WARNING: If the information in these instructions are not followed exactly, a fire
or explosion may result causing property damage, personal injury or death.
— Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone in your building.
•Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
•If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
This manual should be maintained in legible condition and kept adjacent to the
heater or kept in a safe place for future reference.
WARNING: IF YOU DO NOT FOLLOW THESE
INSTRUCTIONS EXACTLY, A FIRE OR
EXPLOSION MAY RESULT, CAUSING
PROPERTY DAMAGE, PERSONAL INJURY OR
LOSS OF LIFE.
SECTION 1 / START-UP PROCEDURES
BEFORE START-UP
BURNERS
Clean main burners and air louvers of dust, lint and
debris. Keep heater area clear and free from combustibles, flammable liquids and chemicals. Do not
obstruct the flow of combustion and ventilating air.
WATER
Water must be flowing through the heater during
operation. Insure that system is filled with water and
have pump operating.
Fig. # 8111.0
3
Page 4
CAUTION: Propane gas is heavier than air and will settle on the ground. Since propane can accumulate
in confined areas, extra care should be exercised when lighting propane heaters.
LIGHTING INSTRUCTIONS AND SHUT-OFF PROCEDURES
MANUALLY LIGHTED PILOTS
MILLIVOLT SYSTEM
A. This appliance has a pilot that must be lighted
by hand. When lighting the pilot, follow these
instructions exactly.
B. BEFORE LIGHTING smell all around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than air
and will settle on the floor.
*If you cannot reach your gas supplier, call the
fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not
push in or turn by hand, do not try to repair it.
Call qualified service technician. Force or
attempted repair may result in a fire or explosion.
WHAT TO DO IF YOU SMELL GAS:
*Do not try to light any appliance.
*Do not touch any electric switch; do not use any
phone in your building.
*Immediately call your gas supplier from a
neighbor's phone. Follow the gas suppliers' instructions.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat on the lowest setting.
3. Turn On/Off switch to the "Off" position.
4. Remove heater door panel.
5. Push in gas control knob slightly and turn
clockwise to "Off".
NOTE: Knob cannot be turned from "Pilot" to "Off"
unless knob is pushed in slightly. Do not
force.
6. Wait 5 minutes to clear out any gas. If you
then smell gas, STOP! Follow "B" in the
safety information above. If you don't smell
gas, go to the next step .
7. Locate pilot mounted on the right side panel
of the burner drawer. For burner drawer
location, see location of control section,
page 22.
GAS CONTROL KNOBS SHOWN IN "OFF"
POSITION.
Honeywell Gas Valve
Millivolt
Fig. #8081.0 Fig. #8079.0
Robertshaw Gas Valve
Millivolt
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to the lowest setting.
2. Turn On/Off switch to the "Off" position.
3. Remove heater door panel.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to replace any part of the control system and any gas
control which has been underwater.
Fig. #8083.0
Honeywell Pilot
8. Turn knob on gas control counter-clockwise
to "Pilot".
9. Push in control knob all the way and hold it
in. Immediately place flame to end of pilot
tube to light pilot. Continue to hold control
knob in for about 1 minute after the pilot is
lighted, release knob and it will pop back up.
Pilot should remain lighted. If it goes out,
repeat steps 5 through 9.
*If knob does not pop up when released,
stop and immediately call your service
technician or gas supplier.
*If the pilot does not stay lit after several
tries, turn the gas control knob to "Off" and
call your service technician or gas supplier.
10. Stand to the side of the heater and turn the
gas control knob counter-clockwise
to "On".
11. Replace heater door panel.
12. Turn On/Off switch to the "On" position.
13. Set thermostat to the desired setting.
4. Push the gas control knob slightly and turn
clockwise to "Off". Do not force.
5. Replace heater door panel.
4
Page 5
CAUTION: Propane gas is heavier than air and will settle on the ground. Since propane can accumulate
in confined areas, extra care should be exercised when lighting propane heaters.
OPERATING INSTRUCTIONS AND SHUT-OFF PROCEDURES
AUTOMATICALLY LIGHTED PILOTS
ELECTRONIC IGNITION SYSTEMS
A. This appliance is equipped with an ignition
device which automatically lights the pilot. Do
not try to light the pilot by hand.
B. BEFORE OPERATING, smell all around the appli-
ance area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will
settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
*Do not try to light any appliance.
*Do not touch any electric switch; do not use
any phone in your building.
*Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition
device which automatically lights the pilot.
Do not try to light the pilot by hand.
5. Remove heater door panel.
6. For Honeywell valve: Push in gas control
knob slightly and turn clockwise to
"Off". Knob cannot be turned to "Off" unless it
is pushed in slightly. Do not force.
For Robertshaw valve: Push in and move
gas control lever counter-clockwise
to "OFF" position.
7. Wait 5 minutes to clear out any gas. If you
then smell gas, STOP! Follow "B" in the
safety information previously stated. If you
don't smell gas, go to the next step.
8. Turn gas control knob counter-clockwise
to "On" (Honeywell).
Move gas control lever clockwise
to "ON" position (Robertshaw).
9. Replace heater door panel.
*If you cannot reach your gas supplier, call the
fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, don't try to repair it;
call a qualified service technician. Force or
attempted repair may result in fire or explosion.
D. Do not use this appliance if any part has been
underwater. Immediately call a qualified service
technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been underwater.
GAS CONTROL KNOBS
SHOWN IN "ON" POSITION
Honeywell
Gas Valve
IID
Fig. # 8082.0
GAS CONTROL
LEVER SHOWN
IN "OFF" POSITION
GAS INLET
Robertshaw
Gas Valve
IID
10. Turn on all electrical power to appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance"
and call your service technician or gas
supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat at the lowest setting.
2. Turn off all the electric power to the appliance if service is to be performed.
3. Remove heater door panel.
4. For Honeywell valve: Push in gas control
knob slightly and turn clockwise to
"Off".
For Robertshaw valve: Push in and move
gas control lever counter-clockwise
to "OFF" postion.
5. Replace heater door panel.
5
Page 6
AFTER START-UP
Feel the inlet and outlet pipes. Outlet pipe should be
only slightly warmer than the inlet. It should not be hot.
WARNING: Should overheating occur or the gas
supply fail to shut off, turn off the manual gas
control valve to the appliance.
VISUAL INSPECTION
With the heater on, remove the door and make a
visual check of the pilot and burner. The flame should
be blue with a well-defined pattern.
MAIN BURNER FLAME
Pressure
Switch
Location
Fig. # 8110.1
SECTION 2 / CAUTION
Elevated water temperature can be hazardous, and the
U.S. Consumer Product Safety Commission recommends the following guidelines:
1. Spa or hot tub water temperatures should
never exceed 104°F (40°C). A temperature
of 100°F(38°C) is considered safe for a
healthy adult. Special caution is suggested
for young children.
Fig. # 8964
PILOT BURNER FLAME
A yellow or "floating" flame indicates restricted air
openings or incorrect orifice size. Should this occur,
shut the heater off and contact your installer or gas
supplier.
WATER PRESSURE SWITCH
A water pressure switch is provided in the heater to
shut off the burners in the event that water supply to the
heater is interrupted. It is very important to verify that
the switch electrically opens and shuts off the gas valve
when water flow to the heater is interrupted. Otherwise, rapid and severe damage will likely occur to the
heater. (The water pressure switch should be checked
and adjusted for proper operation by a qualified service
person at the time of installation and periodically
checked thereafter. Refer to pressure switch servicing
instruction in Section 4 of this manual).
WARNING: Operation of the heater without water
circulation will cause rapid and severe damage to the
heater.
2. Drinking of alcoholic beverages before or
during spa or hot tub use can cause drowsiness which could lead to unconsciousness
and subsequently result in drowning.
3. Pregnant Women Beware! Soaking in water
over 102° F (39°C) can cause fetal damage
during the first three months of pregnancy,
(resulting in the birth of a brain damaged or
deformed child). Pregnant women should
stick to the 100°F (38°C) maximum rule.
4. Before entering the spa or hot tub, users
should check the water temperature with an
accurate thermometer; spa or hot tub,
thermostats may err in regulating water
temperatures by as much as 4°F (2.2°C).
5. Persons with a medical history of heart
disease, circulatory problems, diabetes, or
blood pressure problems should obtain a
physician's advice before using pools or hot
tubs.
6. Persons taking medications which induce
drowsiness, such as tranquilizers, antihistamines, or anticoagulants, should not use
spas or hot tubs.
6
Page 7
SECTION 3 / MAINTENANCE AND CARE PROCEDURES
To be followed one month after start-up and then
semi-annually.
1. Inspect top of heater and draft hood for soot,
(a sticky black substance around finned
tubes and "V" baffles), and open flue gas
passageways.
CAUTION: Soot may be combustible. Wet sooted
surfaces completely prior to cleaning. Do not use steel
wire brush.
2. Clean main burners and pilot burner of dust
and lint.
3. Inspect and operate all controls, gas valve
and pressure relief valve.
4. Make a visual check of the burner and pilot
flame. Flame pattern on the main burner and
pilot is indicated in the previous illustration.
Yellow flame means restriction of the air
openings. Lifting or blowing flame indicates
high gas pressure. Low flame means low
gas pressure. Should this occur, shut the
heater off and contact your gas supplier or
qualified service agency.
5. On indoor heaters, clean room intake openings to assure adequate flow of combustion
and ventilation air.
4. Your pump strainer basket may be full. If so
remove debris.
5. Your filter may be dirty. If so, backwash or
clean filter. (To tell if your filter is dirty, the
gauge pressure will be higher than usual).
6. The pump may have lost it's prime. It may
be running dry, check the pressure gauge
on the filter. If there is no pressure; then
you are not moving water (or your gauge is
broken). Try to get the pump to run at it's
normal flow rate.
POOL &SPA WATER CHEMISTRY
Chemical imbalance can cause severe damage to
your heater and associated equipment. Maintain your
water pH between 7.4 and 7.8 and total alkalinity
between 100 and 150 p.p.m. If the mineral content and
dissolved solids in the water become too high, scale
forms inside the heat exchanger tubes, reducing
heater efficiency and also damaging the heater. If the
pH drops below 7.2, the heater will be severely damaged. This will result in corrosion of the heat exchanger. Heat exchanger damage resulting from
chemical imbalance is not covered by the warranty.
AUTOMATIC CHLORINATORS AND CHEMICAL
FEEDERS
CAUTION: Combustion air must not be contaminated
by corrosive chemical fumes which can damage the
heater and void the warranty.
6. Keep area around heater clear and free from
combustible materials, gasoline and other
flammable and corrosive vapors and liquids.
BASIC TIPS IF HEATER WILL NOT FIRE:
1. If you have no electrical power; it may be
your "circuit breakers" have tripped. Try
re-setting them.
2. If you have electrical power but the heater
will not fire
check the following:
3. The time clock must be moved to the "ON"
position.
All chemicals must be introduced and completely
diluted into the pool or spa water before being circulated through the heater. Do not place chlorine tablets
or bromine sticks in the skimmer. High chemical
concentrations will result when the pump is not running
(i.e. overnight).
Chlorinators must feed downstream of the heater
and have an anti-siphoning device to prevent chemical
back-up into the heater when the pump is shut off.
NOTE: High chemical concentrates from feeders and
chlorinators that are out of adjustment will cause very
rapid corrosion to the heat exchanger in the heaters.
Such damage is not covered under the warranty.
7
Page 8
COLD WEATHER OPERATION
MODERATE CLIMATE: Heater operation can con-
tinue during short term cold spells. When temperatures
are below freezing flow, (continuous pump operation)
must be maintained.
CAUTION: Do not use the heater to maintain water
temperatures just above freezing or for freeze protection. When heaters are used during freezing weather,
care must be taken to avoid freeze ups. Continuous
pump operation is a must. Additional protection may be
required. The heater is not warranted against freeze
ups.
COLD CLIMATE: Prolonged operation with water
temperatures below 50°F is not recommended. When
starting the heater with pool temperatures below 50°F,
operate the heater continuously until higher temperatures are reached. Operating the heater for prolonged
periods with pool water below 50° can seriously damage the heater, and is not covered by the warranty. For
cold climate areas please follow the winterizing procedures listed .
3. Disconnect compression fittings from the pressure
switch and return header that connects to the 1/4"
copper tube and allow the tube to drain.
WINTERIZING THE POOL & SPA HEATER
When heaters installed outdoors in freezing climate
areas are to be shut down for the winter, observe the
following step-by-step procedure:
1. Turn off gas valve, manual gas valve, and electri-
cal supply to the heater.
2. Open drain cock located on the inlet/outlet header,
(under water pipes). Tilt heater to completely
drain all the water from the heat exchanger.
PRESSURE SWITCH
COMPRESSION FITTING
RETURN HEADER
Fig. # 8955
8
Page 9
m
M
PART 2 - INSTALLATION / SERVICE INSTRUCTIONS
SECTION 1 / RECEIVING EQUIPMENT
On receipt of your equipment it is suggested that
you visually check for external damage to the carton. If
the carton is damaged, a note should be made on the Bill
of Lading when signing for equipment. Remove the
heater from the carton and if it is damaged, report the
damage to the carrier immediately.
On occasion, we ship some items loose. Be sure
that you receive the number of packages indicated on
the Bill of Lading.
When ordering parts, you must specify model and
serial number of the heater. When ordering under
warranty conditions, you must also specify date of
installation.
Raypak recommends that this manual be reviewed
thoroughly before installing your Raypak pool/spa
heater. If there are any questions that this manual does
not answer, please contact the factory or your local
Raypak Representative.
SECTION 2 / GENERAL
SPECIFICATIONS
These heaters are design certified and tested under
the requirements of ANSI Z21.56/CSA 4.7 American
National Standard/CSA Standard for gas fired pool
heaters.
The heater is interchangeable and can be used either
indoor or outdoors. The appropriate top designated for
that type of use is required. If desired, the top can be
changed at a later date to change from outdoor to indoor
or vice versa. Millivolt heaters contain a self-generating
electrical system operating between .25 and .75 volts.
AMBIENT TEMPERATURE RATING OF
HEATER COMPONENTS
SECTION 3 / INSTALLATION
INSTRUCTIONS
CALIFORNIA PROPOSITION 65 WARNING: This product
contains chemicals known to the State of California to
cause cancer, birth defects or other reproductive harm.
IMPORTANT NOTICE
These instructions are intended for the use of qualified personnel only, specifically trained and experienced
in the installation of this type of heating equipment and
related system components. Installation and service
personnel may be required by some states to be licensed. If your state is such, be sure your contractor
bears the appropriate license. Persons not qualified
shall not attempt to fix this equipment nor attempt
repairs according to these instructions.
WARNING: Improper installation, adjustment, alteration, service or maintenance may damage the equipment, create a hazard resulting in asphyxiation, explosion or fire, and will void the warranty.
CODE REQUIREMENTS
NOTE: The heater should not be located in an area
where possible water leakage will result in damage to
the area adjacent to the appliance or to the structure.
When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained,
be installed under the appliance. The pan must not
restrict combustion air flow.
Installation must be in accordance with local codes,
or, in the absence of local codes, with the latest edition
of the National Fuel Gas Code, ANSI Z223.1, and the
National Electrical Code, ANSI/NFPA 70.
BASE INSTALLATION
Millivolt Heater with Honeywell Gas Valve
+32°F to +175°F
Millivolt Heater with Robertshaw Gas Valve
0°F to +175°F
Electronic Ignition Heater *
-32°F to + 175°F
* Requires 120V or 240V Power Supply
Rated inputs suitable for up to 2000 feet elevation. For elevations above 2000 feet, reduce input 4% for
each 1000 feet above sea level, as high elevation reduces
Heater must be mounted on a level base, such as
cement slab, cement blocks or another non-combustible
surface. An optional non-combustible base is available
for all models. An alternate method for providing a base
for combustible floors is illustrated. Heaters may not be
installed on carpeting.
ALTERNATE METHOD FOR PROVIDING A NON-COMBUSTIBLE BASE
12"
12"
inimum
HEATER
Minimu
combustion performance.
Fig. # 8148.1
4"
Minimum
Sheet Metal
24 Gauge
Hollow concrete cinder block,
align holes and leave ends open.
9
Page 10
CLEARANCES
WARNING: The heater shall not be located in an area where water sprinklers, or other devices, may cause water
to spray through the cabinet louvers and into the heater. This could cause heavy internal rusting or damage some
electrical components, and this would void the warranty.
ALL HEATERS
For clearances from combustible surfaces, see the following chart.
CLEARANCES FROM COMBUSTIBLE CONSTRUCTION
INDOOR INSTALLATION OUTDOOR INSTALLATION
Top*(Drafthood) -42"Right Side - 6" Top *(Stackless Top or Outdoor Stack) - Unobstructed
Vent - 6"Left Side - 12" Back - 12"
Back-12"Front - Alcove Sides - 6"
*Clearance from Top of Vent Terminal.
For servicing, provide at least 24" in front of the heater for burner tray removal, and at least 18" on the back of the
heater to inspect and delime the heat exchanger.
OUTDOOR HEATERS
These heaters are design certified for outdoor installation, when equipped with the approved tops designated
for outdoor use.
HEATER WITH OUTDOOR
STACKLESS TOP
Fig# 8116
WARNING: Do not install within 3 feet of a Heat Pump or an outdoor condensing unit. Strong air intake from
this equipment can disturb the combustion process and cause damage or personal injury.
10
Page 11
Heaters must not be installed under an overhang of less than three (3) feet from the top of heater. Three (3)
sides must be open in the area under the overhang. Roof water drainage must be diverted away from the heaters
installed under overhangs with the use of gutters:
The point from where the flue products exit the heater must be a minimum of four (4) feet below, four (4) feet
horizontally from or one (1) foot above any door, window or gravity inlet to a building. The top surface of the heater
shall be at least three (3) feet above any forced air inlet, or intake ducts located within ten (10) feet horizontally.
4
foot
Minimum
4
foot
Minimum
4
foot
Minimum
3
foot
Minimum
1
10
foot
Minimum
foot
Minimum
Forced Air Inlet
HIGH WIND CONDITIONS (OUTDOOR UNITS ONLY)
In areas where high winds are frequent, it may be necessary to locate the heater a minimum of 3' from high
vertical walls, or install a wind break so the heater is not in direct wind current.
In areas of daily high winds, it may be necessary to replace the outdoor stackless top with a stack adapter in
combination with a wind resistant/weather proof outdoor stack. See illustration below.
The outdoor stack serves the same function as the
low profile stackless top and should be installed in
accordance with the same clearance requirements.
Fig. # 8245.1
11
Fig. # 9304
Page 12
INDOOR HEATERS
The design is also certified for indoor installation when equipped with the approved draft hood. Locate heater
as close as practical to a chimney or gas vent. Heater must always be vented to the outside. See Vent Piping Section
for venting details. Minimum allowable space is shown on the nameplate.
INDOOR
DRAFT HOOD
Fig. # 9305
COMBUSTION AIR (INDOOR UNITS ONLY)
AIR FOR COMBUSTION AND VENTILATION (Indoor Units Only)
The heater must have both combustion and ventilation air. Minimum requirements for net free air supply
openings, one 12 inches from ceiling for ventilation and one 12 inches from the floor for combustion air as outlined
in Z 223.1 - 1988 and any local codes that may have jurisdiction.
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater
and void the warranty.
a. All Air From Inside the Building:
Each opening shall have a minimum of 151 net free square inches.
b. All Air From Outdoors:
When air is supplied directly from outside of building, each opening shall have a minimum of 38 net free square
inches.
VENTING CONNECTIONS
Top Vent Opening
VENT TERMINAL (Outdoor) STACKLESS TOP
STEP 1 : Remove the front (4) screws which fasten
jacket top to heater.
STEP 2 : Line up top vent opening over heater vent
opening.
STEP 3 : Lower outdoor top onto unit lining up slots
in outdoor top with screw holes in jacket
top.
STEP 4 : Reinstall (6) screws to secure jacket top
and outdoor top to unit.
12
Fig. # 9306
Page 13
VENT TERMINAL (Outdoor) OUTDOOR STACK
STEP 1Line up (8) holes in jacket top with (8)
holes in adapter assembly.
STEP 2Lower entire outdoor stack assembly
on to jacket top.
STEP 3Secure with fasteners provided.
Fig. #9307
VENT TERMINAL (Indoor)
Locate and assemble as shown. Secure with
screws supplied in envelope inside carton.
DRAFT HOOD
MOUNTING
SCREWS (8)
and B149.2) As much as possible avoid long horizontal
runs of vent pipe and too many elbows. If installation
requires horizontal non-vertical runs, the vent pipe must
have a minimum of 1/4 inch per foot rise and should be
supported at not more than five foot intervals. Plumbers
tape, criss-crossed, will serve to space both horizontal
and vertical piping. Gas vents supported only by the
flashing and extending above the roof more than five feet
should be securely guyed or braced to withstand snow
and wind loads. We recommend use of insulated vent
pipe spacer through the roofs and walls.
For protection against rain or blockage by snow, the
vent pipe must terminate with a vent cap which complies with the local codes or, in the absence of such
codes, latest edition of the National Fuel Gas Code,
ANSI Z223.1. (Canada-CAN/CGA-B149.1 and B149.2)
The discharge opening must be a minimum of two
feet vertically from the roof surface and at least two feet
higher than any part of the building within ten feet. Vent
stack shall be at least five feet in vertical height above
the drafthood outlet. The vent cap location shall have
a minimum clearance of 4 feet horizontally from, and in
no case above or below, unless a four foot horizontal
distance is maintained, from electric meters, gas meters regulators and relief equipment.
The weight of the vent stack or chimney must not
rest on boiler draft hood. Support must be provided in
compliance with applicable codes. The boiler top and
draft hood must be readily removeable for maintenance
and inspection. Vent pipe should be adequately supported to maintain proper clearances from combustible
construction.
Type "B" double wall or equivalent vent pipe is
recommended. However single wall metal vent pipe
may be used as specified in the latest edition of the
National Flue Gas Code ANSI Z 223.1. (Canada-CAN/
CGA-B149.1 and B149.2)
Fig. # 9308
VENT PIPING
WARNING: Indoor boilers require a drafthood that
must be connected to a vent pipe and properly vented
to the outside. Failure to follow this procedure can
cause fire or fatal carbon monoxide poisoning.
Vent piping the same size or larger than the draft
hood outlet is recommended, however, when the total vent
height is at least ten (10) feet (draft hood relief opening
to vent terminal), the vent pipe size may be reduced as
specified in Chapter 10 of the latest edition National Fuel
Gas Code, ANSI Z 223.1.(Canada-CAN/CGA-B149.1
13
10' OR LESS
2' MIN
VENT PIPE
DRAFT HOOD
HEATER
VENT CAP
2' MIN
5' MIN
Fig. # 8119.0
Page 14
GAS SUPPLY CONNECTIONS
Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-off valve located outside the heater jacket. All gas piping should
be tested after installation in accordance with local
codes.
Fig. # 8090.1
CAUTION: The heater and its manual shut off valve
must be disconnected from the gas supply during any
pressure testing of that system at test pressures in
excess of 1/2 psig (3.45 KPA). Dissipate test pressure
in the gas supply line before reconnecting the heater
and its manual shut off valve to gas supply line.
FAILURE TO FOLLOW THIS PROCEDURE MAY
DAMAGE THE GAS VALVE. OVER PRESSURED
GAS VALVES ARE NOT COVERED BY WARRANTY.
The heater and its gas connections shall be leak tested
before placing the appliance in operation. Use soapy
water for leak test. Do NOT use open flame.
ROBERTSHAW VALVE
W. C. adjustment
HONEYWELL VALVE
Fig. # 8149.1
W. C. adjustment
NOTE: Do not use teflon tape on gas line pipe thread.
A flexible sealant is recommended.
A minimum of 7" W.C. and a maximum of 14" W.C.
upstream pressure under load, and no load conditions
must be provided for natural gas or a minimum of 12"
W.C. and a maximum of 14" for propane gas.
GAS PRESSURE REGULATOR
The gas pressure regulator is present and sealed
at 4"W.C. for natural gas, and 11"W.C. for propane
gas. Between the gas valve and the burners is a 1/8"
pipe plug. The pressure at this point , taken with a
manometer, should be about 3.7"W.C. natural gas
and 10.5"W.C. propane gas. If an adjustment is
needed, remove seal and turn adjustment screw
clockwise
to increase pressure or counter-clockwise
to decrease pressure.
Fig. # 8081.0
PIPE SIZING FOR GAS CONNECTIONS
MAXIMUM EQUIVALENT PIPE LENGTH
Natural Gas 1000BTU/FT3 .60 Specific Gravity
@ 0.5" WC Pressure Drop
Propane Gas 2500BTU/FT3 1.53 Specific Gravity
@ 0.5" WC Pressure Drop
1/2" 3/4" 1"
MODEL
N P N P N P
155B
15 35 60 145 200 500
14
Page 15
PLUMBING FOR WATER CONNECTIONS
LOCATION
The VERSA heater requires water flow and positive pressure to fire and operate properly. It must
therefore be installed downstream of the discharge
side of the filter pump. A typical installation is plumbed
as follows:
FLOW RATES
MIN GPM 20
MAX GPM 115*
*When flow rates exceed 115 GPM an external auxiliary bypass valve is required. See external auxiliary
bypass valve section for details.
1. The inlet side of the filter is plumbed directly
to the discharge side of the filter pump;
2. The outlet side of the filter is then plumbed
to the inlet of the heater; and
3. The outlet of the heater is plumbed to the
return line to the pool or spa. The pump,
filter and heater are thus plumbed in series.
Plumbing from the heater back to the pool must not
have any valves or restriction that could prevent flow
when the pump is operating. To do so will void the
warranty
Heater must be located so that any water leaks will
not damage the structure of adjacent area. High
temperature 2" plastic pipe (CPVC) may be threaded
directly into the header flanges. This is not the same as
the Schedule 80 PVC pipe which is also colored gray.
PVC may be used immediately after the CPVC adapters
2" CPVC Adapters
COMPANION FLANGE CONNECTIONS
DO NOT use petroleum base assembly fluids
(such as Petroleum Jelly or lubricating oil). If assembly
lubrication is required use a silicone base such as
Amoral etc.
The inlet/outlet single header flanges are designed
for four type of water connections. There are two sets
of flange gaskets supplied with your header; one set
installed, between flanges and in/out header, and the
other set shipped loose in the unit. Use the appropriate
gasket design, for all your heater connections.
GASKET DESIGN #1: (Factory installed) Accepts
1-1/2" copper tube or 1-1/4" galvanized pipe as a slip
connections.
GASKET DESIGN #2: (Loose In a bag) Accepts 2"
copper tube as a slip connection. The flange is
threaded for 2" screw in pipe connections. Also used
with the 2" CPVC adapters.
#1 #2
PVC Pipe
INLET OUTLET HEADER
Fig. # 8192.1
CAUTION: NEVER install PVC directly into header
flanges. Use the 2" CPVC adapter supplied loose with
the heater.
Fig. # 8095.1Fig. # 8097.1
INLET/OUTLET HEADER
DAN MAINES
HEADER FLANGE
15
FLANGE GASKET
S8093.1
Fig. # 8093.1
Page 16
UNITHERM GOVERNOR OPERATION
The patented Unitherm Governor is a thermostatic
mixing valve specifically designed to maintain constant
heater internal temperature between 105°-115°F despite continually changing flow rates from the filter and
changing pool temperatures. This narrow range is
needed to prevent damaging condensation on the burners which will occur if the heater runs for any length of
time below 100°F. It is also needed to inhibit scale
formation in the tubes by maintaining temperatures
well below accelerated scaling temperatures.
INTERNAL AUTOMATIC BY-PASS VALVE
In addition to the Unitherm Governor, a built-in
automatic by-pass valve is provided in the in/out
header. While the Unitherm Governor responds to the
changes in water temperature in the heater, the internal
by-pass valve automatically responds to changes in
water pressure in the piping system. Proper amount of
water flow is maintained through the heater under
varying pressures dictated by the conditions of the
pump and filter.
From Heater To Heater
To Pool From Pool
Auxiliary Bypass Valve (do not use gate valve)
Fig. # 8150.0
AUXILIARY BYPASS VALVE ADJUSTMENT
To set bypass: With clean filter, adjustment is made
by feeling the inlet and outlet pipes at the heater. Outlet
pipes should be slightly warmer than inlet and comfortable to the touch. If pipe is hot, close bypass; if cold,
open bypass.
PRESSURE RELIEF VALVE INSTALLATION
To conform to local building codes, it may be
necessary to install a pressure relief valve. A 3/4"
pressure relief valve having a capacity equal to BTU/HR
output of the heater to be installed is recommended for
this appliance.
A 3/4" NPT connection is provided in the inlet/outlet
header for installation of a pressure relief valve. The
valve shall be installed in a vertical position.
Fig, # 8078.0
EXTERNAL AUXILIARY BYPASS VALVE
(where required)
An auxiliary bypass valve should be used when flow
rates exceed 115 GPM (usually a high performance
pump size larger than 2 HP will exceed this flow rate).
This valve is required to complement the function of the
automatic bypass valve, particularly when starting the
heater in winter or early spring when the spa or pool
temperature is down below 50°F. It also serves to
eliminate needless pressure drop through the heater
and accompanying reduction in the flow rate to the spa
jets, etcetera.
PRESSURE RELIEF
VALVE
INLET/OUTLET HEADER
16
PRV DISCHARGE
CONNECTION
Fig. # 8095.0
Page 17
NOTE: To avoid water damage or scalding due to valve
operation, drain pipe must be connected to valve outlet
and run to a safe place of discharge. Drain pipe must
be the same size as the valve discharge connection
throughout its entire length and must pitch downward
from the valve. No shut-off valve shall be installed
between the relief valve and the drain line. Valve lever
should be tripped at least once a year to ensure that
waterways are clear.
ELECTRICAL WIRING
NOTE: IID PROPANE UNITS ONLY: Heater is equipped
with an electronic ignition device with a 100% safety
lockout feature. If the heater fails to start or lockout,
reset the ignition device by interrupting the power to the
heater for 60 seconds.
CAUTION: If service replacement of the electronic
ignition device is required, replace only with a 100%
safety lockout device with 90 second trial for pilot
ignition.
NOTE: If it is necessary to replace any of the original
wiring, it must be replaced with 105°C wire or its
equivalent, except all black wire must be replaced with
150°C wire or its equivalent.
CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper
and dangerous operation. Verify proper operation after
servicing.
DANGER - SHOCK HAZARD - Make sure electrical
power to the heater is disconnected to avoid potential
serious injury or damage to components.
MILLIVOLT SYSTEM
The Millivolt System Residential Heater is equip-
ped with a self-generating electrical system in which the
electric current is provided by means of a pilot generator.
No external electrical connections are required.
When installing a remote switch, do not exceed 10 feet
of wiring from the heater. Use 18 gage stranded wire.
ELECTRONIC INTERMITTENT IGNITION
DEVICE SYSTEM (IID)
HONEYWELL
INTERMITTENT
IGNITION
DEVICE
Fig. # 8929.1
NOTE: When the electrical hookup to the heater
requires both 24V and 115V or 240V, each input
voltage must be isolated in separate conduit.
The Electronic Intermittent Ignition Device automatically lights the pilot and main burners upon a call for
heat. The heater is supplied with a dual voltage transformer for 120V or 240V input power hookup. Heaters
are factory wired for 240V power supply.
17
Page 18
For 120 V input power to the unit, connect the black wire
to the “L1” or hot leg of the power supply. Connect the
white wire to the “L2” or neutral leg of the power supply.
Attach the wire nut to the red wire. There should be no
connection to the red wire for 120V operation.
Fig. #9240
For 240 V input power to the unit, connect the black wire
to the “L1” or hot leg of the power supply. Connect the red
wire to the “L2” or second hot leg of the power supply.
Attach the wire nut to the white wire. There should be no
connection to the white wire for 240V operation.
WIRING DIAGRAM KEY
Fig. # 9241
Heater must be electrically grounded and bonded in
accordance with local codes, or, in the absence of local
codes, with the latest edition of the National Electrical code,
ANSI/NFPA 70.
NOTE: Input power to the heater (120/240V) should be
supplied from the load (Pump) side of time clock or switch.
Connecting heater to continuous power source will allow
"Fail" indications (service and pressure switch) when pump
is not operating.
Fig. # 8096.0
18
Page 19
WIRING DIAGRAM MILLIVOLT UNITS
*
*If required by Local Code, install at this location.
19
Fig. #2353
Page 20
WIRING DIAGRAM 152148 Model 155 IID
BL
BL
BL
20
Page 21
SECTION 4 / SERVICING INSTRUCTIONS
GENERAL LOCATION OF CONTROLS
VIEW OF HEATER FROM FRONT
SOLID STATE
THERMOSTAT
CONTROL
IGNITION CONTROL
PRESSURE SWITCH
GAS VALVE
PILOT
THERMAL FUSE
CONTROL PANEL REMOVAL
VIEW OF HEATER FROM BACK
HIGH LIMITS
UNITHERM
GOVERNOR
DRAIN VALVE
Fig. # 8110.1
CONTROLS / ADJUSTMENTS / REPLACEMENTS
1. Remove lower door.
2. Remove (2) screws from bottom flange of
control panel.
3. Slide down control panel to clear jacket top
panel.
4. Rotate control panel down until panel stops. Do
not force.
NOTE: Caution must be taken not to damage
controlsor wiring.
Jacket Top Panel
Control Panel
TEMPERATURE CONTROLS
The pool or spa water temperature is controlled by
the pool heater thermostat on the upper front panel of
the heater. The control center contains an On/Off
toggle switch and a thermostat. The switch functions
as a means for turning the heater on or off.
The thermostat is fitted with a means of limiting the
upper temperature limit below the maximum level. The
knob stop adjustment ring illustrated below is adjustable by loosening the set screw, rotating the knobstop
ring to the desired location and retightening the set
screw.
Typical
Comfortable
Spa
Temperature
Typical Comfortable
Pool Temperature
Range
Range
Mounting Screws (2)
Fig. # 8267.0
Set ScrewKnobstop Ring
Fig. # 8104.0
21
Page 22
PRESSURE SWITCH
The pressure switch, or heater actuator, insures
that the heater operates only when the filter pump is in
operation. It is factory set at 1.75 PSI for deck level
installations. When the heater is located below the
level of the spa or pool, it may be necessary to reset the
pressure switch to compensate for the no-flow static
head. If it is necessary to reset the pressure switch, we
recommend the following procedure:
PRESSURE SWITCH ADJUSTMENT:
1. With pump and heater on, turn adjustment
knob (clockwise) until a click is heard from
the gas valve.
3. Turn pump off and on several times. Heater
should shut off immediately. If it does not,
repeat steps above until proper adjustment
is made.
TWO SPEED PUMPS
In some cases, the flow on the low-speed is insufficient to operate the heater. This is apparent when the
pressure switch cannot be further adjusted or if the
heater makes banging noises. In these cases, the
pump must be run at high speed when heating the
water.
CAUTION: Do not operate the heater without the
functionof a properly adjusted pressure switch.
HIGH LIMITS
The heater is equipped with two automatic high
limits. Set to operate at 135°F and 140°F.
NOTE: An erratic high limit is often characteristic of an
internal heat exchanger problem, i.e. scale buildup,
and U.G. operation. Refer to troubleshooting section.
Fig. # 8153.0
Adjustment Knob
Fig. # 8069.1
PRESSURE SWITCH ADJUSTMENT RANGE
Heat Exchanger Height
5' Max.
5' Max.
Pool or Spa
Heat Exchanger Height
Fig. # 8152.0
NOTE: If heater is installed outside of the limits shown,
a flow switch must be used in place of the pressure
switch when mounted and wired adjacent to the heater.
HIGH LIMIT REMOVAL
1. Shut off main electrical power switch to
heater.
2. Remove inspection panels.
3. Drain heater.
4. Remove defective high limit and replace with
a new high limit.
5. Reverse above procedure to re-install.
FLAME ROLL-OUT SAFETY SWITCH
The heater is equipped with a thermal cutoff device
to prevent flame roll-out in the event the heat exchanger becomes blocked. This is a "Single-use" type
fusible link or thermal fuse, that must be replaced when
disabled by an over temperature condition, caused by
excessive restriction in the heat exchanger flue passage.
22
Fig. #9177
Page 23
PILOT SAFETY (Millivolt System)
The heaters equipped with the standing pilot
(millivolt system), have pilot generators which act as a
safety device to shut off the flow of gas to the main
burners and the pilot burner in case the pilot flame is
extinguished. The pilot burner must be manually relighted to place the heater in operation again. Refer to
the lighting instructions provided on the heater label.
3. Lift burners from slotted spacers and slide from
orifices. Clean with a wire brush.
4. Orifices usually do not need to be replaced. To
clean, run either copper wire or wood toothpick
through orifice. Do not enlarge hole. To remove
orifice, use a socket wrench and remove from
manifold. DO NOT overtighten when reinstalling.
Burner Hold Down Bracket
PILOT SAFETY (IID Units) ELECTRIC IGNITION
The heater employs a pilot safety which closes the
main gas valve within 8/10ths of a second whenever the
pilot flame is interrupted. Pilot flame is automatically lit
when the device is powered. Unit performs its own
safety check and opens the main valve only after the
pilot is proven to be lit.
BURNER DRAWER REMOVAL
1. Shut off main electrical power switch to heater.
2. Shut off gas upstream of heater.
3. Remove front door.
4. Disconnect gas line from gas valve.
5. Remove (2) screws that mount burner tray to unit,
and (2) screws that secure gas valve to jacket.
6. Disconnect wires that terminate at gas valve.
7. Slide out burner tray.
8. Reverse above procedure to reinstall.
GAS VALVE REMOVAL
1. Shut off gas supply to the heater. Remove gas
piping to gas valve inlet.
2. Disconnect wires, pilot tubing and bleed line, if
required.
3. Turn vertical gas pipe from manifold slightly and
unscrew gas valve.
4. Reverse above procedure to re-install.
MAIN BURNER AND ORIFICE REMOVAL
Burners
Fig. # 8057.0
PILOT REMOVAL AND CLEANING
1. Disconnect pilot tubing, and wires from gas valve.
2. Remove pilot assembly from burner tray.
3. Remove pilot from bracket.
4. Remove pilot orifice and air opening (Honeywell
MV unit only), and clean with wire or small brush.
CAUTION! Do not enlarge hole in pilot orifice.
5. Reverse above procedure to reinstall.
Pilot
Pilot
Air
Opening
1. Remove burner drawer. See burner drawer
removal procedure.
2. Remove screws and burner hold down bracket.
NOTE: If the heat exchanger is sooted badly, the
burner hold down bracket and spacer can become
distorted from direct flame impingement and this usually necessitates replacement of these parts.
Orifice
Orifice
HONEYWELL PILOT ROBERTSHAW PILOT
Fig. # 8045.1 Fig. # 8102.0
23
Page 24
HEAT EXCHANGER REMOVAL
1. Shut water, gas and electricity off, close valves
and relieve pressure, remove relief valve. Remove side inspection panels.
2. Remove top holding screws.
3. Remove draft diverter, lift and remove top and flue
collector on stack-type models. Remove inspection panels.
4. Loosen bolts and disconnect flange nuts on inlet/
outlet header, loosen union(s) at gas pipe and slide
boiler away from piping until studs clear the
header.
5. Remove combustion chamber clips at the four
corners of the heat exchanger.
6. Lift heat exchanger straight up using caution not to
damage refractory.
7. Reverse above procedure to reinstall.
CONTROL IMMERSION WELL REPLACEMENT
1. Shut water off to heater and drain heat exchanger.
2. Remove jacket top panel.
3. Remove old control well with bushing and sleeve,
with 7/8" wrench or socket.
4. Slip "O" ring gasket over control well and install in
header.
"O" RING GASKET
WELL ASSEMBLY
Fig. # 8101.0
GASKET
U.G.
RETAINER PLUG
SPRING
FIig. # 8071.0
To test the operation of the Unitherm Governor,
place in hot water (over 110 °F) and watch for movement against spring. If there is no movement, replace
unit.
TUBE CLEANING PROCEDURE (Typical)
Establish a regular inspection schedule, frequency
depending on local water condition and severity of
service. Do not let the tubes clog up solidly. Clean out
deposits over 1/16" in thickness.
The heater must be cleaned from the rear as
shown. It is preferable, however, to remove the heat
exchanger and the in/out header for better visibility
through the tubes and to be sure the ground-up lime
dust does not get into the system.
Note that you do not remove the top panel or the
heat exchanger, generally.
After reaming, mount the wire brush in place of the
auger and clean out debris remaining in the tubes.
Another method is to remove the heat exchanger,
ream tubes and immerse heat exchanger in noninhibited de-scale solvent.
UNITHERM GOVERNOR (U.G.) REPLACEMENT
1. Shut water, gas and electricity off, close valves and
relieve pressure.
2. Drain heat exchanger.
3. Remove retainer plug located under outlet pipe
connection.
4. Remove spring and replace old U.G. with a new
U.G.
5. Reverse above procedure to re-install.
Fig. # 8128.0
24
Page 25
TUBE REPLACEMENT PROCEDURE
On Raypak units, tube replacement may be effected without rolling, as a temporary means of repair,
providing there are two or more tubes rolled in to act as
stays on the left or right sides. The "O" rings should
provide a seal up to 125 PSI working pressure. Use 3/
8" heavy duty reversible drill motor or larger to power
the tube roller. If a reversible drill is not available, after
rolling the tube in, remove the drill motor and wrench
out the roller. A tube roller is available from the factory.
Shut gas and power off to the unit, close the system
off and drain the heater. Remove the draft diverter.
Remove the access panel and jacket top. Lift the flue
collector off. Remove "V" baffles over tube(s) to be
replaced. If no pipe unions have been provided, use the
header as a union, remove the flange nuts off the inletoutlet header, break gas connection and slide heater
away from piping to allow room to work. Pull wedge
clips out of control wells and remove sensing bulbs. Lift
heat exchanger straight up and out.
Inspect header gaskets at this time. Unless severed, they are reusable. The tube may be cut out with
a hacksaw or hammer and chiseled adjacent to both
tube sheets, leaving studs in the tube sheets. Then
proceed to collapse studs in the tube sheets with a
chisel or screwdriver. Use caution not to cut into the
tube sheet. Replacement tubes will have the fins
stripped off longer on one end. The long end is inserted
into the opening of the tube sheet first; then the short
end is fitted through the opposite tube sheet. If the tube
ends become dented or bent, straighten at least (4)
inches back from the tube end by means of a tapered
punch.
Insert tube roller into tube opening up to stop
against tube, then push center rod in until roller is tight.
Be careful to keep replacement tube squared up 1/8"
outside each tube sheet. A loose tube will sometimes
pull toward the
roller. Attach drill motor to tube roller,
holding it straight and level. Proceed to expand tube
until the tool begins to grab. At this point, 1/2" to 1"
should be exposed on the tool shank. Reverse drill
motor or wrench out by hand. Care should be exercised
to avoid applying excessive torque during rolling operation and to avoid thinning out any part of the tube
wall excessively over .015". Use same procedure at
the opposite end of the tube.
Apply line pressure test, and re-roll, if necessary,
before reassembly of the heater.
DESOOTING PROCEDURE
CAUTION: SOOT IS COMBUSTIBLE. EXERCISE
EXTREME CARE.
Soot can clog areas between fins and cause eventual tube failure. Any sign of soot at the base of the
burners or around the outer jacket indicates a need for
cleaning.
1. Remove top and flue collector from cabinet.
2. Remove "V" baffles from heat exchanger.
3. Remove burner drawer. (See burner tray
removal).
4. Take garden hose and wash heat exchanger,
making sure soot is removed from between fins.
(Avoid excessive water against refractory).
5. Reassemble-When heater is fired, some steam
will form from wet refractory. This is normal.
NOTE: In extreme cases it may be necessary to remove the heat exchanger completely for cleaning. The
simplest method is steam cleaning at the local car
wash. DO NOT WIREBRUSH.
COMBUSTION CHAMBER REMOVAL
To remove combustion chamber, you must first
have removed the heat exchanger. Unbolt metal combustion chamber retainer from top and remove combustion chamber panels individually.
REFRACTORY PANELS TOP VIEW
Fig. # 8155.0
RAYPAK TUBE CLEANING KIT
Auger with Carbide TipExtension Pieces (5)
25
Wire Brush
Fig. # 8154.0
Page 26
SECTION 5 / TROUBLE SHOOTING GUIDE
IMPORTANT NOTICE
These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation
of this type of heating equipment and related system components. Installation and service personnel may be required by some
states to be licensed. Persons not qualified shall not attempt to install this equipment nor attempt repairs according to these
instructions.
MECHANICAL (FOR QUALIFIED SERVICE PERSONNEL ONLY)
PROBLEMCAUSESOLUTION
Harmonics, or whining noise.U.G. Inoperative..........................Check movement by putting in hot water (110°F
or higher). If no movement, replace.
*Debris or restriction in system........ Locate the restriction and remove. Flush system
and clean.
*Debris in gas line.........................Remove debris or blow out gas line.
Low flow....................................Scale forming in heat exchanger - clean heat
exchanger and check pool pH and total alkalinity.
Heater going on and offDirty filter..................................Backwash filter.
continously.Low water level in pool.................. Raise water level.
NOTE: Some heaters may be equipped with
an ignition module that shuts off pilot gas if
pilot fails to light. To reset, interrupt power to
heater.
WARNING
HIGH VOLTAGE
START
TURN GAS SUPPLY OFF.
TURN THERMOSTAT
(CONTROLLER) TO CALL
FOR HEAT
POWER TO MODULE
(24 V NOMINAL)
YES
SPARK ACROSS
IGNITER/SENSOR GAP
YES
TURN GAS SUPPLY ON
PILOT BURNER LIGHTS?
YES
SPARK STOPS WHEN
PILOT IS LIT?
YES
NO
NO
NO
NO
NOTE:Before troubleshooting, familiarize yourself with the start-up and checkout
procedure.
Check line voltage power, low voltage transformer, limit controller, thermostat
(controller) and wiring.
Pull ignition lead and check spark at module.
Spark Okay?
YES
• Check ignition cable, ground wiring, ceramic insulator and gap, and correct.
• Check boot of the ignition cable for signs of melting or buckling. Take protective
action to shield cable and boot from excessive temperatures.
• Check that all manual gas valves are open, supply tubing and pressures are good,
and pilot burner orifice is not blocked.
• Check electrical connections between module and pilot operator on gas control.
• Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay,
replace gas control; if not, replace module.
NOTE:If S8600H goes into lockout, reset system. Lockout is used on L.P.G. models.
• Check continuity of ignition cable and ground wire.
• Clean flame rod.
• Check electrical connections between flame rod and module.
• Check for cracked ceramic flame rod insulator.
• Check that pilot flame covers flame rod and is steady and blue.
• Adjust pilot flame.
• If problem persists, replace module.
MAIN BURNER LIGHTS?
YES
SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS?
YES
CALL FOR HEAT ENDS
SYSTEM SHUTS OFF?
YES
TROUBLESHOOTING
ENDS
NO
• Check electrical connections between module and gas control. If okay, replace
gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.
NOTE: IF S8600H goes into lockout, reset system.
• Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.
NO
• Check continuity of ignition cable and ground wire.
NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though
operation is normal at the time of checkout.
• Check that pilot flame covers flame rod and is steady and blue.
• If checks are okay, replace module.
NO
Repeat procedure until troublefree operation is obtained.
• Check for proper thermostat (controller) operation.
• Remove MV lead at module; if valve closes, recheck temperature controller and
wiring; if not, replace gas valve.
28
Page 29
ELECTRICAL (SOLID STATE THERMOSTAT IID)
If the pool/spa/hot tub water is too cold, troubleshoot the system as follows:
Check voltage at 24 V terminals.
VOLTAGE BETWEEN 21.5-28.5 V.
Set control to max. temperature. After 2-3
cycles, check water temperature.
TEMPERATURE BELOW 105°F
Disconnect sensor leads from circuit board.
Measure sensor resistance with ohmmeter.
RESISTANCE 1-14k OHMS.
Check water temperature; estimate expected sensor
resistance from chart below.
MEASURED AND ESTIMATED RESISTANCE
MATCH WITHIN 20 PERCENT.
Disconnect potentiometer leads from circuit board.
Measure resistance with ohmmeter. If resistance is:
0-100 ohms at minimum setting;
9k to 11k at maximum setting,
replace circuit board.
Above 11k ohms but less than
15 k ohms, , replace potentiometer.
bove 15k ohms, fix loose or broken wires;
replace potentiometer if necessary.
Reconnect all leads and check out system.
VOLTAGE OUTSIDE RANGE 21.5-28.5 V.
Check transformer, 120 V supply, correct as
necessary
TEMPERATURE 105-106° F.
Control ok.
RESISTANCE O OHMS (SHORT CIRCUIT)
Check system for shorted wires or open circuits.
Replace sensor if necessary.
MEASURED AND ESTIMATED RESISTANCE
DON'T MATCH.
Replace sensor. Reconnect all leads and check
out system.
If the pool/spa/hot tub water is too hot, troubleshoot the system as follows:
Check voltage at 24 V terminals.
VOLTAGE BETWEEN 21.5-28.5 V.
Set control to max. temperature. After 2-3
cycles, check water temperature.
TEMPERATURE ABOVE 108°F
Disconnect sensor leads from circuit board.
Measure sensor resistance with ohmmeter.
RESISTANCE 1-14k OHMS.
Check water temperature; estimate expected
sensor resistance from chart below.
MEASURED AND ESTIMATED RESISTANCE
MATCH WITHIN 20 PERCENT.
Disconnect potentiometer leads from circuit board.
Measure resistance with ohmmeter. If resistance
is:
0-100 ohms at minimum setting:
9k to 11k at maximum setting,
replace circuit board.
Above 11k ohms, replace
potentiometer.
0 ohms (short circuit), replace
potentiometer.
Reconnect all leads and check out system.
VOLTAGE OUTSIDE RANGE 21.5-28.5 V.
Check transformer, 120 V supply, correct as
necessary.
TEMPERATURE 105-106° F.
Control ok.
RESISTANCE ABOVE 15k OHMS (OPEN
CIRCUIT) OR SHORT CIRCUIT.
Fix loose or broken wires. Replace sensor if
necessary.
MEASURED AND ESTIMATED RESISTANCE
DON'T MATCH.
Replace sensor. Reconnect all leads and check
out system.
NOTE: To supply the correct part it is important that
you state the model number, serial number and type
of gas when applicable.
Any part returned for replacement under standard
company warranties must be properly tagged with
RAYPAK return parts tag, completely filled in with the
heater serial number, model number, etc., and shipped
to the Company freight prepaid.
If determined defective by the Company and within
warranty, the part will be returned in kind or equal
substitution, freight collect. Credit will not be issued.
RAYPAK, INC.
2151 Eastman Avenue
Oxnard, CA 93030
30
Page 31
31
Page 32
32
Page 33
33
Page 34
LIMITED WARRANTY
VERSA 155
Raypak, Inc. warrants that all parts of this product will be free from defects in materials and workmanship under
normal use and service for a period of TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE FOR A SINGLE
FAMILY RESIDENCE (ONE YEAR IF OTHER THAN FOR SINGLE FAMILY RESIDENCE USE). In accordance with the
terms of this warranty, we will furnish a Raypak replacement for any defective part or repair the part at our option. The
replacement or repair will be warranted for only the unexpired portion of the original warranty. Labor costs for removal
or reinstallation of parts are not covered by this warranty, nor are shipping charges to or from Raypak’s designated
repair center. This warranty does not cover rusting or corrosion on cabinet or burners that does not affect heater’s
operation.
WARRANTY CONDITIONS
This warranty applies only to the heater at its original place of installation. This warranty will be void if the heater is
installed in violation of applicable local codes and ordinances or if the rating plate or serial number is altered or
removed.
WARRANTY EXCLUSION
This warranty does not cover defects or malfunctions resulting from:
1.Failure to properly install, operate or maintain the heater in accordance with our printed instructions;
2.Abuse, alteration, accident, fire, flood, freeze and the like:
3.Misuse or neglect, including but not limited to, freeze-ups, operating the heater with the cabinet door off, having
flow restrictions or obstructions between the heater outlet and the spa, or not maintaining a proper chemical
balance (PH level must be between 7.4 and 7.8 and total alkalinity between 100 and 150 PPM. Total dissolved
solids (TDS) must be no greater than 3000 PPM);
4.Use of non-factory authorized accessories or other components in conjunction with the heater.
HOW TO MAKE A CLAIM
Immediately notify the dealer from whom the heater was purchased, supplying model and serial numbers of the unit,
date of purchase, and a description of the problem. The dealer should then promptly contact Raypak about the
warranty claim, and for the location of Raypak’s nearest designated repair center. (If the dealer for any reason is not
available, call or write Raypak directly at the address shown below, Attention: Warranty Service). After such notification
has been given and Raypak has advised the location of its designated repair center (which may be the dealer), bring
or ship, transportation prepaid, the defective part for replacement or repair to the designated repair center. However,
Raypak reserves the right at all times to inspect the claimed defect and verify warranty coverage at its factory.
MISCELLANEOUS
No one is authorized to make any other warranties on our behalf, ANY IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, SHALL NOT EXTEND BEYOND THE APPLICABLE
WARRANTY PERIODS SPECIFIED ABOVE. RAYPAK’S SOLE LIABILITY WITH RESPECT TO ANY DEFECT SHALL BE
AS SET FORTH IN THIS WARRANTY AND ANY CLAIMS FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES (INCLUDING DAMAGE FROM WATER LEAKAGE) ARE EXCLUDED. Some states do not allow limitations on how long an
implied warranty lasts, or for the exclusion of incidental or consequential damages, so the above limitation or
exclusion may not apply to you.
We suggest you immediately complete the information below and retain this Warranty Certificate in the event warranty
service is needed. Reasonable proof of the effective date of the warranty must be presented; otherwise, the effective
date will be based upon the date of manufacture plus THIRTY (30) Days.
This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.