel gasket over the rear of the unit to the back of the bezel. The unit should be installed fully assembled. Insert the unit into the panel cutout.
While holding the unit in place, push the panel latch over the rear of the unit so that the tabs of the panel latch engage in the slots on the case. The panel latch should be engaged in the farthest forward slot possible. To achieve a proper seal, tighten the latch screws evenly until the unit is snug in the panel (Torque to approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.
Installation Environment
The unit should be installed in a location that does not exceed the operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided.
PANEL CUT-OUT
+.03
3.62
-.00
+.8
(92 )
-.0
+.02
1.77
+.5
(45 )
-.00
-.0
Main Circuit Board
JUMPER
LOCATIONS
Finger
Tab
REAR TERMINALS
EXCITATION OUTPUT JUMPER
RTD INPUTS
2 A
.25 A .025 A
.0025 A
250 µA
CURRENT INPUTS
FRONT DISPLAY
RTD
100
T
I
18V @ 50mA 2V REF.
1.05 mA REF.
10 ohm RTD 100 ohm RTD
V
V
INPUT RANGE JUMPERS
THERMOCOUPLE/
VOLTAGE
SELECTION
TEMPERATURE
VOLTAGE
LV - 250mV/2V/100Ω/1KΩ M - 10V/100V HV - 25V/200V/10KΩ
VOLTAGE/RESISTANCE
Finger
Tab
INPUTS
REAR TERMINALS
2
Loading...
+ 2 hidden pages