Red Lion GEMINI 33 User Manual

THE ASTRO LINE SERIES
GEMINI 3300 INSTRUCTION MANUAL
INTRODUCTION
The Gemini 3300 is another unit in our multi-purpose series of industrial control products that are field-programmable to solve multiple applications. This series known as the Astro-Line family of products, is built around the concept that the end user has the capability to program different personalities and functions into the unit in order to adapt to different indication and control requirements.
The Gemini 3300 which you have purchased, has the same high quality workmanship and advanced technological capabilities that have made Red Lion Controls the leader in today’s industrial market.
Red Lion Controls has a complete line of industrial indication and control equipment, and we look forward to being of service to you now and in the future.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
TABLE OF CONTENTS
I. GENERAL DESCRIPTION .............................................. 2
SafetySummary.................................................... 2
BasicOperation.................................................... 2-3
ProgrammingTheGemini3300 ........................................... 3
DisplayingtheProcess,Batch&TotalCountValues ............................... 3
ManualReset ..................................................... 3
ProgrammingFunctionCodes ............................................ 4
ProgrammingThePresets,ScaleFactor,TimedOutputs&CounterLoadValues ............... 4-5
FactorySettings ................................................... 6
OperatorAccessibleFunctionsWithProgrammingDisabled ........................... 7
Diagnostics,Self-Test,&“Watchdog”Timer .................................... 7
InputCircuitry&Set-up ............................................... 8
OverflowIndication .................................................. 8
II. PROGRAMMING INSTRUCTIONS FOR THE GEMINI 3300 BATCH COUNTER ................ 9
Codes41,43,44,45,&46 ............................................. 9-10
Codes52,53,54,&55 ................................................ 10-12
Codes61,62,63,64,65,66,PresetValues,ScaleFactor,&CounterLoadValues .............. 12-15
ProgrammingApplicationExample ......................................... 16-18
III. GEMINI 3300 20 MA CURRENT LOOP COMMUNICATIONS ........................... 19
CommunicationFormat ............................................... 19
Sending Commands & Data to the Gemini 3300 .................................. 19-21
ReceivingDatafromtheGemini3300 ....................................... 21
PrintOptions ..................................................... 22
CurrentLoopInstallation ............................................... 22-23
CommunicationsApplication ............................................. 24
Troubleshooting Gemini Serial Communications & Serial Loop-Back Self-Test ................. 25
IV. APPENDIX “A” - INSTALLATION & INPUT CONFIGURATION SWITCH SET-UP ............... 26-33
InstallationEnvironment................................................ 26
EMCComplianceInstallation............................................. 27
V. APPENDIX “B” - SPECIFICATIONS & DIMENSIONS ............................... 34-35
VI. APPENDIX “C” - TROUBLESHOOTING GUIDE .................................. 36-37
VII. APPENDIX “D” - FUNCTION COMMAND CODE SUMMARY .......................... 38-41
VIII. APPENDIX “E” - SCALING FOR COUNTING ................................... 42-43
IX. APPENDIX “F” - GEMINI 3300 PROGRAMMING CHARTS ............................ 44-46
X. APPENDIX “G” - ORDERING INFORMATION ................................... 47
-1-
GENERAL DESCRIPTION
The Gemini 3300 isa two input, microprocessor-based BatchCounter with two Process Presets, a Batch Preset, and corresponding outputs. The 6-digit display features 0.56" LEDs with negative sign, overflow, display mode, and Process output indicators. The unit is available with a 20 mA Current Loop Communications Option, which makes possible remote or computerized monitoring and modification of the CountValues,Presets and Scale Factor.
Flexibility and usefulness are provided through user programmability. With simple front panel keystrokesand rear panel switch settings, any one of a number of configurations can be selected. Once the selection is made, all or part of the keyboard can be disabled to protect the settings andguarantee that no unwanted changes occur during the measurements.
Each time the power is turned off,the unit automatically saves the settings and data in its specialno power memory. When power is restored, the Gemini sets itself back to the operational modes and restores the data it had at power-down. The “no power” E cycles of power being applied to and removed from the unit.
Whenever the power comes on, the Gemini 3300 performs a series of internal diagnostics to verify the integrity of the stored data. There is also a self-test mode and a “watchdog” timer to help prevent processor lockup.
The Gemini 3300 can accept uni-directional, bi-directional, or quadrature signals. It also has the capability to double or quadruple (Quadrature x4) the resolution of the incoming count signal. There are also modes available for anti-coincidence applications. Both channels of count information are monitored simultaneously, no counts are lost, and the final output can be chosen as the sum or difference of the two input channels.
The Gemini 3300 20 mA Current Loop Communications option provides the capability of two-way serial communications between the Gemini 3300 and a variety of equipment,such as a printer, remote terminal, programmable controller, or host computer. The baud rate can be set to 300, 600, 1200, or 2400 baud. The format for transmitted and received data is 1 start bit, 7 data bits, 1 parity bit(odd), anda stop bit. When utilizingan external power supply (30 VDC max), up to sixteen units can be installed in the loop, each with an individual address. When utilizing the Gemini’s 20 mA current source, up to seven units can be installed in a loop. The Count Values, Presets, and Scale Factor can be interrogated or changed by sending the proper command codes and numerical data(if required) tothe unit. Otherfunctions, such asresetting the various counters, can also be performed. Various “Print Options” can be
2
PROM’s life expectancy is at least 100,000
selected to automatically interrogate the Count Values, Presets, and Scale Factor by activating the “Print Request” terminal or by sending a “Transmit Per Print Option” (P) command.
The relays are mounted on a plug-in board which makes it easy to field upgrade the Gemini3300. The contactsare rated for240 VAC or 28 VDC at 5amps.
The construction of the Gemini 3300 features a metal die-cast bezel, offering maximum durability with a high quality appearance. The sealed front panel meets NEMA 4/IP65 specifications for washdown and/or dust when properly installed. Clamp type pressure plate terminals accept stripped #14 AWG wire without lugs.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or onequipment must be observed toensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, orother actuators not equipped withsafeguards. To do so, can be potentiallyharmfulto persons or equipment in the event of a fault to the unit.
BASIC OPERATION
The Gemini 3300 contains three counters that keep track of the Process Count, Batch Count, and Total Count. When a count edge is received, the Process Counter and the Totalizing Counter are adjusted. When displaying the Process or TotalCounts, the processor takes theraw count (actual number of count edges that have been entered) and multiplies it by the Scale Factor and Scale Multiplier and the results are displayed. The Batch Count register, which is adjusted eachtimea batch has been completedis displayeddirectly.
Both the Process Counter and Batch Counter have six Reset Action modes associated with them. Both of them can be independently configured to operate in Reset to Zero (up-count) or Reset to Preset (down-count) modes, and in manual or auto reset modes.
The Process Counter displays the value of display units in the current Batch cycle. The Preset 2 Value of the Process Counter determines the number of display units per batch cycle. When the Process Counter reaches Preset 2 (up-count modes) or zero (down-count modes), Output 2, and Relay 2 will activate and the Batch count will be adjusted by one. The Batch
-2-
Counter will display the number of batches that have been completed (up-count modes) or the number of batches left to complete (down-count modes).
The Total Countis the total number of counts that havebeen received since the Total was last reset. It can be used to keep a running total of process units on a desired pershift, per day, per week,etc. basis.Like the Process and Batch Counts, the Total can be reset independently of the other two.
The internal precision of theProcess and Totalizing Counter is maintained to 9 digits. The internal precision of the Batch Counter is 7 digits.
PROGRAMMING THE GEMINI 3300
When your Gemini 3300 arrives from the factory, it is necessary to program the unit to suit the desired application. It is programmed with the factory settings listed in the “Factory Settings” section. All programming is accomplished by using the pushbuttons located on the front panel. The personality, functions, and modes are accessed by pressing the appropriate keys. A function is defined by atwo-digit code which appears on the leftside of the display. The mode of that function is shown as a one-digit code on the right side ofthe display. At timesthere will be a“-” sign modifier tothe left of the mode.
Data for the Presets, Scale Factors and Timed Output Values are entered differently. Each digit key controls the digit on the display directly above it. Changing the digits can be done by repeatedly pressing the key beneath the digit position you wish to change or by holding the key down. As you hold it down, or repetitively press it, the value of that digit will change cyclically, counting up to 9, then to 0, and then up again. The 6 numbered keys correspond to the six digits, and the “+/-” key corresponds to polarity.
DISPLAYING THE PROCESS, BATCH & TOTAL COUNT VALUES
The Gemini 3300can display anyof the three count values. There are three annunciators to the left of thedisplay with thedesignations, P, B, and T. Only one annunciator will be lit at one time. These annunciators correspond to the Process, Batch andTotal count values. To display a different value,the “+/-” key is repeatedly pressed and released until the annunciator corresponding to the desired count value is displayed. Each time the key is pressed, thedisplay will sequence to the next count value and the appropriate annunciator will light. Once thedisplay has been changed,the unit will displaythe count value until it is changed again.
MANUAL RESET
There are two different methods by which the Gemini 3300’s count values
can be manually reset. These methods are as follows:
Reset by front panel Reset button, “R” Rear Reset terminal Reset utilizing 2-button reset
The reset operation is affected by three function code settings; The Reset Button, and Reset Terminal Actuation modes (Function Code 61),theReset Action modes (Function Codes 62 and 63),andthe“Operator Accessible
Functions” modes (Function Code 66).The“Reset Button and Terminal Actuation Modes” will determine whichcounters will be reset whenthe Reset
button or terminal is activated. The Reset Action modes determine whether the Process or Batch Counter will Reset to Zero or Reset to Preset. The “Operator Accessible Functions” modes will determine which resetting modes are enabled, when the “PGM. DIS.” (program disable) terminal is connected to “COMMON”. The Reset button can be disabled independently of the Reset terminal by setting the “DIS./EN.RST.” position of the Input Configuration DIP switches to “DIS.”.
A 2-button reset method is provided to allow an independent reset for the Process and Batch counters. To reset a counter using this method, the following procedure must be used.
Press the “E” key,
While holding the “E” key also press the
“1” button to reset the Process Counter, or the
“2” button to reset the Batch Counter.
Note: There is no 2-button reset mode for the Total Counter. It can be
independently reset by loading a Counter Load Value of 0.
-3-
PROGRAMMING FUNCTION CODES
Entering function and mode is easily accomplished by pressing the appropriate digit key. To program the Scale Multiplier, you would enter 45 by pressing the front panel keys, 4 and 5.
The digits on the left side of the display show the function code; the digits on theright side showthe current programmed mode.
A new mode selection is made by entering a new number. On some of the entries, you have the option of a plus “+” or minus “-” sign. In the cases where a “+” sign is required, no sign will be displayed. If you do enter a “-” sign (using the “+/-” key), a minus sign will be displayed in front of the appropriate digit.
Pressing the “E” key finalizes the change. The display will now show the count value immediately.
If you do not press the “E” key, the change will not be recorded. The display will remain in the programming mode for 15 seconds, and then return to normal operating mode using the old function and mode settings.
The unit can be programmed with the factory settings by calling up Function Code 41, putting a “-” in front of the mode by pushing the “+/-” key, and entering it.
Refer to the “Factory Settings” section for more details.
PROGRAMMING THE PRESETS, SCALE FACTOR, TIMED OUTPUTS & COUNTER LOAD VALUES
The Presets andScale Factor Values are commonly reprogrammed on adaily basis. As such, single keystroke access has been provided on the front panel.
Pressing the “3” key will call up the Scale Factor.
Once the Scale Factor is displayed, changing the digits can be accomplished by repeatedly pressing thekey beneath the digit position you wish to change or by holding the key down, allowing the digit to increment automatically.
The new value willbe entered when the “E” keyis pressed.
The internal unscaled Process and Total Count Values are multiplied by the Scale Factor Value, which changes the displayed values accordingly.
Presets 1 and 2 are assigned to the Process Counter and the Batch Preset is assigned to the Batch Counter. To call up the Preset for the desired counter, the Gemini 3300 must first be displaying that count value.
To display the Preset 1 Value (Process Counter),the “+/-” key is first pushed (if necessary) until the “P” (Process) annunciator is lit.
The “1” key is then pushed to call up the Preset 1 Value.
To change the value, the digits can be cycled through in the same manner as discussed for the Scale Factors.
The new value willbe entered when the “E” keyis pressed.
The Preset 2 Value is changed in the same manner as described above except that the “2” key is pushed instead of “1”. To change the Batch Preset, the “1” key is pushed while the Batch Counter is being displayed. The Preset Values can range from 0 to +999999.
-4-
The Timed Output Values are changed by entering two-digit function codes. After the code is entered, the display will show the present Timed Output 1, 2 or B Value in seconds with two decimal place resolution. The Timed Output Values can be set from .01 to 599.99 seconds.
It is possibleto change thecounter values of the Gemini 3300 byentering a “Counter Load Value”. This feature can be enabled or disabled by the programming of the“Operator Accessible Functions Modes”, function code
66. The “Counter Load Value” is stored when the unit is powered down. To access the Counter Load Value for the desired counter; first, press the “+/-” key,if necessary,so that the display is indicating the counter that is to be changed.
To change the Timed Output 1 Value, enter function code 53 and enter the new value by holding down or repeatedly pressing the key below the digit position you wish to change.
The new value will be entered when the “E” key is pressed. The display will immediately return to the count value.
Note: A Timed Output Value of zero cannot be programmed into the Gemini
3300. If a value of0 is entered into the display, and the “E” keyis pressed,
the unit will remain in data entry mode. If a new value is not entered, it will
time out and the unit will continue to use its previous setting.
As with the other functions, you must press “E” to record the changes.For the data entry modes, if you do not press the “E” key, a time out of 5 seconds occurs, and the display returns to operating mode without any changes to the value. The only time any change will occur is when the “E” key is pressed.
Secondly, press the “E” key and while holding it down,
press the “+/-” key.
The Gemini will now display the Counter Load Value
for the Counter that is displayed.
To change the value, press the key under the digit to be
changed as explained previously for the Preset.
To load the value into the counter, press the “E” key. The display will flash momentarily and will display the counter with the new value.
-5-
FACTORY SETTINGS
INITIAL FACTORY CONFIGURATION
Keys Struck Display Description
4,3 43 1 Count with Inhibit
4,4 44 1 Count on falling edge of Input A
4,5 45 1 Scale Multiplier of 1.0
4,6 46 1 Leading zero blanking and no decimal point
5,2 52 5 Output 1 terminates after Timed Output, Normal Phase
5,3 0000.10 Timed Output 1 Value of 0.1 sec
5,4 54 5 Output 2 terminates after Timed Output, Normal Phase
5,5 0000.10 Timed Output 2 Value of 0.1 sec
6,1 61 4 Reset Process, Batch, and Total Counter
6,2 62 1 Process Counter, Manual Reset to Zero
6,3 63 1 Batch Counter, Manual Reset to Zero
6,4 64 3 Output B terminates at reset. Normal output phase
6,5 0000.10 Timed Output B Value of 0.1 sec
6,6 66 6 Presets, Scale Factor 2-Button Reset, & Counter
3 01.0000 Scale Factor set to 1.0000
1 000100 Preset 1 set to 100 (when Process Count displayed)
2 000200 Preset 2 set to 200 (when Process Count displayed)
1 000010 Preset B set to 10 (when Batch Count is displayed)
E & +/- 000000 Counter Load Values set to 0 (displays value for
Note: Entering a -1 in function code 41 will restore the unit to the factory configuration shown above.
Load Programming Enabled
displayed counter)
-6-
OPERATOR ACCESSIBLE FUNCTIONS WITH PROGRAMMING DISABLED
(For details on keyboard entry, see preceding section)
One of the important features of the Gemini 3300 is the ability to disable programming. With this ability, accidental bumping of the keys or tampering by unauthorized personnel canbe prevented. However,it may be necessary toallow reset and certain programming functions, such as Presets and the Scale Factor Value, to be changed indaily operation. The Gemini3300, through theuse of the “Operator Accessible Functions” Modes can enable these functions even when the “PGM. DIS.” (Program Disable) terminal is connected to “COMMON”.
The “Operator Accessible Functions” modes areprogrammedby entering a two-digit function code (66) and the desired mode. Unlike other function codes, the mode doesnot take effect immediately. The “PGM. DIS.” terminal must be connected to “COMMON” in order for the Gemini to disable programming and operate as per the mode programmed.
There are six basic “Operator Accessible Functions” Modes available. These modes enable the following functions.
1. NO FUNCTIONS ENABLED
2. PRESET PROGRAMMING ENABLED
3. SCALE FACTOR PROGRAMMING ENABLED
4. SCALE FACTOR AND PRESET PROGRAMMING ENABLED
5. PRESET, COUNTER LOAD PROGRAMMING, AND 2-BUTTON
RESET ENABLED
6. PRESET, SCALE FACTOR AND COUNTER LOAD PROGRAMMING,
AND 2-BUTTON RESET ENABLED
Note: In all of the modes above, the Reset button and terminal are enabled.
All of these modes can be modified with the addition of a “-” sign. The
minus sign disables the manual reset, at the front panel and the reset
terminal at the rear of the unit.
There is also a rear panel DIP switch which permits disabling of the front panel reset button. This is independent of the rear reset terminal, and can be used in conjunction with any front panel disable mode.
DIAGNOSTICS, SELF TEST, & “WATCHDOG” TIMER
The security of the Gemini 3300 is further enhanced by its self-test
diagnostic and “watchdog” timer capabilities.
The diagnostics are concerned with the special, no power memory of the Gemini 3300. When power is turned off, all pertinent function settings and measurements are automatically saved. When power is restored, the functions and data are re-instated. This allows you to program the unit once and not have to re-program it until you wish to use it in another mode.
When the function codes and data are saved, computations are made with these values. The result of these computations is stored in the memory to serve as a check against possible error. On power-up the same computations are repeated on the stored data. If the results do not agree with the stored results, a “P” will appear on the left side of the display. If thisoccurs, refer to the “Troubleshooting Guide” for directions.
Another error indicator is the “watchdog” timer. In order to insure the software is functioning properly, the program constantly monitors itself. If the proper sequence and timing of internal events does not occur,an “E” will appear on the left side of the display. If this occurs, refer to the “Troubleshooting Guide” for directions.
The final type ofbuilt-in errorchecking is the front panelinitiated self-test. It can beperformedat any time, evenwhen the Gemini 3300 is running. It will not interfere withthe accumulation of counts or control functions.A function code of “6”, “+/-” starts the test. At this time, whatever was displayed will disappear and be replaced by a string of decimal points and the overflow indicator. Then the display will show a string of 9’s, then 8’s etc., until a string of 0’s are shown. The self-test will then turn off the overflow indicator and activate the minus “-” sign. Then the unit shows an interlace pattern of
-010101, then -212121, followed by 232323 etc., until 898989 is reached. At this time the outputs can be tested by pressing the “1” key for Output 1, the “2” key for Output 2, and the “3” key for Output B.
(The program disable terminal must be disconnected in order to allow activation of the outputs. Also, when testing theoutput, use caution, so as not to cause any undesirable or hazardous conditions in the system.) An
automatic exit willtake place aftersix seconds or immediately if the Program Disable terminal is connected to common. Normal length of display time for each of the patterns is approximately 0.5 sec. Rapidly pressing “E” during self-test can speed up the sequence.
-7-
INPUT CIRCUITRY & SET-UP
There are two independent input channels on the Gemini 3300. Various types of sensor outputs can be accommodated by appropriate DIP switch set-up. These include: TTL orCMOS logic,currentsinking, current sourcing, or dry contact and more.
Channel A consists of a logic input and a separate low level magnetic pickup input.
Channel B is a completely independent count or control input channel. Like Channel A, it canbe programmedwith DIP switches for awide variety of logic inputs, and is identical to Channel A in this regard. For a complete detailed description of input set-up, see Appendix “A”.
OVERFLOW INDICATION
The Gemini 3300 features an overflow indicator (LED) which is located to the left ofthe sixth digitand above the polarity annunciator.This LED will turn on if the capacity of the display (6-digits) is exceeded or if the internal count capacity (9-digits, 7 digits for batch counter) is exceeded. Use of extremely small scale multiplier and Scale Factor Value can cause the internal count (Process and Total) capacity to overflow before the displayed value would overflow. For example, if a Scale Factor of 0.0001 and a Scale Multiplier of
0.001 is used, for every 10,000,000 count edges received, the display would increment by 1. Before the display reaches 215, the internal counter would overflow. When the capacity of the display is exceeded, the countvalue will be maintained and will be valid. But if the internal count capacity is exceeded, then this value will no longer be valid. The internal Process and Total count values will overflow after 2,147,483,647 counts have been entered. The count information will become invalid after 4,294,967,295 counts. At this point the counter will change sign and the displayed count will decrement in value.
The internal count capacity for the Batch Counter is 16,777,216. This amounts to overflowing the Batch Counter display over 16 times. If this number is exceeded, the counter will rollover to zero, however, thedisplayed digits will no longer be valid. It should also be noted that the use of a Scale Factor larger than one could cause the displayed Process or Total value to overflow before 999,999 counts are accumulated.
The Batch and Totalizing counters should not be allowed to operate in the overflowed condition. As soon as, or before the counters overflow, the information should be recorded and the counters reset.
-8-
PROGRAMMING INSTRUCTIONS FOR THE GEMINI 3300 BATCH COUNTER
The first part of this section provides detailed descriptions of the function command codes for Input response modes, reset modes, output termination modes, etc. Then, using an actual application example, the programming instructions are “walked through” to give the user a full understanding of the Gemini 3300 programming procedure. The descriptions below give the function command code first, followedby the individual mode identifier. The Function Command Summary in Appendix “D”, lists all codes.
CODE 41 - FACTORY SETTINGS
When Code 41 is called up, the unit will display a 1 as the mode.Entering a “-” sign in front of the mode will cause the unit to re-load the factory settings as shown in the “Factory Settings” section.
CODE 43 - INPUTS A & B RESPONSE MODES
The Gemini 3300 has six different input response modes that will directly affect the Process Counter and the Total Counter. They are: Count (A) with Inhibit (B); Count (A) with Up/Down Control (B); Two input anti-coincidence Add (A)/Subtract (B); Two input anti-coincidence Add (A)/Add (B); Quadrature; and Quadrature x4.
[43 1] COUNT WITH INHIBIT - Input A serves as the count. Input B serves
as the Inhibit input. When Input B is low, the counter will ignore the count
signal appearing at Input A. When Input B is at a high level, the signal
appearing on Input A will be counted. The “Process Counter Reset Action
Modes” will determine the count direction for the Process Counter. In
applications where the Inhibit function is not actually used, the Input B
“SRC/SNK” position of the “INPUT CONFIGURATION DIP SWITCH”
should be setto the “SNK” positionto provide a 7.8Kohm pull-up resistor.
This will set Input B to the Non-Inhibit state. [43 2] COUNT WITH UP/DOWN CONTROL - In this mode,count direction
can be controlledby the second input.Input A serves asthe count input and
Input B serves as the direction control signal input.
When Input B is at a high level, the counter will count up. When Input B is
at a low level, the counter will count down.
[43 3] TWO INPUT ANTI-COINCIDENCE ADD/SUBTRACT - This mode
effectively separates count pulses which may simultaneously appear at the two inputs. The Gemini unit processes the count pulses into a string of time-separated pulses, so the internal counter will not lose any count pulses. Input A serves as the add input (count increments) and Input B serves as the subtract input (count decrements).
[43 4] TWO INPUT ANTI-COINCIDENCE SUMMING - Input A and B are
summed or added in the same manner as above. This mode is uni-directional. The “Process Counter Reset Action Modes”, will determine the count direction for the Process Counter.
[43 5] QUADRATURE COUNTING - Quadrature counting modes are
primarily used in positioning and anti-jitter applications. The reason this mode works is due to the manner in which two pickups are positioned relative to each other. The signal on Input B is a pulse train signal shifted 90° away from the Input A signal. These two signals are processed by the Gemini as follows: Input A serves as the count, while Input B serves as the quadrature input. For quadrature with single edge counting, the counter will count in a positive direction when Input A is a negativegoing edge andInput B is at a low level. The counter will count in a negative direction when Input A is a positive going edge and InputB is at a low level. All transitionson Input A are ignored when Input B is at a high level. These logic rules provide the basis for anti-jitter operation which will prevent false counts from occurring due to back-lash, vibration, chatter, etc. When two edge counting is used, the quadrature mode works the same as with single edge counting when Input B is low. But when Input B is at a high level, counts at Input A are no longer ignored. Instead the logic rules for Input A are complemented, allowing both edges of Input A to be counted. This doubles the effective resolution of the encoded input.
-9-
CODE 43 - INPUTS A & B RESPONSE MODES (Cont’d)
[43 6] QUADRATURE TIMES 4- This modetakes the quadraturemode, with
two edgecounting, one step further. In quadrature times 4, both Input A and
Input B serve as the count or quadrature input, depending on their state. In
one instance, Input A will serve as the count input and Input B will serve as
the quadrature input. In another instance, Input A will be the quadrature
input and Input B will be the count input. This enables each edge, positive
and negative going, of both inputs, A and B, to be counted. This results in a
resolution four times greater than in the basic quadrature x1 mode.
CODE 44 - NUMBER OF COUNT EDGES
The Gemini 3300 can be programmed for either single (negative going edge) or two edge (x2) counting. The number of count edges cannot be set when the count mode is programmed for quadrature x4 operation. The Gemini will ignore any attempt to enter Function Command Code 44 when set for quadrature x4.
[44 1] SINGLE EDGE COUNTING (x1) - The unit counts on the negative
going (falling) edge of the count input signal.The count mode descriptions
describe how each mode uses this method of edge counting. [44 2] TWOEDGE COUNTING (x2) - This mode is used whendoubling of the
count signal input isrequired. The unit counts on the positive going (rising)
edge of the countinput signal,as well as the negativegoing (falling)edge.
CODE 45 - SCALE MULTIPLIER
There are four Counter B Scale Multipliers that are available. They effectively divide the internal Process and Total Count Values by 1, 10, 100, and 1000 respectively, to yield the displayed values. (Note: Use of a small
scale multiplier in conjunction with a small Scale Factor could cause the internal count value to be exceeded before the 6-digit display value is exceeded.) See “Overflow Indication” section for more details.
[45 1] x1 [45 2] x 0.1 [45 3] x0.01 [45 4] x0.001
CODE 46 - DECIMAL POINT & LEADING ZERO BLANKING
There are six basic modes of decimal point placement for the Process and Total counter of the Gemini 3300. The decimal point is placed to the right of the display digit that corresponds to the mode identifier. (The right most decimal point, digit 1, is never turned on.) A “-” sign in front of the mode identifier will inhibit leading zero blanking. The absence of a “-” sign will enable leading zero blanking.
[46 1] 0 [46 2] 0.0 [46 3] 0.0 0 LEADING ZERO [46 4] 0.0 0 0 BLANKING [46 5] 0.0000 [46 6] 0.00000
[46-1] 000000 [46-2] 00000.0 [46-3] 0000.00 LEADINGZERO [46 -4] 0 0 0.0 0 0 BLANKING INHIBITED [46-5] 00.0000 [46-6] 0.00000
CODE 52 - OUTPUT 1 TERMINATION MODES
The Gemini 3300 has five “Output 1 Termination Modes”, which control the way Output 1 (O1) will terminate or reset. An Output 1 response will occur when theProcess Counter reaches the Preset 1 Value (when counting in the “normal” count direction). In all modes, Output 1 will terminate immediately when the Process counter is manually reset.
A reverse phase mode is available on the Gemini 3300. This refers to the complementing of the logic state of the output. With normal phase operation, when the Process counter value reaches Preset 1, Output 1 will turn on. The reset condition of Output 1is output off. In reverse phase operation, Output 1 turns off when Preset 1 is reached. The reset condition of Output 1 is output on. (Note: The state of the relay, if used, is also reversed.) A “-” sign in front of the mode identifier will provide for reverse phase operation. The absence of a “-” sign will indicate normal phase operation.
-10-
[52 1] TERMINATE AT OUTPUT 2 START - Output 1 (O1) will terminate
when Output 2 starts. Output 1 is set for normal phase operation.
[52 2] TERMINATE AT OUTPUT 2 END - Output 1 (O1) will terminate
when Output 2 ends. Output 1 is set for normal phase operation.
[52 3] TERMINATE AT MANUAL RESET - Output 1 (O1) activates when
the Process Counter Value reaches the Preset 1 value. In this mode, once Output 1 is activated,itdoes not deactivate untilthe moment amanualreset occurs. Output 1 is set for normal phase operation.
[52 4] TERMINATE AT MANUAL RESET END - This mode is like the
preceding, except Output 1 (O1) deactivates when manual reset ends. Output 1 is set for normal phase operation.
[52 5] TERMINATE AFTER TIMED OUTPUT 1 - Once Output 1 (O1) has
been activated, it will deactivate after the predetermined length of time (Code 53) has expired. Manual reset will override the timed output and reset Output 1. Output 1 is set for normal phase operation.
[52 -1] [52 -2] [52 -3] These modes are the same as above with the exception [52 -4] that the output is set for reverse phase operation. [52 -5]
CODE 53 - TIMED OUTPUT 1 VALUE
The Gemini 3300 has the capability of varying the Timed Output 1 Value from 0.01 second to 599.99 seconds. When the code is entered, instead of a single mode identifier digit beingdisplayed, six digits willbe shown.Refer to
“Programming the Presets, Scale Factor, Timed Outputs & Counter Load values” section for more details about entering. The timed output will be
terminated if the Process counter is manually reset.
Note: A Timed Output value of zero cannot be programmed into the Gemini
3300. If a value of 0 is entered into the display and the “E” key is pressed,
the unit will not enter the 0, but will stay in the data entry mode. If a new
value is not entered, it will time out and the unit will continue to use its
previous setting.
CODE 54 - OUTPUT 2 TERMINATION MODES
The Gemini 3300 has five “Output 2 Termination Modes”,which control the way Output 2 (O2) will terminate or reset.An Output 2response will occurwhen the Process Counterreaches the Preset 2 value orzero. In all modes, Output2 will terminate immediately when the Process Counter is manually reset.
A reverse phase mode is available on the Gemini 3300. This refers to the complementing of the logic state of the output. With normal phase operation, when the Process counter value reaches Preset 2, Output 2 will turn on. The reset condition of Output 2is output off. In reverse phase operation, Output 2 turns off when Preset 2 is reached. The reset condition of Output 2 is output on. (Note: The state of the relay, if used, is also reversed.) A “-” sign in front of the mode identifier will provide for reverse phase operation. The absence of a “-” sign will indicate normal phase operation.
[54 1] TERMINATE AT OUTPUT 1 START - Output 2 (O2) will terminate
when Output 1 starts. Output 2 is set for normal phase operation. [54 2] TERMINATE AT OUTPUT 1 END - Output 2 (O2) will terminate
when Output 1 ends. Output 2 is set for normal phase operation. [54 3] TERMINATE AT MANUAL RESET - Output 2 (O2) activates when
the Process Counter reaches the Preset 2 value or zero. In this mode, once
Output 2 is activated,itdoes not deactivate untilthe moment amanualreset
occurs. Output 2 is set for normal phase operation. [54 4] TERMINATE AT MANUAL RESET END - This mode is like the
preceding, except Output 2 (O2) deactivates when manual reset ends.
Output 2 is set for normal phase operation. [54 5] TERMINATE AFTER TIMED OUTPUT 2 - Once Output 2 (O2) has
been activated, it will deactivate after the predetermined length of time
(Code 55) has expired. Manual reset will override the timed output and
reset Output 2. Output 2 is set for normal phase operation.
[54 -1]
[54 -2] These modes are the same as above with the exception
[54 -3] that the output is set for reverse phase operation.
[54 -4]
[54 -5]
-11-
CODE 55 - TIMED OUTPUT 2 VALUE
The Gemini 3300 has the capability of varying the Timed Output 2 Value from 0.01 second to 599.99 seconds. When the code is entered, instead of a single mode identifier digit beingdisplayed, six digits willbe shown.Refer to
“Programming the Presets, Scale Factor, Timed Outputs & Counter Load Values” section for more details about entering. The timed output will be
terminated if the Process Counter is manually reset.
Note: A Timed Output Value of zero cannot be programmed into the Gemini
3300. If a value of 0 is entered into the display and the “E” key is pressed,
the unit will not enter the 0, but will stay in the data entry mode. If a new
value is not entered, it will time out and the unit will continue to use its
previous setting.
CODE 61 - RESET BUTTON & TERMINAL ACTUATION MODES
Since there are three counters integrated intothe Gemini 3300,various modes are available to provide the desired reset response to the activation of the front panel Reset button, “R”, or rear “RST” terminal. The mode selected, determines which counter(s) will reset when the reset button or terminal is activated.
There are two ways the manual reset can act on the unit. The first is a “maintained” reset action, in which the unit is held reset as long as the reset button or terminal is activated. If the Process Counter is held in “maintained” reset, counting on all three counters will be inhibited. The second is a “momentary” action in which the unit resets and starts counting immediately, even though the reset button or terminal may still be activated. A “-” sign preceding the mode identifier indicates “momentary” reset action. The absence of a “-” sign indicates “maintained” reset action.
[61 1] RESET PROCESS COUNT ONLY [61 2] RESET BATCH COUNT ONLY [61 3] RESET PROCESS AND BATCH COUNT [61 4] RESET PROCESS, BATCH AND TOTAL COUNT
[61 -1] [61 -2] These modes are the same as above with the exception [61 -3] that reset is set for “Momentary” operation. [61 -4]
CODE 62 - PROCESS COUNTER RESET ACTION & PRESET TRACKING MODES
The “Process Counter Reset Action Mode” determines how the Process Counter can be reset and the type resetaction thatwill occur. In the manual reset modes, reset can only occurby activation of the Reset button, resetterminal (See “Reset Button & Terminal Actuation Modes” - Code 61), 2-button reset, or through serial communications. In the “Auto Reset” modes the Process Counter can be reset manually and canalso be resetwhen the ProcessCounter reaches the Preset 2 value, orzero,or after Timed Output 2,depending onthe mode selected.
A Preset tracking mode is also incorporated in Function Code 62. A “-” sign preceding the reset action mode indicates that Preset tracking is enabled. The absence of a “-” sign indicates that Preset tracking is disabled.
If Preset tracking is enabled, whenever the Preset 2 value is changed, the Preset 1 valuewill also change so that the offsetbetween Preset 2 and Preset 1 remains the same. The amount of offset is changed by changing the Preset 1 value. For example, if Preset 2 is 100 and it is desired that Preset 1 occurs 20 counts before Preset 2, thePreset 1 value would be set to 80. If Preset 2 is then changed to200, Preset 1 will automatically change to 180, maintaining the same 20 count offset.
The Preset 1 Value cannot be changed when Preset tracking is enabled and the “PGM.DIS.” (Program Disable) terminal isconnected to“COMMON”.
[62 1] MANUAL RESET TO ZERO - Manualreset to zero is accomplished by
pulling the “RST.” terminal to “COMMON” or, if the front panel reset is
enabled, bypressing the front panel resetbutton, or by using the “Two Button
Reset” (pressing the “E” key and the “1” key). Preset tracking is disabled. [62 2] MANUAL RESET TO PRESET 2 - Manual reset to Preset 2 is
accomplished by pulling the “RST.” terminal to “COMMON” or, if the
front panel reset is enabled, by pressing the front panel reset button, or by
using the “Two Button Reset” (pressing the “E” key and the “1” key).
Preset tracking is disabled. [62 3] AUTOMATIC RESET TO ZERO AFTER TIMED OUTPUT 2 - The
Process Counter automatically resets to zero when Timed Output 2 ends.
The “Output 2 Termination Mode” should be programmed for timed
output operation, [54 5], when in this mode. Preset tracking is disabled.
-12-
[62 4] AUTOMATIC RESET TO PRESET 2 AFTER TIMED OUTPUT 2 -
The Process Counter automatically resets to Preset 2 when Timed Output 2 ends. The “Output 2 Termination Mode” should be programmed for timed output operation, [54 5], when in this mode. Preset tracking is disabled.
[62 5] AUTOMATIC RESET TOZERO AT THEBEGINNING OF TIMED
OUTPUT 2 (AT PRESET 2) - In this reset mode, the Process Counter will automatically reset to zero at the beginning of Timed Output 2 (at Preset
2). The Timed Output 2 Value (Code 55) must be shorter than the time required for the counter to count to the Preset 2 Value, otherwise, Output 2 will appear to be latched on. The “Output 2 Termination Mode” should be programmed for timed output operation, [54 5], when in this mode. Preset tracking is disabled.
[62 6] AUTOMATIC RESET TO PRESET 2 AT THE BEGINNING OF
TIMED OUTPUT 2 (AT ZERO) -In this resetmode, the ProcessCounter will automatically reset to Preset 2 at the beginning of Timed Output 2 (at zero). The Timed Output 2 Value (Code 55) must be shorter than the time required for the counter to count to zero, otherwise, Output 2 will appear to be latched on. The “Output 2 Termination Mode” should be programmed for timed output operation, [54 5], when in this mode. Preset tracking is disabled.
[62 -1] [62 -2] [62 -3] These modes are the same as above with the exception [62 -4] that Preset Tacking is enabled. [62 -5] [62 -6]
CODE 63 - BATCH COUNTER RESET ACTION MODES
The “Batch Counter Reset Action Mode” determines how the Batch Counter can bereset and thetype reset action that willoccur. In themanual reset modes, the Batch Counter can only be reset by activation of the Reset button, reset terminal (See “Reset Button & Terminal Actuation Modes” - Code 61), 2-button reset, or through serial communications. In the “Auto Reset”modes,the Batch Countercan be reset manually and can also be reset when the Batch Counter reaches the Batch Preset value or zero (reset to Preset modes), or after the Batch Timed Output.
[63 1] MANUAL RESET TO ZERO - Manual reset to zero is accomplished
by pulling the “RST.” terminalto “COMMON”or, if the front panelreset is enabled, by pressing the front panel reset button, or by using the “Two
Button Reset” (pressing the “E” key and the “2” key).
[63 2] MANUAL RESET TO BATCH PRESET - Manual reset to Batch
Preset is accomplished by pulling the “RST.” terminal to “COMMON” or, if the front panel reset is enabled, by pressing the front panel reset button, or by using the “TwoButton Reset”(pressingthe “E” key and the“2”key).
[63 3] AUTOMATIC RESET TOZERO AFTER BATCH TIMED OUTPUT
- The Batch Counterautomatically resets to zero when Batch Timed Output ends. The “Batch Output Termination Mode” should be programmed for timed output operation, [64 5], when in this mode.
[63 4] AUTOMATIC RESET TO BATCH PRESET AFTER BATCH TIMED
OUTPUT - The Batch Counter automatically resets to Batch Preset when Batch Timed Output ends. The “Batch Output Termination Mode” should be programmed for timed output operation, [64 5], when in this mode.
[63 5] AUTOMATIC RESET TOZERO AT THE BEGINNING OFBATCH
TIMED OUTPUT (AT BATCH PRESET) - In this reset mode, the Batch Counter will automatically reset to zero at the beginning of Batch Timed Output (at Batch Preset). The Batch Timed Output Value (Code 65) must be shorter than thetime required for thecounter to count to theBatch Preset Value, otherwise, the Batch Output will appear to be latched on. The “Batch Output Termination Mode” should be programmed for timed output operation, [64 5], when in this mode.
[63 6] AUTOMATIC RESET TO BATCH PRESET AT THEBEGINNING OF
BATCH TIMED OUTPUT (AT ZERO) - In this reset mode, the Batch Counter will automatically reset to Batch Preset at the beginning of Batch Timed Output (at zero). The Batch Timed Output Value (Code 65) must be shorter than the time required for the counter to count to zero, otherwise, the Batch Output will appear to be latched on. The “Batch Output Termination Mode” should be programmed for timed output operation, [64 5], when in this mode.
CODE 64 - BATCH OUTPUT TERMINATION MODES
The Gemini 3300 has three “Batch Output Termination Modes”,which control the way Batch Output (OB) will terminate or reset. A Batch Output response will occurwhen the BatchCounter reaches theBatch Preset value or zero. In all modes, the Batch Output will terminate immediately when the Batch Counter is manually reset.
-13-
CODE 64 - BATCH OUTPUT TERMINATION MODES (Cont’d)
A reverse phase mode is available on the Gemini 3300. This refers to the complementing of the logic state of the output. With normal phase operation, when the Batch counter value reaches the BatchPreset, the Batch Output will turn on. The resetcondition of the BatchOutput isoutput off. In reversephase operation, the Batch Output turns off when the Batch Preset is reached. The reset condition of the Batch Output is output on. A “-” sign in front of the mode identifier will provide for reverse phaseoperation. The absence ofa “-” sign will indicate normal phase operation. [64 3] TERMINATE AT MANUAL RESET - The Batch Output (OB)
activates when theBatch Counterreaches the Batch Presetvalue or zero. In
this mode, once the Batch Output is activated, it does not deactivate until
the moment a manual reset of the Batch Counter occurs. The Batch Output
is set for normal phase operation. [64 4] TERMINATE AT MANUAL RESET END - This mode is like the
preceding, except the Batch Output (OB) deactivates when manual reset
ends. The Batch Output is set for normal phase operation. [64 5] TERMINATE AFTER TIMED BATCH OUTPUT - Once the Batch
Output (OB) hasbeen activated, it willdeactivate after the predetermined
length of time (Code 65) has expired. Manual reset will override the
timed output and reset the Batch Output. The Batch Output is set for
normal phase operation.
[64 -3] These modes are the same as above with the exception [64 -4] that the output is set for reverse phase operation. [64 -5]
CODE 65 - BATCH TIMED OUTPUT VALUE
The Gemini 3300 has the capability of varying the Batch Timed Output Value from 0.01 second to 599.99 seconds. Whenthe code is entered, instead of a single mode identifier digit being displayed, six digits will be shown. Refer to “Programming the Presets, Scale Factor, Timed Outputs & Counter Load Values” section for more details about entering. The timed output will be terminated if the Batch Counter is manually reset.
Note: ATimed Output Value of zerocannot be programmed into theGemini 3300.
If a value of 0is entered into the displayand the “E”key is pressed,the unit will
not enter the 0, but willstay in thedata entry mode.If a newvalue is not entered,
it will time out and the unit will continue to use its previous setting.
CODE 66 - “OPERATOR ACCESSIBLE FUNCTIONS” MODES
The Gemini 3300 hassix basiclevels of “Operator AccessibleFunctions”. Each of these levels can be modified to enable or disable manual reset. When the “PGM. DIS.” (Program Disable) terminal is connected to “COMMON”, access to all functions is disabled except for those listed below which will remain enabled. All ofthe function codes and parameters can be interrogated, regardless of the “Operator Accessible Functions” mode selected.
A “-” sign in front of the mode identifier will disable the front panel Reset button and the “RST.” terminal.
Note: The frontpanel reset button can beindependently disabled by usingthe
disable reset DIP switch.
[66 1] NOFUNCTIONS ENABLED EXCEPT RESET - In this mode, manual
reset is enabled, but none of the programming functions can be changed. [66 2] PRESET PROGRAMMING AND RESET ENABLED - In this mode,
manual reset and the programming of the Preset Values are enabled. [66 3] SCALE FACTOR PROGRAMMING AND RESET ENABLED - In
this mode, manual reset and the programming of the Scale Factor Value
are enabled. [66 4] SCALE FACTOR, PRESET PROGRAMMING AND RESET
ENABLED - In this mode, manual reset and the programming of the Scale
Factor and Preset Values are enabled. [66 5] PRESET, COUNTER LOAD PROGRAMMING, 2-BUTTON RESET
AND RESET ENABLED - In this mode,manual reset and the programming
of the Presets, Counter Load Values and 2-Button Reset are enabled. [66 6] PRESET, SCALE FACTOR, COUNTER LOAD PROGRAMMING,
2-BUTTON RESET AND RESET ENABLED - In this mode, manual reset
and the programming of the Presets, Scale Factor, Counter Load Values
and 2-Button Reset are enabled.
[66 -1] [66 -2] [66 -3] These modes are the same as above with the exception [66 -4] that manual reset (Reset Button & Terminal) is disabled. [66 -5] [66 -6]
-14-
Loading...
+ 36 hidden pages