WARNING: If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage, personal injury or death.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone in your building.
•Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
•If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service agency or
the gas supplier.
This manual should be maintained in legible condition and kept adjacent to the
heater or in a safe place for future reference.
P/N 240251 Rev. 16
Contents
SECTION 1: RECEIVING EQUIPMENT
3
SECTION 2: GENERAL SPECIFICATIONS
3
SECTION 3: INSTALLATION INSTRUCTIONS
3
Code Requirements
3
Base Installation
3
Clearances
4
Combustion Air
4
Venting Connections
5
Gas Supply Connections
6
Water connections
7
Controls
8
Wiring Diagrams
14
18
SECTION 4: SERVICING INSTRUCTIONS
18
General Location of Controls
19
Start-Up Procedures
20
Inspection Procedures
21
Servicing Procedures
24
Maintenance & Care
25
SECTION 5: TROUBLE SHOOTING
25
Mechanical
27
Electrical
SECTION 6: REPLACEMENT PARTS
28
WARRANTY
35
m
M
SECTION 1 / RECEIVING EQUIPMENT
On receipt of the equipment, visually check for external
IMPORTANT NOTICE
damage to the carton or the shipping crate. If the carton
or shipping crate is damaged, make a note on the Bill of
Lading and report the damage to the Carrier immediately.
Remove the boiler from the carton or shipping crate.
Do NOT use the shipping base crate as an installation
base.
On occasion, we ship some items loose. Be sure that
you receive the number of packages indicated on the
Bill of Lading.
When ordering parts, you must specify Model and
These instructions are intended for the use of qualified
personnel only, specifically trained and experienced in
the installation of this type of heating equipment and
related system components. Installation and service
personnel may be required by some states to be licensed. If your state is such, be sure your contractor
bears the appropriate license. Persons not qualified
shall not attempt to fix this equipment nor attempt
repairs according to these instructions.
Serial Number of boiler. When ordering under warranty
conditions, you must also specify date of installation.
Raypak recommends that this manual be reviewed
thoroughly before installing your Raypak Pool Heater. If
there are any questions which this manual does not
answer, please contact the factory or your local Raypak
WARNING:
Improper installation, adjustment, alteration, service
or maintenance may damage the equipment, create a
hazard resulting in asphyxiation, explosion or fire, and
will void the warranty.
representative.
Claims for shortages and damages must be filed with
CODE REQUIREMENTS
carrier by consignee. Permission to return goods must
be factory authorized and are subject to a stocking
charge.
Purchased parts are subject to replacement only
under the manufacturer's warranty. Debits for defective
replacement parts will not be accepted and will be
replaced in kind only per our standard warranties.
NOTE: The heater should not be located in an area
where possible water leakage will result in damage to
the area adjacent to the appliance or to the structure.
When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained,
be installed under the appliance. The pan must not
restrict combustion air flow.
SECTION 2 / GENERAL SPECIFICATIONS
Installation must be in accordance with local codes,
Models 962, 1125, 1223, 1336, 1468, 1631, 1826 &
2100 through 4001 are specifically designed for indoor
or, in the absence of local codes, with the latest editions
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
and National Electrical Code, ANSI/NFPA 70.
installation only. Models 926, 1083, 1178, 1287, 1414,
1571 & 1758 are specifically designed for outdoor instal-
BASE INSTALLATION
lation only. All heaters are standard with electronic
ignition for both natural and propane applications. Heaters require 115V power supply. Control circuits operate
at 24V, to be supplied by a 115V to 24V transformer.
Do NOT use the shipping base crate as an installation
base.
Heater must be mounted on a level base, such as
cement slab, cement blocks or other non-combustible
These heaters are design certified and tested under the
requirements of ANSI Z21.56 / CSA 4.7 American National Standard for Gas-Fired Pool Heaters. Rated inputs
suitable for up to 2000 feet elevation. For elevations above
2000 feet, reduce input 4% for each 1000 feet above sea
level, as high elevation reduces combustion performance.
surface. An optional non-combustible base is available
for Indoor Heater 962 through 1826. An alternative
method for providing a base for combustible floors as
illustrated below. Heaters may not be installed on
carpeting.
12"
12"
inimum
HEATER
Minimu
SECTION 3 / INSTALLATION
INSTRUCTIONS
Sheet Metal
4"
CALIFORNIA PROPOSITION 65 WARNING:
This product contains chemicals known to the State of
California to cause cancer, birth defects or other reproductive
harm.
Hollow concrete cinder block; align holes and leave
ends open. Alternative method for providing a non-com-
Minimum
bustible base.
24 Gauge
Fig. #8148
3
CLEARANCES
ALL HEATERS
For clearances from combustible surfaces, see chart
below. We require a minimal vertical clearance of three
feet between the upper surface of the flue outlet to a noncombustible material.
MINIMUM CLEARANCES FROM COMBUSTIBLE
CONSTRUCTION
INDOOR HEATERS
Top - 24"*Vent - 6"
Back - 24"
Right Side - 24"
Left Side - 24"
OUTDOOR HEATERS (926-1758)
Top - unobstructed
Back - 24"
Right side - 24"
Left Side - 24"
For servicing provide a front clearance as shown below
Model 926/962-758/1826 - 24"
Model 2100-4001 - 48"
*Vent includes factory supplied drafthood and does not
include field supplied vent systems above the drafthood. On Models 2100-4001 drafthood is built into
boiler.
For servicing, provide at least 24" in front of the heater
on Models 926-1826 & 48" in front of the heater on Models
2100-4001 for burner tray removal, and at least 18" on the
right side of the heater to inspect and delime the heat
exchanger.
OUTDOOR HEATERS (MODELS 926-1758)
These heaters are design certified for outdoor
installation,when equipped with the approved top designated for outdoor use. Heaters must not be installed
under an overhang of less than three (3) feet from the top
of the heater. Three (3) sides must be open in the area
under the overhang. Roof water drainage must be diverted
away from the heaters installed under overhangs with the
use of gutters.
4
foot
4
foot
Minimum
3
foot
Minimum
Forced Air Inlet
10
foot
Minimum
Minimum
4
foot
Minimum
1
foot
Minimum
Fig. #8245
The point from where the flue products exit the heater
must be a minimum of four (4) feet below, four (4) feet
horizontally from or one (1) foot above any door, window
or gravity inlet to a building. The top surface of the heater
shall be at least three (3) feet above any forced air inlet,
or intake ducts located within ten (10 ) feet horizontally.
HIGH WIND CONDITIONS (OUTDOOR UNITS ONLY)
In areas where high winds are frequent, it may be
necessary to locate the heater a minimum of 3' from
high vertical walls, or install a wind break so the heater
is not in direct wind current.
INDOOR HEATERS
The design is also certified for indoor installation
when equipped with approved drafthood. Locate heater
as close as practical to a chimney or gas vent.
COMBUSTION AIR (INDOOR UNITS ONLY)
The heater must have both combustion and ventilation air. Openings must not be obstructed. Minimum
requirements are as follows:
CAUTION: Combustion air must not be contaminated
by corrosive chemical fumes which can damage the
heater and void the warranty.
1. Free combustion air 1 sq. in. per 1000 BTU
input within 12" of the floor.
WARNING: The heater shall not be located in an
area where water sprinklers, or other devices, may
cause water to spray through the cabinet louvers
and into the heater. This could cause heavy internal
rusting or damage some electrical components,
and this would void the warranty.
2. Free ventilation air 1 sq. in. per 1000 BTU input
within 12" of the ceiling level.
NOTE: If the room the heater is installed in is located
against an outside wall and air openings communicate
directly with the outdoors, the openings may be 1/4 the
size specified above (ANSI Z223.1/NFPA 54, latest
edition)
4
VENTING CONNECTIONS
DRAFTHOOD (INDOOR) MODELS 962-1826
Locate and assemble as shown below. Secure with
screws supplied in envelope in carton.
Fig # 8165
For protection against rain or blockage by snow, the
vent pipe must terminate with a vent cap which complies
with the local codes or, in the absence of such codes,
to the latest edition of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
The discharge opening must be a minimum of two feet
vertically from the roof surface and at least two feet
higher than any part of the building within ten feet. Vent
stack shall be at least five feet in vertical height above
the drafthood outlet. The vent cap location shall have a
minimum clearance of 4 feet horizontally from, and in no
case above or below, unless a 4-foot horizontal distance is maintained, from electric meters, gas meters
regulators and relief equipment.
The weight of the vent stack or chimney must not rest
on boiler drafthood. Support must be provided in compliance with applicable codes. The heater top and draft
hood must be readily removable for maintenance and
inspection. Vent pipe should be adequately supported to
maintain proper clearances from combustible construction.
Type "B" double wall or equivalent vent pipe is recommended. However single wall metal vent pipe may be
used as specified in the latest edition of the National
Fuel Gas Code ANSI Z223.1/NFPA 54.
Models 2100-4001 have built-in drafthoods that must be
properly vented to the outside.
VENT PIPING
WARNING:
Indoor heater requires a drafthood that must be
connected to a vent pipe and properly vented to the
outside. Failure to follow this procedure can cause fire
or fatal carbon monoxide poisoning.
Vent piping the same size or larger than the draft hood
outlet is recommended, however, when the total vent
height is at least ten (10) feet (drafthood relief opening to
vent terminal), the vent pipe size may be reduced as
specified in Chapter 10 of the National Fuel Gas Code,
ANSI Z 223.1/NFPA 54 - latest edition. Avoid long
horizontal runs of vent pipe and too many elbows. If
installation requires horizontal or non-vertical runs, the
vent pipe must have a minimum of 1/4 inch per foot rise
and should be supported at not more than five foot
intervals. Plumbers' tape, criss-crossed, will serve to
space both horizontal and vertical piping. Gas vents
supported only by the flashing and extending above the
roof more than five feet should be securely guyed or
braced to withstand snow and wind loads. We recommend use of insulated vent pipe spacer through the roofs
and walls.
10' OR LESS
2' MIN
VENT PIPE
DRAFT HOOD
HEATER
VENT CAP
2' MIN
5' MIN
Fig. #8119
At the time of removal of an existing heater, the
following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances remaining
connected to the common venting system are not in
operation.
5
(a) Seal any unused openings in the common
venting system.
(b) Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion
and other deficiencies which could cause an
unsafe condition.
(c) Insofar as is practical, close all building doors
and windows and all doors between the space
in which the appliances remaining connected
to the common venting system are located and
other spaces of the building. Turn on clothes
dryers and any appliance not connected to the
common venting system. Turn on any exhaust
fans, such as range hoods and bathroom
exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust fan.
Close fireplace dampers.
(d) Place in operation the appliance being inspected.
Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
(e ) Test for spillage at the drafthood relief opening
after 5 minutes of main burner operation. Use
the flame of a match or candle, or smoke from
a cigarette, cigar or pipe.
GAS SUPPLY CONNECTIONS
Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-off valve located
outside the heater jacket. All gas piping should be
tested after installation in accordance with local codes.
MANUAL SHUTHEATERGAS VALVE
OFF VALVEJACKET
GAS INLET
UNION
SEDIMENT
TRAP
FIG. #8090.0
CAUTION: The heater and its manual shut-off valve must
be disconnected from the gas supply during any pressure
testing of that system at test pressures in excess of 1/
2 psig (3.45 KPA). Dissipate test pressure in the gas
supply line before reconnecting the heater and its manual
shut-off valve to gas supply line. FAILURE TO FOLLOW
THIS PROCEDURE MAY DAMAGE THE GAS VALVE.
OVER PRESSURIZED GAS VALVES ARE NOT COVERED BY WARRANTY. The heater and its gas connections shall be leak tested before placing the appliance in
operation. Use soapy water for leak test. DO NOT use
open flame.
(f) After it has been determined that each
appliance remaining connected to the common
venting system properly vents when tested as
outlined above, return doors, windows, exhaust
fans, fireplace dampers and any other gas
burning appliance to their previous conditions
of use.
(g) Any improper operation of the common venting
system should be corrected so the installation
conforms with the latest edition of the National
Fuel Gas Code, ANSI Z223.1/NFPA 54. When
re-sizing any portion of the common venting
system, the common venting system should be
re-sized to approach the minimum size as
determined using the appropriate tables in Part
11 of the National Fuel Gas Code, ANSI Z223.1/
NFPA 54.
For special venting applications that require reduced
vent sizes and through the wall venting, the optional D
Series Power Vent can be used. Consult the factory or
your local Raypak representative.
NOTE: Do not use teflon tape on gas line pipe thread.
A flexible sealant is recommended.
A minimum of 7 in. WC and a maximum of 10.5 in. WC
upstream pressure under load, and no load conditions
must be provided for natural gas or a minimum of 11 in.
WC and a maximum of 13 in. WC for propane gas.
6
GAS PRESSURE REGULATOR
The gas pressure regulator is preset and sealed at 4 in.
WC for natural gas, and 11 in. WC for propane gas.
Between the gas valve and the burners is a 1/8" pipe plug.
The pressure at this point, taken with a manometer,
should be about 3.7 in. WC natural gas and 10.5 in. WC
propane gas. If an adjustment is needed, remove seal
and turn adjustment screw clockwise , to
increase pressure or counterclocwise , to
decrease pressure.
GAS PRESSUREMANOMETER
TEST UPSTREAM
MANUAL
SHUT-OFF
VALVE
GAS PRESSURE TEST
AT GAS VALVE
GAS PRESSURE TEST
AT HEATER
PIPE SIZING FOR GAS CONNECTIONS
Fig. #8149.0
Bleed
Line Connection
Fig. # 8185.2
WATER CONNECTIONS
LOCATION
The heater requires water flow and positive pressure
to fire and operate properly. It must therefore be
installed downstream of the discharge side of the filter
pump. A typical installation is plumbed as follows:
1.The inlet side of the filter is plumbed directly to the
discharge side of the filter pump;
2.The outlet side of the filter is then plumbed to the
inlet of the heater; and
3.The outlet of the heater is plumbed to the return
line to the pool or spa. The pump, filter and heater
are thus plumbed in series.
Heater must be located so that any water leaks will not
damage the structure of adjacent area. High temperature plastic pipe (CPVC) may be connected directly into
the heater Models 926-1223, if local codes permit and
if controls operate the pump for at least fifteen minutes
after the heater is turned off.
VENTING OF DIAPHRAGM GAS COMPONENTS
Heaters have gas train components that have diaphragms in their construction are supplied with a bleed
line connection that must be connected to the outside
atmosphere as required by the National Fuel Gas Code.
Under NO circumstances shall bleed lines terminate in
the gas utilization equipment flue or exhaust system.
CAUTION (Models 926-1223): NEVER install PVC
directly into heater. Four feet of copper or high temperature pipe and two elbows are required between the
heater and the PVC connections.
Fig. # 8129.0
7
When local codes permit the use of less than four feet
high temperature piping or two elbows, provisions
should be made to always shut the heater off a minimum
of 15 minutes prior to pump shut down in order to carry
away residual heat and prevent damage to the low
temperature piping. A fireman switch included in the
time clock may be used for this purpose with instructions not to override this sequence manually. See
wiring diagram section for electrical hookup location of
the fireman switch in the electrical circuit.
NOTE (Models 926-1223): If piping is used into the
heater, this piping (copper) must be anchored or screwed
into the flange (metal) if operating pressures above 30
PSI are encountered.
CONTROLS
WATER PRESSURE SWITCH
A water pressure switch is provided in the heater to
shut down the gas valves in the event the water supply to
the heater is interrupted. It is very important to verify that
the switch electrically opens and shuts off the gas valve
when water flow to the heater is interrupted. Otherwise,
rapid and severe damage to the heater will likely occur.
(The water pressure switch should be checked and
adjusted for proper operation by a qualified service person
at the time of installation and periodically checked
thereafter. Refer to pressure switch servicing instructions in Section 4 of this manual).
WARNING:Operation of the heater without water
circulation will cause rapid and severe damage to the
heater.
AUTOMATIC CHLORINATORS AND CHEMICAL
FEEDERS
UNITHERM GOVERNOR OPERATION
The patented Unitherm Governor is a thermostatic
mixing valve specifically designed to maintain constant
heater internal temperature between 105° to 115°F
despite continually changing flow rates from the filter
and changing pool temperatures. This narrow range is
needed to prevent damaging condensation on the burners which will occur if the heater runs for any length of
time below 100°F. It is also needed to inhibit scale
formation in the tubes by maintaining temperatures well
below accelerated scaling temperatures.
The Unitherm Governor is built into the inlet/outlet
header on models 926 through 1223. The larger sizes,
models 1287 through 4001, have an externally mounted
bypass pump that is designed to maintain the water
entering the heater at the proper temperature that will
prevent condensation and scale. Thermometers are
provided on the inlet and outlet to the heater.
COMPANION FLANGE CONNECTIONS
(Models 926-1223)
DO NOT use petroleum base assembly fluids (such
as Petroleum Jelly or Lubricating Oil). If assembly lube
is required use a silicone base such as Armoral etc.
The inlet/outlet header flange accepts a 2" copper
tube as a slip connection directly into the header. The
flange is also threaded for a 2" NPT copper male adapter.
MODELS 926 - 1223
INLET/OUTLET HEADER
All chemicals must be introduced and completely
diluted into the pool or spa water before being circulated
through the heater. Do not place chlorine tablets or
bromine sticks in the skimmer. High chemical concentrations will result when the pump is not running (eg,
overnight).
Chlorinators must feed downstream of the heater and
have an anti-siphoning device to prevent chemical
backup into the heater when the pump is shut off.
NOTE: High chemical concentrates from feeders and
chlorinators that are out of adjustment will cause very
rapid corrosion to the heat exchanger in the heater.
Such damage is not covered under the warranty.
FLANGE GASKET
OUTLET
INLET
HEADER FLANGE
Fig. #8221.0
8
MODELS 1287/1336 - 1758/1826
1-1/2" Slip Ball Valve
2-1/2" Outlet
2-1/2" Inlet
MODELS 2100-4001
2" Slip
Ball Valve
3" Outlet
Inlet/Outlet
Header
Pump
Inlet/Outlet
Header
Fig. #9200
3" Inlet
2 H.P. Pump
FLOW RATES/WATER CONNECTIONS
MODELCONNECTION SIZEMIN GPMMAX GPM
926-1223*60120
1287-18262-1/2" FPTRefer to flow rate table
2100-40013" FPT
*Loop is secondary piping to
heater from main system.
Fig. #9270
9
Raypak recommends the installation of an air bleed vent at a suitable location (usually the highest point) to remove
air from the piping system. These units should be available at your local wholesale supplier. Raypak does not provide
this item.
CAUTION:
Power to the heater should be interlocked with the main system pump to make sure the heater does not
fire without the main system pump in operation.
Improper flow control can damage the heater. Uncontrolled flow (too high) or restricted flow (too low) can
seriously affect heater operation. Follow these instructions to make sure your heater is properly installed.
Models 1287 through 4001 are equipped with an external pump and bypass arrangement that blends outlet water with
the inlet to increase the inlet water temperature, thereby reducing the likelihood of condensation forming on the heat
exchanger. The pump also serves to circulate water through the heater from the main system piping.
To complete the installation of the pool heater, the pool thermostat needs to be installed in the main return water line.
This will ensure that the heater will be energized at the right time. If the main water line is too far away from the heater
and the capillary bulb will not reach it, locate the pool thermostat adjacent to the main line and run wires back to the
heater. Follow the instructions listed below to install the pool stat.
MOUNTING THE POOLSTAT CONTROL WITH FRONT-MOUNTED
LOOP USING MOUNTING SLOTS
For heater models:
1287, 1336, 1414, 1468, 1571, 1631, 1758, 1826, 2100, 2500, 3001,
3500, 4001.
Note: For more detail on piping, see figures 9268 and 9269.
1. Remove the poolstat control cover by removing the two cover
screws at the top. See Figs. 1 & 2.
2. Lace metal strapping or clamps, (NOT PROVIDED) through the ¾”
slots on the cover and fasten securely to pipe as shown in Figs. 3
& 4. NOTE: Do not over-tighten clamps.
3. Remove either the left or right “knock-out” for wiring on the poolstat
control as shown in Fig. 5.
4. Attach appropriate conduit and connectors to the poolstat control.
5. Attach wires to the poolstat wire terminals. See Fig.6.
6. Install poolstat control to the cover and fasten cover screws.
7. Poolstat should be mounted level as shown in Fig. 7.
Fig. 3: Hose Clamp Slots
Fig. 4
Fig. 1: Poolstat Control
Fig. 2: Control Cover
Fig. 5Fig. 6Fig. 7
10
MOUNTING WELL INTO SYSTEM RETURN LOOP PIPE - FRONT-MOUNTED LOOP:
Note: For more detail on piping configurations for large systems, see figures 9268 and 9269.
1. Locate and mark an area on the main system return loop pipe where the well is always exposed to the water
circulating back from the pool. See Fig. 8.
2. Shut off water and drain any water from the pipe as necessary.
3. Drill a 23/32" diameter hole (½” NPT) into the pipe as shown in Fig. 9.
4. Using a ½” NPT tap and appropriate handle, thread the tap into the pipe.
5. Apply pipe dope as necessary to male threads of well and insert into threaded hole.
Note: Do not over-tighten well.
Fig. 8
Fig. 10
Fig. 9
Note: The drawings and instructions above show only one of several acceptable ways of installing the
dry well into main system loop. The use of saddle clamps and “Weld O Lets” (shown in Fig. 10) are
acceptable. Follow clamp manufacturer’s instructions.
To adjust the temperature:
1. Both isolation valves must be fully open.
2. Adjust Bypass Valve "A" 1/2 open and Balancing Valve "B" fully open. (See piping configuration page 11)
3. Fire your Raypak pool heater and adjust Bypass Valve "A" to obtain a heater inlet temperature approximately
100°F-105°F. Turning Valve A in the open direction will raise the heater inlet temperature and closing Valve "A"
will lower the heater inlet temperature.
4. If the heater inlet temperature remains less than 100°F and Valve "A" is fully open, leave Valve "A" fully open and
throttle Valve "B" until the heater inlet temperature rises to within the range of 100°F-105°F.
5. The resultant heater outlet temperature should be in the range of 120-130°F.
6. As the pool temperature rises to the desired temperature as controlled by the Pool aquastat, small adjustments
to valves "A" and "B" will be required for optimum performance. Heater temperatures should be checked regularly
to prevent heater condensation. The heater inlet temperature can be higher than 100°F without heater damage
but operating at less than 100°F inlet can cause damage from condensation.
Note: Consult factory if target temperatures cannot be achieved.
Loading...
+ 26 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.