red lion CSMSTRSX, CSMSTRGT User Manual

Bulletin No. CSMSTRSX-F
5.30
(134.7)
RS232
ETHERNET
CF
STS
USB/PG
RS485
RS232/PG
3.09 (78.5)
4.15 (105.4)
C
US LISTED
Drawing No. LP0610 Released 11/09
MODELS CSMSTRSX AND CSMSTRGT – ENHANCED MODULAR CONTROLLER SERIES MASTER
PROVIDES ENHANCED FEATURES FOR DATA ACQUISITION
OR MULTI-ZONE PID CONTROL APPLICATIONS
WEBSERVER PROVIDES WORLDWIDE ACCESS TO DATA
LOGS AND VIRTUAL HMI
VIRTUAL HMI OFFERS BUILT-IN PC-BASED SCADA
FUNCTIONALITY
PERFORMS HIERARCHICAL CONTROL OF OTHER MODULES
STORES MODULE CONFIGURATION INFORMATION, AND
AUTOMATICALLY REPROGRAMS REPLACED MODULES
EXTENSIVE BUILT-IN DRIVER LIST ALLOWS EASY DATA
MAPPING TO PLCs, PCs, AND SCADA SYSTEMS
INDEPENDENT SERIAL PORTS PROVIDE VIRTUALLY
UNLIMITED INTEGRATION METHODS
10 BASE-T/100 BASE-TX ETHERNET CONNECTION PROVIDES
NETWORKING CAPABILITY
U
R
C
L
US LISTED
IND. CONT. EQ.
34AD
SUPPORTS UP TO 16 MODULAR CONTROLLER SERIES
MODULES
COMPACTFLASH
®
SLOT ALLOWS PROCESS DATA TO BE
LOGGED DIRECTLY TO CSV FILES
GENERAL DESCRIPTION
The Model CSMSTR is a communications and control platform designed for use with Modular Controller Series slave modules. The CSMSTR uses a proprietary high speed serial protocol to communicate, via backplane connection, with up to 16 slave modules. Through the same connection, the Master also provides power to the modules.
When powered up, the CSMSTR automatically identifies and addresses connected slave modules. By storing the configuration information of all of the modules, the CSMSTR is able to automatically configure modules if they are replaced.
The Master provides high-speed RS232/422/485 communication ports and an Ethernet port for connection to PCs, PLCs, and SCADA systems. An extensive list of master and slave protocol drivers are available to allow the CSMSTR to share and exchange variable data with external devices. The 10 Base-T/100 Base-TX Ethernet port can also be used to connect and share data with other devices at high speeds. The virtual HMI feature allows you to create and control an HMI from any networked PC. An onboard CompactFlash slot provides storage for the Master’s built-in data logger.
DIMENSIONS In inches (mm)
The design of the Modular Controller Series high density packaging and DIN rail mounting saves time and panel space. The controller snaps easily onto standard top hat (T) profile DIN rail.
SOFTWARE
The CSMSTR is programmed with Crimson 2.0 software for Windows® 2000 or later platforms. The software is an easy to use, graphical interface which provides a means of communication configuration, as well as commissioning and calibration of new systems.
CONTENTS OF PACKAGE
- CS Master
- Termination Plug
- Terminal Block for connecting power
- Rubber End Cap
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the controller. An independent and redundant temperature limit indicator with alarm outputs is strongly recommended.
CompactFlash is a registered trademark of CompactFlash Association.
1
Read complete instructions prior to installation
CAUTION: Risk of Danger.
and operation of the unit.
SPECIFICATIONS
1. POWER: 24 VDC ± 10%
400 mA min. (1 module)
3.5 Amps max. (16 modules + Expansion Card) Must use NEC Class 2 or Limited Power Source (LPS) rated power supply.
2. COMMUNICATIONS: USB/PG Port: Adheres to USB specification 1.1. Device only using Type B
connection.
Serial Ports: Format and Baud Rates for each port are individually software
programmable up to 115,200 baud.
RS232/PG Port: RS232 port via RJ12 COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12 DH485 TXEN: Transmit enable; open collector, V
VOL = 0.5 V @ 25 mA max.
Note: For additional information on the communications or signal common
and connections to earth ground please see the “Connecting to Earth Ground” in the section “Installing and Powering the CSMSTRSX.”
Ethernet Port: 10 BASE-T / 100 BASE-TX
RJ45 jack is wired as a NIC (Network Interface Card).
3. LEDs: STS – Status LED indicates condition of master. TX/RX – Transmit/Receive LEDs show serial activity. Ethernet – Link and activity LEDs. CF – CompactFlash LED indicates card status and read/write activity
4. MEMORY: On-board User Memory: 4 Mbytes of non-volatile Flash memory. On-board SDRAM:
CSMSTRSX: 2 Mbytes CSMSTRGT: 8 Mbytes
Memory Card: CompactFlash Type II slot for Type I and Type II cards.
5. REAL-TIME CLOCK: Typical accuracy is less than one minute per month drift. Crimson 2.0’s SNTP facility allows synchronization with external servers. Battery: Lithium Coin Cell. Typical lifetime of 10 years at 25 ºC.
A “Battery Low” system variable is available so that the programmer can
choose specific action(s) to occur when the battery voltage drops below its nominal voltage.
This unit is NOT field serviceable. All work must be done by a qualified technician.
6. ENVIRONMENTAL CONDITIONS: Operating Temperature Range: 0 to 50°C Storage Temperature Range: -30 to +70°C Operating and Storage Humidity: 80% max relative humidity,
non-condensing, from 0 to 50°C
Vibration According to IEC 68-2-6: Operational 10 to 150 Hz, 0.075 mm
amplitude in X, Y, Z direction for 1.5 hours, 1 g.
= 15 VDC,
OH
Shock According to IEC 68-2-27: Operational 25 g's, 11 msec in 3 directions. Altitude: Up to 2000 meters
7. CONSTRUCTION: Case body is burgundy high impact plastic and stainless
steel. For indoor use only. Installation Category II, Pollution Degree 2.
8. POWER CONNECTION: Removable wire clamp screw terminal block.
Wire Gage Capacity: 24 AWG to 12 AWG Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)
9. MOUNTING: Snaps onto standard DIN style top hat (T) profile mounting
rails according to EN50022 -35 x 7.5 and -35 x 15.
10. CERTIFICA TIONS AND COMPLIANCES:
SAFETY
UL Listed, File #E302106, UL508, CSA 22.2 No. 14-M05 and File #E179259,
UL61010-1, CAN/CSA-C22.2 No. 61010-1 LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
IECEE CB Scheme Test Report #E179259-A5-CB-1
Issued by Underwriters Laboratories Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: 2006: Electrical Equipment for Measurement, Control and Laboratory use.
Immunity to Industrial Locations: Electrostatic discharge EN 61000-4-2 Criterion B
4 kV contact discharge
Electromagnetic RF fields EN 61000-4-3 Criterion B
8 kV air discharge
3
10 V/m
Fast transients (burst) EN 61000-4-4 Criterion B
power 2 kV
I/O signal connected to power
I/O signal
1 kV 2 kV
Surge EN 61000-4-5 Criterion B
power
1kV L-L,2 kV L-G
signal
1kV
RF conducted interference EN 61000-4-6 Criterion A
3 V/rms
Emissions:
Emissions EN 55011 Class A
Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: T emporary loss of performance fr om which the unit self-r ecovers.
3. The modules with analog input and/or output signals may have their signals deviate during disturbance but self-recover when disturbance is removed.
11. WEIGHT: 15.1 oz (456.4 g)
ORDERING INFORMATION
TYPE MODEL NO. DESCRIPTION PART NUMBER
Modular Controller Master, Comms, Ethernet CSMSTRV2 Modular Controller Master with multiple protocol converter, data logger, web server with Virtual
Master Module CSMSTR
Communications
Cables (10 feet)
Software SFCRM2 Crimson 2.0
Power Supply PSDR DIN Rail Mounted Power Supply PSDRxxxx
Accessories
1
Visit www.redlion.net for a complete list of PID modules, data acquisition modules, communications drivers and cables.
2
Use this part number to purchase Crimson on CD with a printed Modular Controller Manual, USB cable, and RS-232 cable. Otherwise, download free of charge from
www.redlion.net.
3
Industrial grade two million write cycles. SMART Modular Technologies model SG9CF (UL Listed Directory Category NWGQ).
1
HMI up to QVGA (320 x 240) size and expansion slot. Modular Controller Master with multiple protocol converter, data logger, web server with Virtual
HMI up to VGA (640 x 480) size and expansion slot with increased SDRAM. RS232 Programming Cable CBLPROG0
CBL
XCCN CANopen option card for Modular Controller or Data Station Plus XCCN0000 XCDN DeviceNet option card for Modular Controller or Data Station Plus XCDN0000 XCPB PROFIBUS option card for Modular Controller or Data Station Plus XCPBDP00 XCRS RS232/485 option card for Modular Controller or Data Station Plus XCRS0000 G3CF CompactFlash Card
USB Cable CBLUSB00 Communications Cables
Rail Stops (Qty 2) RSRSTP00 Replacement Base CSBASE00 Replacement Termination Plug CSTERM00 Replacement Rubber End Cap CSBUNG00
2
, Modular Controller Manual, and Download Cable SFCRM2MC
1
3
CSMSTRSX
CSMSTRGT
CBLxxxxx
G3CFxxxx
2
HARDWARE
CompactFlash
(Top Side)
CompactFlash­Insert Top Side Towards Left
INSTALLATION
DIN rail should be mounted horizontally so that the unit’s ventilation holes are vertical in relation to cabinet orientation. A minimum clearance of 1 inch (25.4 mm) should be maintained above and below the unit in order to ensure proper thermal regulation.
The unit shall be installed inside a UL Listed Industrial Control Panel or similar type of enclosure. A minimum 3.2 mm distance shall be maintained between the hazardous live parts of the equipment and accessible parts of the fire/electrical enclosure.
1
2
REMOVE
1.00"
min. clearance
1.00"
min. clearance
STS
CF
TOP
RS232/PG
USB/PG
RS485
RS232
ETHERNET
DEPRESS
3
4
4
BOTTOM
Figure 2 - Attach Slave Bases To DIN Rail
DIN RAIL
Figure 1 - Attach CSMSTR Master To DIN Rail and Remove
Rubber End Cap
RS232/PG
STS
USB/PG
CF
RS485
RS232
ETHERNET
5
DIN RAIL
Figure 3 - Attach Termination Plug*
* Supplied with CSMSTR Master Module.
PROTOCOL CONVERSION
Mount the Master as shown under Hardware Installation Figure 1 above. Install the rubber end cap. The end cap protects the pins from damage. Configure the Master for zero modules.
RS232/PG
STS
USB/PG
CF
RS485
RS232
ETHERNET
DIN RAIL
Figure 4 - Installation Complete
COMPACTFLASH® CARD
CompactFlash socket is a Type II socket that can accept either Type I or II cards. Use cards with a minimum of 4 Mbytes and a maximum of 2 Gbytes with the Master’s CompactFlash socket. Cards are available at most computer and office supply retailers. CompactFlash can be used for configuration transfers, data logging, and trending.
For reliable operation of this and other Red Lion products, one of the
following brands of CompactFlash card must be used...
SimpleTech SMART® Modular
®
SanDisk
Silicon Systems
NOTE
Not all of the above manufacturers offer CompactFlash cards recognized
to UL standards, which may be required for your application.
Note: Do not remove or insert
the CompactFlash card while power is applied.
Information stored on a CompactFlash card can be read by a card reader attached to a PC. This information is stored in IBM (Windows
®
) PC compatible
FAT16 file format.
3
Loading...
+ 4 hidden pages