Raypak WH1-1003 Installation Manual

Page 1
INSTALLATION & OPERATING
INSTRUCTIONS
Cold Water Start & Cold Water Run
For Hi Delta, MVB & Raytherm
Heaters & Boilers
This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place for future reference.
Catalog No: 1000.57I Effective: 02-27-13 Replaces: 07-22-10 P/N 241275 Rev. 10
Page 2
Rev. 10 reflects the following: Changes to: Additions:
Deletions:
None
None
Illustrated Parts List (was on previous pages 34-39)
Page 3
CONTENTS
WARNINGS 4 GENERAL SAFETY 5
Time/Temperature Relationships in Scalds 5
COLD WATER START 6
Installation 6 Check Power Source 6 Mounting the Control Box 6 Installing the Temperature Sensor 7 Connecting the Valve Assembly 7 Connecting Power to the Controller 8 Connecting Boiler to Cold Water Start 8 Operation 8 Cold Start Sequence of Operation 9 Troubleshooting 10 Mounting the Actuator to the Valve 11 Mounting Brackets 11 Locating the Rotation Stop 11 Drive Linkage 12 Verifying B Actuator to Valve Orientation 12 Installing the Three-Way Valve 13 High Pressure Tab 13 Actuator 13 Cold Water Start Troubleshooting Guide 14 Typical Cold Water Start Piping 15 Wiring Diagram 16 Heater Interface Wiring 17
CWS—MULTIPLE BOILER 18
Materials Included 18 Installation 18 Mounting the Control Boxes 18 Installing the Temperature Sensor 18 Installing the Three-Way Valve 18 Connecting Power to the Controller 18
all Position 12
Connecting Cold Water Start to Multi­Heater Interlock Box 18 Connecting Heater to Cold Water Start Multi-Heater Interlock 18 Actuator to Valve Orientation 19 Three-Way Valve Ball Orientation 19 Valve Installation 19 4 Inch Valve Orientation 20 Connecting the Actuator 20 Typical Cold Water Start Multiple Boiler Piping 21 Wiring Diagram 22
COLD WATER RUN 23
Purpose 23 Typical Cold Water Run Applications 23 CWR vs. CWS 23 Installation 23 Installation Codes 23 Mounting the Injector & Heater Pump Comparison 24 Check the Power Source 25 Injector Pump Wiring 25 Injection Pump Cover Installation 27 Typical Cold Water Run Piping ­Heating Applications 29 Typical Cold Water Run Piping ­Pool Applications 29 Operation 30 Cold Run Sequence of Operation 30 Cold Water Run Troubleshooting Guide 31 Wiring Diagrams 32
REPLACEMENT PARTS 34
Control B
ox 23
Page 4

WARNINGS

Pay Attention to These Terms
DANGER:
WARNING:
CAUTION:
NOTE:
NOTE: Minimum 18 AWG, 105°C, stranded wire
must be used for all low voltage (less than 30 volts) external connections to the unit. Solid conductors should not be used because they can cause exces­sive tension on contact points. Install conduit as appropriate. All high voltage wires must be the same size (105°C, stranded wire) as the ones on the unit or larger.
Indicates the presence of immediate hazards which will cause severe person­al injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
NOTE: Piping diagrams in this manual are not intended to replace an engineered piping system.
NOTE: Consult the factory for units with a 30 pound pressure relief valve (PRV).
Page 5
GENERAL SAFETY
Water temperature over 125°F can cause instant severe burns or death from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
See instruction manual before set­ting temperature at water heater.
Feel water before bathing or show­ering.
Temperature limiting valves are available, see manual.
Water
Temp.
Time to Produce
Serious Burn
120°F More than 5 minutes
125°F 1-1/2 to 2 minutes
130°F About 30 seconds
135°F About 10 seconds
140°F Less than 5 seconds
145°F Less than 3 seconds
150°F About 1-1/2 seconds
155°F About 1 second
Table co urtesy of The Shriners Burn Institute
To meet commercial hot water use needs, the high limit safety control on this water heater is adjustable up to 210°F. However, water temperatures over 125°F
an cause instant severe burns or death from scalds.
c When supplying general purpose hot water, the rec­ommended initial setting for the temperature control is 125°F.
Safety and energy conservation are factors to be con­sidered when setting the water temperature on the thermostat. The most energy-efficient operation will result when the temperature setting is the lowest that satisfies the needs of the application.
Water temperature over 125°F can cause instant severe burns or death from scalds. Children, disabled and elderly are at highest risk of being scalded.
Feel water before bathing or showering.
Temperature limiting valves are available.
NOTE: When this water heater is supplying general purpose hot water for use by individuals, a thermo­statically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury. Contact a licensed plumber or the local plumbing authority for further information.
Maximum water temperatures occur just after the heater’s burner(s) have shut off. To determine the water temperature being delivered, turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer.
Time/Temperature Relationships in Scalds
The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.
Table A: Time to Produce Serious Burn
Page 6
COLD WATER START
CIRCUIT
B
REAKER
W
HITE
GROUND
B
LACK
GREEN
AB C
Before beginning the installation, it's important to first
nspect the system and determine what materials you
i will need. Some parts are included with the controller while others you will need to provide.
1 Control Box
1 Temperature Sensor
1 Valve assembly with actuator (Shipped separately)
Wiring and mounting hardware (Provided by installer)
NOTE: After testing at the factory it may be prudent to ship the piping assembly disassembled and attached to the heater pallet. This is done to avoid shipping damage and it must be reassembled on the jobsite. Use Fig. 1 to assist in reassembling the pip­ing.
Fig. 2: Wiring Connections
Check the power source:
AC = 108 VAC Minimum, 132 VAC MAX AB = 108 VAC Minimum, 132 VAC MAX
BC = <1 VAC Maximum
Fig. 1: Cold Water Start Assembly
Installation
Check the Power Source
CAUTION: Do not use for swimming pool applica-
tions
WARNING: Using a multi-meter, check the follow­ing voltages at the breaker panel prior to connecting any equipment. Make sure proper polarity is followed and house ground is proven.
Mounting the Control Box
The control box should be mounted on the side of the heater to which the system piping and valve assembly are to be attached as shown in Figs. 4–8. The con­troller should be mounted so as to provide maximum support by using the mounting holes provided on the base of the controller to the side center brace on the heater. On MVB and Hi Delta models, locating dimples are provided for ease of drilling the mounting holes. You will need to drill mounting holes through the heater side panel for the routing of wiring and the sensor.
Fig. 3: Multi-meter
Page 7
THREE-WAY VALVE
11-1/8”
1”
10-5/16”
11-1/8”
11/16”
7-1/4”
Installing the Temperature Sensor
void routing wiring on or near other electrical wires,
A conduit, motors, spark igniters or other sources of high
ntermittent voltage or current. The sensor should be
i placed in the dry well on the inlet header, or as indicat­ed in the piping for multiple heaters, as shown on page
21. Ensure it is installed using thermal paste (field supplied) and that it is held firmly at the bottom of the well.
Connecting the Valve Assembly
Connect the valve assembly into the bypass piping. The branch (port B) is connected to the crossover pipe (bypass between inlet and outlet). The actuator tail stock should be oriented to point down. Refer to the Actuator to Valve Orientation section.
Route wiring from the valve to the controller thru one of the bottom panel conduit knockouts to TB2. Refer to the wiring diagram provided on the inside of the con­troller cover assembly.
NOTE: Four knockouts are located on the bottom
f the control for ease of installation.
CAUTION: Miswiring the actuator may cause unwarrantable damage. Verify the wire colors against the actuator make and model.
LEFT SIDE
Fig. 5: Component Locations—Raytherm Models
514–824
Models X Y Z
302B-902B
992B-2342B
Fig. 4: Component Locations—Hi Delta
7 2 1-9/16
13-1/41-5/16 6-5/8
Fig. 6: Component Locations—Raytherm Models
926–1826
Page 8
Reset Switch*
9-9/16”
5/16”
1-3/4”
22”
7
-5/8”
1-1/2”
*The reset switch may be located on the front control panel on some MVB models.
Fig. 9: Location of TB1 in Control Box
Fig. 7: Component Locations—Raytherm Models
2100–4001
INSTALL INSULATION ON INSIDE OF REAR PANEL
Fig. 8: Component Locations—MVB
Connecting Power to the Controller
Connect power from the 120 VAC power input of the heater to the controller power inputs Terminal Block (TB1). This is accomplished by connecting wiring from the control box to the heater 120 VAC power input con­nections. Refer to the heater wiring diagrams.
Connecting Boiler to Cold Water Start
The installer must provide five 18AWG stranded wires between the heater and the controller terminal block. Wiring is to be run in separate conduit from line volt­age to ensure proper operation. Refer to the diagrams on page 17 for connection points depending on the Raypak product being used.
Operation
Verify the following upon a CALL FOR HEAT signal from the heater:
1. CALL FOR HEAT: LED on PCB illuminates GREEN.
CAUTION: Install the foil-faced insulation on the inside of the rear panel of MVB heaters as indicated in Fig. 8. Use spray adhesive or high temp foil tape to attach the insulation. Ensure that the foil faces the heat exchanger assembly. Failure to install this insu­lation as directed can cause overheating of the com­ponents and may void the warranty on the control.
2. START UP MODE: LED on PCB illuminates YEL­LOW. It should go out in less than 7 minutes, as the boiler inlet temperature approaches the setpoint temperature.
3. The “ACTUATOR” should be in the fully open posi­tion or move to the fully open position if not already there. (Actuator and ball rotated to the at-rest CCW position).
Page 9
Setpoint
Pot
CALL FOR HEAT START UP MODE I
NLET TEMP ERROR
SENSOR OUT OF RANGE
Fig. 10: Control PCB
4. If the control is operating properly, the “START UP MODE” LED should go out in less than 7 minutes. At this point, the inlet water temperature should be stable at a temperature between 105°F and 120°F corresponding to the Setpoint Pot setting on the PCB. The actuator should have stopped moving.
NOTE: The minimum inlet water temperature to the heater to prevent condensate is 105°F on heaters with an efficiency of 85% or less, and 120°F on 87% efficiency heaters. Ensure that during operation the Setpoint Pot is adjusted properly.
NOTE: If a “DIP” switch is provided on the control PCB, verify that the switch settings are: 1 = OFF, 2 = ON, 3 = OFF.
Cold Start Sequence of Operation
1. 120VAC to heater sends 120VAC to Cold Start
control on terminal block 1.
2. 120/24VAC transformer and 120VAC-12VDC con-
verter are powered.
3. 120/24VAC transformer outputs 24VAC to pin 2 of
terminal block 2
4. 24VAC leaves pin 2 of terminal block 2 and goes
to the modulating three-way valve on the 20­30VAC lead, and to the NO contacts of the SPST relay located in the cold start control panel.
. 120VAC-12VDC converter outputs 12VDC to the
common terminal of the reset switch, located on the bottom of the cold start control panel.
6. The 12VDC signal crosses over the reset switch nd goes to Terminal FS on the cold start circuit
7. Cold start control is now in standby until a Call for
Heat occurs at heater.
8. The heater outputs 24VAC to terminal 4 of termi-
nal block 3 located in Cold Start controller to indicate a CFH from the heater.
9. Terminal 4 of TB 3 sends 24VAC to the coil of the
SPST relay located in the cold start control panel.
10. The SPST relay coil is energized and closes the
contacts allowing 24VAC to energize the CFH ter­minal on the cold start circuit board. a) A two second delay occurs from the CFH sig-
nal to the output of power from terminal MC of the cold start circuit board.
11. 24 VAC is sent from terminal 2 of terminal block 3
to the NO contacts of the DPST relay located in the cold start control panel.
12. After the two second delay on the cold start circuit
board, pin MC outputs a 24 VAC signal to the coil of the DPST relay located in the cold start control panel.
13. The DPST relay coil energizes and closes the NO
contacts.
14. Once the NO contacts of the DPST close, the
heater 24 VAC is sent back to the heater to com­plete the circuit (pin 3 of terminal block 3) and the interlock circuit (pin 1 & 2 of terminal block 3) allowing the heater to fire.
15. Pin FR on the TVC board outputs 10VDC to the
modulating three-way valve actuator to drive it fully open for two minutes waiting for the heater to reach full fire.
16. After the two-minute delay the 10VDC output sig-
nal from pin FR reduces to approximately 8VDC.
17. The output signal continues to vary depending on
the heater inlet temperature.
NOTE: The heater will lockout and shut down if the setpoint on the inlet temperature is not achieved within seven minutes from a call for heat.
Page 10
D
IP SWITCH SETTINGS
F
OR 3-WAY ACTUATOR
VDC
0-10
DA
FIXED
~
mA
2-10
RA
AUTO
6-9
S
WITCH MUST BE IN THIS POSITION
TURN CLOCKWISE TO FURTHEST STOP
M
ODE SELECTION SWITCH
DIRECT ACTING, ON INCREASING SIGNAL
SIDE
“A”
NOTE:
SIDE “A” MUST FACE AWAY FROM VALV E
DETENT MUST BE
SET TO POSITION 4
S
IDE
“B”
NOTE:
SIDE “B” MUST FACE AWAY F
ROM VALV E
he DIP switches on the three-way valve actuator
T must be set as indicated in the Fig. 11 below:
Fig. 11: Set Dip Switch Settings — Delta Actuator
Fig. 14: Elodrive Actuator — Actuator Shown in Full
System Flow Position
NOTE: The Elodrive actuator is NEMA 4 rated. No outdoor cover is required.
Troubleshooting
Fig. 12: Delta Actuator — Actuator Shown in Full
System Flow Position
CAUTION: Delta actuator requires the use of the factory-supplied weatherproof cover for outdoor installations.
Check your power source using a Volt-Ohm meter; check the following voltages at TB1 terminal block:
TB1-1 to TB1-2 = 108 VAC Minimum, 132 VAC Maximum
TB1-1 to TB1-3 = 108 VAC Minimum, 132 VAC Maximum
TB1-2 to TB1-3 = Must be less than .6 VAC
IF CALL FOR HEAT LED does not illuminate when the heater has a CFH signal, check for 24VAC between pins 4 and 5 of TB3 on the cold start control. If voltage is present, check wiring using the wiring diagram. If voltage is not present, the problem exists in the heater.
IF VALVE DOES NOT MOVE: Check for voltage out at TB2-1: Should be a 1VDC to 10VDC output to the actuator valve. If no voltage is present, check for volt­age at pin FS on the control board, there should be a 12VDC signal. If the 12VDC signal is not present, ver­ify that the converter is wired correctly using the wiring diagram.
Fig. 13: Elodrive Actuator — Rotation Knob Setting
Set adjustment knob to Position 4
IF INLET TEMP ERROR is illuminated: The setpoint temperature has not been reached within the 7 minute time period.
Push the Reset Switch (see Fig. 9) or remove power and watch for proper operation.
10
Page 11
Check pump sizing and valve/piping sizing and cor-
• rect as necessary.
IF SENSOR OUT OF RANGE LED is illuminated: The sensor may have a short or open circuit.
Press and release the Reset Switch (see Fig. 9) and watch for proper operation.
Replace sensor.
Check wiring using wiring diagram.
Mounting the Actuator to the Valve
When mounting the actuator to the valve, ensure that the valve stem is oriented with the machined flat notch positioned parallel to the “A” and “AB” ports as shown in Fig. 15.
All actuators used by Raypak include the “spring return” safety feature. This means that upon loss of power during operation the valve automatically rotates back to the full system flow position avoiding high limit lockouts or other issues.
Mounting Brackets (Elodrive)
There are different actuator mounting brackets on the three-way valves. When ordering a replacement bracket you will receive the newest design available
rom the manufacturer. If it appears to be different than
f the damaged bracket, the new and old are inter­changeable and will fit all valve bodies. See Fig. 16.
A
B
AB
Flat Notch
Fig. 15: Orient Notch Parallel with “A” and “AB” Ports
Flow
Fig. 16: Elodrive Mounting Bracket
Locating the Rotation Stop (Elodrive)
An internal rotation stop device is built into the actua­tor mounting bracket and this can be installed only two ways for proper operation of the valve. The stop is labeled on each side with either “D” or “P”. This indi­cates that the valve is set up for either a diverting application or proportional (mixing) application. Raypak uses the three-way valve in a mixing applica­tion therefore the “P” designator must be facing away from the bracket.
The valve rotates in a clockwise direction when it is operating. The rotational stop must be positioned so that the drive linkage can rotate. The drive linkage is keyed to allow only 90 degrees of rotation. Ensure that the key is positioned so the linkage may rotate clock­wise as shown in Fig. 17.
11
Page 12
If you do not see two openings at this point, con-
PORT A B
POSITION ROTATIONAL STOP SO THAT DRIVE LINKAGE CAN ROTATE
tinue rotating the stem and ball until you do.
Once you can see two openings, STOP, as shown n Fig. 18. Then rotate the stem counterclockwise
i until only one opening remains e.g. you can see
ompletely through the valve (through ports A and
c AB).
Now the ball is correctly oriented inside of the valve body. Reassemble the valve, base and actuator, and then install the assembly into your piping system as indicated in this manual.
Fig. 17: Elodrive Rotational Stop Positioning
Drive Linkage (Elodrive)
The drive linkage for the 2” NPT and 2-1/2” NPT three­way valves originally were supplied with an orientation groove in the end of the stem. This groove has now been removed by the vendor. All new linkage stems will have a smooth end. Using the groove to determine ball position inside of the valve is not reliable and should be avoided.
Verifying Ball Position
All field-installed valves must have the ball properly positioned. Occasionally differences occur from the manufacturer of the valve body. The square stem that the drive linkage attaches to should have a machined notch to verify ball position, however on occasion it is not there. To properly orient the ball follow these instructions PRIOR to installation into your plumbing system.
Remove the actuator and base from the valve body.
With port “AB” facing you, rotate the valve stem approximately 45 degrees clockwise. You must see two port openings if the ball is correctly orient­ed.
Fig. 18: Verifying Ball Position
Actuator to Valve Orientation
Install the actuator so that the tail is pointing downward as shown in Fig. 19. You may also install it horizontal­ly, however, DO NOT mount it so that the tail is pointing up as shown in Fig. 20. Doing so will allow water and debris to collect in the cup where the wiring exits the actuator, potentially causing damage.
Fig. 19: Recommended Orientation of Actuator
12
Page 13
Fig. 20: Incorrect Orientation of Actuator
HIGH PRESSURE TAB
INSERT ALLEN WRENCH UNDER THIS LABEL
Installing the Three-Way Valve
Fig. 21: High Pressure Tab
Actuator
The ELODRIVE actuator has a manual override for the valve. The label located over the silver colored primary label states, “Please read manual before using manu­al override”. Using the Allen wrench supplied with the loose valve, place it in the hexagonal opening under the label. See Fig. 22.
When threading any pipe into the ports of the three­way valve, a backing wrench MUST be employed. You must capture the valve body with a secondary wrench to avoid damaging the internal seals. Valve bodies leaking from improper installation are non-war­rantable.
High Pressure Tab
Located between the valve body and the actuator mounting bracket, is a yellow tab labeled “High Pressure” see Fig. 21. This is for maintenance of the valve only.
If the valve stem begins leaking beneath the yellow tab the internal packing material must be replaced. The “High Pressure” tab is held on with two screws located under the mounting bracket.
To replace the packing material, all water pressure must be removed from the valve assembly and the assembly must be isolated from the system water. Then remove the actuator and bracket, then remove the two screws holding the “High Pressure” tab in place.
At this point the packing material can be removed and replaced just like any other valve assembly. The pack­ing material is not available from Raypak.
By pressing the red release button on the tail of the actuator and simultaneously rotating the Allen wrench you can rotate the ball clockwise. Once you release or remove the Allen wrench the ball will return to its orig­inal position by way of the “spring return”. This is an easy way to determine if the ball is oriented properly inside of the valve.
Fig. 22: Actuator
13
Page 14
Step9
Step8
Step10
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Is there a Call For
H
eat at the heate
r
?
Are the 120/24VAC
transformer and 120VAC-
12VDC inverter in the cold
start controller powered?
Replace 120VAC-12VDC
inverter or correct wiring.
D
oes the cold start 12VDC inverter
output 12VDC to the reset switch
and to common pin FS of the cold
start circuit board?
Does the cold start 120/24VAC transformer output 24VAC to pin 2
of TB2 and the valve actuator?
Replace transformer or
correct the wiring
Replace circuit board
Are the terminals 1-4 of TB3
connected to N.O. contacts of
DPDT relay?
Does cold start DPDT
relay coil receive 24VAC
from MC on circuit board?
Are terminals 1-4 of TB3
correctly connected back
to the heater?
Call our Technical Service Department
1-805-278-5300
NO
Verify 120VAC at separate c
ircuit breaker and correct.
YES
D
oes TB1 of cold start
controller have 120
V
AC?
Heater is in standby mode
Correct wiring to
match wiring diagram
YES
N
O
N
O
YES
Y
ES
N
O
N
O
NO
YES
YES
NO
The unit is okay
YES
NO
YES
Correct wiring
Is the actuator modulating after
2-1/2 minutes?
NO
Correct wiring
YES
Is the heater tripping the high
limit?
YES
NO
Verify actuator is set to reverse acting
and three-way valve is not installed
backwards.
2” & 2-1/2” valve must
rotate CW on decreasing 0-
10VDC signal. 4” valve will
rotate CCW.
YES
Correct settings or valve
orientation
NO
Is 24VAC present at CFH
terminal on cold start circuit
board?
Check and verify 24VAC between pin 4 and 5
of TB3 in cold start controller and correct.
Is 0-10VDC present at
connection FR of cold start
circuit board?
NO
Replace cold start circuit board
YES
NO
YES
Does cold start circuit board lock-out on
“Sensor out of Range”?
NO
YES
Is sensor resistance correct?
YES
NO
Replace sensor
Is system water
temperature below 32ºF?
NO
YES
Does the reset switch send
12VDC to terminal FS on the
cold start circuit board?
NO
YES
Cold Water Start Troubleshooting Guide
14
Page 15
NOTES:
1.LOCATE UNIONS TO FA CILITATE SERVICING OF PLUMBING SIDE.
2.PLUMB SWING CHECK VALVE IN GRAVITY-CLOSED POSITION.
3.PIPE ALL RELIEF VALVES TO DRAIN, OR AS LOCAL CODES REQUIRE.
4.BUFFER TANK REQUIRED WHEN WATER VOLUME IN BOILER LOOP
ISNOT ADEQUAT E TO PROVIDE STA BLE TEMPERATU RE CONTROL.
CONSULT FA CTORY FOR TA NK SIZING.
5.SYSTEM FLOW MUST EXCEED HEATER FLOW AT ALL TIMES.
Typical Cold Water Start Piping
15
Page 16
BRACKET RESTS AGAINST VALVE MOUNTING CHASIS
* VALVE NOT DEPICTED
Panel Control and Wrapper Control Cover Assembly
with Support Valve Cover; Full Assembly
Wiring Diagrams—Cold Water Start
16
Page 17
HEATER INTERFACE WIRING FOR CWS OR CWR
CWS/CWR C
ONTROL OR MULTIPLE BOILER INTERFACE
C
WS/CWR
C
ONTROL OR
M
ULTIPLE BOILER
INTERFACE
CWS/CWR CONTROL OR MULTIPLE BOILER INTERFACE
17
Page 18
COLD WATER START—
Installing the Three-way Valve
MULTIPLE HEATER
(Maximum 4 heaters)
Materials Included
1 Cold Start Control Box 1 Multi-Boiler Interlock Box 1 Water Sensor & Well 1 Three-way Diverting Valve assembly with Actuator
NOTE: Flanges, bolts and gaskets for flanged valves supplied by others.
Installation
Mounting the Control Boxes
Cold Start Control and Multi-Boiler Interlock should be mounted in such a manner as to allow for easy access for wiring of the boiler interlock connections.
Installing the Temperature Sensor
Temperature sensor to be installed in a drywell with thermal paste at the location indicated in the diagram on page 21 to ensure proper operation of the control system. Installer must ensure the drywell extends at least 2 inches into the water flow path. Sensor wiring must be run in separate conduit from line voltage and should be a minimum of 18 AWG shielded cable. Refer to diagram on page 22 for wiring information.
Install three-way diverting valve into common boiler piping manifold as shown in the diagram on page 18.
oiler common outlets to be connected at port AB.
B Discharge to system from port A with bypass port being port B. Common pipe sizing may be larger than three-way valve port connections requiring the use of increasers for installation (see Table B for valve siz­ing). It is recommended that three-way valve be installed as near the main system piping as is feasible. Route control wiring in separate conduit to the Cold Water Start control box and wire as shown in the dia­gram on page 19.
Connecting Power to the Controller
Installer to provide a dedicated 120V circuit with local disconnect to the Cold Water Start Control. Refer to wiring Fig. 9 on page 8 for detailed instruction.
Connecting Cold Water Start to Multi-Heater Interlock Box
Installer to provide four 18AWG stranded wires between pins 7-10 on the Cold Start Control and 7-10 on the Multi-Boiler Interlock as shown in the diagram on page 22. Do not use solid core wire when wiring any portion of the Cold Start Multi-Boiler system.
Connecting Heater to Cold Water Start Multi-Heater Interlock
Installer to provide five 18AWG stranded wires between each boiler and Multi-Boiler Interlock box. Wiring to be run in separate conduit from line voltage to ensure proper operation. Refer to the diagram on page 22 for connection points depending on Raypak product being used.
Total Load
(MBTU)
600-1000 2” NPT 2 57 70 3.5 ft 22 14.4 012228
1001-1800 2.5” NPT 2.5 74 100 4.2 ft 30.2 16.8 012229
1801-2600 2.5” NPT 3 100 150 5.2 ft 29.1 20.1 012230
2601-4000 4” FLG* 4 152 220 4.8 ft 30.5 22.9 012231
4001-6000 4” FLG* 4 254 330 3.9 ft 30.5 20.3 012232
6001-8000 4” FLG* 6 327 440 4.2 ft 30.5 22.5 012233
Standard boiler pump options offered by Raypak may NOT be appropriate for these applications.
*CAUTION: Approved for closed loop systems only.
Valve
Size
Minimum Pipe Size
Cv
Table B: Valve Sizing Chart
Flow Rate
(gpm)
18
Valve
Pressure
Drop
∆T @
Max Size
∆T @
Min. Size
Order
No.
Page 19
Actuator to Valve Orientation
LOCKING BOLT
WING NUT
PORT A B
Install the actuator so that the tail is pointing horizon­tally as shown in Fig. 26 or is pointing down. DO NOT
ount it so that the tail is pointing up as shown in Fig.
m
20. Doing so will allow water and debris to collect in the cup where the wiring exits the actuator, potentially
causing damage.
Three-Way Valve Ball Orientation
The ball orientation must be verified prior to mounting the flanged valve into the piping system. With the flanged four-inch valve it is a fairly simple procedure. Do not use the groove on the end of the drive linkage to verify.
First, remove the actuator by removing the wing-nut underneath the mount bracket near the tail. Second, loosen the locking bolt on top of the actuator that clamps to the drive linkage. See Fig. 23.
Reinstall the actuator and bracket assembly in reverse order, and ensure that the ball assembly is properly oriented. Mount the flanged valve into your piping sys-
em in accordance with this manual.
t
Valve Installation
To properly install this valve port “AB” must be con­nected to the combined outlet of the heater(s); and port “B” must be attached to the bypass between the combined inlet and the combined outlet, as shown on page 21. The valve body has the port designators cast into the drive linkage housing. See Fig. 25.
Fig. 23: Removing the Actuator (Elodrive)
Once this has been done, remove the actuator by lift­ing straight off the drive linkage shaft.
Now the ball position must be verified. Using pliers, grasp the base of the drive linkage. While looking into port AB, rotate the drive linkage counterclockwise about 45 degrees. See Fig. 24. You should see two partial openings similar to Fig. 18.
If you do not see the two partial openings after 45 degrees of rotation, continue rotating until you do. Once you see the two partial openings, STOP. Now rotate the shaft in the reverse direction (clockwise) until you can see straight through to valve from port AB to port A.
Fig. 24: Rotating the Drive Linkage
Fig. 25: Valve Orientation
19
Page 20
NOTE: SIDE A MUST FACE AWAY FROM VALVE BODY
DETENT MUST BE SET TO POSITION 2
NOTE: SIDE A MUST FACE AWAY FROM 4” VALVE BODY
4-Inch Valve Orientation
The valve must be installed so that the combined boil­er outlets enter through Port "AB" (See Fig. 26). Port
B" is the bypass port and port "A" is the return to the
" system (port designations are cast into the stem of the
alve body). The valve body should be installed so that
v the actuator input shaft is in the vertical or horizontal position. The Actuator stem should never be hanging downward.
The actuator, as shipped from the factory, is in the hor­izontal position when the valve is installed as shown in Fig. 26. The actuator position can be changed to suit job site conditions.
Under no circumstances should the actuator be posi­tioned such that the electrical connection is pointing upwards (see Fig. 20) as this can allow for moisture or debris to enter the actuator assembly and potentially damage the actuator.
Before installing into the piping system, verify the valve is positioned properly by referring to Fig. 26 and the diagram on page 21.
Fig. 27: Elodrive actuator used on 4” valves
(Actuator shown in full system flow position.)
Connecting the Actuator
The 4-inch valve is shipped loose, and must be field wired. Connect the actuator leads to the Cold Water Start control panel, as indicated in the wiring diagram on Page 16.
The actuator for the 4” valves rotates opposite to the direction of the smaller actuators. On an Elodrive actuator, Side A must be facing away from the valve.
Fig. 26: Valve Orientation (Elodrive Actuator)
Fig. 28: Rotational Setting for Elodrive Actuator
Used on 4” Valves
20
Page 21
1.PLUMB SWING CHECK VALVE IN GRAVI TY-CLOSED POSITION.
2.PIPE ALL RELIEF VALVES TO DRAIN, OR AS LOCAL CODES REQUIRE.
3.LOCATE UNIONS TO FACILITATE SERVICING OF PLUMBING SIDE.
4.BUFFER TANKS MAY BE REQUIRED TO PROVIDE STABLE TEMPERAT URE
CONTROL ON SYSTEMS WITH VARIABLE FLOW OR LOW WATE R VOLUME.
CONSULT FACTORY FOR SELECTION CRITERIA.
5.MAXIMUM 4 TIMES THE PIPE DIAMETER OR 12”, WHICHEVER IS LESS.
6.SYSTEM FLOW MUST EXCEED HEATER FLOW AT ALL TIMES.
Typical Cold Water Start Multiple Heater Piping
21
Page 22
CWS CONTROL
BOX ASSY
(SEE PAGE 16)
FOR HEATER INTERFACE WIRING
(SEE PAGE 17)
Wiring Diagram Multiple Heater
22
Page 23
COLD WATER RUN
CWR vs. CWS
NOTE: After testing at the factory it may be prudent
to ship the piping assembly disassembled and attached to the heater pallet. This is done to avoid
hipping damage and it must be reassembled on the
s jobsite. Use Fig. 29 to assist you in reassembling the piping.
Cold water start is for transient cold water opera­tion.
Cold water run is for continuous operation below 105°F system return temperature.
Cold water start maintains design flow rate at sys­tem design temperature but reduces boiler flow rate during heavy bypass operation.
Cold water run maintains constant design flow rate in the boiler.
Installation
Before beginning the installation, it's important to first inspect the system and determine what materials you will need. Some parts are included with the controller while others you will need to provide.
Installation Codes
Installations must be in accordance with local, state, provincial, and national codes, laws, regulations and ordinances. In the absence of local codes, installa­tions must be in accordance with the latest editions of the:
National Fuel Gas Code, ANSI Z223.1/NFPA 54
National Electrical Code, ANSI/NFPA 70
For Canada only: CAN/CSA B149 Installation Code and CSA C22.1 C.E.C. Part 1 and Part 2
Fig. 29: Cold Water Run Assembly
Purpose
The Cold Water Run system utilizes a variable-speed pump to inject the proper amount of water from the main system loop into the heater to maintain the opti­mum inlet temperature. This approach allows the full capacity of the heater to be utilized to meet the system load, while at the same time continuously maintaining the optimum inlet water temperature to prevent con­densation.
Typical Cold Water Run Applications
Swimming pools.
Any system with steady-state (or “consistent”) return water temperature below 105°F.
Mounting the Control Box
NOTE: The heater should not be located in an area
where possible water leakage will result in damage to the area adjacent to the heater or to the structure. When such locations cannot be avoided, it is rec­ommended that a suitable drain pan, with adequate drainage, be installed under the heater. The pan must not restrict combustion air flow.
The control box should be mounted on the side of the heater to which the system piping and pump assem­blies are to be attached as shown in Figs. 4–8 on pages 7 & 8. The controller should be mounted so as to provide maximum support by using the mounting holes provided on the base of the controller to the side center brace on the heater. You will need to drill mounting holes for #10 hardware and 3/4” conduit access holes through the heater side panel for the routing of wiring and the sensor.
CAUTION: Remote mounted controller must be installed within 25 feet of wire length to the heater.
23
Page 24
Injector & Heater Pump Comparison
Heater
Model
302 32 16 2 112 13 40 1911-1⁄4 hp
402 34 20 2 112 17 40 1911-1⁄4 hp
502 42 20 2.3 1630/4.0 22 40 1911-1⁄4 hp
652 55 20 4.1 1630/4.0 28 40 1911-1⁄4 hp
752 63 20 5.7 1630/4.2 32 40 1911-1⁄4 hp
902 76 20 8.4 1630/4.2 38 40 1911-1⁄4 hp
992 83 20 5.2 1630/4.7 42 40 1911-1⁄4 hp
1262 107 20 9.6 1630/4.7 54 40 1911-1⁄3hp
1532 120 22 12.4 1632/5.6 62 42 1911-1⁄3hp
1802 120 25 13 1632/5.6 68 45 1911-1⁄3hp
2002 132 26 19 1634/6.1 74 46 1935-3⁄4hp
Flow
Heater Pump Injector Pump
Temp.
Rise
Press.
Drop
Pump
Model/Imp.
Flow
Temp.
Rise
Pump
Model-hp
2072 132 27 19 1634/6.1 75 47 1935-3⁄4hp
2342 132 30 21.4 1634/6.1 80 50 1935-3⁄4hp
Table C: Injector and Heater Pump Specifications—Hi Delta
Heater
Model
503 58 15 2.4 1611 29 30 1911-1⁄4 hp
753 63 21 5.6 1611 44 30 1911-1⁄4 hp
1003 87 20 8.2 1630 58 30 1911-1⁄3 hp
1253 86 25 12.2 1630 73 30 1911-1⁄3 hp
1503 100 26 18.5 1632 87 30 1911-1⁄3 hp
1753 109 28 26 1634 102 30 1911-1⁄3 hp
2003 116 30 36.2 1636 116 30 1935-3⁄4 hp
Flow
Heater Pump Injector Pump
Temp.
Rise
Table D: Injector and Heater Pump Specifications—MVB
Press.
Drop
Pump
Model
Flow
Temp.
Rise
Pump
Model-hp
24
Page 25
CIRCUIT
BREAKER
WHITE
GROUND
BLACK
GREEN
AB C
Heater
Heater Pump Injector Pump
Model
Flow
Temp.
ise
R
Press.
rop
D
Pump
odel/Imp.
M
Flow
Temp.
ise
R
Pump odel-hp
M
926/962 79 20 8.5 1630/4.7 50 32 1911-1⁄4 hp
1083/1125 90 21 12.0 1630/4.7 50 37 1911-1⁄4 hp
1178/1223 90 22 12.5 1630/4.7 60 33 1911-1⁄3 hp
1287/1336 90 25 13.2 1630/4.7 60 37 1911-1⁄3 hp
1414/1468 90 27 14.0 1632/5.65 60 40 1911-1⁄3 hp
1571/1631 90 30 14.5 1632/5.65 60 45 1911-1⁄3 hp
1758/1826 90 34 15.4 1632/5.65 60 50 1911-1⁄3 hp
2100 172 20 11.0 1641/6.9 130 26 1935-3⁄4hp
2500 200 21 15.8 1641/6.9 130 32 1935-3⁄4hp
3001 200 25 16.7 1641/6.9 130 38 1935-3⁄4hp
3500 200 29 17.5 1641/6.9 130 44 1935-3⁄4hp
4001 200 33 18.7 1641/6.9 130 50 1935-3⁄4hp
Table E: Injector and Heater Pump Specifications—Raytherm
Check the Power Source
WARNING: Using a multi-meter, check the follow-
ing voltages at the circuit breaker panel prior to con­necting any equipment. Make sure proper polarity is followed and house ground is proven.
HOT (L1)
HOT (L2)
Fig. 31: Multi-meter
Injector Pump Wiring
The 3-phase cold water run pump is shipped loose and must be field wired.
Fig. 30: Wiring Connections
Check the power source:
AC = 104 VAC Minimum, 126 VAC MAX AB = 208 VAC Minimum, 252 VAC MAX BC = 104 VAC Minimum, 126 VAC MAX
Before Starting
1. Turn off power to the unit at the circuit breaker.
2. Turn off gas supply.
3. Shut off the water supply to the heater and, if nec­essary, drain water from the system.
25
Page 26
4. Locate the pump junction box and wiring decal shown in Fig. 32.
230 VAC 3 ø Line Low Voltage Pump Wiring
Black Orange (3) and Gray (9)
Red Red (8) and White (2)
White Pink (7) and Blue (1)
ellow (4) and Black (5) and
———————
Y Violet (6)
Green Ground Lug
Table F: Cold Water Run Control Panel and Injector
Pump Wiring
Cover
Fig. 32: Pump Wiring Decal and Junction Box
5. Remove the pump junction box cover shown in Fig. 32 and locate the 9 wires inside.
6. Wire in accordance with the low voltage (230 VAC) decal located next to the pump junction box (do not connect high voltage 460 volt power to the control box).
7. In the absence of the pump mounted decal, use Table F to complete the wiring between the cold water run control box and the 3-phase injector pump. Use wire nuts (field supplied) to complete these connections and ensure that all connections are tight.
Fig. 33: Cold Water Run Control Panel and Injector
Pump Wiring
8. Re-install the injector pump junction box cover.
9. Turn on the water and gas supply.
10. Turn the electrical supply on to the heater and to the cold water run system.
11. Turn heater on to receive a “call-for-heat” and ver­ify the injector pump is rotating in the proper direction (clockwise). The pump volute has an arrow cast into the housing indicating the proper rotational direction. See Fig. 34.
Directional Arrow
26
Fig. 34: Directional Arrow
Page 27
12. If the pump is rotating in the proper direction, secure the heater from installation.
13. If the pump is rotating incorrectly, turn off power and swap ONLY two of the line voltage leads into the pump (for example, swap the red and black leads). Confirm that the pump now rotates in the
roper direction before proceeding.
14. Secure from installation.
Injection Pump Cover Installation (Required for Outdoor Installation Only)
Before Starting
1. Turn off power to the unit at the circuit breaker.
2. Turn off gas supply.
3. Shut off the water supply to the heater and, if nec-
essary, drain water from the system.
4. Allow heater to cool down before attempting work.
In order to install the pump cover, you will need to rotate the pump body so that the electrical box is point­ing downward, as outlined in the following steps:
2. Remove the pump body then rotate it so that the electrical box is pointing downward, ensuring not to damage the seal. See Figs. 36, 37 and 38.
1. Loosen and remove the eight (8) 9/16” bolts hold­ing the pump body in place. See Fig. 35.
Fig. 36: Remove the pump body
Fig. 35: Remove the eight bolts holding the pump body
in place
Fig. 37: Be sure not to damage the seal when removing
or replacing the pump body
27
Page 28
Fig. 38: Reposition the pump body so that the electrical
box points downward
3. Insert and tighten all eight (8) bolts, securing the pump body in place.
4. You will now be able to install the pump cover. See Figs. 39 and 40.
Fig. 40: Pump cover - angle view
Fig. 39: Place the cover on the pump
28
Page 29
Typical Cold Water Run Piping - Heating Applications
ALTE RNATE SENSOR POSITION
12” MAX, OR MIN FEASIBLE
NOTES:
1.LOCATE UNIONS TO FACILITATE SERVICING OF PLUMBING SIDE.
2.PLUMB SWING CHECK VA LVE IN GRAVITY-CLOSED POSITION.
3.PIPE ALL RELIEF VALVES TO DRAIN, OR AS LOCAL CODES REQUIRE.
4.SYSTEM FLOW MUST EXCEED HEATER FLOW AT ALL TIMES.
SEE NOTE 4
NOTES:
1.LOCATE UNIONS TO FACILITATE SERVICING OF PLUMBING SIDE.
2.PLUMB SWING CHECK VALVE IN GRAVITY-CLOSED POSITION.
3.PIPE ALL RELIEF VALVES TO DRAIN, OR AS LOCAL CODES REQUIRE.
4.USE REDUCING TEES WHERE INDICATED.
5.SYSTEM FLOW MUST EXCEED HEATER FLOW AT ALL TIMES.
Typical Cold Water Run Piping - Pool Applications
29
Page 30
Operation
Run full system flow for two minutes.
Initiate PID pump control to achieve target inlet emperature by slowing injector pump.
t
Boiler ∆T will not increase during bypass operation.
If target temperature is not achieved after 7 min-
utes from “call for heat”, the system will shut down.
Fig. 41: Control Board
7. After the two second delay on the cold run circuit board, pin MC outputs a 24 VAC signal to terminal AL0 of the Hitachi inverter.
8. The AL0 relay closes and outputs a 24 VAC signal to the coil of the DPST relay located in the cold run control panel.
9. The DPST relay coil energizes and closes the NO contacts.
10. Once the NO contacts of the DPST close, the heater 24 VAC is sent back to the heater to com­plete the circuit (pin 3 of terminal block 3) and the interlock circuit (pin 1 & 2 of terminal block 3) allowing the heater to fire.
11. Pin SC of the cold run circuit board sends 10VDC to Pin 1 (Forward) on Hitachi Inverter.
12. PCS terminal on Inverter outputs 12VDC signal to the common terminal of the reset switch located on the bottom of the cold run control panel.
13. The 12VDC signal crosses over the reset switch and goes to Pin FS and to pin S1 on cold run cir­cuit board.
14. Pin FR on the TVC board outputs 10VDC to pin O of the Inverter to drive injector pump at full speed for two-minutes waiting for the heater to reach full fire.
15. After the two-minute delay the 10VDC output sig­nal from pin FR reduces to approximately 8VDC at the inverter thus slowing the pump to approxi­mately 50 Hz.
16. The output signal continues to vary depending on the heater inlet temperature.
Cold Run Sequence of Operation
1. Supply separate 220VAC, 1 phase, 60 Hz power for the Hitachi Inverter (blue-colored inverter), or 120VAC or 220VAC, 1 phase, 60 Hz power for the AC Tech Inverter (white-colored inverter).
2. Call for heat occurs at heater.
3. The heater outputs 24VAC to terminal 4 of termi­nal block 3 located in Cold Run controller.
4. Terminal 4 of TB 3 sends 24VAC to the coil of the SPST relay located in the cold run control panel.
5. The SPST relay coil is energized and closes the contacts allowing 24VAC from the Cold Run con­trol transformer to be sent to the CFH terminal of the Cold Run circuit board. a) A two second delay occurs from the CFH sig-
nal waiting to send power from terminal MC of the cold run circuit board.
6. 24 VAC is sent from terminal 2 of terminal block 3 to the NO contacts of the DPST relay located in the cold run control panel.
The heater will lockout and shut down if the set point on the inlet temperature is not achieved within 7 min­utes from a call for heat.
The DIP switches on the Hitachi Inverter must be set as indicated on Fig. 42 below.
Fig. 42: DIP Switch Settings (Hitachi)
30
Page 31
Step9
Step8
Step10
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Is there a Call For
Heat at the heate
r
?
Is the inverter in the
cold run controller powered?
Replace inverter or
correct wiring
Does the cold run inverter output 12VDC from PCS to the
reset switch
,
Pin S1 andpin FS of the cold run circuit board?
Replace circuit board
Are the terminals 1-2 of TB3
connected to N.O. contacts of
DPDT relay?
Does cold run terminal AL0
relay coil receive 24VAC
from MC on circuit board?
Are terminals 1-4 of TB3 correctly
connected back to the heater?
Call our Technical Service Department
1-805-278-5300
NO
Verify 120VAC* or 230VAC* from separate circuit breaker
YES
Does TB1 of cold run
controller have 120VAC*
or 230VAC*?
Heater is in standby mode
C
orrect Wiring
Y
ES
NO
NO
YES
Y
ES
N
O
NO
NO
YES
YES
NO
The unit is okay
YES
NO
YES
Correct wiring
Is the injector pump
modulating after 2-1/2
minutes?
NO
Correct wiring
YES
Is the heater tripping the high
limit?
YES
NO
Verify pump is rotating in proper
direction
Pump must decrease
RPM’s on decreasing 0-
10VDC signal
YES
Correct 3 phase pump wiring
NO
Is 24VAC present at CFH
connection on cold run circuit
board?
Check and verify 24VAC between pin 4 and 5
of TB3 in cold run controller and correct.
Is 0-10VDC present at
connection FR of cold run circuit
board and pin 0 of the inverter?
NO
Replace cold run circuit board
or correct wiring.
YES
Does cold run circuit board lock-out on
“Sensor out of Range”?
NO
YES
Is sensor resistance correct?
YES
NO
Replace sensor
Is the system
water temperature
º
NO
YES
*NOTE: See wiring diagrams
f
or proper supply voltage based
o
n inverter used on heater.
Cold Water Run Troubleshooting Guide
31
Page 32
Wiring Diagram—Cold Water Run (Hitachi Inverter)
17
32
Page 33
Wiring Diagram—Cold Water Run (AC Tech Inverter)
(SEE PAGE 17)
33
Page 34
REPLACEMENT PARTS
To order replacement parts, consult the Raypak Illustrated Parts Lists 9300.82 for Cold Water Start and 9300.83 for Cold Water Run.
NOTE: To receive the correct part, it is important that you state the model number and serial number when ordering.
Any part returned for replacement under standard company warranties must be properly tagged with RAYPAK return parts tag, completely filled in with the heater serial number, model number, etc., and shipped to the Company freight prepaid. If determined defective by the Company and within warranty, the part will be returned in kind or equal substitution, freight collect. Credit will not be issued.
RAYPAK, INC.
2151 Eastman Avenue
Oxnard, CA 93030
34
Page 35
35
Page 36
www.raypak.com
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468
Litho in U.S.A.
36
Loading...