Red Lion Converter Modules User Manual

Tel +1 (717) 767-6511
(SEE ORDERING INFORMATION FOR WIRE COLOR)
BLACK
OUTPUT LEADS: 6" (150mm) Long 22GA Stranded, 300V Insulation
INPUT LEADS: 6"(150mm) Long, 22GA. VCM and TCM Leads have 600V Insulation. LCM has 3 Leads with 300V Insulation. (For color codes see specific model.)
1.12 (28.5)
1.52 (38.5)
0.71 (18)
0.45
(11.5)
SELF STICK ADHESIVE PAD
OUTPUT
INPUT
Fax +1 (717) 764-0839 www.redlion.net
CONVERTER MODULES
ADAPTS MANY RED LION CONTROLS’ COUNTERS AND ACCESSORIES
TO A WIDE RANGE OF SIGNAL SOURCES
Bulletin No. VCM-A Drawing No. LP0646 Released 02/10
VCM - VOLTAGE CONVERTER MODULES
Converts AC/DC voltages to an acceptable signal input for many RLC counters and accessories and provides input/output voltage isolation.
TCM - TRIAC CONVERTER MODULE
Accepts unloaded, high off-state leakage triac output from sensors and programmable controllers.
LCM - LOGIC CONVERTER MODULE
Interfaces with CMOS, TTL, and other logic circuits up to +28 VDC, at speeds to 50 KHz. Allows Cub Counters to share sensor outputs with other series counters.
These miniature sized modules are completely encapsulated in PVC, which provides protection against oil, water, dirt, and mechanical damage. They can be quickly and easily mounted to most surfaces by using the self-stick adhesive pad.
VCM - VOLTAGE CONVERTER MODULES
These modules provide a convenient way to adapt RLC Counters to most any machine control voltage signal. They also make it easy to upgrade electro­mechanical counter installations with RLC Counters.
VCM’s are available in two input voltage ranges that cover the spectrum from 4-270 V. The non-polarized input of these modules will accept A.C. (50/60 Hz) or D.C. voltages at input cycles up to 30 Hz. The output uses MOSFET technology that is compatible with either the L.S. Count or Remote Reset inputs of RLC Counters. Electrical isolation between input and output is achieved by means of an internal opto-isolator rated at 2300 VRMS.
DIMENSIONS FOR VCM, TCM, & LCM In inches (mm)
SPECIFICATIONS
1. INPUT: VCM1 = 4 to 50 VAC/DC, 50/60 Hz
2. OUTPUT: Solid state DC contact closure
3. FREQUENCY: Max output frequency 20 Hz
4. ENVIRONMENT: 0-50 ºC
VCM2 = 50 to 270 VAC/DC, 50/60 Hz
Output rating: 30 VDC at 100 mA max Output Isolation: 2300 V Off State Leakage: 1 A max
RMS
1
TCM - TRIAC CONVERTER MODULE
CUB CONTROLLER
COMMON
RST. EN.
REM. RST.
L.S. CNT.
H.S. CNT.
BLUE
OR
BLK
TO EXT. D.C. SUPPLY +5 TO 28VDC, 8mA
INPUT COUNT PULSE V = 2.5 TO 28VDC V = +1.0V
COMMON
IH
IL
WHITE
BLACK
ALTERNATE CONNECTION FOR SWITCH CONTACT INPUT (SEE TEXT)
INPUT
OUTPUT
INPUT
OUTPUT
OUTPUT
INPUT
RELAY COIL
EXISTING CONTACT USED TO OPERATE RELAY
MACHINE CONTROL VOLTAGE
RESET CONTACT
MACHINE CONTROL VOLTAGE
ORANGE
ORANGE
ORANGE
ORANGE
BLACK
BLACK
COUNT
VCM/TCM
VCM/TCM
RESET
REMOTE
RLC COUNTER
COUNT
RESET
COMMON
SEE ORDERING INFORMATION FOR WIRE COLOR
SEE ORDERING INFORMATION FOR WIRE COLOR
The TCM is a specialized version of the VCM. It is specifically designed to operate with photo-electric sensors and programmable controllers that have 115 VAC Triac outputs. Due to protective suppression circuits connected in parallel with Triacs, these outputs have a high OFF-State Leakage current, which, if unloaded, is sufficient to keep a VCM in the ON condition continuously.
The TCM incorporates a current bias that offsets output leakage currents up to 4 mA and allows the application of RLC Counters to most unloaded Triac outputs. These modules are available for operation with 115 VAC ±10% 50/60 Hz only. They operate at count rates up to 10 cps, and also provide input/output electrical isolation. Connections for the TCM are the same as those for the VCM.
Note: VCM’s can be used with Triac outputs that are also driving substantial
loads, since the load will shunt the leakage current away from the VCM input.
TYPICAL CONNECTION EXAMPLE FOR VCM & TCM
(Shown with optional VCM for Control Voltage Remote Reset)
Consult Connections and Configurations set up information in counter instruction literature for wiring. Reference switch and contact input information.
SPECIFICATIONS
1. INPUT: 115 VAC 10% (50/60 Hz) 10 mA max current draw
2. FREQUENCY: 10 Hz max output
3. OUTPUT: Solid state DC contact closure
Output rating: 30 VDC at 100 mA Output Isolation: 2300 V Off State Leakage: 1 A max
4. ENVIRONMENT: 0-50 ºC
RMS
LCM - CONVERTER MODULE
The LCM adapts CUB* Counters to practically any type of logic and sensor output, and to any count signal voltage from +3 to +28 VDC. The module accepts input count pulses from NPN Open-Collector Transistor outputs, Bi-Polar outputs, or sourcing outputs such as Emitter-Follower or PNP Open­Collector Transistors (Sourcing outputs must be externally loaded with a load of 10 Kohms or less). The LCM output is a Bi-Polar drive that is compatible with either the Low-Speed or High-Speed Counter inputs as well as the Remote Reset input** of the CUB Counters. The output is inverted with respect to the input which causes the CUB Counter to increment on the leading (positive going) edge of a count pulse. Power for operation of the LCM can be normally obtained from the existing D.C. power supply used to operate the sensor or other logic circuitry. When count pulse signals are generated by switch contacts the LCM output can be applied to the L.S. input of the CUB to de-bounce these pulses. Minimum pulse width when driving the L.S. input is 10 msec and maximum count rate is 50 cps.
* LCM intended for use with CUB1,2,3,and 7. ** When used to operate Remote Reset input, the LCM will reset counter when
input to LCM goes high due to signal inversion.
SPECIFICATIONS
1. POWER: 5 to 28 VDC, 8 mA max
2. INPUT: V
3. OUTPUT: Bipolar 3 VDC with 1 mA sink/source (output should not be
connected to voltage levels above 3.5 VDC)
4. FREQUENCY: MAX input/output frequency = 50 KHz (see counter input
for frequency limitations)
5. ENVIRONMENT: 0-50 ºC
2
= +2.5 to 28 VDC, 500 A max source
IH
VIL = +1.0 VDC, 50 A max sink