Up to 85% Thermal Efficiency
California AB 1953 Compliant - < .25% Pb
100% Factory Fire Tested
Maximum Outlet Water Temperature: 200°F
Minimum Acceptable Inlet Water Temperature: 120°F
Full Safety Diagnostics with History
Footprint: Less Than 5-1/2 ft
Limited Twenty-Year Thermal Shock Warranty
Limited Five-Year Heat Exchanger Warranty
Soft-Start Modulating Controller with LCD Display
2
MVB
®
- Type WH
Water Heaters
Models 504-2004
Status Display Lights
Heat Exchanger
Bronze Headers
ASME HLW Stamped
160 PSIG Working Pressure
National Board Approved
Fin Tubing
Copper – Standard
Cupro Nickel – Option A-3
ASME Powder-Coated Tube
Sheet
Silicone High Temp O-Rings
ASME Pressure Relief Valve
125 PSIG – Standard
PSIG – Optional
Temperature and Pressure
Gauge,
Shipped Loose
Stainless Steel Evaporator Plate
Control
120V, 60Hz, 1Ø, Power Supply
120/24V 60Hz Transformer
Ignition Module
3-Try – Standard
Single-Try – Option C-6
Hot Surface Ignition (HSI)
Remote Flame Sensor
High Limit, Manual Reset, Fixed,
200ºF
On/Off Power Switch
Flow Switch
Blocked Vent Pressure Switch
Combustion Air Proving Switch
Pump Switch
Pump Time Delay
Diagnostics Panel
Control (cont.)
On/Off Temperature Control
Water Temperature Sensors (3)
Burner
Ultra-Low NOx: Less than 20 PPM
Gas Train
Fuel
Natural Gas
Propane
Zero Governor Regulator
Dual-Seat Combination Valve
On/Off Firing with Soft-Start
Construction
Indoor/Outdoor Construction
Front Controls Enclosed
PolyTuf Powder Coat Finish
Rear Connections (Water, Electrical,
Gas, Vent, Combustion Air)
Design Certified ANSI Z21.10.3/
CSA 4.3
AB-1953 Compliant
Venting
Vent Termination
Outdoor – Option D-11
Indoor, Horizontal – Option D-15
Indoor, Vertical (by others)
Combustion Air
In-Line Filter Kit – Option D-17
Air Intake Elbow – Option D-16
Extractor – Optional
By others
Not required
Temperature Controllers
B-26 Temp-Tracker Digital Controller,
2 Water Heaters
B-21 Temp-Tracker Digital Controller,
3-4 Water Heaters
Y-241 Electronic Sequencer,
2-4 Water Heaters
Y-281 Electronic Sequencer,
5-8 Water Heaters
Options
A-30 Air Vent, Auto, 150 PSI
F-10 Low Water Cut-Off, Remote Probe
I-3 High Limit, Auto Reset, Adj.,
40-180°F
I-5 High Limit, Manual Reset, Adj.,
100-200°F
P- Bronze Pump: HP, 120V, 1∅,
60Hz
Water Hardness:
P- Cold Water Start
P- Cold Water Run
S-1 Low Gas Pressure Switch,
S-2 High Gas Pressure Switch,
Regulatory Agency Requirements
Loose Mounted
Manual Reset
Manual Reset
GPG
L
W
Catalog No.: 3500.284D Effective: 02-15-10 Replaces: 07-15-08

MVB – Type WH
Models 504-2004 Model
Model
(WH1-)
504 500 420 43 30 35 23-3/4 1 2 8 14-1/8 6 36 8 2 600 5.4 12
754
1104 1045 888 55 43 47 35-3/4 1-1/4 2-1/2 10 16 6 49 8 2 720 5.4 12
1504 1425 1211 61 50 53 41-3/4 1-1/4 2-1/2 12 18-1/8 8 53 8 2 780 5.4 12
2004 1900 1615 75 61 65 53-3/4 2 2-1/2 14 20-1/8 8 69 9 5 940 5.4 18
- Ratings shown are for elevations up to 4,500 feet. For installations at elevations
above 4,500 feet, please consult the factory for additional instructions.
- For direct vent applications, please contact the factory about relocating the pump.
MBTUH
Input Output Height NPT NPT Flue Ø C/A Ø
750 630 49 36 41 29-3/4 1 2 10 16 6 42 8 2 670 5.4 12
B D E F G H K M N P R V
Dimensions (in.)
* Current draw is for heater only.
(Supply breaker must have delayed trip.)
Ship
Weight
(Lbs.)
Foot-
print
(Ft
2
Amps*
)

Model
(WH1-)
*
PUMP HP – AMPS*
Water Hardness
Soft Medium Hard
504 1/4 - 6 1/4 - 6 3/4 - 11
754 1/4 - 6 1/2 - 7 3/4 - 11
1104 1/4 - 6 1/2 - 7 1 - 14
1504 1/2 - 7 1 - 14 1 - 14
2004 1 - 14 1 1/2 - 15 1 1/2 - 15
CLEARANCES
Front 24” 24”
Rear 12” 24”
Right 1” -Left 1” -Top 0” 10”
Floor 0” -Vent 1” --
Certified
Minimum
Recommended
Service
Water Hardness
Soft Medium Hard*
0-4 Grains Per Gallon 5-15 Grains Per Gallon 16-25 Grains Per Gallon**
ΔT
Model
504 17 50 3.6 2 8.3 17 50 3.6 2 8.3 9 95 10.4 2 25.7
754 26 50 4.0 2 8.7 17 73 7.8 2 17.3 14 90 11.4 2 25.3
1104 21 85 11.5 2-1/2 16.2 21 85 11.5 2-1/2 16.2 15 116 19.6 2-1/2 27.8
1504 27 94 16.2 2-1/2 21.7 24 105 19.6 2-1/2 26.5 22 115 23.0 2-1/2 31.1
2004 31 108 25.2 2-1/2 32.4 31 108 25.2 2-1/2 32.4 29 118 29.6 2-1/2 38.1
SHL includes 50ft of tubing each way (total 100 ft)
* Must use optional Cupro-nickel heat exchanger
** If over 25 GPG, a water softener MUST be used.
(ºF)
GPM
ΔP
(ft wc)
504 2545 1697 1273 1018 848 727 636 566 509
754 3818 2545 1909 1527 1273 1091 955 848 764
1104 5383 3589 2692 2153 1794 1538 1346 1196 1077
1504 7341 4894 3670 2936 2447 2097 1835 1631 1468
2004 9788 6525 4894 3915 3263 2797 2447 2157 1958
MTS
(in)
SHL
(ft wc)
ΔT
(ºF)
Temperature Rise (ºF)
20 30 40
GPM
RECOVERY RATES
50 60 70 80 90 100
ΔP
(ft wc)
MTS
(in)
SHL
(ft wc)
ΔT
(ºF)
GPM
ΔP
(ft wc)
MTS
(in)
SHL
(ft wc)

Raypak, Inc. ▪ 2151 Eastman Avenue, Oxnard, CA 93030 ▪ (805) 278-5300 ▪ Fax (805) 872-9725 ▪ www.raypak.com