Red Lion ICM8 User Manual

Tel +1 (717) 767-6511
4.15 (105.4)
5.30
(134.7)
1.75 (44.5)
Fax +1 (717) 764-0839 www.redlion.net
MODEL ICM8 – ETHERNET GATEWAY
Bulletin No. ICM8-C Drawing No. LP0642 Released 12/11
 ETHERNET GATEWAY FOR RED LION PANEL METERS  PROGRAMMABLE VIA CRIMSON SOFTWARE  USB PROGRAMMING PORT  EXTENSIVE ETHERNET DRIVER LIST ALLOWS EASY DATA
MAPPING TO PLCS, PCS, AND SCADA SYSTEMS
 10 BASE-T/100 BASE-TX ETHERNET
GENERAL DESCRIPTION
The ICM8’S DIN rail mounting saves time and panel space and snaps easily onto standard top hat (T) profile DIN rail.
SOFTWARE
The ICM8 is programmed with Windows® compatible Crimson software. The software is an easy to use graphical interface which can be purchased as part of a kit that includes a manual and cables, or downloaded free of charge from www.redlion.net.
DIMENSIONS In inches (mm)
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
SPECIFICATIONS
1. POWER: 24 VDC ± 10% 200 mA max. Must use a Class 2 or SELV rated
power supply.
2. COMMUNICATIONS:
USB/PG Port: Adheres to USB specification 1.1. Device only using Type B
connection.
Serial Ports: Format and Baud Rates for each port are individually software
programmable up to 115,200 baud.
RS232/PG Port: RS232 port via RJ12
COMMS Ports: RS485 port via RJ11
Ethernet Port: 10 BASE-T / 100 BASE-TX
3. LEDs:
STS – Status LED indicates condition of ICM8.
TX/RX – Transmit/Receive LEDs show serial activity.
Ethernet – Link and activity LEDs.
4. MEMORY:
On-board User Memory: 4 Mbytes of non-volatile Flash memory.
On-board SDRAM: 2 Mbytes
1
5. CERTIFICA TIONS AND COMPLIANCES:
2
1
SAFETY
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment for measurement, control, and laboratory use, Part 1.
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement, Control and Laboratory use.
Immunity to Industrial Locations: Electrostatic discharge EN 61000-4-2 Criterion B
4 kV contact discharge 8 kV air discharge
Electromagnetic RF fields EN 61000-4-3 Criterion A
10 V/m
Fast transients (burst) EN 61000-4-4 Criterion B
2 kV power 1 kV signal
Surge EN 61000-4-5 Criterion A
1kV L-L,2 kV L&N-E power
RF conducted interference EN 61000-4-6 Criterion A
3 V/rms
Emissions:
Emissions EN 55011 Class A
Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self­recovers.
3. This device was designed for installation in an enclosure. To avoid electrostatic discharge to the unit in environments with static levels above 4 kV precautions should be taken when the device is mounted outside an enclosure. When working in an enclosure (ex. making adjustments, setting switches etc.) typical anti-static precautions should be observed before touching the unit.
3
6. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C Storage Temperature Range: -30 to +70°C Operating and Storage Humidity: 80% max relative humidity,
non-condensing, from 0 to 50°C
Altitude: Up to 2000 meters
7. CONSTRUCTION: Case body is black high impact plastic and stainless
steel. Installation Category I, Pollution Degree 2.
8. POWER CONNECTION: Removable wire clamp screw terminal block.
Wire Gage Capacity: 24 AWG to 12 AWG Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)
9. MOUNTING: Snaps onto standard DIN style top hat (T) profile mounting
rails according to EN50022 -35 x 7.5 and -35 x 15.
10. WEIGHT: 12.3 oz (348g)
HARDWARE
INSTALLATION
Figure 1 - Attach ICM8 To DIN Rail
POWER SUPPLY REQUIREMENTS
It is very important that the power supply is mounted correctly if the unit is
to operate reliably. Please take care to observe the following points:
– The power supply must be mounted close to the unit, with usually not more
than 6 feet (1.8 m) of cable between the supply and the ICM8. Ideally, the shortest length possible should be used.
– The wire used to connect the ICM8’s power supply should be at least
22-gage wire. If a longer cable run is used, a heavier gage wire should be used. The routing of the cable should be kept away from large contactors, inverters, and other devices which may generate significant electrical noise.
– A power supply with a Class 2 or SELV rating is to be used. A Class 2 or
SELV power supply provides isolation to accessible circuits from hazardous voltage levels generated by a mains power supply due to single faults. SELV is an acronym for “safety extra-low voltage.” Safety extra­low voltage circuits shall exhibit voltages safe to touch both under normal operating conditions and after a single fault, such as a breakdown of a layer of basic insulation or after the failure of a single component has occurred.
2
EMC INSTALLATION GUIDELINES
Although Red Lion Controls Products are designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into a unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMI guidelines for a successful installation in an industrial environment.
1. To reduce the chance of noise spikes entering the unit via the power lines,
connections should be made to a clean source. Connecting to circuits that also
power loads such as contactors, relays, motors, solenoids etc. should be avoided.
2. The unit should be mounted in a metal enclosure, which is properly connected
to protective earth.
3. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield to earth ground (protective earth) at one end where the
unit is mounted.
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is over 1 MHz.
c. Connect the shield to common of the Data Station and leave the other end
of the shield unconnected and insulated from earth ground.
WIRING
POWER CONNECTION
4. Never run Signal or Control cables in the same conduit or raceway with AC power lines, conductors feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run through metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter. Also, Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.
5. Long cable runs are more susceptible to EMI pickup than short cable runs. Therefore, keep cable runs as short as possible.
6. In extremely high EMI environments, the use of external EMI suppression devices is effective. The following EMI suppression devices (or equivalent) are recommended: Ferrite Suppression Cores for signal and control cables:
Fair-Rite part number 0443167251 (RLC part number FCOR0000) TDK part number ZCAT3035-1330A Steward part number 28B2029-0A0
Line Filters for input power cables:
Schaffner part number FN2010-1/07 (RLC part number LFIL0000) Schaffner part number FN670-1.8/07 Corcom part number 1 VR3
Visit RLC's web site at www.redlion.net for more information on EMI
guidelines, Safety and CE issues as they relate to Red Lion Controls products.
COMMON
+24 VDC
COMM
231
+24
---
N/C
PROGRAMMING PORTS
USB/PG
RS232/PG
CTS Rx COMM COMM
RS232
Tx RTS
312
CBLUSB00
OR
CBLPROG0
3
RST
CBLxxxxx*
DSP
TT
O
NXMMI
A
PAR
FF1 2
V
PS1P
S
2
PS3PS4
COMMUNICATION PORTS
RS232/PG
CTS Rx COMM COMM Tx
RS232
RTS
RS485
CBLPROG0
OR
CBLxxxxx*
A
X
M
NIM
8.8.8.8.8
O
T
T
SS
1P2P
DSP
PAR
F1
V
S
3PS
4P
RST
2F
* Use appropriate communications cable. See Ordering Information for descriptions of the available cables.
RS485
NC (PIN 1) NC COMM A (+)
B (-) NC (PIN 6)
PORT 3 - ETHERNET CONNECTION
GREEN/ORANGE LED
AMBER LED
8.8.8.8.8
Standard Ethernet cable
4
24VDC ±10%
COMMS
PORT
RS232/PG PORT
RTS (PIN 6)
CTS (PIN 1)
USB/PG
RS232
COMMTxCOMM
Rx
POWER
CONNECTOR
N/C
3
2
COMMON
1
ETHERNET
RS485
RS232/PG
USB/PG
STS
ETHERNET
(NIC)
ORANGE
GREEN/
LED
LED
AMBER
PORT
RS485
NC
NC (PIN 1)
NC (PIN 6)
A (+)
COMM
B (-)
ICM8 PORT PIN OUTS
TROUBLESHOOTING
1. This module is designed to operate with Red Lion panel meters only.
Please make sure a Red Lion product is connected to either one of the two serial ports for the gateway to be active.
2. The Ethernet port is equipped with data LEDs. If they are blinking,
the converter is active and the data is available at the port. Please verify the receiving equipment is properly programmed.
3. If for any reason you have trouble operating, connecting, or simply
have questions concerning your new ICM8, contact Red Lion’s technical support. For contact information, refer to the back page of this bulletin for phone and fax numbers.
EMAIL: techsupport@redlion.net Web Site: http://www.redlion.net
COMMUNICATING WITH THE ICM8
CONFIGURING THE ICM8
The ICM8 is configured using Crimson software. Crimson is available as a free download from Red Lion’s website, or it can be ordered on CD. Updates to Crimson for new features and drivers are posted on the website as they become available. Crimson software can configure the ICM8 through the RS232/PG port or USB/PG port. The USB/PG port is connected using a standard USB cable with a Type B connector.
The driver needed to use the USB port will be installed with Crimson. The RS232/PG port uses a programming cable made by Red Lion to connect to the DB9 COM port of your computer. If making your own cable, refer to the “ICM8 Port Pin Outs” for wiring information.
ETHERNET COMMUNICATIONS
Ethernet communications can be established at either 10 BASE-T or 100 BASE-TX. The Crimson manual contains additional information on Ethernet communications.
RS232 PORTS
The ICM8 has one RS232 port. The port can be used for programming or communications.
ICM8 RS232/PG PORT
CTS
RS232
Rx COMM COMM Tx RTS
TXD
RXD
COMM
RECEIVING DEVICE
DB9 DTE
3
2
5
RS485 PORT
The ICM8 has one RS485 port.
ICM8 COMMS PORT
NC
RS485
NC COMM
A (+) B (-)
NC
Note: All Red Lion devices connect A to A and B to B.
B (-)
A (+)
COMM.*
RECEIVING DEVICE
* OPTIONAL
5
LEDS
STS – STATUS LED
The green Status LED provides information regarding the state of the ICM8. This includes indication of the various stages of the start-up routine (power-up), and any errors that may occur.
ETHERNET LEDS
LED INDICATION
YELLOW (Solid) Link Established
YELLOW (Flashing) Network Activity
Startup Routing
INDICATION
Rapidly Flashing Steady ICM8 is operating properly
ICM8 is currently running the boot loader and/or being flash upgraded by Crimson
USER COMMUNICATION PORTS - TX/RX LEDS
LED INDICATION
GREEN Transmitting RED Receiving
GREEN 10 BASE-T Communications AMBER 100 BASE-T Communications
ORDERING INFORMATION
PART NUMBERDESCRIPTIONMODEL NO.
ICM8
CBL
DR
1
Contact your Red Lion distributor or visit our website for complete selection.
2
Use this part number to purchase Crimson on CD with a printed manual, USB
cable, and RS-232 cable. Otherwise, download free of charge from www.redlion.net.
3
Red Lion offers RJ modular jack adapters. Refer to the DR literature for
complete details.
Communication Gateway
1
3
ICM80000 PSDRxxxxDIN Rail Power SupplyPSDR
SFCRM200Crimson 2.0 2, Manual and Download CableSFCRM2
CBLPROG0RS-232 Programming Cable
CBLUSB00USB Cable
CBLxxxxxCommunications Cables DRxxxxxxDIN Rail Mountable Adapter Products
6
This page intentionally left blank
7
The Company warrants the products it manufactures against defects in materials and workmanship
LIMITED WARRANTY
for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
Red Lion Controls Headquarters 20 Willow Springs Circle York PA 17406 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839
Red Lion Controls
Europe
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
54, Vishvas Tenement
GST Road, New Ranip,
Ahmedabad-382480 Gujarat, India
Tel +91 987 954 0503
Fax +91 79 275 31 350
Red Lion Controls
China
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683
Loading...