Bulletin No. ICM8-C
Drawing No. LP0642
Released 12/11
ETHERNET GATEWAY FOR RED LION PANEL METERS PROGRAMMABLE VIA CRIMSON SOFTWARE USB PROGRAMMING PORT EXTENSIVE ETHERNET DRIVER LIST ALLOWS EASY DATA
MAPPING TO PLCS, PCS, AND SCADA SYSTEMS
10 BASE-T/100 BASE-TX ETHERNET
GENERAL DESCRIPTION
The ICM8 is designed to act as an ethernet gateway offering multiple
protocol conversion for Red Lion panel meters. With two serial ports (one
RS232 and one RS485) and a 10 Base-T/100 Ethernet Port, the unit performs
protocol conversion, allowing Red Lion panel meters to communicate
seamlessly to the ethernet network. Programming the unit can be accomplished
via the RS232 or the USB Port using Crimson Software. It is important to note
that this device is designed to function with Red Lion panel meters and will not
offer protocol conversion if a Red Lion Product is not connected to at least one
of the serial ports.
The ICM8’S DIN rail mounting saves time and panel space and snaps easily
onto standard top hat (T) profile DIN rail.
SOFTWARE
The ICM8 is programmed with Windows® compatible Crimson software.
The software is an easy to use graphical interface which can be purchased as part
of a kit that includes a manual and cables, or downloaded free of charge from
www.redlion.net.
DIMENSIONS In inches (mm)
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
SPECIFICATIONS
1. POWER: 24 VDC ± 10% 200 mA max. Must use a Class 2 or SELV rated
power supply.
2. COMMUNICATIONS:
USB/PG Port: Adheres to USB specification 1.1. Device only using Type B
connection.
Serial Ports: Format and Baud Rates for each port are individually software
programmable up to 115,200 baud.
RS232/PG Port: RS232 port via RJ12
COMMS Ports: RS485 port via RJ11
Ethernet Port: 10 BASE-T / 100 BASE-TX
3. LEDs:
STS – Status LED indicates condition of ICM8.
TX/RX – Transmit/Receive LEDs show serial activity.
Ethernet – Link and activity LEDs.
4. MEMORY:
On-board User Memory: 4 Mbytes of non-volatile Flash memory.
On-board SDRAM: 2 Mbytes
1
5. CERTIFICA TIONS AND COMPLIANCES:
2
1
SAFETY
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment for
measurement, control, and laboratory use, Part 1.
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
Control and Laboratory use.
Immunity to Industrial Locations:
Electrostatic dischargeEN 61000-4-2Criterion B
4 kV contact discharge
8 kV air discharge
Electromagnetic RF fieldsEN 61000-4-3Criterion A
10 V/m
Fast transients (burst)EN 61000-4-4Criterion B
2 kV power
1 kV signal
SurgeEN 61000-4-5Criterion A
1kV L-L,2 kV
L&N-E power
RF conducted interference EN 61000-4-6Criterion A
3 V/rms
Emissions:
EmissionsEN 55011Class A
Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit selfrecovers.
3. This device was designed for installation in an enclosure. To avoid
electrostatic discharge to the unit in environments with static levels above
4 kV precautions should be taken when the device is mounted outside an
enclosure. When working in an enclosure (ex. making adjustments, setting
switches etc.) typical anti-static precautions should be observed before
touching the unit.
3
6. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C
Storage Temperature Range: -30 to +70°C
Operating and Storage Humidity: 80% max relative humidity,
non-condensing, from 0 to 50°C
Altitude: Up to 2000 meters
7. CONSTRUCTION: Case body is black high impact plastic and stainless
steel. Installation Category I, Pollution Degree 2.
8. POWER CONNECTION: Removable wire clamp screw terminal block.
Wire Gage Capacity: 24 AWG to 12 AWG
Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)
9. MOUNTING: Snaps onto standard DIN style top hat (T) profile mounting
rails according to EN50022 -35 x 7.5 and -35 x 15.
10. WEIGHT: 12.3 oz (348g)
HARDWARE
INSTALLATION
Figure 1 - Attach ICM8 To DIN Rail
POWER SUPPLY REQUIREMENTS
It is very important that the power supply is mounted correctly if the unit is
to operate reliably. Please take care to observe the following points:
– The power supply must be mounted close to the unit, with usually not more
than 6 feet (1.8 m) of cable between the supply and the ICM8. Ideally, the
shortest length possible should be used.
– The wire used to connect the ICM8’s power supply should be at least
22-gage wire. If a longer cable run is used, a heavier gage wire should be
used. The routing of the cable should be kept away from large contactors,
inverters, and other devices which may generate significant electrical
noise.
– A power supply with a Class 2 or SELV rating is to be used. A Class 2 or
SELV power supply provides isolation to accessible circuits from
hazardous voltage levels generated by a mains power supply due to single
faults. SELV is an acronym for “safety extra-low voltage.” Safety extralow voltage circuits shall exhibit voltages safe to touch both under normal
operating conditions and after a single fault, such as a breakdown of a layer
of basic insulation or after the failure of a single component has occurred.
2
EMC INSTALLATION GUIDELINES
Although Red Lion Controls Products are designed with a high degree of
immunity to Electromagnetic Interference (EMI), proper installation and wiring
methods must be followed to ensure compatibility in each application. The type
of the electrical noise, source or coupling method into a unit may be different
for various installations. Cable length, routing, and shield termination are very
important and can mean the difference between a successful or troublesome
installation. Listed are some EMI guidelines for a successful installation in an
industrial environment.
1. To reduce the chance of noise spikes entering the unit via the power lines,
connections should be made to a clean source. Connecting to circuits that also
power loads such as contactors, relays, motors, solenoids etc. should be avoided.
2. The unit should be mounted in a metal enclosure, which is properly connected
to protective earth.
3. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield to earth ground (protective earth) at one end where the
unit is mounted.
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is over 1 MHz.
c. Connect the shield to common of the Data Station and leave the other end
of the shield unconnected and insulated from earth ground.
WIRING
POWER CONNECTION
4. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run through metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter. Also, Signal or Control cables within
an enclosure should be routed as far away as possible from contactors, control
relays, transformers, and other noisy components.
5. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
6. In extremely high EMI environments, the use of external EMI suppression
devices is effective. The following EMI suppression devices (or equivalent)
are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite part number 0443167251 (RLC part number FCOR0000)
TDK part number ZCAT3035-1330A
Steward part number 28B2029-0A0
Line Filters for input power cables:
Schaffner part number FN2010-1/07 (RLC part number LFIL0000)
Schaffner part number FN670-1.8/07
Corcom part number 1 VR3
Visit RLC's web site at www.redlion.net for more information on EMI
guidelines, Safety and CE issues as they relate to Red Lion Controls products.
COMMON
+24 VDC
COMM
231
+24
---
N/C
PROGRAMMING PORTS
USB/PG
RS232/PG
CTS
Rx
COMM
COMM
RS232
Tx
RTS
312
CBLUSB00
OR
CBLPROG0
3