Red Lion AFCM Data Sheet

MODEL AFCM - ANALOG TO FREQUENCY CONVERTER MODULE
VOLTAGE/CURRENT TO FREQUENCY CONVERTER
3-WAY ISOLATION OF INPUT / OUTPUT SIGNALS
UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS
SELECTED VIA DIP SWITCH SETTINGS
ULTRA SLIM DESIGN – ONLY 0.244" WIDE
19 to 30 VDC POWER
UL Recognized Component, File # E257265
DESCRIPTION
The DIP switches are accessible on the side of the housing and allow the following parameters to be configured:
– Input signal
– Output values
– Output type (frequency or PWM)
– Filter type (for smoothing interferences on the input signal)
– Input over/under range fault detection
DIMENSIONS In inches (mm)
0.24
(6.2)
1
5
6
7
S1
S2
8
OFF
ON
1
8
1
1
2
2
4.00
3
(102.5)
8
4
3
4
SAFETY SUMMARY
The device may only be installed and put into operation by qualified personnel.
The corresponding national regulations must be observed.
CAUTION: Risk of Danger.
Read complete instructions prior to
installationand operation of the unit.
CAUTION: Risk of electric shock.
SPECIFICATIONS
INPUT
1. INPUT SIGNAL RANGE (Configurable): 0 - 20 mA, 4 - 20 mA, 0 - 10 mA, 2 - 10 mA, 0 - 10 V, 2 - 10 V, 0 - 5 V, 1 - 5 V
2. MAX. INPUT SIGNAL: Current inputs: 100 mA Voltage inputs: 30 VDC
3. INPUT RESISTANCE: Current inputs: 50 , approx. Voltage inputs: 110 K, approx.
OUTPUT
1. OUTPUT SIGNAL RANGE (Configurable): Frequencies: 0 - 10 kHz, 0 - 5 kHz, 0 - 2.5 kHz, 0 - 1 kHz, 0 - 500 Hz 0 - 250
Hz, 0 - 100 Hz, 0 - 50 Hz
PWM: 7.8 kHz, 3.9 kHz, 1.9 kHz, 977 Hz, 488 Hz, 244 Hz, 122 Hz, 61 Hz
2. MIN. LOAD: Frequency: 6 K PWM: 2 K
3. MAX. LOAD CURRENT: 20 mA
4. OUTPUT: NPN open collector transistor
5. MAX. SWITCHING VOLTAGE: 30 V
6. OVER-RANGE/UNDER-RANGE FAULT DETECTION: Configurable
7. OUTPUT PROTECTION: Short circuit and polarity protection
3.66 (93.1)
ORDERING INFORMATION
DESCRIPTIONMODEL NO.
Analog to Frequency Converter Module AFCM
PART NUMBER
AFCM0000
GENERAL DATA
1. SUPPLY VOLTAGE: 19.2 - 30 VDC
2. NOMINAL VOLTAGE: 24 VDC
3. CURRENT CONSUMPTION: < 10 mA
4. POWER CONSUMPTION: < 200 mW
5. TRANSMISSION ERROR: < 0.1% of full scale
6. TEMPERATURE COEFFICIENT (MAX.): < 0.02%/K
7. STEP RESPONSE: 0% to 99%: < 15 msec + (1/T) With Largest Filter: < 1 sec + (1/T)
8. TEST VOLTAGE (INPUT / OUTPUT / SUPPLY): 1.5 kV, 50 Hz, 1 min
9. AMBIENT TEMPERATURE RANGE: Operation: -20 to +65°C (-4 to 148°F) Storage: -40 to +85°C (-4 to 183°F)
10. FAULT DETECTION: Red LED under clear cover top
11. CERTIFICATIONS AND COMPLIANCES:
Conformance With EMC Guideline 2014/30/EU
Immunity to Interference According to EN 61000-6-2
Discharge of static electricity (ESD) EN 61000-4-2 Criterion B Electromagnetic HF field EN 61000-4-3 Criterion A Fast transients (Burst) EN 61000-4-4 Criterion B Surge voltage capacities (Surge) EN 61000-4-5 Criterion B Conducted disturbance EN 61000-4-6 Criterion A
Noise Emission According to EN 61000-6-4
Noise emission of housing EN 55011 Class A
1
Criterion B: Temporary impairment to operational behavior that is corrected
by the device itself.
2
Criterion A: Normal operating behavior within the defined limits.
3
Class A: Area of application; industry.
1
2
1
1
2
3
12. CONNECTIONS: Wire Gauge: 24-12 AWG Stripping length: 0.47" (12 mm)
13. CONSTRUCTION: Polybutylenterephthalate PBT, black
14. MOUNTING: Standard DIN top hat (T) profile rail according to EN50022
- 35x7.5
15. WEIGHT: 2 oz. (54 g)
WIRING CONNECTIONS
Primary power is
connected to terminals 7 or 3 (19.2 – 30 VDC) and 8 or 4 (GND 3). For best results, the Power should be relatively
INPUT
COMM
GND 2
19.2...30VDC
GND 3
Out f
5
6
7
8
1
In U,I
2
3
GND 1
19.2...30VDC
GND 3
4
POWER
“clean” and within the specified variation limits. Drawing power from heavily loaded circuits or from
RECEIVING DEVICE SET UP FOR
SINK (PULL UP RESISTOR).
circuits that also power loads that cycle on and off, should be avoided.
The input signal is
connected to terminal 1 (In UI) and 2 (GND
1). Connections for
the output signal is on
INPUT
19.2...30VDC
COMM
GND 2
GND 3
Out f
5
6
7
8
1
In U,I
2
3
GND 1
19.2...30VDC
GND 3
4
POWER
terminals 5 (Out f) and 6 (GND 2).
RECEIVING DEVICE SET UP FOR
SOURCE (PULL DOWN RESISTOR).
CONFIGURATION
DIP Switch S1
Using DIP switch S1, you can set the input values, and the values for Moving
Average Filter and Over sampling.
1 2 3 4 ANALOG IN
0 – 10V
ON 1 – 5V
ON 0 – 5V
ON
ON ON 0 – 20 mA
ON ON ON 4 – 20 mA
ON ON ON 0 – 10 mA
ON ON ON ON 2 – 10 mA
The moving average filter can group
values (1, 2, 4, 6) using moving window averaging to form a new measured value. In moving window averaging, the average of a fixed number of measured values is taken, whereby the oldest value is always dropped and the most recent added.
ON 2 – 10V
5 6
ON 2 values
ON 4 values
ON ON 6 values
MOVING WINDOW
AVERAGING
1 value
7 8
OVER SAMPLING
1 value
ON 10 values
ON 50 values
ON ON 100 values
In order to smooth the measured values, an average can be formed from several measured values (1, 10, 50, 100). This process is called Over sampling. In oversampling, the average is updated every time the selected number of values is reached.
DIP Switch S2
Using DIP switch S2, you can set the output values, the output type and fault
detection.
Output Signals
Frequency Output:
Variable frequency/period duration T
PWM Output (Pulse Wide Modulation):
Variable pulse to pause ratio/fixed
period duration T
Change can only be read by PWM
input meters.
1 2 3 4
ON 0 - 5 kHz
ON 0 – 2.5 kHz
ON ON 0 - 1 kHz
ON 0 - 500 Hz
ON ON 0 - 250 Hz
ON ON 0 - 100 Hz
ON ON ON 0 - 50 Hz
1 2 3 4
ON ON 3.9 KHz
ON ON 1.9 KHz
ON ON ON 977 Hz
ON ON 488 Hz
ON ON ON 244 Hz
ON ON ON 122 Hz
ON ON ON ON 61 Hz
FREQUENCY
OUTPUT
0 - 10 kHz
PWM
OUTPUT
ON 7.8 KHz
Fault Detection
5 6 INPUT OVER RANGE
Freeze at 100% measuring range end value
ON 105% measuring range end value
ON 110% measuring range end value
ON ON
7 8 INPUT UNDER RANGE
Fault detection OFF (continues past end value)
Freeze at 100% measuring range start value
ON 105% measuring range end value
ON 110% measuring range end value
ON ON Fault detection OFF (stops at start value)
INSTALLATION
The unit is equipped with a universal mounting foot for attachment to standard DIN style top hat (T) profile rail according to EN50022 - 35 x 7.5 and 35 x 15. The unit should be installed in a location that does not exceed the maximum operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided.
T Rail Installation
To install the AFCM on a “T” style rail, angle the module so that the top groove of the “foot” is located over the lip of the top rail. Push the module toward the rail until it snaps into place. To remove a module from the rail, insert a screwdriver into the slot on the bottom of the “foot”, and pry upwards on the module until it releases from the rail.