Red Lion IAMS Data Sheet

GENERAL DESCRIPTION
The IAMS3535 Smart Analog to MODBUS Conditioner with Alarms module accepts a wide range of DC analog process signals. There are eighteen different DC analog input ranges which determine the input span and type. The input accepts a maximum of 110 VDC and 110 mA DC.
The IAMS converts an analog input signal into a register format that can be read using ASCII or RTU MODBUS protocol. With the features of gain and offset, the input signal can be scaled to meet process requirements. Additionally, two setpoint values can be entered for dual relay process monitoring alarms.
The IAMS is programmed with Windows
®
based SFIMS software. The software allows configuration, calibration, and storage of IAMS program files. Additionally, all setup parameters can be interrogated and modified through MODBUS register and coil commands.
The RS485 port allows the IAMS to be multidropped, with Baud rates up to
38400. The CBPRO007 programming cable converts the RS232 port of a PC to RS485, and is terminated with an RJ-11 connector. The bidirectional capability of the CBPRO007 allows it to be used as a permanent interface cable as well as a programming cable.
The IAMS’s two Form A relay alarms can be configured independently for absolute high or low acting with balanced or unbalanced hysteresis. Alarm 2 can also be configured for deviation and band alarms. In these modes, Setpoint 2 tracks Setpoint 1. Adjustable alarm trip delays can be used for delaying output response. The alarms can be programmed for Automatic or Latching. Latched alarms must be reset via serial command. A standby feature supresses the alarm during power-up until the process stabilizes outside the alarm region. Standby eliminates power-up tripping for low acting alarms. The output relays can also be manually controlled via register commands.
The module’s high density packaging and DIN rail mounting saves time and panel space. The module is equipped with a universal mounting foot for attachment to standard DIN rails, including top hat (T) profile or G profile rail.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
ORDERING INFORMATION
SPECIFICATIONS
1. POWER: 18 to 36 VDC, 3.0 W max. or 24 VAC, ± 10%, 50/60 Hz, 4 VA max.
2. INPUT DC RANGES:
0-20 mV, 0-50 mV, 0-100 mV, 0-200 mV, 0-500 mV, 0-1V, 0-2 V, 0-5 V,
0-10 V, 0-20 V, 0-50 V, 0-100 V, 0-2 mA, 0-5 mA, 0-10 mA, 0-20 mA,
0-50 mA, 0-100 mA
3. MAX. INPUT SIGNAL:
Current Input: 110 mA DC
Voltage Inputs: Terminal 7: 1 VDC +10%
Terminal 8: 10 VDC +10% Terminal 9: 100 VDC +10%
4. INPUT RESISTANCE:
Current: 10 Ohms
Voltage: greater than 100 K
5. INPUT PROTECTION: Surge suppressor diode
Current Terminal: Protected to 110 mA DC max., 1.1 VDC.
100 V Terminal: Protected to 110 VDC.
1 V & 10 V Terminal: Protected to 100 VDC for one minute.
6. INPUT COMMON MODE REJECTION: 50/60 Hz, 110 dB min.
7. ISOLATION LEVEL: 1.5 kV @ 50/60 Hz, 1 min. between input, RS485
and power supply. 2300 Vrms, 1 min. to relay contacts.
1
z ANALOG TO MODBUS CONVERSION
z 18 DIFFERENT DC ANALOG INPUT RANGES
z PROCESSOR BASED SCALING
z PC CONFIGURATION SOFTWARE
z DUAL SETPOINT RELAY ALARMS
z FOUR WAY SIGNAL ISOLATION
MODEL IAMS - INTELLIGENT ANALOG TO MODBUS CONDITIONER W/ ALARMS
IAMS
DESCRIPTION
Smart Analog to Modbus Conditioner w/Alarms
PART NUMBER
IAMS3535
CBPRO
SFIMS
Programming Interface Cable
PC Configuration Software for Windows
CBPRO007
SFIMS
-
CBJ
RJ11 to Terminal Adapter
Cable RJ11 to Unterminated 7 foot length
DRRJ11T6
CBJ11A07
Cable RJ11 to RJ11 6 inch jumper CBJ11BD5
DIMENSIONS In inches (mm)
CAUTION: Risk of Danger
Read complete instructions prior to
installationand operation of the unit.
CAUTION: Risk of electric shock.
UL Recognized Component, File # E179259
MODEL NO.
2
8. SERIAL COMMUNICATIONS: Type: RS485, MODBUS RTU and ASCII modes Baud: 300, 600, 1200, 2400, 4800, 9600, 19.2K, and 38.4K Format: 7/8 bit, odd, even and no parity Transmit Delay: Programmable. (See Transmit Delay explanation in Step 6) Transmit Enable (TXEN): (primarily for 20 mA loop converter) V
OH
= 10 VDC max. VOL= 0.5 VDC @ 5 mA max. current limit
9. A/D CONVERTER: 16 bit resolution
10. ACCURACY (including linearity): 0.1% of span
11. RESOLUTION: 0.002% of span
12. GAIN / OFFSET: Programmable
13. RELAY OUTPUTS:
Type: 2 Form A N.O. contacts Rating: 5A @ 30 VDC or 250 VAC max. (resistive)
1/10 HP @ 120 VAC (inductive) Response Time: 155 msec. max. to close including step response, 153 msec. max. to open.
14. OUTPUT ON DELAY TIME: Programmable from 0 to 32000 sec, ±0.01% - 1 sec. max.
15. MEMORY: Nonvolatile E2PROM retains all programmable parameters.
16. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -20 to +65 °C Storage Temperature Range: -40 to +85 °C Operating and Storage Humidity: 85% max. relative humidity (non­condensing) from -20 to +65 °C Temperature Coefficient: +0.01%/ °C (100 PPM °C) max. Altitude: Up to 2000 meters
17. CERTIFICATIONS AND COMPLIANCE: SAFETY
UL Recognized Component, File # E179259, UL3101-1, CSA 22.2 No. 1010-1
Recognized to U.S. and Canadian requirements under the Component Recognition Program of Underwriters Laboratories, Inc.
IECEE CB Scheme Test Certificate # US/5141A/UL,
CB Scheme Test Report # 01ME11540-0702001
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. This device was designed for installation in an enclosure. To avoid
electrostatic discharge to the module in environments with static levels above 6 KV, precautions should be taken when the device is mounted outside an enclosure. When working in an enclosure (ex. making connections, etc.), typical anti-static precautions should be observed before touching the module.
Refer to the EMC Installation Guidelines section of this bulletin for
additional information.
18. CONSTRUCTION: Case body is black high impact plastic. Installation Category II, Pollution Degree 2.
19. CONNECTIONS: 14 AWG max.
20. MOUNTING: Universal mounting foot for attachment to standard DIN
style mounting rails, including top hat (T) profile rail according to EN50022
- 35 x 7.5 and - 35 x 15, and G profile rail according to EN50035 - G32.
21. WEIGHT: 4.5 oz. (127.57 g)
MODULE ISOLATION
The IAMS features “4-way” signal isolation. The 4-way isolation is a
combination of optical, transformer and relay barriers, providing common mode voltage (CMV) isolation to 1.5 KV for 1 minute between input, RS485, and power supply. Isolation between relay contacts and all other inputs is 2300 Vrms for 1 minute.
LED FUNCTIONALITY
Power mains class A
Enclosure class AEN 55011RF interference
Emissions to EN 55011
Level 3; 10 V/mENV 50204Simulation of cordless telephone
150 KHz - 80 MHz
Level 3; 10 V/rms EN 61000-4-6RF conducted interference
Level 3; 2 KV power
Level 4; 2 KV I/O EN 61000-4-4Fast transients (burst)
80 MHz - 1 GHz
Level 3; 10 V/MEN 61000-4-3Electromagnetic RF fields
Level 3; 8 KV air
1
Level 2; 4 KV contact EN 61000-4-2Electrostatic discharge
200 Hz, 50% duty cycle
Immunity to EN 50082-2
900 MHz ± 5 MHz
CONDITION GREEN LED 2 RED LEDS
Power Applied On ——— Communication Received Flashing ——— Respective Alarm ——— On Checksum error Flashing Flashing Calibration Off On
BLOCK DIAGRAM
3
WIRING CONNECTIONS
All conductors should meet voltage and current ratings for each terminal. Also, cabling should conform to appropriate standards of good installation, local codes and regulations. When wiring the module, use the numbers on the label to identify the position number with the proper function. Strip the wire, leaving approximately 1/4" (6 mm) of bare wire exposed. Insert the wire into the terminal, and tighten the screw until the wire is clamped tightly. (Pull wire to verify tightness.) Each terminal can accept up to one #14 AWG (2.55 mm), two #18 AWG (1.02 mm), or four #20 AWG (0.61 mm) wires.
MODULE POWER CONNECTIONS
Module power is connected to terminals 1 and 2. For best results, the power should be relatively “clean” and within the specified limits. Drawing power from heavily loaded circuits or from circuits that also power loads that cycle on and off should be avoided. It is recommended that power supplied to the module be protected by a fuse or circuit breaker.
INPUT CONNECTIONS
Current Input
Wiring for a current input is connected to terminals 10 (+) and 12 (-).
Terminal 10 (+): 100 mA
Voltage Input
Wiring for a voltage input is connected to terminal 12 (-) and one of the voltage terminals listed below.
Terminal 7 (+): 1 VDC max.
Terminal 8 (+): 10 VDC max.
Terminal 9 (+): 100 VDC max.
RELAY OUTPUT CONNECTIONS
There are two Form A output relays. The wiring for Relay 1 is connected between terminals 5 and 6. The wiring for Relay 2 is connected between terminals 3 and 4.
To prolong contact life and suppress electrical noise interference due to the switching of inductive loads, it is good installation practice to install a snubber across the contactor. Follow the manufacturer’s instructions for installation.
Note: Snubber leakage current can cause some high impedance loads to be
held ON.
DEFAULT SERIAL SETTING CONNECTION
If the IAMS settings are unknown, or forgotten, they can be reset to the factory defaults by connecting the Serial Default terminal 11 to Input Comm. terminal 12 with a jumper, and then cycling power.
DEFAULTS:
RS485 SERIAL CONNECTIONS
There are two RJ-11 connectors located on the bottom for paralleling communications. For single device communications, either connector can be used. When used in conjunction with Red Lion Control Paradigm HMI products, reverse A+ and B- wiring.
RJ11 IAMS
1 Not used
2B-
3A+
4 COMM
5 TXEN
6
2345
Not used
IAMS CONNECTOR
STEP 1 WIRING THE MODULE
Protocol: RTU
Address: 247
Baud Rate: 9600
Data Bits:
Parity:8none
Although this unit is designed with a high degree of immunity to Electro­Magnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into the unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation.
Listed below are some EMC guidelines for successful installation in an industrial environment.
1. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the rail where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
c. Connect the shield to common of the unit and leave the other end of the
shield unconnected and insulated from earth ground.
2. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
3. Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.
4. In extremely high EMI environments, the use of external EMI suppression devices, such as ferrite suppression cores, is effective. Install them on Signal and Control cables as close to the unit as possible. Loop the cable through the core several times or use multiple cores on each cable for additional protection. Install line filters on the power input cable to the unit to suppress power line interference. Install them near the power entry point of the enclosure. The following EMI suppression devices (or equivalent) are recommended: Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC # FCOR0000) TDK # ZCAT3035-1330A Steward # 28B2029-0A0 Line Filters for input power cables: Schaffner # FN610-1/07 (RLC # LFIL0000) Schaffner # FN670-1.8/07 Corcom # 1 VR3
Note: Reference manufacturer’s instructions when installing a line filter.
5. Long cable runs are more susceptible to EMI pickup than short cable runs. Therefore, keep cable runs as short as possible.
EMC INSTALLATION GUIDELINES
4
STEP 4 PROGRAMMING THE INPUT
The IAMS receives an analog input, converts it to a raw digital value, and stores this number in the ADC Value (register 40001). This number is scaled into engineering units using the Gain Value (register 40010) and Offset Value (register 40011). The result of this scaling is stored as the Process Value (register 40002). It is also stored in the IEEE 754 Standard 32-bit floating decimal format (register 40003 and 40004). The non-scaled ADC, the scaled Process value, or the Floating point value may be accessed for the purpose of monitoring the input level.
INPUT SIGNAL
ADC READING
Register 40001
INTERNAL
MATH
GAIN/OFFSET
PROCESS
VALUE
IEEE STANDARD 754
FLOATING DECIMAL POINT
LO Order Byte
HI Order Byte
Register 40003 Register 40004
Register 40002
Register 40010/40011
Input Range: Select the desired input range from the pull down menu.
Gain & Offset: The Gain & Offset values are used to scale the input signal into
engineering units. The result is stored in the Process Value register. To determine the Gain and Offset for your application, use the Scaling Wizard button.
STEP 3 PROGRAMMING - Getting Started
Run RLCPro by double-clicking the icon, or use the start menu.
Use the FILE pull-down menu
to select a NEW file.
You will be prompted to
select the proper device,
and then the model.
STEP 2 INSTALLING SFIMS
(Software for Intelligent Modules)
Insert the SFIMS diskette into the A: or B: drive. Then Run A:\SETUP (or B:\SETUP) to install RLCPro onto the hard drive. An icon labeled RLCPro will be created under the group RLCPro.
5
Filter Response: The Filter Response is a time constant, in tenth of second increments, that is used
to stabilize an erratic input. The Process value stabilizes to 99% of the final value within approximately 5 time constants. A value of ‘0’ disables digital filtering.
Filter Band: Filter Band is a value expressed in Process units. When a fluctuating signal remains
within the band value, the Digital Filter is active, and therefore stabilizes the Process Value. When a fluctuating signal exceeds the Filter Band value, the Digital Filter is momentarily disabled to allow for a quick response to valid process changes. Once the signal variation is less than the Filter Band value, the Digital Filter is reactivated.
The Scaling Wizard prompts you to enter four values. Simply key in the Minimum and Maximum signal Input Values, and the desired Process Value equivalents. Press the Next button to calculate the new Gain and Offset values.
Note: The Process Values must be between –32000 and +32000. (negative values will be
transmitted as 2’s complement)
Once the Next key is pressed, the software will display the new Gain and Offset values. It will also display the exact Process Value result for your input signal. The Process values may be different than those previously entered due to the resolution of the Gain and Offset values. Press the Accept button to have the Gain and Offset values entered into the Input Setup screen. When a download is performed, the Gain and Offset values are written to registers 40010 and 40011 respectively.
STEP 5 PROGRAMMING THE ALARMS
Action: Alarm 1 can be programmed for 5 modes of operation, Alarm 2 has 8 possible modes.
Manual: In Manual mode, the Alarms are forced on and off by writing ‘0’ or ‘1’ to the appropriate
MODBUS register (Alarm 1 state = 40024, Alarm 2 state = 40025).
Absolute HI: (with balanced or unbalanced hysteresis) The Alarm energizes when the Process exceeds the
Setpoint Limit Value.
Absolute LO: (with balanced or unbalanced hysteresis) The Alarm energizes when the Process falls below
the Setpoint Limit Value.
Deviation HI, Deviation LO, Band Outside: In these modes, Alarm 2 “tracks” Alarm/Setpoint 1. (See
Setpoint ALarm Figures below.)
Setpoint: The Alarm setpoint, entered in scaled Process units.
Hysteresis: Hysteresis is used to eliminate output chatter. The Hysteresis Amount is the difference between
the points that an Alarm will “turn on” and “turn off”. In Unbalanced modes, the alarm turns on at the Setpoint, and turns off at Setpoint-HYS for HI alarms, and Setpoint+HYS for LO alarms. In Balanced modes, the Hysteresis is evenly divided above and below the Setpoint value. (See the Setpoint Alarm Figures below) The software calculates the hysteresis percentage and displays it for you.
Note: The Setpoint, along with the Hysteresis, MUST NOT produce a “trip point” higher than 32,000, or
less than -32,000. (See the Setpoint Alarm Figures below)
Reset: The alarms can be programmed for Latched or Automatic. In Automatic mode, an energized alarm
turns off by itself once the Process leaves the alarm area. In Latched mode, an energized alarm requires a serial reset. This is done by writing a ‘0’ to the appropriate MODBUS register. (Alarm 1 state = 40024, Alarm 2 state = 40025)
On Delay: The time, in whole second increments, that the alarm will take to energize when the Process
Value crosses into an alarm state area.
Enable Standby Delay: Standby prevents nuisance (typically low level) alarms after a power up. After
powering up the unit, the Process must stabilize outside the alarm region. Once this has occurred, the standby is disabled, and the alarm responds normally until the next module power up.
Loading...
+ 9 hidden pages