Red Lion IAMS0002, IAMS0020, IAMS0022 Users Manual

IAMS
Models No. 0002 0022 / 0020
Drawing No. LP1109 Version No. 104 Revision Date 19/06
IAMS 0002 / 0022 / 0020
CONTENTS
Warning ....................................................................................................... 4
Symbol identification ............................................................................ 5
Safety instructions ................................................................................. 5
How to dismantle the IAMS 0002 / 0022 / 0020 .................... 7
When front LED lights red / display shows AO.ER .................... 7
Advanced features ................................................................................. 8
Application ................................................................................................. 8
Technical characteristics ...................................................................... 9
PGM display / programmer front ...................................................... 10
Mounting / demounting the PGMMOD ........................................... 11
Applications ............................................................................................. 12
Electrical specifications........................................................................ 13
Visualisation in the PGM of sensor error detection
and input signal outside range ......................................................... 18
Sensor error detection limits .......................................................... 18
Error indications ................................................................................... 19
Connections .............................................................................................. 20
Block diagram ........................................................................................... 21
Configuration / operating the function keys ............................... 22
Routing diagram ...................................................................................... 29
Routing diagram, Routing diagram,
Manual deactivation of the latch function ................................... 33
Scrolling help text in display line 3 ................................................. 34
Graphic depiction of latch function setpoint ............................... 36
Graphic depiction of latch function window ................................ 37
Graphic depiction of relay action setpoint ................................... 38
Graphic depiction of relay action window .................................... 38
Ordering information ............................................................................. 39
Advanced settings (ADV.SET) .................................. 32
LP1109 3
GENERAL
The IAMS devices are designed for connection to hazardous

WARNING

electric voltages. Ignoring this warning can result in severe personal injury or mechanical damage. To avoid the risk of electric shock and fire, the safety instructions of this manual must be observed and the guidelines fol lowed. The specifications must not be exceeded, and the device must only be applied as described in the following. Prior to the commissioning of the device, this manual must be examined carefully. Only qualified personnel (technicians) should install these devices. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Until the devices are fixed, do not connect hazardous voltages to the devices.
HAZARD OUS
VOLTAGE
The following operations should only be carried out on a discon­nected devices and under ESD safe conditions: General mounting, connection and disconnection of wires. Troubleshooting the device.
Repair of the device must be done by Red Lion Controls only.
WARNING
WARNING
To keep the safety distances, the relay contacts on the devices must not be connected to both hazardous and non-hazard ous volt ages at the same time.
INSTAL­LATION
The IAMS devices must be mounted on a DIN rail according to DIN
46277.
WARNING
Do not open the front plate of the devices as this will cause damage to the connector for the display / programming module PGMMOD00. This devices contains no DIP-switches or jumpers.
4 LP1109

SYMBOL IDENTIFICATION

Triangle with an exclamation mark: Warning / demand.
Potentially lethal situations.
The CE mark proves the compliance of the device with the essential requirements of the directives.
The double insulation symbol shows that the device is protected by double or reinforced insulation.
DEFINITIONS Hazardous
50 to 1000 Volt AC. Technicians are qualified persons educated or trained to mount, operate, and also troubleshoot technically correct and in accordance with safety regulations. Operators, being familiar with the contents of this manual, adjust and operate the knobs or potentiometers during normal operation.
RECEIPT AND UNPACKING
Unpack the device without damaging it. The packing should always follow the device until this has been permanently mounted. Check at the receipt of the module whether the type corresponds to the one ordered.
ENVIRONMENT
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as well as rain and heavy moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation. All devices fall under Installation Category II, Pollution Degree 1, and Insulation Class II.
MOUNTING
Only technicians who are familiar with the technical terms, warnings, and instruc­tions in the manual and who are able to follow these should connect the devices. Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively,
voltages have been defined as the ranges: 75 to 1500 Volt DC, and

SAFETY INSTRUCTIONS

Red Lion Controls
LP1109 5
Mounting and connection of the devices should comply with national legislation for mounting of electric materials, i.e. wire cross section, protective fuse, and location. Descriptions of input / output and supply connections are shown in the block diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power switch, it should be easily accessible and close to the device. The power switch should be marked with a label indicating that it will switch off the volt age to the device.
UL INSTALLATION REQUIREMENTS
Use 60/75°C copper conducters only For use only in pollution degree 2 or better
Max. ambient temperature ............................ 60°C
Max. wire size ...................................................... AWG 26-14
UL file number .................................................... E324843
CALIBRATION AND ADJUSTMENT
During calibration and adjustment, the measuring and connection of external voltages must be carried out according to the specifications of this manual. The technician must use tools and instruments that are safe to use.
NORMAL OPERATION
Operators are only allowed to adjust and operate devices that are safely fixed in panels, etc., thus avoiding the danger of personal injury and damage. This means there is no electrical shock hazard, and the device is easily accessible.
CLEANING
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
LIABILITY
To the extent that the instructions in this manual are not strictly observed, the custom er cannot advance a demand against Red Lion Controls that would otherwise exist according to the concluded sales agreement.
6 LP1109

HOW TO DISMANTLE THE IAMS 0002 / 0022 / 0020

First, remember to demount the connectors with hazardous voltages.
Picture 1:
Detach the device from the DIN rail by lifting the bottom lock.

When front LED lights red / display shows AO.ER

IAMS0002 and IAMS0022 are designed as SIL 2 devices with a high safety level.
Therefore, a continuous measurement of the outgoing current is carried out on
a 4...20 mA and 20...4 mA output signal. If the current output signal is different
from the internal calculated output value or the current output is 0 (due to e.g.
an open circuit breakage), an error mode switches on the red front LED.
This function is not a default option but must be actively selected via the
programming menu (S4-20 & S20-4).
The error mode can only be reset by switching off and then switching on the
supply voltage to the device.
LP1109 7
IAMS 0002 / 0022 / 0020
• Input for RTD, TC, Ohm, potentiometer, mA and V
• 2-wire supply > 16 V
• 2 adjustable alarm limits
• FM-approved for installation in Div. 2
• Output for current , voltage and 2 relays
• Universal AC or DC supply

Advanced features

• Programmable by way of detachable display front (PGMMOD 00/C1), process calibration, signal simulation, password protection, error diagnostics and selec­tion of help text available in several languages.

Application

• Linearised, electronic temperature measurement with RTD or TC sensor.
• Conversion of linear resistance variation to a standard analogue current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentio meter.
• Power supply and signal isolator for 2-wire transmitters.
• Process control with 2 pairs of potential-free relay contacts and analogue output.
• Process control with 2 pairs of potential-free relay contacts which can be configured to suit any application.
• Process control with standard analogue output.
• Galvanic separation of analogue signals and measurement of floating signals.
• The IAMS0002 and IAMS0022 have been designed according to strict safety requirements and is thus suitable for application in SIL 2 installations.
• Trip amplifier with window function allowing the relay to change state within a high and a low setpoint on the input span.
• Relay latch function, where the relay is activated and can only be reset manually.
• Sophisticated sensor error surveillance, where one relay holds the state immediately prior to the sensor error, thus allowing the process to continue. The other relay can be set for sensor error alarm so that the defect sensor can be replaced immediately.
8 LP1109

Technical characteristics

• When the devices are used in combination with a programming front (PGMMOD 00/C1), all operational parameters can be modified to suit any application. As the devices are designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
• A green / red front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
• Continuous check of vital stored data for safety reasons.
• 3-port 2.3 kVAC galvanic isolation.
• 4-port 2.3 kVAC galvanic isolation. (IAMS0022)
LP1109 9

PGM DISPLAY / PROGRAMMER FRONT

Functionality
The simple and easily understandable menu structure and the explanatory help texts guide you effortlessly and automatically through the configuration steps, thus making the product very easy to use. Functions and configuration options are described in the section ”Configuration / operating the function keys”.
Application
• Communications interface for modification of operational parameters in the IAMS devices.
• Can be moved from one device to another and download the configuration of the first transmitter to subsequent transmitters.
• Fixed display for readout of process data and status.
Technical characteristics
• LCD display with 4 lines; Line 1 (H=5.57 mm) shows input signal, line 2 (H=3.33 mm) shows units, line 3 (H=3.33 mm) shows analogue output or tag no. and line 4 shows communication and relay status.
• Programming access can be blocked by assigning a password. The password is saved in the transmitter in order to ensure a high degree of protection against unauthorised modifications to the configuration.
Mounting / installation
• Click PGM onto the front of the device.
10 LP1109

MOUNTING / DEMOUNTING THE PGMMOD

OK


1
3

4
2
PGM
1: Insert the tabs of PGMMOD into the holes at the top of the device. 2: Swing PGMMOD into place.
Demounting of PGMMOD
3: Push the release button on the bottom of PGMMOD and swing PGMMOD up.
LP1109 11
Input signals:
Potentio-
Volt -
Current
+
-
age
meter
+
-
Output signals:

APPLICATIONS

RTD and lin.R TC
Connect., wires
*
-
+
See the connection drawing on page 20.
44
43
42
41
Relays
12
14
+
10 V
1 V
-
13
11
Analogue, 0/4...20 mA and voltage
Supply:
33
21.6...253 VAC or
19.2...300 VDC
Polarity is reversible.
12 LP1109
32
31
+
-
10 V
1 V
+
+
-
-
24
23
22
21

Electrical specifications

Environmental conditions
Specifications range ............................................... -20°C to +60°C
Calibration temperature ........................................ 20...28°C
Relative humidity..................................................... < 95% RH (non-cond.)
Protection degree .................................................... IP20
Mechanical specifications
Dimensions (HxBxD) ............................................... 109 x 23.5 x 104 mm
Dimensions, with PGMMOD (HxBxD) ................ 109 x 23.5 x 116 / 131 mm
Weights
IAMS0002 .............................................................. 145 g (5.1 oz)
IAMS0020 .............................................................. 159 g (5.6 oz)
IAMS0022 .............................................................. 170 g (6.0 oz)
Max. wire size ............................................................ 1 x 2.5 mm
Screw terminal torque ........................................... 0.5 Nm
Vibration ...................................................................... IEC 60068-2-6 : 2007 (IAMS0002)
IEC 60068-2-6 (IAMS0022/IAMS0020)
2...13.2 Hz .............................................................. ±1 mm
13.2...100 Hz ........................................................ ±0.7 g
Common specifications
Supply voltage, universal ..................................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Max. consumption .................................................... 2.0 W
Fuse ............................................................................... 400 mA SB / 250 VAC
Isolation voltage, test / operation .................... 2.3 kVAC / 250 VAC
Communications interface ................................... Communication enabler PGMMODC1
Signal / noise ratio .................................................. Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%):
Temperature input .............................................. 1 s
mA / V input .......................................................... 400 ms
2
stranded wire
LP1109 13
Accuracy, the greater of the general and basic values:
Input
type
All ±0.1% of span ±0.01% of span / °C
General values
Absolute accuracy
Temperature
coefficient
14 LP1109
Basic values
Input
type
Basic
accuracy
Temperature
coefficient
mA ±4 µA ±0.4 µA / °C
Volt ±20 µV ±2 µV / °C
Pt100 ±0.2°C ±0.01°C / °C
Linear resistance ±0.1 Ω ±0.01 Ω / °C
Potentiometer ±0.1 Ω ±0.01 Ω / °C
TC type:
E, J, K, L, N, T, U ±1°C ±0.05°C / °C
TC type: R, S, W3,
W5, LR ±2°C ±0.2°C / °C
TC type: B
85...200°C TC type: B
200...1820°C
EMC immunity influence .................................................. < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst ................................. < ±1% of span
Auxiliary supplies:
2-wire supply (terminal 44...43) ........................ 25...16 VDC / 0...20 mA
RTD, linear resistance and potentiometer input
Input for RTD types:
Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000 Ni50, Ni100, Ni120, Ni1000, Cu10, Cu20, Cu50, Cu100
Input
type
Pt10...Pt1000 Ni50...Ni1000
Cu10...Cu100
Lin. R
Potentiometer
Cable resistance per wire (max.), RTD............. 50 Ω
Sensor current, RTD ................................................ Nom. 0.2 mA
Effect of sensor cable resistance
(3- / 4-wire), RTD ..................................................... < 0.002 Ω / Ω
Sensor error detection, RTD ................................ Yes
Short circuit detection, RTD ................................ < 15 Ω
±4°C ±0.4°C / °C
±2°C ±0.2°C / °C
Min.
value
-200°C
-60°C
-200°C 0 Ω
10 Ω
Max.
value Standard
+850°C +250°C +260°C
10000 Ω
100 kΩ
IEC 60751
DIN 43760
α = 0,00427
-
-
LP1109 15
TC input
Type
B E
J K L N R S T U
W3 W5
LR
Cold junction compensation (CJC)
via internal CJC sensor ...................................... ±(2.0°C + 0.4°C * Δt)
Δt = internal temperature - ambient temperature
Sensor error detection, all TC types................. Yes
Sensor error current:
when detecting .................................................... Nom. 2 μA
else ........................................................................... 0 μA
Current input
Measurement range ................................................ 0...20 mA
Programmable measurement ranges ............... 0...20 and 4...20 mA
Input resistance........................................................ Nom. 20 Ω + PTC 50 Ω
Sensor error detection:
Loop break 4...20 mA ......................................... Yes
Voltage input
Measurement range ................................................ 0...12 VDC
Programmable measurement ranges ............... 0...1 / 0.2...1 / 0...5 / 1...5 /
Input resistance........................................................ Nom. 10 MΩ
value
0°C
-100°C
-100°C
-180°C
-200°C
-180°C
-50°C
-50°C
-200°C
-200°C 0°C 0°C
-200°C
Min.
Max.
value Standard
+1820°C +1000°C +1200°C +1372°C
+900°C +1300°C +1760°C +1760°C
+400°C
+600°C +2300°C +2300°C
+800°C
IEC 60584-1 IEC 60584-1 IEC 60584-1 IEC 60584-1
DIN 43710 IEC 60584-1 IEC 60584-1 IEC 60584-1 IEC 60584-1
DIN 43710
ASTM E988-90 ASTM E988-90 GOST 3044-84
0...10 and 2...10 VDC
16 LP1109
Current output
Signal range (span) ................................................. 0...20 mA
Programmable signal ranges ............................... 0...20 / 4...20 / 20...0 / 20...4 mA
Load (max.) ................................................................. 20 mA / 800 Ω / 16 VDC
Load stability ............................................................. 0.01% of span / 100 Ω
Sensor error detection ........................................... 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale / Downscale ............... 23 mA / 3.5 mA
Output limitation:
on 4...20 and 20...4 mA signals ..................... 3.8...20.5 mA
on 0...20 and 20...0 mA signals ..................... 0...20.5 mA
Current limit ............................................................... 28 mA
Voltage output
Signal range ............................................................... 0...10 VDC
Programmable signal ranges ............................... 0...1 / 0.2...1 / 0...10 / 0...5 / 1...5 /
Load (min.) .................................................................. 500 kΩ
2...10 / 1...0 / 1...0.2 / 5...0 / 5...1 /
10...0 and 10...2 V
Ex / I.S. approval
FM, applicable in ....................................................... Class I, Div. 2, Group A, B, C, D
Max. ambient temperature for T5 .................... 60°C
Class I, Div. 2, Group IIC Zone 2
Relay outputs
Relay functions ......................................................... Setpoint, Window, Sensor error,
Hysteresis ................................................................... 0...100%
On and Off delay ...................................................... 0...3600 s
Sensor error detection ........................................... Break / Make / Hold
Max. voltage .............................................................. 250 VRMS
Max. current ............................................................... 2 A / AC or 1 A / DC
Max. AC power .......................................................... 500 VA
Latch, Power and Off
Observed authority requirements Standard
EMC 2004/108/EC .................................................. EN 61326-1 (IAMS0002)
EMC 2014/30/EU ..................................................... EN 61326-1 (IAMS 0022 / 0020)
LVD 2006/95/EC ...................................................... EN 61010-1 (IAMS0002)
LVD 2014/35/EU ..................................................... EN 61010-1 (IAMS 0022 / 0020)
FM .................................................................................. 3600, 3611, 3810 and ISA 82.02.01
UL, Standard for Safety ......................................... UL 508
of span = of the currently selected measurement range
LP1109 17

Visualisation in the PGM of sensor error detection and input signal outside range

R1, ERR.ACT=NONE - R2, ERR.ACT=NONE,
Input Range Readout Limit
VO LT
CURR 0...20 mA / 4...20 mA
LIN.R
POTM -
TEMP TC / RTD
Input Range Readout Limit
All All
Configuration Sensor error detection:
OUT.ERR=NONE.
Else: ON
If the valid range of the A/D converter or the polynomial is exceeded

Sensor error detection limits

Input Range Readout Limit CURR Loop break (4..20 mA) SE.BR <= 3.6 mA; > = 21 mA POTM All, SE.BR on all 3-wire SE.BR > ca. 126 k
LIN.R
TEMP
No SE.SH for Cuxx, Pt10, Pt20 and Pt50
Sensor error check:
OFF
Outside range readout (IN.LO, IN.HI):
0...1 V / 0.2...1 V
0...10 V / 2...10 V
0...800
Ω
0...10 kΩ
Display readout below min.- / above max. (-1999, 9999):
Sensor error detection (SE.BR, SE.SH):
0...800
Ω SE.BR > ca. 875 Ω
0...10 kΩ SE.BR > ca. 11 kΩ TC SE.BR > ca. 750 k
RTD, 2-, 3-, and 4-wire
IN.LO < -25 mV IN.HI > 1.2 V IN.LO < -25 mV IN.HI > 12 V IN.LO < -1.05 mA IN.HI > 25.05 mA IN.LO < 0 Ω IN.HI > 1075 Ω IN.LO < 0 Ω IN.HI < 110 kΩ IN.LO < -0.5 % IN.HI > 100.5 % IN.LO < temperature range -2°C IN.HI > temperature range +2°C
-1999 Display readout <-1999 9999 Display readout >9999
SE.BR > ca. 15 k SE.SH < ca. 15 Ω
Ω / (1.25 V)
Ω
Ω
18 LP1109

Error indications

Error search Readout Error cause
Test of internal CJC sensor CJ.ER
Checksum test of the configuration in FLASH FL.ER Error in FLASH
Check measurement of analogue output current* AO.ER
Communications test PGM / device NO.CO Connection error Check that input signal matches input configuration IN.ER 1) Error levels on input
Check that saved configuration in PGM matches device TY.ER
Error indications in the display flash once per second. The help text explains the error. * Does not apply to IAMS0020.
1) The error is reset by switching off and then switching on the supply voltage to the device.
Readout at hardware error
CJC sensor defect or tem-
perature outside range
1) No load on the current out­put (only S4...20/S20...4 mA)
Configuration is not IAMS
0002 / 0022 / 0020
LP1109 19
Supply:
31 32 33

CONNECTIONS

Inputs:
RTD, 2-wire Resistance, 2-wire
41 42 43 44 41 42 43 44 41 42 43 44 41 42 43 44
Resistance,
3- / 4-wire
41 42 43 44 41 42 43 44 41 42 43 44 41 42 43 44
Voltage
41 42 43 44
- +
RTD, 3- / 4-wire
Potentiometer
TC, internal
CJC sensor
-+
- +
Tx
Current2-wire transmitter
- +
Outputs:
11 12 13 14 11 12 13 14 11 12 13 14
- + - + - +
mA
Voltage, 1 V Voltage, 10 VCurrent Relays
V V
21 22 23 24
R1 R2
20 LP1109

BLOCK DIAGRAM

+
-
2-wire transmitter
+
-
VALVE 5
l / min
50.0
PGM
21
+
-
41
42
CJC
PTC
20 Ω
MUX
Current
Voltage
Potentiometer
4
RTD og lin.R,
connection,
wires
23
TC
43
44
0.2 mA
CPU
12
I+
V
loop
31
Supply
21.6...253 VAC or
19.2...300 VDC
33
Supply
Green
EEPROM
Out.
Out.
Out.
I + V
I
V
Red
Safety
500 Ω
50 Ω
11
Gnd.
13
1 V
V
V
Yellow
21
Relay 1
Relay 1
Yellow
22
23
24
Relay 2
Relay 2
A / D
D / A
14
10 V
mA
mA
LP1109 21

CONFIGURATION / OPERATING THE FUNCTION KEYS

Documentation for routing diagram.
In general:
When configuring the IAMS devices, you will be guided through all parameters
and you can choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in line 3 on the display.
Configuration is carried out by using the 3 function keys:
1 will increase the numerical value or choose the next parameter 2will decrease the numerical value or choose the previous parameter 3will accept the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0.
See the reference diagram on page 28.
Pressing and holding
state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state
(1.0) without saving the changed values or parameters.
Further explanations:
Fast setpoint adjustment and relay test: These menus allow you to make a
quick setpoint change and relay test when the FastSet menu is activated. This function can only be activated when the relays are set for setpoint function and are controlled by a setpoint.
Pressing
1 and 2 simultaneously will activate a relay test and change the state
of the relay.
Pressing
3 will save the setpoint change.
Holding down 3 for more than 1 second will return the unit to the default state
without saving the setpoint change.
Password protection: Programming access can be blocked by assigning a
password. The password is saved in the transmitter in order to ensure a high degree of protection against unauthorised modifications to the configuration. Default password 2008 allows acces to all configuration menus.
3 will return to the previous menu or return to the default
22 LP1109
Signal and sensor error info via display front PGMMOD00
Sensor error (see limits in the table) is displayed as SE.BR (sensor break) or SE.SH
(sensor short). Signals outside the selected range (not sensor error, see table for limits) are displayed as IN.LO indicating low input signal or IN.HI indicating high input signal. The error indication is displayed in line 3 as text and at the same time the backlight flashes. Line 4 of the display is a status line which displays status of relay 1 and relay 2, COM (flashing bullet) indicating correct functioning of PGMMOD00 and arrow up/down which indicates tendency readout of the input signal. If the figure 1 or figure 2 flashes, the unit has detected that the setpoint has been exceeded and that the relay is in “delay” mode. When the delay time has passed and the relay makes/breakes, the relay sign either displays or disappears.
Signal and sensor error indication without display front
Status of the unit can also be read from the red/green LED in the front of the device.
Green flashing LED 13 Hz indicates normal operation. Green flashing LED 1 Hz indicates sensor error. Steady green LED indicates internal error. Steady red LED indicates fatal error.
Relay functions
6 different settings of relay function can be selected.
Setpoint: The unit works as a single limit switch Window: The relay has a window that is defined by a low and a high
Error function: The relay is activated by sensor error. Power: The relay is activated as long as the power is on. Off: The relay is deactivated. Latch: The relay is latched. Only valid for setpoint and window
Increasing/decreasing: The relays can be set to activate at increasing or
decreasing input signal.
Delay: An ON and an OFF delay can be set on both relays in the range
0...3600 s.
Hysteresis: 0.0...100.0%.
setpoint. On both sides of the window the relay has the same status.
function.
LP1109 23
Latch
When the setpoint is exceeded the relay outputs enter an alarm state. The latch
function of the IAMS0022 and IAMS0020 will hold the relays in this state until the function is deactivated manually. The latch function can be applied when the relay function setpoint or window is selected.
The latch function can be selected separately for each relay output. If the
configuration is copied from one device to another by way of the PGMMOD00, the latch function must be reconfigured.
The latch function activates and holds the relays when the input signal rises
above or falls below the selected setpoints and the relay action has been selected as increasing or decreasing.
The window function is selected by choosing ”window” in the menu and defining
a high and a low setpoint.
It can be selected for each relay contact whether the contact is open or closed
inside the window. This selection is made in the menu R1.cont and R2.cont.
The setpoint function is selected by choosing ”setpoint” in the menu and entering
the desired limit. The device then works as a single limit switch.
An activated relay means that the contact is closed if the contact function
”normally open” is selected, and the contact is open if the contact function ”normally closed” is selected.
The delay time for activation and deactivation can be set independently of each
other in the menus ON.DEL and OFF DEL respectively.
If the relay function ”Error” is active, the relay will latch when a sensor error
occurs and will not be deactivated automatically when the sensor error is rectified.
The relay can only be deactivated by an operator and only when the normal
conditions for deactivation are met. If the input signal still has a value that will activate the relay, the relay will latch again.
See the graphic depiction of the setpoint and window functions on pages 36, 37
and 38.
24 LP1109
Manual deactivation of the latch function
If the relay outputs are activated and thereby latched, it will be indicated in
the display. The backlight flashes and the scrolling help text tells you how to deactivate the output. Manual deactivation is carried out by way of the front buttons on the PGMMOD00. Use 1 and 2to navigate in the menu and 3 to validate your selection. If the password protection has been activated, the password must be entered in order to access the deactivation menu. See the menu structure on page 33.
Advanced functions
The unit gives access to a number of advanced functions which can be reached
by answering “Yes” to the point “adv.set”.
Display setup: Here you can adjust the brightness contrast and the backlight.
Setup of TAG number with 6 alphanumerics. Selection of functional readout in line 3 of the display - choose between readout of analogue output or TAG number.
Two-point process calibration: The unit can be process-calibrated in 2 points to
fit a given input signal. A low input signal (not necessarily 0%) is applied and the actual value is entered via PGMMOD00. Then a high signal (not necessarily 100%) is applied and the actual value is entered via PGMMOD00. If you accept to use the calibration, the unit will work according to this new adjustment. If you later reject this menu point or choose another type of input signal the unit will return to factory calibration.
Process simulation function: If you say ”yes” to the point “EN.SIM” it is possible
to simulate an input signal by means of the arrow keys and thus control the output signal up or down. When you finalise the point with 3, the unit returns to normal mode.The point REL.SIM allows you to activate relay 1 and relay 2 by means of the arrow-keys up/down. You must exit the menu by pressing 3 (no time-out).
Password: Here you can choose a password between 0000 and 9999 in order to
protect the unit against unauthorised modifications to the configuration. The unit is delivered default without password. If you have locked the device with a password by mistake, you can always open the menu by using the master password 2008.
Language: In the menu ”lang.setup” you can choose between 7 different
language versions of help texts that will appear in the menu. You can choose between UK, DE, FR, IT, ES, SE and DK.
LP1109 25
Auto diagnosis
The unit performs an advanced auto diagnosis of the internal circuits.
The following possible errors can by display in the front unit PGMMOD00. CJ.ER - CJC sensor defect or CJC temperature outside range FL.ER - Flash error AO.ER - No load on the current output (only for S4...20 mA/S20...4 mA) NO.CO - Connection error IN.ER - Error levels on input TY.ER - Configuration in PGMMOD00 does not match this product type
26 LP1109
Selection of units
After choosing the input signal type you can choose the process units which will
be displayed in text line 2 (see table). By selection of temperature input the process value is always displayed in Celsius or Fahrenheit. This is selected in the menu point after selection of temperature input.
Safety readback
When the device is delivered with default configuration, the SIL function is
disabled. The safety readback function (loop surveillance) can be selected in the menu O.RANGE, thus enabling the device to run in SIL mode. In order to enable the SIL functionality, the menu item S4...20 mA must be selected. Please note, however, that when safety readback is enabled, a sensor error will be indicated as an error on the analogue output signal.
Memory
In the memory menu you can save the configuration of the device in the
PGMMOD00, and then move the PGMMOD00 onto another device of the same type and download the configuration in the new device.
LP1109 27
Power up
1 2
50.0
12.0
1.0
1 2
1.2
1 2
3
%
0000 9999
1 2
3
0000
PASSW.
Txt 1
50.0
RELAY1
Txt 57
75.0
RELAY2 Txt 57
NO
YES
1 2
NO
ADV.SET
Txt 2
3
3
3
VOLT
IN TYPE
Txt 3
1.1
1.0 = Default state Line 1 shows input signal. Line 2 shows UNIT. By pressing 1 and 2 simultaneously line 3 alternates between A.Out and TAG. Line 4 shows relay and communication status.
1.1 = Only if password-
protected.
1.2 = Only if FastSet is acti-
vated and the relay
function is setpoint.
1.3 = Not valid for these input signals: 0...20 mA and
voltage.
1.4 = Only if input signal is
temperature.
1.5 = The relay can only be deactivated by an ope-
rator and only if the
normal conditions for deactivation are met. If the input signal still has a value that will activate the relay, the relay will latch again.
ADV.SET
YES
Txt 2
CURR
IN TYPE
Txt 3
POTM
IN TYPE
Txt 3
LIN.R
IN TYPE
Txt 3
TEMP
IN TYPE
Txt 3
Continued on the page Routing diagram ADV.SET
3
28 LP1109
Fast setpoint adjustment
and relay test
1 Increase setpoint 2 Decrease setpoint 3 Save and exit the menu 1 and 2 simultaneously = change relay state
VOLT CURR POTM LIN.R TEMP
1 2
3
2-10
V.RANGE
0-20 4-20
3
4-20
I.RANGE
3
2W 3W 4W
3
CONNEC.
3
2-10 0-10
1-5
0-5
0.2-1 0-1
1 2
Txt 4
1 2
Txt 5
1 2
3W
Txt 6
@C mA
rpm
(69 units)
(see pg 29 for
units list)
1 2
3
UNIT
%
Txt 11
3
0...9999
1 2
3
0
R 0%
Txt 7
Cu Pt Ni TC
1 2
Pt
SENSOR
Txt 10
Ni
SENSOR
Txt 10
TC.B TC.E TC.J TC.K TC.L TC.N TC.R TC.S TC.T TC.U TC.W3 TC.W5 TC.Lr
TC
SENSOR
Txt 10
Cu
SENSOR
Txt 10
1111
111.1
11.11
1.111
1 2
3
111.1
DEC.P
Txt 12
0...9999
1 2
3
2500
R 100%
Txt 8
10...1000
1 2 1 2
3
100
Pt TYPE
Txt 16
50...1000
1 2 1 2
3
100
Ni TYPE
Txt 17
1 2
3
TC.K
TC.TYPE
Txt 18
10...100
1 2 1 2
3
10
Cu TYPE
Txt 69
3
3
3
3
3
3
999.9
-199.9
1 2
0.0
DISP.LO
Txt 13
2W 3W 4W
3W
CONNEC.
Txt 6
2W 3W 4W
3W
CONNEC.
Txt 6
INT
CJC
Txt 63
2W 3W 4W
3W
CONNEC.
Txt 6

ROUTING DIAGRAM

If no key is activated for 1 minute, the display will return to the default state 1.0 without saving configuration changes.
1 Increase value / choose next parameter 2 Decrease value / choose previous parameter 3 Accept the chosen value and proceed to the next menu
Hold 3 Back to previous menu / return to menu 1.0 without saving
Availability of output parameters are model number dependent.
SETP
WIND
ERR
3
999.9
-199.9
1 2
100.0
DISP.HI Txt 14
3
DISP PERC
1 2
PERC
REL.UN Txt 15
3
POW OFF
1 2
SETP
R1.FUNC
Txt 19
3
N.O. N.C.
1 2
N.O.
R1.CONT
Txt 20
100.0
0.0
1 2
3
50.0
R1.SETP
Txt 21
3
INCR
ACT.DIR
Txt 22
INCR DECR
1 2
100.0
0.0
1 2
3
1.0
R1.HYST Txt 23
3
O.I.W C.I.W
1 2
3
@C @F
% A
bar
cm ft
ft/h
ft/s
g
gal/h
GW
O.I.W
R1.CONT
Txt 27
3
OPEN
ERR.ACT
Txt 34
3
3
UNITS:
CLOS OPEN
1 2
WIND
R1.FUNC
Txt 19
1.3
ERR
R1.FUNC
Txt 19
3
3
@C @F
1 2
@C
UNIT
Txt 9
R1.FUNC
R1.FUNC
Selectable
3
POW
Txt 19
OFF
Txt 19
3
ft/min
3
gal/min
3
3
hp
hPa
Hz
in
in/h
in/min
in/s
ips
K kA kg kJ
kPa
kV
100.0
0.0
1 2
60.0
SETP.LO
Txt 29
m3/min
100.0
0.0
1 2
3
70.0
SETP.HI
Txt 28
3
Continued on the next page
kW
kWh
l
l/h
l/min
l/s
m
m/h
m/min
m/s
m/s2
m3
m3/h
mA
mbar
mils
min
mm
mm/s
mol MPa
mV MW
MWh
N
Ohm
Pa
100.0
0.0
1 2
1.0
R1.HYST Txt 30
3
pH
rpm
s S t
t/h
uA um uS
V
W Wh yd
[blank]
LP1109 29
HOLD CLOS OPEN NONE
1 2
NONE
ERR.ACT
Txt 24
1.3
HOLD CLOS OPEN NONE
1 2
NONE
ERR.ACT
Txt 31
1.3
SETP WIND
ERR
3
3
POW OFF
1 2
SETP
R2.FUNC
Txt 19
WIND
R2.FUNC
Txt 19
1.3
ERR
R2.FUNC
Txt 19
POW
R2.FUNC
Txt 19
OFF
3
3
3
3
3
N.O. N.C.
1 2
N.O.
R2.CONT
Txt 20
O.I.W C.I.W
1 2
O.I.W
R2.CONT
Txt 27
CLOS OPEN
1 2
OPEN
ERR.ACT
Txt 34
3
3
3
100.0
0.0
1 2
50.0
R2.SETP
Txt 21
100.0
0.0
1 2
60.0
SETP.LO
Txt 29
3
3
INCR
DECR
1 2
INCR
ACT.DIR
Txt 22
100.0
0.0
1 2
70.0
SETP.HI
Txt 28
3
3
100.0
0.0
1 2
1.0
R2.HYST
Txt 23
100.0
0.0
1 2
1.0
R2.HYST
Txt 30
3600 0000
1 2
3
0
ON.DEL
Txt 25
3600 0000
1 2
3
0
ON.DEL
Txt 32
3
3
3600 0000
1 2
0
OFF.DEL
Txt 26
3600 0000
1 2
0
OFF.DEL
Txt 33
30 LP1109
3
3
HOLD CLOS OPEN NONE
1 2
NONE
ERR.ACT
Txt 24
1.3
HOLD CLOS OPEN NONE
1 2
NONE
ERR.ACT
Txt 31
1.3
S20-4
20-4 20-0
S4-20
3
3
4-20 0-20
1 2
4-20
O.RANGE
Txt 37
10-2 10-0
5-1
5-0
1-0.2
1-0 2-10 0-10
1-5 0-5
0.2-1 0-1
1 2
0-10
O.RANGE
Txt 39
3600 0000
1 2
3
0
ON.DEL Txt 25
3600 0000
1 2
3
0
ON.DEL Txt 32
3
3
3600 0000
1 2
0
OFF.DEL Txt 26
3600 0000
1 2
0
OFF.DEL Txt 33
3
3
VOLT CURR
1 2
CURR
ANA.OUT
Txt 36
VOLT
ANA.OUT
Txt 36
3
3
23mA
0/3.5mA
NONE
1 2
23mA
OUT.ERR
Txt 38
1.3
850
-200
1 2
3
0.0
OUT.LO Txt 41
1.4 1.4
To default
state 1.0
3
850
-200
1 2
150.0
OUT.HI
Txt 42
3
LP1109 31
MEM
DISP
CAL
SIM PASS LANG
1 2
MEM
SETUP
Txt 43
DISP
SETUP
Txt 43
CAL
SETUP
Txt 43
SIM
SETUP
Txt 43
PASS
SETUP
Txt 43
LANG
SETUP
Txt 43
LATC
SETUP
Txt 43
SAVE LOAD
1 2
3
SAVE
MEMORY Txt 44
9 0
1 2
3
3
CONTRA Txt 45
YES
NO
1 2
3
YES
CAL.LO
Txt 49
YES
NO
1 2
3
YES
EN.SIM
Txt 51
2.0
YES
NO
1 2
3 3
YES
EN.PASS
Txt 54
DE, DK, ES, FR, IT, SE,
UK
1 2
3
UK
LANGUA Txt 59
YES
NO
1 2
3
NO
R1.LATC Txt 64
ROUTING DIAGRAM
Advanced settings (ADV.SET)
2.0 In the submenu simulation (SIM) you must press 3 to return to the default state 1.0.
3
3
3
3
3
3
Txt 46
Txt 61
NO
25.0
Txt 52
NO
0000
NEW.PAS
Txt 55
NO
R2.LATC
Txt 64
9 0
1 2
9
LIGHT
100.0
0.0
1 2
2.0
%
100.0
0.0
1 2
%
9999 0000
1 2
YES
NO
1 2
NO
3
3
3
3
33
9 A
1 2
VALVE 5
Txt 47
YES
NO
1 2
YES
CAL.HI
Txt 50
REL.SIM
Txt 53
YES
NO
1 2
YES
EN.FAST
Txt 56
3
100.0
0.0
1 2
3
NO
90.0
%
Txt 62
3
3
3
YES
NO
1 2
3
YES
USE.CAL
Txt 60
To default state 1.0
32 LP1109
Manual deactivation of the latch function
To setup menu
40.0
Rx.LATC
Txt 65
R1 reset
40.0
R1.LATC
Txt 65
3
3
ROUTING DIAGRAM
YES
NO
1 2
NO
ENT.SET
Txt 67
1
3
0000 9999
1 2
0000
PASSW
Txt 1
1.1 1.4
3
40.0
R1.LATC
Txt 65
3
YES
NO
1 2
NO
R1.RLSE Txt 66
3
To default state 1.0
R2 reset
40.0
R2.LATC
Txt 65
3
40.0
R2.LATC
Txt 65
2
0000 9999
1 2
0000
PASSW
Txt 1
1.1
3
YES
NO
1 2
NO
R2.RLSE
Txt 66
1.4
3
LP1109 33
[01] Set correct password [19] Select OFF function - relay is permanently off

SCROLLING HELP TEXT IN DISPLAY LINE 3

[02] Enter advanced setup menu? Select POWER function - relay indicates power status OK [03] Select temperature input Select ERROR function - relay indicates sensor error only
Select potentiometer input Select SETPOINT function - relay controlled by 1 setpoint Select linear resistance input [20] Select Normally Closed contact Select current input Select Normally Open contact Select voltage input [21] Set relay setpoint
[04] Select 0.0-1 V input range [22] Activate relay on decreasing signal
Select 0.2-1 V input range Activate relay on increasing signal Select 0-5 V input range [23] Set relay hysteresis Select 1-5 V input range [24] No error action - undefined status at error Select 0-10 V input range Open relay contact at error Select 2-10 V input range Close relay contact at error
[05] Select 0-20 mA input range Hold relay status at error
Select 0-20 mA input range [25] Set relay ON delay in seconds
[06] Select 2-wire sensor connection [26] Set relay OFF delay in seconds
Select 3-wire sensor connection [27] Relay contact is Closed Inside Window
Select 4-wire sensor connection Relay contact is Open Inside Window [07] Set resistance value low [28] Set relay window setpoint high [08] Set resistance value high [29] Set relay window setpoint low [09] Select Celsius as temperature unit [30] Set relay window hysteresis
Select Fahrenheit as temperature unit [31] No error action - undefined status at error [10] Select TC sensor type Open relay contact at error
Select Ni sensor type Close relay contact at error
Select Pt sensor type Hold relay status at error
Select Cu sensor type [32] Set relay ON delay in seconds [11] Select display unit [33] Set relay OFF delay in seconds [12] Select decimal point position [34] Open relay contact at error [13] Set display range low Close relay contact at error [14] Set display range high [36] Select current as analogue output type [16] Select Pt10 as sensor type Select voltage as analogue output type
Select Pt20 as sensor type [37] Select 0-20 mA output range
Select Pt50 as sensor type Select 4-20 mA output range
Select Pt100 as sensor type Select S4-20 mA with safety readback
Select Pt200 as sensor type Select 20-0 mA output range
Select Pt250 as sensor type Select 20-4 mA output range
Select Pt300 as sensor type Select S20-4 mA with safety readback
Select Pt400 as sensor type [38] Select no error action - output undefined at error
Select Pt500 as sensor type Select downscale at error
Select Pt1000 as sensor type Select NAMUR NE43 downscale at error [17] Select Ni50 as sensor type Select NAMUR NE43 upscale at error
Select Ni100 as sensor type [39] Select 0.0-1 V output range
Select Ni120 as sensor type Select 0.2-1 V output range
Select Ni1000 as sensor type Select 0-5 V output range [18] Select TC-B as sensor type Select 1-5 V output range
Select TC-E as sensor type Select 0-10 V output range
Select TC-J as sensor type Select 2-10 V output range
Select TC-K as sensor type Select 1-0.0 V output range
Select TC-L as sensor type Select 1-0.2 V output range
Select TC-N as sensor type Select 5-0 V output range
Select TC-R as sensor type Select 5-1 V output range
Select TC-S as sensor type Select 10-0 V output range
Select TC-T as sensor type Select 10-2 V output range
Select TC-U as sensor type [41] Set temperature for analogue output low
Select TC-W3 as sensor type [42] Set temperature for analogue output high
Select TC-W5 as sensor type
Select TC-Lr as sensor type
34 LP1109
[43] Enter password setup
Enter simulation mode
Perform process calibration Enter display setup Perform memory operations
[44] Load saved configuration into IAMS0002
Save IAMS0002 configuration in PGM [45] Adjust LCD contrast [46] Adjust LCD backlight [47] Write a 6-character device TAG [48] Analogue output value is shown in dis-
play line 3
Device TAG is shown in display line 3 [49] Calibrate input low to process value? [50] Calibrate input high to process value? [51] Enable simulation mode? [52] Set the input simulation value [54] Enable password protection? [55] Set new password [59] Select language [60] Use process calibration values? [61] Set value for low calibration point [62] Set value for high calibration point [63] Select CJC connector (accessory)
Select internal temperature sensor [64] Enable relay latch function? [65] Relay is latched - press 3 to acknowledge
Relay 1 is latched - press 1 to release
Relay 2 is latched - press 2 to release
Relays are latched - press 1 or 2 tor relea-
se relay 1 or relay 2 [66] Release relay? (if conditions allow) [67] Enter setup menu? (latched relays may
release!) [69] Select Cu10 as sensor type
Select Cu20 as sensor type
Select Cu50 as sensor type
Select Cu100 as sensor type
LP1109 35

Graphic depiction of latch function setpoint

Input
signal
Setpoint
(increasing)
Hysteresis
Closed
Relay contact
(N.O.)
Open
Release not possible (setpoint still exceeded)
Release not possible (setpoint-hysteresis still exceeded)
Release not possible (OFF delay still exceeded)
Release possible (manual deactivation)
ON delay
Relay latched
OFF delay
Time
36 LP1109

Graphic depiction of latch function window

Time
ON delay OFF delay
Window
ON delay OFF- delay
Relay latched
Relay latched
Hysteresis
Open
Closed
Setpoint low
Setpoint high
Relay contact (N.O.)
Hysteresis
LP1109 37
Release possible
Release not possible (inside hysteresis)
Release not possible (still inside window)
Release not possible (OFF delay still active)

Graphic depiction of relay action setpoint

100
90
80
70
60
50
40
30
20
10
0 10 20 30 40 50 60 70 80 90 100
Relay action: Increasing Relay action: Decreasing
Setpoint = 50
Hysteresis = 10
O N.O. O N.O.On N.O.
On N.C. On N.C.
O N.C.
t
Relay unitsRelay units
100
90
80
70
60
50
40
30
O N.O. O N.O.On N.O.
20
On N.C. On N.C.
10
0 10 20 30 40 50 60 70 80 90 100

Graphic depiction of relay action window

100
Relay units
90
80
70
60
50
40
30
20
10
0 10 20 30 40 50 60 70 80 90 100
Relay function: Window (shown for increasing signal)
Contact: Closed inside window = Contact: Open inside window =
Hysteresis = 5
Setpoint High = 60
Setpoint Low = 40
Hysteresis = 5
1 1
O OO
2 2
1 2
OnOn On
100
Relay units
90
80
70
60
50
40
30
20
10
t
0 10 20 30 40 50 60 70 80 90 100
Relay function: Window (shown for decreasing signal)
Contact: Closed inside window = Contact: Open inside window =
Hysteresis = 10
Setpoint = 50
O N.C.
Hysteresis = 5
Setpoint High = 60
Setpoint Low = 40
Hysteresis = 5
1 1
O OO
2 2
1 2
t
OnOn On
t
38 LP1109

Ordering information

DESCRIPTION PART NUMBER
Universal transmitter with analog output IAMS0002
Universal transmitter with analog output / 2 relays IAMS0022
Universal trip amplifier / 2 relays IAMS0020
Display / programming module PGMMOD00
Display/Comms Module - Modbus RTU protocol interface over RS-485
LP1109 39
PGMMODC1
40 LP1109
Loading...