RED COMPACT SLIM 15, COMPACT 14-2015 Installation Manual

Page 1
INSTALLATION GUIDE GB
Translation of original instructions
PELLET BOILER
COMPACT SLIM 15
Page 2
II
TABLE OF CONTENTS
INTRODUCTION ............................................................................................. 1
1WARNINGS AND WARRANTY CONDITIONS ...................................................... 2
2INSTALLATION INSTRUCTIONS ..................................................................... 9
3DRAWINGS AND TECHNICAL CHARACTERISTICS .............................................19
4  UNPACKING ............................................................................................22
5  POSITIONING ..........................................................................................23
6  PANEL REMOVAL ......................................................................................26
7  HYDRAULIC CONNECTION ..........................................................................34
8  ELECTRICAL CONNECTION .........................................................................40
9  FIRST STARTUP ......................................................................................42
10  MENU ITEMS AND FUNCTION ...................................................................46
11  SAFETY DEVICES AND ALARMS .................................................................61
12RECOMMENDATIONS FOR A SAFE USE .........................................................65
13  MAINTENANCE AND CLEANING .................................................................66
14  TROUBLESHOOTING ................................................................................74
15  ELECTRICAL PLAN ..................................................................................77
Page 3
1
INTRODUCTION
Technical Dept. - All rights reserved - Reproduction is prohibited
Dear Customer, Our boilers are designed and built in compliance with the European standard EN 303-5 (manual or automatic loading solid fuel boilers). They also meet the essential requirements of directive 2006/95/EC (Low Voltage) and directive 2004/108/EC (Electromagnetic Compatibility).
To get the best performance out of your boiler, we suggest you read the instructions in this manual carefully before starting it up for the rst time.
This installation and use manual forms an integral part of the product: ensure that the manual is always supplied with the device, even if the boiler changes owner. If the manual is lost, you can request another copy from the local technical service or download it directly from the company website. All local regulations, including those regarding national and European regulations, must be respected when the device is installed. In Italy, for the installation of devices with biomass lower than 35KW, refer to ministerial decree 37/08, and the qualied installation technician with the appropriate requisites must issue a certicate of compliance for the system installed.
REVISIONS TO THE PUBLICATION
The content of this manual is strictly technical and the property of MCZ Group Spa. No part of this manual may be translated into other languages, adapted or reproduced, even in part, in other mechanical or electronic forms, photocopies, recordings or other, without the prior written authorisation from MCZ Group Spa. The company reserves the right to make changes to the product at any time without prior notice. The proprietary company reserves its rights according to the law.
CARE OF THE MANUAL AND HOW TO CONSULT IT
Take care of this manual and keep it in an easily accessible place.
Should the manual be misplaced or ruined, request a copy from your retailer or directly from the authorised Technical Assistance Department. It can be downloaded from the company website.
The "text in bold" must be read with particular care.
The "text in italics" draws attention to other sections in this manual or clarications.
“NOTE” provides the reader with additional information.
SYMBOLS USED IN THE MANUAL
ATTENTION: Read the relative message with care as failure to observe the information provided could result in serious damage to the product and put the persons who use it at risk.
INFORMATION:
failure to comply with these provisions will compromise the use of the product.
OPERATING SEQUENCES:
sequence of buttons to be pressed to access the menus or change settings.
MANUAL
carefully read this manual or the relative instructions.
Page 4
2
1-WARNINGS AND WARRANTY CONDITIONS
SAFETY PRECAUTIONS
Installation, electrical connection, function test and maintenance must only be carried out by authorised and qualied personnel.
Install the product in accordance with all local and national legislation and regulations in force in the region or state.
A bad use or unproper maintainance of the product can bring to a serious risk of explosion in the combustion chamber.
Only use the fuel recommended by the manufacturer. The product must not be used as an incinerator.
It is strictly forbidden to use alcohol, petrol, liquid fuel for lanterns, diesel, bio­ethanol, uids for lighting charcoal or similar liquids to light/rekindle the ame in these devices. Keep these ammable liquids well away from the appliance when in use.
Do not put any fuel other than wood pellets in the hopper.
The instructions provided in this manual must always be complied with to ensure the product and any electronic appliances connected to it are used correctly and accidents are prevented.
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
The user, or whoever is operating the product, must read and fully understand the contents of this installation guide before performing any operation. Errors or incorrect settings can cause hazardous conditions and/or poor operation.
Do not climb on or lean on the product.
Do not put linen on the product to dry. Any drying racks or similar objects must be kept at a safe distance from the product. Fire hazard.
All liability for improper use of the product is entirely borne by the user and relieves the Manufacturer from any civil and criminal liability.
Page 5
3
1-WARNINGS AND WARRANTY CONDITIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
Any type of tampering or unauthorised replacement with non-original spare parts could be hazardous for the operator’s safety and relieves the company from any civil and criminal liability.
Many of the surfaces of the product get very hot (door, handle, glass, smoke extraction pipes, etc.). Avoid coming into contact with these parts
without adequate protective clothing or suitable means, such as gloves with thermal protection or “cold handle” operating systems.
It is forbidden to operate the product with the door open or the glass broken.
The doors/covers on the appliance must remain closed when it is not used.
The product must be powered by an electrical system that is equipped with an eective earthing device.
Switch the product o in the event of a fault or malfunction.
Accumulated unburned pellets in the burner after each “failed start-up” must be removed before lighting again. Check that the burner is clean and positioned properly before lighting again.
Shut the stove down in the event of a breakdown or bad running and contact the engineer immediately.
Pellets must not be fed manually into the burner – this wrong behaviour can generate an abnormal amount of unburned gas, with a risk of explosion in the chamber.
Accumulated unburnt pellets in the burner after a failed ignitions must be removed before lighting.
Failure too clean and maintain the brazier can result in improper running and explosions within the stove. Make sure you remove and clear the holes in the brazier and any loose encrustations every time you empty the ash from the stove or every time you have a failed ignition.Make sure that the holes in the brazier are never reduced in size as this will aect the safe performance of the stove if not maintained.
Do not wash the product with water. The water could get inside the unit and damage the electrical insulation and cause electric shocks.
Page 6
4
1-WARNINGS AND WARRANTY CONDITIONS
A carbon monoxide alarm must be tted in the room where the appliance is sited Refer too ADJ part 2.34 through too 2.36 page 41 (ONLY FOR UK).
If there is a re in the ue pipe, extinguish the stove, disconnect it from the power supply and never open the door. Then contact the competent authorities.
Do not light the stove with ammable materials if the ignition system breaks down.
Do not stand for a long time in front of the product in operation. Do not overheat the room you are in and where the product is installed. This could cause injuries and health problems.
Install the product in a location that does not present a re hazard and is equipped with power and air supplies and smoke extractors.
In the event of re in the chimney, turn o the device, disconnect it from the mains electricity and do not open the hatch. Then contact the competent authorities.
The product and the cladding must be stored in a dry place and must not be exposed to weathering.
It is recommended not to remove the feet that support the product in order to guarantee adequate insulation, especially if the ooring is made of ammable materials.
In the event of a malfunction with the ignition system, do not force it to light by using ammable materials.
Special maintenance must only be performed by authorised and qualied personnel.
Assess the static conditions of the surface on which the weight of the product will rest and provide suitable insulation if it is made of ammable material (e.g. wood, tted carpet or plastic).
Live electrical parts: only power the product after completing assembly.
Disconnect the product from the 230V power supply before performing any maintenance operation.
IF ANY SMOKE SPILLAGE IS SEEN WITHIN THE ROOM OR THE APPLIANCE SUFFERS FROM AN EXPLOSIVE IGNITION PLEASE TURN OFF THE APPLIANCE, VENTILATE THE ROOM AND CONTACT THE INSTALLER/ SERVICE ENGINEER IMMEDIATELY.
Page 7
5
1-WARNINGS AND WARRANTY CONDITIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
INFORMATION
In case of any problems, get in touch with your dealer, or a qualied engineer authorised by MCZ, and if a repair is necessary, insist on the use of original spare parts.
Use only the fuel recommended by MCZ (for Italy pellets with a diameter of 6 mm and for other European countries with a diameter of 6-8 mm) and provided only with an automatic supply system.
Periodically check and clean the smoke outlet ducts (connection to the ue pipe).
Accumulated unburnt pellets in the burner after repeated failed ignitions must be removed before lighting.
The pellet stove is not a cooking appliance.
Always keep the cover of the fuel hopper closed.
Keep this instruction manual carefully because it must stay with the stove throughout its working life. If the stove is sold or transferred to another user, always make sure that the booklet goes with the product.
If it gets lost, ask MCZ or your authorised dealer for another copy.
INTENDED USE
The product only works with wood pellets and must be installed indoors.
WARRANTY CONDITIONS
The company guarantees the product, with the exception of elements subject to normal wear listed below, for a period of 2 (two) years from the date of purchase attested by:
a document to serve as proof of purchase (invoice and/or receipt) that shows the name of the vendor and the date on which the purchase was made;
forwarding of the completed certicate of guarantee within 8 days of purchase.
Furthermore, in order for the guarantee to be valid, the device must be installed and calibrated by qualied personnel, and where necessary, the user must be issued with a declaration of conformity and correct functioning of the product. We suggest performing the product function test before completing the ner calibrations. Any installation that fails to comply with the regulations in force will invalidate the product guarantee, as will improper use or failure to carry out the maintenance prescribed by the manufacturer. The guarantee is valid on the condition that the instructions and warnings contained in the use and maintenance manual are observed, and therefore the product is used correctly. The replacement of the entire system or the repair of one of its components does not extend the guarantee period, and the original expiry date remains unchanged. The guarantee covers the replacement or free repair of parts recognised as being faulty at source due to manufacturing defects. To benet from the guarantee, in the event of a fault, the customer must have the guarantee certicate and present it with the proof of purchase document to the Technical Assistance Oce.
Page 8
6
1-WARNINGS AND WARRANTY CONDITIONS
EXCLUSIONS
The guarantee does not cover malfunctions and/or damage to the appliance that arise due to the following causes:
Damage caused during transportation or relocation
all parts that develop faults due to negligence or improper use, incorrect maintenance, installation that does not comply with the manufacturer's instructions (always refer to the installation and use manual provided with the appliance)
incorrect dimensioning with regards to the use or faults in the installation or failure to adopt the necessary devices to guarantee proper execution
improper overheating of the equipment, use of fuels not conforming to the types and quantities indicated in the instructions provided
further damage caused by incorrect user interventions in an attempt to x the initial fault
worsening of the damage caused by the user continuing to operate the appliance even after the fault has been noticed
any corrosion, incrustation or cracking caused by water ow, condensation, hardness or acidity of the water, improper de-scaling treatments, lack of water, mud or limescale deposits
ineciency of chimneys, ues or parts of the system aecting the appliance
damage caused by tampering with the appliance, atmospheric agents, natural disasters, vandalism, electrical discharges, res.
faults in the electric and/or hydraulic system.
Also excluded from this guarantee are:
parts subject to normal wear such as seals, glass, claddings and cast iron grids, painted parts, handles and electric cables, bulbs, indicator lights, knobs, all removable parts from the rebox.
Chrome variations of painted parts.
masonry work
parts of the system not supplied by the manufacturer
Any technical interventions on the product to eliminate the defects mentioned above and consequent damages must be agreed upon with the Technical Assistance Centre, who reserves the right to accept the relative appointment or not. However, said interventions will not be carried out under the guarantee but as technical assistance to be granted as part of any eventual and specic agreed conditions and in accordance with the fee applicable for the work to be carried out. The user will also be charged for any costs incurred to remedy the incorrect technical interventions, tampering or damage to the appliance, not attributable to original faults. Save for the legal or regulatory limits, the guarantee does not cover the containment of atmospheric and acoustic pollution.
The company declines all liability for any damage which may be caused, directly or indirectly, to persons, animals or objects as a consequence of non compliance with any prescription specied in the manual, especially warnings regarding installation, use and maintenance of the appliance.
Page 9
7
1-WARNINGS AND WARRANTY CONDITIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
SPARE PARTS
In the event of a malfunction, consult the retailer who will forward the call to the Technical Assistance Service.
Use only original spare parts. The retailer or service centre can provide all necessary information regarding spare parts. We do not recommend waiting for the parts to be worn before having them replaced. It is important to perform regular maintenance.
The company declines all liability if the product and any other accessory is used improperly or modied without authorisation. All parts must be replaced with original spare parts.
WARNINGS FOR THE CORRECT DISPOSAL OF THE PRODUCT.
The owner is the sole party responsible for demolishing and disposing of the product. This must be performed in compliance with laws related to safety and environmental protection in force in his/her country. At the end of its working life, the product must not be disposed of as urban waste. It must be taken to a special dierentiated waste collection centre set up by the local authorities or to a retailer that provides this service. Separating and recycling prevents potential negative eects on the environment and health (often caused by inappropriately disposing of product parts). It also allows materials to be recovered in order to obtain signicant savings in energy and resources.
Page 10
8
1-WARNINGS AND WARRANTY CONDITIONS
RULES FOR INSTALLATION
The product is a boiler that uses wood pellets. Below is a list of European regulations regarding the installation of the product: EN 303-5:2012: Solid fuel boilers, with manual or automatic loading, nominal thermal power of 500 kW - Terminology, requisites, tests and marking. EN 12828 Heating systems design. Electrical systems with rated voltage not exceeding 1000 V AC and 1500 V DC.
EN 1443 General chimney regulation EN 1856-1 metal smoke ducts EN 1856-2 metal smoke extraction channels EN 1457 chimneys - Interior terracotta / ceramic ues EN 13384-1 Chimneys - Thermal and dynamic uid calculation methods - Part 1: Chimneys connected to a single appliance
Below are some applicable regulations for Italy: UNI 10683:2012 Heat generators fuelled by wood or other solid bio-fuels - Test, installation, control and maintenance (for thermochemical power at the rebox lower than 35kW)
UNI/TS 11278 general technical regulation for the choice of smoke duct/ue UNI 10847:2000 Smoke extractor systems for liquid and solid fuelled generators - Maintenance and control - Guidelines and procedures UNI 8065 water treatment in civil plants. UNI 9182 Hot and cold (sanitary) air supply and distribution systems.
Installation must be carried out with reference to the diagram of the heating system prepared in accordance with the standards and local recommendations in force: In any case, respect:
For the heating appliance Local requirements concerning the chimney connection. Local requirements for re-ghting standards. For electrical parts - EN 60335 ''Safety of electrical household appliances and similar Part 1 - General requirements Part 2 - Special regulations for appliances with gas, gas oil and solid fuel burners with electrical connections.
Page 11
9
2-INSTALLATION INSTRUCTIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
The instructions in this chapter refer explicitly to the Italian installation regulation UNI 10683. In any case, always observe the domestic regulations in force.
PELLETS
Wood pellets are manufactured by hot-extruding compressed sawdust which is produced during the working of natural dried wood. The compactness of the material is guaranteed by the lignin contained in the wood itself and allows pellets to be produced without glue or binders. The market oers dierent types of pellets with characteristics that vary according to the wood mixtures used. The most common diameter on the market is 6 mm (although 8 mm diameter is available too) with a length, on average, of between 3 and 40 mm. A good quality pellet has a density of between 600 and 750 or more kg/metres cubed and a water content that accounts for 5 to 8% of its weight. Pellets have technical advantages besides being an ecological fuel, as the wood residue is used completely, thereby achieving cleaner combustion than that of fossil fuels. Good-quality wood has a caloric value of 4.4 kW/kg (15% moisture, after about 18 months of seasoning), whereas that of pellets is 4.9 kW/kg. To ensure good combustion, the pellets must be stored in a dry place and protected from dirt. Pellets are usually supplied in 15 kg bags, therefore, storing them is very convenient. Good quality pellets guarantee good combustion, thereby decreasing harmful emissions into the atmosphere.
The poorer the quality of the fuel, the more often the internal parts of the brazier and combustion chamber must be cleaned.
The main quality certications for pellets currently available on the European market guarantee that the fuel complies with class A1/ A2 according to ISO 17225-2. (formerly EN 14961). These certications include, for example, ENPlus, DINplus, Ö-Norm M7135, and in particular, guarantee the following characteristics:
caloric value: 4.6 ÷ 5.3 kWh/kg.
Moisture content: ≤ 10% of the weight.
Percentage of ash: max 1.2% of the weight (A1 less than 0.7%).
Diameter: 6±1/8±1 mm.
Length: 3÷ 40 mm.
Content: 100% untreated wood without the addition of binding substances (max 5% bark).
Packaging: in sacks made from ecologically compatible or biologically decomposing material.
The company strongly recommends using certied fuel for its products (ENplus, DINplus, Ö-Norm M7135). Poor quality pellets or others that do not comply with the characteristics specied previously may compromise the operation of your product and can therefore render the guarantee and product liability invalid.
15 Kg BAG OF FUEL
Page 12
10
2-INSTALLATION INSTRUCTIONS
PRECAUTIONS REGARDING INSTALLATION
IMPORTANT! Product installation and assembly must be carried out by qualied personnel.
The product must be installed in a suitable place that allows easy access for it to be opened regularly and for routine maintenance to be performed. The installation area must be:
suitable to enable the appliance to operate correctly.
Equipped with an adequate smoke extraction system.
Equipped with adequate ventilation from outside.
Equipped with 230V 50 Hz power supply with an EC compliant earthing system.
IMPORTANT! The product must be connected to a chimney that expels the smoke at the highest point of the building. The chimney must be of suitable dimensions, caulked, and tted with a condensation collector for collecting the water vapour that can form due to the high performance of the appliance and the consequently low temperatures of the outgoing fumes. The chimney must comply with regulations in force. The holes of the external air inlet and the smoke outlet pipe must be drilled before positioning the product.
THE OPERATING AREA
The boiler must be installed indoors in an area well protected from atmospheric elements. The surface on which it stands and/or support points must have sucient load bearing capacity to support the total weight of the appliance, its accessories and covers. To ensure the appliance works well, we recommend installing the boiler detached from any walls or furniture, and with good air circulation to allow eective ventilation for the appliance. The product should be located in an area that allows sucient space for normal use and maintenance operations.
The volume of the room should be no less than 15 m3.
It is essential that an adequate outdoor air intake is provided that supplies the air for combustion needed for the product to function correctly. These air inlets must be arranged so that it is impossible for them to be obstructed. Protect the inlets with grilles, metal mesh, etc., without reducing the net cross-section.
Remember that the ventilation grilles always have the useful cross-section in cm2 indicated on one side. When choosing the grille and size of the inlet, check that the useful cross-section of the grille is larger or equal to the section required for product operation.
The ow of air between the outside and the room of installation may be direct, through an inlet in an external wall of the building; or indirect, through the intake of air from rooms adjoining and connecting permanently with the room of installation. Adjoining areas may not include sleeping areas, garages or general areas that present a re hazard. For air ducts, up to 3m increase the cross-section by approximately 5%, while for ducts that run for longer increase it by 15%.
IMPORTANT! The air ow can also be drawn from an adjoining room to that of the room where the product is installed, provided the air can ow freely through permanent openings to the outside; avoid connection to sleeping areas and rooms that present a re hazard in general.
Page 13
11
2-INSTALLATION INSTRUCTIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
POSITIONING AND RESTRICTIONS
In the case of simultaneous installation with other heating appliances, provide appropriate air inlets for each one (according to the instructions of each product).
Installation of the product is not permitted:
in rooms where there are liquid fuel appliances with continuous or intermittent operation that draw the combustion air from the room they are installed in;
in rooms where there are B-type gas heating appliances, with or without domestic hot water production and interconnecting rooms;
in rooms in which the decrease in pressure during use, as measured between the pressure outside and the pressure in the room, is greater than 4 Pa.
The product may not be installed in rooms used as sleeping areas, bathrooms, garages or in rooms that present a re hazard in general.
BOILER ROOM
Check that the room meets the requirements and provisions of the standards in force. There must also be a ow of at least enough air in the room for normal combustion. Vents must be installed in the walls of the room that meet the following requirements:
Increase the cross-section by at least 6 cm2 for each 1 kW (859.64kcal/h) The minimum cross-section of the opening must not, however, measure less than 100 cm. The cross-section can be calculated using the following relations: S = K * Q ≥ 100 cm
2
Where “S” is in cm2, “Q” in kW, “K” = 6 cm2/kW
The opening must be located at the base of an external wall, preferably opposite the one with the outlet for combusted gases.
Heat-sensitive or ammable objects cannot be stored near the product; keep such objects at a minimum distance of 80 cm from the outermost point of the product.
Page 14
12
min.3,5 metri
AT
(A)
AP
(B)
2-INSTALLATION INSTRUCTIONS
FOREWORD
This chapter on the Smoke Flue has been produced in reference to the prescriptions of European regulations (EN13384 - EN1443 - EN1856
- EN1457).
The chapter provides indications for installing an ecient and correct smoke ue but is under no circumstances to substitute the regulations in force, which the qualied technician must be in possession of. Check with local authorities whether there are any restrictive regulations in force regarding the intake of air for combustion, the smoke extraction system, the ue or the chimney. The company declines all liability relating to the poor functioning of the boiler if this is due to the use of an insuciently sized ue in violation of regulations in force.
SMOKE FLUE
Have the eciency of the ue checked by an authorised technician. The ue or chimney is vital to the correct functioning of a forced draft solid fuel heating appliance, given that boilers with high performance have cooler fumes with consequently weaker draft and the possible formation of condensation. It is therefore essential that the ue meets all construction standards and is always maintained in perfect condition. A ue that serves a pellet/wood fuelled appliance must be at least category T400 (or greater if the appliance requires, and resistant to soot res. Smoke must be extracted through a single ue made of insulated steel (A) or an existing ue that complies with the intended use (B). A simple air shaft in cement must be suitably lined. In either case, ensure to include an inspection cap (AT) or inspection door (AP) and a suitable device for collecting condensation - FIG.1. It is prohibited to connect more than one wood/pellet or any other type of appliance (vent cowling...) to the same ue.
FIGURE 1  SMOKE FLUE
Page 15
13
A
B
C
D
E
A
B
C
D
15°
E
F
2-INSTALLATION INSTRUCTIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
TECHNICAL CHARACTERISTICS
Flues serving a pellet/wood fuelled appliance must meet the following requirements:
made of materials that are suciently resistant to mechanical stress, heat, the action of the products of combustion and their vapours.
made of materials that are impermeable to fumes, condensation, be thermally insulated and resistant to normal mechanical stress over time
go in a vertical direction and deviate no more than 45° from the vertical axis and be free of choke points
be suited to the specic operating conditions of the product and have CE marking (EN1856-1, EN1443).
Be of the correct size to suit the draft/smoke extraction requirements necessary for the product to work properly (EN13384-1)
Be suitably caulked externally to avoid condensation and reduce the cooling of the smoke.
Be at least category T400 (or greater if the appliance requires) and resistant to soot res.
We recommend in particular to check on the data tags of the ue (in accordance with EN1856-1, EN1443) the safety distances that must be respected in presence of passing combustible materials and the type of insulating material to be used. These indications must be followed rigorously to avoid serious harm to personnel and surrounding infrastructure. The chimney opening must be in the same room as the appliance, or at most in the adjoining room, and have a soot and condensation collection chamber beneath the opening, and be accessible via a watertight metal hatch. Smoke must be extracted through a single ue (see g. 3) with insulated steel tubes (A) or though an existing ue that complies with the intended use (B). A simple air shaft in cement must be suitably lined. In either case, ensure to include an inspection cap (AT) and/or inspection door (AP) and a suitable device for collecting condensation - FIG.1. It is prohibited to connect more than one wood/pellet or any other type of appliance (vent cowling...) to the same ue.
FLAT ROOF
ROOF AT 15°
A = 0.50 metres B = DISTANCE > 2 metres C = DISTANCE < 2 metres D = O.50 metres E = TECHNICAL VOLUME
A = MIN. 1.00 metres B = DISTANCE > 1.85 metres C = DISTANCE < 1.85 metres D = 0.50 metres above highest point E = 0.50 metres F = REFLUX ZONE
FIGURE 2
FIGURE 3
Page 16
14
A
B
C
D
E
30°
F
A
B
D
60°
E
C
F
A
B
C
D
E
45°
F
2-INSTALLATION INSTRUCTIONS
ROOF AT 30°
ROOF AT 45°
ROOF AT 60°
A = MIN. 1.30 metres B = DISTANCE > 1.50 metres C = DISTANCE < 1.50 metres D = 0.50 metres ABOVE HIGHEST POINT E = 0.80 metres F = REFLUX ZONE
FIGURE 4
A = MIN. 2.60 metres B = DISTANCE > 1.20 metres C = DISTANCE < 1.20 metres D = 0.50 metres ABOVE HIGHEST POINT E = 2.10 metres F = REFLUX ZONE
FIGURE 6
A = MIN. 2.00 metres B = DISTANCE > 1.30 metres C = DISTANCE < 1.30 metres D = 0.50 metres ABOVE HIGHEST POINT E = 1.50 metres F = REFLUX ZONE
FIGURE 5
Page 17
15
2-INSTALLATION INSTRUCTIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
DIMENSIONING
The drop in pressure (draft) of a ue depends on its height. Check the drop in pressure with the values indicated in the technical characteristics. The minimum height of the chimney is 3.5 meters.
The interior cross-section of the ue can be circular (best variation), square or rectangular (the ratio between the interior sides must be ≤1.5) with the sides joined with a minimum radius of 20 mm. The dimension of the cross-section must be a minimum Ø150mm.
The cross-sections/lengths of the chimneys shown in the technical data tables are indications for correct installation. Any alternative congurations must be correctly dimensioned in accordance with the general method of calculation of UNI EN13384-1 or other proven eciency methods.
Below is a list of some ues available on the market:
Steel chimney AISI 316 with double chamber insulated with ceramic bre or equivalent resistant up to 400°C.
Refractory chimney with double insulated chamber and external lightweight concrete cladding with cellular material such as clay.
Traditional square-section clay chimney with insulating empty inserts.
Avoid products with an internal rectangular section where the larger side is 1.5 times the smaller side (e.g. 20x40 or 15x30).
EXCELLENT GOOD POOR VERY POOR
Page 18
16
1
9
9
2
3
4
5
6
7
8
9
2-INSTALLATION INSTRUCTIONS
MAINTENANCE
The ue must be kept clean, since the deposit of soot or unburned oils reduces the cross-section reducing the draft and thus compromising the ecient functioning of the heater and, if large build-ups accumulate, can catch re. The ue and chimney must be cleaned and checked by a qualied chimney sweep at least once a year. Once the maintenance has been performed, request a written declaration that the device is safe. Failure to clean the system jeopardises the safety.
CHIMNEY
The chimney is a crucial element for the heating appliance to work properly: we recommend a wind proof chimney (A), see Figure 7. The area of the opening for smoke extraction must be at least double the cross-section of the smoke duct/ue system, and arranged so
that smoke extraction is ensured even in strong wind. The chimney must prevent rain, snow or animals from entering the chimney. The height of outow into the atmosphere must be beyond the reux zone created by the shape of the roof or any obstacles near the outlet (see Figures 2-3-4-5-6).
CHIMNEY COMPONENTS
KE Y: (1) CHIMNEY (2) REFLUX CHANNEL (3) SMOKE DUCT (4) THERMAL INSULATION (5) OUTSIDE WALL (6) CHIMNEY CONNECTION (7) SMOKE CHANNEL (8) HEAT GENERATOR (9) INSPECTION ACCESS PANEL
FIGURE 7
FIGURE 8
Page 19
17
2-INSTALLATION INSTRUCTIONS
Technical Dept. - All rights reserved - Reproduction is prohibited
CONNECTION TO FLUE
The connection between the ue and the appliance must be via a smoke duct that conforms with EN 1856-2. The connecting section must extend no more than 4 m horizontally, with a maximum incline of 3% and containing a maximum of 3 90% bends (accessible for inspection - do not count the T joint at the appliance outlet). The diameter of the smoke duct must be equal to or greater than that of the outlet of the appliance (Ø 100 mm).
TYPE OF DEVICE SMOKE DUCT
Minimum vertical length 1.5 metres
Maximum length (with 1 accessible 90° bend)
6.5 metres
Maximum length (with 3 accessible 90° bends)
4.5 metres
Maximum number of accessible 90° bends 3
Horizontal sections (minimum incline 3%)
4 metres
Use smoke ues of 100mm diameter and silicon seals or similar seals that can resist the high operating temperatures of the appliance (min. T200 class P1). The use of exible metal tubes in bre cement or aluminium is prohibited. For direction changes, we always recommend the use of a T joint with an inspection cap allowing easy access for cleaning the tubes. Always ensure that the inspection cap is replaced and hermetically sealed with the seal in tact after cleaning. It is prohibited to connect more than one appliance to the same smoke duct, or the discharge from overhead cowling. It is prohibited to extract the products of combustion directly through the wall, whether into indoor spaces or outdoors. The smoke duct must be a minimum distance of 400 mm from ammable or heat-sensitive structures.
We recommend in particular to check the data tags of the ue for the safety distances that must be respected in presence of combustible materials and the type of insulating material to be used. These indications must be followed rigorously to avoid serious harm to personnel and surrounding infrastructure.
Page 20
18
T
I
S
I
U
B
A
P
U
I
I
C
4
3
D
2
I
E
V
U
1
F
2-INSTALLATION INSTRUCTIONS
EXAMPLES OF CORRECT INSTALLATION
1. Installation of Ø150mm ue with hole for the passage
of the tube increased by: minimum 100 mm around the tube if next to non ammable parts such as cement, brick, etc.; or minimum 300 mm around the tube (or as prescribed by data tags) if next to ammable parts such as wood etc. In both cases, install suitable insulation between the ue and the ceiling. Always check and respect the data tags on the ue, in particular the minimum safety distances from combustible materials. The previous rules also apply for holes made in walls.
2. Old ue, minimum tube Ø150mm with the inclusion of an external access door for chimney cleaning.
3. External ue made of insulated stainless steel tubes, i.e. with double walls minimum Ø150mm: all securely mounted to the wall. With wind-proof chimney. See g. 7 type A.
4. Ducting system using T joints that allow easy access for cleaning without having to remove the tubes
FIGURE 11
U = INSULATING V = ANY REDUCTION FROM 100 TO 80 MM I = INSPECTION CAP S = INSPECTION ACCESS PANEL P = AIR INLET T = T JOINT WITH INSPECTION CAP
A = MINIMUM 40 MM B = MAXIMUM 4 M C = MINIMUM 3° D = MINIMUM 400 MM E = HOLE DIAMETER F = SEE FIG.23456
Page 21
19
357
ø80
ø48
76
674 336
391
27
1208
776
280
74
98
ø80
339
1086
1086
280
3-DRAWINGS AND TECHNICAL CHARACTERISTICS
Technical Dept. - All rights reserved - Reproduction is prohibited
DRAWINGS AND CHARACTERISTICS
COMPACT SLIM 15 DIMENSIONS (dimensions in mm)
Page 22
20
3-DRAWINGS AND TECHNICAL CHARACTERISTICS
TECHNICAL CHARACTERISTICS COMPACT SLIM 15
Product class (EN 303-5/2012) 5
Rated thermal capacity of the rebox 15 kW (12900 kcal/h)
Nominal output power: 13.5 kW (11610 kcal/h)
Minimum output power 4.0 kW (3440 kcal/h)
Eciency at Max 90,0%
Eciency at Min 90,9%
Temperature of exhaust smoke at Max 85°C
Temperature of exhaust smoke at Min 50°C
Max congurable temperature 80°C
Max operating temperature 95°C
Particles/OGC/Nox (10%O2) 26 mg/Nm3 - 2 mg/Nm
3 -
193 mg/Nm
3
CO at 10% O2 at Min and at Max 0.007 - 0.039%
CO2 at Min and at Max 7.0 - 9.7%
Recommended draught at Max power 0.10 mbar - 10 Pa
Recommended draught at Min power 0.05 mbar - 5 Pa
Smoke mass 10.3 g/sec
Hopper capacity 57 litres
Type of pellet fuel Pellet diameter 6-8 mm and size 5/30 mm
Pellet hourly consumption Min ~ 1.0 kg/h* - Max ~ 3.1 kg/h*
Autonomy At min ~ 37 h* - At max ~ 12 h*
Heatable volume m
3
290/40 - 332/35 - 387/30**
Water content 20 litres
Max operating temperature 3 bar - 300 kPa
Combustion air inlet  50 mm
Smoke outlet  80 mm
Air intlet 100 cm
2
Rated electrical power (EN 60335-1) 180 W (Max 430 W)
Supply voltage and frequency 230 Volt / 50 Hz
Net weight 200 kg
Weight with packaging 220 kg
* Data that may vary depending on the type of pellets used. ** Volume that can be heated, according to the power requirement in m3 (respectively 40-35-30 Kcal/h per m3)
Page 23
21
0
100
200
300
400
500
600
0 500 1000 1500 2000
A
B
3-DRAWINGS AND TECHNICAL CHARACTERISTICS
Technical Dept. - All rights reserved - Reproduction is prohibited
Residual head
A = Residual head (mbar) B = Flow (l/h)
Page 24
22
u
t
4 - UNPACKING
PREPARATION AND UNPACKING
The Compact Slim 15 boiler is delivered complete with all its electrical, mechanical and hydraulic components and having been tested in the factory: Remove the cardboard, supports and polystyrene that secure the boiler to the pallet. At this point, open the two side panels and remove the two brackets holding the boiler. To remove the brackets, undo the two "t" screws between the bracket and the pallet and the two "u" screws between the bracket and the boiler (g.1).
Install the boiler in the area set aside for it, making sure it conforms to the requirements. The boiler body or unit must always be kept in a vertical position when moved, and only ever moved using suitable lifting trolleys. Pay particular attention to the door and its glass, protecting them from mechanical knocks that would compromise their integrity.
The product must always be moved with care. If possible, unwrap the boiler near the chosen place of installation. The packaging materials are neither toxic nor harmful, and therefore no particular disposal measures are required. The product, as indicated in gure 1 consists of a single packaged unit. After removing all the packaging, check that the boiler is complete and not damaged. If in doubt, contact the retailer. The following documents are provided in the package:
Plant booklet
Instruction booklet
Annex G - Technical test report for thermal plant of less than 35 kW.
Guarantee
Figure 1 - Packaging
Page 25
23
1500
MIN. 300
MIN. 300
10
MIN.
400
MIN.
1800
5 - POSITIONING
Technical Dept. - All rights reserved - Reproduction is prohibited
REQUIREMENTS FOR INSTALLATION OF THE PLANT - POSITIONING
The most important thing to do before installation of the boiler is to set aside a suitable area that meets the minimum requirements for installation.
the minimum clearance in front of the product to allow suitable access for cleaning, maintenance, etc. must be 400 mm;
the minimum permissible distance between the back of the product and a wall must be 10 mm;
the minimum distance between the top of the product and the ceiling must be 600 mm to ensure easy access to the heat exchanger
for the purpose of cleaning and maintenance (e.g. for removing ash);
the minimum clearance between the product and the wall (side) must be 300 mm.
COMPACT SLIM 15 BOILER MINIMUM REQUIREMENTS
Page 26
24
P
4 - UNPACKING
TURN THE FEET CLOCKWISE TO LOWER THE PRODUCT. TURN THE FEET ANTI-CLOCKWISE TO RAISE THE PRODUCT.
FOOT ADJUSTMENT
The underside of the boiler is tted with adjustable feet.
Use a spanner to unscrew the feet to adjust the length and make the structure stable.
Page 27
25
H
T
H
P
4 - UNPACKING
Technical Dept. - All rights reserved - Reproduction is prohibited
CONNECTION OF THE SMOKE OUTLET PIPE
You can choose whether to extract the smoke from the rear or the top of the product. The product arrives set up with the outlet at the back, if you wish to connect the outlet to the top, proceed as follows:
Open the side panel "T"
Remove cap "H" and place it on the rear smoke outlet
Insert the tube "P" until it engages with the smoke joint.
Page 28
26
C
C
6 - PANEL REMOVAL
REMOVAL OF PANELS
Opening side panels
The side panels are held closed by a magnet. To open them, simply pull lightly.
Page 29
27
6 - PANEL REMOVAL
Technical Dept. - All rights reserved - Reproduction is prohibited
OPENING/CLOSING THE FIREBOX DOOR
ATTENTION! The door must be securely closed for the boiler to work correctly.
To open the door, insert the hook into the hole in the handle, lift and pull towards you.
Page 30
28
B
C
A
6 - PANEL REMOVAL
Upper top
Lift top "A", remove and secure tops "B" and "C". Tops "B" and "C" are only supported.
Page 31
29
e
e
D
6 - PANEL REMOVAL
Technical Dept. - All rights reserved - Reproduction is prohibited
Front central panel
First open the door to the rebox, then undo the two screws "e" shown in the gure, located in the lower part of the panel. Now pull the front panel "D" upwards and put it safely aside.
Page 32
30
f
E
E
D
6 - PANEL REMOVAL
Front side panels
Remove the four screws "f" per panel located three along the side and one on the inside towards the front panel "D". Now slide out the panels "E" and place them safely aside.
Page 33
31
v
a
F
6 - PANEL REMOVAL
Technical Dept. - All rights reserved - Reproduction is prohibited
Filler panel "F"
Loosen the three screws "v" and raise the panel "F" slightly so that screw "v" comes out of the hole "a" then slide out panel "F".
Page 34
32
k
u
a
y
j
T
6 - PANEL REMOVAL
Complete top "T"
Remove the three screws "u", loosen the two screws "k" and the three screws "y" until the top "T" can be removed from the holes "a" and "j".
Page 35
33
p
F
C
6 - PANEL REMOVAL
Technical Dept. - All rights reserved - Reproduction is prohibited
ACCESS TO THE ELECTRONIC BOARD
To access the electronic board you must open the side panel, remove the two screws "p" and lower the window.
If it is necessary to connect external cables to the appliance, feed the cables through the hole "F" on the back and fasten the cables "C" to the board with the window lowered to avoid the cables being moved the next time the window is opened.
Page 36
34
7882
80
4
3
1
2
1
4
3
2
559
165
7 - HYDRAULIC CONNECTION
HYDRAULIC CONNECTION
1
1/2" SAFETY VALVE DISCHARGE 3 bar
2
3/4" SYSTEM DELIVERY
3
1/2" SYSTEM OUTLET
4
3/4" SYSTEM RETURN
IMPORTANT!!! CLEAN THE ENTIRE SYSTEM BEFORE CONNECTING THE BOILER, IN ORDER TO REMOVE ALL RESIDUE AND DEPOSITS. Always install shutters in the system leading to the boiler so as to disconnect it from the hydraulic system should it be necessary to move it, or when performing routine and/or special maintenance. Connect the boiler using exible tubes.
Page 37
35
g
K
s
T
r
V
7 - HYDRAULIC CONNECTION
Technical Dept. - All rights reserved - Reproduction is prohibited
HYDRAULIC KIT ATTACHABLE TO THE SIDE OF THE BOILER (OPTIONAL KIT)
It is also possible to connect the hydraulics to the side of the boiler. To do this, you must:
remove the plate "K" from the right side of the boiler by removing the ve screws "g" (g. 1)
acquire the optional hydraulic kit "V" (g. 2)
remove the outlet tap "r" (g. 2)
attach the optional kit with the three screws "n" (g. 3)
connect the tubes to the existing kit (g. 4)
screw the outlet tap "r" to the new kit (g. 4)
FIGURE 1
FIGURE 2
Page 38
36
n
V
r
7 - HYDRAULIC CONNECTION
FIGURE 3
FIGURE 4
Page 39
37
7 - HYDRAULIC CONNECTION
Technical Dept. - All rights reserved - Reproduction is prohibited
CLEANING THE SYSTEM
Install suitable shutters to cut o the tubes from the heating system. To protect the heating system from being damaged by corrosion, incrustation or smoke deposits, it is extremely important, before the appliance is installed, that it be washed according to the UNI 8065 standard (water treatment of thermal systems for civil use) with appropriate products. As standard, RED supplied the product FERNOX PROTECTOR F1 with the product. This provides long term protection against corrosion and calcium build-up for the heating appliance. It prevents the corrosion of the metal parts of the appliance, i.e. the ferrous metals, copper and copper and aluminium alloys. It also reduces the noise produced by the boiler. Refer to the instructions on the product. Cleaning should be performed by a qualied technician. We also recommend the use of FERNOX CLEANER F3 and LEAK SEALER F4, available from our authorised distribution centres. FERNOX F3 is a neutral product for rapid and ecient cleaning of heating appliances. It has been designed to eliminate residue, oily deposits and incrustations from existing appliances of all ages. It can help restore the heating eciency of the boiler and reduce the noise it generates. FERNOX F4 is intended to be used with all heating appliances to seal micro fractures that cause small and inaccessible leaks.
Attention: Failure to clean the thermal system or to use an adequate inhibitor will invalidate the warranty of the appliance and of the other accessories like the pump and valves.
FILLING THE SYSTEM
Fill the system slowly to allow air bubbles to pass through the vent holes of the heating system. For closed circuit heating systems, the lling pressure of the system at cold and the pre-ination pressure of the expansion tank must be the same.
In open vessel heating systems, direct contact between circulating liquid and air is allowed. During the heating season, the user
must check the circulating water level in the expansion tank regularly. The water level in the circulation system must be kept constant. Practical experience shows that a regular check of the water level must be made every 14 days to maintain a relatively constant level. When necessary, the water level must be topped up when the boiler has cooled to room temperature. This is to avoid and damage being caused to the steel body of the boiler due to thermal stress.
In systems with an open vessel, the water pressure in the boiler must not be less than 0.3 bar when the system is cool.
The water used for lling the heating system must be decontaminated and not contain air.
Attention! Do not mix heating water with incorrect concentrations of anti-freeze or anti-corrosion substances! This could damage the gaskets and cause noise during operation. The manufacturer denies any liability for harm caused to persons, animals or objects caused by failure to observe these precautions.
After making all the hydraulic connections, pressure-test the seals by lling the boiler.
This must be done with care by doing the following:
open the air vent valves of the radiators, boiler and system;
gradually open the lling tap of the system, making sure that any automatic air vent valves in the system work correctly;
close the vent valves of the radiators as soon as water comes out;
use the pressure gauge inserted in the system to check that the pressure reaches a value of approximately 1 bar; for open vessel systems, the water is topped up automatically through the vessel.
close the lling tap of the system and then open the vent valves of the radiators again to purge any air;
check the seal of all the connections;
Page 40
38
7 - HYDRAULIC CONNECTION
after starting up the boiler for the rst time and bringing the system up to temperature, stop the pumps and repeat the air purging procedure;
leave the system to cool, and if necessary, restore the water pressure to 1 bar.
NOTE In systems with a closed vessel, where possible, the water pressure in the heating system must not be lower than 1 bar when the system is at room temperature; if this is not the case, use the tap to ll the system. This operation must be performed when the system is cool. The pressure gauge on the system enables you to read the pressure in the circuit.
To ll the system, the hydraulic kit is equipped with a tab, with a stop valve, so that you can manually ll the heating system. During this operation, any air in the system is released from the automatic vent valve located at the top of the body of the boiler.
To allow the valve to vent, loosen the side cap (see gure) The lling pressure of the system WHEN COLD must be 1 bar. Upon completion of this operation, always close the tap.
To access the vent valve, lift the central cover and loosen the side cap.
PURGE VALVE WITH CAP
Page 41
39
1
4
3
2
559
165
a
c
7 - HYDRAULIC CONNECTION
Technical Dept. - All rights reserved - Reproduction is prohibited
THERMOSTATIC DIVERTER VALVE (COMPULSORY)
The automatic thermostatic diverter valve is used in solid fuel boilers to prevent the return of cold water into the exchanger which would cause condensation to form. The prolonged formation of condensation irreparably damages the heat exchanger. The lack of a device to prevent this invalidates the guarantee. A higher return temperature reduces the formation of condensation of the fumes and extends the life of the boiler. Valves available oer various calibrations. RED recommends the model (see accessories list) at 55°C with hydraulic connections of 1". Once the calibration temperature is reached, the valve opens allowing water to pass between sections "a" - "c" and supplying hot water to the system.
1 = SAFETY VALVE DISCHARGE 3 BAR 2 = SYSTEM DELIVERY 3 = SYSTEM OUTLET 4 = SYSTEM RETURN
Page 42
40
8 - ELECTRICAL CONNECTION
GENERAL PRECAUTIONS
The electrical safety of the system is guaranteed only when this is connected correctly to an ecient earthing system installed in accordance with the safety standards in force: the pipes of the gas, water and heating systems do not constitute a suitable earth system. It is necessary to ensure this essential safety requirement; if in doubt, have a qualied technician test the electrical system with care because the manufacturer of the boiler does not assume responsibility for damage caused by the absence of an earthing system. A qualied technician should check that the electrical system is compatible with the max consumption of the system, checking in particular that the cross-section of the cables of the system is compatible with the power consumption of the loads. The use of any component that requires electrical energy requires compliance with certain essential rules like:
do not touch the appliance with wet and/or damp parts of the body and/or when barefoot;
do not pull on the electrical cables;
do not expose the appliance to the elements (rain, sun, etc.);
do not allow children or inexperienced persons to use the appliance.
Electrical connection
The installation of additional electrical components of the boiler requires electrical connection to a230V - 50Hzpower supply: This connection must be made in accordance with the CEI standards in force.
Danger! Electrical installation must be entrusted to a single qualied technician. Before making the connections or carrying out any work on the electrical parts, always turn o the power supply and make sure it cannot be turned on again accidentally. Remember that it is necessary to install a bipolar switch in the boiler's electrical power circuit with a distance of 3mm between the main contacts. The switches must be easily accessible to allow quick and safe maintenance.
The power cable must be replaced only by an authorised technician. Failure to observe the above could compromise the safety of the appliance.
Page 43
41
A
B
8 - ELECTRICAL CONNECTION
Technical Dept. - All rights reserved - Reproduction is prohibited
ELECTRICAL CONNECTION
Open the left side access panel. At the bottom you can access the electrical connection for the boiler and the various electrical connections on the board. Insert the power cable into the socket below the boiler's power switch (A), feed the cable through the hole (B) in the back of the boiler and connect it to the power socket on the wall.
When the boiler is not in use, turn the power switch o.
ELECTRICAL CONNECTION
Page 44
42
9 - FIRST START-UP
GENERAL PRECAUTIONS
Remove any objects that may burn from the brazier (manual, various adhesive labels or any remaining polystyrene).
Check that the brazier is positioned correctly and rests properly on the base.
The rst start-up may not be successful as the feed screw is empty and does not always manage to load the required amount of pellets in time to light the ame.
CANCEL THE ALARM FOR THE LIGHTING FAILURE BY HOLDING DOWN BUTTON 1 (ESC). REMOVE THE PELLET LEFT IN THE BRAZIER AND REPEAT THE START-UP.
If after repeated attempts, the ame fails to ignite, despite a regular ow of pellets in the brazier, which must rest snugly against the slots and be clean without any ash incrustations. If no anomaly is found during this inspection, there may be a problem with the
product components or installation may not be correct.
REMOVE THE PELLETS FROM THE BRAZIER AND CONTACT AN AUTHORISED TECHNICIAN.
Do not touch the boiler during the rst lighting, as it is during this phase that the paint sets. If you touch the paint, you may expose the steel surface.
If necessary, touch up the paint with the spray can of the specic colour. (See ‘’Pellet stove accessories’’).
It is good practice to ensure eective ventilation in the room during the initial start-up, as the boiler will emit some smoke and smell of paint.
ATTENTION! Please ensure the brazier is clear of ALL pellets and ash build up following any failed ignitions. Failure to clear out the brazier prior to resetting may result in further failed ignitions or in certain conditions an explosive ignition.
Page 45
43
I
1
9 - FIRST START-UP
Technical Dept. - All rights reserved - Reproduction is prohibited
Do not stand close to the stove and, as mentioned, air the room. The smoke and smell of paint will disappear after about an hour of operation, however, they are not harmful in any case. The boiler will be subject to expansion and contraction during the lighting and cooling down stages, and may therefore make slight creaking noises. This is absolutely normal as the structure is made of laminated steel and must not be considered a defect. It is extremely important to make sure the boiler does not reach high temperatures straight away, but to increase the temperature gradually using low power at rst. This will prevent damaging the ceramic or serpentine stone tiles, the welds and the steel structure.
DO NOT EXPECT HEATING EFFICIENCY IMMEDIATELY!!! ATTENTION!
If during operation or initial ignition you encounter smoke spillage in to the room from the appliance or the ue then please switch o the appliance, ventilate the room and contact the installation / service engineer immediately.
SETTINGS TO BE CARRIED OUT BEFORE THE INITIAL START-UP
After connecting the power cable to the electrical socket, turn the power switch to the (I) position. Turn the boiler on or o at button 1 on the control panel.
Page 46
44
U
V
9 - FIRST START-UP
LOADING THE PELLETS
The pellets can be loaded either manually or automatically. The tank can contain up to 57 litres or 40 kg of pellets.
Manual Loading:
Open the top cover of the boiler and pour in the pellets.
Automatic Loading (with remote tank of 100/200 or 400 kg - optional - see accessories):
At the back of the boiler, remove the perforated panel "U" and attach the duct "V" for the additional tank (optional - see accessories). Then connect the additional tank.
Never remove the protective grate from inside the tank. When loading pellets, keep the bag from coming into contact with hot surfaces.
Page 47
45
9 - FIRST START-UP
Technical Dept. - All rights reserved - Reproduction is prohibited
SAFETY PROCEDURE TO FOLLOW IF ANY SMOKE SPILLAGE IS SEEN WITHIN THE ROOM OR THE APPLIANCE SUFFERS FROM AN EXPLOSIVE IGNITION PLEASE TURN OFF THE APPLIANCE, VENTILATE THE ROOM AND CONTACT THE INSTALLER/ SERVICE ENGINEER IMIDIAT­LEY.
User Training
In ALL cases the installation and commissioning engineer MUST carry out a thorough handover of the appliance to the ho­meowner / end user. The following elements should be covered to the satisfaction of the end user. Failure to do this may result in unsafe use of the appliance:
Explanation of the appliance and how it works
Necessity to maintain ventilation to the appliance and the issues that may arise otherwise
Fuel useage and supply
How to light the appliance safely
What to do in the event of failed ignitions
What to do in the event of alarms (in particular those generated when the appliance runs out of fuel)
How to maintain the appliance correctly and the importance of carrying out these tasks each month
It is good practise to agree a date for the srt annual service
Explain the importance of the CO alarm in accordance with approved document J of the building regs (ONLY FOR UK)
Explain the need for the ue draft stabiliser and its position within the ue system (ONLY FOR UK)
Discuss the use of secondary heating systems if applicable
Explain how the remote control or room stats operate and their optimal positioning
Explain the need for the appliance data plate in accordance with approved document J of the building regulations (ONLY FOR UK)
The commissioning process and paperwork should also be explained to the homeowner. A copy of the base settings on the commissioning paperwork should also be left with the appliance (ONLY FOR UK).
Page 48
46
7
2 3 4
61 5
10 - MENU ITEMS AND FUNCTION
CONTROL PANEL DISPLAY
Menu options
KEY
1. Switching on/switching o the boiler
2. Scrolling down through the programming menu
3. Menu
4. Scrolling up the programming menu
5. Decrease set temperature / programming functions.
6. Increase set temperature / programming functions.
7. Display.
MAIN MENU
Press key 3 (menu) to access. The options accessed are:
Date and Time
Timer
Sleep (only when boiler is on)
Settings
Info
Date and time conguration
Congure the time and date as follows:
Press the "menu" key.
Select "Date and Time".
Press "menu" to conrm.
Scroll through with the arrow keys and select the variables to be edited one at a time: Day, Hour, Min, Num. day, Month, Year.
Press "menu" to conrm
Use the + and - keys to edit.
Finally, press "menu" to conrm and "esc" to exit.
Page 49
47
10 - MENU ITEMS AND FUNCTION
Technical Dept. - All rights reserved - Reproduction is prohibited
PROGRAMMED MODE (TIMER) - Main menu
The current time and date must be congured to ensure correct operation of the timer.
There are six congurable TIMERS; for each one, the user can select a start and stop time and the days of the week when it is in use. When one or more programs are active, the status of the boiler and the TIMER "n" alternate on the display. "n" is the number of timer programs in use, separated by dashes. Example: TIMER 1 Timer 1 program active. TIMER 1-4 Timer 1 and 4 programs active. TIMER 1-2-3-4-5-6 All timer programs active. EXAMPLE OF PROGRAMMING With the boiler on or o:
access the MENU,
scroll to the TIMER item using the <> arrows,
press the "Menu" key
the system shows "P1" (Press the <> keys to move through the timers P2, P3, P4, P5, P6)
Press the "Menu" key to activate "P1".
press + - and select "ON"
press the "Menu" key to conrm
At this point the start time is 00:00. Press the + - key to set the start time and press the "menu" key to conrm. Next, the proposed stop time is 10 minutes later than the congured start time: press the + key and edit the stop time, and press the "menu" key to conrm. Next, you are asked to set the days of the week when the congured timer is to be enabled or disabled. Press the - or + keys to select the day you want to activate the time. It will light up white, then conrm with the "menu" key. If no day is selected for enabling the timer, the timer program is no longer enabled on the status window. Next, program the other days or press "ESC" to exit. Repeat this procedure to program the other timers. EXAMPLES OF PROGRAMMING
P1
P2
on o day on o day
08:00 12:00 mon 11:00 14:00 mon
Boiler on between 08:00 and 14:00
P1 P2
on o day on o day
08:00 11:00 mon 11:00 14:00 mon
Boiler on between 08:00 and 14:00
P1 P2
on o day on o day
17:00 24:00 mon 00:00 06:00 tue
Boiler on between 17:00 on Monday to 06:00 on Tuesday
Page 50
48
10 - MENU ITEMS AND FUNCTION
NOTES ON USE OF THE TIMER
The timer always starts the boiler with the last temperature and ventilation settings (or with the default settings at 20°C and V3 if they have never been altered).
The start time can be between 00:00 and 23:50
If the stop time has not yet been saved, the program proposes a start time at +10 minutes.
If a timer program turns o the boiler at 24:00 on one day and another program starts it up at 00:00 on the next day: the boiler remains on.
A program has a start-up and/or shut-down time that overlap the times of another program: if the boiler is already on, the start has no eect while OFF turns o the boiler.
When the boiler is on and the timer is active, pressing the OFF key turns o the boiler; the boiler then restarts automatically at the next time of the timer.
When the boiler is o and the timer is active, pressing the ON key turns on the boiler; the boiler then stops automatically at the next time of the timer.
SLEEP FUNCTION (main menu)
Sleep may be activated only when the boiler is on and allows you to quickly set a time for the product to turn o. To set the Sleep function, proceed as follows:
Enter the MENU
Scroll to the SLEEP item with the <> arrows
Press Menu
Set the turn-o time you want using the + and - keys.
The panel shows a default time of 10 minutes after the current time, which can be adjusted with key 4 up to the following day (i.e. the turn-o can be delayed for a maximum of 23 hours and 50 minutes). If the SLEEP function is active with the TIMER active, the former has priority, therefore the boiler will not turn o at the time set in the timer program but at the time set by the sleep function, even if it comes after the time set by the timer.
ADJUSTMENTS MENU
To access the menu, proceed as follows:
Press the - + keys
Scroll with the <> arrows and select "Set Amb. T" or "Set Water T" or "Exchanger Speed"
Press "menu" to enter the option selected.
Change with the + - keys.
Press "menu" to conrm and "esc" to exit.
Page 51
49
10 - MENU ITEMS AND FUNCTION
Technical Dept. - All rights reserved - Reproduction is prohibited
SETTINGS MENU
The SETTINGS menu is for conguring use of the boiler: a. Language. b. Cleaning (shown only when boiler is o). c. Auger loading (shown only when boiler is o ). d. Tones. e. External thermostat (activation). f. Auto Eco (activation). g. Eco Turn-o T (default 10 minutes) h. Pump on T (default 50°C). i. Auxiliary boiler (default deactivated). j. Pellet recipe. k. Fumes rpm % ventilation. l. Maximum power (1-5 - default 5). m. Component test (shown only when boiler is o). n. "Chimney sweeper" function (can be enabled only when boiler is on, for checking emissions in eld). o. System conguration (factory settings: system 02). p. Season q. Technical menu. NOTE: Some of the options listed above cannot be enabled in certain "system congurations".
a - Language
Select the language as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Use the arrow keys to scroll through and select "language".
Press “menu” to conrm.
Use the + - keys to select the required language (IT/EN/DE/FR/ES/NL/PL/DA)
Press "menu" to conrm and "esc" to exit.
b - Cleaning
Select "Cleaning" (only with boiler o) as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Use the arrow keys to scroll through and select ''Cleaning''
Press “menu” to conrm.
Use the + - keys to select "On".
Press "menu" to conrm and "esc" to exit.
Page 52
50
10 - MENU ITEMS AND FUNCTION
c - Load auger
This is for lling the the pellet loading system. This can be enabled only when the boiler is o. A countdown appears. The auger stops automatically at the end of the countdown and the menu closes. To select ''Load auger'' (only with boiler o) proceed as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Scroll with the arrows and select "Load auger".
Press “menu” to conrm.
With the + - keys, select "Enable".
Press "menu" to conrm and "esc" to exit.
d - Tones
This function is disabled by default. To enable it proceed as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Use the arrow keys to scroll through and select ''Tones''
Press “menu” to conrm.
Use the + - keys to select ''On''.
e - External thermostat
EXTERNAL THERMOSTAT (not included with the boiler, it must be provided by the user) The temperature of the boiler can also be controlled by an external thermostat in the room. It should be positioned centrally in the room where the boiler is installed. It provides a closer match between the heating temperature requested of the boiler and the actual room temperature it provides. Connect the wires of the external thermostat to points 1-2 of the terminal block on the boiler. Once the thermostat has been connected it needs to be enabled. To do this, proceed as follows:
Press the "menu" key.
Scroll with the arrows to "Settings".
Press "menu" to select.
Now use the arrows to scroll to "External thermostat".
Press ''menu'' to select.
Press the - + keys
Select "On" to activate the external thermostat.
Press the “menu” key to conrm.
Press the “esc” key to exit.
f - Auto-Eco activation
To select the Auto-Eco function, proceed as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Scroll with the arrows and select "Auto-Eco".
Press “menu” to conrm.
With the + - keys, select "On".
Press "menu" to conrm and "esc" to exit.
Page 53
51
10 - MENU ITEMS AND FUNCTION
Technical Dept. - All rights reserved - Reproduction is prohibited
g - Eco Stop T
To select the Eco Stop T function, proceed as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Scroll with the arrows and select ''T Eco o''.
Press “menu” to conrm.
Enter the minutes with the + - keys.
Press "menu" to conrm and "esc" to exit.
AUTO ECO MODE
For activation of the "Auto Eco" mode and time settings, see paragraphs 8 f and 8 g respectively. The ''ECO stop T'' can be adjusted to ensure correct operation in the various environments in which the boiler can be installed and to avoid constant stopping and starting when the room temperature is subject to sudden change (drafts, poorly insulated rooms, etc.). The ECO stop procedure is activated automatically when all the power recall devices included in the "system conguration" are satised: room temperature probe/external thermostat (congurations 1-2-3), ow switch (conguration 2), thermostat/ntc (10 kß3435) puer (conguration 4-5) or thermostat/ntc (10 k ß3435) boiler (conguration 2-3). If all the devices present are satised, the time begins to decrease "T ECO o" (10 minutes default, can be changed in the "Settings" menu). During this phase, the panel alternates between displaying ON with a small ame and Crono (if active) - Eco active. The minutes counting down to the Eco Stop are shown at the top of the display. The ame moves to P1 and remains there until the set "T Eco Stop" time reaches zero, and if the conditions are still satised, turns o the boiler. The ECO stop count is cancelled if one of the devices recalls power. When the boiler begins to turn o, the panel shows: O - Eco Active - ashing small ame. When the boiler turns o, OFF-ECO appears on the display with the ame symbol o. The following conditions have to be met simultaneously for the ECO to restart:
Power recall
5 minutes have passed since shut-down.
TH2O < TSetH2O.
If the power is recalled by the domestic hot water (DHW), the 5' are ignored and the boiler starts up as required.
NOTE: In conguration 4 - 5 the Auto Eco mode is enabled automatically. Also when in conguration 2 - 3, with the 'summer' function set, it is enabled automatically. Where it is prescribed that it should be enabled, the mode cannot be disabled.
h - T Pump On
This option enables adjustment of the pump activation temperature.
Select the Pump On T function as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Scroll with the arrows and select "T Pump On".
Press “menu” to conrm.
Use the + - keys to change the °C.
Press ''menu'' to conrm and ''esc'' to exit.
Page 54
52
10 - MENU ITEMS AND FUNCTION
i - Auxiliary boiler
An additional module (optional) must be installed to allow the start-up of an auxiliary boiler when the main boiler is o or has been stopped due to an alarm. The default settings have this function disabled. To enable the function, go to the settings menu.
l - Pellet Recipe
This function is for adapting the boiler to the type of pellet in use. As there are many types of pellet available on the market, the operation of the boiler can vary considerably according to the quality of the fuel. When the pellets clog up the brazier due to excess loading of fuel or when the ames are high even at low power, or when the ames are low, it is possible to decrease/increase the amount of pellets in the brazier: Available values:
-3 = A decrease of 30% on the factory setting.
-2 = A decrease of 20% on the factory setting.
-1 = A decrease of 10% on the factory setting. 0 = No changes. 1 = An increase of 5% on the factory setting. 2 = An increase of 10% on the factory setting. 3 = An increase of 15% on the factory setting.
Edit the recipe as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Scroll with the arrows and select "Pellet recipe''
Press “menu” to conrm.
Alter the % with the + - keys.
Press ''menu'' to conrm and ''esc'' to exit.
m - Fumes rpm % ventilation
In the event the installation presents problems in extracting smoke (lack of draft or even pressure in the duct), it is possible to increase the smoke and ash extraction speed. This change resolves all the potential problems related to pellets clogging in the brazier and deposits forming at the bottom of the brazier itself caused by poor quality fuel or fuel that produces a lot of ash. The extraction speed may be altered between -30% to +50%, with increments of 10 percent at a time. Negative variation can be necessary if the ame is too low.
To alter this parameter, proceed as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Scroll with the arrows and select "Fumes rpm Var."
Press “menu” to conrm.
Alter the % with the + - keys.
Press ''menu'' to conrm and ''esc'' to exit.
Page 55
53
10 - MENU ITEMS AND FUNCTION
Technical Dept. - All rights reserved - Reproduction is prohibited
n - Maximum power
Allows you to set the maximum power limit of the ames which the boiler can use to reach the set target temperature.
Modify the power as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Scroll with the arrows and select ''Maximum power''.
Press “menu” to conrm.
Change the power from 01 to 05 using the + - keys.
Press ''menu'' to conrm and ''esc'' to exit.
o - Components test
This can be done only when the boiler is o and allows you to select the components to be tested:
Spark plug: it is turned on for a xed test period during which the panel displays the countdown in seconds.
Feed screw: it is powered for a xed test period during which the panel displays the countdown in seconds.
Aspirator: it is activated at 2500 rpm for a xed test period during which the panel displays the countdown in seconds.
Exchanger: enables you to conduct the test in V5 for a xed test period during which the panel displays the countdown in seconds.
Pump: it is activated for a xed period of 10 seconds during which the panel displays the countdown.
3-way valve: the 3-way valve is activated for a xed test period of 1 minute during which the panel displays the countdown in
seconds.
Enable the "Component test" function (only with boiler o) as follows:
Press key 3 ''menu''.
Use the arrow keys to scroll through and select "Settings"
Press 3 “menu” to conrm.
Use the arrow keys to scroll through and select ''Component test''
Press 3 “menu” to conrm.
Use the + - keys to select the test to be carried out.
Press ''menu'' to conrm and ''esc'' to exit.
p - Chimney sweep Function
This function can only be activated when the boiler is on and power is supplied, and it forces operation of the boiler at the parameters P5, with the ventilator (if present) in V5. Any corrections to the loading/smoke ventilation percentage must be read. This state lasts 20 minutes, the countdown is displayed on the panel. During this interval, the system ignores any thermostat/puer/room set point/ set point H20 values, only the safety shut-down at 85°C remains active. At any time, the technician may interrupt this phase by pressing the on/o switch quickly. Enable the "Chimney sweeper" function as follows:
Press the ''menu'' key.
Use the arrow keys to scroll through and select "Settings"
Press “menu” to conrm.
Use the arrow keys to scroll through and select ''Chimney sweeper function''
Press “menu” to conrm.
Use the + - keys to select "On" (O by default)
Press ''menu'' to conrm and ''esc'' to exit.
Page 56
54
10 - MENU ITEMS AND FUNCTION
q - System conguration
To change the conguration of the system, proceed as follows:
Press the "menu" key.
Use the arrow keys to scroll through and select "Settings"
Press 3 “menu” to conrm.
Use the arrow keys to scroll through and select ''System conguration''
Press 3 “menu” to conrm.
Use the + - keys to modify the conguration between 01 and 05.
Press "menu" to conrm and "esc" to exit.
r - Season
In congurations 2 and 3, enabling the ''summer'' function disables deviation of the 3-way valve towards the heating system to prevent the radiators from heating up, and so the ow is always towards the hot water system (DHW). Selecting the "summer" option automatically enables the auto-eco function (cannot be deactivated). The room temperature probe/ external thermostat are ignored.
Modify the function as follows:
Press the ''menu'' key.
Use the arrow keys to scroll through and select "Settings"
Press 3 “menu” to conrm.
Use the arrow keys to scroll through and select ''Season''
Press 3 “menu” to conrm.
Use the + - keys to select "Summer" or "Winter".
Press "menu" to conrm and "esc" to exit.
s - Technical menu
To access the technical menu you must contact the assistance centre as it requires a password.
Access the "technical menu" as follows:
Press the ''menu'' key.
Use the arrow keys to scroll through and select "Settings"
Press 3 “menu” to conrm.
Use the arrow keys to scroll through and select ''Technical menu''
Press 3 “menu” to conrm.
With the + - keys, select "Product Type", "Service", "Parameters", "Sanitary Par", "Counter memories", "Enable fan" and "Puer data".
Press ''menu'' to conrm and ''esc'' to exit.
Page 57
55
1
3
2
5
4
V
10 - MENU ITEMS AND FUNCTION
Technical Dept. - All rights reserved - Reproduction is prohibited
SYSTEM CONFIGURATIONS
At the time of installation, the product must be congured according to the type of system by selecting the relative parameter in the "SETTINGS" menu. There are 5 possible congurations, described below:
Conguration Description
1 Room temperature control via boiler's on-board probe or by enabling external thermostat FACTORY SETTING
2 Room temperature control via boiler's on-board probe or enabling external thermostat; DHW production for
boiler or storage with thermostat (optional).
3 Room temperature control via boiler's on-board probe or enabling external thermostat; DHW production with
NTC probe (10 k ß3435).
4 External Puer controlled by thermostat.
5 External Puer controlled by NTC probe (10 k ß3435).
CONFIGURATION 1 (FACTORY SETTING)
Page 58
56
1
3
7
8
5
5
4
11
6
10
9
2
V
1
7
5
5
3
12
4
8
11
6
9
2
V
10 - MENU ITEMS AND FUNCTION
CONFIGURATION 2
CONFIGURATION 3
Page 59
57
3
2
5
5
17
13
11
4
4
15
14
7
6
1
V
10 - MENU ITEMS AND FUNCTION
Technical Dept. - All rights reserved - Reproduction is prohibited
CONFIGURATION 4
Page 60
58
1
5
5
44
13
11
6
7
14
16
2
3
V
10 - MENU ITEMS AND FUNCTION
CONFIGURATION 5
1 COMPACT SLIM 15
2 HEATING DELIVERY
3 HEATING RETURN
4 ZONE VALVE
5 HEATING BODIES
6 HOT SANITARY WATER
7 DOMESTIC COLD WATER
8 SANITARY WATER BOILER
9 DIVERTER VALVE
10 BOILER THERMOSTAT
11 THERMOSTATIC MIXER VALVE
12 NTC PROBE 10 k β3434 SANITARY WATER
13 HEATING PUFFER
14 HEATING SYSTEM CIRCULATOR
15 PUFFER THERMOSTAT
16 NTC PROBE 10 k β3434 PUFFER
17 SAFETY VALVE
V ANTI-CONDENSATION VALVE
Page 61
59
10 - MENU ITEMS AND FUNCTION
Technical Dept. - All rights reserved - Reproduction is prohibited
OPERATING MODE
The operating mode for boilers is always AUTOMATIC (there is no manual operating mode available). The modulation of the ame is controlled according to the "System conguration" by the room temperature probe located at the back of the appliance (see img.), by the external thermostat, by the temperature of the water in the boiler or by the NTC probes.
ELECTRICAL CONNECTIONS
TERMINAL BLOCK CONTACTS
POS.1-2 EXTERNAL THERMOSTAT/PUFFER THERMOSTAT POS.8 NEUTRAL THREE-WAY VALVE
POS.3-4 PUFFER/BOILER PROBE POS.9 THREE-WAY VALVE PHASE (sanitary)
POS.5 EARTHING POS.10 THREE-WAY VALVE PHASE (heating)
POS.6-7 AUXILIARY BOILER
Page 62
60
10 - MENU ITEMS AND FUNCTION
START-UP
Press key 1 (esc) to start up the appliance. The display will show ON with the ashing ame symbol. When the ame stops blinking, the boiler has reached the operating condition for "supplying power". The default target room temperature is set at 20°C. To change this setting, follow the instructions in the adjustments menu; do the same to set the heating water temperature and the speed of the ventilation fan. To activate an external thermostat, if present, see the dedicated paragraph.
POWER SUPPLY
When start-up is complete, the panel with show ON with a constant ame at level 3 . The modulation of the ame for higher or lower power is then controlled autonomously on the basis of the temperatures set in the "System conguration."
Page 63
61
11 - SAFETY DEVICES AND ALARMS
Technical Dept. - All rights reserved - Reproduction is prohibited
SAFETY DEVICES
The product is tted with the following safety devices
PRESSURE SWITCH
Monitors pressure in the smoke duct. It is designed to shut down the pellet feed screw in the event of an obstructed ue or signicant back-pressure. (caused by wind)
SMOKE TEMPERATURE PROBE
Detects the temperature of the smoke, thereby enabling start-up or stopping the product when the temperature drops below the preset value.
CONTACT THERMOSTAT IN THE FUEL HOPPER
If the temperature exceeds the preset safety level, it immediately shuts down the running of the boiler.
CONTACT THERMOSTAT IN THE BOILER
If the temperature exceeds the preset safety level, it immediately shuts down the running of the boiler.
WATER TEMPERATURE SENSOR
When the water reaches the stop temperature (85°C) the probe automatically instructs the boiler to turn o "OFF Stand-by".
ELECTRICAL SAFETY
The boiler is protected against violent changes in current by a general fuse located in the control panel at the back of the boiler. Other fuses that protect the electronic boards are found on the latter.
SMOKE FAN
If the fan stops, the electronic board shuts o the supply of pellets in good time, and an alarm message is displayed.
GEAR MOTOR
If the reduction motor stops, the boiler will continue to run until the ame goes out due to lack of fuel and until a minimum level of cooling is reached.
TEMPORARY POWER CUT
When a power cut is less than 10" the boiler returns to its previous operating state; if it is more, it executes a cooling/re-ignition cycle.
FAILED START-UP
If the fuel fails to ignite during the start-up phase, the boiler will go into alarm status.
ANTI-FREEZE FUNCTION
If the probe in the boiler detects a water temperature of less than 5°C, the circulation pump is automatically activated to keep the system from freezing.
PUMP ANTI-SEIZURE FUNCTION
If the pump is not used for prolonged periods, it is activated periodically for a few seconds to keep it from seizing up.
Page 64
62
C
F
11 - SAFETY DEVICES AND ALARMS
TAMPERING WITH THE SAFETY DEVICES IS PROHIBITED If the product is NOT used as described in this instruction manual, the manufacturer declines all liability for any damage caused to persons and property. In particular:
All the necessary measures and/or precautions must be adopted when performing maintenance, cleaning and repairs.
Do not tamper with the safety devices.
Do not remove the safety devices.
Connect the product to an ecient smoke expulsion system.
First, check that the environment where it is to be installed is properly ventilated.
Only after eliminating the cause of the intervention of the safety system is it possible to start the product back up. This manual will help you understand which anomaly has occurred, and explain how to intervene according to the alarm message displayed on the appliance.
Boiler stop
The following conditions may cause the product to be stopped:
Overheating of the structure and pellet hopper
Overheating of the water in the boiler
High pressure of the outlet fumes (read on the pressure switch) and possible obstruction of the outlet. The control panel will indicate the cause of the alarm and sound an acoustic warning. In this situation, the automatic shut-down sequence is activated. When this sequence is initiated, any attempt to restart the system will be ineective.
Safety thermostat with manual rearming at 95°C
The boiler enters a state of safety ALARM called "A03" Thermostat alarms, caused by high water temperature. To cancel the alarm status, the thermostat must be rearmed manually. Only when the boiler has cooled, remove the upper cover "C" and use a tool "F" at least 30 cm long inserted through the hole with the arrow to press the reset button; you will hear the thermostat click. The manually rearmed thermostat has now been reactivated. Replace the cover "C".
Page 65
63
11 - SAFETY DEVICES AND ALARMS
Technical Dept. - All rights reserved - Reproduction is prohibited
ALARM SIGNALLING
When a condition occurs other than the one expected for regular operation of the boiler, an alarm is triggered. The reason for the alarm is given on the control panel. The sound signal is not enabled for alarms A01-A02 in order not to disturb the user when there is an absence of pellets in the night tank.
Panel signalling type of problem Solution
A01
The ame does not light Check the level of pellets in the tank.
Check that the brazier is correctly positioned in its seat and has no build-up or unburned material. Make sure the ignition plug warms up. Thoroughly empty and clean the brazier before restarting.
A02
The ame is extinguished unexpectedly. Check the level of pellets in the tank.
A03
Thermostats alarm
The temperature of the pellet hopper or the water temperature exceeds the safety threshold.
Wait until the end of the cooling phase, stop the alarm and re-ignite the boiler setting the supply of fuel to minimum (SETTINGS menu - pellet recipe). If the alarm persists, contact the service centre.
A04
Smoke overtemperature The set smoke threshold has been exceeded. Reduce
the load of pellets (SETTINGS menu - Pellet recipe).
A05
Pressure switch alarm
Fumes pressure switch intervention or water pressure insucient.
Check for chimney obstructions / door open or the pressure of the hydraulic system.
A08
Anomalous operation of smoke fan. If the alarm persists, contact the service centre.
A09
Fault with the smoke sensor. If the alarm persists, contact the service centre.
A19
Fault with water sensor. Water sensor detached / interrupted / defective / not
recognised.
A20
Puer probe alarm. Puer probe detached / interrupted / defective / not
recognised.
Service
Routine maintenance warning (does not seize) When this blinking message appears upon start-up, it
means it is time to carry out scheduled maintenance. Call the assistance centre.
ALARM RESET
NEVER open the appliance door whilst the stove is either in the initial startup or on its shut down cycle, pellets will still be smoldering or therefore volatiles may be present. ATTENTION! If during operation or initial ignition you encounter smoke spillage in to the room from the appliance or the ue then please switch o the appliance, ventilate the room and contact the installation / service engineer immediately.
Page 66
64
11 - SAFETY DEVICES AND ALARMS
To reset the alarm, press and hold key 1 (ESC) for a few seconds. The boiler checks whether the cause of the alarm is ongoing. In the rst case, the alarm continues to be displayed, in the second case it turns OFF. If the alarm persists, contact a service centre.
NORMAL SHUTDOWN (on the panel: OFF with ashing ame symbol)
When the shutdown key is pressed, or when there is an alarm signal, the boiler enters the thermal extinguishing phase which involves automatic execution of the following phases:
Stop pellet loading
The smoke extractor fan is is activated at maximum speed and remains on for a xed period of 10 minutes, at the end of which if the smoke T has dropped below the stop threshold, the fan stops, otherwise it will continue to operate at minimum speed until the temperature drops below the threshold.
If the boiler has been shutdown regularly but, due to thermal inertia, the smoke temperature exceeds the threshold again, the shutdown phase will be repeated at minimum speed until the temperature falls.
BLACKOUT with boiler ON
In the event of a blackout, the boiler does the following:
Blackout of less than 10": continues the work in progress;
After a loss of power of more than 10'' which occurred when the boiler was on, or during ignition, you can restore the boiler to its previous operating condition when power returns as follows:
1. Cool the boiler by activating the smoke extractor at minimum speed for 10' then proceed to the next step;
2. Restore the boiler to the operating condition prior to the blackout.
During phase 1, the panel shows ON BLACK OUT. During phase 2, the panel shows Start-up. If during phase 1 the system receives manual user commands from the control panel, it stops the blackout restoration sequence and begins the start-up or shutdown commanded by the user.
BLACKOUT OF MORE THAN 10'' DURING EXTINCTION OF BOILER
If the boiler experiences a loss of power greater than 10'' while it is shutting down, when power is restored to the boiler, it will automatically turn on in shutdown mode, even if the smoke temperature has fallen below 45°C in the meantime. This phase can be skipped by pressing key 1 (esc) (skips to start-up) and pressing it again (recognises that the boiler is o).
Page 67
65
12-RECOMMENDATIONS FOR A SAFE USE
Technical Dept. - All rights reserved - Reproduction is prohibited
ONLY CORRECT INSTALLATION AND APPROPRIATE MAINTENANCE AND CLEANING OF THE APPLIANCE CAN GUARANTEE CORRECT OPERATION AND SAFE USE OF THE PRODUCT
We would like to inform you that we are aware of cases of malfunctioning of domestic pellet-fuelled heating products, mainly due to incorrect installation and use, as well as inadequate maintenance. We would like to assure you that all of our products are extremely safe and certied according to European standards of reference. The ignition system has been tested with the utmost attention to enhance ignition eciency and to prevent any type of problem, even in the worst operating conditions. In any case, like for any other pellet-fuelled product, our appliances must be installed correctly and undergo regular periodical cleaning and maintenance to guarantee safe operation. Our studies show us that malfunctioning is mainly due to the combination of part or all of the following factors:
Brazier holes obstructed or brazier deformed, due to lack of maintenance and conditions which can cause delayed ignitions, generating an anomalous production of unburned gases.
Insucient combustion air due to a reduced or clogged air inlet duct.
Use of smoke ducts nonconforming to regulatory installation requirements, failing to guarantee an adequate draught.
Partially clogged chimney, due to lack of maintenance, reducing the draught and making ignition dicult.
End chimneypot nonconforming to the indications of the instruction manual, and therefore not suitable to prevent potential inverse draught.
This factor is crucial when the product is installed in especially windy areas, such as costal regions.
The combination of one or more of these factors could generate important malfunctioning conditions. To keep this from occurring, it is fundamental to guarantee that the product is installed in compliance with standards in force. Furthermore it is of the utmost importance to respect the following simple rules:
Every time the brazier is removed for cleaning, it must always be put back properly in the work position before using the product, completely removing any residual lth left on the support base.
Pellets must never be loaded in the brazier manually, either before ignition or during operation.
The accumulation of unburned pellets ensuing a failed ignition must be removed before repeating ignition. Also check that they are fed correctly and that the combustion air inlet/smoke outlet are regular.
If ignition fails repeatedly, immediately suspend use of the product and contact a qualied technician to check its operation.
Compliance with these indications is absolutely sucient to guarantee proper operation and to avoid any type of problems with the product. If the above-mentioned precautions are not taken, and during ignition the brazier is overloaded with pellets thus generating anomalous smoke in the combustion chamber, carefully follow the indications below:
Do not disconnect electrical power to the product for any reason whatsoever: this would stop the smoke extractor, releasing smoke into the environment.
Take the precaution of opening the windows to ventilate the installation room from any smoke in the environment (the chimney might not work properly).
Do not open the re door: this would compromise regular operation of the smoke extraction system to the chimney.
Just switch the stove o by acting on the on-o button on the control panel (not the rear power supply socket button!) and move away until smoke has completely evacuated.
Before attempting re-ignition, clean the brazier and its air passage holes completely of all deposits and unburned pellets. Put the brazier back in place, removing any residue from its support base. If ignition fails repeatedly, immediately suspend use of the product and contact a qualied technician to check its operation and the chimney.
Page 68
66
13 - MAINTENANCE AND CLEANING
DAILY OR WEEKLY CLEANING PERFORMED BY THE USER
Only a proper maintainance and cleaning of the product can assure you the correct functionality and a safe use of your stove.
ATTENTION! All the cleaning operations of all parts must be performed with the product completely cold and the plug disconnected. Disconnect the product from the 230V power supply before performing any maintenance operation.
The product requires little maintenance if used with certied high quality pellets.
DAILY OR WEEKLY CLEANING PERFORMED BY THE USER Brazier cleaning
Before ignition, always clean the brazier and remove any ash or incrustation from it that might obstruct the air ow holes, paying attention to hot ash. In the case of ignition failure, or if fuel in the tank runs out, unburned pellets may accumulate in the brazier. Always empty the residue in the brazier before each start-up. Only if ash is completely cold may a vacuum cleaner be used to remove it. In this case, use a suitable vacuum cleaner to remove small sized particles.
REMEMBER THAT ONLY A CORRECTLY POSITIONED AND CLEAN BRAZIER CAN GUARANTEE SAFE IGNITION AND OPTIMAL OPERATION OF YOUR PELLET PRODUCT. IN CASE OF FAILED IGNITION AND AFTER ANY OTHER LOCK STATE OF THE PRODUCT, IT IS ESSENTIAL TO EMPT Y THE BRAZIER BEFORE EVERY RESTART.
For the brazier to be cleaned properly, remove it from its housing completely and thoroughly clean all the holes and the grate on the bottom. If good quality pellets are used, you will normally only need to use a brush to restore the optimal operating conditions of the component.
Ash tray cleaning
Remove and empty the ash tray. Wipe away any residual ash before reinserting the tray. Your experience and the quality of the pellets will determine the ash tray cleaning frequency. However, it is recommended not to exceed 2 or 3 days.
CLEANING THE ASH COLLECTION COMPARTMENT
Page 69
67
H
V
B
13 - MAINTENANCE AND CLEANING
Technical Dept. - All rights reserved - Reproduction is prohibited
CLEAN THE EXCHANGER AND THE COMPARTMENT BENEATH THE BRAZIER EVERY 2/3 DAYS
Cleaning the exchanger and the compartment beneath the brazier is a simple operation but very important if the boiler is to maintain optimal performance.
We therefore recommend cleaning the internal exchanger every 2-3 days, performing these simple operations in sequence:
Activate the "CLEANING" function - with the boiler o press - menu, select "Settings", with the arrows <> select "Cleaning", conrm with the "Menu" key, activate the cleaning "ON" with the + - keys. This procedure starts the smoke extractor on the maximum setting to expel the soot that becomes dislodged when the exchanger is cleaned.
Clean the pipe unit - Using the hook provided, shake the rods located beneath the cover "B" rmly 5-6 times. This should remove the soot that has deposited on the smoke ducts of the exchanger during normal use of the boiler (g. 1).
Deactivate the "CLEANING" function - this function is deactivated automatically after two minutes. If you need to stop the function sooner, press the "Esc" key.
Clean the smoke conveyor compartment (g.2) - The boiler is equipped with a removable ash tray "H" which collects any accumulations of soot and ash.
When done cleaning, close the cover and ash tray.
If the cleaning is not done every 2-3 days, the boiler could go into alarm caused by ash clogging after several hours of operation.
Figure 1 Figure 2
Page 70
68
x
V
13 - MAINTENANCE AND CLEANING
PERIODIC CLEANING PERFORMED BY A QUALIFIED TECHNICIAN
CLEANING THE EXCHANGER AND PIPE UNIT
CLEANING THE UPPER COMPARTMENT
With the boiler cool and after removing the covers (see paragraph on panel removal); loosen the 4 M6 screws "x" on the right and left and lift the cover "V" (g.3).
The three pipes have now been extracted (g.4). Using a rod or a brush for cleaning bottles, clean inside the pipe unit and the pipes, removing any ash deposits (g.5). Check the cover seal and replace it if necessary.
ATTENTION: the exchanger must be cleaned at the end of the season by an authorised technician so that any worn seals may be replaced.
Figure 3
Page 71
69
13 - MAINTENANCE AND CLEANING
Technical Dept. - All rights reserved - Reproduction is prohibited
Figure 5
Figure 4
Page 72
70
H
V
E
13 - MAINTENANCE AND CLEANING
CLEANING THE LOWER COMPARTMENT
Remove the brazier "V", lower the lever "E" and take out the tray "H". Clean the brazier and tray removing any ash and vacuum any ash or soot that may have accumulated under the tray. Check the seal of the door seal and replace it if necessary.
This general cleaning must be performed at the end of the winter season to make it easier to remove and combustion residue.
Page 73
71
L
s
13 - MAINTENANCE AND CLEANING
Technical Dept. - All rights reserved - Reproduction is prohibited
CLEANING OF THE SMOKE EXTRACTOR COMPARTMENT
Open the access panel on the right side, and remove the two screws "s" at the bottom right. Lower the window "L" and use the vacuum cleaner to remove any ash that has accumulated on the extractor fan.
Page 74
72
13 - MAINTENANCE AND CLEANING
CLEANING OF SMOKE DUCT AND GENERAL CHECKS: Clean the smoke extractor duct, especially around the T joints, bends and any horizontal sections. For information on cleaning the ue, contact a chimney sweep.
Check the integrity of the ceramic bre seals on the door of the boiler. If necessary, order new replacement seals from the retailer or contact an authorized service centre to carry out this task.
ATTENTION: The frequency with which the smoke exhaust system must be cleaned depends on the use of the boiler and the type of installation. We recommend relying on an authorized service centre for end-of-season cleaning and maintenance, they will carry out all of the previously mentioned work and make a general check of the stove's components.
END-OF-SEASON SHUTDOWN
At the end of the season, before shutting down the boiler, we recommend removing all pellets from the hopper with a vacuum cleaner with an extension. When starting up the boiler at the beginning of the season, if the control panel display fails to light up when you press the power switch (located on the back of the boiler), it could mean that the service fuse needs replacing. There is a fusebox at the back of the boiler underneath the power socket. Open the fusebox cover with a screwdriver and replace the fuse if necessary (3.15 A delayed) - seek assistance from an authorised and qualied technician.
CHECKING THE INTERNAL COMPONENTS
ATTENTION! The internal electromechanical components must only be checked by qualied personnel whose technical expertise includes combustion and electricity.
We recommend that an annual maintenance service is carried out with a scheduled service contract. This service is essentially a visual and functional inspection of the following components: The following is a summary of the checks and/or maintenance that are indispensable for the correct operation of the product.
Gearmotor
Smoke extractor fan
Smoke probe
Ignition spark plug
Automatic rearm pellet thermostat
Manual rearm water thermostat
Room/water temperature probe
Motherboard
Fuses protecting panel-motherboard
Wiring
Page 75
73
13 - MAINTENANCE AND CLEANING
Technical Dept. - All rights reserved - Reproduction is prohibited
PARTS/INTERVAL 23 DAYS EVERY WEEK 15 DAYS 6090 DAYS
EVERY
SEASON
EVERY 2 SEASONS
Cleaning the brazier *
.
Cleaning the ash collection tray with the vacuum cleaner
.
Cleaning the ash tray
.
Cleaning the re door porthole
.
Cleaning pipes
.
Cleaning lower ash tray
.
Cleaning the outlet "T" (outside the boiler)
.
Cleaning the exchangers and removing ash and incrustations
.
Cleaning the smoke tting
.
checking the circulation pump
.
Checking for hydraulic leaks
.
Checking the door seal
.
Checking the spark plug
.
* The frequency of cleaning should be increased if the pellets are of poor quality.
Page 76
74
14 - TROUBLESHOOTING
CHECKING THE INTERNAL COMPONENTS
ATTENTION: GUIDE FOR THE USE OF THE SPECIALISED TECHNICIAN ONLY ATTENTION: All repairs must be carried out exclusively by a specialised technician, while the boiler is completely cold and the electric plug is disconnected. The operations in bold type must be carried out by specialised personnel. The manufacturer will not be liable and the guarantee is invalidated if this condition is not respected.
ANOMALY POSSIBLE CAUSES SOLUTIONS
The pellets are not fed into the combustion chamber.
The pellet hopper is empty Fill the hopper with pellets
Sawdust has blocked the feed screw Empty the hopper and remove the sawdust
from the feed screw by hand
Faulty gear motor Replace the gear motor
Faulty electronic board Replace the circuit board
The re goes out or the boiler stops automatically.
The pellet hopper is empty Fill the hopper with pellets
The pellets are not fed See the previous anomaly
The pellet temperature safety probe has been triggered
Let the boiler cool down, reset the thermostat until the problem is resolved and switch the boiler back on. If the problem persists contact Technical Assistance.
The door is not closed properly or the gaskets are worn
Close the door and replace the gaskets with original ones
Unsuitable pellets Change the type of pellets with those
recommended by the manufacturer
Low pellet supply Check the ow of fuel following the instruc-
tions in the booklet.
The combustion chamber is dirty Clean the combustion chamber, following
instructions in the manual
Clogged outlet Clean the smoke duct
Faulty smoke extraction motor Check the motor and replace it, if necessary
Pressure switch broken or defective. Replace the pressure switch.
Page 77
75
14 - TROUBLESHOOTING
Technical Dept. - All rights reserved - Reproduction is prohibited
ANOMALY POSSIBLE CAUSES SOLUTIONS
The boiler runs for a few minutes and then goes out.
Start-up phase is not completed Repeat start-up
Temporary power cut Wait for the automatic restart
Clogged smoke duct Clean the smoke duct
Faulty or malfunctioning temperature probes
Check and replace the probes
Faulty spark plug Check the spark plug and replace it, if
necessary
Pellets accumulate in the brazier, the glass of the door gets dirty and the ame is weak
Insucient combustion air Clean the brazier and check that all the
holes are clear. Perform a general cleaning of the combustion chamber and the smoke duct. Check that the entry of air is not obstructed.
Damp or unsuitable pellets Change the type of pellets
Faulty smoke evacuation motor Check the motor and replace it, if necessary
The smoke evacuation motor does not work
No electrical supply to the boiler. Check the mains voltage and the
protection fuse
The motor is faulty Check the motor and capacitor and replace
them, if necessary
Defective motherboard Replace the electronic board
Control panel broken Replace the control panel
In the automatic position the boiler always runs at full power.
Thermostat is set to minimum Reset the temperature of the thermostat.
Room thermostat in position that always detects cold.
Reposition of the probe
Malfunctioning temperature probe. Check the probe and replace it if necessary.
Faulty or malfunctioning control panel. Check the panel and replace if necessary.
Page 78
76
14 - TROUBLESHOOTING
The stove does not run No power supply Check that the plug is inserted and the
main switch is in the “I” position.
Pellet probe stop Cancel stoppage by changing the setting of
the rear thermostat. If the problem persists, request assistance.
Blown fuse Replace the fuse.
Pressure switch broken (lockout indicated).
Insucient pressure of water in boiler
Clogged smoke exhaust or smoke duct. Clean the smoke exhaust and/or the
smoke duct.
Water temperature sensor triggered Call for assistance
ANOMALIES RELATED TO THE HYDRAULIC CIRCUIT
No increase in temperature with boiler in operation
Incorrect combustion adjustment. Check recipe and parameters.
Boiler / system dirty. Check and clean the boiler.
Insucient stove power. Check that the boiler is properly sized for
the requirements of the system.
Poor pellet quality Use quality pellets.
Condensation in boiler Incorrect temperature setting. Set the boiler to a higher temperature.
Insucient fuel consumption. Check the recipe and/or technical
parameters.
Radiators cold in winter Room thermostat (local or remote) set
too low. If remote thermostat, check if it is defective.
Set to higher temperature or replace. (if remote)
Circulator does not run because blocked. Free up the circulator by removing the plug
and turning the shaft with a screwdriver.
Circulator does not run. Check the electrical connections of the
circulator; replace if necessary.
Radiators have air in them Vent the radiators
ATTENTION!
The operations in italics must be carried out by specialised personnel. The manufacturer will not be liable and the guarantee lapses if this condition is not respected.
Page 79
77
15 - ELECTRICAL PLAN
Technical Dept. - All rights reserved - Reproduction is prohibited
MOTHERBOARD WIRING KEY
1. FUSE
2. BOARD PHASE
3. BOARD NEUTRAL
4. SMOKE EXTRACTOR FAN
5. ROOM FAN
6. PELLET SAFETY THERMOSTAT
7. WATER TEMPERATURE OVERLOAD CUT-OUT
8. SPARK PLUG
9. CONNECT TO THE WATER PRESSURE SWITCH OF THE HYDRAULIC KIT (OPTIONAL)
10. AIR PRESSURE SWITCH
11. AUXILIARY BOILER CONNECTION (TERMINAL)
12. AUGER
13. SMOKE TEMPERATURE PROBE
14. EXTERNAL THERMOSTAT CONNECTION (TERMINAL)
15. ROOM TEMPERATURE PROBE
16. PUFFER/BOILER PROBE CONNECTION (TERMINAL)
17. BOILER WATER TEMPERATURE PROBE
18. SMOKE EXTRACTOR FAN REVOLUTION CONTROL
19. BOILER FLOW SWITCH OR THERMOSTAT TO CONNECT TO THE HYDRAULIC KIT (OPTIONAL)
20. 3-WAY VALVE PHASE (HEATING)
21. 3-WAY VALVE PHASE (DOMESTIC)
22. PUMP PHASE
23. PUMP NEUTRAL
24. 3-WAY VALVE NEUTRAL
25. CONTROL PANEL
PLEASE NOTE The electrical wiring of individual components is tted with pre-wired connectors of dierent sizes.
Page 80
REV. 38901305300 04/02/2016
Via La Croce n°8
33074 Vigonovo di Fontanafredda (PN) – ITALY
Telephone: +39 0434/599599 r.a.
Fax: +39 0434/599598
Internet: www.mcz.it
e-mail: info.red@mcz.it
Loading...