Red Lion IAMA User Manual

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL IAMA - UNIVERSAL SIGNAL CONDITIONING MODULE
3-WAY ISOLATION OF ANALOG SIGNALS
UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS
SELECTED VIA DIP SWITCH SETTINGS
OVER 100 INPUT AND OUTPUT ANALOG CONVERSION
COMBINATIONS
CHOOSE LINEAR OR SQUARE ROOT EXTRACTION MODEL
ALL RANGES ARE FACTORY PRECALIBRATED. CUSTOM FIELD
11 to 36 VDC AND 24 VAC MODULE POWER
UL Recognized Component, File # E179259
Bulletin No. IAMA-J
Drawing No. LP0413
Released 12/13
GENERAL DESCRIPTION
The IAMA – Universal Signal Conditioning Module Series can isolate and convert over 100 combinations of analog signal ranges. The IAMA3535 converts and transmits signals linearly proportional to the input, while the IAMA6262 transmits the scaled square root of the input signal. This allows the IAMA6262 to provide a signal that is linear to flow rate in applications utilizing a differential pressure transducer.
DIP switch range selection eliminates the need to order and stock different modules for each input and output signal range, and allows quick and convenient setup for over 100 standard signal conversions. By utilizing the Field mode of calibration, the user can customize the input and output scaling for odd applications, including reversal of the output relative to the input.
In addition to the conversion capabilities, the IAMA modules feature optically isolated Input/Output signal circuits and transformer isolated Power to Input, Power to Output circuits.
The modules’ overall full scale accuracy typically exceed 0.05% depending upon range selection and scaling. The microprocessor based design provides ease of field scaling and the onboard E2PROM stores scaling values for future recall. Both models come factory precalibrated for all input and output ranges. Factory or custom field scaling can be selected by a simple mode switch change. The IAMA can be factory recalibrated in the field if desired.
The modules’ environmental operating temperature range is -20°C to +65°C. DIN rail mounting saves time and panel space. The units are equipped with universal mounting feet for attachment to standard DIN style rails, including top hat profile rail according to EN50022 - 35x7.5 and 35 x 15 and G profile rail according to EN50035-G32.
DIMENSIONS In inches (mm)
MC2279X
ON
DIP SWITCH SETTINGS:
ON = 1
OFF = 0
0-100mA
0-50mA
0-20mA
4-20mA
0-10mA
0-5mA
0-2mA
000
111
1
1
000
0
0
111
0
0
1 000
10
10
11
11
0101010
(79.2)
I
IN
10
11 12
INPUT
COMM
3
2
1
OUT FIELD/FACT.
IN FIELD/FACT.
0-100V
0-1mA
0-50V
0-20V
000
111
1
1
0
000
10
10 0
1
3.12
1V
879
*
100V
10V
6
OUTPUT RANGE
0-10V
0-5V
1-5V
000
0
1 0
001
11
010
101
0-2V
0
11
STATUS
*
01100-1V 0
I
OUT+
546
V
V
OUT+
OUT-
98754
INPUT RANGE
0-200mV
0-500mV
0-100mV
000
000
0
0
1
1
1 0
0
1
I
OUT-
213
VDC+
10
20mA/1mA OUTPUT
0-50mV
0-20mV
0
0
0
000
0
1
VDC-
11-36VDC
RED LION CONTROLS
YORK, PA.
MODEL IAMA
MADE IN U.S.A.
0-20mA
4-20mA
0-1mA
0-10V
INPUT
0-5V
6
000
7
0
00
8
1
1
0
0
0010090
1
1
10
OUTPUT
SWITCH 1
34
5
4.20 REF
(106.7)
1.08
(27.5)
IAMA
MC2290C
S T A T U S
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
CAUTION: Risk of Danger.
Read complete instructions prior
to installation and operation of the unit.
CAUTION: Risk of electric shock.
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBER
Linear Universal Signal Conditioning Module IAMA3535
IAMA
Square Root Universal Signal Conditioning Module IAMA6262
SPECIFICATIONS
1. POWER: 11 to 36 VDC, 3 W max. or 24 VAC, ±10%, 50/60 Hz, 4.8 VA max.
2. INPUT/OUTPUT RANGES: See Tables 2 and 3
3. ZERO/SPAN ADJUSTMENTS: Digital (DIP Switch Transition)
4. MAX INPUT SIGNAL:
Current Input: 110 mA DC, 1.1 VDC
Voltage Inputs: Terminal 7- 1 VDC +10%
Terminal 8- 10 VDC +10%
5. INPUT RESISTANCE:
6. INPUT PROTECTION: Surge suppressor diodes
7. OUTPUT: Self-powered (Active)
8. MAX OUTPUT CURRENT:
9. LOAD RESISTANCE:
10. OUTPUT COMPLIANCE:
11. ISOLATION LEVEL INPUT TO OUTPUT: 1.5 kV @ 50/60 Hz, 1 min
12. STEP RESPONSE: To within 99% of full scale: 300 msec
Terminal 9- 100 VDC +10%
Current: 10
Voltage: > 100 K
Current Output: 22 mA
Voltage Output: 10 mA
Current Output: 600
Voltage Output: 1 K
Current: 4 to 20 mA, 0 to 20 mA: 12 V min ( 600 Ω)
0 to 1 mA: 10 V min (10 KΩ)
Voltage: 10 VDC across a min. 1 KΩ load (10 mA). Factory calibrated for
loads of > 1 MΩ.
1
13. ACCURACY (INCLUDING LINEARITY): Factory: ±0.1% of span
OUT+
max. for all ranges except 1 mA, 2 mA, and 20 mV. These ranges are accurate to ±0.2% of span max. All ranges can be field calibrated to 0.1% of span max.
14. RESOLUTION: 0.01% full scale input, 0.01% full scale output
15. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -20 to +65 °C Storage Temperature Range: -40 to +85 °C Operating and Storage Humidity: 85% max. relative humidity (non-
condensing) from -20 to +65 °C
Temperature Coefficient: ± 0.01%/°C (100 PPM/°C) max. Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g. Shock to IEC 68-2-27: Operational 30 g Altitude: Up to 2000 meters
16. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A IEC/EN 61010-1
UL Recognized Component: File #E179259
Refer to EMC Installation Guidelines section of this bulletin for additional
information.
17. CONSTRUCTION: Case body is black high impact plastic
18. CONNECTIONS: 14 AWG max
19. MOUNTING: Standard DIN top hat (T) profile rail according to EN50022
- 35x7.5 and 35 x 15 and G profile rail according to EN50035-G32.
20. WEIGHT: 4.5 oz. (127.57 g)
IAMA is received from the factory. Therefore, until the IAMA is field scaled, factory and field modes perform identically. See SCALING PROCEDURE for detailed instructions on field programming the IAMA.
The units can be scaled to any minimum scale and full scale values within the extent of the selected range. The closer together the minimum and full scale values are to each other, the less accurate the signal will be. For example, if the 0 to 1 V input range is selected, and the unit is scaled for 0 to 0.5 V, the signal has the same resolution as the 0 to 1 V range. Since this resolution will be two times the percentage of span for 0.5 V, more accuracy can be achieved by using the 0 to 0.5 V range.
The input may exceed the full scale value for the selected range by 10% of span, but the IAMA will not update the output beyond 10% over range.
The red and green LED’s indicate the status of the modules during scaling and normal operation. Table 1, LED Indications, details the LED indications for various unit conditions.
The IAMA – Signal Conditioning Module Series is designed for use in industrial environments. Suppressor diodes protect both input and output circuits from wiring errors and transient high voltage conditions.
INPUTS
The IAMAs accept a full range of process signal inputs and isolate and convert these signals to common industrial control signals. The input signal combinations are configured by making specific DIP switch selections on the 10 position DIP switch.
BLOCK DIAGRAM
V
*
IN
I
IN
INPUT
COMMON
DC+ (AC)
DC- (AC)
* Terminal number is dependent on max. input voltage.
VARIABLE
10
GAIN
12
AMP
3
POWER
SUPPLY
2
V/F
CONVERTER
PROCESS CIRCUITY
PWM
CIRCUITRY
6
V
5
V
OUT-
4
I
OUT+
1
I
OUT-
MODULE ISOLATION
IAMA modules feature “3-Way” Signal Isolation. The 3-Way isolation is a combination of optical and transformer isolation. The optical isolation provides common mode voltage (CMV) isolation up to 1.5 kV between the sensor input and the process signal output. The IAMA’s power is isolated from the sensor signal input and the process signal output by a DC/DC transformer isolation circuit.
OVERVIEW
The IAMA3535 continuously monitors a voltage or current input and provides a linearly proportional voltage or current output, while the IAMA6262 transmits the scaled square root of the input signal. This allows the IAMA6262 to provide a signal that is linear to flow rate in applications utilizing a differential pressure transducer. Both units have two modes of operation known as Factory and Field modes. Factory mode is used when the default input and output ranges are suitable. Field mode can be independently selected for both the input and output, and allows the user to custom calibrate, or scale the signal. If Factory mode is selected, the IAMAs use factory presets for the selected input or output range. If Field mode is selected, the IAMAs can be custom scaled within a selected input or output range. Field mode also allows the IAMA to reverse its output in relation to its input.
The units are factory precalibrated for minimum and full scale for all input and output ranges. The factory calibration values are permanently stored in E2PROM and should not be changed in the field, unless unacceptable error or a factory checksum error occurs. See Factory Recalibration for details. Field scaling is achieved by applying minimum and full scale values from a calibration source and storing the values by a single DIP switch transition. Field scaling is available for all input and output ranges and the values are permanently stored in E2PROM until reprogramming occurs.
After field scaling, the IAMAs can be changed between Factory and Field modes for a particular range, which restores the respective setting. The Factory and Field E2PROM locations contain the same calibration values when the
OUTPUTS
As with the input choices, the process signal output of the modules is DIP switch selectable. A 1 position DIP switch is used to select between the 1 mA/20 mA output ranges. The maximum output current signal is 22 mA with ≤600 Ω output resistance and the maximum output voltage signal is 11 V with 1 K output resistance.
ZERO AND SPAN
The input zero and span are set by first applying the minimum value then transitioning S1-2 to store that value. Next, the full scale value is applied and the DIP switch transition stores the value. The output scaling is performed in a similar manner but the output is driven to the desired minimum and full scale values by the calibration source applied to the input. S1-1 is used to store the minimum and full scale output values.
The span is defined by: span = (full scale - minimum scale).
ILLEGAL RANGE SELECTIONS AND CHANGES
The ranges should only be selected before power is applied. If an invalid input or output range is selected when power is applied the output is set to approximately 0 VDC and the red LED indicates the error according to Table 1. Power must be removed and valid ranges selected for the IAMA to operate properly.
If S1 switches 3 through 10 are changed while the IAMA is operating, the red LED indicates a range change according to Table 1, LED Indications and the output goes to the previously stored range minimum scale value. Normal operation will be resumed if the switches are placed back in the previous positions or power is removed and restored.
CHECKSUM ERRORS
A checksum is performed every time power is applied to the IAMA. If a checksum error occurs, the LEDs will indicate where the error occurred according to Table 1, LED Indications. Operation with a checksum error is not recommended but can be done in critical situations. If an error occurs, re-calibration of the field or factory ranges to be used must be performed.
If a field checksum error occurs, the IAMA will operate only in factory mode. If a factory checksum occurs, the IAMA will operate only in a previously calibrated field mode. Do not perform a field scaling until the factory checksum is cleared. Since a checksum error is a high priority LED indication, the LEDs will indicate the error until it is cleared. This will exclude other LED information.
2
TABLE 1, LED INDICATIONS
CONDITION GREEN LED RED LED
Normal Operation On Off
Scaling Mode Alternate with Red Alternate with Green
Under Range Off Slow Flash (0.8 sec rate)
Over Range Off Fast Flash (0.4 sec rate)
Invalid Range Off On
Illegal Range Change Off On
Factory Checksum Off On, short off
Field Checksum On, short off Off
User Factory Calibration Fast Flash for 2 sec Off
GETTING STARTED
One method for the Input (1 or 2 below) should be configured, and one
method for the Output (3 or 4 below) should be configured.
1. FACTORY preprogrammed settings for the Input, see Section 1.0
2. FIELD scaling method for the Input, see Section 2.0
3. FACTORY preprogrammed setting for the Output, see Section 3.0
4. FIELD scaling method for the Output, see Section 4.0
Note: The ranges should only be changed while power is removed from the IAMA.
TABLE 2, OUTPUT RANGE SETTINGS
OUTPUT
RANGE
VOLTAGE
OUTPUTS
CURRENT OUTPUTS
Note: DIP switch settings 0 = OFF 1 = ON
0 - 5 V
0 - 10 V
0 - 1 mA
4 - 20 mA
0 - 20 mA
RANGE DIP
SWITCHES
3 4 5
0 0 0 0 0 1 0 1 0 0 1 1 1 0 0
TABLE 3, INPUT RANGE SETTINGS
RANGE
0 - 20 mV
0 - 50 mV
0 - 100 mV
0 - 200 mV
0 - 500 mV
INPUT
VOLTAGE
INPUT
CURRENT
Note: DIP switch settings 0 = OFF 1 = ON
0 - 1 V
0 - 2 V
1 - 5 V
0 - 5 V
0 - 10 V
0 - 20 V
0 - 50 V
0 - 100 V
0 - 1 mA
0 - 2 mA
0 - 5 mA
0 - 10 mA
4 - 20 mA
0 - 20 mA
0 - 50 mA
0 - 100 mA
RANGE DIP SWITCHES
6 7 8 9 10
0 0 0 0 0 0 0 0 0 1 0 0 0 1 0 0 0 0 1 1 0 0 1 0 0 0 0 1 0 1 0 0 1 1 0 0 0 1 1 1 0 1 0 0 0 0 1 0 0 1 0 1 0 1 0 0 1 0 1 1 0 1 1 0 0 0 1 1 0 1 0 1 1 1 0 0 1 1 1 1 1 0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0
FIELD OR FACTORY MODE SELECTION
SELECTING FIELD MODE (2 Methods):
1. Scale the input or output according to SCALING PROCEDURE 2.0 or 4.0
2. Before applying power, set the input or output (or both) field/factory switch to the up (field) position. Field calibration values will be restored upon power-up. If the IAMA has not been previously field calibrated, the E2PROM will contain the factory calibration values which will be restored.
SELECTING FACTORY MODE (2 Methods):
1. Before applying power to the IAMA set the input or output (or both) field/ factory switch to the down (factory) position. Factory calibration values will
be restored upon power-up.
2. While power is applied to the IAMA and it is operating in the field input and/ or output mode, set the desired field/factory switch(s) to the down (factory) position. The factory calibration values will be restored.
EMC INSTALLATION GUIDELINES
Although Red Lion Controls Products are designed with a high degree of
immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into a unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMI guidelines for a successful installation in an industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly connected to protective earth.
2. Use shielded cables for all Signal and Control inputs. The shield connection should be made as short as possible. The connection point for the shield depends somewhat upon the application. Listed below are the recommended methods of connecting the shield, in order of their effectiveness. a. Connect the shield to earth ground (protective earth) at one end where the
unit is mounted.
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is over 1 MHz.
3. Never run Signal or Control cables in the same conduit or raceway with AC power lines, conductors, feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run through metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter. Also, Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.
4. Long cable runs are more susceptible to EMI pickup than short cable runs.
5. In extremely high EMI environments, the use of external EMI suppression devices such as Ferrite Suppression Cores for signal and control cables is effective. The following EMI suppression devices (or equivalent) are recommended:
Fair-Rite part number 0443167251 (RLC part number FCOR0000) Line Filters for input power cables:
Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)
6. To protect relay contacts that control inductive loads and to minimize radiated and conducted noise (EMI), some type of contact protection network is normally installed across the load, the contacts or both. The most effective location is across the load. a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide
varistor (MOV) across an AC inductive load is very effective at reducing EMI and increasing relay contact life.
b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor
switch, care must be taken not to exceed the breakdown voltage of the transistor when the load is switched. One of the most effective ways is to place a diode across the inductive load. Most RLC products with solid state outputs have internal zener diode protection. However external diode protection at the load is always a good design practice to limit EMI. Although the use of a snubber or varistor could be used. RLC part numbers: Snubber: SNUB0000 Varistor: ILS11500 or ILS23000
7. Care should be taken when connecting input and output devices to the instrument. When a separate input and output common is provided, they should not be mixed. Therefore a sensor common should NOT be connected to an output common. This would cause EMI on the sensitive input common, which could affect the instrument’s operation.
Visit RLC’s web site at http://www.redlion.net/Support/InstallationConsiderations.
html for more information on EMI guidelines, Safety and CE issues as they relate to Red Lion Controls products.
WIRING CONNECTIONS
All conductors should meet voltage and current ratings for each terminal.
Also cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that power supplied to the unit be protected by a fuse or circuit breaker. When wiring the unit, use the numbers on the label to identify the position number with the proper function. Strip the wire, leaving approximately 1/4" (6 mm) of bare wire exposed. Insert the wire into the terminal, and tighten the screw until the wire is clamped tightly.
3
Loading...
+ 5 hidden pages