Red Lion CTL User Manual

Bulletin No. CTL-C
C
EQ.
Drawing No. LP0652
Released 03/14
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL CTL - AVERAGE RESPONDING AC CURRENT TRANSDUCERS
AVERAGE RESPONDING OUTPUT: 0-10 VDC or 4-20 mA
JUMPER SELECTABLE RANGES
OUTPUT IS MAGNETICALLY ISOLATED FROM THE INPUT
SPLIT-CORE AND FIXED-CORE CASES
U
R
US LISTED
L
IND. CONT.
5T44
GENERAL DESCRIPTION
CTL Series transducers combine a current transformer and a signal conditioner into a single package. This provides higher accuracy, lower wiring costs, easier installation and saves valuable panel space.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators not equipped with safeguards. To do so, can be potentially harmful to persons or equipment in the event of a fault to the unit.
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
DIMENSIONS In inches (mm)
3.04
(77.2)
1.19
(30.2)
3.53
(89.7)
2.40 (61)
0.85
(21.6)
2.25
(57.2)
CAUTION: Risk of electric shock.
SPLIT-CORE
Ø 0.19
(4.8)
0.85
(21.6)
SPECIFICATIONS
0-10 VDC 4-20 mA
1. OUTPUT SIGNAL: 0-10 VDC 4-20 mA
2. OUTPUT LIMIT: 15 VDC 40 mA
3. FREQUENCY RANGE: 50-60 Hz 20-100 Hz
4. RESPONSE TIME: 100 msec 300 msec
5. ACCURACY:
6. POWER SUPPLY:
7. INPUT RANGES: (Jumper Selectable)
PART
NUMBER
CTL005
CTL050
CTL200
RANGE
_ _
_ _
_ _
2 A 125 A80 A 250 A
5 A 125 A100 A 250 A 10 A 20 A 50 A
100 A 300 A200 A 600 A 150 A 450 A300 A 800 A 200 A 500 A400 A 1000 A
8. ISOLATION VOLTAGE: 3 kV
9. CASE: UL 94V-0 Flammability rated thermoplastic
10. ENVIRONMENTAL: -4 to 122 °F (-20 to 50 °C) 0-95% RH, non-condensing
11. TORQUE RATINGS: 7 in-lbs on Fixed-core models; 9 in-lbs on Split-core models.
12. LISTING: UL 508 Industrial Control Equipment, CSA C22.2 No. 14-M95, and CE Certified.
DIMENSIONS In inches (mm)
Ø 0.19
(4.8)
2.18
(55.4)
1.0% FS 0.5% FS
Self-powered
80 A 110 A 175 A
24 VDC Nominal, 40 VDC max.
MAXIMUM
6 secContinuous 1 sec
125 A 150 A 215 A
FIXED-CORE
3.03
(77.0)
0.93
(23.6)
2.40
(61.0)
3.50
(88.9)
250 A 300 A 400 A
Ø 0.74
(19)
INSTALLATION
Important!
Keep Contact
Area CLEAN!
To Open
Press Tab
Toward Hinge.
Run wire to be monitored through opening in the sensor. The CTL Series transducers work in the same environment as motors, contactors, heaters, pull­boxes, and other electrical enclosures. They can be mounted in any position or hung directly on wires with a wire tie. Just leave at least one inch (25.4 mm) distance between sensor and other magnetic devices.
Split-Core Versions
Press the tab in the direction as shown to open the sensor. After placing the wire in the opening, press the hinged portion firmly downward until a definite click is heard and the tab pops out fully.
KEEP SPLIT-CORE SENSORS CLEAN.
Silicone grease is factory applied on the mating surfaces to prevent rust and improve performance. Be careful not to allow grit or dirt onto the grease in the contact area. Operation can be impaired if the mating surfaces do not have good contact. Check visually before closing.
OUTPUT WIRING
Connect control or monitoring wires to the sensor. Use up to 14 AWG copper wire and tighten terminals to 7 inch-pounds torque for solid-core models and 9 inch-pounds torque for split-core models. Be sure the output load or loop power requirements are met (see diagram).
POWER SUPPLY
VL = 12VDC + (RL× 0.020A)
25
20
15
10
5
Loop Power (VDC)
0
CONNECTIONS
4–20mA Option
Range Jumper
10 VDC Option
Range Jumper
= Minimum Loop Supply
where V
L
R
= Total Loop Resistance (Ohms)
L
250
500
Total Loop Impedance (Ohms)
24 VDC Power
(+)(–)
2(+)1(–)
Output
2(+)1(–)
Output
Operating Range
1000750
Load
(Controller,
(+)
Meter, etc.)
(–)
Notes: Captive screw terminals.
12–22 AWG solid or stranded. Observe polarity.
1M
Recommended
Acceptable (Add
100K
1.3% error for 100 K)
RANGE SELECT
CTL series transducers feature field selectable ranges. The ranges are factory
calibrated, eliminating time consuming and inaccurate field setting of zero or span.
1. Determine the normal operating amperage of your monitored circuit
2. Select the range that is equal to or slightly higher than the normal operating amperage.
3. Place the range jumper in the appropriate position.
TROUBLE SHOOTING
0-10 VDC OUTPUT MODELS
1. Sensor Has No Output
A. Polarity is not properly matched. Check and correct wiring polarity. B. Monitored load is not AC or is not on. Check that the monitored load is
AC and that it is actually on.
C. Split Core models: The core contact area may be dirty. Open the sensor and
clean the contact area.
2. Output Signal Too Low
A. The jumper may be set in a range that is too high for current being
monitored. Move jumper to the correct range.
B. Output load too low. Check output load, be sure that it is at least 100K
and preferably 1 MΩ.
C. Monitored current is below minimum required. Loop the monitored wire
several times through the aperture until the “sensed” current rises above minimum. Sensed Amps = (Actual Amps) x (Number of Loops). Count loops on the inside of the aperture.
3. Output Signal Is Always At Maximum
A. The jumper may be set in a range that is too low for current being
monitored. Move jumper to the correct range.
4-20 mA OUTPUT MODELS
1. Sensor Has No Output
A. Power supply is not properly sized. Check power supply voltage and
current rating. B. Polarity is not properly matched. Check and correct wiring polarity C. Split Core models: The core contact area may be dirty. Open the sensor and
clean the contact area.
2. Output Signal Too Low
A. The jumper may be set in a range that is too high for current being
monitored. Move jumper to the correct range. B. The load current is not sinusoidal. C. Monitored current is below minimum required. Loop the monitored wire
several times through the aperture until the “sensed” current rises above
minimum. Sensed Amps = (Actual Amps) x (Number of Loops). Count
loops on the inside of the aperture.
3. Sensor Is Always At 4 mA
A. Monitored load is not AC or is not on. Check that the monitored load is
AC and that it is actually on.
4. Output Signal Is Always At 20 mA
A. The jumper may be set in a range that is too low for current being
monitored. Move jumper to the correct range.
ORDERING INFORMATION
TYPE MODEL NO. DESCRIPTION PART NUMBER
CTL12S 2-5 A / 4-20 mA CTL0052S
SPLIT CORE
FIXED CORE
4-20 mA
FIXED CORE
0-10 VDC
CTL52S 10-50 A / 4-20 mA CTL0502S
CTL22S 100-200 A / 4-20 mA CTL2002S
CTL52F 10-50 A / 4-20 mA CTL0502F
CTL22F 100-200 A / 4-20 mA CTL2002F
CTL51F 10-50 A / 10 VDC CTL0501F
CTL21F 100-200 A / 10 VDC CTL2001F
Red Lion Controls Headquarters 20 Willow Springs Circle York PA 17406 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839
Red Lion Controls
Europe
Softwareweg 9
NL - 3821 BN Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India 201-B, 2nd Floor, Park Centra Opp 32 Mile Stone, Sector-30
Gurgaon-122002 Haryana, India
Tel +91 984 487 0503
Red Lion Controls
China
Unit 302, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113 3688
Fax +86 21 6113 3683
Loading...