The IAMS devices are designed for connection to hazardous
WARNING
electric voltages.
Ignoring this warning can result in severe personal injury or
mechanical damage.
To avoid the risk of electric shock and fire, the safety instructions
of this manual must be observed and the guidelines fol lowed.
The specifications must not be exceeded, and the device must
only be applied as described in the following.
Prior to the commissioning of the device, this manual must be
examined carefully.
Only qualified personnel (technicians) should install these
devices. If the equipment is used in a manner not specified by
the manufacturer, the protection provided by the equipment may
be impaired.
Until the devices are fixed, do not connect hazardous voltages to
the devices.
HAZARD OUS
VOLTAGE
The following operations should only be carried out on a disconnected devices and under ESD safe conditions:
General mounting, connection and disconnection of wires.
Troubleshooting the device.
Repair of the device must be done by Red Lion Controls only.
WARNING
WARNING
To keep the safety distances, the relay contacts on the devices
must not be connected to both hazardous and non-hazard ous
volt ages at the same time.
INSTALLATION
The IAMS devices must be mounted on a DIN rail according to DIN
46277.
WARNING
Do not open the front plate of the devices as this will cause
damage to the connector for the display / programming module
PGMMOD00. This devices contains no DIP-switches or jumpers.
4 LP1109
SYMBOL IDENTIFICATION
Triangle with an exclamation mark: Warning / demand.
Potentially lethal situations.
The CE mark proves the compliance of the device with the essential
requirements of the directives.
The double insulation symbol shows that the device is protected by
double or reinforced insulation.
DEFINITIONS
Hazardous
50 to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and also
troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate
the knobs or potentiometers during normal operation.
RECEIPT AND UNPACKING
Unpack the device without damaging it. The packing should always follow the
device until this has been permanently mounted.
Check at the receipt of the module whether the type corresponds to the one
ordered.
ENVIRONMENT
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,
as well as rain and heavy moisture. If necessary, heating in excess of the stated
limits for ambient temperatures should be avoided by way of ventilation.
All devices fall under Installation Category II, Pollution Degree 1, and Insulation
Class II.
MOUNTING
Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to follow these should connect the devices.
Should there be any doubt as to the correct handling of the device, please contact
your local distributor or, alternatively,
voltages have been defined as the ranges: 75 to 1500 Volt DC, and
SAFETY INSTRUCTIONS
Red Lion Controls
LP1109 5
Mounting and connection of the devices should comply with national legislation
for mounting of electric materials, i.e. wire cross section, protective fuse, and
location. Descriptions of input / output and supply connections are shown in the
block diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power
switch, it should be easily accessible and close to the device. The power
switch should be marked with a label indicating that it will switch off the
volt age to the device.
UL INSTALLATION REQUIREMENTS
Use 60/75°C copper conducters only
For use only in pollution degree 2 or better
Max. ambient temperature ............................ 60°C
UL file number .................................................... E324843
CALIBRATION AND ADJUSTMENT
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
NORMAL OPERATION
Operators are only allowed to adjust and operate devices that are safely fixed in
panels, etc., thus avoiding the danger of personal injury and damage. This means
there is no electrical shock hazard, and the device is easily accessible.
CLEANING
When disconnected, the device may be cleaned with a cloth moistened with
distilled water.
LIABILITY
To the extent that the instructions in this manual are not strictly observed,
the custom er cannot advance a demand against Red Lion Controls that would
otherwise exist according to the concluded sales agreement.
6 LP1109
HOW TO DISMANTLE THE IAMS 0002 / 0022 / 0020
First, remember to demount the connectors with hazardous voltages.
Picture 1:
Detach the device from the DIN rail
by lifting the bottom lock.
When front LED lights red / display shows AO.ER
IAMS0002 and IAMS0022 are designed as SIL 2 devices with a high safety level.
Therefore, a continuous measurement of the outgoing current is carried out on
a 4...20 mA and 20...4 mA output signal. If the current output signal is different
from the internal calculated output value or the current output is 0 (due to e.g.
an open circuit breakage), an error mode switches on the red front LED.
This function is not a default option but must be actively selected via the
programming menu (S4-20 & S20-4).
The error mode can only be reset by switching off and then switching on the
supply voltage to the device.
LP1109 7
IAMS 0002 / 0022 / 0020
• Input for RTD, TC, Ohm, potentiometer, mA and V
• 2-wire supply > 16 V
• 2 adjustable alarm limits
• FM-approved for installation in Div. 2
• Output for current , voltage and 2 relays
• Universal AC or DC supply
Advanced features
• Programmable by way of detachable display front (PGMMOD 00/C1), process
calibration, signal simulation, password protection, error diagnostics and selection of help text available in several languages.
Application
• Linearised, electronic temperature measurement with RTD or TC sensor.
• Conversion of linear resistance variation to a standard analogue current /
voltage signal, i.e. from solenoids and butterfly valves or linear movements
with attached potentio meter.
• Power supply and signal isolator for 2-wire transmitters.
• Process control with 2 pairs of potential-free relay contacts and analogue
output.
• Process control with 2 pairs of potential-free relay contacts which can be
configured to suit any application.
• Process control with standard analogue output.
• Galvanic separation of analogue signals and measurement of floating signals.
• The IAMS0002 and IAMS0022 have been designed according to strict safety
requirements and is thus suitable for application in SIL 2 installations.
• Trip amplifier with window function allowing the relay to change state within a
high and a low setpoint on the input span.
• Relay latch function, where the relay is activated and can only be reset
manually.
• Sophisticated sensor error surveillance, where one relay holds the state
immediately prior to the sensor error, thus allowing the process to continue.
The other relay can be set for sensor error alarm so that the defect sensor can
be replaced immediately.
8 LP1109
Technical characteristics
• When the devices are used in combination with a programming front (PGMMOD
00/C1), all operational parameters can be modified to suit any application. As
the devices are designed with electronic hardware switches, it is not necessary
to open the device for setting of DIP-switches.
• A green / red front LED indicates normal operation and malfunction. A yellow
LED is ON for each active output relay.
• Continuous check of vital stored data for safety reasons.
• 3-port 2.3 kVAC galvanic isolation.
• 4-port 2.3 kVAC galvanic isolation. (IAMS0022)
LP1109 9
PGM DISPLAY / PROGRAMMER FRONT
Functionality
The simple and easily understandable menu structure
and the explanatory help texts guide you effortlessly
and automatically through the configuration steps,
thus making the product very easy to use. Functions
and configuration options are described in the section
”Configuration / operating the function keys”.
Application
• Communications interface for modification of operational parameters in the
IAMS devices.
• Can be moved from one device to another and download the configuration of
the first transmitter to subsequent transmitters.
• Fixed display for readout of process data and status.
Technical characteristics
• LCD display with 4 lines; Line 1 (H=5.57 mm) shows input signal, line 2
(H=3.33 mm) shows units, line 3 (H=3.33 mm) shows analogue output or tag
no. and line 4 shows communication and relay status.
• Programming access can be blocked by assigning a password. The password is
saved in the transmitter in order to ensure a high degree of protection against
unauthorised modifications to the configuration.
Mounting / installation
• Click PGM onto the front of the device.
10LP1109
MOUNTING / DEMOUNTING THE PGMMOD
OK
1
3
4
2
PGM
1: Insert the tabs of PGMMOD into the holes at the top of the device.
2: Swing PGMMOD into place.
Demounting of PGMMOD
3: Push the release button on the bottom of PGMMOD and swing PGMMOD up.
LP1109 11
Input signals:
Potentio-
Volt -
Current
+
-
age
meter
+
-
Output signals:
APPLICATIONS
RTD and lin.RTC
Connect., wires
*
-
+
See the connection drawing on page 20.
44
43
42
41
Relays
12
14
+
10 V
1 V
-
13
11
Analogue, 0/4...20 mA and voltage
Supply:
33
21.6...253 VAC
or
19.2...300 VDC
Polarity is reversible.
12LP1109
32
31
+
-
10 V
1 V
+
+
-
-
24
23
22
21
Electrical specifications
Environmental conditions
Specifications range ............................................... -20°C to +60°C
Calibration temperature ........................................ 20...28°C
Checksum test of the configuration in FLASHFL.ERError in FLASH
Check measurement of analogue output current*AO.ER
Communications test PGM / deviceNO.COConnection error
Check that input signal matches input configurationIN.ER1) Error levels on input
Check that saved configuration in PGM matches deviceTY.ER
Error indications in the display flash once per second. The help text explains the error.
* Does not apply to IAMS0020.
1) The error is reset by switching off and then switching on the supply voltage to the device.
Readout at hardware error
CJC sensor defect or tem-
perature outside range
1) No load on the current output (only S4...20/S20...4 mA)
Configuration is not IAMS
0002 / 0022 / 0020
LP1109 19
Supply:
313233
CONNECTIONS
Inputs:
RTD, 2-wireResistance, 2-wire
41 42 43 4441 42 43 4441 42 43 4441 42 43 44
Resistance,
3- / 4-wire
41 42 43 4441 42 43 4441 42 43 4441 42 43 44
Voltage
41 42 43 44
-+
RTD, 3- / 4-wire
Potentiometer
TC, internal
CJC sensor
-+
-+
Tx
Current2-wire transmitter
-+
Outputs:
11 12 13 1411 12 13 1411 12 13 14
-+-+-+
mA
Voltage, 1 VVoltage, 10 VCurrentRelays
VV
21 22 23 24
R1R2
20LP1109
BLOCK DIAGRAM
+
-
2-wire transmitter
+
-
VALVE 5
l / min
50.0
PGM
21
+
-
41
42
CJC
PTC
20 Ω
MUX
Current
Voltage
Potentiometer
4
RTD og lin.R,
connection,
wires
23
TC
43
44
0.2 mA
CPU
12
I+
V
loop
31
Supply
21.6...253 VAC or
19.2...300 VDC
33
Supply
Green
EEPROM
Out.
Out.
Out.
I + V
I
V
Red
Safety
500 Ω
50 Ω
11
Gnd.
13
1 V
V
V
Yellow
21
Relay 1
Relay 1
Yellow
22
23
24
Relay 2
Relay 2
A / D
D / A
14
10 V
mA
mA
LP1109 21
CONFIGURATION / OPERATING THE FUNCTION KEYS
Documentation for routing diagram.
In general:
When configuring the IAMS devices, you will be guided through all parameters
and you can choose the settings which fit the application. For each menu there
is a scrolling help text which is automatically shown in line 3 on the display.
Configuration is carried out by using the 3 function keys:
1 will increase the numerical value or choose the next parameter
2will decrease the numerical value or choose the previous parameter
3will accept the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0.
See the reference diagram on page 28.
Pressing and holding
state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state
(1.0) without saving the changed values or parameters.
Further explanations:
Fast setpoint adjustment and relay test: These menus allow you to make a
quick setpoint change and relay test when the FastSet menu is activated. This
function can only be activated when the relays are set for setpoint function
and are controlled by a setpoint.
Pressing
1 and 2 simultaneously will activate a relay test and change the state
of the relay.
Pressing
3 will save the setpoint change.
Holding down 3 for more than 1 second will return the unit to the default state
without saving the setpoint change.
Password protection: Programming access can be blocked by assigning a
password. The password is saved in the transmitter in order to ensure a high
degree of protection against unauthorised modifications to the configuration.
Default password 2008 allows acces to all configuration menus.
3 will return to the previous menu or return to the default
22LP1109
Signal and sensor error info via display front PGMMOD00
Sensor error (see limits in the table) is displayed as SE.BR (sensor break) or SE.SH
(sensor short). Signals outside the selected range (not sensor error, see table
for limits) are displayed as IN.LO indicating low input signal or IN.HI indicating
high input signal. The error indication is displayed in line 3 as text and at the
same time the backlight flashes. Line 4 of the display is a status line which
displays status of relay 1 and relay 2, COM (flashing bullet) indicating correct
functioning of PGMMOD00 and arrow up/down which indicates tendency
readout of the input signal. If the figure 1 or figure 2 flashes, the unit has
detected that the setpoint has been exceeded and that the relay is in “delay”
mode. When the delay time has passed and the relay makes/breakes, the relay
sign either displays or disappears.
Signal and sensor error indication without display front
Status of the unit can also be read from the red/green LED in the front of the device.
Green flashing LED 13 Hz indicates normal operation.
Green flashing LED 1 Hz indicates sensor error.
Steady green LED indicates internal error.
Steady red LED indicates fatal error.
Relay functions
6 different settings of relay function can be selected.
Setpoint: The unit works as a single limit switch
Window: The relay has a window that is defined by a low and a high
Error function: The relay is activated by sensor error.
Power: The relay is activated as long as the power is on.
Off: The relay is deactivated.
Latch: The relay is latched. Only valid for setpoint and window
Increasing/decreasing: The relays can be set to activate at increasing or
decreasing input signal.
Delay: An ON and an OFF delay can be set on both relays in the range
0...3600 s.
Hysteresis: 0.0...100.0%.
setpoint. On both sides of the window the relay has the
same status.
function.
LP1109 23
Latch
When the setpoint is exceeded the relay outputs enter an alarm state. The latch
function of the IAMS0022 and IAMS0020 will hold the relays in this state until
the function is deactivated manually. The latch function can be applied when
the relay function setpoint or window is selected.
The latch function can be selected separately for each relay output. If the
configuration is copied from one device to another by way of the PGMMOD00,
the latch function must be reconfigured.
The latch function activates and holds the relays when the input signal rises
above or falls below the selected setpoints and the relay action has been
selected as increasing or decreasing.
The window function is selected by choosing ”window” in the menu and defining
a high and a low setpoint.
It can be selected for each relay contact whether the contact is open or closed
inside the window. This selection is made in the menu R1.cont and R2.cont.
The setpoint function is selected by choosing ”setpoint” in the menu and entering
the desired limit. The device then works as a single limit switch.
An activated relay means that the contact is closed if the contact function
”normally open” is selected, and the contact is open if the contact function
”normally closed” is selected.
The delay time for activation and deactivation can be set independently of each
other in the menus ON.DEL and OFF DEL respectively.
If the relay function ”Error” is active, the relay will latch when a sensor error
occurs and will not be deactivated automatically when the sensor error is
rectified.
The relay can only be deactivated by an operator and only when the normal
conditions for deactivation are met. If the input signal still has a value that will
activate the relay, the relay will latch again.
See the graphic depiction of the setpoint and window functions on pages 36, 37
and 38.
24LP1109
Manual deactivation of the latch function
If the relay outputs are activated and thereby latched, it will be indicated in
the display. The backlight flashes and the scrolling help text tells you how to
deactivate the output. Manual deactivation is carried out by way of the front
buttons on the PGMMOD00. Use 1 and 2to navigate in the menu and 3
to validate your selection. If the password protection has been activated, the
password must be entered in order to access the deactivation menu. See the
menu structure on page 33.
Advanced functions
The unit gives access to a number of advanced functions which can be reached
by answering “Yes” to the point “adv.set”.
Display setup: Here you can adjust the brightness contrast and the backlight.
Setup of TAG number with 6 alphanumerics. Selection of functional readout
in line 3 of the display - choose between readout of analogue output or TAG
number.
Two-point process calibration: The unit can be process-calibrated in 2 points to
fit a given input signal. A low input signal (not necessarily 0%) is applied and
the actual value is entered via PGMMOD00. Then a high signal (not necessarily
100%) is applied and the actual value is entered via PGMMOD00. If you accept
to use the calibration, the unit will work according to this new adjustment. If
you later reject this menu point or choose another type of input signal the unit
will return to factory calibration.
Process simulation function: If you say ”yes” to the point “EN.SIM” it is possible
to simulate an input signal by means of the arrow keys and thus control the
output signal up or down. When you finalise the point with 3, the unit returns
to normal mode.The point REL.SIM allows you to activate relay 1 and relay 2 by
means of the arrow-keys up/down. You must exit the menu by pressing 3 (no
time-out).
Password: Here you can choose a password between 0000 and 9999 in order to
protect the unit against unauthorised modifications to the configuration. The
unit is delivered default without password. If you have locked the device with
a password by mistake, you can always open the menu by using the master
password 2008.
Language: In the menu ”lang.setup” you can choose between 7 different
language versions of help texts that will appear in the menu. You can choose
between UK, DE, FR, IT, ES, SE and DK.
LP1109 25
Auto diagnosis
The unit performs an advanced auto diagnosis of the internal circuits.
The following possible errors can by display in the front unit PGMMOD00.
CJ.ER - CJC sensor defect or CJC temperature outside range
FL.ER - Flash error
AO.ER - No load on the current output (only for S4...20 mA/S20...4 mA)
NO.CO - Connection error
IN.ER - Error levels on input
TY.ER - Configuration in PGMMOD00 does not match this product type
26LP1109
Selection of units
After choosing the input signal type you can choose the process units which will
be displayed in text line 2 (see table). By selection of temperature input the
process value is always displayed in Celsius or Fahrenheit. This is selected in
the menu point after selection of temperature input.
Safety readback
When the device is delivered with default configuration, the SIL function is
disabled. The safety readback function (loop surveillance) can be selected
in the menu O.RANGE, thus enabling the device to run in SIL mode. In order
to enable the SIL functionality, the menu item S4...20 mA must be selected.
Please note, however, that when safety readback is enabled, a sensor error will
be indicated as an error on the analogue output signal.
Memory
In the memory menu you can save the configuration of the device in the
PGMMOD00, and then move the PGMMOD00 onto another device of the same
type and download the configuration in the new device.
LP1109 27
Power up
1 2
50.0
12.0
1.0
1 2
1.2
1 2
3
%
0000
9999
1 2
3
0000
PASSW.
Txt 1
50.0
RELAY1
Txt 57
75.0
RELAY2
Txt 57
NO
YES
1 2
NO
ADV.SET
Txt 2
3
3
3
VOLT
IN TYPE
Txt 3
1.1
1.0 = Default state Line 1
shows input signal.
Line 2 shows UNIT.
By pressing 1 and
2 simultaneously line 3
alternates between
A.Out and TAG.
Line 4 shows relay and
communication status.
1.1 = Only if password-
protected.
1.2 = Only if FastSet is acti-
vated and the relay
function is setpoint.
1.3 = Not valid for these input
signals: 0...20 mA and
voltage.
1.4 = Only if input signal is
temperature.
1.5 = The relay can only be
deactivated by an ope-
rator and only if the
normal conditions for
deactivation are met.
If the input signal still
has a value that will
activate the relay, the
relay will latch again.
ADV.SET
YES
Txt 2
CURR
IN TYPE
Txt 3
POTM
IN TYPE
Txt 3
LIN.R
IN TYPE
Txt 3
TEMP
IN TYPE
Txt 3
Continued on the page
Routing diagram ADV.SET
3
28LP1109
Fast setpoint adjustment
and relay test
1 Increase setpoint
2 Decrease setpoint
3 Save and exit the menu
1 and 2 simultaneously = change relay state
If no key is activated for 1 minute, the display will return to the default
state 1.0 without saving configuration changes.
1 Increase value / choose next parameter
2 Decrease value / choose previous parameter
3 Accept the chosen value and proceed to the next menu
Hold 3 Back to previous menu / return to menu 1.0 without saving
Availability of output parameters are model number dependent.
SETP
WIND
ERR
3
999.9
-199.9
1 2
100.0
DISP.HI
Txt 14
3
DISP
PERC
1 2
PERC
REL.UN
Txt 15
3
POW
OFF
1 2
SETP
R1.FUNC
Txt 19
3
N.O.
N.C.
1 2
N.O.
R1.CONT
Txt 20
100.0
0.0
1 2
3
50.0
R1.SETP
Txt 21
3
INCR
ACT.DIR
Txt 22
INCR
DECR
1 2
100.0
0.0
1 2
3
1.0
R1.HYST
Txt 23
3
O.I.W
C.I.W
1 2
3
@C
@F
%
A
bar
cm
ft
ft/h
ft/s
g
gal/h
GW
O.I.W
R1.CONT
Txt 27
3
OPEN
ERR.ACT
Txt 34
3
3
UNITS:
CLOS
OPEN
1 2
WIND
R1.FUNC
Txt 19
1.3
ERR
R1.FUNC
Txt 19
3
3
@C
@F
1 2
@C
UNIT
Txt 9
R1.FUNC
R1.FUNC
Selectable
3
POW
Txt 19
OFF
Txt 19
3
ft/min
3
gal/min
3
3
hp
hPa
Hz
in
in/h
in/min
in/s
ips
K
kA
kg
kJ
kPa
kV
100.0
0.0
1 2
60.0
SETP.LO
Txt 29
m3/min
100.0
0.0
1 2
3
70.0
SETP.HI
Txt 28
3
Continued on the next page
kW
kWh
l
l/h
l/min
l/s
m
m/h
m/min
m/s
m/s2
m3
m3/h
mA
mbar
mils
min
mm
mm/s
mol
MPa
mV
MW
MWh
N
Ohm
Pa
100.0
0.0
1 2
1.0
R1.HYST
Txt 30
3
pH
rpm
s
S
t
t/h
uA
um
uS
V
W
Wh
yd
[blank]
LP1109 29
HOLD
CLOS
OPEN
NONE
1 2
NONE
ERR.ACT
Txt 24
1.3
HOLD
CLOS
OPEN
NONE
1 2
NONE
ERR.ACT
Txt 31
1.3
SETP
WIND
ERR
3
3
POW
OFF
1 2
SETP
R2.FUNC
Txt 19
WIND
R2.FUNC
Txt 19
1.3
ERR
R2.FUNC
Txt 19
POW
R2.FUNC
Txt 19
OFF
3
3
3
3
3
N.O.
N.C.
1 2
N.O.
R2.CONT
Txt 20
O.I.W
C.I.W
1 2
O.I.W
R2.CONT
Txt 27
CLOS
OPEN
1 2
OPEN
ERR.ACT
Txt 34
3
3
3
100.0
0.0
1 2
50.0
R2.SETP
Txt 21
100.0
0.0
1 2
60.0
SETP.LO
Txt 29
3
3
INCR
DECR
1 2
INCR
ACT.DIR
Txt 22
100.0
0.0
1 2
70.0
SETP.HI
Txt 28
3
3
100.0
0.0
1 2
1.0
R2.HYST
Txt 23
100.0
0.0
1 2
1.0
R2.HYST
Txt 30
3600
0000
1 2
3
0
ON.DEL
Txt 25
3600
0000
1 2
3
0
ON.DEL
Txt 32
3
3
3600
0000
1 2
0
OFF.DEL
Txt 26
3600
0000
1 2
0
OFF.DEL
Txt 33
30LP1109
3
3
HOLD
CLOS
OPEN
NONE
1 2
NONE
ERR.ACT
Txt 24
1.3
HOLD
CLOS
OPEN
NONE
1 2
NONE
ERR.ACT
Txt 31
1.3
S20-4
20-4
20-0
S4-20
3
3
4-20
0-20
1 2
4-20
O.RANGE
Txt 37
10-2
10-0
5-1
5-0
1-0.2
1-0
2-10
0-10
1-5
0-5
0.2-1
0-1
1 2
0-10
O.RANGE
Txt 39
3600
0000
1 2
3
0
ON.DEL
Txt 25
3600
0000
1 2
3
0
ON.DEL
Txt 32
3
3
3600
0000
1 2
0
OFF.DEL
Txt 26
3600
0000
1 2
0
OFF.DEL
Txt 33
3
3
VOLT
CURR
1 2
CURR
ANA.OUT
Txt 36
VOLT
ANA.OUT
Txt 36
3
3
23mA
0/3.5mA
NONE
1 2
23mA
OUT.ERR
Txt 38
1.3
850
-200
1 2
3
0.0
OUT.LO
Txt 41
1.4 1.4
To default
state 1.0
3
850
-200
1 2
150.0
OUT.HI
Txt 42
3
LP1109 31
MEM
DISP
CAL
SIM
PASS
LANG
1 2
MEM
SETUP
Txt 43
DISP
SETUP
Txt 43
CAL
SETUP
Txt 43
SIM
SETUP
Txt 43
PASS
SETUP
Txt 43
LANG
SETUP
Txt 43
LATC
SETUP
Txt 43
SAVE
LOAD
1 2
3
SAVE
MEMORY
Txt 44
9
0
1 2
3
3
CONTRA
Txt 45
YES
NO
1 2
3
YES
CAL.LO
Txt 49
YES
NO
1 2
3
YES
EN.SIM
Txt 51
2.0
YES
NO
1 2
33
YES
EN.PASS
Txt 54
DE, DK,
ES, FR,
IT, SE,
UK
1 2
3
UK
LANGUA
Txt 59
YES
NO
1 2
3
NO
R1.LATC
Txt 64
ROUTING DIAGRAM
Advanced settings (ADV.SET)
2.0 In the submenu simulation (SIM) you must
press 3 to return to the default state 1.0.
3
3
3
3
3
3
Txt 46
Txt 61
NO
25.0
Txt 52
NO
0000
NEW.PAS
Txt 55
NO
R2.LATC
Txt 64
9
0
1 2
9
LIGHT
100.0
0.0
1 2
2.0
%
100.0
0.0
1 2
%
9999
0000
1 2
YES
NO
1 2
NO
3
3
3
3
33
9
A
1 2
VALVE 5
Txt 47
YES
NO
1 2
YES
CAL.HI
Txt 50
REL.SIM
Txt 53
YES
NO
1 2
YES
EN.FAST
Txt 56
3
100.0
0.0
1 2
3
NO
90.0
%
Txt 62
3
3
3
YES
NO
1 2
3
YES
USE.CAL
Txt 60
To default state 1.0
32LP1109
Manual deactivation of the latch function
To setup menu
40.0
Rx.LATC
Txt 65
R1 reset
40.0
R1.LATC
Txt 65
3
3
ROUTING DIAGRAM
YES
NO
1 2
NO
ENT.SET
Txt 67
1
3
0000
9999
1 2
0000
PASSW
Txt 1
1.1 1.4
3
40.0
R1.LATC
Txt 65
3
YES
NO
1 2
NO
R1.RLSE
Txt 66
3
To default state 1.0
R2 reset
40.0
R2.LATC
Txt 65
3
40.0
R2.LATC
Txt 65
2
0000
9999
1 2
0000
PASSW
Txt 1
1.1
3
YES
NO
1 2
NO
R2.RLSE
Txt 66
1.4
3
LP1109 33
[01] Set correct password[19] Select OFF function - relay is permanently off
SCROLLING HELP TEXT IN DISPLAY LINE 3
[02] Enter advanced setup menu?Select POWER function - relay indicates power status OK
[03] Select temperature inputSelect ERROR function - relay indicates sensor error only
Select potentiometer inputSelect SETPOINT function - relay controlled by 1 setpoint
Select linear resistance input[20] Select Normally Closed contact
Select current inputSelect Normally Open contact
Select voltage input[21] Set relay setpoint
[04] Select 0.0-1 V input range[22] Activate relay on decreasing signal
Select 0.2-1 V input rangeActivate relay on increasing signal
Select 0-5 V input range[23] Set relay hysteresis
Select 1-5 V input range[24] No error action - undefined status at error
Select 0-10 V input rangeOpen relay contact at error
Select 2-10 V input rangeClose relay contact at error
[05] Select 0-20 mA input rangeHold relay status at error
Select 0-20 mA input range[25] Set relay ON delay in seconds
[06] Select 2-wire sensor connection[26] Set relay OFF delay in seconds
Select 3-wire sensor connection[27] Relay contact is Closed Inside Window
Select 4-wire sensor connectionRelay contact is Open Inside Window
[07] Set resistance value low[28] Set relay window setpoint high
[08] Set resistance value high[29] Set relay window setpoint low
[09] Select Celsius as temperature unit[30] Set relay window hysteresis
Select Fahrenheit as temperature unit[31] No error action - undefined status at error
[10] Select TC sensor typeOpen relay contact at error
Select Ni sensor typeClose relay contact at error
Select Pt sensor typeHold relay status at error
Select Cu sensor type[32] Set relay ON delay in seconds
[11] Select display unit[33] Set relay OFF delay in seconds
[12] Select decimal point position[34] Open relay contact at error
[13] Set display range lowClose relay contact at error
[14] Set display range high[36] Select current as analogue output type
[16] Select Pt10 as sensor typeSelect voltage as analogue output type
Select Pt20 as sensor type[37] Select 0-20 mA output range
Select Pt50 as sensor typeSelect 4-20 mA output range
Select Pt100 as sensor typeSelect S4-20 mA with safety readback
Select Pt200 as sensor typeSelect 20-0 mA output range
Select Pt250 as sensor typeSelect 20-4 mA output range
Select Pt300 as sensor typeSelect S20-4 mA with safety readback
Select Pt400 as sensor type[38] Select no error action - output undefined at error
Select Pt500 as sensor typeSelect downscale at error
Select Pt1000 as sensor typeSelect NAMUR NE43 downscale at error
[17] Select Ni50 as sensor typeSelect NAMUR NE43 upscale at error
Select Ni100 as sensor type[39] Select 0.0-1 V output range
Select Ni120 as sensor typeSelect 0.2-1 V output range
Select Ni1000 as sensor typeSelect 0-5 V output range
[18] Select TC-B as sensor typeSelect 1-5 V output range
Select TC-E as sensor typeSelect 0-10 V output range
Select TC-J as sensor typeSelect 2-10 V output range
Select TC-K as sensor typeSelect 1-0.0 V output range
Select TC-L as sensor typeSelect 1-0.2 V output range
Select TC-N as sensor typeSelect 5-0 V output range
Select TC-R as sensor typeSelect 5-1 V output range
Select TC-S as sensor typeSelect 10-0 V output range
Select TC-T as sensor typeSelect 10-2 V output range
Select TC-U as sensor type[41] Set temperature for analogue output low
Select TC-W3 as sensor type[42] Set temperature for analogue output high
Select TC-W5 as sensor type
Select TC-Lr as sensor type
34LP1109
[43] Enter password setup
Enter simulation mode
Perform process calibration
Enter display setup
Perform memory operations
[44] Load saved configuration into IAMS0002
Save IAMS0002 configuration in PGM
[45] Adjust LCD contrast
[46] Adjust LCD backlight
[47] Write a 6-character device TAG
[48] Analogue output value is shown in dis-
play line 3
Device TAG is shown in display line 3
[49] Calibrate input low to process value?
[50] Calibrate input high to process value?
[51] Enable simulation mode?
[52] Set the input simulation value
[54] Enable password protection?
[55] Set new password
[59] Select language
[60] Use process calibration values?
[61] Set value for low calibration point
[62] Set value for high calibration point
[63] Select CJC connector (accessory)
Select internal temperature sensor
[64] Enable relay latch function?
[65] Relay is latched - press 3 to acknowledge
Relay 1 is latched - press 1 to release
Relay 2 is latched - press 2 to release
Relays are latched - press 1 or 2 tor relea-
se relay 1 or relay 2
[66] Release relay? (if conditions allow)
[67] Enter setup menu? (latched relays may
release!)
[69] Select Cu10 as sensor type
Select Cu20 as sensor type
Select Cu50 as sensor type
Select Cu100 as sensor type
LP1109 35
Graphic depiction of latch function setpoint
Input
signal
Setpoint
(increasing)
Hysteresis
Closed
Relay contact
(N.O.)
Open
Release not possible (setpoint still exceeded)
Release not possible (setpoint-hysteresis still exceeded)
Release not possible (OFF delay still exceeded)
Release possible (manual deactivation)
ON delay
Relay latched
OFF delay
Time
36LP1109
Graphic depiction of latch function window
Time
ON delayOFF delay
Window
ON delayOFF- delay
Relay latched
Relay latched
Hysteresis
Open
Closed
Setpoint low
Setpoint high
Relay contact (N.O.)
Hysteresis
LP1109 37
Release possible
Release not possible (inside hysteresis)
Release not possible (still inside window)
Release not possible (OFF delay still active)
Graphic depiction of relay action setpoint
100
90
80
70
60
50
40
30
20
10
0 10 20 30 40 50 60 70 80 90 100
Relay action: IncreasingRelay action: Decreasing
Setpoint = 50
Hysteresis = 10
O N.O.O N.O.On N.O.
On N.C.On N.C.
O N.C.
t
Relay unitsRelay units
100
90
80
70
60
50
40
30
O N.O.O N.O.On N.O.
20
On N.C.On N.C.
10
0 10 20 30 40 50 60 70 80 90 100
Graphic depiction of relay action window
100
Relay units
90
80
70
60
50
40
30
20
10
0 10 20 30 40 50 60 70 80 90 100
Relay function: Window (shown for increasing signal)
Contact: Closed inside window =
Contact: Open inside window =
Hysteresis = 5
Setpoint High = 60
Setpoint Low = 40
Hysteresis = 5
11
OOO
22
1
2
OnOnOn
100
Relay units
90
80
70
60
50
40
30
20
10
t
0 10 20 30 40 50 60 70 80 90 100
Relay function: Window (shown for decreasing signal)
Contact: Closed inside window =
Contact: Open inside window =
Hysteresis = 10
Setpoint = 50
O N.C.
Hysteresis = 5
Setpoint High = 60
Setpoint Low = 40
Hysteresis = 5
11
OOO
22
1
2
t
OnOnOn
t
38LP1109
Ordering information
DESCRIPTIONPART NUMBER
Universal transmitter with analog outputIAMS0002
Universal transmitter with analog output / 2 relaysIAMS0022
Universal trip amplifier / 2 relaysIAMS0020
Display / programming modulePGMMOD00
Display/Comms Module - Modbus RTU protocol
interface over RS-485
LP1109 39
PGMMODC1
40LP1109
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.