Red Lion ITMS User Manual

GENERAL DESCRIPTION
The ITMS4037 Intelligent Temperature to MODBUS™ Conditioner with Alarms accepts a wide range of temperature sensors (thermocouple and RTD elements), and converts the signal into a register format that can be read using either ASCII or RTU MODBUS protocol.
The ITMS allows a choice of either Fahrenheit or Celsius readout with 0.1 or 1 degree of resolution. An offset value can be programmed to scale the input signal to meet most process requirements. Additionally, two setpoint values can be entered for dual relay process monitoring alarms.
The ITMS is programmed with Windows™ based SFIMS software. The software allows configuration, calibration, and storage of ITMS program files. Additionally, all setup parameters can be interrogated and modified through MODBUS register and coil commands.
The RS485 port allows the ITMS to be multidropped, with Baud rates up to
38400. The CBPRO007 programming cable converts the RS232 port of a PC to RS485, and is terminated with an RJ-11 connector. The bidirectional capability of the CBPRO007 allows it to be used as a permanent interface cable as well as a programming cable.
The ITMS’s two relay alarms can be configured independently for absolute high or low acting with balanced or unbalanced hysteresis. Alarm 2 can also be configured for deviation and band alarms. In these modes, Setpoint 2 tracks Setpoint 1. Adjustable alarm trip delays can be used for delaying output response. The alarms can be programmed for Automatic or Latching. Latched alarms can be reset with a serial command or a user input. A standby feature suppresses the alarm during power-up until the temperature stabilizes outside the alarm region. Standby eliminates power-up tripping for low acting alarms. A user input can be used to set and reset non-latching alarms. The output relays can also be manually controlled with register commands.
The module’s high density packaging and DIN rail mounting saves time and panel space. The module is equipped with a universal mounting foot for attachment to standard DIN rails, including top hat (T) profile or G profile rail.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
1
O
TEMPERATURE TO MODBUS CONVERSION
O
ACCEPTS THERMOCOUPLE, RTD, mV OR RESISTANCE
SIGNALS
O
PROCESSOR BASED SCALING
O
PC CONFIGURATION SOFTWARE
O
DUAL SETPOINT RELAY ALARMS
O
FOUR WAY SIGNAL ISOLATION
MODEL ITMS - INTELLIGENT TEMPERATURE TO MODBUS CONDITIONER W/ ALARMS
MODEL
ITMS
DESCRIPTION
Temperature to MODBUS Conditioner w/Alarms
PART NUMBER
ITMS4037
CBPRO
SFIMS
Programming Interface Cable
PC Configuration Software for Windows
CBPRO007
SFIMS
CBJ
Cable RJ11 to Unterminated 7 foot length CBJ11A07
RJ Connector to Terminal Adapter
Cable RJ11 to RJ11 6 inch jumper
DRRJ11T6
CBJ11BD5
ORDERING INFORMATION
DIMENSIONS In inches (mm)
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
Bulletin No. ITMS-B
Drawing No. LP0494
Released 1/07
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
UL Recognized Component, File # E179259
2
SPECIFICATIONS
1. POWER: 18-36 VDC, 3.0 W max. or 24 VAC, ±10%, 50/60 Hz, 4 VA max.
2. INPUT: Sample Rate: 67 msec. (15 Hz) Failed Sensor Response: Open or shorted (RTD only) sensor coils indication,
error code returned in Process Value Common Mode Rejection: 50/60 Hz, 110 dB min. Overvoltage: 30 VDC Response Time: 150 msec. max.
3. THERMOCOUPLE INPUTS: Types: T, E, J, K, R, S, B, N, C, linear mV Input Impedance: 20 M Lead Resistance Effect: 0.22 µV/ Resolution: 1° or 0.1° for all types
4. RTD INPUTS: Type: 2 or 3 wire Excitation: 150 µA Lead Resistance: 10 Ω max. Resolution: 1° or 0.1° for all types
5. INDICATION ACCURACY: ±(0.3% of span, +1°C), includes NIST conformity, cold junction effect, A/D conversion errors, tempco and linearization conformity at 23°C after 20 minute warm-up. Span Drift (max) : 0.01% /°C
6. USER INPUT: Internally pulled up to +5 VDC. VIL= 0.78 V max., VIH= 1.8 V min. I
OFF
= 9 µA max. 30 V max. over voltage continuously.
7. ISOLATION LEVEL: 1.5 KV @ 50/60 Hz, 1 minute (150 V working) between input, RS485 and power supply. 2300 Vrms, 1 minute (300 V working) to relay contacts.
8. SERIAL COMMUNICATIONS: Type: RS485; RTU and ASCII MODBUS modes Baud: 300, 600, 1200, 2400, 4800, 9600, 19200, and 38400 Format: 7/8 bit, odd, even and no parity Transmit Delay: Programmable. (See Transmit Delay explanation in Step 6) Transmit Enable (TXEN): (primarily for 20 mA loop converter) open collector V
OH
= 10 VDC max. VOL= 0.5 VDC @ 5 mA max. current limit
9. A/D CONVERTER: 16 bit resolution
10. RELAY OUTPUTS: Type: 1 Form A N.O. contacts, 1 Form C DPDT Rating: 5A @ 30 VDC or 250 VAC max. (resistive)
1/10 HP @ 120 VAC (inductive)
Response Time: 155 msec. max. to close including step response, 153 msec.
max. to open.
Output On Delay Time: Programmable from 0 to 32000 sec ±0.01% - 1 sec. max.
11. MEMORY: Nonvolatile E
2
PROM retains all programmable parameters.
12. ENVIRONMENTAL CONDITIONS: Operating Temperature Range: -20 to +65 °C Storage Temperature Range: -40 to +85 °C Operating and Storage Humidity: 85% max. relative humidity (non­condensing) from -20 to +65 °C Altitude: Up to 2000 meters
13. CERTIFICATIONS AND COMPLIANCE:
SAFETY
UL Recognized Component, File # E179259, UL3101-1, CSA 22.2 No. 1010-1
Recognized to U.S. and Canadian requirements under the Component Recognition Program of Underwriters Laboratories, Inc.
IECEE CB Scheme Test Certificate # US/5141A/UL,
CB Scheme Test Report # 01ME11540-0702001
Issued by Underwriters Laboratories, Inc.
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. This device was designed for installation in an enclosure. To avoid
electrostatic discharge to the unit in environments with static levels above 6 KV, precautions should be taken when the device is mounted outside an enclosure. When working in an enclosure (ex. making connections, etc.), typical anti-static precautions should be observed before touching the module.
Refer to the EMC Installation Guidelines section of this bulletin for
additional information.
14. CONSTRUCTION: Case body is black high impact plastic. Installation Category II, Pollution Degree 2.
15. CONNECTIONS: Wire clamping screw terminals.
16. MOUNTING: Universal mounting foot for attachment to standard DIN style mounting rails, including top hat (T) profile rail according to EN50022
- 35 x 7.5 and -35 x 15, and G profile rail according to EN50035 - G32.
17. WEIGHT: 4.5 oz. (127.57 g)
Power mains class A
Enclosure class AEN 55011RF interference
Emissions to EN 55011
Level 3; 10 V/mENV 50204Simulation of cordless telephone
150 KHz - 80 MHz
Level 3; 10 V/rms EN 61000-4-6RF conducted interference
Level 3; 2 KV power
Level 4; 2 KV I/O EN 61000-4-4Fast transients (burst)
80 MHz - 1 GHz
Level3; 10 V/MEN 61000-4-3Electromagnetic RF fields
Level 3; 8 KV air
1
Level 2; 4 KV contact EN 61000-4-2Electrostatic discharge
200 Hz, 50% duty cycle
Immunity to EN 50082-2
900 MHz ± 5 MHz
BLOCK DIAGRAM
RTD TYPE INPUT TYPE RANGE
385
100 platinum, Alpha=.00385
-200 to +800°C
-328 to +1472°F
392
100 platinum, Alpha=.003919
-200 to +800°C
-328 to +1472°F
672
120 Ω nickel, Alpha=.00672
-80 to +260°C
-112 to +500°F
Ohms Linear Resistance
0 to 440
TC TYPE DISPLAY RANGE
WIRE COLOR
ANSI BS 1843
T
-200 to +400°C
-328 to +752°F
(+) blue
(-) red
(+) white
(-) blue
E
-200 to +750°C
-328 to +1382°F
(+) violet
(-) red
(+) brown
(-) blue
J
-200 to +760°C
-328 to +1400°F
(+) white
(-) red
(+) yellow
(-) blue
K
-200 to +1372°C
-328 to +2502°F
(+) yellow
(-) red
(+) brown
(-) blue
R
0 to +1768°C +32 to +3214°F
No Standard
(+) white
(-) blue
S
0 to +1768°C +32 to +3214°F
No Standard
(+) white
(-) blue
B
+200 to +1820°C +392 to +3308°F
No Standard No Standard
N
-200 to +1300°C
-328 to +2372°F
(+) orange
(-) red
(+) orange
(-) blue
C
W5/W26
0 to +2315°C +32 to +4199°F
No Standard No Standard
mV -10 mV to 65 mV NA NA
3
MODULE ISOLATION
The ITMS features “4-way” signal isolation. The 4-way isolation is a combination of optical, transformer and relay barriers, providing common mode voltage (CMV) isolation to 1.5 KV for 1 minute between input, RS485, and power supply. Isolation between relay contacts and all other inputs is 2300 Vrms for 1 minute.
LED FUNCTIONALITY
CONDITION GREEN LED 2 RED LEDS
Power Applied On ———
Communication Received Flashing ———
Respective Alarm On On
Checksum error Flashing Flashing
Calibration Off On
EMC INSTALLATION GUIDELINES
Although this module is designed with a high degree of immunity to Electro­Magnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into the unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation.
Listed below are some EMC guidelines for successful installation in an industrial environment.
1. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the rail where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
c. Connect the shield to common of the unit and leave the other end of the
shield unconnected and insulated from earth ground.
2. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
3. Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.
4. In extremely high EMI environments, the use of external EMI suppression devices, such as ferrite suppression cores, is effective. Install them on Signal and Control cables as close to the unit as possible. Loop the cable through the core several times or use multiple cores on each cable for additional protection. Install line filters on the power input cable to the unit to suppress power line interference. Install them near the power entry point of the enclosure. The following EMI suppression devices (or equivalent) are recommended: Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC # FCOR0000) TDK # ZCAT3035-1330A Steward # 28B209-0A0 Line Filters for input power cables: Schaffner # FN610-1/07 (RLC # LFIL0000) Schaffner # FN670-1.8/07 Corcom # 1 VR3
Note: Reference manufacturer’s instructions when installing a line filter.
5. Long cable runs are more susceptible to EMI pickup than short cable runs. Therefore, keep cable runs as short as possible.
4
WIRING CONNECTIONS
All conductors should meet voltage and current ratings for each terminal. Also, cabling should conform to appropriate standards of good installation, local codes and regulations. When wiring the module, use the numbers on the label to identify the position number with the proper function. Strip the wire, leaving approximately 1/4" (6 mm) of bare wire exposed. Insert the wire into the terminal, and tighten the screw until the wire is clamped tightly. (Pull wire to verify tightness.) Each terminal can accept up to one #14 AWG (2.55 mm), two #18 AWG (1.02 mm), or four #20 AWG (0.61 mm) wires.
MODULE POWER CONNECTIONS
AC module power is connected to terminals 1 and 2. DC module power is connected with (+) to terminal 1 and (-) to terminal 2. For best results, the power should be relatively “clean” and within the specified limits. Drawing power from heavily loaded circuits or from circuits that also power loads that cycle on and off should be avoided. It is recommended that power supplied to the module be protected by a fuse or circuit breaker.
INPUT CONNECTIONS
Thermocouple Input
Thermocouple leads are connected to terminals 11 (+) and 12 (-).
RTD Input
For 3-wire RTD elements, connect the sense leads to terminals 11 and 12. The excitation lead is connected to terminal 10 (EXC).
For 2-wire RTD elements, connect the sense leads to terminals 11 and 12. Install a copper sense lead of the same gauge and length as the RTD leads. Attach one end of the wire at the probe and the other end to terminal 10. Complete lead wire compensation is obtained. This is the preferred method. If a sense wire is not used, then Terminal 11 should be shorted to terminal 10. A temperature offset error will exist. The error may be compensated by programming a temperature offset.
RELAY OUTPUT CONNECTIONS
Relay 1
Relay 1 is a Form A output relay. Wiring is connected between terminal 9
(COMM.) common and terminal 8 (N.O.) the normally open contact.
Relay 2
Relay 2 is a Form C output relay. Wiring is connected between terminal 4 (COMM.) common and either terminal 5 (N.O.), the normally open contact, or terminal 3 (N.C.), the normally closed contact.
To prolong contact life and suppress electrical noise interference due to the switching of inductive loads, it is good installation practice to install a snubber across the contacts. Follow the manufacturer’s instructions for installation.
Note: Snubber leakage current can cause some high impedance loads to be held ON.
DEFAULT SERIAL SETTING CONNECTION
If the ITMS settings are unknown, or forgotten, they can be reset to the factory defaults by connecting the Serial Default terminal 7 to Input Comm. terminal 12 with a jumper, and then cycling power.
Defaults:
USER INPUT CONNECTION
The user input is activated when terminal 6 is pulled low (connected to Input Comm. terminal 12).
RS485 SERIAL CONNECTIONS
There are two RJ-11 connectors located on the bottom for paralleling communications. For single device communications, either connector can be used. When used in conjunction with Red Lion Control Paradigm HMI products, reverse A+ and B- wiring.
RJ11 ITMS
1 Not used
2B-
3A+
4 COMM
5 TXEN
6
2345
Not used
ITMS CONNECTOR
STEP 1 WIRING THE MODULE
STEP 2 INSTALLING SFIMS (Software for Intelligent Modules)
Insert the SFIMS diskette into the A: or B: drive. Then Run A:\SETUP (or B:\SETUP) to install RLCPro onto the hard drive. An icon labeled RLCPro will be created under the group RLCPro.
Protocol: RTU 8Data Bits:
Address: 247 noneParity:
Baud Rate: 9600
5
STEP 3 PROGRAMMING - Getting Started
Run RLCPro by double-clicking the icon, or use the start menu.
Use the FILE pull-down menu
to select a NEW file.
You will be prompted to
select the proper device,
and then the model.
STEP 4 PROGRAMMING THE INPUT
The ITMS receives a temperature sensor input, converts it to a raw digital value, and stores this number in the ADC Value (register 40001). This number is scaled into degrees, and a programmable Offset Value (register 40012), that can be used for sensor correction, is applied. The result is stored as the Temperature Value (register 40002). It is also stored in the IEEE 754 Standard 32-bit floating decimal format (register 40003 and 40004). The non-scaled ADC, the scaled Process Temperature Value, or the Floating Point Value may be accessed for the purpose of monitoring the input level.
INPUT SIGNAL
Register 40001
ADC READING
INTERNAL
MATH
OFFSET
PROCESS
TEMPERATURE
VALUE
LO Order Byte
HI Order Byte
IEEE STANDARD 754
FLOATING DECIMAL POINT
Register 40003 Register 40004
Register
40012
Register 40002
Input Type: Select the proper input type from the pull down menu.
Scale: Select Fahrenheit or Celsius. In linear millivolt or resistance modes, this has no
effect.
Resolution: For thermocouple, RTD, or linear resistance modes, low resolution selects
whole degrees or ohms. In these same modes, high resolution selects tenth of degrees or ohms. In linear mV mode, low selects hundredths of mV, and high selects thousandths of mV.
Offset: The Offset value can be used as a sensor correction value.
Filter Response: The Filter Response is a time constant, in tenth of second increments,
that is used to stabilize an erratic input. The Process Value stabilizes to 99% of the final value within approximately 5 time constants. A value of ‘0’ disables digital filtering.
Filter Band: Filter Band is a value expressed in Temperature (degrees or tenths) units.
When a fluctuating signal remains within the band value, the Digital Filter is active, and therefore stabilizes the Process Temperature Value. When a fluctuating signal exceeds the Filter Band value, the Digital Filter is momentarily disabled to allow for quick response to valid process changes. Once the signal variation is less than the Filter Band value, the Digital Filter is reactivated.
Loading...
+ 11 hidden pages