Raypak MVB 5042004 User Manual

INSTALLATION & OPERATING
W
INSTRUCTIONS
Models 504–2004
Types H, WH, P & WHP
WARNING: Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury, exposure to hazardous materials* or loss of life. Review the information in this manual carefully. *This unit contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future reference.
CATALOG NO. 3400.54E Effective: 03-25-10 Replaces: 03-19-09 P/N 241317 Rev. 6
Rev. 5 reflects the following: Changes to: Air Filter instructions on page 11, minor text changes on pages 13 and 14, Figs. 10 and 11 on page 15,. Fig 12
and Table G on page 16, Fig 13 on page 17, minor text changes on page 20, Fig. 21 on page 22, Figs. 22-28 on pages 25­30, Table N on page 29, Fig. 35 on page 32, Mode 8 description on page 33, minor text changes on pages 42, 43 and 46, Troubleshooting chart on page 48. Additions: Fig. 2 on page 6, Low-lead requirement on page 5, Fig. 8 on page 11, note on page 12, Caution on page 20, Fig. 22 on page 22, Fig. 36 on page 33, air filter instructions on pages 50 and 51.
2
CONTENTS
WARNINGS 4 BEFORE INSTALLATION 5
Product Receipt 5 Model Identification 5 Ratings and Certifications 5 Installations at Elevation 5 Component Locations 6 General Information 6
GENERAL SAFETY 7
Time/Temperature Relationships in Scalds 7
INSTALLATION 8
Installation Codes 8 Equipment Base 8 Clearances 8 Combustion and Ventilation Air 9 Conventional Combustion Air Supply 11 Water Piping 12 Hydronic Heating 14 Gas Supply 19 Electrical Power Connections 20 Field Wiring Connection 22 Venting 22 Venting Installation Tips 24 Venting Configurations 24 Engineered Vent Systems 27
Outdoor Installation 29 Controls 30 Heater Sequence of Operation 37
WIRING DIAGRAMS 40 START-UP 42
Pre Start-up 42 Start-Up 43
OPERATION 46
Lighting Instructions 46 To Turn Off Gas To Appliance 47 UDB Fault History 47
TROUBLESHOOTING 48 MAINTENANCE 49
Suggested Minimum Maintenance Schedule 49 Preventative Maintenance Schedule 49 Filter Maintenance 50 Filter Replacement 51
APPENDIX 51
Inside Air Contamination 51
IMPORTANT INSTRUCTIONS FOR THE COMMONWEALTH OF MASSACHUSETTS 52 WARRANTY 53 START-UP CHECKLIST 55
3

WARNINGS

Pay Attention to These Terms
ndicates the presence of immediate hazards which will cause severe
DANGER:
I personal injury, death or substantial property damage if ignored.
WARNING:
CAUTION:
NOTE:
DANGER: Make sure the gas on which the heater
will operate is the same type as that specified on the heater rating plate.
WARNING: Should overheating occur or the gas supply valve fail to shut, do not turn off or disconnect the electrical supply to the heater. Instead, shut off the gas supply at a location external to the heater.
WARNING: Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
WARNING: To minimize the possibility of improper operation, serious personal injury, fire, or damage to the heater:
Always keep the area around the heater free of combustible materials, gasoline, and other flammable liquids and vapors.
Heater should never be covered or have any blockage to the flow of fresh air to the heater.
WARNING: Risk of electrical shock. More than one disconnect switch may be required to de-energize the equipment before servicing.
Indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
CAUTION: Operation of this heater in low temperature systems requires special piping. Harmful internal condensation will occur if the inlet water temperature does not exceed 120°F. Warranty claims will be denied when condensation occurs.
CAUTION: If this heater is to be installed above radiation level, it must be provided with a low water cut-off device at the time of heater installation.
CAUTION: This heater requires forced water circulation when the burner is operating. See minimum and maximum flow rates. Severe damage will occur if the heater is operated without proper water flow circulation.
CAUTION: If this heater is to be installed in a negative or positive pressure equipment room, there are special installation requirements. Consult factory for details.
NOTE: Minimum 18 AWG, 105°C, stranded wire must be used for all low voltage (less than 30 volts) external connections to the unit. Solid conductors should not be used because they can cause excessive tension on contact points. Install conduit as appropriate. All high voltage wires must be the same size (105°C, stranded wire) as the ones on the unit or larger.
WARNING - CALIFORNIA PROPOSITION 65: This product contains chemicals known to the
State of California to cause cancer, birth defects or other reproductive harm.
4

BEFORE INSTALLATION

Raypak strongly recommends that this manual be re­viewed thoroughly before installing your MVB heater. Please review the General Safety information before installing the heater. Factory warranty does not apply to heaters that have been improperly installed or oper­ated. (Refer to the warranty at the back of this manual.) Installation and service must be performed by a qualified installer, service agency or gas supplier. If, after reviewing this manual, you still have questions which this manual does not answer, please contact your local Raypak representative or visit our website at www.raypak.com.
he upper rear jacket panel of the heater. The model
t number will have the form H7-2004 or similar depend­ing on the heater size and configuration. The letter(s) in the first group of characters identifies the application
H = Hydronic Heating, P = Pool Heating, WH =
( Domestic Hot Water (DHW), WHP = Water Heater for
ool Heating). The number which follows identifies the
P firing mode (7 = electronic modulation, 1 = On/Off). The second group of characters identifies the size of the heater (three or four numbers representing the approximate MBTUH input), and, where applicable, a letter, indicating the manufacturing series.

Ratings and Certifications

Thank you for purchasing a Raypak product. We hope you will be satisfied with the high quality and durability of our equipment.

Product Receipt

On receipt of your heater it is suggested that you visu­ally check for external damage to the shipping crate. If the crate is damaged, make a note to that effect on the Bill of Lading when signing for the shipment. Next, remove the heater from the shipping packaging. Report any damage to the carrier immediately.
On occasion, items are shipped loose. Be sure that you receive the correct number of packages as indi­cated on the Bill of Lading.
Claims for shortages and damages must be filed with the carrier by consignee. Permission to return goods must be received from the factory prior to shipping. Goods returned to the factory without an authorized Returned Goods Receipt number will not be accepted. All returned goods are subject to a restocking charge.
When ordering parts, you must specify the model and serial number of the heater. When ordering under war­ranty conditions, you must also specify the date of installation.
Purchased parts are subject to replacement only under the manufacturer’s warranty. Debits for defec­tive replacement parts will not be accepted. Parts will be replaced in kind only per Raypak’s standard war­ranties.

Model Identification

The model identification number and heater serial number are found on the heater rating plate located on
Standards:
ANSI Z21.56 · CSA 4.7 - latest edition, Gas-Fired Pool Heaters
ANSI Z21.13 · CSA 4.9 - latest edition, Gas-Fired Hot Water Boilers
CAN 3.1 - latest edition, Industrial and Commercial Gas-Fired Package Boilers
ANSI Z21.10.3 · CSA 4.3 - latest edition, Gas Wa­ter Heaters
SCAQMD Rule 1146.2
Low-lead content (<.25%) CSA-verified
All Raypak heaters are National Board Approved, and design-certified and tested by the Canadian Standards Association (CSA) for the U.S. and Canada. Each heater is constructed in accordance with Section IV of the American Society of Mechanical Engineers (ASME) Heater Pressure Vessel Code and bears the ASME stamp. This heater also complies with the latest edition of the ASHRAE 90.1 Standard.
WARNING: Altering any Raypak pressure vessel by installing replacement heat exchangers, tube bundle headers, or any ASME parts not manufactured and/or approved by Raypak will instantly void the ASME and CSA ratings of the vessel and any Raypak warranty on the vessel. Altering the ASME or CSA ratings of the vessel also violates national, state, and local approval codes.
Installations at Elevation
Rated inputs are suitable for up to 4,500 ft elevation without de-rating. Consult your local representative or the factory for installations at altitudes over 4,500 ft above sea level. No hardware changes are required to the heaters for installations up to 10,000 ft (adjust­ments may be required).
5
HIGH VOLTAGE ELECTRICAL CONNECTIONS

Component Locations

Fig. 3: Component Locations – Rear
Panels omitted for clarity
Fig. 1: Component Locations – Side
Top panel, blower and gas train omitted for clarity
Fig. 4: Component Locations – Top
General Information
Model
No.
504 500 350 2 1 1 8 6
754 750 525 2 1 1 10 6
1104 1100 770 2-1/2 1-1/4 1 10 6
1504 1500 1050 2-1/2 1-1/4 1 12 8
MBTUH
Input*
Max.* Min.* N P Flue Intake
Water Conn. (NPT)
Gas
Conn.
(NPT)
Vent Size
(in.)
Panels omitted for clarity
Fig. 2: Component Locations – Front
2004 1999 1400 2-1/2 2 1 14 8
*H7 units only.
Table A: Basic Data
6
GENERAL SAFETY
Water temperature over 125°F can cause instant severe burns or death from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
See instruction manual before set­ting temperature at water heater.
Feel water before bathing or show­ering.
Temperature limiting valves are available, see manual.
Water
Temp.
Time to Produce Serious
Burn
120°F More than 5 minutes
125°F 1-1/2 to 2 minutes
130°F About 30 seconds
135°F About 10 seconds
140°F Less than 5 seconds
145°F Less than 3 seconds
150°F About 1-1/2 seconds
155°F About 1 second
Table courtesy of The Shriners Burn Institute
To meet commercial hot water use needs, the high limit safety control on this water heater will shut off the main gas valve before the outlet temperature reaches 210°F. However, water temperatures over 125°F can cause instant severe burns or death from scalds. When supplying general purpose hot water, the rec­ommended initial setting for the temperature control is 125°F.
This section applies to Hot Water Supply Boilers and Hot Water Heaters ONLY. For sanitary rinse applica­tions where outlet temperatures of 180°F to 195°F are required, a boiler is recommended since the 210°F limit on water heaters will NOT allow the heater to maintain these desired sanitary rinse temperatures.
Safety and energy conservation are factors to be con­sidered when setting the water temperature on the thermostat. The most energy-efficient operation will result when the temperature setting is the lowest that satisfies the needs of the application.
Water temperature over 125°F can cause instant severe burns or death from scalds. Children, disabled and elderly are at highest risk of being scalded.
Feel water before bathing or showering.
Temperature limiting valves are available.
NOTE: When this water heater is supplying general purpose hot water for use by individuals, a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury. Contact a licensed plumber or the local plumbing authority for further information.
Maximum water temperatures occur just after the heater’s burner has shut off. To determine the water temperature being delivered, turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer.
Time/Temperature Relationships in Scalds
The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.
Table B: Time to Produce Serious Burn
7
Heater
Side
Minimum Clearance
from Combustible
Surfaces
Minimum
Service
Clearance
Floor* 0” 0”
Rear 12” 24”
Right
Side
1” 1”
Left Side 1” 1”
Top 0” 10”
Front Open 24”
Vent 1” 1”
The temperature of the water in the heater can be reg­ulated by using the Raypak Modulating Temperature Control. To comply with safety regulations, the control is set at 120°F when shipped from the factory (Mode 3 default setting for Tank Target).
To adjust the water temperature, follow the instruction for the operation of the control starting on page 30 of this manual. The control is shown below for identifica­tion purposes only. (See Fig. 5.)
Equipment Base
The heater should be mounted on a level, structurally
ound surface. The heater is approved for installation
s on a combustible surface but must NEVER be
nstalled on carpeting. Gas-fueled equipment installed
i in enclosed parking garages must be located at least 18 in. above the floor.
CAUTION: This heater should be located in an area where water leakage will not result in damage to the area adjacent to the appliances or to the structure. When such locations cannot be avoided, it is recommended that a suitable catch pan, adequately drained, be installed under the appliance. The pan must not restrict air flow.
In addition, the heater shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation or service (circulator replacement, control replacement, etc.).
Fig. 5: Modulating Temperature Control
CAUTION: Hotter water increases the risk of scalding! There is a hot water scald potential if the thermostat is set too high.
INSTALLATION
INSTALLATION
Installation Codes
Installations must follow these codes:
Local, state, provincial, and national codes, laws, regulations and ordinances
National Fuel Gas Code, ANSI Z223.1/NFPA 54 – latest edition (NFGC)
National Electrical Code, ANSI/NFPA 70 - latest edition (NEC)
Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, (CSD-1) when required
For Canada only: CAN/CSA B149 Natural Gas and Propane Installation Code and CSA C22.1 C.E.C. Part 1 (C22.1)
If the heater needs to be secured to the ground, use the brackets that were used to bolt the heater to the shipping pallet.
Clearances
Indoor Installations
*DO NOT install on carpeting.
Table C: Clearances – Indoor Installations
When installed according to the listed minimum clear­ances from combustible construction, these heaters can still be serviced without removing permanent structural construction around the heater. However, for ease of servicing, a clearance of at least 24 in. in front, at least 24 in. on the rear and 10 in. above the top of the heater is required. This will allow the heater to be
8
odes and the requirments of the gas supplier. Three
c sides must be open in the area under the overhang. Roof water drainage must be diverted away from heaters installed under overhangs.
The combustion air intake terminal MUST be used for
utdoor installations. The elbow is shipped loose to be
o installed on the rear of the heater at the job site.
Heater
Side
Rear 12” 24”
Front Open 24”
Right Side 1” 1”
Left Side 1” 1”
Top Unobstructed 10”
Vent
Termination
Table D: Clearances – Outdoor Installations
Min. Clearance
from Combustible
Surfaces
12” 12”
Minimum
Service
Clearance
Combustion and Ventilation Air
NOTE: Use of this heater in construction areas
where fine particulate matter, such as concrete or dry-wall dust, is present may result in damage to the heater that is not covered by the warranty. If operated in a construction environment, a clean source of combustion air must be provided directly to the heater.
Venting not shown for clarity. Heater must be vented per instruc-
tions in this manual
Fig. 6: Minimum Clearances from Combustible
Surfaces – Indoor and Outdoor Installations
serviced in its installed location without movement or removal of the heater.
Service clearances less than the minimum may require removal of the heater to service either the heat exchanger or the burner components. In either case, the heater must be installed in a manner that will enable the heater to be serviced without removing any structure around the heater.
Outdoor Installations
These heaters are design-certified for outdoor installa­tion. Heaters must not be installed under an overhang unless they are in accordance with local installation
Indoor Units
This heater must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment ventilation. Combustion air can be sup­plied via conventional means where combustion air is drawn from the area immediately surrounding the heater, or via direct vent, where combustion air is drawn directly from outside. All installations must com­ply with the requirements of the NFGC (U.S.) and B149 (Canada), and all local codes.
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty. (See the Appendix.)
NOTE: It is recommended that the intake vent be insulated to minimize sweating.
9
U.S. Installations
1
Canadian Insta llations
2
A
Clearance above grade, veranda, porch, deck, or balcony
1 ft (30 cm) 1 ft (30 cm)
B
Clearance to window or door that may be opened
4 ft (1.2m) below or to side
of opening; 1 foot (30 cm)
above opening
3 ft (91 cm)
C Clearance to permanently closed window **
D
Vertical clearance to ventilated soffit located
above the terminal within a horizontal dis­tance of 2 ft (61cm) from the centerline of the terminal
5 ft (1.5m) *
E Clearance to unventilated soffit **
F Clearance to outside corner **
G Clearance to inside corner 6 ft (1.83m) *
H
Clearance to each side of center line ex- tended above meter/regulator assembly
*
3 ft (91 cm) within a height
15 ft above the me-
ter/regulator assembly
I Clearance to service regulator vent outlet * 6 ft (1.83m)
J
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
4 ft (1.2m) below or to side
of opening; 1 ft (30 cm)
above opening
3 ft (91 cm)
K Clearance to mechanical air supply inlet
3 ft (91 cm) above if within
10 ft (3m) horizontally
6 ft (1.83m)
L
Clearance above paved sidewalk or paved driveway located on public property
7 ft (2.13m)
7 ft (2.13m) t
M
Clearance under veranda, porch, deck or balcony
* 12 in. (30 cm) TT
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code
2
In accordance with the current CAN/CGA-B149 Installation Codes
t Vent terminal shall not terminate dir ectly above sidewalk or paved driveway located between 2 single family dwellings that s erves
both dwellings
TT Permitted only if veranda, porc h, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal and
underside of veranda, porch, deck or balcony is greater than 1 ft (30c m)
* Clearances in accordance with local installation codes and the requirements of the gas supplier
Fig. 7: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations
Table E: Vent/Air Inlet Termination Clearances
10
Air Filter
An air filter is supplied standard with the heater. This filter is shipped loose for field installation. Refer to the Air Filter Kit Installation Instructions (Part No. 241338) for details.
r sealed single-wall galvanized ducting. The duct will
o attach directly to the air collar located on the rear of the heater, using three or four sheet metal screws (not supplied) equally positioned around the circumference
f the duct. The screen assembly should be removed
o before attaching any air duct to the heater. The screws
nd duct connection point must be sealed with RTV
a (not supplied). TruSeal is generally used when dam­aging contaminants are present in the mechanical room.
All ducting must be self-supported.
CAUTION: Use TruSeal combustion air if damaging airborne contaminants are or may be present in the heater area. See the Appendix of this manual regarding air contamination.
Fig. 8: Air Filter Box
Direct Vent
If outside air is drawn through the intake pipe directly to the unit for combustion:
1. Install combustion air direct vent in accordance with Fig. 27 (horizontal) or Fig. 28 (vertical) of this manual (pages 28 and 29, respectively).
2. Provide adequate ventilation of the space occu­pied by the heater(s) by an opening(s) for ventilation air at the highest practical point com­municating with the outdoors. The total cross-sectional area shall be at least 1 in.2of free area per 20,000 BTUH (111 mm input rating of all equipment in the room when the opening is communicating directly with the out­doors or through vertical duct(s). The total cross-sectional area shall be at least 1 in. area per 10,000 BTUH (222 mm input rating of all equipment in the room when the opening is communicating with the outdoors through horizontal duct(s).
3. In cold climates, and to mitigate potential freeze­up, Raypak highly recommends the installation of a motorized sealed damper to prevent the circula­tion of cold air through the heater during the non-operating hours.
2
per kW) of total
2
2
per kW) of total
of free
TruSeal™ Combustion Air
In addition to the 3 previous steps, combustion air may be ducted directly to the heater by using PVC, CPVC
Conventional Combustion Air Supply
U.S. Installations
All Air from Inside the Building
The confined space shall be provided with TWO per­manent openings communicating directly with an additional room(s) of sufficient volume so that the com­bined volume of all spaces meets the criteria for a room large in comparison (NFGC). The total input of all gas utilization equipment installed in the combined space shall be considered in making this determina­tion. Each opening shall have a minimum free area of 1 in.2per 1,000 BTUH (2,225 mm2per kW) of the total input rating of all gas utilization equipment in the con­fined space, but not less than 100 in.2(645 cm2). One opening shall commence within 12 in. (305 mm) of the top, and one opening shall commence within 12 in. (305 mm) of the bottom of the enclosure. The mini­mum dimension of air openings shall be not less than 3 in. (76 mm) in any direction.
All Air from Outdoors
The confined space shall communicate with the out­doors in accordance with one of the methods below. The minimum dimension of air openings shall not be less than 3 in. (76 mm) in any direction. Where ducts are used, they shall be of the same cross-sectional area as the net free area of the openings to which they connect.
1. Two permanent openings, one commencing
within 12 in. (305 mm) of the top, and one com­mencing within 12 in. (305 mm) of the bottom of
11
the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the
utdoors or spaces (crawl or attic) that freely com-
o municate with the outdoors.
a. Where directly communicating with the out-
oors or where communicating to the
d outdoors through vertical ducts, each open- ing shall have a minimum free area of 1 in. per 4,000 BTUH (550 mm2per kW) of total input rating of all equipment in the enclosure.
b. Where communicating with the outdoors
through horizontal ducts, each opening shall have a minimum free area of 1 in.2per 2,000 BTUH (1,100 mm2per kW) of total input rat­ing of all equipment in the enclosure.
2. One permanent opening, commencing within 12
in. (305 mm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (152 mm) from the front of the appliance. The opening shall directly communicate with the out­doors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors, and shall have a minimum free area of:
a. 1 in.2per 3,000 BTUH (740 mm2per kW) of
the total input rating of all equipment located in the enclosure, and
b. Not less than the sum of the areas of all vent
connectors in the confined space.
WARNING: Do not use the “one permanent opening” method if the equipment room is under negative pressure conditions.
Canadian Installations
CAUTION: All combustion air must be drawn from
outside of the building; the mechanical equipment room must communicate directly with the outdoors.
2. For heaters using a barometric damper in the vent system there shall be a permanent air supply
pening(s) having a cross section area of not less
o than 1 in.
2
per 7,000 BTUH (320 mm2per kW) up to and including 1 million BTUH, plus 1 in.2per 14,000 BTUH (160 mm2per kW) in excess of 1
illion BTUH. This opening(s) shall be either
m located at or ducted to a point not more than 18 in.
2
(450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down and terminated 18 in. (450 mm) from the floor, but not near piping. This air supply opening require­ment shall be in addition to the air opening for ventilation air required in 1. (above).
WARNING: Care must be taken to ensure that the equipment room is not under negative pressure conditions.
3. For heaters not using a barometric damper in the vent system, and when air supply is provided by natural air flow from outdoors for a power burner and there is no draft regulator, drafthood or similar flue gas dilution device installed in the same space, in addition to the opening for ventilation air required in 1., there shall be a permanent air sup­ply opening(s) having a total cross-sectional area
2
of not less than 1 in.
for each 30,000 BTUH (74 mm2per kW) of total rated input of the burner(s), and the location of the opening(s) shall not inter­fere with the intended purpose of the opening(s) for ventilation air referred to in 1. This opening(s) can be ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down 18 in. (450 mm) from the floor, but not near piping.
4. Refer to the B149 Installation Code for additional information.
Water Piping
1. Ventilation of the space occupied by the heater shall be provided by an opening(s) for ventilation air at the highest practical point communicating with the outdoors. The total cross-sectional area of such an opening(s) shall be at least 10% of the area required in 2. and 3. (below), but in no case shall the cross-sectional area be less than 10 in. (65 cm2).
General
The heater should be located so that any water leaks will not cause damage to the adjacent area or struc­tures.
2
NOTE: In lieu of installing the System Temp Sensor in the system return loop, an alternate system using a buffer tank (see Fig. 31) can be used for better sys­tem temperature control.
12
CAUTION: This heater requires forced water circulation when the burner is operating. See Table F and Table G for minimum and maximum flow rates and water pump selection. The pump must be interlocked with the heater to prevent heater
peration without water circulation.
o
feed valve. Test at standard operating pressure for at least 24 hours.
2. Make sure constant gauge pressure has been maintained throughout test.
. Check for leaks. Repair if found.
3
NOTE: Minimum pipe size for in/out connections is 2 in. NPT for 504 and 754 models and 2-1⁄2 in NPT for 1104–2004 models. Verify proper flow rates and ∆T as instructed in this manual.
Relief Valve Piping
WARNING: Pressure relief valve discharge piping
must be piped near the floor and close to a drain to eliminate the potential of severe burns. Do not pipe to any area where freezing could occur. Refer to local codes.
Temperature & Pressure Gauge
The temperature and pressure gauge is shipped loose for field installation and must be installed within 12 inches of the boiler outlet (if possible) in an easily readable location. Installation must comply with ASME Section IV as well as all applicable national, state and
local codes.
Hydrostatic Test
Unlike many types of heaters, this heater does not re­quire hydrostatic testing prior to being placed in operation. The heat exchanger has already been fac­tory-tested and is rated for 160 psi operating pressure. However, Raypak does recommend hydrostatic test­ing of the piping connections to the heater and the rest of the system prior to operation. This is particularly true for hydronic systems using expensive glycol­based anti-freeze. Raypak recommends conducting the hydrostatic test before connecting gas piping or electrical supply.
Leaks must be repaired at once to prevent damage to the heater. NEVER use petroleum-based stop-leak compounds.
To perform hydrostatic test:
1. Connect fill water supply. With bleed valve open, fill heater with water. When water flows from bleed valve, shut off water. Close bleed valve. Carefully fill the rest of the system, making sure to eliminate any entrapped air by using high-point vents. Close
Cold Water Operation
CAUTION: Damage due to internal condensation
may occur if the heater inlet water temperature does not exceed 120°F (49°C) within 7 minutes of start­up.
This heater is equipped with a proprietary condensate evaporation system which will evaporate any conden­sate that may begin to accumulate inside the primary heat exchanger with water temperatures as low as 120°F (49°C).
Heaters operated with an inlet temperature of less than 120°F (49°C) MUST have a manual bypass (see Fig. 16) or an approved low-temperature operation system (Figs. 9 and 10) to prevent problems with con­densation. This piping is similar to a primary/secondary boiler installation, with a bypass acting as the secondary boiler piping. Raypak strong­ly recommends that thermometer(s) be placed into the heater piping next to the in/out header to facilitate tem­perature adjustment. Inlet water temperatures below 120°F (49°C) can excessively cool the products of combustion, resulting in collection of condensate in the heat exchanger area beyond the capacity of the con­densate evaporation system.
Failure to reach or exceed 120°F (49°C) within 7 min­utes may damage or cause failure of the heat exchanger, combustion chamber, or other parts within the combustion chamber. It can cause operational problems, bad combustion, sooting, flue gas leakage and reduced service life of the appliance and the vent system. A bypass allows part of the heater discharge water to be mixed with the cooler water returning to the heater inlet to increase the heater inlet temperature above 120°F (49°C). This precautionary measure should prevent the products of combustion from con­densing beyond the ability of the condensate management system employed in this heater in most installations. Warranty claims will be denied for
damage or failures caused by condensation.
Cold water operation issues are applicable to both cold water start and cold water run applications. Cold water operation for 7 minutes or less on initial daily start-up is acceptable. Where cold water starts will last
13
longer than 7 minutes or where cold water operation is
*
*
continuous, provisions must be made to mix higher
emperature outlet water with the colder inlet water
t and thereby raise the inlet temperature to at least 120°F (49°C) within the 7-minute time limit.
Cold Water Starts
Cold water starts, where the inlet water temperature remains below 120°F (49°C) for more than 7 minutes,
have cold water start protection. Known pro-
must
tection methods consist of mixing heated outlet water with the inlet water using a bypass to raise the inlet to 120°F (49°C) or higher. Once the system is heated up and has return water temperatures of 120°F (49°C) or higher, the mixing of outlet water with inlet water is no longer needed and the bypass can be shut off. If the bypass is not shut off as the system heats up, the out­let temperature may continue to climb and trip the high limit, thereby shutting down the heater. Thus an auto­matic valve system, such as a three-way proportional valve or a modulating two-way valve to control the bypass, should be utilized.
and manually adjusted to achieve an inlet temperature of 120°F (49°C) or higher as adjusted at the minimum
emperature in this narrow temperature range (i.e.
t Range 75°F to 85°F – adjust bypass with temperature at 75°F (24°C)) so that when temperature is 85°F (29°C), minimum inlet temperature would be 130°F
54°C). An injector pump arrangement may also be uti-
( lized to keep the heater loop at or above 120°F (49°C). An injector pump approach has the added value of being able to adjust to changes in the system water coming back to the heater take-off.
*Maximum 4 times the pipe diameter or 12”, whichever is less.
Fig. 9: Cold Water Start
Cold Water Run
Cold water run differs from cold water start in that the system water entering the heater remains below 120°F (49°C) continuously. Typically, this is the case in swimming pool heating. If the system water is kept in a narrow temperature range of no more than 10°F (5°C), a permanent manual bypass can be employed
*Maximum 4 times the pipe diameter or 12”, whichever is less.
Fig. 10: Cold Water Run
Hydronic Heating
Pump Selection
In order to ensure proper performance of your heater system, you must install a correctly-sized pump. Ray­pak requires designing for a ∆T within the range of 10°F to 40°F (5°C to 20°C). See Table F for accept­able flow rates for each model (∆T is the temperature difference between the inlet and outlet water when the heater is firing at full rate).
Feedwater Regulator
Raypak recommends that a feedwater regulator be in­stalled and set at 12 psi minimum pressure at the highest point of the system. Install a check valve or back flow device upstream of the regulator, with a manual shut-off valve as required by local codes.
14
T
HERMOSTAT OR
S
YSTEM SENSOR
THERMOSTATOR SYSTEM SENSOR
Model
N
Input Output 20° ∆T 30° ∆T 40° ∆T Min. Flow Max. Flow
o.
MBTUH gpm ∆P gpm ∆P gpm ∆P gpm ∆P ∆T gpm ∆P ∆T
504 500 420 42 2.7 28 1.4 25 1.1 34 100 11.3 8
754 750 630 63 6.0 42 2.9 32 1.7 32 1.7 40 100 13.8 13
1104 1100 924 92 13.3 62 6.7 46 4.1 46 4.1 40 113 18.6 16
1504 1500 1260 84 13.3 63 8.0 63 8.0 40 113 22.2 22
2004 1999 1679 112 26.9 84 16.0 84 16.0 40 113 27.2 30
Note: Basis for minimum flow is ∆T. Basis for maximum flow is gpm.
Table F: Heater Rates of Flow and Pressure Drops
Piping
All high points should be vented. A heater installed above radiation level must be provided with a low wa­ter cut-off device (sales order option F-10). This heater, when used in connection with a refrigeration system, must be installed so that the chilled medium is piped in parallel with the heater with appropriate valves to pre-vent the chilled medium from entering the heater.
The piping system of a hot water heater connected to heating coils located in air handling units where they may be exposed to circulating refrigerated air, must be equipped with flow control valves or other automatic means to prevent gravity circulation of the heater water during the cooling cycle. It is highly recommend­ed that the piping be insulated.
Air-Separation/Expansion Tank
All heaters should be equipped with a properly sized expansion tank and air separator fitting as shown in Fig. 11.
*Maximum 4 times the pipe diameter or 12”, whichever is less.
Fig. 12: Single Heater - Low-Temperature (Heat Pump)
Application with Primary/Secondary Piping
Fig. 11: Air-Separation/Expansion Tank
*Maximum 4 times the pipe diameter or 12”, whichever is less.
Fig. 13: Dual Heaters (Reverse/Return)
with Primary/Secondary Piping
15
SYSTEM SUPPLY
S
YSTEM
RETURN
Three-Way Valves
Three-way valves intended to regulate system water temperatures by reducing flow in the boiler should not be used. Raypak heaters are high-recovery, low-mass
eaters which are not subject to thermal shock. See
h Fig. 16 and instructions on page 17 for adjusting the manual bypass.
Domestic Hot Water
NOTE: If local codes require a vacuum relief valve,
acquire one locally and install per valve manufacturer’s instructions.
Potable Water and Space Heating
CAUTION: When this heater is used for both
potable water and space heating, observe the following to ensure proper operation.
When designing the water piping system for domestic hot water applications, water hardness should be con­sidered. Table G indicates the suggested flow rates for soft, medium and hard water. Water hardness is ex­pressed in grains per gallon.
Fig. 14: Single Domestic Hot Water Heater and Storage
Tank
1. All piping materials and components connected to the water heater for the space heating application shall be suitable for use with potable water.
2. Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water used for space heating.
3. If the heater will be used to supply potable water, it shall not be connected to any heating system or components previously used with a non-potable water heating appliance.
4. When the system requires water for space heating at temperatures higher than 140°F (60°C), a means such as a mixing valve shall be installed to temper the water in order to reduce scald hazard potential.
Pool Heating
When a boiler or water heater is used in a pool heat­ing application, ensure that all the following installation requirements are met.
Model
No.
504 500 420 17 50 3.6 2 5.9 13 65 5.5 2 9.3 9 95 10.4 2 18.1
754 750 630 25 50 4.0 2 6.3 20 65 6.4 2 10.2 13 100 13.8 2 22.2
1104 1045 888 30 60 6.4 2-1/2 7.6 20 92 13.2 2-1/2 15.9 16 113 18.7 2-1/2 22.6
1504 1425 1211 30 82 12.7 2-1/2 14.9 22 113 22.3 2-1/2 26.3 22 113 22.3 2-1/2 26.3
2004 1900 1615 30 110 26.1 2-1/2 29.8 29 113 27.4 2-1/2 31.3 29 113 27.4 2-1/2 31.3
∆T = Temperature rise, °F ∆P = Pressure drop through heat exchanger, ft SHL = System head loss, ft (based on heater and tank placed no more than 5 ft apart and equivalent length of 50 eq ft of tubing) gpm = Gallons per minute, flow rate MTS = Minimum tubing size *Must utilize optional cupro-nickel tubes. If over 25 grains per gallon, a water softener/treatment system must be utilized. Caution: For scale free operation with "Hard Water" (16-25 grains per gallon of total hardness), the operating control must NOT be set higher than 130°F. For higher than 130°F operation, a water softener/treatment system must be utilized.
MBTUH Soft (0-4 grains per gallon) Medium (5-15 grains per gallon) Hard* (16-25 grains per gallon)
Input Output ∆T gpm ∆P MTS SHL ∆T gpm ∆P MTS SHL ∆T gpm ∆P MTS SHL
Table G: Domestic Water Heater Flow Rate Requirements
16
The MVB must be equipped with a field-supplied ex-
*
POOL
THERMOSTAT
FROM
FILTER
TO POOL
C
HEMICAL
FEED
ternal pump and bypass arrangement. This arrangement blends outlet water with the inlet water to
ncrease the inlet water temperature to a minimum of
i 105°F (40°C) for Pool Heater (P and WHP) versions
nd 120°F (49°C) for Hydronic Heating (H7) or
a Domestic Hot Water (WH1) versions, thereby reducing the likelihood of condensation forming on the heat exchanger. The pump also serves to circulate water through the heater from the main system piping.
CAUTION: Power to the heater should be interlocked with the main system pump to make sure the heater does not fire without the main system pump in operation. Improper flow control can damage the heater. Uncontrolled flow (too high) or restricted flow (too low) can seriously damage the heater. Follow these instructions to make sure your heater is properly installed.
To complete the installation of the pool heater, the pool thermostat must be installed in the main return water line, upstream of the heater. This will ensure that the heater will be energized at the right time.
1. Turn on pump.
2. Turn on heater and wait until heater goes to full ire.
f
. With the heater operating at 100% firing rate, set
3
Valve A (the bypass) to
1
2 open position, and Valve
B to fully open position. See Fig. 16.
4. Adjust Valve A until the inlet water temperature is
105°F (40°C) or 120°F (49°C) depending upon heater type.
NOTE: Opening the valve will increase the temperature and closing the valve will decrease the temperature.
5. If this process does not raise the inlet water tem-
perature to 105°F (40°C) for Pool Heater (P and WHP) versions and 120°F (49°C) for Hydronic Heating (H7) or Domestic Hot Water (WH1) ver­sions and Valve A is fully open, then slowly throttle Valve B closed to increase the inlet water temper­ature to the required temperature.
*Maximum 4 times the pipe diameter or 12”, whichever is less.
Fig. 15: Single Pool Heater Application
Adjustment of the manual bypass valve is critical to proper operation of the heater. The manual bypass valve should be adjusted to achieve a minimum inlet water temperature of 105°F (40°C) for Pool Heater (P and WHP) versions and 120°F (49°C) for Hydronic Heating (H7) or Domestic Hot Water (WH1) versions and a system supply water temperature below 140°F (60°C). When starting with a cold pool, make initial adjustments. Make final adjustments when pool water approaches desired temperature.
The use of a bypass is required for proper operation in a pool heating application. Use the following instruc­tions to set the manual bypass:
Fig. 16: “H” Bypass Setting
17
Loading...
+ 39 hidden pages