Red Lion IAMS0001, IAMS0011, IAMS0010 Users Manual

US/UK
Page 1
IAMS
Models No. 0001 / 0011 / 0010
FR
DE
Page 29
Seite 57
IAMS 0001 / 0011 / 0010
CONTENTS
Warning! ............................................................................. 2
Symbol identification .......................................................... 3
Safety instructions .............................................................. 3
How to dismantle the IAMS Devices ................................. 5
When front LED lights red / display shows AO.ER ............ 5
Advanced features ............................................................. 6
Application ......................................................................... 6
Technical characteristics .................................................... 6
PGMMOD00 Display / programming front .......................... 7
Applications ........................................................................ 8
Order codes ....................................................................... 9
Electrical specifications ...................................................... 9
Visualisation of sensor error detection and
input signal outside range ................................................. 13
Sensor error detection limits .............................................. 14
Error indications ................................................................. 14
connections ........................................................................ 15
Block diagram .................................................................... 16
Setup / operating the function keys ................................... 17
Routing diagram ................................................................. 23
Routing diagram ................................................................. 26
Advanced settings (ADV.SET) ............................................ 26
Scrolling help text in display line 3 .................................... 27
Graphic depiction of relay action Setpoint ........................ 28
Graphic depiction of relay action Window ......................... 28
1
GENERAL
The IAMS devices are designed for connection to hazardous
WARNING!
electric voltages. Ignoring this warning can result in severe personal injury or mechanical damage. To avoid the risk of electric shock and fire, the safety instruc­tions of this manual must be observed and the guidelines fol lowed. The specifications must not be exceeded, and the devices must only be applied as described in the following. Prior to the commissioning of the devices, this manual must be examined carefully. Only qualified personnel (technicians) should install these devices. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
HAZARD-
OUS
VOLTAGE
INSTAL-
LATION
2
Until the devices are fixed, do not connect hazardous voltages
WARNING!
to the devices. The following operations should only be carried out on disconnected devices and under ESD safe conditions: General mounting, connection and disconnection of wires. Troubleshooting the devices.
Repair of the device must be done by Red Lion Controls only.
WARNING
To keep the safety distances, the relay contacts on the devices must not be connected to both hazardous and non-hazard ous volt ages at the same time. The IAMS devices must be mounted on a DIN rail according to DIN 46277.
WARNING
Do not open the front plate of the devices as this will cause damage to the connector for the display / programming module PGMMOD00. The devices contain no DIP-switches or jumpers.
SYMBOL IDENTIFICATION
Triangle with an exclamation mark: Warning / demand. Potentially lethal situations.
The CE mark proves the compliance of the devices with the essential requirements of the directives.
The double insulation symbol shows that the devices are protected by double or reinforced insulation.
SAFETY INSTRUCTIONS
DEFINITIONS: Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and
50 to 1000 Volt AC. Technicians are qualified persons educated or trained to mount, operate, and also troubleshoot technically correct and in accordance with safety regulations. Operators, being familiar with the contents of this manual, adjust and operate the knobs or potentiometers during normal operation.
RECEIPT AND UNPACKING:
Unpack the device without damaging it and make sure that the manual always follows the device and is always available. The packing should always follow the device until this has been permanently mounted. Check at the receipt of the device whether the type corresponds to the one ordered.
ENVIRONMENT:
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as well as rain and heavy moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation. All devices fall under Installation Category II, Pollution Degree 1, and Insulation Class II.
MOUNTING:
Only technicians who are familiar with the technical terms, warnings, and instruc­tions in the manual and who are able to follow these should connect the devices. Should there be any doubt as to the correct handling of the devices, please contact your local distributor or, alternatively, Red Lion Controls Worldwide Headquarters, 20 Willow Springs Circle, York, PA 17406 USA, Phone: +1 (717) 767-6511, Fax: +1 (717) 764-0839
3
Mounting and connection of the devices should comply with national legislation for mounting of electric materials, i.a. wire cross section, protective fuse, and location. Descriptions of input / output and supply connections are shown in the block diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power switch, it should be easily accessible and close to the device. The power switch should be marked with a label indicating that it will switch off the volt age to the device.
Year of manufacture can be taken from the first two digits in the serial number.
UL INSTALLATION REQUIREMENTS:
Use 60/75°C copper conducters only For use only in pollution degree 2 or better
Max. ambient temperature ..................... 60°C
Max. wire size ......................................... AWG 26-14
UL file number ........................................ E324843
CALIBRATION AND ADJUSTMENT:
During calibration and adjustment, the measuring and connection of external voltages must be carried out according to the specifications of this manual. The technician must use tools and instruments that are safe to use.
NORMAL OPERATION:
Operators are only allowed to adjust and operate devices that are safely fixed in panels, etc., thus avoiding the danger of personal injury and damage. This means there is no electrical shock hazard, and the device is easily accessible.
CLEANING:
When disconnected, the devices may be cleaned with a cloth moistened with distilled water.
LIABILITY:
To the extent that the instructions in this manual are not strictly observed, the customer cannot advance a demand against Red Lion that would otherwise exist according to the concluded sales agreement.
4
HOW TO DISMANTLE THE IAMS DEVICES
First, remember to demount the connectors with hazardous voltages.
Picture 1:
Detach the device from the DIN rail by lifting the bottom lock.
When front LED lights red / display shows AO.ER
IAMS0001 and IAMS0011 are designed with a high safety level. Therefore, a
continuous measurement of the outgoing current is carried out on a 4...20 mA output signal. If the current output signal is different from the internally calculated output value or the current output is 0 (due to e.g. an open circuit breakage), an error mode switches on the red front LED and disables the relays. This function is not a default option but must be actively selected via the programming menu (S4...20 & S20...4). The error mode can only be reset by switching off and then switching on the supply voltage to the device.
5
IAMS 0001 / 0011 / 0010
• Input for RTD, TC, Ohm, potentiometer, mA and V
• 2-wire supply > 16 V
• FM-approved for installation in Div. 2
• Output for current, voltage and 2 relays
• Universal AC or DC supply
Advanced features
• Programmableviadetachabledisplayfront(PGMMOD00),process
calibration, signal and relay simulation, password protection, error diagnostics and selection of help text in several languages.
Application
• Linearised,electronictemperaturemeasurementwithRTDorTCsensor.
• Conversionoflinearresistancevariationtoastandardanaloguecurrent/volt
age signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
• Powersupplyandsignalisolatorfor2wiretransmitters.
• Processcontrolwith2pairsofpotentialfreerelaycontactsandanalogue
output.
• Galvanicseparationofanaloguesignalsandmeasurementoffloatingsignals.
• TheIAMS0001andIAMS0011havebeendesignedaccordingtostrictsafety
requirements and are thus suit able for application in SIL 2 installations.
Technical characteristics
• WhenthedevicesareusedincombinationwiththePGMMOD00display/
programming front, all operational parameters can be modified to suit any application. As the devices are designed with electronic hardware switches, it is not necessary to open them for setting of DIP-switches.
• Agreen/redfrontLEDindicatesnormaloperationandmalfunction.Ayellow
LED is ON for each active output relay.
• Continuouscheckofvitalstoreddataforsafetyreasons.
• 4port2.3kVACgalvanicisolation.
6
PGMMOD00 DISPLAY / PROGRAMMING FRONT
Functionality
The simple and easily understandable menu structure and the explanatory help texts guide you effortless ly and automatically through the setup steps, thus making the product very easy to use. Functions and setup options are described in the section ”Setup / operating the function keys”.
Application
• Communicationsinterfaceformodificationofoperationalparametersinthe
IAMS devices.
• Canbemovedfromonedevicetoanotherofthesametypeanddownload
the setup of the first device to subsequent devices.
• Fixeddisplayforreadoutofprocessdataandstatus.
Technical characteristics
• LCDdisplaywith4lines;Line1(H=.2inch/5.57mm)showsinputsignal, line2(H=.2inch/3.33mm)showsunits,line3(H=.13inch/3.33mm)shows
analogue output or tag no. and line 4 shows communication and relay status.
• Programmingaccesscanbeblockedbyassigningapassword.The
password is saved in the device in order to ensure a high degree of protection against unauthorised modifications to the setup.
Mounting / installation
• ClickPGMMOD00ontothefrontofthedevice.
7
Input signals:
Current
Volt -
age
+
+
Output signals:
APPLICATIONS
Potenti-
RTD and lin.R TC
ometer
Connect., wires
4 3 2
44
43
42
+
41
Relays
Supply:
8
12
14
13
11
Analogue, 0/4...20 mA and voltage
21.6...253 VAC or
19.2...300 VDC
+
10 V
1 V
-
10 V
1 V
+
+
-
-
+
-
33
32
31
24
23
22
21