Red Lion GEMINI 42 User Manual

THE ASTRO LINE SERIES
GEMINI 4000 INSTRUCTION MANUAL
INTRODUCTION
The Gemini 4100 and 4200 are both units in a multi-purpose series of industrial control units that are field-programmable to solve multiple applications. This series, known as the Astro-Line family of products, is built around the concept that the end user has the capability to program different personalities and functions into the unit in order to adapt to different indication and control requirements.
The Gemini, which you have purchased, has the same high quality workmanship and advanced technological capabilities that have made Red Lion Controls the leader in today's industrial market.
Red Lion Controls has a complete line of industrial indication and control equipment, and we look forward to being of service to you now and in the future.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
TABLE OF CONTENTS
I. GENERAL DESCRIPTION 2
A) Safety Summary B) Programming The Gemini C) Programming The Personality D) Programming The Presets, Scale Factors, Timed Outputs & Counter Load Values E) Initial Factory Configuration Counter/Rate & Dual Counter Factory Settings F) Operator Accessible Functions With Programming Disabled G) Diagnostics, Self-Test, & “Watchdog” Timer H) Input Circuitry & Set-up I) Overflow Indication
II. PROGRAMMING INSTRUCTIONS FOR THE COUNTER/RATE VERSION OF THE GEMINI
A) Codes 41, 42, 43, 44, 45, & 46, 51, 52, 53, 54, 55, & 56 B) Codes 61, 62, 63, 64, 65, 66, Preset Values, Scale FactorsA&B,Counter Load Value C) Dual Preset Counter & Rate Application
III. PROGRAMMING INSTRUCTIONS FOR THE DUAL COUNTER VERSION OF THE GEMINI
A) Codes 41, 42, 43, 44, 45, & 46 B) Codes 51, 52, 53, 54, 55, & 56 C) Codes 61, 64, 65, 66, Preset Values, Scale FactorsA&B,Counter Load Values E) Dual Counter Batching Application
IV. 20 MA CURRENT LOOP COMMUNICATIONS
A) Communication Format B) Sending Commands & Data To The Gemini C) Receiving Data From The Gemini D) Print Options E) Current Loop Installation F) Communications Application G) Troubleshooting Gemini Serial Communications & Serial Loop-Back Self-Test
V. APPENDIX “A” - INSTALLATION & INPUT CONFIGURATION SWITCH SET-UP VI. APPENDIX “B” - SPECIFICATIONS & DIMENSIONS VII. APPENDIX “C” - TROUBLESHOOTING GUIDE VIII. APPENDIX “D” - COUNTER/RATE & DUAL COUNTER MODE FUNCTION COMMAND CODE SUMMARY 50-57 IX. APPENDIX “E” - SCALING FOR COUNTING X. APPENDIX “F” - SCALING FOR RATE XI. APPENDIX “G” - GEMINI 4100 PROGRAMMING CHARTS XII. APPENDIX “H” - GEMINI 4200 PROGRAMMING CHARTS XIII. APPENDIX “I” - ORDERING INFORMATION
2 3 3
3-5
6 7
7-8
8 8 9
9-14 15-17 18-19
20 20-22 22-25 25-27 28-29
30
30 30-32
32
33
34
35
36 37-45 46-47 48-49
58-59 60-61 62-64 65-69
70
-1-
GENERAL DESCRIPTION
The Gemini 4000 series (4100 & 4200) instruments are two input microprocessor based dual function counter/rate or dual counter instruments. The 6-digit display features 0.56" high LEDs with negative sign, overflow and displayed value indicators (A & B) located to the left of the display. When programmedas a counter/rate instrument, the Aindicator will be onwhen therate is displayed and the B indicator will be on when the count is being displayed. Pushing the “+/-” button toggles the display between the counter and rate or the two counters depending on the personality selected.
The Gemini 4000 series consists of two basic units, a singlepreset version,the Gemini 4100, and a two preset version, the Gemini 4200. Each basic unit is also available in 115/230VAC versions, with orwithout Serial communications and a relay board. The 20 mA current loop option (serial communications) makes possible remote or computerized monitoring or control of the Count, Presets and Scale Factors.
Flexibility and usefulness are insured through user programmability. With simple front panel keystrokes andrear panel switch settings, any one of a number of configurations can be selected. Once the selection is made, all or part of the keyboard can be disabled to protect the settings and guarantee that no unwanted changes can occur during the measurements.
Each time the power is turned off, the unitautomatically saves the settings and data in its special no power memory. When power is restored, the Gemini sets itself back to the operational modes and restores the data it had at power down. The “no power” E being applied to and removed from the unit.
Whenever the power comes on, the Gemini performs a series of internal diagnostics to verify the integrity of the stored data.There isalso a self-test mode and a “watchdog” timer to help prevent processor lockup.
The Gemini 4000 seriescounters can accept bi-directional, uni-directional, or quadrature signals. They also have the capability to double or quadruple (Quadrature x4) the resolution of the incoming count signal. A separate input mode is available to make the counter/rate or dual counters completely independent of each other.
One input provides the signal for rate or a counter and the other input provides the signal for a counter. An anti-coincidence add/subtract mode is also provided to obtain a difference between two input signals.
Each channel features separate scaling and decimal point placement for readout in different units or at different resolutions.
2
PROM’s life expectancy is at least 100,000 cycles of power
A Counter Load feature enables the operator to modify the count value under circumstances that occur when flawed material has been counted and it is necessary to adjust the countvalue accordingly. The Counter Loadfeature can be “locked out” in applications where it is not required.
The Rate Indicator portion uses a time interval method (1/tau) to calculate the rate value.This methodenables high resolution at all rates. The unit countsinput pulses and after a programmable minimum update time has occurred, it waits until the next edge occurs, takes the elapsed time and number of edges, and calculates the rate value. At slower rates, averaging can be accomplished by programming the “Rate Minimum Update Time” (0.5 sec. to 16 sec.) for the desired response. Extensive scaling capabilities allow practically any desired reading at very slow count rates.
For maximum flexibility, the Gemini’s output(s) can be assigned to either the rate or count channels or one to each. When in dual counter mode, the output(s) can be assigned to the Counter B channel. For the Gemini 4200, one can be assigned to Counter A and the other to Counter B.
The relay(s) are mounted on a plug-in board which makes it easy to field upgrade your Gemini. Thecontacts are ratedfor 240 VAC or28 VDC at 5amps.
The construction of the Gemini features a metal, die cast bezel for maximum durability with high quality appearance. The sealed front panel meets NEMA 4/IP65 specifications for washdown and/or dust, when properly installed. Electrical connections are made with removable, plug-in terminal strips at the rear of the unit. Clamp-type pressure plate terminals accept stripped #14 AWG wire without lugs.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not usethis unit to directly command motors, valves,or otheractuators not equipped with safeguards. To do so, can be potentially harmful to persons or equipment in the event of a fault to the unit.
-2-
PROGRAMMING THE GEMINI
When your Gemini arrives from the factory, it has already been programmed to function as a counter and rate indicator. It is programmed with the factory settings listed in the “Initial Factory Configuration” section. If it is required to have the unit operate as two counters, the Unit Personality function code can be changedtodoso.
The personality, functions, and modes are accessed by pressing the appropriate keys. A function is defined by a two-digit code which appears on the left sideof the display. Themode of that function is shown asa one-digit code on theright side of the display. At times there will be a “-” sign modifier to the left of the mode.
Data for the Presets, Scale Factors, Timed Output Values, and Counter Load Values are entered differently. Each digit key controls the digit on the display directly aboveit. Changing the digits can be done by repeatedly pressing the key beneath the digit position you wish tochange orby holding the key down. Asyou hold it down, or repetitively press it, the valueof thatdigit willchange cyclically, counting up to 9, thento 0, and then upagain. The 6 numberedkeys correspond to the six digits, and the “+/-” key corresponds to polarity.
PROGRAMMING THE PERSONALITY
Entering function and mode is easily accomplished by pressing theappropriate digitkey. Forthe personality function, you would enter 41 by pressing the front panel keys 4 and 1.
The digits on the left side of the display show thefunction code; the digits on the right side show the current programmed mode.
A mode selection is made by entering a new number. On some of the entries, you have the option of a plus “+” or minus “-” sign. In the cases where a “+” sign is required, no sign will be displayed. If you do enter a “-” sign (using the “+/-” key), a minus sign will be displayed in front of the appropriate digit.
Pressing the “E” key finalizes the change. The display will now show the count or rate value immediately.
If you do not press the “E” key, the change will not be recorded. The display will remain in the programming mode for 15 seconds, and then return to normal operating mode using the old functional mode setting.
Whenever the Unit Personality is changed, the factory settings will automatically be loaded into the unit. The factory settings can also be programmed into the unit bycalling upthe UnitPersonality, puttinga “-” in front of the mode by pushing the “+/-” button, and entering it.
Refer to the “Initial Factory Configuration” section for more details.
PROGRAMMING THE PRESET, SCALE FACTORS, TIMED OUTPUTS & COUNTER LOAD VALUES
The Presets and Scale Factor Values are commonly reprogrammed on a daily basis. As such, single keystroke access has been provided.
The Gemini has two Scale Factors, one for display A (Counter A or Rate A), and one for display B (Counter B). Pressing the “3” key will call up the Scale Factor for the current display (Rate A/Counter A, or Counter B).
To call up the “other” Scale Factor, the “+/-” key is first pushed to change the display to the“other” value,then the “3” key ispushed to display the ScaleFactor for that value.
-3-
PROGRAMMING THE PRESET, SCALE FACTORS, TIMED OUTPUTS & COUNTER LOAD VALUES (Cont’d)
The new value will be entered when the “E” key is pressed.
Once the Scale Factor is displayed, changing the digits can beaccomplished byrepeatedly pressingthe keybeneath the digit position you wish to change or by holding the key down, allowing the digit to cycle.
The new value will be entered when the “E” key is pressed.
The internal count value is multiplied by the Scale Factor Value, which changes the displayed value accordingly. It is important tonote thatthe precision of an application cannot beimproved by using a ScaleFactor greater than one.To accomplish greater precision, more pulse information must be generated per measuring unit. For example, if 5 pulses are being received per foot of material, the precision of 10th of feet cannot be attained by simply programming a Scale Factor of 2.0000, even though the display is reading in tenths. In this case, the display will increment by two for each count input. Thus, if an odd Preset Value is entered, such as 6.7 ft., the Gemini will alter the Preset display to read in even tenths of feet.
To display the Preset 1 Value the “1” key is pushed.
To change the value, the digits can be cycled through in the same manner as discussed for the Scale Factor. The preset values can range from -999999 to +999999.
The ScaleFactor Value will have a direct effect on the preset being entered (if assigned to the counter). For Scale Factors greater than one, the preset value should be an integer multiple of the Scale Factor. If it is not, the Gemini will automatically adjust the presetvalue up or down to force it to be evenly divisible by the Scale Factor.
The Timed Output 1 or 2 Value is changed by entering a two-digit function code. After the code is entered, the display will show the present Timed Output Value in seconds with two decimal place resolution. The Timed Output Values can be set from .01 to 599.99 seconds.
To change the Timed Output 1 Value, enter function code 53 and enter the new value by holding down or repeatedly pressing the keybelow the digit position youwish to change. The new value will be entered when the “E” key is pressed. The display will immediately return to the count value.
Note: ATimed Output Value of zero cannot be programmed into the Gemini.If a
value of 0 is entered into the display and the “E” key is pressed, the unit will
remain in data entry mode.If a new value isnot entered, it will time outand the
unit will continue to use its previous setting.
As with the other functions, you mustpress “E” to record the changes. For the data entrymodes, if you do not press the“E” key, a time out of 5seconds occurs, and the display returns to operating mode without any changes to the value. The only time any change will occur is when the “E” key is pressed.
-4-
It is possible to change the counter values of the Gemini. This feature can be enabled or disabled by the programming of the “Operator Accessible Functions Modes”, function code 66. The “Counter LoadValue” isnot stored when the unit is powered down. When the unit is powered up, the Counter Load values for both counters (if Dual counterpersonality) are resetto zero.Once changed,the values will be held until the unit is again powered down.
To accessthe Counter Load valuefor thedesired counter; first, press the “+/-” key, if necessary, so that the display is indicating the counter value which is to be changed.
Secondly, press the “E” key and while holding it down, press the “+/-” key.
The Gemini will now display the displayed Counter Load value. (It will be zero, unless the value had been changed since the unit was powered up.)
To change the value, press the key under the digit to be changed as explained previously for the Preset.
To load the value into the counter, press the “E” key.
The display will flash momentarily and will display the counter with the new value.
-5-
INITIAL FACTORY CONFIGURATION DUAL COUNTER FACTORY SETTINGS*
Keys struck Display Description
4,1 41 1 Personality selected as COUNTER/RATE 4,2 42 3 Reset Rate (A) Output(s) & Counter (B) 4,3 43 1 Count with Inhibit 4,4 44 1 Single edge counting (B) 4,5 45 1 Counter B Scale multiplier of 1.0 4,6 46 1 Counter B leading zero blanking and no decimal point 5,1 51 2 Outputs 1 & 2 assigned to Counter (B) 5,2 52 3 Output 1 terminates at Reset, Normal Phase 5,3 0000.10 Timed Output 1 Value of 0.1 Sec 5,4 54 3 Output 2 terminates at Reset, Normal Phase 5,5 0000.10 Timed Output 2 Value of 0.1 Sec 5,6 56 1 Counter (B), manual reset to zero 6,1 61 4 No Rate (A) right hand dummy zeros 6,2 62 1 Rate per Second 6,3 63 1 Rate (A) 0.5 Sec Minimum Update Time 6,4 64 4 Rate (A) Scale multiplier of 1 6,5 65 1 Rate (A) leading zero blanking, no decimal point 6,6 66 1 No functions except Reset enabled
3 01.0000 Scale Factor A (Rate) set to 1.0000 3 01.0000 Scale Factor B (Counter) set to 1.0000 1 000500 Preset 1 set to 500 2 001000 Preset 2 set to 1000
Keys struck Display Description
4,1 41 2 Personality selected as DUAL COUNTER 4,2 42 3 Reset Counters A & B 4,3 43 1 Count with Inhibit 4,4 44 1 Single edge counting (A & B) 4,5 45 1 Counter B Scale multiplier of 1.0 4,6 46 1 Counter B leading zero blanking and no decimal point 5,1 51 2 Outputs 1 & 2 assigned to Counter B 5,2 52 3 Output 1 terminates at Reset, Normal Phase. 5,3 0000.10 Timed Output 1 Value of 0.1 Sec 5,4 54 3 Output 2 terminates at Reset, Normal Phase. 5,5 0000.10 Timed Output 2 Value of 0.1 Sec 5,6 56 1 Counter B, manual reset to zero 6,1 61 1 Counter A, manual reset to zero 6,4 64 1 Counter A scale multiplier of 1 6,5 65 1 Counter A leading zero blanking, no decimal point 6,6 66 1 No functions except Reset enabled
3 01.0000 Scale Factor A set to 1.0000 3 01.0000 Scale Factor B set to 1.0000 1 000500 Preset 1 set to 500 2 001000 Preset 2 set to 1000
* If [41 1] is changed to [41 2], then the factory settings are as shown.
-6-
OPERATOR ACCESSIBLE FUNCTIONS WITH PROGRAMMING DISABLED
(For details on keyboard entry, see preceding section)
One of the important features of the Gemini is the ability to disable programming. With this ability, accidental bumping of the keys or tampering by unauthorized personnel can be prevented. However, it may be necessary to allow reset and certain programming functions, such as Presetand Scale Factor Values, to be changed in daily operation. The Gemini, through the use of the “Operator Accessible Functions” Modes can enable these functions even when the “PGM. DIS.” (Program Disable) terminal is connected to “COMMON”.
The “Operator Accessible Functions” modes are programmed by entering a two-digit function code (66) and the desired mode. Unlike other function codes, the mode does not take effect immediately. The “PGM. DIS.” terminal must be connected to “COMMON” in order for the Gemini to disable programming and operate as per the mode programmed.
There are six basic “Operator Accessible Functions” Modes available. These modes enable the following functions.
1. NO FUNCTIONS EXCEPT RESET ENABLED - In this mode, manual
reset is enabled, but none of the programming functions can be changed.
However, the functions can be interrogated.
2. PRESET PROGRAMMING AND RESET ENABLED - Theentirefront
panel is disabled with the exceptions of Preset programmability and manual
reset. All functions can be interrogated.
3. SCALE FACTOR PROGRAMMING AND RESET ENABLED - The
entire front panel is disabled with the exceptions of Scale Factor
programmability and manual reset. All functions can be interrogated.
4. SCALE FACTOR AND PRESET PROGRAMMING, AND RESET
ENABLED - The entire front panel is disabled with the exceptions of Scale
Factor and Preset programmability, and manual reset. All functions can be
interrogated.
5. PRESET AND COUNTER LOAD PROGRAMMING, AND RESET
ENABLED - The entire front panel is disabled with the exceptions of Preset
and Counter Load programmability. All functions can be interrogated.
6. PRESET,SCALE FACTOR AND COUNTER LOADPROGRAMMING, AND RESET ENABLED - The entire front panel is disabled with the exceptions of Preset, Scale Factor and Counter Load programmability. All functions can be interrogated.
All of these modes can be modified with the addition of a “-” sign. The minus
sign disables the manual reset, at the front panel and the remote reset (RST., not RST.A) terminal, at the rear of the unit.
There is also a rearpanel DIP switch whichpermits disabling of the frontpanel
reset button. This is independent of the rear terminal remote reset, and can be used in conjunction with any front panel disable mode. The combination of a manual and remote reset inputs provides a high level of security without sacrificing flexibility.
DIAGNOSTICS, SELF-TEST, & “WATCHDOG” TIMER
The security of the Gemini is further enhanced by its self-test diagnostic and
“watchdog” timer capabilities.
The diagnostics are concerned with the special, no power memory of the
Gemini. Whenever the power is turned off, all pertinent function settings and measurements (except the Counter Load values) are automatically saved. When power is restored, the functions and data are re-instated. This allows you to program the unit once and not have to re-program it until you wish to use it in another mode.
When the function codes and data are saved, computations are made with
these values. Theresult ofthese computations is storedin thememory to serve as a check against possible error. On power up the same computations are repeated on the stored data. If the results do not agree with the stored results, a “P” will appear onthe leftside of the display. If this occurs, refer to the “Troubleshooting Guide” for directions.
-7-
DIAGNOSTICS, SELF-TEST, & “WATCHDOG” TIMER [Cont’d]
Another error indicator is the “watchdog” timer. In order to insure the software is functioning properly, the program constantly monitors itself. If the proper sequenceand timing of internal events does not occur, an “E” will appear on the left side of the display.If this occurs, refer tothe “TroubleshootingGuide” for directions.
The final type of built-in error checking is the front panel initiated self-test. It can be performed at any time, even when the Gemini is running. It will not interfere with theaccumulation of countsor controlfunctions. Afunction code of “6”, “+/-” starts the test. At this time, whatever was displayedwill disappear and be replaced by a string of decimal points and the overflow indicator. Then the display will showa string of 9’s, then 8’s etc., until a string of0’s are shown. The self-test willthen turn off the overflow indicator and activate the minus “-” sign. Then the unit shows an interlace pattern of -010101, then -212121, followed by 232323 etc., until -898989 is reached. At this time the outputs can be tested by pressing the “1”or “2”key. (Theprogram disable terminal must be disconnected in order to allow activation of the outputs. Also, when testing the output, use caution, so as not to cause any undesirable or hazardous conditions in the system.) An automatic exit will takeplace after six seconds or immediately if the Program Disable terminal is connected to common. Normal length of display time for each of the patterns is approximately 0.5 sec. Rapidly pressing “E” during self-test can speed up the sequence.
INPUT CIRCUITRY & SET-UP
There are two independent input channels on the Gemini. Various types of sensor outputs can be accommodated by appropriate DIP switch set-up. These include: TTL or CMOS logic, current sinking, current sourcing, or dry contact and more.
Channel 1 consists of a logic input and a separate low level magnetic pickup input.
Channel 2 is a completely independent count or control input channel. Like Channel 1, it can be programmed with DIP switches for a wide variety of logic inputs, and is identical to Channel 1 in this regard. For a complete detailed description of input set-up, see Appendix “A”.
OVERFLOW INDICATION
The Gemini features an overflow indicator (LED) which is located to the left of thesixth digit and above the polarity annunciator. This LEDwill turn on if the capacity of the display (6-digits) is exceeded or if the internal count capacity (9-digits) is exceeded. Use of extremely small scale multiplier and Scale Factor Values can cause the internal count capacity to overflow before the displayed value would overflow. It should also be noted that the use of Right Hand Dummy Zeros or Scale Factors larger than one could cause the displayed value to overflow before a value of 999,999 (6-digits) is accumulated.
When the capacity of the display is exceeded, the count value will be maintained and will be valid.But ifthe internal count value is exceeded, thenthis value may no longer be valid.
The overflow LED can also turn on under certain conditions when the rate input frequencyexceeds the maximum 3250 cps allowedfor a rate update period of 16 sec. See Code 63 - “Rate Minimum Update Time”.
-8-
PROGRAMMING INSTRUCTIONS FOR THE COUNTER/RATE VERSION OF THE GEMINI 4000
The first part of this section provides detailed descriptions of the function command codes for inputs response modes, reset modes, output terminations, etc. Then, using an actual application example, the programming instructions for a Counter/Rate version will be “walked through”, to give the user a full understanding of the Gemini programming procedure. The descriptions below give the function command code first, followed by the individual mode identifier. The Function Command Code Summary in the appendix, lists all codes. (Only commands and modes pertaining to the Counter/Rate personality will be discussed in this section.)
CODE 41 - UNIT PERSONALITY
The Gemini can be programmed to operate in one of two different personalities. In each of the two unit personalities,the Gemini operates as a dual function indicator. The personality selected determines whether display channel A will indicate rate or count. In both personalities, display channel B operates as a counter.
When the Unit Personality is changed and entered, all modes and data values (Preset, Scale Factors, function codes etc.) will be automatically loaded with the factory settings for that personality. If, for any reason during programming, it is desired to return to the factory settings (while in code 41), the “+/-” key can be pushed. When the “E” key is pressed the unit will load the factory settings into the Gemini.
The programming procedure willvary for the two unit personalities. This entire section deals with the unit programmed as a Counter/Rate indicator, [41 1].
[41 1] COUNTER(B)/RATE (A)- In thismode, display channelA functionsas
a rate indicator and display channel B functions as a counter. See the
“PROGRAMMING INSTRUCTIONS FOR THE GEMINI 4000” section
for details.
[41 2] DUAL COUNTER - In this mode, both display channels, A & B, function
as counters.
CODE 42 - RESET BUTTON & TERMINAL ACTUATION MODES
The “Reset Button & Terminal Actuation Modes” controls the affect that the reset button and terminal have on the two display channels. Resetting will not affect the rate display in any manner. If the output(s) is assigned to the rate channel, activating the reset button or terminal will reset the rate output(s) if that particular response mode is programmed. Resetting counter (B)will alwaysreset the assigned output(s).
There is a separate “RST. A” terminal, which resets the Rate (A) output when activated (if output(s) is assigned to rate). It is provided to allow independent resetting of each channel.
[42 1] RESET RATE (A) OUTPUT(S) [42 2] RESET COUNTER (B) [42 3] RESET RATE (A) OUTPUT(S) AND COUNTER (B)
CODE 43 - INPUTS1&2RESPONSE MODES
The Gemini has six different input response modes. They are: Count(1) with Inhibit(2); Count(1) with Up/Down Control (2); Two input anticoincidence Add(1)/Subtract(2); Separate Inputmode; Quadrature;and Quadrature x4. In all modes, except [43 4], Input 1 is used by both the counter and rate channels.
[43 1] COUNT WITH INHIBIT- Input 1 serves asthe count and rate input.Input
2 serves as the Inhibit input. When Input 2 is low, the counter will ignore the
count signal appearing at Input1. The rate channel, however, will continue to
indicate the rate of the signal on Input 1.
When Input 2 is ata high level, thesignal appearing on Input 1 willbe counted.
The “Counter (B) Reset Modes” will determine the count direction. In
applications where the Inhibit function is not actually used, the Input 2
“SRC/SNK” position of the “INPUT CONFIGURATION DIP SWITCH”
should be set to the “SNK” position to provide a 7.8 Kohm pull-up resistor.
This will set Input 2 to the Non-Inhibit state.
-9-
CODE 43 - INPUTS1&2RESPONSE MODES [Cont’d]
[43 2] COUNT WITH UP/DOWN CONTROL - In this mode, count direction
can be controlled by thesecond input. Input 1serves as the countand rate input and Input 2 serves as the direction control signal input. When Input 2 is at a high level, thecounter will count up. WhenInput 2 is ata low level, thecounter will count down. The rate is not affected by the directional control Input 2.
[43 3] TWO INPUT ANTI-COINCIDENCE ADD/SUBTRACT - This mode
effectively separates count pulses which may simultaneously appear at the two inputs. The Gemini unit processes the count pulses into a string of time-separated pulses, so the internal counter will not lose any count pulses. Input 1 serves as the add and rate input (count increments) and Input 2 serves as the subtract input (count decrements).
[43 4] SEPARATE INPUT - In this mode, the two functions, Counter (B) and
Rate (A) are independently controlled bythe inputs.Input 1 serves as the Rate (A) input and Input 2 serves as the Counter (B) input.
[43 6] QUADRATURE TIMES 4 - This mode takes the quadrature mode, with
two edge counting, one step further. In quadrature times 4, both Input 1 and
Input 2serve as the count or quadrature input, dependingon their state. In one
instance, Input 1 will serve as the count input and Input 2 will serve as the
quadrature input.In another instance, Input 1 will be the quadrature input and
Input 2 will be the count input. This enables each edge, positive and negative
going, of both inputs, 1 and 2, to be counted. This results in a resolution four
times greater than in the basic quadrature x1 mode. As in the other modes,
Input 1 is also used for the rate input. The rate indicator will only use the
falling edge of the Input 1 signal, due to the method of rate indication used.
CODE 44 - COUNTER (B) NUMBER OF COUNT EDGES
The counter of the Gemini can be programmed for either single or two edge (x2) counting. The number of count edges cannot be set when the count mode is programmed for quadrature x4 operation. The Gemini will ignore any attempt to enter function command code 44 when set for quadrature x4.
[43 5] QUADRATURE COUNTING - Quadrature counting modes are
primarily used inpositioning and anti-jitterapplications. The reason this mode works is due to the manner in which two pickups are positioned relative to each other. The signal on Input 2 is a pulse train signal shifted 90° away from the Input 1signal. These twosignals are processed by theGemini asfollows: Input 1 serves as the count and rate input, while Input 2 serves as the quadrature input. For quadrature with single edge counting, the counter will count ina positive direction when Input 1 is a negative going edgeand Input 2 is ata low level. The counter will count in a negative direction when Input 1 is a positive going edge and Input 2is at a low level. Alltransitions onInput 1 are ignored when Input 2 is at a high level. These logic rules provide the basis for anti-jitter operation which will prevent false counts from occurring due to back-lash, vibration, chatter, etc. When twoedge counting is used, the quadrature mode works the same as with single edge counting when Input 2 is low. But when Input 2 is at a high level, counts at Input 1 are no longer ignored. Instead the logic rules for Input 1 are complemented, allowing both edges of Input 1to becounted. This doubles the effective resolution of the encoded input. The rate indicator will only use the falling edge of the Input 1 signal, due to the method of rate indication used.
[44 1] SINGLEEDGE COUNTING (x1) - The unitcounts onthe negativegoing
(falling) edgeof the count input signal.The count mode descriptions describe
how each mode uses this method of edge counting.
[44 2] TWO EDGE COUNTING (x2) - This mode is used when doubling of the
count signal input is required. The unit counts on the positive going (rising)
edge of the count input signal, as well as, the negative going (falling) edge.
-10-
CODE 45 - COUNTER (B) SCALE MULTIPLIER
There are four Counter B Scale Multipliersthat areavailable. They effectively divide the internal Count B value by 1, 10, 100, and 1000 respectively, to yield the displayed Counter B value. Note: Use of a small scale multiplier in conjunction with a small Scale Factor could cause the internal count value to be exceeded before the 6-digit display value is exceeded. See “Programming the Presets, Scale Factors, Timed Outputs & Counter Load Values” section for more details.
[45 1] x1 [45 2] x0.1 [45 3] x0.01 [45 4] x0.001
CODE 46 - COUNTER (B) DECIMAL POINT & LEADING ZERO BLANKING
There are six basic modes of decimal point placement for the counter of the Gemini. The decimal point is placed to the right of the display digit that corresponds to the mode identifier. (The right most decimal point, digit 1, is never turned on.) A “-” sign in front of the mode identifier will inhibit leading zero blanking. The absence of a “-” sign will enable leading zero blanking.
[46 1] 0 [46 2] 0.0 [46 3] 0.0 0 LEADING ZERO [46 4] 0.0 0 0 BLANKING [46 5] 0.0000 [46 6] 0.00000
[46 -1] 000000 [46 -2] 00000.0 [46 -3] 0 0 0 0.0 0 LEADING ZERO [46 -4] 0 0 0.0 0 0 BLANKING INHIBITED [46 -5] 00.0000 [46 -6] 0.00000
CODE 51 - OUTPUT ASSIGNMENT
The output(s) of the Gemini 4000 can be assigned to either the rate or count channel. Assigning the output(s) to the rate [51 3] will automatically configure the “Counter (B) Reset Mode” to Reset to Zero, [56 1].
The Gemini 4200 has a Preset tracking feature which allows Preset 1 to track Preset 2. If Preset tracking is programmed, whenever the Preset 2 value is changed, the Preset 1 value will also change to maintain the same offset. For example, if Preset 1 is 100 and Preset 2 is 200, changing Preset 2 to 300 will automatically change Preset 1 to 200, maintaining same 100 unit offset. In order to changethe amount of offset, the Preset 1 value is changed.The Preset tracking feature is programmed by adding a “-” modifier in front of the desired mode.
[51 1] OUTPUT 1 ASSIGNED TO RATE (A), OUTPUT 2 TO COUNTER
(Gemini 4200 only)
[51 2] OUTPUTS 1 & 2 ASSIGNED TO COUNTER (B) [51 3] OUTPUTS 1 & 2 ASSIGNED TO RATE (A)
[51 -1] [51 -2] [51 -3]
These modes are identical with the exception that Preset Tracking is enabled.
CODE 52 - OUTPUT 1 TERMINATION MODES
The Gemini has six “Output 1 Termination Modes” which control the way Output 1 will terminate or reset. In all modes, Output 1 will terminate immediately when the channel to which it is assigned is manually reset.
For the Gemini 4200, the Output 1 termination modes 1 & 2 are available only when both outputs are assigned to the Counter (B), [51 2].
A reverse phase mode is available on the Gemini. This refers to the complementing of the logic state of the output. With normal phase operation, when the display value reaches Preset 1, Output 1 will turn on. The reset condition of Output1 isoutput off.In reversephase operation,Output 1turns off when the Preset 1 Valueis reached. The reset condition of Output 1 is output on. (Note: The state of the relay, if used, is also reversed.) A “-” sign in front of the mode identifier will provide for reverse phase operation. The absence of a “-” sign will indicate normal phase operation.
-11-
CODE 52 - OUTPUT 1 TERMINATION MODES (Cont’d)
[52 1] TERMINATE AT OUTPUT 2 START - Output 1 will terminate when
Output 2 starts.Output 1is setfor normal phaseoperation. (Gemini 4200Only)
[52 2] TERMINATE AT OUTPUT 2 END - Output 1 will terminate when
Output 2 ends.Output 1 isset for normalphase operation. (Gemini 4200 Only)
[52 3] TERMINATE AT MANUAL RESET - Output 1 activates when the rate
or count, whichever it is assigned to, is greater than or equal to the Preset 1 Value. Inthis mode,once Output 1 is activated, it does not deactivateuntil the moment a reset occurs. Output 1 is set for normal phase operation.
[52 4] TERMINATE AT MANUAL RESET END - This mode is like the
preceding, except Output 1 deactivates when reset ends. Output 1 is set for normal phase operation.
[52 5] TERMINATE AFTER TIMED OUTPUT 1 - Once Output 1 has been
activated, it will deactivate after the predetermined length of time (code 53) has expired. Manual reset will override the timed output and reset Output 1. Output 1 is set for normal phase operation. When Output 1 alone is assigned to the rate [51 1], the output will activate when therate isgreater than or equal to the Preset 1 Value. When bothoutputs are assigned to Rate [51 3], Output 1 will act as an “underspeed” detect. Itwill activate when the rate is less than or equal to the Preset 1 Value. Output 1 will activate every update time period for which the above conditions are true. If the Timed Output 1 Value, code 53, is greater than the rate update time, the output will appear to belatched on,deactivating when the rate dropsbelow the Preset and the output time expires.
output again deactivates. When Output 1 is assigned to the counter and the
Preset 1 value is changed, Output 1 will immediately go to the proper state.
Upon power up, Output 1,if assigned to CounterB, will“remember” itspower
down boundary condition and go to that state. Output 1 is set for normal
phase operation.
[52 -1] [52 -2] [52 -3] These modes are the same as above with the exception [52 -4] that the output is set for reverse phase operation. [52 -5] [52 -6]
CODE 53 - TIMED OUTPUT 1 VALUE
The Gemini has the capabilityof varying the Timed Output 1 Value from 0.01 second to 599.99 seconds. When the code is entered, instead of a single mode identifier digitbeing displayed, six digits will be shown. Refer to “Programming the Presets, Scale Factors, Timed Outputs & Counter Load Values” section for more details about entering. The timed output will be terminated if the unit is manually reset.
The Timed Output 1 Value is used only when in Timed Output 1 Termination mode, [52 5].
Note: ATimed Output Value of zero cannot be programmed into the Gemini.If a
value of 0 is entered into the display and the “E” key is pressed, the unit will
not enter the 0, but will stay in the data entry mode. If a new value is not
entered, it willtime out and the unitwill continueto use its previoussetting.
[52 6] BOUNDARY MODE - When in boundary mode, the Preset 1 Value
serves as the boundary point. When the display value (count or rate) is less than the Preset 1 Value, Output 1 is not activated (normal phase). When the display value is greater than or equal to the Preset 1 Value, Output 1 is activated. If the display value were to drop below Preset 1, Output 1 would then deactivate.For negative Preset points, Output 1 is not activated when the count value is more positive than the Preset 1 Value. When the count is more negative than (only possible with counter) or equal to Preset 1, Output 1 is activated. If the count becomes more positive than the Preset 1 Value, the
CODE 54 - OUTPUT 2 TERMINATION MODES (GEMINI 4200 Only)
The Gemini 4200 has six “Output 2 Termination Modes” which control the way Output 2 will terminate or reset. In all modes, Output 2 will terminate immediately when the channel to which it is assigned is manually reset.
Output 2 termination modes 1 & 2 are available only when both outputs are assigned to the Counter (B), [51 2].
-12-
A reverse phase mode is available on the Gemini 4200. This refers to the complementing of the logic state of the output. With normal phase operation, when the display value reaches Preset 2, Output 2 will turn on. The reset condition of Output2 isoutput off.In reversephase operation,Output 2turns off when the Preset 2 Valueis reached. The reset condition of Output 2 is output on. (Note: The state of the relay, if used, is also reversed.) A “-” sign in front of the mode identifier will provide for reverse phase operation. The absence of a “-” sign will indicate normal phase operation.
negative than (only possible with counter) or equal to Preset 2, Output 2 is activated. If the count becomes more positive than the Preset 2 Value, the output again deactivates. When Output 2 is assigned to the counter and the Preset 2 value is changed, Output 2 will immediately go to the proper state. Upon power up, Output 2,if assigned to CounterB, will“remember” itspower down boundarycondition andgo to that state. Output 2 is set for normal phase operation. Programming Boundary mode will automatically select [56 1], if [51 1 or 2] is programmed.
[54 1] TERMINATE AT OUTPUT 1 START - Output 2 will terminate when
Output 1 starts. Output 2 is set for normal phase operation.
[54 2] TERMINATE AT OUTPUT 1 END - Output 2 will terminate when
Output 1 ends. Output 2 is set for normal phase operation.
[54 3] TERMINATE AT MANUAL RESET - Output 2 activates when the rate
or count, whichever it is assigned to, is greater than or equal to the Preset 2
Value. Inthis mode,once Output 2 is activated, it does not deactivateuntil the
moment a reset occurs. Output 2 is set for normal phase operation.
[54 4] TERMINATE AT MANUAL RESET END - This mode is like the
preceding, except Output 2 deactivates when reset ends. Output 2 is set for
normal phase operation.
[54 5] TERMINATE AFTER TIMED OUTPUT 2 - Once Output 2 has been
activated, it will deactivate after the predetermined length of time (code
55) has expired. Manualreset will overridethe timed output andreset Output
2. When assigned to count or rate, Output 2 will activate when the display
value is greater than orequal tothe Preset 2 Value. Output 2 is set for normal
phase operation.
[54 6] BOUNDARY MODE - When in boundary mode, the Preset 2 Value
serves as the boundary point. When the display value (count or rate) is less
than the Preset 2 Value, Output 2 is not activated (normal phase). When the
display value is greater than or equal to the Preset 2 Value, Output 2 is
activated. If the display value were to drop below Preset 2, Output 2 would
then deactivate.For negative Preset points, Output 2 is not activated when the
count value is more positive than the Preset 2 Value. When the count is more
[54 -1] [54 -2] [54 -3] These modes are the same as above with the exception [54 -4] that the output is set for reverse phase operation. [54 -5] [54 -6]
CODE 55 - TIMED OUTPUT 2 VALUE (GEMINI 4200 Only)
The Gemini 4200 has thecapability of varying the TimedOutput 2Value from
0.01 second to 599.99 seconds. When the code is entered, instead of a single mode identifier digit being displayed, six digits will be shown. Refer to “Programming the Presets, Scale Factors, Timed Outputs & Counter Load Values” section for more details about entering. The timed output will be terminated if the unit is manually reset.
The Timed Output 2 Value is used only when in Timed Output 2 Termination
mode, [54 5].
Note: A Timed Output Value of zero cannot be programmed into the Gemini
4200. If a value of 0 is entered into thedisplay and the “E” key is pressed, the unit will not enter the 0, but will stay in the data entry mode. If a new value is not entered itwill time out and theunit willcontinue to use itsprevious setting.
-13-
CODE 56 - COUNTER (B) RESET MODES
The Gemini 4000 has six different counter reset modes. There are also two methods by which manual resetcan acton thecounter (reset must be enabled, see function code 66 and dip switch set-up). The first is a “maintained” reset action, where the unit is held at reset for as long as the reset terminal or reset button is activated. The second is a“momentary” reset, in which theunit resets, when reset is activated, and starts counting even though the terminal or resetbutton may still be active. A “-” sign in front of the mode identifier indicates “momentary” reset action, the absence of the “-” sign indicates “maintained” reset action.
For the Gemini 4200, if both outputs are assigned to the Rate Channel [51 3], or the Output 2 Termination modeis boundary[54 6], theonly Counter (B) Reset mode that is available is Reset to Zero [56 1].
In Reset to Zero modes the Output (if assigned to Counter B) activates at the Preset Value. In Reset to Preset modes the Output activates at zero.
In the “Reset to Preset” modes, for proper operation, the counter normally counts down. In the “Count with Inhibit” and “Separate Inputs” input response modes, [43 1 or 4], the unit will automatically count down if a Reset to Preset mode is selected. In the other input response modes, proper input phasing is required for down counting. See “CODE 43 - INPUTS 1 & 2 RESPONSE MODES” section for more details.
[56 3] AUTOMATIC RESET TO ZERO AFTER TIMED OUTPUT - The
counter automatically resets to zero when Timed Output ends. Manual reset is “maintained” and will override automatic reset. The “Output Termination Mode” should be programmed for timed output operation, [54 5], when in this mode.
[56 4] AUTOMATIC RESET TO PRESET AFTER TIMED OUTPUT - The
counter automatically resets to Preset when Timed Output ends. Manual reset is “maintained” and will override automatic reset.
The “Output Termination Mode” should be programmed for timed output
operation, [54 5], when in this mode.
[56 5] AUTOMATIC RESET TO ZERO AT BEGINNING OF TIMED
OUTPUT (AT PRESET) - In this reset mode, the counter will automatically reset to zero at the beginning of Timed Output (at Preset). The Timed Output Value must be shorter than the time required for the counter to count to the Preset Value,otherwise, the Output will appear to be latched on.Manual reset is “maintained” and will override automatic reset. The “Output Termination Mode” should be programmed for timed output operation, [54 5], when in this mode.
Note: The Reset Button & Terminal Actuation Mode must be programmed to
mode [42 2 or 3] in order to be able to manually reset the Counter (B). The
activation and de-activation response time for reset is 10 msec. Note: For the Gemini 4200, all reset to preset modesreset to preset 2 and Timed
Output refers to Output 2.
[56 1] MANUAL RESET TO ZERO (RTZ) - Manual reset to zero is
accomplished by pulling the “RST.” terminal to “COMMON” or, if the front
panel reset is enabled, by pressing the front panel reset button. Reset is
“maintained”.
[56 2] MANUAL RESET TO PRESET (RTP) - Manual reset to Preset is
accomplished by pulling the “RST.” terminal to “COMMON” or, if the front
panel reset is enabled, by pressing the front panel reset button. Reset is
“maintained”.
[56 6] AUTOMATIC RESET TO PRESET AT BEGINNING OF TIMED
OUTPUT (AT ZERO) - Inthis reset mode,the counterwill automaticallyreset to Presetat the beginning of Timed Output (at zero). The Timed Output Value must be shorter than the time required for the counter to count to zero, otherwise, the Output will appear to be latched on. Manual reset is “maintained” and will override automatic reset. The “Output Termination Mode” should be programmed for timed output operation, [54 5], when in this mode.
[56 -1] [56 -2] [56 -3] These modes are the same as above with the exception [56 -4] that manual reset is set for “momentary” operation. [56 -5] [56 -6]
-14-
CODE 61 - RATE (A) RIGHT HAND DUMMY ZEROS
Dummy zeros can be used to alleviate display fluctuations due to an unstable input signal. These zeros effectivelymove significantdigits tothe left. Therefore,a normal count of 1 could be shown as a 10, 100, or 1000. Using the dummy zeros will make it necessary to adjust the scaling if they were not considered before.
[61 1] 1 RIGHT HAND DUMMY ZERO [61 2] 2 RIGHT HAND DUMMY ZEROS [61 3] 3 RIGHT HAND DUMMY ZEROS [61 4] NO RIGHT HAND DUMMY ZEROS
CODE 62 - RATE CONVERSION FACTOR
The rate conversion factor provides a simple means of obtaining thedesired rate reading, usingthe sameScale Factor Value as the counter, when the rateand count units are the same. In most applications, it is simply programmed to the desired time unit that the rate is to displayed in. See Appendix “F” - Scaling For Rate.
[62 1] Rate Per Second (x1) [62 2] Rate Per Minute (x60) [62 3] Rate Per Hour (x3600)
CODE 63 - RATE MINIMUM UPDATE TIME
The determination of the rate value uses a method in which the elapsed time is measured between the first and last pulse of the update period. The minimum update time is the shortest the timeperiod canbe. Once the minimum updatetime has expired, the unit will end the measurement period when the next negative going count edge occurs. If the unitdoes notreceive the next negative count edge within the maximum update time at the start of the measurement period, the unit will end the time period and the rate display will go to zero. At very slow count rates the update time period will be the actual period of one count cycle.
[63 1] 0.5 Sec. minimum/1 Sec. maximum [63 2] 1 Sec. minimum/2 Secs. maximum [63 3] 2 Sec. minimum/4 Secs. maximum [63 4] 4 Sec. minimum/8 Secs. maximum [63 5] 8 Sec. minimum/16 Secs. maximum (max. rate = 7500 cps) [63 6] 16 Sec. minimum/32 Secs. maximum (max. rate = 3250 cps)
CODE 64 - RATE SCALE MULTIPLIER
The Rate Scale Multiplier is used in conjunction with the Rate Scale Factor A and Rate Conversion Factor to scale the actual signal input to obtain the desired reading. See Appendix “F” - Scaling For Rate.
[64 1] x 1000 [64 2] x 100 [64 3] x10 [64 4] x1 [64 5] x0.1 [64 6] x0.01
CODE 65 - RATE (A) DECIMAL POINT & LEADING ZERO BLANKING
There aresix basicmodes ofdecimal pointplacement forthe Rateindicator of the Gemini. The decimal point is placed to the right of the display digit that corresponds to the mode identifier. (The right most decimal point, digit 1, is never turned on.) A “-” sign in front of the mode identifier will inhibit leading zero blanking. The absence of a “-” sign will enable leading zero blanking.
[65 1] 0 [65 2] 0.0 [65 3] 0.0 0 LEADING ZERO [65 4] 0.0 0 0 BLANKING [65 5] 0.0000 [65 6] 0.00000
[65 -1] 000000 [65 -2] 00000.0 [65 -3] 0 0 0 0.0 0 LEADING ZERO [65 -4] 0 0 0.0 0 0 BLANKING INHIBITED [65 -5] 00.0000 [65 -6] 0.00000
-15-
CODE 66 - “OPERATOR ACCESSIBLE FUNCTIONS” MODES
The Gemini has six basic levels of “Operator Accessible Functions”. Each of these levels can be modified to enable or disable manual reset. When the “PGM. DIS.” (Program Disable) terminal is connected to “COMMON”, access to all functions is disabled except forthose listed below whichwill remain enabled.All of the function codes and parameters can be interrogated, regardless of the “Operator Accessible Functions” mode selected.
A “-” sign in front of the mode identifier will disable the front panel Reset button and the “RST.” terminal.
Note: The front panel reset button can be independently disabled by using the
disable reset DIP switch.
[66 1] NO FUNCTIONS ENABLED EXCEPT RESET - In this mode, manual
reset is enabled, but none of the programming functions can be changed.
[66 2] PRESET PROGRAMMING AND RESET ENABLED - In this mode,
manual reset and the programming of the Preset Values are enabled.
[66 3] SCALE FACTOR PROGRAMMING AND RESET ENABLED - In this
mode, manual resetand the programming of the Scale FactorValues are enabled.
[66 4] SCALE FACTOR, PRESET PROGRAMMING AND RESET
ENABLED - In this mode, manual reset and the programming of the Scale
Factor and Preset Values are enabled.
[66 5] PRESET, COUNTER LOAD PROGRAMMING AND RESET
ENABLED - In this mode, manual reset and the programming of the Presets
and Counter Load Value are enabled.
[66 6] PRESET, SCALE FACTOR, COUNTER LOAD PROGRAMMING
AND RESET ENABLED- In thismode, manual resetand the programming of
the Presets, Scale Factors and Counter Load Value are enabled.
[66 -1] [66 -2] [66 -3] These modes are the same as above with the [66 -4] exception that manual reset is disabled. [66 -5] [66 -6]
PRESET VALUE
Whenever the display value equals the preset value (when output is assigned to that display channel), an output action will occur. This action depends on the previously programmed modes. The preset values may range from -999,999 to 999,999. (Refer to “Programming the Presets, Scale Factors, Timed Outputs & Counter Load Values” section for instructions on entering the preset values.)
The Counter (B)Scale Factor, SFB,will have a direct effecton the preset value being entered (if assigned to the counter). For a Scale Factor Value greater than one, thepreset valueshould be an integer multiple of the Scale Factor. If itis not, the Gemini will automatically adjust the preset value up or down to force it to be evenly divisible by the Scale Factor.
“1” - PRESET 1 VALUE “2” - PRESET 2 VALUE (GEMINI 4200 Only)
SCALE FACTORS A & B
“3” SCALE FACTOR - The Scale Factor, for which value (count or rate) is currently being displayed, is accessed by pressing the “3” key. To access the Scale Factor of the “other” display value, the “+/-” key would be pushed (to change the display to the other value), then the “3” key would be pushed.
The number of pulses counted (internal count value) is multiplied by the Scale Factor, which changes the displayed value accordingly. A Scale Factor Value of
1.0000 would result in a display of the actual number of input pulses that have been counted. The Scale Factor is used primarily for conversion from existing pulses per unit of measure to the required displayed units. This includes conversion from different units of measure (i.e feet to meters, etc.).
The Scale Factor Values may range from -5.9999 to +5.9999 (positive onlyfor Rate (A) Scale Factor, SFA). Refer to “Programming the Presets, Scale Factors, Timed Outputs & Counter Load Values” section for entering instructions. It is important to note that the precision of a counter application cannot be improved by using a Scale Factor greater than one. To accomplish greater precision, more
-16-
pulse information must be generated per measuring unit. For example, if 5 pulses are being received per foot of material, the precision of 10th of feet cannot be attained by simply programming a Scale Factor of 2.0000, even though the display is reading in 10ths.In this case, thedisplay will incrementby twofor each count input. Thus if an odd Preset Value was entered, such as 6.7 ft., the Gemini will alter the preset to read in even tenths of feet.
Note: Use of a small Scale Factor in conjunction with a small scale multiplier
could cause the internal count value (counter) to be exceeded before the 6-digit display value is exceeded.
COUNTER LOAD VALUE
The Counter Load Value is provided to allow the user to modify the count value. The Counter Load Value is reset to zero when the Gemini is powered up. Once the Counter Load Value has been changed, it will remain set to that value until the unitis powereddown andup. Accessingthe CounterLoad Valuefor the counter that is currently being displayed is accomplished by pushing the “E” button, and while holding it down, also pushing the “+/-” button. See “Programming the Presets, Scale Factors, Timed Outputs & Counter Load Values” section for entering instructions.
“E” & “+/-” - Counter Load Value for the currently displayed counter.
-17-
DUAL PRESET COUNTER & RATE APPLICATION
A wire screen manufacturer requires a cut to length system, and in addition, a prewarning of an overspeed condition. The cutting machine is equipped with an existing 12 tooth gear, driving a one foot circumference feed roller.
The Gemini 4200’s counter is to read in feet. When 15,000 feet has been accumulated on thetake uproll, the counter outputis to turn onand deactivatethe drive system. The operator will then make the cut, load a new take up roll and reset the Gemini to start a new roll.
In addition to cut to length, the same Gemini 4200 is to be used to indicate the speed of the wire screen in feet per minute, while providing a “overspeed” warning. The normal running speed of the material is 225 feet per minute. The maximum allowable speed of the process is 250 feet per minute.
HARDWARE SETUP
The accompanying drawing shows how the hardware is setup for this application. A Model PSAC proximity sensor is used to sense the teeth on the gear. The application does not require bi-directional counting, so the Gemini 4200 will be programmed for the Count with Inhibit “Inputs 1 & 2 Response Mode”. In this mode, both the rate indicator and counter will utilize the same input signal. The switch settings and the wiring connections are as shown. The Input 2 switch positions 5-7 are setto put the Input 2 in the non-inhibit state with maximum noise immunity.
SCALING THE COUNTER
In order to scale the counter, the procedure and formulas in Appendix “E” ­Scaling for Counting are used.
In converting pulse units to “Display Units”, it is known that 12 pulses are equivalent to 1 revolution of the feed roll, which is equivalent to 1 foot linear travel of the wire screen.The “Display Unit”, therefore is 1 foot and the“Number of Pulses” per display unit is 12.
STEP 1 - Calculate the Total Scaling Factor, “K
Appendix “E”.
K
= Display Unit / Number of Pulses
T
K
= 1/12 = 0.083333
T
”, using Formula #1 of
T
STEP 2 - Determine the Number of Count Edges, “NCE”, necessary for this
application, and calculate the Remaining Scaling required, “K Formula #2 of Appendix “E”. Since the Total Scaling Factor, “K be used, therefore, the Number of Count Edges, “NCE”, is 1.
K
= 0.083333/1 = 0.083333
R
”, is less than 1, single edge counting can
T
K
/NCE
R=KT
”, using
R
-18-
STEP 3 - Determine the Scale Multiplier Value, “SCM”, and calculate the Scale
Factor, “SF”, using Formula #3 of Appendix “E”.
A Scale Multiplier value of 0.1 is chosen to provide the maximum number of
significant digits in the Scale Factor.
SF = K
/SCM
SF = 0.083333/0.1 = 0.8333
R
SCALING THE RATE INDICATOR
In this application the rate indicator can be programmed with the same scale factor and scalemultiplier values asobtained whenscaling the counter. The only other scaling that would be required is choosing the proper Rate Conversion Factor, to obtain the displayin the desired timeunits. The application callsfor the rate to be indicated in feet per minute, therefore, the Rate Per Minute Rate Conversion Factor is selected.
STEP BY STEP PROGRAMMING OF THE GEMINI 4200
STEP 1 - Enter code 41 (Unit Personality). Select and enter a mode identifier of
1, for the Gemini to operate as a Counter and Rate indicator. STEP 2 -Enter code42 (ResetButton & Terminal Actuation Modes). Select and
enter mode 2 to reset the counter when reset is activated. STEP 3 - Enter code43 (Inputs 1 & 2Response Modes). Select and enter mode 1,
“Count with Inhibit”. STEP 4 - Enter code 44 (Counter B Number of Count Edges). Select and enter
mode 1 for single edge counting. STEP 5 - Enter code45 (Counter B ScaleMultiplier). Select and enter mode2 for
a scale multiplier of 0.1. STEP 6 - Enter code 46 (Counter B Decimal Point & Leading Zero Blanking).
Select and enter mode 1 for no decimal point. STEP 7 - Enter code 51 (Output Assignment). Select and enter mode 1 to assign
Output 1 to the rate indicator and Output 2 to the counter. STEP 8 - Enter code 52 (Output 1 Termination Modes). Select andenter mode 6
for boundary operation. Output 1 will activate when the maximum speed
value, Preset 1, is exceeded. Output 1 will deactivate when the rate decreases
to a value below the maximum speed.
Note: The Timed Output 1 Value, code 53, is not used in this application.
STEP 9 - Enter code 54 (Output 2 Termination Modes). Select andenter mode 4
for Output 2 Terminate at Manual Reset.
Note: The Timed Output 2 Value, code 55, is not used in this application.
STEP 10 - Enter code 56 (Counter B Reset Modes). Select and enter mode 1 for
manual reset to zero.
STEP 11 - Enter code 61 (Rate Right Hand Dummy Zeros). Select and enter
mode 4 for no right hand dummy zeros.
STEP 12 - Enter code 62 (Rate Conversion Factor). Select andenter mode 2 for a
Rate Per Minute conversion factor.
STEP 13 - Enter code 63 (Rate Minimum UpdateTime). Select and enter mode1
for a minimum update time of 0.5 Second. If the rate display jumps around, a larger minimum update time can be used to provide averaging.
STEP 14 - Enter code 64 (Rate Scale Multiplier). Select and enter mode 5 for a
Scale Multiplier of 0.1, as previously determined.
STEP 15- Entercode 65 (Rate Decimal Point & Leading Zero Blanking). Select
and enter mode 1 for no decimal point.
STEP 16 - Enter code 66 (Operator Accessible Functions Modes). Select and
enter mode (+)1 for nofunctions except reset enabled. When the “PGM.DIS.” terminal is connected to “COMM.”, the only changes that will be possible is resetting the counter.
STEP 17 -The “+/-” keyis pushed,if necessary,so that the rateis being indicated
on the Gemini 4200. The “3” key is then pushed to call up the Rate Scale Factor. The value is changed to 0.8333.
STEP 18 - The “+/-” key is pushed, so that the count is being indicated on the
Gemini 4200. The “3” key is then pushed to call up the Counter Scale Factor. The value is changed to 0.8333.
STEP 19 - Enter aPreset 1value of 250, by pushing the “1” key andchanging the
value to 250.
STEP 20 - Enter a Preset 2 value of 15,000, by pushing the “2” key and changing
the value to 15,000. After the unit is programmed, the “PGM. DIS.” terminal is connected to “COMM.” to prevent any unauthorized or accidental mode changes. The function codes can, however, be called up to view or verify that the proper modes are entered.
-19-
PROGRAMMING INSTRUCTIONS FOR THE DUAL COUNTER VERSION OF THE GEMINI 4000
The first part of this section provides detailed descriptions of the function command codes for input response modes, reset modes, outputterminations, etc. Then, using an actual application example, the programming instructions for the Dual Counter version will be “walked through”, to give the user a full understanding of the Gemini 4000 programming procedure. The descriptions below give the function command code first, followed by the individual mode identifier. The Function Command Code Summary in the appendix, lists all codes. (Only commands and modes pertaining to the Dual Counter personality will be discussed in this section.)
CODE 41 - UNIT PERSONALITY
The Gemini can be programmed to operate in one of two different unit personalities. In each of the two personalities the Gemini operates as a dual function indicator. The personality selected determines whether display channel A will indicate rate or count. In both personalities, display channel B operates as a counter.
When the Unit Personality is changed and entered, all modes and data values (Presets, Scale Factors, function codes, etc.) will be automatically loaded with the factory settings for that personality. If, for any reason during programming,it is desired to return to the factory settings, the “+/” key can be pushed while in code 41. Then, when the “E” keyis pressed the unit will load the factory settings into the Gemini.
The programming procedures for the two unit personalities will vary. This entire section dealswith theunit programmedas a Dual Counterindicator, [41 2].
[41 1] COUNTER(B)/RATE (A) -In this mode,display channel Afunctions as a
rate indicator and display channel B functions as a counter. See
“PROGRAMMING INSTRUCTIONS FOR COUNTER/RATE VERSION
OF THE GEMINI” section for details. [41 2] DUAL COUNTER - In this mode, both display channels {A & B}
function as counters.
CODE 42 - RESET BUTTON & TERMINAL ACTUATION MODES
The “Reset Button & Terminal Actuation modes” control the affect that the
reset button and terminal have on the two display channels.
There is a separate “Rst A” terminal which resets Counter A, when activated.
It is provided to allow independent resetting of each channel.
[42 1] RESET COUNTER A [42 2] RESET COUNTER B [42 3] RESET COUNTER A & B
CODE 43 - INPUTS1&2RESPONSE MODES
The Gemini has six different input response modes. They are: Count(1) with Inhibit(2); Count(1) with Up/Down Control (2); Two input anticoincidence Add(1)/Subtract(2); Separate Inputmode; Quadrature;and Quadrature x4. In all modes, except [43 4], both counters will respond identically to both inputs. These modes are most suitable for applications where one channel is used for control, and the other for totalizing counts.
[43 1] COUNT WITH INHIBIT- Input 1 servesas the count input. Input2 serves
as the Inhibit input. When Input 2 is low, the counters will ignore the count
signal appearing at Input 1. When Input 2 is at a high level, the pulses
appearing at Input 1 will be counted. [43 2] COUNT WITH UP/DOWN CONTROL - In this mode, count direction
can be controlled by the second input. Input 1 serves as the count input and
Input 2 serves as the direction control signal input. When Input 2 is at a high
level, the counters will count up. When Input 2 is at a low level, the counters
will count down. [43 3] TWO INPUT ANTICOINCIDENCE ADD/SUBTRACT - This mode
effectively separates count pulses which may simultaneously appear at the
two inputs. The Gemini unit processes the count pulses into a string of
time-separated pulses, sothe internal counters will notlose any counts.Input 1
serves as the add input (count increments) and Input 2 serves as the subtract
input (count decrements).
-20-
[43 4] SEPARATE INPUT - In this mode, the two counters, A & B, are
independently controlled by the inputs. Input 1 serves as the Counter A input and Input 2 serves as the Counter B input.
[43 5] QUADRATURE COUNTING - Quadrature counting modes are primarily
used in positioning and anti-jitter applications. The reason this mode works is due to the manner in which two pickups are positioned relative to each other. The signal on Input 2 is a pulse train signal shifted 90° away from the signal on Input 1. These two signals are processed by the Gemini as follows: Input 1 serves as the count input, while Input 2 serves as the quadrature input. For quadrature withsingle edgecounting, thecounters will count in a positive direction when Input 1 is a negative going edge and Input 2 is at a low level. The counters willcount ina negative direction whenInput 1 is a positivegoing edge and Input 2 is at a low level. All transitions on Input 1 are ignored when Input 2 is at a high level. These logic rules provide the basis for anti-jitter operation which will prevent false counts from occurring due to back-lash, vibration, chatter, etc. When twoedge counting is used, the quadrature mode works the same as with single edge counting when Input 2 is low. But when Input 2 is at a high level, counts at Input 1 are no longer ignored. Instead the logic rules for Input 1 are complemented, allowing both edges of Input 1to becounted. This doubles the effective resolution of the encoded input.
[43 6] QUADRATURE TIMES 4 - This mode takes the quadrature mode, with
two edge counting, one step further. In quadrature times 4, both Input 1 and Input 2serve as the count or quadrature input, depending on their state. In one instance, Input 1 will serve as the count input and Input 2 will serve as the quadrature input.In another instance, Input 1 will be the quadrature input and Input 2 will be the count input. This enables each edge, positive and negative going, of both inputs, 1 and 2, to be counted. This results in a resolution four times greater than in the basic quadrature x1 mode.
CODE 44 - COUNTERS A & B NUMBER OF COUNT EDGES
The counters of the Gemini can be programmed for either single or two edge (x2) counting. The number of count edges cannot be set when the count mode is programmed for quadrature x4 operation. The Gemini will ignore any attempt to enter function command code 44, when set for quadrature x4.
[44 1] SINGLEEDGE COUNTING (x1) - The unitcounts onthe negativegoing
(falling) edge of the count input signal. The Inputs 1 & 2 Response mode
descriptions describe how each mode uses this method of edge counting.
[44 2] TWO EDGE COUNTING (x2) - This mode is used when doubling of the
count signal input is required. The unit counts on the positive going (rising)
edge of the count input signal, as well as, the negative going (falling) edge.
CODE 45 - COUNTER B SCALE MULTIPLIER
There are four “Counter B Scale Multipliers” that are available. They effectively divide the internal countB value by 1, 10,100, and 1000 respectively, to yield the displayed Counter B value. Note: Use of a small scale multiplier in conjunction with a small Scale Factor could cause the internal count value to be exceeded before the 6-digit display value is exceeded. See “Programming the Presets, Scale Factors, Timed Outputs & Counter Load Values” section for more details.
[45 1] x1 [45 2] x0.1 [45 3] x0.01 [45 4] x0.001
-21-
Loading...
+ 51 hidden pages