Red Lion LD2A05P0, LD4A05P0, LD2A, LD4A User guide

AIR PRESSURE STABILIZATION VENT
(57.15)
2.25
X
Z
Y
Tel +1 (717) 767-6511
C
US LISTED
C
US LISTED
Fax +1 (717) 764-0839 www.redlion.net
MODEL LD - LARGE DC VOLT/CURRENT/PROCESS DISPLAY
2.25" & 4" HIGH RED LED DIGITS PROGRAMMABLE SCALING AND DECIMAL POINTS PROGRAMMABLE USER INPUT DUAL 5 AMP FORM C RELAY ALUMINUM NEMA 4X/IP65 CASE CONSTRUCTION RS232/RS485 SERIAL COMMUNICATIONS
U
R
C
L
US LISTED
IND. CONT. EQ.
51EB
U
R
C
L
US LISTED
LABORATORY EQUIPMENT
3RSD
UNIVERSALLY POWERED
Bulletin No. LDA-C Drawing No. LP0673 Released 09/09
GENERAL DESCRIPTION
All models also come with dual Form C relay outputs and RS232 / RS485 serial communications.
SAFETY SUMMARY
All safety regulations, local codes and instructions that appear in this and corresponding literature, or on equipment, must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
The protective conductor terminal is bonded to conductive parts of the equipment for safety purposes and must be connected to an external protective earthing system.
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBER
LD2A
LD4A
LD Plug
2.25" High 5 Digit Red LED Volt/Current Meter w/ Relay Output and RS232/RS485 Serial Comms
4" High 5 Digit Red LED Volt/Current Meter w/ Relay Output and RS232/RS485 Serial Comms
Panel Meter Plug for LD models (NOT included in LD Product UL File)
LD2A05P0
LD4A05P0
LDPLUG00
SPECIFICATIONS
1. DISPLAY: 5 digit, 2.25" (57 mm) or 4" (101 mm) intensity adjustable Red LED
(-99999 to 99999)
2. POWER REQUIREMENTS:
AC POWER: 50 to 250 VAC 50/60 Hz, 26 VA DC POWER: 21.6 to 250 VDC, 11 W DC Out: +24 VDC @ 100 mA if input voltage is greater than 50 VAC/VDC
+24 VDC @ 50 mA if input voltage is less than 50 VDC
Isolation: 2300 Vrms for 1 min. to all inputs and outputs
3. INPUT RANGES: Jumper Selectable D.C. Voltages: 200 mV, 2 V, 20 V, 200 V, 10 V
INPUT
RANGE
200 mV 0.1% of span
20 V 0.1% of span
200 V
10 V
ACCURACY @
23
C LESS
THAN 85% RH
2 V 0.1% of span
0.1% of span
0.1% of span
INPUT
IMPEDANCE
1.027 M
1.027 M
1.027 M
1.027 M 538 K
D.C. Currents: 200 A, 2 mA, 20 mA, 200 mA
INPUT
RANGE
200 μΑ 0.1% of span
2 mA 0.1% of span
20 mA 0.1% of span
200 mA 0.1% of span
ACCURACY @
23
C LESS
THAN 85% RH
INPUT
IMPEDANCE
1.111 K 111 11 1
D.C. Process: 4 to 20 mA, 1 to 5 VDC, 0/1 to 10 VDC
INPUT RANGE SELECT RANGE
4 - 20 mA Use the 20 mA range
1 - 5 VDC Use the 10V range
1 - 10 VDC Use the 10V range
4. OVERRANGE/UNDERRANGE INDICATION: Input Overrange Indication: “
OLOL”.
Input Underrange Indication: “ULUL”.
Display Overrange/Underrange Indication: “.....”/“-.....
MAX
INPUT
RESOLUTION
SIGNAL
75 VDC 10 μV 70 ppm /°C
75 VDC 0.1 mV 70 ppm /°C
250 VDC 1 mV 70 ppm /°C
250 VDC
30 V
MAX
INPUT
SIGNAL
15 mA 10 nA 70 ppm /°C
50 mA 0.1 μA 70 ppm /°C
150 mA 1 μA 70 ppm /°C
500 mA 10 μA 70 ppm /°C
10 mV
1 mV
RESOLUTION
TEMP.
COEFFICIENT
70 ppm /°C
70 ppm /°C
TEMP.
COEFFICIENT
DIMENSIONS In inches (mm)
1
PART
NUMBER
Y (Height)X (Length)
4 (101.6)16 (406.4)LD2A05P0
7.875 (200)26 (660.4)LD4A05P0
Z (Center)
12 (304.3)
22 (558.8)
5. A/D CONVERTER: 16 bit resolution
MOUNTING HOLE (.281")
MUST BE CONNECTED TO
TERMINAL #3 (TBA)
A/D Conversion Rate: 6 readings/sec.
6. DISPLAY RESPONSE TIME: 500 msec min.
7. USER INPUT:
Software selectable pull-up (8.6 K) or pull-down resistor
(3.9 K) that determines active high or active low input logic. Trigger levels: V Response Time: 5 msec typ.; 50 msec debounce (activation and release)
= 1.0 V max; VIH = 2.4 V min; V
IL
MAX
= 28 VDC
8. COMMUNICATIONS:
Type: RS485 or RS232 Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Data: 7/8 bits Parity: no, odd or even Baud Rate: 300 to 38.4 K Bus Address: Selectable 0 to 99, Max. 32 meters per line (RS485)
9. MEMORY: Nonvolatile E
2
PROM retains all programming parameters and
max/min values when power is removed.
10. OUTPUT:
Type: Single FORM-C relay Isolation To Sensor & User Input Commons: 1400 Vrms for 1 min.
Working Voltage: 150 Vrms Contact Rating: 5 amps @ 120/240 VAC or 28 VDC (resistive load), 1/8
H.P. @ 120 VAC (inductive load)
Life Expectancy: 100,000 minimum operations Response Time:
Turn On Time: 4 msec max.
Turn Off Time: 4 msec max.
11. ENVIRONMENTAL CONDITIONS:
Operating temperature: 0 to 50 °C Storage temperature: -40 to 70 °C Operating and storage humidity: 0 to 85% max. RH (non-condensing) Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
direction for 1.5 hours, 2 g’s (1 g relay). Shock According to IEC 68-2-27: Operational 30 g’s (10 g relay), 11 msec
in 3 directions. Altitude: Up to 2,000 meters
12. CONNECTIONS:Internal removable terminal blocks
Wire Strip Length: 0.4" (10 mm) Wire Gage: 24-12 AWG copper wire Torque: 5.3 inch-lbs (0.6 N-m) max. Cable Diameter: Outside diameter must be 0.181" (4.6 mm) to 0.312" (7.9
mm) to maintain NEMA 4 rating of cord grips.
13. CONSTRUCTION: Aluminum enclosure, and steel side panels with textured
black polyurethane paint for scratch and corrosion resistance protection. Meets NEMA 4X/IP65 specifications. Installation Category II, Pollution Degree 2.
14. CERTIFICA TIONS AND COMPLIANCES:
SAFETY
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
File # E179259, UL61010A-1, CSA C22.2 No. 61010-1
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards Type 4X Enclosure rating, UL50 IECEE CB Scheme Test Report #E179259-A3-CB-1
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating, IEC 529
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
Control and Laboratory use.
Notes:
Immunity to Industrial Locations:
Criterion BEN 61000-4-2Electrostatic discharge 4 kV contact discharge 8 kV air discharge Criterion BEN 61000-4-3Electromagnetic RF fields 10 V/m Criterion BEN 61000-4-4Fast transients (burst) 2 kV power 1 kV signal Criterion AEN 61000-4-5Surge 1 kV L-L, 2 kV L&N-E power Criterion BEN 61000-4-6RF conducted interference 3 V/rms
Voltage dip/interruptions
Criterion AEN 61000-4-11
0.5 cycle
Emissions:
Class AEN 55011Emissions
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self-
recovers.
15. WEIGHT:
LD2A05XX - 4.5 lbs (2.04 kg) LD4A05XX - 10.5 lbs (4.76 kg)
1.0 INSTALLING THE METER
INSTALLATION
The meter meets NEMA 4X/IP65 requirements when properly installed.
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the operating temperature. Placing the unit near devices that generate excessive heat should be avoided. The unit should only be cleaned with a soft cloth and neutral soap product. Do NOT use solvents.
Continuous exposure to direct sunlight may accelerate the aging process of the front overlay. Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the keypad of the unit.
2.0 SETTING THE JUMPERS
INPUT RANGE JUMPER
This jumper is used to select the proper input range. The input range selected in programming must match the jumper setting. Select a range that is high enough to accommodate the maximum signal input to avoid overloads. To access the jumper, remove the side cover of the meter.
Warning: Exposed line voltage exists on the circuit boards.
Remove all power to the meter and load circuits before accessing inside of the meter.
MOUNTING INSTRUCTIONS
This display is designed to be wall mounted or suspended from a ceiling truss or other suitable structure capable of supporting the LDA. Caution should be exercised when hanging the display to provide for the safety of personnel. If hanging the LDA, run the suspension cables (or chains) through the mounting bracket holes. For wall mounting use #10-32 size bolts.
20 V/200 V
10 V
200 MV/2 V
2 MA
200 µA
20 MA
200 MA
RANGE SELECT
654231
TBC
2
3.0 WIRING THE METER
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to Electro­Magnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into the meter may be different for various installations. The meter becomes more immune to EMI with fewer I/O connections. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed below are some EMC guidelines for successful installation in an industrial environment.
1. The meter should be properly connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
c. Connect the shield to common of the meter and leave the other end of the
shield unconnected and insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be ran in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
4. Signal or Control cables within an enclosure should be routed as far as
possible from contactors, control relays, transformers, and other noisy
components.
5. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entry point of the enclosure. The
following EMI suppression devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC# FCOR0000) TDK # ZCAT3035-1330A Steward # 28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC# LFIL0000) Schaffner # FN670-1.8/07 Corcom # 1 VR3
Note: Reference manufacturer's instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
7. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubber: RLC# SNUB0000.
WIRING OVERVIEW
Electrical connections are made via pluggable terminal blocks located inside the meter. All conductors should conform to the meter's voltage and current ratings. All cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that the power supplied to the meter (DC or AC) be protected by a fuse or circuit breaker. When wiring the meter, compare the numbers on the label on the back of the meter case against those shown in wiring drawings for proper wire position. Strip the wire, leaving approximately 0.4" (10 mm) bare lead exposed (stranded wires should be tinned with solder.) Insert the lead under the correct screw clamp terminal and tighten until the wire is secure. (Pull wire to verify tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two #18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
WIRING CONNECTIONS
Internal removable terminal blocks are used for power and signal wiring. Access to terminal blocks is through conduit fittings. Remove end plates with ¼" nut driver. For LD4 versions, all wiring is on right side of unit. For LD2 versions, power and relay wiring is on the right side and the input, serial, DC out and user input is on the left side.
Connect drain wire from shielded cable(s) to screw on side plate for proper grounding.
TBA
321
Front
TBB
465132
Front
LD2
RANGE SELECT
TBC
TBD
LD4
321
465321
654231
53421
TBA
TBB
RANGE SELECT
TBC
TBD
31 2 4 56
Front
1 2345
3.1 POWER WIRING
The power wiring is made via the 3 position terminal block (TBA) located
inside the unit (right side). The DC out power is located: LD2 - left side, LD4
- right side
Power
Terminal 1: VAC/DC + Terminal 2: VAC/DC ­Terminal 3: Protective Conductor
Terminal
+
-
L1
1
2
L2
TBA
3
RIGHT SIDE VIEW LEFT SIDE VIEW
DC Out Power
Terminal 4: + 24 VDC OUT Terminal 6: User Common
3
+ EXC
4
USER COMM
6
TBC
3.2 USER INPUT WIRING
The User Input is located: LD2 - left side, LD4 - right side
Sinking Logic Sourcing Logic
Terminal 5: User Input Terminal 6: User Comm
5
USER
6
USER COMM
3.3 SETPOINT (OUTPUT) WIRING
The setpoint relays use a six position terminal block (TBB) located inside the
(right side).
N.C. 1
Terminal 1: NC 1 Terminal 2: NO 2 Terminal 3: Relay 1 Common Terminal 4: NC 1 Terminal 5: NO 2 Terminal 6: Relay 2 Common
1
2
N.O. 1
COMM 1
3
N.C. 2
4
5
N.O. 2
COMM 2
6
TBB
TBC
+
5
-
USER
6
USER COMM
TBC
3.4 INPUT WIRING
Before connecting signal wires, the Input Range Jumper should be verified
for proper position.
TBC
VOLT INPUT
INPUT COMMON
CURRENT INPUT
+24 VDC EXC.
USER INPUT
USER/EXC. COMMON
1
2
3
4
20 V/200 V 10 V 200 MV/2 V 200 µA 2 MA 20 MA 200 MA
5
6
3.5 INPUT SIGNAL WIRING
Voltage Signal (self powered)
Terminal 1: +VDC Terminal 2: -VDC
Current Signal (self powered)
Terminal 3: +ADC Terminal 2: -ADC
Current Signal (2 wire requiring excitation)
Terminal 4: +EXC Terminal 3: +ADC
CAUTION: Analog common is NOT isolated from user input
common. In order to preserve the safety of the meter application, the DC common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth ground potential. If not, hazardous voltage may be present at the User Input and Input Common terminals. Appropriate considerations must then be given to the potential of the input common with respect to earth ground. Always connect the analog signal common to terminal 2.
Current Signal (3 wire requiring excitation)
Terminal 3: +ADC (signal) Terminal 2: -ADC (common) Terminal 4: +EXC
VOLT
1 2
+
-
200 VDC MAX.
ANALOG COMM
2
200 MA DC MAX.
ANALOG COMM
CURRENT
3
Load
+
-
CURRENT
3
2 WIRE
TRANSMITTER
-
+ EXC.
4
+
out
ANALOG COMM
2
CURRENT
34
COMM
I
out
+ EXC.
Voltage Signal (3 wire requiring excitation)
Terminal 1: +VDC (signal) Terminal 2: -VDC (common) Terminal 4: +EXC
4
VOLT
1
V
3 WIRE TRANSMITTER
3.6 SERIAL WIRING
TBD
A
COMM
RXD
TXD
4
2
3
1
B
5
232
485
5
LD METER RECEIVING DEVICE
+5V
4
47K
47K
3
B (-)
A (+)
COMM.*
Transmit Enable
* OPTIONAL
1
TXD
RXD
COMM.
LD METER (DTE)
RECEIVING DEVICE
2
RXD
TXD
3
32
75
5
DTE
3
2
DB9
2
3
DTEDCE
DB25DB25
The serial connections are made via terminal block TBD located inside the
unit on the left side for the LD2 and on the right side for the LD4.
Terminal Block Connection Figure
RS485 Communications
The RS485 communication standard allows the connection of up to 32 devices on a single pair of wires, distances up to 4,000 ft. and data rates as high as 10M baud (the LDA is limited to 38.4k baud). The same pair of wires is used to both transmit and receive data. RS485 is therefore always half-duplex, that is, data cannot be received and transmitted simultaneously.
RS232 Communications
RS232 is intended to allow two devices to communicate over distances up to 50 feet. Data T erminal Equipment (DTE) transmits data on the T ransmitted Data (TXD) line and receives data on the Received Data (RXD) line. Data Computer Equipment (DCE) receives data on the TXD line and transmits data on the RXD line. The LD emulates a DTE. If the other device connected to the meter also emulates a DTE, the TXD and RXD lines must be interchanged for communications to take place. This is known as a null modem connection. Most printers emulate a DCE device while most computers emulate a DTE device.
Some devices cannot accept more than two or three characters in succession without a pause in between. In these cases, the meter employs a busy function.
As the meter begins to transmit data, the RXD line (RS232) is monitored to determine if the receiving device is “busy”. The receiving device asserts that it is busy by setting the RXD line to a space condition (logic 0). The meter then suspends transmission until the RXD line is released by the receiving device.
Terminal Block Connection Figure
4.0 REVIEWING THE FRONT BUTTONS AND DISPLAY
OPERATING MODE DISPLAY DESIGNATORS
MAX - Maximum display capture value MIN
Pressing the SEL button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically every four seconds
between the enabled display values.
BUTTON DISPLAY MODE OPERATION PROGRAMMING MODE OPERATION
PAR Access Programming Mode Store selected parameter and index to next parameter SEL RST
- Minimum display capture value
Index display through selected displays
Resets display
Advance through selection list/select digit position in parameter value
Increment selected digit of parameter value
“1” - To the left of the display indicates setpoint 1 output activated. “2” - To the left of the display indicates setpoint 2 output activated.
5
5.0 PROGRAMMING THE METER
Parameters
Output
Setpoint
Parameters
Signal Input
Pro
DISPLAY
MODE
Panel Key
Function
Parameters
3-dSP
Parameters
Display and Front
NO
PAR
RST
PAR PAR PAR PAR
2-SEC
1-INP
4-SPt
5-SEr
PAR
Serial
Setup
Parameters
Secondary
Display
Decimal
Point
Filter
Setting
Filter Band
Input Value
for Scaling
Point 1
Display Value
For Scaling
Point 1
User Input
Assignment
Input
Range
PAR
rANGE
dECPt
FILtr
bANd
INP 1
dSP 1
INP 2
U-ASN
1-INP
Pro
User Input
Function
dSP 2
USrIN
Input Value
for Scaling
Point 2
Display Value
For Scaling
Point 2
StYLE
Scaling
Style
OFSEt
Display
Offset Value
U-Act
User Input
Active Level
OVERVIEW
PROGRAMMING MENU
PROGRAMMING MODE ENTRY (PAR BUTTON)
It is recommended all programming changes be made off line, or before installation. The meter normally operates in the Display Mode. No parameters can be programmed in this mode. The Programming Mode is entered by pressing the PAR button. If it is not accessible, then it is locked by either a security code or a hardware lock.
MODULE ENTRY (SEL & PAR BUTTONS)
The Programming Menu is organized into five modules. These modules group together parameters that are related in function. The display will alternate between
 and the present module. The SEL button is used to select the desired
module. The displayed module is entered by pressing the PAR button.
MODULE MENU (PAR BUTTON)
Each module has a separate module menu (which is shown at the start of each module discussion). The PAR button is pressed to advance to a particular parameter to be changed, without changing the programming of preceding parameters. After completing a module, the display will return to  . Programming may continue by accessing additional modules.
SELECTION / VALUE ENTRY
For each parameter, the display alternates between the present parameter and the selections/value for that parameter. The SELand RST buttons are used to move through the selections/values for that parameter. Pressing the PAR button, stores and activates the displayed selection/value. This also advances the meter to the next parameter.
For numeric values, the value is displayed with one digit flashing (initially the right most digit). Pressing the RST button increments the digit by one or the user can hold the RST button and the digit will automatically scroll. The
SEL button will select the next digit to the left. Pressing the PAR button will
enter the value and move to the next parameter.
PROGRAMMING MODE EXIT (PAR BUTTON)
The Programming Mode is exited by pressing the PAR button with Pro NO displayed. This will commit any stored parameter changes to memory and return the meter to the Display Mode. (If power loss occurs before returning to the Display Mode, verify recent parameter changes.)
PROGRAMMING TIPS
It is recommended to start with Module 1 and proceed through each module in sequence. When programming is complete, it is recommended to record the parameter programming and lock out parameter programming with the user input or programming security code.
FACTORY SETTINGS
Factory Settings may be completely restored in Module 2. This is useful when encountering programming problems.
ALTERNATING SELECTION DISPLAY
In the explanation of the modules, the following dual display with arrows will appear. This is used to illustrate the display alternating between the parameter on top and the parameter’s Factory Setting on the bottom. In most cases, selections and values for the parameter will be listed on the right.
Indicates Program Mode Alternating Display
Parameter
USrIN
Factory Settings are shown.
N0
Selection/Value
5.1 MODULE 1 - SIGNAL INPUT PARAMETERS (1-INP)
PARAMETER MENU
INPUT RANGE
rAN6E
200v
SELECTION
200uA
0.002A
0.2u 2u
10u
Select the input range that corresponds to the external signal. This selection should be high enough to avoid input signal overload but low enough for the desired input resolution. This selection and the position of the Input Range Jumper must match.
RANGE
RESOLUTION
200.00 A
2.0000 mA
200.00 mV
2.0000 V
10.000 V
SELECTION
0.02A
0.2A 20u
200u
RANGE
RESOLUTION
20.000 mA
200.00 mA
20.000 V
200.00 V
dECPt
selection also affects the dSP1 and dSP2 parameters and setpoint values and offset value.
OFSEt
compensate for signal variations or sensor errors. This value is automatically
6
0.00
Select the decimal point location for the Input, MIN and MAX displays. This
0.00
The display can be corrected with an offset value. This can be used to
DISPLAY DECIMAL POINT
DISPLAY OFFSET VALUE
-19999 to 19999
0.000 0.00000.000.00
updated after a Zero Display to show how far the display is offset. A value of zero removes the effects of offset. The decimal point follows the dECPt selection.
FILTER SETTING
FILtr
If the displayed value is difficult to read due to small process variations or noise, increased levels of filtering will help to stabilize the display. Software filtering effectively combines a fraction of the current input reading with a fraction of the previous displayed reading to generate the new display.
Filter values represent no filtering (0), up to heavy filtering (3). A value of 1 for the filter uses 1/4 of the new input and 3/4 of the previous display to generate the new display. A filter value of 2 uses 1/8 new and 7/8 previous. A filter value of 3 uses 1/16 new and 15/16 previous.
0,1 2 3
1
DISPLAY VALUE FOR SCALING POINT 2
dSP 2
Enter the second Display Value by using the front panel buttons. This is the same for KEY and APLY scaling styles. The decimal point follows the dECPt selection.
General Notes on Scaling
1. When using the Apply (APLY) scaling style, input values for scaling points
must be confined to the range limits shown.
2. The same Input Value should not correspond to more than one Display Value.
(Example: 20 mA can not equal 0 and 20.)
3. For input levels beyond the programmed Input Values, the meter extends the
Display Value by calculating the slope from the two coordinate pairs (INP1 /
dSP1 & INP2 / dSP2).
100.00
-19999 to 99999
FILTER BAND
bANd
The filter will adapt to variations in the input signal. When the variation exceeds the input filter band value, the filter disengages. When the variation becomes less than the band value, the filter engages again. This allows for a stable readout, but permits the display to settle rapidly after a large process change. The value of the band is in display units, independent of the Display Decimal Point position. A band setting of ‘0’ keeps the filter permanently engaged at the filter level selected above.
StYLE
If Input Values and corresponding Display Values are known, the Key-in (KEY) scaling style can be used. This allows scaling without the presence or changing of the input signal. If Input Values have to be derived from the actual input signal source or simulator, the Apply (APLY) scaling style must be used.
INP 1
For Key-in (KEY) style, enter the first Input Value using the front panel buttons.
(The Input Range selection sets the decimal location for the Input Value).
For Apply (APLY) style, the meter shows the previously stored Input Value. To retain this value, press the SEL button to advance to the next parameter. To change the Input Value, press the meter. Adjust the signal source externally until the desired Input Value appears. Press the SEL button to enter the value being displayed.
dSP 1
Enter the first Display Value by using the front panel buttons. This is the same for KEY and APLY scaling styles. The decimal point follows the dECPt selection.
INP 2
For Key-in (KEY) style, enter the known second Input Value using the front panel buttons.
For Apply (APLY) style, the meter shows the previously stored Input Value for Scaling Point 2. To retain this value, press the SEL button to advance to the next parameter. To change the Input Value, press the RST button and apply the input signal to the meter. Adjust the signal source externally until the desired Input Value appears. Press the SEL button to enter the value being displayed.
0 to 199 display units
10
SCALING STYLE
KEy APLY
KEy
INPUT VALUE FOR SCALING POINT 1
0 to 29999
0.00
RST button and apply the input signal to the
DISPLAY VALUE FOR SCALING POINT 1
-19999 to 99999
0.00
INPUT VALUE FOR SCALING POINT 2
0 to 29999
100.00
USER INPUT FUNCTION
USrIN
P-Loc
ZErO
rESEt
d-HLd
d-SEL
d-LEV
Print
P-r5t rSt-1
rSt-2 rSt12
U-ASN
Select the value(s) to which the User Input Function is assigned. The User Input Assignment only applies if a selection of reset, display hold, or print and reset is selected in the User Input Function menu.
U-Act
Select whether the user input is configured as active low or active high.
NO
MODEDISPLAY
No Function
NO
Program Mode Lock-out
Zero Input (Edge triggered)
Reset (Edge triggered)
Display Hold
Display Select (Edge Triggered)
Display Intensity Level (Edge Triggered)
Print Request
Print and Reset
Setpoint 1 Reset
Setpoint 2 Reset
Setpoint 1 and 2 Reset
USER INPUT ASSIGNMENT
dSP
USER INPUT ACTIVE LEVEL
LO
DESCRIPTION
User Input disabled.
See Programming Mode Access chart (Module 3).
Zero the Input Display value causing Display Reading to be Offset.
Resets the assigned value(s) to the current input value.
Holds the assigned display, but all other meter functions continue as long as activated (maintained action).
Advance once for each activation.
Increase intensity one level for each activation.
Serial transmit of the active parameters selected in the Print Options menu (Module 5).
Same as Print Request followed by a momentary reset of the assigned value(s).
Resets setpoint 1 output.
Resets setpoint 2 output.
Reset both setpoint 1 and 2 outputs.
HI-LO HI
dSPLO
LO HI
7
5.2 MODULE 2 - SECONDARY FUNCTION PARAMETERS (2-SEC)
PAR
Max Capture
Delay Time
Max Display
Enable
Min Display
Enable
Access Code
For Service
Operations
Min Capture
Delay TIme
Factory
Service
Operations
2-SEC
HI-En HI-t
LO-En LO-t FCS
CodE
Pro
PARAMETER MENU
MAX DISPLAY ENABLE
HI-En
Enables the Maximum Display Capture capability.
HI-t
When the Input Display is above the present MAX value for the entered delay time, the meter will capture that display value as the new MAX reading. A delay time helps to avoid false captures of sudden short spikes.
LO-En
Enables the Minimum Display Capture capability.
LO-t
When the Input Display is below the present MIN value for the entered delay time, the meter will capture that display value as the new MIN reading. A delay time helps to avoid false captures of sudden short spikes.
FCS
Select yES to perform either of the Factory Service Operations shown below.
CodE
CodE
YESNO
NO
MAX CAPTURE DELAY TIME
0.0 to 999.9 seconds
2.0
MIN DISPLAY ENABLE
YESNO
NO
MIN CAPTURE DELAY TIME
0.0 to 999.9 seconds
2.0
FACTORY SERVICE OPERATIONS
yESNO
NO
RESTORE FACTORY DEFAULT SETTINGS
66
50
Entering Code 66 will overwrite all user settings with the factory settings. The meter will display rESEt and then return to
CodE 00. Press the PAR button to exit the module.
VIEW MODEL AND VERSION DISPLAY
Entering Code 50 will display the model (LDA) and version (x.x) of the meter. The display then returns to
CodE 00. Press the PAR button to exit the module.
CALIBRATION
CodE
every 1 to 2 years should be sufficient.
Calibration of the LD involves a calibration which should only be performed by individuals experienced in calibrating electronic equipment. Allow 30 minute warm up before performing any calibration related procedure. The following procedures should be performed at an ambient temperature of 15 to 35 °C (59 to 95 °F).
CAUTION: The accuracy of the calibration equipment will directly affect the
Current Calibration
1. Connect the negative lead of a precision DC current source with an accuracy
of 0.01% or better to the COMM terminal. Leave the positive lead of the DC
current source unconnected.
2. With the display at CodE 48, press the PAR button. Unit will display CAL NO
3. Press the RST button to select the range to be calibrated.
4. Press the PAR button. Display reads 0.0A
5. With the positive lead of the DC current source unconnected, press PAR.
Display reads CALC for about 8 seconds.
6. When the display reads the selected range, connect the positive lead of the DC
current source to the current input and apply full-scale input signal for the
range. (Note: For 200 mA range, apply 100 mA as indicated on the display.)
Press PAR. Display reads CALC for about 8 seconds.
7. Repeat steps 3 through 6 for each input range to be calibrated. When display
reads CAL NO, press the PAR button to exit calibration.
Voltage Calibration
1. Connect a precision DC voltage source with an accuracy of 0.01% or better
to the volt input and COMM terminals of the LD. Set the output of the voltage
source to zero.
2. With the display at
3. Press the RST button to select the range to be calibrated.
4. Press the PAR button. Display reads 0.0v.
5. With the voltage source set to zero (or a dead short applied to the input), press
PAR. Display reads CALC for about 8 seconds.
6. When the display reads the selected range, apply full-scale input signal for the
range. (Note: For 200V range, apply 100V as indicated on the display.) Press
PAR. Display reads CALC for about 8 seconds.
7. Repeat steps 3 through 6 for each input range to be calibrated. When display
reads CAL NO, press the PAR button to exit calibration
48
accuracy of the LD.
The LD uses stored calibration values to provide accurate measurements. Over time, the electrical characteristics of the components inside the LD will slowly change with the result that the stored calibration values no longer accurately define the input circuit. For most applications, recalibration
CodE 48, press the PAR button. Unit will display CAL NO.
8
5.3 MODULE 3 - DISPLAY AND FRONT PANEL BUTTON
PAR
Pro
Front Panel
Display
Select Enable
Display
Update Time
Front Panel
Reset Enable
Programming
Security Code
Zero Display
W/Display
Reset
3-dSP
dSP-t SEL rSt ZErO CodE
Display
Intensity
Level
d-LEVScroL
Display
Scroll
Enable
P
ARAMETERS (3-dSP)
PARAMETER MENU
DISPLAY UPDATE TIME
dSP-t
This parameter sets the display update time in seconds.
SEL
The yES selection allows the SEL button to toggle through the enabled
displays.
rSt
This selection allows the RST button to reset the selected value(s).
ZErO
This parameter enables the RST button or user input to zero the input display
value, causing the display reading to be offset.
Note: For this parameter to operate, the RST button or User Input being used must be set to dSP and the Input value must be displayed. If these conditions are not met, the display will not zero.
0.5
1
2
seconds
1
FRONT PANEL DISPLAY SELECT ENABLE (SEL)
yES
FRONT PANEL RESET ENABLE (RST)
yES NO
NO dSP HI
LO HI-LO
dSP
ZERO DISPLAY WITH DISPLAY RESET
NO
yES NO
CodE
The Security Code determines the programming mode and the accessibility of programming parameters. This code can be used along with the Program Mode Lock-out (P-Loc) in the User Input Function parameter (Module 1).
Two programming modes are available. Full Programming mode allows all parameters to be viewed and modified. Quick Programming mode permits only the Setpoint values to be modified, but allows direct access to these values without having to enter Full Programming mode.
Programming a Security Code other than 0, requires this code to be entered at the CodE prompt in order to access Full Programming mode. Depending on the code value, Quick Programming may be accessible before the CodE prompt appears (see chart).
USER INPUT
FUNCTION
not P-Loc
000
USER INPUT
P-Loc
Not Active 0-999
PROGRAMMING SECURITY CODE
STATE
______
Active
000 to 999
SECURITY
CODE
0
1-99
100-999
0
1-99
100-999
MODE WHEN “SEL”
BUTTON IS PRESSED
Full Programming Immediate Access
Quick Programming
CodE prompt
Programming Lock No Access
Quick Programming No Access
CodE prompt
Full Programming Immediate Access
FULL PROGRAMMING
MODE ACCESS
After Quick Programming with correct code entry at
CodE prompt *
With correct code entry
CodE prompt *
at
With correct code entry
CodE prompt *
at
DISPLAY SCROLL ENABLE
ScroL
The yES selection allows the display to automatically scroll through the enabled displays. The scroll rate is every 4 seconds. This parameter only appears when the MAX or MIN displays are enabled.
d-LEV
Enter the desired Display Intensity Level (1-5). The display will actively dim or brighten as levels are changed.
NO
yES NO
DISPLAY INTENSITY LEVEL
1 to 5
5
9
OUTPUT
STATE
OFF
ON
Hys
SP + Hys
SP
OFF
TRIGGER POINTS
OUTPUT
STATE
OFF
ON
Hys
SP
SP - Hys
OFF
TRIGGER POINTS
5.4 MODULE 4 - SETPOINT OUTPUT PARAMETERS (4-SPt)
PAR
Setpoint
Action
Setpoint
Select
Setpoint
Value
Output Reset
Action
Hysteresis
Value
Off Time
Delay
On Time
Delay
Output Reset
W/Display
Reset
SPSEL
4-SPt
Act-n SPt-n HYS-n tON-n tOF-n rSt-n rEn-n
Pro
Standby
Operation
Stb-n
Enb-n
Setpoint
Enable
OUTPUT
STATE
OFF
ON
Hys
SP + ½Hys
SP
SP - ½Hys
OFF
TRIGGER POINTS
OUTPUT
STATE
OFF
ON
Hys
SP + ½Hys
SP
SP - ½Hys
OFF
TRIGGER POINTS
PARAMETER MENU
SETPOINT SELECT
SPSEL
Enter the setpoint (output) to be programmed. The n in the following parameters will reflect the chosen setpoint number. After the chosen setpoint is completely programmed, the display will return to SPSEL. Repeat steps for each setpoint to be programmed. Select
NO
NO SP-1 SP-2
NO to exit the module.
SETPOINT ENABLE
Enb-n
Select YES to enable Setpoint n and access the setup parameters. If NO is selected, the unit returns to SPSEL and Setpoint n is disabled.
NO
YES NO
SETPOINT ACTION
Act-n
Enter the action for the selected setpoint (output). See Setpoint Output Figures for a visual detail of each action.
HI-Ub
HI-bL LO-bL HI-Ub LO-Ub
HI-bL LO-bL HI-Ub LO-Ub
High Acting, with balanced hysteresis
=
Low Acting, with balanced hysteresis
=
High Acting, with unbalanced hysteresis
=
Low Acting, with unbalanced hysteresis
=
SETPOINT VALUE
SPt-n
Enter the desired setpoint value. The decimal point position for the setpoint
and hysteresis values follow the selection set in Module 1.
100
-19999 to 99999
HYSTERESIS VALUE
HYS-n
Enter desired hysteresis value. See Setpoint Output Figures for visual explanation of how setpoint output actions (balanced and unbalanced) are affected by the hysteresis. When the setpoint is a control output, usually balanced hysteresis is used. For alarm applications, usually unbalanced hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on the low side for high acting setpoints and functions on the high side for low acting setpoints.
Note: Hysteresis eliminates output chatter at the switch point, while time delay
can be used to prevent false triggering during process transient events.
1 to 59999
2
ON TIME DELAY
tON-n
Enter the time value in seconds that the output is delayed from turning on after the trigger point is reached. A value of 0.0 allows the meter to update the output status per the response time listed in the Specifications.
0.0
0.0 to 599.9 seconds
High Acting (Balanced Hys) = HI-bL
High Acting (Unbalanced Hys) = HI-Ub
OFF TIME DELAY
0.0
Low Acting (Balanced Hys) = LO-bL
tOF-n
Enter the time value in seconds that the output is delayed from turning off after the trigger point is reached. A value of 0.0 allows the meter to update the output status per the response time listed in the Specifications.
OUTPUT RESET ACTION
rSt-n
Auto
Enter the reset action of the output. See figure for details.
Auto = Automatic action; This action allows the output to automatically reset of f
at the trigger points per the Setpoint Action shown in Setpoint Output
Low Acting (Unbalanced Hys) = LO-Ub
Figures. The “on” output may be manually reset (off) immediately by the front panel point is crossed again.
RST button or user input.The output remains off until the trigger
LAtCH = Latch with immediate reset action; This action latches the output on at
the trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch means that the output can only be turned off by the front panel RST button or user input manual reset, serial reset command or meter power cycle. When the user input or RST button is activated (momentary action), the
10
0.0 to 599.9 seconds
LAtCHAuto L-dLY
OUTPUT
STATE
OFF
ON
Hys
SP
Auto
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
MANUAL RESET
LAtCH
L-dLY
SP - Hys
( )
( )
( )
{
PAR
Data BitBaud Rate Parity Bit Print
Options
Meter
Address
Abbreviated
Printing
5-SEr
bAUd dAtA
PAr Addr Abbr
OPt
Pro
corresponding “on” output is reset immediately and remains off until the trigger point is crossed again. (Previously latched alarms will be off if power up Display Value is lower than setpoint value.)
L-dLY = Latch with delay reset action; This action latches the output on at the
trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch means that the output can only be turned off by the front panel or user input manual reset, serial reset command or meter power cycle. When the user input or RST button is activated (momentary action), the meter delays the event until the corresponding “on” output crosses the trigger off point. (Previously latched outputs are off if power up Display Value is lower than setpoint value. During a power cycle, the meter erases a previous reset if it is not activated at power up.)
RST button
L-dLY
OUTPUT RESET WITH DISPLAY RESET
rEn-n
This parameter enables the RST button or user input to reset the output when
the display is reset.
Note: For this parameter to operate, the RST button or User Input being used must be set to not met, the output will not reset.
YESNO
YES
dSP and the Input value must be displayed. If these conditions are
STANDBY OPERATION
Stb-n
When YES, the output is disabled (after a power up) until the trigger point is crossed. Once the output is on, the output operates normally per the Setpoint Action and Output Reset Action.
Setpoint Output Reset Actions
NO
5.5 MODULE 5 - SERIAL SETUP PARAMETERS (5-SEr)
PARAMETER MENU
YESNO
Module 5 is the programming module for the Serial Communications Parameters. These parameters are used to match the serial settings of the LD with those of the host computer or other serial device.
bAUd
Normally, the baud rate is set to the highest value that all of the serial communications equipment is capable of transmitting and receiving.
9600
Set the baud rate to match that of other serial communications equipment.
dAtA
Select either 7- or 8-bit data word length. Set the word length to match the
other serial communications equipment on the serial link.
BAUD RATE
1200300 2400600
4800 9600
19200 38400
PAr
This parameter only appears when the Data Bit parameter is set to a 7-bit data word length. Set the parity bit to match that of the other serial equipment on the serial link. The meter ignores parity when receiving data and sets the parity bit for outgoing data. If parity is set to NO, an additional stop bit is used to force the frame size to 10 bits.
11
7-bit
Odd
DATA BIT
8-bit7-bit
PARITY BIT
EVENOddNO
METER ADDRESS
Addr
Enter the serial node address. With a single unit, an address is not needed and a value of zero can be used (RS232 applications). Otherwise, with multiple bussed units, a unique address number must be assigned to each meter. The node address applies specifically to RS485 applications.
00
0 to 99
ABBREVIATED PRINTING
Abbr
This parameter determines the formatting of data transmitted from the meter
in response to a Transmit Value command or a Block Print Request. Select NO
for a full print transmission, consisting of the meter address, mnemonics, and parameter data. Select YES for abbreviated print transmissions, consisting of the parameter data only. This setting is applied to all the parameters selected in the PRINT OPTIONS. (Note: If the meter address is 0, the address will not be sent during a full transmission.)
NO
YESNO
PRINT OPTIONS
OPt
This parameter selects the meter values transmitted in response to a Print Request. A print request is also referred to as a block print because more than one parameter can be sent to a printer or computer as a block.
Selecting in the print block. All active parameters entered as transmitted during a block print. Parameters entered as
The “Print All” (P ALL) option selects all meter values for transmitting (YES), without having to individually select each parameter in the sublist.
Note: Inactive parameters will not be sent regardless of the print option setting. The Setpoint value will not be sent unless the setpoint is enabled
NO
YES displays a sublist for choosing the meter parameters to appear
DISPLAY DESCRIPTION
HI LO
Input
Maximum
Minimum
Setpoint 1
Setpoint 2
INP
SPt-1 SPt-2
YESNO
FACTORY
SETTING
YES
NO NO NO NO
YES in the sublist will be
NO will not be sent.
MNEMONIC
INP
MAX
MIN
SP1
SP2
Sending Serial Commands and Data
When sending commands to the meter, a string containing at least one command character must be constructed. A command string consists of a command character, a value identifier, numerical data (if writing data to the meter) followed by a command terminator character, * or $.
Command Chart
Command Description Notes
Node (meter)
N
Address Specifier
T Transmit Value (read)
V Value Change (write)
R Reset
Block Print Request
P
(read)
Command String Construction
The command string must be constructed in a specific sequence. The meter does not respond with an error message to illegal commands. The following procedure details construction of a command string:
1. The first 2 or 3 characters consist of the Node Address Specifier (N) followed
by a 1 or 2 character node address number. The node address number of the
meter is programmable. If the node address is 0, this command and the node
address itself may be omitted. This is the only command that may be used in
conjunction with other commands.
2. After the optional address specifier, the next character is the command
character.
3. The next character is the register ID. This identifies the register that the
command affects. The P command does not require a register ID character. It
prints all the active selections chosen in the Print Options menu parameter.
4. If constructing a value change command (writing data), the numeric data is
sent next.
5. All command strings must be terminated with the string termination
characters * or $. The meter does not begin processing the command string
until this character is received. See timing diagram figure
Address a specific meter. Must be followed by one or two digit node address. Not required when node address = 0. Read a register from the meter. Must be followed by a register ID character.
Write to register of the meter. Must be followed by a register ID character and numeric data.
Reset a min or max value or the output. Must be followed by a register ID character
Initiates a block print output. Registers in the print block are selected in Print Options.
Register Identification Chart
ID Value Description MNEMONIC
A Input INP T, R 5 digit
B Maximum MAX T, R 5 digit
C Minimum MIN T, R 5 digit
D Setpoint 1 SP1 T, R, V 5 digit positive/4 digit negative
E Setpoint 2 SP2 T, R, V 5 digit positive/4 digit negative
Applicable
Commands
Transmit Details (T and V)
Command String Examples:
1. Node address = 17, Write 350 to the Setpoint 1 value String: N17VD350$
2. Node address = 5, Read Input, response time of 50 msec min String: N5TA*
3. Node address = 31, Request a Block Print Output, response time of 2 msec min String: N31P$
Transmitting Data to the Meter
Numeric data sent to the meter must be limited to transmit details listed in the Register Identification Chart. Leading zeros are ignored. Negative numbers must have a minus sign. The meter ignores any decimal point and conforms the number to the scaled resolution. (For example: The meter’s scaled decimal point position is set for 0.0 and 25 is written to a register. The value of the register is now 2.5. In this case, write a value of 250 to equal 25.0).
Note: Since the meter does not issue a reply to value change commands, follow
with a transmit value command for readback verification.
12
Ready Ready
1
t t
2
Ready
t
1
t
2
Ready
t
3
Command
String
Transmission
Meter
Response
Time
Command
Terminator
Received
First
Character
of Reply
Reply
Transmission
NO REPLY FROM METER
RESPONSE FROM METER
Receiving Data From The Meter
Data is transmitted from the meter in response to either a transmit command (T), a block print request command (P) or a User Input print request. The response from the meter is either a full field transmission or an abbreviated transmission, depending on the selection chosen in Module 5.
Full Field Transmission
DescriptionByte
2 byte Node Address field [00-99]1, 2
<SP> (Space)3
3 byte Register Mnemonic field4-6
9 byte data field; 7 bytes for number, one byte for sign, one byte for
7-15
decimal point
<CR> (carriage return)16
<LF> (line feed)17
<SP>* (Space)18
<CR>* (carriage return)19
<LF>* (line feed)20
* These characters only appear in the last line of a block print.
The first two characters transmitted are the meter address. If the address assigned is 0, two spaces are substituted. A space follows the meter address field. The next three characters are the register mnemonic, as shown in the Register Identification Chart.
The numeric data is transmitted next. The numeric field (bytes 7 to 15) is 9 characters long. This field consists of a minus sign (for negative values), a floating decimal point (if applicable), and five positions for the requested value. The data within bytes 9 to 15 is right-aligned with leading spaces for any unfilled positions. When a requested value exceeds the meter’s display limits, decimal points are transmitted instead of a numeric value.
The end of the response string is terminated with a <CR> and <LF>. After the last line of a block print, an extra <SP>, <CR> and <LF> are added to provide separation between the print blocks.
Abbreviated Transmission
DescriptionByte
9 byte data field, 7 bytes for number, one byte for sign, one
1-9
byte for decimal point <CR> (carriage return)10
<LF> (line feed)11
<SP>* (Space)12
<CR>* (carriage return)13
<LF>* (line feed)14
* These characters only appear in the last line of a block print.
The abbreviated response suppresses the node address and register ID,
leaving only the numeric part of the response.
Meter Response Examples:
1. Node address = 17, full field response, Input = 875 17 INP 875 <CR><LF>
2. Node address = 0, full field response, Setpoint 1 = -250.5 SP1 -250.5<CR><LF>
3. Node address = 0, abbreviated response, Setpoint 2 = 250, last line of block
print 250<CR><LF><SP><CR><LF>
Command Response Time
The meter can only receive data or transmit data at any one time (half-duplex operation). During RS232 transmissions, the meter ignores commands while transmitting data, but instead uses RXD as a busy signal. When sending commands and data to the meter, a delay must be imposed before sending another command. This allows enough time for the meter to process the command and prepare for the next command.
At the start of the time interval t string to the com port, thus initiating a transmission. During t1, the command characters are under transmission and at the end of this period, the command terminating character (* or $) is received by the meter. The time duration of t1 is dependent on the number of characters and baud rate of the channel.
t1 = (10 times the # of characters) / baud rate
At the start of time interval t2, the meter starts the interpretation of the command and when complete, performs the command function. This time interval t2 varies. If no response from the meter is expected, the meter is ready to accept another command.
If the meter is to reply with data, the time interval t2 is controlled by the use of the command terminating character. The ‘*’ terminating character results in a response time of 50 msec. minimum. This allows sufficient time for the release of the sending driver on the RS485 bus. Terminating the command line with ‘$’ results in a response time (t2) of 2 msec. minimum. The faster response time of this terminating character requires that sending drivers release within 2 msec. after the terminating character is received.
, the computer program prints or writes the
1
At the beginning of time interval t
character of the reply. As with t1, the time duration of t3 is dependent on the
, the meter responds with the first
3
number of characters and baud rate of the channel. At the end of t3, the meter is ready to receive the next command.
t3 = (10 times the # of characters) / baud rate The maximum serial throughput of the meter is limited to the sum of the
times t1, t2 and t3.
Time
Timing Diagram Figure
13
Communication Format
Data is transferred from the meter through a serial communication channel. In serial communications, the voltage is switched between a high and low level at a predetermined rate (baud rate) using ASCII encoding. The receiving device reads the voltage levels at the same intervals and then translates the switched levels back to a character. The voltage level conventions depend on the interface standard. The table lists the voltage levels for each standard.
LOGIC RS232* RS485*INTERFACE STATE
1 TXD,RXD; -3 to -15 V a-b < -200 mVmark (idle)
0 TXD,RXD; +3 to +15 V a-b > +200 mVspace (active)
* Voltage levels at the Receiver
Data is transmitted one byte at a time with a variable idle period between characters (0 to an optional parity bit and one or more ending stop bits. The data format and baud rate must match that of other equipment in order for communication to take place. The figures list the data formats employed by the meter.
). Each ASCII character is “framed” with a beginning start bit,
Start Bit and Data Bits
Data transmission always begins with the start bit. The start bit signals the receiving device to prepare for reception of data. One bit period later, the least significant bit of the ASCII encoded character is transmitted, followed by the remaining data bits. The receiving device then reads each bit position as they are transmitted.
Parity Bit
After the data bits, the parity bit is sent. The transmitter sets the parity bit to a zero or a one, so that the total number of ones contained in the transmission (including the parity bit) is either even or odd. This bit is used by the receiver to detect errors that may occur to an odd number of bits in the transmission. However, a single parity bit cannot detect errors that may occur to an even number of bits. Given this limitation, the parity bit is often ignored by the receiving device. The meter ignores the parity bit of incoming data and sets the parity bit to odd, even or none (mark parity) for outgoing data.
Stop Bit
The last character transmitted is the stop bit. The stop bit provides a single bit period pause to allow the receiver to prepare to re-synchronize to the start of a new transmission (start bit of next byte). The receiver then continuously looks for the occurrence of the start bit. If 7 data bits and no parity is selected, then 2 stop bits are sent from the meter.
Character Frame Figure
14
Setpoint
Action
Setpoint
Select
Setpoint
Value
Output Reset
Action
Hysteresis
Value
O Time
Delay
On Time
Delay
Output Reset
W/Display
Reset
SPSEL
4-SPt
Act-n SPt-n HYS-n tON-n tOF-n rSt-n rEn-n
Standby
Operation
Stb-n
Front Panel
Reset Enable
Front Panel
Display
Select Enable
Display
Update Time
dSP-t SEL rSt
3-dSP
Display
Intensity
Level
d-LEV
Programming
Security Code
CodE
Filter Band
Input
Range
rANGE
Display
Decimal Point
dECPt
1-INP
Filter Setting
FILtr
bANd
USrIN
User Input
Function
Input Value
for Scaling
Point 1
INP 1 dSP 1
INP 2
U-ASN
User Input
Assignment
LO-En
Min Display
Enable
Max Capture
Delay Time
Max Display
Enable
HI-En HI-t2-SEC
Min Capture
Delay TIme
LO-t
Factory
Service
Operations
FCS
Access Code
For Service
Operations
CodE
PAr
Parity BitBaud Rate
bAUd
Data Bit
dAtA
5-SEr
Meter
Address
Addr
Abbreviated
Printing
Abbr
Print
Options
OPt
PAR
SEL
NO
Pro
Exit
Programming
End
PAR
SEL
SEL
SEL
SEL
SEL
PAR
PAR
PAR
PAR
Display Value
for Scaling
Point 1
Input Value
for Scaling
Point 2
Display Value
for Scaling
Point 2
dSP 2
OFSEt
Display Oset
Value
StYLE
Scaling Style
Zero Display
W/Display
Reset
ZErO ScroL
Display
Scroll
Enable
Enb-n
Setpoint
Enable
User Input
Active Level
U-ACt
LDA PROGRAMMING QUICK OVERVIEW
Press PAR key to enter
Programming Mode.
15
The Company warrants the products it manufactures against defects in materials and workmanship
LIMITED WARRANTY
for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
Red Lion Controls Headquarters 20 Willow Springs Circle York PA 17406 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839
Red Lion Controls
Europe
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
54, Vishvas Tenement
GST Road, New Ranip,
Ahmedabad-382480 Gujarat, India
Tel +91 987 954 0503
Fax +91 79 275 31 350
Red Lion Controls
China
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683
Loading...