INSTALLATION
Run wire to be monitored through opening in the sensor. The CTS Series
transducers work in the same environment as motors, contactors, heaters, pullboxes, and other electrical enclosures. They can be mounted in any position or
hung directly on wires with a wire tie. Just leave at least one inch (25.4 mm)
distance between sensor and other magnetic devices.
Split-Core Versions
Press the tab in the direction as shown to open the sensor. After placing the
wire in the opening, press the hinged portion firmly downward until a definite
click is heard and the tab pops out fully.
KEEP SPLIT-CORE SENSORS CLEAN.
Silicone grease is factory applied on the mating surfaces to prevent rust and
improve performance. Be careful not to allow grit or dirt onto the grease in the
contact area. Operation can be impaired if the mating surfaces do not have good
contact. Check visually before closing.
OUTPUT WIRING
Connect control or monitoring wires to the sensor. Use up to 14 AWG copper
wire and tighten terminals to 5 inch-pounds torque. Be sure the output load does
not exceed the switch rating.
CAUTION: Incandescent lamps can have “Cold Filament Inrush” current of up
to 10 times their rated amperage. Use caution when switching lamps.
SETPOINT ADJUSTMENT
CTS Series SETPOINT is adjusted with a 4-turn potentiometer (CTSS) or a
15-turn potentiometer (CTSF). The pot is shipped factory set to the lowest
setpoint, fully clockwise (CW). Turning the pot counter-clockwise (CCW) will
increase the setpoint. The pot has a slip-clutch to prevent damage at either end
of its rotation. To determine where the adjustment is, turn the pot all the way
CW. This will return it to the minimum setpoint.
Adjustment Notes:
1. Output contacts are solid-state. Check output status by applying voltage to the
contacts and reading the voltage drop across the contacts. An Ohmmeter set
on “Continuity” will give misleading results.
2. It is recommended that the setpoint be adjusted to allow for voltage variations
of 10-15%.
Typical Adjustment
1. Turn the pot to minimum setpoint (4 or 15 turns CW).
2. Have normal operating current running through the sensor. The output
should be tripped since the pot is at its minimum setpoint. For units with
LED, it should be flashing fast (2 to 3 times per second).
3. Turn the pot CCW until the unit un-trips. This is indicated by the slow
flashing of the LED (once every 2 to 3 seconds), or by the changing of
the output switch status.
4. Now turn the pot CW slowly until the unit trips again.
It is now set at the current level being monitored.
A. To Set UNDERLOAD - Turn the pot about 1/8 turn further CW.
B. To Set OVERLOAD - Turn the pot about 1/8 turn further CCW.
TROUBLE SHOOTING
1. Sensor Is Always Tripped
A. The setpoint may be too low. Turn pot CCW to increase setpoint.
B. Switch has been overloaded and contacts are burned out. Check the output
load, remembering to include inrush on inductive loads (coils, motors,
ballasts).
2. Sensor Will Not Trip
A. The setpoint may be too high. Turn pot CW to decrease setpoint.
B. Split Core models: The core contact area may be dirty. Open the sensor and
clean the contact area.
C. Monitored current is below minimum required. Loop the monitored wire
several times through the aperture until the “sensed” current rises above
minimum. Sensed Amps = (Actual Amps) x (Number of Loops). Count
loops on the inside of the aperture.
D. Switch has been overloaded and contacts are burned out. Check the output
load, remembering to include inrush on inductive loads (coils, motors,
ballasts).
DESCRIPTION
PART NUMBERS
CTS
.75 A Fixed-Core Current Switch, Go-No Go
1-150 A Fixed-Core Current Switch, Adjustable
CTSG0000
CTSF0000
CTSS0000
ORDERING INFORMATION
MODEL NO.
MONITORED AMPS OUTPUT SMART-LED
None or <Min. OPEN OFF
Below Trip Level OPEN SLOW (2 sec)
Above Trip Level CLOSED FAST (0.5 sec)
1.75-150 A Split-Core Current Switch, Adjustable
Toward Hinge.