Low NOx Models 207A, 266L,
267A, 337A, 399L, and 407A
WARNING: If the information is not followed exactly, a re or explosion may result causing property
damage, personal injury or death.
— Do not store or use gasoline or other flammable vapors and liquids or other combustible materials
in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future
reference.
Pressure relief valve: See page 17 for recommended
PRV orientation.
Flow rates: See page 15 for ow rate values.
GAS
Distance to regulator (pipe lengths) and gas inlet
sizes: See page 14.
Required pressure for Natural Gas:
Min = 5" WC, Max = 10.5" WC
Sediment trap is required for all installations:
See page 13.
WATER CHEMISTRY
Water chemistry requirements: See page 5.
POWER
Supply voltage: See page 20 for acceptable input
voltages.
VENTING
Materials: See pages 8, 10 and 12.
D-2 Power Vent Kit: See page 12.
Indoor Stack kit: See page 9.
CONTROLS INTERFACE
Wiring diagram: See page 21.
User interface: See page 22.
Remote operation: See page 26.
Revision 1 reects the following changes:
Added model 266L, 399L to tables D, E, F, G, H, I, J, K, gure 7, and parts list. Removed Model Identication section. Amended text
in gures 27, 28, and wiring diagram.
Digital - Flow Chart................................................ 36
Control Logic - Flow Chart .................................... 37
11. REPLACEMENT PARTS ..................................... 38
12. ILLUSTRATED PARTS LIST .............................. 39
3
1. WARNINGS
Pay Attention to These Terms
DANGER
AA
WARNING
AA
CAUTION
AA
CAUTION
NOTE
DANGER: Failure to install the drafthood on indoor
AA
installation and properly vent the heater to the outdoors
as outlined in the venting section of this manual can
result in unsafe operation of the heater. To avoid the risk
of re, explosion, or asphyxiation from carbon monoxide,
never operate this heater unless it is properly vented
and has an adequate air supply for proper operation. Be
sure to inspect the vent system for proper installation at
initial start-up, and at least annually thereafter. Refer to
the venting section of this manual for more information
regarding vent system inspections.
Indicates the presence of immediate hazards which will cause severe personal injury, death or
substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause severe personal injury,
death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause minor personal injury
or product or property damage if ignored.
CAUTION used without the warning alert symbol indicates a potentially hazardous condition
which could cause minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which are important but
not related to personal injury hazards.
WARNING: Improper installation, adjustment,
AA
alteration, service, or maintenance can cause property
damage, personal injury or loss of life. Installation
and service must be performed by a qualied installer,
service agency, or the gas supplier.
WARNING: Gasoline, as well as other ammable
AA
materials and liquids (adhesives, solvents, etc.), and
the vapors they produce, are extremely dangerous. Do
not handle, use, or store gasoline or other ammable or
combustible materials in the vicinity of a heater.
WARNING: To minimize the possibility of improper
AA
operation, serious personal injury, re, or damage to the
heater:
• Always keep the area around the heater free of
combustible materials, gasoline, and other ammable
liquids and vapors.
• Heater should never be covered or have any blockage
to the ow of fresh air to the heater.
WARNING: This unit contains refractory ceramic
AA
ber (RCF) insulation in the combustion chamber. RCF,
as manufactured, does not contain respirable crystalline
silica. However, following sustained exposure to very
high temperatures [greater than 2192°F (1200°C)], the
RCF can transform into crystalline silica (cristabolite).
The International Agency for Research on Cancer
(IARC) has classied the inhalation of crystalline silica
(cristabolite) as carcinogenic to humans.
When removing the burners or heat exchangers, take
precautions to avoid creating airborne dust and avoid
inhaling airborne bers. When cleaning spills, use wet
sweeping or High Eciency Particulate Air (HEPA)
ltered vacuum to minimize airborne dust. Use feasible
engineering controls such as local exhaust ventilation
or dust collecting systems to minimize airborne dust.
Wear appropriate personal protective equipment
including gloves, safety glasses with side shields, and
appropriate NIOSH certied respiratory protection,
to avoid inhalation of airborne dust and airborne ber
particles.
WARNING: Both natural gas and propane have
AA
an odorant added to aid in detecting a gas leak. Some
people may not physically be able to smell or recognize
this odorant. If you are unsure or unfamiliar with the
smell of natural gas or propane, ask your local gas
supplier. Other conditions, such as “odorant fade,”
which causes the odorant to diminish in intensity, can
also hide, camouage, or otherwise make detecting a
gas leak by smell more dicult.
WARNING: UL-recognized fuel gas detectors are
AA
recommended in all enclosed propane and natural
gas applications wherein there is a potential for an
explosive mixture of fuel gas to accumulate and their
installation should be in accordance with the detector
manufacturer’s recommendations and/or local laws,
rules, regulations, or customs.
WARNING: Do not install within 3 feet (0.9 m) of
AA
a heat pump or an outdoor condensing unit. Strong
air intake from this type of equipment can disturb the
combustion process and cause damage or personal
injury.
WARNING: The heater shall not be located in an
AA
area where water sprinklers, or other devices, may cause
water to spray through the cabinet louvers and into the
heater. This could cause internal rusting or damage
electrical components, and void the warranty.
4
CAUTION: Elevated water temperature can be
AA
hazardous. The U.S. Consumer Product Safety
Commission has these guidelines:
1. Spa water temperatures should never exceed
104°F (40°C). A temperature of 100°F (38°C) is
considered safe for a healthy adult. Special caution
is suggested for young children.
2. Drinking of alcoholic beverages before or during spa
or hot tub use can cause drowsiness which could
lead to unconsciousness and subsequently result in
drowning.
3. Pregnant Women Beware! Soaking in water over
102°F (39°C) can cause fetal damage during the rst
three months of pregnancy resulting in the birth of a
brain-damaged or deformed child. Pregnant women
should stick to the 100°F (38°C) maximum rule.
4. Before entering the spa or hot tub, users should
check the water temperature with an accurate
thermometer; spa or hot tub thermostats may err
in regulating water temperatures by as much as 4°F
(2.2°C).
5. Persons with a medical history of heart disease,
circulatory problems, diabetes, or blood pressure
problems should obtain a physician’s advice before
using pools or hot tubs.
6. Persons taking medications which induce
drowsiness, such as tranquilizers, antihistamines,
or anticoagulants, should not use spas or hot tubs
.
2. WATER CHEMISTRY
NOTE: Corrosive water voids all warranties.
Chemical imbalance can cause severe damage to your
heater and associated equipment. Maintain your water
chemistry according to Table A. If the mineral content
and dissolved solids in the water become too high, scale
forms inside the heat exchanger tubes, reducing heater
eciency and damaging the heater. If the pH drops below
7.2, this will cause corrosion of the heat exchanger and
severely damage the heater. Heat exchanger damage
resulting from chemical imbalance is not covered by
the warranty.
For your health and the protection of your pool equipment,
it is essential that your water be chemically balanced. The
following levels must be used as a guide for balanced
water.
CAUTION: Free chlorine must not exceed 5 ppm
AA
which can damage the heater and is not covered under
warranty.
• Occasional chemical shock dosing of the pool or spa
water should not damage the heater providing the
water is balanced.
• Automatic chemical dosing devices and salt
chlorinators are usually more efficient in heated
water, unless controlled, they can lead to excessive
chlorine level which can damage your heater.
• Check valve should be installed between the heater
outlet and a chlorinator or other chemical dosing
device.
• Further advice should be obtained from your pool
or spa builder, accredited pool shop, or chemical
supplier for the correct levels for your water.
Automatic Chlorinators
and Chemical Feeders
All chemicals must be introduced and completely diluted
into the pool or spa water before being circulated through
the heater. Do not place sanitizing chemicals in the
skimmer. High chemical concentrations will result when
the pump is not running (e.g. overnight).
Chlorinators must feed downstream of the heater and
have an anti-siphoning device to prevent chemical backup
into the heater when the pump is shut o.
See "Plumbing Diagram" on page 18.
NOTE: High chemical concentrates from feeders and
chlorinators that are out of adjustment will cause rapid
corrosion to the heat exchanger. Such damage is not
covered under the warranty.
Recommended Level(s)Fiberglass PoolsFiberglass SpasOther Pool and Spa Types
Water Temperature68-88°F (20-31°C)89-104°F (31-40°C)68-104°F (20-40°C)
pH7.3-7.47.3-7.47.6-7.8
Total Alkalinity (ppm)120-150120-15080-120
Calcium Hardness (ppm)200-300150-200200-400
Salt (ppm)4500 Maximum4500 Maximum4500 Maximum
Free Chlorine (ppm)*2-32-32-3
Total Dissolved Solids (ppm)3000 Maximum**3000 Maximum**3000 Maximum**
*Free Chlorine MUST NOT EXCEED 5 ppm!
**In saltwater chlorinated pools, the total TDS can be as high as 6000 ppm.
Table A. Pool Water Chemistry
5
3. BEFORE INSTALLATION
Receiving equipment
The manufacturer recommends that this manual be
reviewed thoroughly before installing the pool/spa heater. If
there are any questions that this manual does not answer,
please contact the factory or your local representative.
On receipt of your equipment it is suggested that you
visually check for external damage to the carton. If the
carton is damaged, a note should be made on the Bill
of Lading when signing for the equipment. Remove the
heater from the carton. If it is damaged, report the damage
to the carrier immediately. Save the carton.
These items are shipped inside a box in the carton with
the heater:
Standard Unit (POLYMER HEADERS)
1. “Pagoda” top
2. 2" CPVC union half with "O" rings (2)
3. Plastic pipe finish flange for gas line
4. Bonding lug with mounting screw
ASME Unit (BRASS HEADERS)
1. “Pagoda” top
2. 2" CPVC union half with "O" rings (2)
3. Plastic pipe finish flange for gas line
4. Bonding lug with mounting screw
5. Pressure Relief Valve
6. ProTek Shield Adapter with ProTek Shield Assembly
and wing nut
THE MODEL AND SERIAL NO.
CAN ALSO BE FOUND INSIDE
THE BEZEL ABOVE THE DISPLAY
Be sure that you receive the number of packages indicated
on the Bill of Lading.
Rating and certications
These heaters are design-certied and tested under the
latest requirements of the ANSI Z21.56 / CSA 4.7 Standard
for Gas-Fired Pool Heaters. All heaters can be used either
indoor or outdoors when appropriate venting is installed.
The appropriate top designated for each type of use is
required. If necessary, the top can be changed at a later
date to change from outdoor to indoor or vice versa.
Elevation
Rated inputs are suitable for up to 5,000 feet (1524 m)
elevation. For elevations above 5,000 feet (1524 m),
consult the factory.
Ambient Temperature Rating
Heater Components
Electronic Ignition Heater* -32°F to 175°F (-35°C to 79°C)
*Requires 120 or 240VAC, 1 Ph, 60 Hz Power Supply
4. INSTALLATION
WARNING: This unit contains refractory ceramic
AA
ber (RCF) insulation in the combustion chamber. RCF,
as manufactured, does not contain respirable crystalline
silica. However, following sustained exposure to very
high temperatures (>2192°F), the RCF can transform
into crystalline silica (cristabolite). The International
Agency for Research on Cancer (IARC) has classied
the inhalation of crystalline silica (cristabolite) as
carcinogenic to humans.
When removing the burners or heat exchangers, take
precautions to avoid creating airborne dust and avoid
inhaling airborne bers. When cleaning spills, use wet
sweeping or High Eciency Particulate Air (HEPA)
ltered vacuum to minimize airborne dust. Use feasible
engineering controls such as local exhaust ventilation
or dust collecting systems to minimize airborne dust.
Wear appropriate personal protective equipment
including gloves, safety glasses with side shields, and
appropriate NIOSH certied respiratory protection,
to avoid inhalation of airborne dust and airborne ber
particles.
MODEL AND SERIAL NO.
LOCATED ON RATING PLATE
Figure 1. Rating Plate Location
6
F10639-1
IMPORTANT NOTICE: These instructions are intended
only for the use by qualied personnel, specically
trained and experienced in the installation of this type
of heating equipment and related system components.
Installation and service personnel may be required by
some states to be licensed. If your state is such, be sure
your contractor bears the appropriate license. Persons
not qualied shall not attempt to x the equipment nor
attempt repairs according to these instructions.
WARNING: Improper installation, adjustment,
AA
alteration, service or maintenance may damage the
equipment, create a hazard resulting in asphyxiation,
explosion or re, and will void the warranty.
NOTE: The heater should not be located in an area
where possible water leakage will result in damage to
the area adjacent to the heater or to the structure. When
such locations cannot be avoided, it is recommended
that a suitable drain pan, with adequate drainage, be
installed under the heater. The pan must not restrict
combustion air ow.
Installation Codes
Installation must be in accordance with local codes, or,
in the absence of local codes, with the latest edition of
the National Fuel Gas Code, ANSI Z223.1/NFPA54 and
National Electrical Code, ANSI/NFPA 70, and for Canada,
the latest edition of CAN/CSA-B149 Installation Codes,
and Canadian Electrical Code, CSA C22.1 Part 1 and
Part 2.
Clearances
All Heaters
For indoor and outdoor clearances from combustible
surfaces, see the chart below.
LocationIndoor Installation
Top *30" (762 mm) Drafthood
FrontAlcove (Open)
Vent6" (152 mm)
Floor **0"
Back6" (152 mm)
Right Side12" (305 mm) Water Side
Left Side6" (152 mm) Opposite Water Side
When installed according to the listed minimum clearances
from combustible construction, the pool heater can still be
serviced without removing permanent construction around
the heater.
However for ease of servicing, we recommend a clearance
of at least 24" (610 mm) in the front, and at least 18"
(457 mm) on the water connection side. This will enable
the heater to be serviced in its installed location, that is,
without movement or removal of the heater.
Clearances less than these may require removal of the
heater to service either the heat exchanger or the burner
tray. In either case, the heater must be installed in a
manner that will enable the heater to be serviced without
removing any structure around the heater.
Flooring
This heater can be installed on combustible ooring.
The combustible clearances listed can be reduced by
protecting the exposed combustible surfaces as shown in
Table C.
Outdoor Heater Installation
These heaters are design-certied for outdoor installation,
when equipped with the approved tops designated for
outdoor use.
WARNING: The heater shall not be located in an
AA
area where water sprinklers, or other devices, may cause
water to spray through the cabinet louvers and into the
heater. This could cause internal rusting or damage
electrical components, and void the warranty.
WARNING: Do not install within 3' (0.9 m) of a heat
AA
pump or an outdoor condensing unit. Strong air intake
from this type of equipment can disturb the combustion
process and cause damage or personal injury.
PAGODA TOP
INSTALLATION
LocationOutdoor Installation
Top *Unobstructed (Outdoor Stack)
Top ***36" (914 mm) (Stackless Top)
Floor0"
Back6" (152 mm)
Right Side12" (305 mm) Water Side
Left Side6" (152 mm) Opposite Water Side
* Clearance from top of vent terminal
** Do not install on carpeting
*** Clearance from top of heater
Table B. Minimum Clearances from Combustible Surfaces
F10647-2
Figure 2. Heater with Outdoor Stackless Top
7
DescriptionLocation
Back9 (229)
a. 3-1/2" (89 mm) thick
masonry walls without
ventilated air space
b. 1/2" (13 mm)insulation
board over 1" (25 mm)
glass ber or mineral
wool batts
c. 0.024 sheet metal over
1" (25 mm) glass ber
or mineral wool batts
reinforced with wire on
rear face with ventilated
air space
d. 3-1/2" (89 mm) thick
masonry wall with
ventilated air space
e. 0.024 sheet metal with
ventilated air space
f. 1/2" (13 mm) thick
insulation board with
ventilated air space
g. 0.024 sheet metal with
ventilated air space over
0.024 sheet metal with
ventilated air space.
h. 1" (25 mm) glass ber
or mineral wool batts
sandwiched between two
sheets 0.024 sheet metal
with ventilated air space
Derived from National Fuel Gas Code, Table 10.2.3
Table C. Reduction of Clearances to Protected Surfaces
Heaters must not be installed under an overhang of less
than three 3' (0.9 m) from the top of the heater. Three sides
must be open in the area under the overhang. Roof water
drainage must be diverted away from the heaters installed
under overhangs with the use of gutters.
For U.S. installations, the point from where the ue
products exit the heater must be a minimum of 4' (1.2 m)
below, 4' (1.2 m) horizontally from, or 1' (0.3 m) above any
door, window or gravity inlet into any building. The top
surface of the heater shall be at least 3' (0.9 m) above
any forced air inlet, or intake ducts located within 10' (3 m)
horizontally.
For Canadian installations, pool heaters shall not be
installed with the top of the vent assembly within 10' (3 m)
below, or to either side, of any opening into the building.
Refer to the latest revisions of CAN/CSA-B149.
A minimum of 6' (1.8 m) is required from the heater to an
inside corner wall for proper outdoor venting.
For installations in Florida and Texas, that must comply
with the Florida or Texas Building Code, follow the directions
shown in Figure 7 for the installation of hurricane tie-down
brackets for all models.
4' (1.2 m)
Minimum
4' (1.2 m)
Minimum
4' (1.2 m)
Minimum
3' (0.9 m)
Minimum
10' (3 m)
Minimum
Forced Air Inlet
Figure 3. Clearances
1' (0.3 m)
Minimum
Pagoda Top Installation
1. Insert tabs into keyhole (4 places). See Figure 4,
detail A.
2. Snap tabs into keyholes so as not to pull out. See
Figure 4, detail B.
DETAIL ADETAIL B
OUTDOOR TOP
(SHIPPED LOOSE WITH HEATER)
Figure 4. Outdoor Top Installation
Indoor Heater Installation
The heater is also design-certied for indoor installation
when equipped with the approved drafthood.
8
For Canada, indoor installation is restricted to an enclosure
that is not occupied and does not directly communicate
with an occupied area. Refer to the latest edition of CAN/
CSA-B149 for specic requirements. Locate heater as
close as is practical to a chimney or gas vent. Heater
must always be vented to the outside. See section "Vent Piping" on page 12 for details. Minimum allowable
space is shown on the nameplate.
WARNING: Indoor heaters require a drafthood that
AA
must be connected to a vent pipe and properly vented to
the outside. Failure to follow this procedure can cause
re or fatal carbon monoxide poisoning.
Outdoor and Indoor Stacks
The outdoor and indoor stacks are optional equipment
and do not come standard with the heater. Refer to
installation instructions inside box for instructions on
how to install outdoor/indoor stack.
Model
207A009834009838
266L/267A009835009839
337A009836009840
399L/407A 009837009841
Table D. Outdoor and Indoor Stack Kit Number
Outdoor StackIndoor Stack
Part NoPart No.
or Canada CAN/CSA-B149) and any local codes that
may have jurisdiction. The most common approach is
the "2-opening" method, with combustion air opening no
more than 12" from the oor and the ventilation opening
no more than 12" from the ceiling. For opening sizes using
this method, see below.
All Air from Inside the Building:
Each opening shall have a minimum net free area as
noted:
ModelSq. in. (m2)
207A200 (0.13)
266L/267A266 (0.17)
337A333 (0.21)
399L/407A399 (0.26)
Table E. Opening Minimum Net Free Requirements -
Indoor Air
All Air from Outdoors:
When air is supplied directly from outside the building, each
opening shall have a minimum net free area as noted:
Model
Unrestricted
Opening
sq. in. (m²)
Typical Screened
or Louvered
Opening
sq. in. (m²)
Typical Screened
and Louvered
Opening
sq. in. (m²)
NOTE: The outdoor drafthood kit does not require any
additional vent pipe for proper operation. This drafthood
functions as the vent termination.
Combustion and Ventilation Air
Indoor Units Only
The heater must have both combustion and ventilation
air. The minimum requirements are listed in the latest
edition of the National Fuel Gas Code (U.S. ANSI Z223.1
OUTDOOR STACK KIT
(1) Outdoor stack, painted
(1) Adapter plate
(3) Mounting brackets (clips)
(1) Top panel cover
(2) 1-foot sections of metal tape
(3) Screws
(1) Instructions
Clips
207A50 (0.03)75 (0.05)100 (0.1)
266L/267A67 (0.04)101 (0.06)134 (0.09)
337A84 (0.05)126 (0.08)168 (0.11)
399L/407A100 (0.06)150 (0.1)200 (0.13)
Table F. Opening Minimum Net Free Requirements -
Outdoor Air
CAUTION: Combustion air must not be contaminated
AA
by corrosive chemical fumes which can damage the
heater. Such damage will not be covered by the warranty
INDOOR STACK KIT
(1) Drafthood, unpainted
(1) Adapter plate
(3) Mounting brackets (clips)
(3) Screws
(1) Instructions
Figure 5. Outdoor Stack Kit Components
Clips
Figure 6. Indoor Stack Kit Components
9
Min. Edge
Florida and Texas Building Code:
Wind Speed = 150 mph 3 sec gust
Exposure = C
B
Model
B
in. (mm)
207A20 (508)
266L/267A23 (584)
337A26 (660)
399L/407A29 (737)
2" x 6" x 1/8" Pallet
Anchor Bracket (4 Total) (Kit# 011636)
31-13/16"
(792 mm)
F10649
28"
(709 mm)
3" (76 mm)
Min. Conc.
Pad by others
1/4" x 1-3/4" S.S.
Tapcon Bolt and Washer (Field-Supplied)
NOTE: Use hole closest to unit with
washer overlapping edge of unit.
Distance
6"
(152 mm)
Min. Edge
Distance
6"
(152 mm)
(1)–1/4" x 1-3/4" S.S. Tapcon
Bolt & Washer (Field-Supplied)
Ea. Pallet Anchor Bracket
Use hole closest to unit (4 total)
*Note: For outdoor stack, use J dimension in the table below for appropriate size plus 6" (152 mm).
(B)
Flue
Dia.
in.
(mm)
(C)
Indoor
Drafthood
in. (mm)
55-5/8
(1413)
56
(1422)
57
(1448)
(D)
in. (mm)
10.0
(254)
11.5
(292)
13.0
(330)
(J)*
in. (mm)
11-3/4
(298)
11
(279)
10-5/8
(270)
Gas
Conn.
in.
3/42
3/42
3/42
Water
Conn.
in.
Heater
Model
207A
266L
267A
337A
BTUH
Input
(000)
(kw)
199.5
(58.4)
266.0
(77.9)
332.5
(97.4)
(A)
Cabinet
Width
in. (mm)
20
(508)6 (152)
23
(584)7 (178)
26
(660)8(203)
399L
407A
399
(116.9)
29
(737)9 (229)
58-1/2
(1486)
14.5
(368)
12-1/2
(318)
3/42
28"
Figure 9. Side View
Shipping Weights - lbs (kg)
Standard
Heater
w/Stackless
w/Stackless
Top
174
(79)
197
(89)
219
(99)
237
(108)
ASME
Heater
Top
193
(88)
N/A
216
(98)
238
(108)
N/A
256
(116)
Indoor
Draft-
hood
14
(6.4)
16
(7.3)
19
(8.6)
21
(9.5)
Table G. Heater Specications and Dimensions
11
Vent Piping
WARNING: Indoor heaters require a drafthood that
AA
must be connected to a vent pipe and properly vented to
the outside. Failure to follow this procedure can cause
re or fatal carbon monoxide poisoning.
Flue materials must be certied to CATEGORY I or
better. Type “B” double-wall or equivalent vent pipe is
recommended. A draft of -0.01" to -0.08" WC must be
maintained. However single-wall metal vent pipe may be
used as specied in the latest edition of the National Flue
Gas Code, ANSI Z223.1 (Canada - CAN/CSA-B149).
When properly installed outdoors, only the outdoor
stackless top, provided, is required. If installed indoors,
a drafthood is required, connected to a CATEGORY
I (a heater that operates with a non-positive vent static
pressure and a vent gas temperature that avoids excessive
condensate production in the vent) vent per the National
Fuel Gas Code and local requirements.
Vent piping the same size as the drafthood outlet is
recommended, however, when the total vent height is at
least 10 ft (3 m) (drafthood relief opening to vent terminal),
the vent pipe size may be reduced by no more than one
size as specied in Chapter 13 of the National Fuel Gas
Code, ANSI Z223.1 (Canada - CAN/CSA-B149).
As much as possible, avoid long horizontal runs of vent
pipe and too many elbows. If installation requires horizontal
runs, the vent pipe must have a minimum of 1/4 in. per ft
rise (20.8 mm per meter rise) and should be supported at
not more than 5 ft (1.5 m) intervals.
Plumber's tape, criss-crossed, will serve to space both
horizontal and vertical piping. Gas vents supported only
by the ashing and extending above the roof more than 5
ft (1.5 m) should be securely guyed or braced to withstand
snow and wind loads. We recommend use of insulated
vent pipe spacers through the roof and walls.
D-2 Power Vent Kit
Another option for an installation that requires horizontal
runs is using the D-2 power vent kit option.
Model120 VAC P/N240 VAC P/N
207A010744009832
266L/267A010744009832
337A010745009833
399L/407A010745009833
Table H. Power Vent Kit Part Numbers
NOTE: The D-2 Power Vent operates with a positive vent
static pressure and with a vent gas temperature that
prevents excessive condensate production in the vent,
and as such, is a CATEGORY III appliance. For more
information consult the D-2 Power Vent manual, Catalog
no 6000.57.1. CATEGORY I vent material such as B-vent
must not be used under CATEGORY III conditions.
For protection against rain or blockage by snow, the vent
pipe must terminate with a vent cap which complies with
the local codes or, in the absence of such codes, to the
latest edition of the National Fuel Gas Code, ANSI Z223.1
(Canada - CAN/CSA-B149).
The discharge opening must be a minimum of 2' (0.6
m) vertically from the roof surface and at least 2' (0.6 m)
higher than any part of the building within 8' (2.4 m). Vent
stack shall be at least 5' (1.5 m) in vertical height above
the drafthood outlet. The vent cap location shall have a
minimum clearance of 4' (1.2 m) horizontally from, and in
no case below, unless a 4' (1.2 m) horizontal distance is
maintained, from electric meters, gas meters, regulators
and relief equipment.
The weight of the vent stack or chimney must not rest on the
heater drafthood. Support must be provided in compliance
with applicable codes. The heater top and drafthood must
be readily removable for maintenance and inspection.
Vent pipe should be adequately supported to maintain
proper clearances from combustible construction.
Figure 10. D-2 Power Vent Option
The power vent system is a fan-assisted vent system
designed for application used on models 207A-407A.
The power vent system, when installed as directed, is
capable of operating in applications such as through-thewall venting with reduced horizontal and vertical vent pipe
sizes in new and current installations. The unit is factorywired for 240 VAC, with capability of eld-rewiring for 120
VAC.
For more information consult the D-2 Power Vent manual,
(Catalog No. 6000.57.1).
12
F10639-4
8' (2.4 m)
OR LESS
2' MIN
(0.6 m)
VENT PIPE
DRAFT HOOD
HEATER
VENT CAP
2' MIN
(0.6 m)
5' MIN
(1.5 m)
Figure 11. Venting Clearances
NOTE: With venting application of two or more heaters,
contact the factory.
CAUTION: The heater and its manual shut-o valve
AA
must be disconnected from the gas supply during any
pressure testing of that system at test pressures in
excess of 1/2 psi (3.45 kPa). Dissipate test pressure in
the gas supply line before reconnecting the heater and
its manual shut o valve to gas supply line. FAILURE
TO FOLLOW THIS PROCEDURE MAY DAMAGE THE
GAS VALVE. OVER PRESSURIZED GAS VALVES ARE
NOT COVERED BY WARRANTY. The heater and its gas
connections shall be leak tested before placing the
appliance in operation. Use soapy water for leak test. DO
NOT use open ame.
Supply Pressure
CAUTION: Do not use teon tape on gas line pipe
AA
thread. Only sealant tape or a pipe compound rated for
use with natural and propane gases is recommended.
Apply sparingly only on male pipe ends, leaving the two
end threads bare.
A minimum of 5 in. WC and a maximum of 10.5 in. WC
upstream pressure under load and no-load conditions
must be provided for natural gas.
Gas Pressure Regulator
The gas pressure regulator is preset at 3.1 in. WC for
natural gas. The pressure at the gas valve, taken with a
manometer, should be about 3.1 in. WC natural gas. If an
adjustment is needed, remove seal and turn adjustment
screw clockwise
clockwise to decrease pressure.
to increase pressure or counter-
Gas Supply Connections
HEATER JACKET
GAS INLET
3" MIN
(76 mm)
Typical
Figure 12. Gas Supply Plumbing
Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-o valve located
outside the heater jacket. All gas piping should be tested
after installation in accordance with local codes.
MANUAL
SHUT-OFF
VALV E
(Field supplied)
FINISH FLANGE
UNION
(Field supplied)
SEDIMENT TRAP
(Field supplied)
GAS VALVE
MANUAL
SHUT-OFF
VALV E
UNION
Figure 13. Manual Shut-O Valve Installation
13
Gas Pressure Adjustment Locations
F10638-1
Gas Pressure Adjustment
Figure 14. Honeywell VR8340
Pipe Sizing for Gas Connection
The capacities shown below are based on using SCH
40 black iron pipe. For capacities using other materials,
consult local codes.
Maximum Equivalent Pipe Length (ft) (m)
3
Natural Gas 1000 BTU/FT
WC Pressure Drop
Model3/4"1"1-1/4"1-1/2"
207A25 (7.6)90 (27.4) 360 (109.7)n/a
266L/267A 15 (4.6) 50 (15.2)210 (64.0)445 (135.6)
337A10 (3.0)30 (9.1)140 (42.7)290 (88.4)
0.60 Specic Gravity @ 0.5 in.
Figure 15. Polymer Headers Water Flow
F10637-1
Figure 16. Brass Headers (ASME) Water Flow
399L/407A*20 (6.1)95 (29.0)215 (65.5)
* A 3/4" gas line can be used for up to 5' (1.5 m) maximum length from the gas
valve in addition to the sediment trap.
Table I. Gas Pipe Sizing
Flow Rates
ModelPipe SizeMin. GPM (lpm) Max. GPM (lpm)
207A1-1/4"–1-1/2"–2" 20 (75)125 (473)
266L/267A1-1/4"–1-1/2"–2" 25 (95)125 (473)
337A1-1/4"–1-1/2"–2" 35 (132)125 (473)
399L/407A1-1/4"–1-1/2"–2" 40 (151)125 (473)
* When ow rates exceed maximum GPM an external auxiliary bypass valve is
required. See external bypass valve section for details.
Heater must be located so that any water leaks will not
damage the structure of adjacent area. Before attaching
the ProTek Shield Adapter to the inlet connection and the
2-inch unions, make sure the O-rings are properly seated
in the grooves. Use Aqualube or equivalent non-petroleumbased lubricant on the O-ring. Hand tighten the unions.
Glue PVC piping directly to the unions.
60 (227)TBDTBDTBDTBD
70 (265)TBDTBDTBDTBD
80 (303)TBDTBDTBDTBD
90 (340)TBDTBDTBDTBD
100 (378)TBDTBDTBDTBD
Table L. Brass Heat Exchanger Pressure Drop - ASME
Models - UG Fully Open
NOTE: Table capacity is based on Schedule 40 black
iron pipe. For capacity using other material, consult
local codes.
Polymer Headers (Residential Models)
Before attaching the 2-inch unions to the inlet/outlet
header, make sure the O-rings are properly seated in
the grooves. Use Aqualube or equivalent non-petroleumbased lubricant on the O-ring. Hand tighten the unions.
Glue PVC piping directly to the unions.
O-RING
HEADER FLANGE
(CPVC)
PLUMBING
PROTEK
SHIELD
ASSY
HEADER FLANGE NUT
(CPVC)
F10641
HEADER FLANGE
(CPVC)
HEADER FLANGE NUT
(CPVC)
HEADER
PROTEK SHIELD
ASSEMBLY
PLUMBING
Figure 18. Inlet/Outlet Header – Brass
NOTE: Some jurisdictions require the addition of a ow
switch on ASME installations. Kit # TBD can be ordered
that will allow a standard ASME unit to comply with the
code requirements.
ProTek Shield Assembly
This heater is equipped with a ProTek Shield Assembly
(located under the inlet connection on polymer headers
and in the ProTek Shield Adapter assembly shipped loose
in the accessory carton for eld installation on brass ASME
headers).
This component provides protection to the heat exchanger
against galvanic corrosion, when properly bonded to the
heat exchanger. It should be replaced when the weight of
the ProTek Shield is reduced to about 40% of the original
weight (1.46 #).
Figure 17. Inlet/Outlet Header – Polymer
High temperature CPVC header anges and header
ange nuts are provided. If there is any possibility of backsiphoning when the pump stops, it is suggested that a
check valve (or valves) also be installed in the system.
F10715
Figure 19. ProTek Shield Assy
15
CAUTION: STOP the pool pump before attempting
F10642-2
F10642-1
BYPASS DISC
AA
to remove ProTek Shield Assembly. Failure to do so may
result in damage to ProTek Shield Assy, loss of pool
water, or personal injury.
CAUTION: Do not use tools to remove (twist) the
ProTek Shield Assy or the wing nut on the stud of the
ProTek Shield Assy. Non-warrantable damage may
occur.
Follow the steps below to replace the ProTek Shield Assy:
1. Shut off the pool pump and bleed pressure from the
system.
2. Close isolation valves to minimize pool/spa water
loss.
3. Remove wing nut from bottom stud on ProTek Shield
Assy.
4. Remove bonding wire ring terminal from stud.
5. Rotate ProTek Shield Assy clockwise (by hand) to
unscrew it from the assembly.
6. Inspect/replace as necessary and reverse above
procedure to reinstall. Hand tighten only! Do not use
tools.
UG/BYPASS ASSY
UNITHERM
GOVERNOR
Figure 21. Unitherm Governor – Brass
Internal Automatic Bypass Valve
In addition to the Unitherm Governor, a built-in automatic
bypass valve is provided in the In/Out header. While the
Unitherm Governor responds to the changes in water
temperature in the heater, the internal bypass valve
automatically responds to changes in water pressure in the
piping system. Proper amount of water ow is maintained
through the heater under varying pressures dictated by the
conditions of the pump and lter.
UG/BYPASS ASSY
NOTE: Make sure the O-ring is properly seated in the
O-ring groove before installation.
Unitherm Governor Operation
a thermostatic mixing valve specically designed to
maintain constant heater internal temperature between
105°F (41°C) and 115°F (46°C) despite continually
changing ow rates from the lter and changing pool
temperatures. This narrow range is needed to prevent
damaging condensation on the burners which will
occur if the heater runs for any length of time below
100°F (38°C). It is also needed to inhibit scale formation
in the tubes by maintaining temperatures well below
accelerated scaling temperatures.
Figure 20. Unitherm Governor – Polymer
CAUTION: The patented Unitherm Governor is
AA
UG PLUG
UNITHERM GOVERNOR
GASKET
F10725
SPRING
"RED" - 206/266
"SILVER" - 336/406
Figure 22. Internal Automatic Bypass Valve ASME
NOTE: The Unitherm Governor and Bypass Valve Assy
are not individually replaced components on ASME
units. If either needs to be replaced, the entire UG/
Bypass assy must be replaced. The "red" spring is used
on models 207A, 266L, and 267A. The "silver" spring is
used on models 337A, 399L, and 407A.
External Auxiliary Bypass Valve
Where Required - An auxiliary bypass valve should be
used when ow rates exceed 125 GPM (473 lpm). Usually
a high-performance pump size larger than two horsepower
will exceed this ow rate. This valve is required to
complement the function of the automatic bypass valve,
particularly when starting the heater in winter or early
spring when the spa or pool temperature is below 50°F
(10°C). It also serves to eliminate needless pressure drop
through the heater and accompanying reduction in the ow
rate to the spa jets, etc.
16
FROM HEATER
FULL PORT
BALL VALVE
OR GLOBE
TO HEATER
VALV E
TO POOL/SPA
BYPASS VALVE
Do not use gate valve.
Figure 23. Auxiliary Bypass Valve
FROM POOL/SPA
Auxiliary Bypass Valve Adjustment
To set bypass - With clean lter, adjustment is made by
feeling the inlet and outlet pipes at the heater. Outlet pipes
should be slightly warmer than inlet and comfortable to the
touch. If pipe is hot, close bypass; if cold, open bypass.
Pressure Relief Valve Installation
To conform to local building codes, it may be necessary
to install a pressure relief valve. A 3/4" pressure relief
valve, having a capacity equal to the BTU output of the
model to be installed, is recommended for this heater. The
maximum acceptable pressure relief valve setting is 125
psi (862 kPa).
A 3/4" NPT connection is provided in the Polymer header
for installation of a pressure relief valve. The valve shall be
installed in a vertical position. Do not over-tighten. Install
pressure relief valve hand tight plus 1/2 turn.
PRESSURE RELIEF VALVE
PRV DISCHARGE
CONNECTION
F10663
Figure 25. Pressure Relief Valve Brass Header
(ASME Models)
NOTE: To avoid water damage or scalding due to valve
operation, drain pipe must be connected to valve outlet
and run to a safe place of discharge. Drain pipe must
be the same size as the valve discharge connection
throughout its entire length and must pitch downward
from the valve. No shut-o valve shall be installed
between the relief valve and the drain line. Valve lever
should be tripped at least once a year to ensure that
waterways are clear.
PRESSURE RELIEF VALVE
The heater requires water ow and positive pressure to
re and operate properly. It must therefore be installed
downstream of the discharge side of the lter pump. See.
Figure 29 and Figure 30.
A typical installation is plumbed as follows:
1. The inlet side of the filter is plumbed directly to the
discharge side of the filter pump;
2. The outlet side of the filter is then plumbed to the inlet
of the heater; and
3. The outlet of the heater is plumbed to the return line
to the pool or spa. The pump, filter and heater are
thus plumbed in series (Salt generators and chemical
feeders must be down stream of the pool heater).
Plumbing from the heater back to the pool or spa must not
have any valves or restriction that could prevent ow when
the pump is operating.
A 3/4" NPT connection is provided in the header for
installation of a 75 PSI (517 kPa) pressure relief valve.
The PRV is shipped loose in the accessory carton with the
pagoda top. The valve pressure relief shall be installed in
a vertical position.
CAUTION: An additional source of heated water,
AA
e.g. a solar system, must be connected to the main line
ahead of the heater inlet pipe in order for it to act as
the primary heat source. If the primary system provides
adequate heat to maintain setpoint, the heater will not
re. Be advised that the control panel will then display
sensed water temperatures downstream of the primary
heating system, rather than the temperature of the water
exiting the pool.
Heater must be located so that any water leaks will not
damage the structure of adjacent area. PVC pipe may be
glued directly into the headers unions.
17
Plumbing Diagram
TO REPACE AN ENGINEERED PIPING SYSTEM BY A PROFESSIONAL ENGINEER
Water Connection
ISOLATION
VALVE
THIS DIAGRAM IS A RECOMMENDATION AND IS NOT INTENDED
TO REPACE AN ENGINEERED PIPING SYSTEM BY A PROFESSIONAL ENGINEER
Figure 29. Single Pool Heater Installation
BALL VALVE
PRESSURE
RELIEF VALVE
PUMP
UNION
CHECK VALVE
18
THIS DIAGRAM IS A RECOMMENDATION AND IS NOT INTENDED
Figure 30. Multiple Pool Heater Installation
Heat Exchanger Reversal
Procedure for Residential Models
1. Remove right and left side access panels. See
Figure 26.
F10652
Figure 26. Access Panels
2. Disconnect wires at high limit, AGS (automatic gas
shut-off), water pressure switch on the in/out header,
and ProTek Shield bonding wire. See Figure 27.
Re-attach the headers to the opposite sides, making
sure they are installed in an upright position. Do not
over-tighten. Torque should not exceed 7 ft/lb. See
Figure 27.
5. Reconnect high limit, AGS, water pressure switch
wires, and ProTek Shield bonding wire.
6. Insert the temperature sensor into the compression
fitting, so that the sensor is flush with the top of the
fitting. Tighten 1/2 turn past hand tight.
7. Allow for water flow through the heater and check for
leaks.
8. Re-attach access panels to the opposite sides.
For instructions on reversing the heat exchanger
connections on ASME models, call your factory
representative.
5. ELECTRICAL WIRING
NOTE: If it is necessary to replace any of the original
wiring, use 105°C wire or its equivalent, and/or 150°C
wire or its equivalent, like the original wiring.
3. Remove the thermostat temperature sensor by
loosening the compression fitting nut. Re-route the
sensor to left side of the heater. See Figure 28.
F10654
Figure 28. Thermostat Temperature Sensor Location
4. Remove (12) nuts holding the inlet/outlet and return
headers to the tube sheets. Clean off tube sheet
area where the gasket seats. Also clean off the
header and the gasket. Apply a non-petroleumbased lubricant to the gasket such as Aqualube.
WARNING: Digital heaters are factory-wired for
AA
240 VAC, 1Ph, 60Hz power supply. DO NOT attempt to
operate at 208 VAC.
The standard eld-wiring connection is on the right side of
the heater.
To wire the heater from the left side, follow these steps:
1. Remove the two (2) screws that hold the front door
to the heater. Remove and set aside door for better
access to wiring.
2. Remove the four (4) screws that hold down the
junction box to the sway brace.
3. Remove the transformer cover located on the far
right by removing one (1) screw.
4. Remove the two (2) screws that hold down the
transformer.
5. Remove the one (1) screw that holds down the
ground wires.
6. Disconnect P6 connector from PC board.
7. Remove transformer from its current location and
relocate it on the far left side of the heater.
8. Re-route all high-voltage wires and ground wires
through the left jacket side of heater.
9. Re-install P6 connector, ground wires (SPG),
transformer, junction box, front door, and plug right
side with the left side’s grommet plug.
NOTE: 7/8" diameter holes not utilized on jacket and
control box can be used for reman switch, auxiliary
control interface or power vent (D-2) wiring.
19
Electrical Power Draw
F10651
RED
WHITE
CAUTION: Heater must be electrically grounded and
AA
bonded. Bonding lug is provided loose with the heater.
Install bonding lug on lower right or left side of jacket
as necessary for bonding the heater. Mounting hole is
provided on the jacket.
NOTE: Failure to ground the heater electrically could
aect the heater’s electronics.
NOTE: See "Time Clock/Fireman’s Switch" on page
28 for further instructions if using a time clock/
reman’s switch.
BLACK
WHITE
SUPPLY
L1
RETURN
or
NEUTRAL
HOT
BLACKBLACK
WHITEWHITE
SIDE
GROUND
GREENGREEN
RED
Figure 32. 120 VAC Wire Connection Models
HEATER
7 WIRES
The Electronic Intermittent Ignition Device automatically
lights the pilot and main burners upon a call for heat. The
heater is supplied with a dual-voltage transformer for 120
VAC or 240 VAC input power hookup.
When operating on 120VAC power, units draw 6 amps.
When operating on 240VAC units draw 3 amps.
OPTION LOCATION
LEFT SIDE FIELD WIRING
BONDING LUG
(OPTIONAL
LOCATION)
CONTROL BOX
(FACTORY MOUNTED
LOCATION)
SWAY BRACE
BONDING LUG
(STANDARD
LOCATION)
240 VAC Wiring
For 240 VAC input power to the unit, connect the black
wire to the L1 or hot leg of the power supply. Connect the
red wire to the “L2” or second hot leg of the power supply.
There should be no connection to the white wires for
240 VAC operation. Attach a wire nut to each white wire
independently.
WARNING: DO NOT attempt to operate the heater
AA
at 208 VAC.
240V LOW NOx HEATER
HOT
L1
BLACK
SUPPLY
SIDE
GROUND
HOT
L2
RED
GREENGREEN
Figure 33. 240 VAC Wire Connection
BLACK
BLACK
RED
RED
WHITE
HEATER
7 WIRES
Figure 31. Heater Wiring Locations
Transformer Wiring
120 VAC Wiring
For 120 VAC input power to the unit, connect the black
wire to the L1 or hot leg of the power supply. Connect the
white wire to the “Ret” or neutral leg of the power supply.
There should be no connection to the red wires for
120 VAC operation. Attach a wire nut to each red wire
independently.
20
The heater must be electrically grounded and bonded in
accordance with local codes, or, in the absence of local
codes, with the latest edition of the National Electrical
Code, ANSI/NFPA 70. (Canada - Canadian Electrical
Code, CSA C22.1, Part 1 and Part 2.)
CAUTION: If the transformer’s primary side is wired for
120 VAC and 240 VAC is applied, damage to the transformer and PC board may result. Such damages are not
covered under manufacturer’s limited warranty.
NOTE: Input power to the heater (120 or 240 VAC) can be
supplied from the load (pump) side of time clock or directly
from the GFCI power source. It is preferred that full-time
power be supplied to the heater from the GFCI power
source, and that the heater be controlled by the reman’s
switch connection or using a two or three-wire remote. If
using a switched GFCI power source, the heater could display
false service indicators on the display panel if the pump is
turned o.
6. WIRING DIAGRAM
21
7. CONTROLS
PRESSURE SWITCH
TEMP SENSOR
HL1 - HIGH LIMIT
HL2 - HIGH LIMIT
PROTEK
SHIELD
ASSY
GAS
VALV E
CONTROL
BEZEL
PILOT
AIR PRESSURE
SWITCH
MANUAL
RESET
ROLL-OUT
SWITCH
Figure 34. Location of Controls (View One)
UNITHERM
GOVERNOR
F10639-3
NOTE: Caution must be used to not damage controls
or wiring.
KNURLED
SCREW
F10647-3
Figure 36. Knurled Screw Location
Control Adjustments
The pool heater touchpad, located on the upper front
panel of the heater, allows the user to select either POOL
or SPA operation, and to adjust the setpoint temperature.
The LCD display window indicates the mode (OFF, SPA,
POOL) and the actual water temperature. A manual power
switch provided below the touchpad turns the control
power ON or OFF. See Figure 37.
BLOWER
DRAIN PLUG IN
REAR HEADER
F10639-2
Figure 35. Location of Controls (View Two)
Control Panel Removal
1. Remove screw from front door. Set aside door for
serviceability.
2. Remove (4) screws from sides of control panel.
3. Rotate control panel down until panel stops. Do not
force.
TEMP ADJUST BUTTONS
TEMP
LCD DISPLAY
Figure 37. Control Adjustments
MODE BUTTON
MODE
ON
OFF
22
Mode Button
Program Mode Button (SW1)
The Mode button is used to select POOL or SPA operation.
It allows the user to turn the heater o electronically. The
LCD remains energized and displays OFF, while continues
to show the actual water temperature.
Temp Buttons
If the heater is in POOL or SPA mode, the desired water
temperature (SETPOINT) will be displayed and may be
adjusted using the UP or DOWN buttons.
Operation
In the POOL or SPA modes, the actual water temperature
is displayed along with the desired water temperature
(SETPOINT). When the water temperature is above the
setpoint, “Water Temp” will alternate with “No Demand.”
When the water temperature is below the setpoint and the
heater is ring, “Water Temp” will alternate with “Heating.”
To adjust the setpoint temperature, make sure the control
is in the appropriate mode (POOL or SPA) and push the
UP or DOWN buttons.
By default, the setpoint range is 50-104°F (10-40°C). See
page 24 to increase the MAX setting, if necessary.
Service Menu and Fault History
To access the Service Menu and fault history, press the
MODE and UP buttons simultaneously for 3 to 5 seconds.
The heater will continue to operate while in the Service
Menu. The rst screen displayed is the Flame Strength
indicator, which indicates the pilot ame current using a bar
graph and numerical display. A signal of less than 4 bars
indicates a weak ame signal and may require service.
Refer to the Troubleshooting section for possible causes
and corrections.
Figure 40. Flame Strength Indicator
Press the DOWN button. The Supply Voltage screen
indicates the voltage supplied to the control board. Normal
readings range from 24 to 29 volts.
Figure 38. Alternating Display During Heating
Figure 39. Thermostat Program Button (SW1)
Figure 41. Supply Voltage Indicator
Press the DOWN button. The Run Time indicates the total
hours of operation for the pool heater, as measured by the
amount of time that the main gas valve has been powered.
The Cycle count indicates the number of on/o cycles of
the heater, as measured by the number of times the pilot
valve has been powered.
Figure 42. Run Time/Cycles
Press the DOWN button. The Fault History displays up to
ten faults in memory. The order of the faults begins with
“Fault Last,” which is the most recent fault, and proceeds
through ten most recent messages in chronological order.
The second line of the display shows the fault message.
If there are no faults in the history buer, the second line
reads “All Faults Clear.”
Figure 43. Fault History Indicator
23
Program Button
1. Remove the four screws holding the control cover, and
swing the panel down so the back side of the board
is visible. Locate the Program Mode button (SW1) as
shown in Figure 39. Press and hold the button for 5-7
seconds until SET FACTORY DEFAULTS appears
on the display. Release the program button.
2. Press the MODE button sequentially until the desired
program event is reached. There are 5 different
events that can be programmed. They appear in the
sequence listed in Figure 44 below.
Resets board to factory default
settings.
Resets faults in the History File.
Change from Fahrenheit to
Celsius.
SPA setpoint maximum
adjustment.
POOL setpoint maximum
adjustment.
Figure 44. Programmable Events
Set Factory Defaults
Refer to step one above to access the program screen.
SET FACTORY DEFAULTS should appear on the screen.
If it does not, press the MODE button until it appears on
the digital display. Press and hold both UP and DOWN
buttons for 5-7 seconds until DEFAULTS SET appears.
This operation resets the operating program to its factory
default values.
Both the POOL and SPA setpoints will revert to 65°F
(18°C) and both POOL and SPA maximum temperature
settings will be 104°F (40°C). The Control Lockout PIN will
be cleared and the control will resume normal operation.
Clear Faults
Refer to step one above to access the program screen.
Press the MODE button until CLEAR FAULTS appears
on the digital display. Press and hold both UP and DOWN
buttons for 5-7 seconds until FAULTS CLEARED appears.
This operation resets the Fault History le to “0” and clears
all the stored faults.
Fahrenheit or Celsius
Refer to step one above to access the program screen.
Press the MODE button until FAHRENHEIT or CELSIUS
appears on the digital display. The UP or DOWN buttons
will select FAHRENHEIT or CELSIUS on the temperature
display. Choose the desired temperature scale.
Spa Max Temp – Spa Setpoint Maximum Adjustment
Refer to step one above to access the program screen.
Press the MODE button until SPA MAX TEMP appears on
the digital display. Using the UP and DOWN buttons will
change the Maximum Temperature Setting to your desired
value. The control can be set for a maximum of 107°F
(42°C).
Pool Max Temp – Pool Setpoint Maximum
Adjustment
Refer to step one above access into the program screen.
Press the MODE button until POOL MAX TEMP appears
on the digital display. Using the UP and DOWN buttons
will change the Maximum Temperature Setting to your
desired value. The control can be set for a maximum of
107°F (42°C).
Control Lockout
The heater is equipped with a Control Lockout feature
to prevent unauthorized tampering or adjustment of the
control settings. To lock out the controls, press the DOWN
button and MODE button for 5 seconds. Choose a three
digit PIN, using the UP and DOWN buttons to select the
digits and the MODE button to lock in selections. Conrm
your selection and record your PIN.
To unlock the controls, press any button to bring up the
ENTER PIN menu. Enter the PIN that was used to lock the
control. Note that power cycling will not clear the lockout.
Successfully unlocking the control will display LOCKOUT
CLEARED. Failure to enter the correct PIN will display
INVALID PIN.
In the event that the user-selected PIN is lost or does not
clear the Control Lockout, use the Program Button to SET
FACTORY DEFAULTS. This will clear the PIN and allow
normal operation and selection of a new PIN if desired.
See the "Program Button" on page 24 for details.
NOTE: Both the POOL and SPA setpoints will revert
back to 65°F (18°C) and the POOL and SPA maximum
temperature settings will be 104°F (40°C). These
setpoints will need to be readjusted to desired settings.
NOTE: The LCD temperature display may not agree with
the temperature reading of your pool or spa thermometer.
The heater reads the water temperature at the inlet. Due
to the circulation characteristics of any pool or spa, the
water temperature at the inlet to the heater may dier
from that observed at a given location in the pool or spa.
24
Status and Diagnostics
The digital models are programmed to display a variety
of status and diagnostic messages, depending on the
operating conditions.
The following heat status messages are displayed in Pool,
Spa, and Remote modes when there are no active fault
conditions.
The following conditions are displayed only while there is a
demand for heat present.
DisplayCondition
Water Sw OpenWater pressure switch open.
Vent/Field
Sw #1
Hi Limit 1 FaultHigh limit 1 open.
Vent spill switch/eld switch #1 open.
DisplayCondition
HeatingCall for heat established, ame present.
SparkSpark operating.
No DemandHeat demand is satised.
Table M. Heater Status Messages - No Active Faults
The following conditions are displayed in Pool, Spa and
Remote modes when there are active fault conditions.
DisplayCondition
Sensor Failure
Sensor Open
Sensor Short
Flame w/o CFH
MV Output Fault
Lo NOx Tab Fault
Internal FaultBoard fault, replace board.
EEPROM Fault
Clock/Fireman Sw
Low Temp
Lockout
Thermistor temperatures disagree by
more than 2°F (1°C)
Board is sensing ame when
both main and pilot valves are
commanded shut.
Main gas valve output is not in
commanded state.
Voltage is sensed at the Lo NOx
terminal on a non-Lo NOx Heater (Lo
NOx tab is intact)
Memory fault, reset set points,
replace board if fault does not clear.
Time clock/reman switch circuit is
open.
Water temperature below 36°F (2°C).
Hi Limit 2 FaultHigh limit 2 open.
Rollout Sw OpenRollout switch open.
Flow/Field SW #2
Fan Lockout
Fan 5 Min Delay
Ignition Lockout
(Propane Tab
Broken)
Ignition Failure
(Propane Tab Not
Broken)
Ign 6min Delay
(Propane Tab Not
Broken)
Table O. Heater Status Messages - Demand for Heat
Field-supplied ow switch/eld switch
#2 open.
3 fan switch faults within same heat
demand cycle, power must be cycled
to clear the fault
Heater shut down for 5 minutes
because LoNOx fan switch didn't close
Alternating with “No pilot sensed”
- Pilot ame not established within the
required time (15 sec or 90 sec).
Alternating with “Main Ign Failure”
- Pilot ame lost during the 8 second
trial to ignite the main burner.
Alternating with “No pilot sensed”
- Pilot ame not established within 90
seconds.
Alternating with “Main Ign Failure”
- Pilot ame lost 4 times within the 8
second trial to ignite the main burner.
Heater will lockout for 6 minutes before
retrying.
Table N. Heater Status Messages - Active Faults
25
Remote Control Installation
and Operation
CAUTION: Before installing remote controls
AA
to the heaters, read the following: The digital
thermostat model is remote-ready in most cases. The
digital liquid crystal display (LCD) shows the actual pool
temperature, operating status, and service codes. See
Figure 45. The touch pad on the control panel allows
you to select the desired pool or spa temperature. It also
indicates when a remote system is controlling the heater
by displaying Remote in the display. When connecting
the heater to a remote system, identify whether it is a
two- or three-wire remote system. Select the appropriate
instruction listed below to properly install the remote to
the heater.
Remote Operation
The heaters are equipped with the ability to work with
external remote controls. The supplied 7-pin remote wiring
connector supplies power out to either a toggle switch or
the switch contacts of a third-party remote. The remote
works by either making or breaking the circuit created
by the remote wiring. Typically, a remote does not supply
power to the heater, it only provides a switching function
to turn the heater On or O. If your remote is supplying
its own voltage to the heater, it will not work with this
heater and may damage the digital circuit board.
For operation of the heater using the onboard thermostatic
controls with a time clock. See "Time Clock/Fireman’s
Switch" on page 28.
OFF Mode
Activating the Remote
To activate or deactivate the remote function:
1. Press and hold the UP and DOWN arrow buttons for
3 to 5 seconds.
The second line of the display will alternate even when the
unit is o (“No Demand”).
NOTE: When in remote operation, the keypad mode and
temp buttons are disabled.
Figure 46. Remote Control Menu - Activation
Remote Control Wiring
ATTENTION
OBSERVE PRECAUTIONS
ELECTROSTATIC
SENSITIVE DEVICES
CAUTION: Electrostatic Discharge (ESD) damage
AA
can be caused by direct or indirect contact with the
wiring or circuit board. When one walks to the heater
area, an electrostatic charge accumulates on the body.
Contact of a nger allows the body to discharge, possibly
causing device damage. This damage can be limited if
the service person discharges himself, following ESD
preventive/removal practices, and holds on to the heater
enclosure for 5 seconds before proceeding.
Heating in the POOL Mode
Heating in the SPA Mode
Remote Mode
Figure 45. Remote Control Menu - Remote Operation
26
Important Installation Notes for Remote or External
Wiring Conguration:
• Remote wiring must be run in a separate conduit.
• Remote wiring must not be run parallel to high voltage
lines.
• For runs of under 30' (9 m), remote wiring should
have stranded conductors with a minimum of 22
AWG, 600V, cable twisting 1.5" to 2.5" (3.8 to 6.4 cm)
lay and jacketed.
• For runs over 30' (9 m), the conductors should be a
minimum of 20 AWG, 600V, cable twisting 1.5" to 2.5"
(3.8 to 6.4 cm) lay that is shielded and jacketed.
• Maximum cable length is 200' (61 m).
• For both two- and three-wire remote systems, the
provided 7-pin wiring connector must be utilized.
NOTE: The remote wires must be connected to the
7-pin connector before the connector is plugged into the
board.
2-Wire Remote Control (On-O)
This application assumes that only one heating function
(pool or spa) is required.
1. Turn on power to the heater.
2. For a 2-Wire Remote Control from a remote without
its own sensor, push the MODE button to the “POOL”
or “SPA” mode and set the desired setpoint (eg.
102°F (39°C) for Spa).
3. For a 2-Wire Remote Control from a remote with its
own sensor, push the MODE button “POOL” or “SPA”
mode and set the temperature to the highest setting
available on the control. The actual setpoint will be
controlled by the remote control.
4. Turn the MODE button to "OFF" and remove power
from the heater.
5. On the “Remote Interface Harness”, connect the
BLUE wire to one side of the “REMOTE” switch and
connect the other side to either the ORANGE/BLACK
wire for “SPA” operation or the BLACK/ORANGE
wire for “POOL” operation. See Figure 47.
BLU - 24VAC
ORN/BLK - To Spa (COMM)
Wire Nut BLK/ORN - To Pool (COMM)
Figure 48. 2-Wire Remote Harness Installation on the P8
Connector of the Board
Pool Common
(BLK/ORN)
Spa Common
(ORN/BLK)
24VAC HOT
(BLU)
Figure 47. 7-Pin Remote Interface Harness
6. Attach wire nut on unused wire to the “Remote
Interface Harness.”
7. Install the “7-Pin Remote Interface Harness” to the
P8 connector and turn power "ON" to the heater.
See Figure 48.
For activation of the remote control, see section on page
26.
3-Wire Remote Control Using ThreePosition Switch (Pool-O-Spa, or Low-OHigh)
This application assumes that both heating functions (pool
and spa) are required.
1. Turn on power to the heater.
2. Push the MODE button to the “POOL” or “SPA” mode
and set the desired temperature for each (eg. 80°F
(27°C) for Pool and 102°F (39°C) for Spa).
3. Turn the MODE button to OFF and remove power
from the heater.
BLU - 24VAC
ORN/BLK - To Spa (COMM)
BLK/ORN - To Pool (COMM)
Figure 49. 3-Wire Remote Harness Installation on the P8
Connector of the Board
4. On the “Remote Interface Harness” connect the BLUE
wire to one side of the “REMOTE” switch and connect
the ORANGE/BLACK wire for “SPA” operation and
the BLACK/ORANGE wire for the “POOL” operation.
See Figure 47.
5. Install the “Remote Interface Harness” to the
P8 connector and turn power ON to the heater.
See Figure 49.
For activation of the remote control, see section on page
26.
27
Time Clock/Fireman’s Switch
To operate the heater with a time clock, connect the timer
to the reman’s switch connection in the heater’s wiring.
The time clock should be of the dual-switch type and set to
shut o the call for heat to the pool heater 15 to 20 minutes
prior to shutting down the pool pump.
The reman’s switch connection is located on the 14pin header connected to the digital control board. Splice
into the red wire jumper tagged “Where necessary add
“Fireman’s” switch circuit here” to connect the time clock.
The reman’s switch connection must be a dry contact
and must not supply power to the heater. Powering the
reman’s switch connection externally may damage
the heater, and is not covered by warranty.
Do not exceed 50' (15 m) of total wiring using 18 AWG
stranded copper wire rated for 105°C minimum.
NOTE: When using a time clock, the heater will display
“Clock/Fireman Sw” when the reman’s switch is open,
indicating that the time clock has shut o the call for
heat.
Water Pressure Switch
The water pressure switch ensures that the heater operates
only when the lter pump is in operation. It is located on the
In/Out header. It is factory-set at 1.75 PSI for deck level
installation.
Water Pressure Switch Adjustment
When the heater is located below the level of the spa or
pool, it may be necessary to adjust the pressure switch to
compensate for the no-ow static head, If it is necessary to
adjust the water pressure switch, do the following:
1. Make sure the pool filter is clean before adjusting the
switch.
2. Set the heater control to the OFF mode.
3. Turn the filter pump ON and confirm that the pressure
switch is closed (use a multimeter to check). If the
pressure switch fails to close, either the switch setting
is too high or not enough pressure is being supplied
by the filter pump.
4. Turn the heater ON.
5. Manually turn the pressure adjustment knob clockwise
until the heater shuts off. (A flat screwdriver may be
necessary if knob is too tight.)
6. Slowly turn the adjustment knob counter-clockwise
until the heater calls for heat again.
7. Turn an additional 1/2 turn counter-clockwise.
8. While the heater is running, check the adjustment
by turning the pump off and on several times. The
burners should shut off immediately when the pump
is turned off. If it does not, repeat the above steps
until proper operation is observed.
F10671
Figure 50. Water Pressure Switch Assembly
NOTE: The sheet metal access panels should be in
place at all times to protect the water pressure switch
from rain and other environmental factors.
NOTE: If heater is installed outside of the limits shown,
a higher pressure rated (11 psi / 76 kPa) switch may be
used. A ow switch, mounted and wired adjacent to the
heater, may be used in place of the factory-mounted
pressure switch. See "ILLUSTRATED PARTS LIST" on
page 39 for 11 psi / 76 kPa water pressure switch.
Two Speed Pumps
In some cases, the ow on the low-speed is insucient
to operate the heater. This is apparent when the water
pressure switch cannot be further adjusted or if the heater
makes banging noises or shuts o on high limit. In these
cases, the pump must be run at high speed when heating
the water.
CAUTION: Do not operate the heater without the
AA
function of a properly adjusted water pressure switch
or ow switch.
28
Flame Roll-Out Safety Switch
Heaters are equipped with a thermal cuto device to
prevent ame roll-out in the event the heat exchanger
becomes blocked. It is a “manual reset” type roll-out
switch that must be reset by a service technician after any
over-temperature conditions have been xed. Excessive
restriction in the heat exchanger ue passage may cause
the switch to disable the heater.
Figure 52. Flame Roll-out Switch – Manual Reset
High Limits
The heater is equipped with two high limits.
On units with polymer headers, both are automatic and
are located in the inlet/outlet header. Both are set at 135°F
(57°C).
On units with brass header, both are located on the inlet/
outlet headers. HL1 is manual reset and set to open at
160°F (71°C). HL2 is automatic and set to open at 135°F
(57°C).
Pilot Safety
The heater employs a pilot safety which closes the main
gas valve within 8/10ths of a second whenever the pilot
ame is interrupted. The pilot ame is automatically lit
when the device is powered. The heater performs its own
safety check and opens the main valve only after the pilot
is proven to be lit.
Burner Tray Removal
1. Shut off main electrical power switch to heater.
2. Shut off gas upstream of heater.
3. Remove front door.
4. Disconnect gas line from gas valve.
5. Remove (2) screws that mount burner tray to the
base of the unit, (2) screws that mount the blower
box to the burner tray, and (1) screw that secures the
anti-rotation bracket to the heater.
6. Disconnect wires that terminate at gas valve.
7. Unscrew (4) screws that secure the control box.
8. Disconnect pilot wire from the pilot assembly.
9. Disconnect wire connector from the combustion
blower.
10. Carefully slide out the burner tray assembly.
11. Reverse above procedure to reinstall.
NOTE: An erratic high limit is often characteristic of
an internal heat exchanger problem, e.g. scale build-up,
defective bypass. Refer to "TROUBLESHOOTING" on
page 35.
AUTO RESET
Figure 53. High Limit Switches
MANUAL RESET
(ASME ONLY)
F10669-1
High Limit Removal
1. Shut off main electrical power switch to heater.
2. Remove inlet/outlet sheet metal access panel.
3. Remove defective high limit and replace with the
correct, new high limit.
4. Replace access panel.
Figure 54. Burner Tray Assembly
29
Gas Valve Removal
1. Shut off gas supply to the heater. Remove gas piping
to gas valve inlet.
2. Remove burner tray, following above procedure.
3. Disconnect, pilot tubing from gas valve.
4. Remove (2) screws that mount anti-rotation bracket
to the burner tray.
5. Turn vertical gas pipe from manifold slightly and
unscrew gas valve.
6. Reverse above procedure to reinstall.
Main Burner And Orice Removal
1. Remove burner tray, following above procedure.
2. Remove pilot. See pilot removal procedure.
3. Remove (8) total screws from the burner hold-down
brackets, front and rear of tray.
4. Remove (8) total screws from the left and right
sides of the manifold assembly. Detach the air/gas
manifold assembly from the burner tray assembly.
5. Remove burners by raising them straight up off the
rear end slots.
6. Use a long 9/16” socket wrench to remove orifice
from the gas manifold.
7. Reverse above procedure to reinstall.
Pilot Removal
1. Disconnect pilot tubing from gas valve.
2. Remove the pilot wire from the pilot assembly.
3. Remove (2) screws that mount the pilot assembly to
the burner tray.
4. Pull the pilot assembly downwards and outwards.
5. Reverse above procedure to reinstall.
Electrode Alignment
Detail
.18± .04 inch (4.57±1 mm)
Figure 55. Lo NOx Pilot
Combustion Blower Removal
1. Remove the (2) screws that secure the blower box to
the burner tray.
2. Remove (2) screws that mount the blower box to the
base of the heater.
3. Disconnect wire connector from the combustion
blower.
4. Carefully remove blower box with combustion blower.
5. Remove (2) screws that secure combustion blower
to blower box.
6. Reverse above procedure to reinstall.
Heat Exchanger Removal
1. Shut water, gas and electricity off, close valves and
relieve pressure, then remove relief valve. Remove
side access panels.
2. Remove top jacket holding screws.
3. Remove rear top panel.
4. Remove screws mounting the rain shield to the rear
panel. Also remove the screws that mount the rain
shield to the sway brace. Remove rain shield.
5. Remove the four (4) screws holding down the flue
collector. Remove the flue collector.
6. Disconnect flange nuts on Inlet/Outlet header,
remove ProTek Shield Assy bonding wire from heat
exchanger stud, loosen union(s) at gas pipe and slide
heater away from piping.
7. Lift heat exchanger straight up using caution not to
damage refractory.
8. Reverse above procedure to reinstall. Make sure the
insulation strips are properly replaced on top of the
refractory retainer.
Tube Cleaning Procedure
Establish a regular inspection schedule, the frequency
depending on the local water conditions and the severity
of service. Do not let the tubes clog up solidly. Clean out
deposits over 1/16” in thickness.
The heater may be cleaned from the return header
side, without breaking pipe connections. It is preferable,
however, to remove both headers for better visibility
through the tubes and to be sure the ground-up lime dust
does not get into the system. Note that you do not remove
the top panel or the heater exchanger, generally.
After reaming, mount the wire brush in place of the auger
and clean out debris remaining in the tubes.
Another method is to remove the heat exchanger, ream
tubes and immerse heat exchanger in non-inhibited descale solvent for severe scale build-up.
30
Extension
F10724
F10642-2
Pieces (2)
Figure 56. Tube Cleaning Kit
Auger
with Carbide Tip
Wire Brush
Desooting Procedure
WARNING: Soot Is Combustible. Exercise Extreme
AA
Care.
Soot will clog areas between ns and cause eventual
tube failure. Any sign of soot at the base of the burners or
around the outer jacket indicates a need for cleaning.
5. Remove heat exchanger from the heater and wash
with a garden hose, making sure soot is removed
from spaces between fins.
6. Reverse above procedure to reinstall.
NOTE: In extreme cases it may be necessary to do
steam cleaning at the local car wash. DO NOT WIRE
BRUSH.
Combustion Chamber Removal
To remove combustion chamber, you must rst have
removed the heat exchanger.
Unitherm Governor (U.G.) Replacement
1. Shut water, gas and electricity off, close valves and
relieve pressure.
2. Drain heat exchanger.
3. Remove retainer plug located next to the outlet pipe
connection on polymer header models.
4. Unsnap old U.G. to remove from retainer plug. Snap
in new U.G.
5. Reinstall retainer plug, taking care to lubricate
gasket with a non-petroleum based grease such as
AquaLube.
UG PLUG
UNITHERM GOVERNOR
GASKET
F10725
Figure 58. Unitherm Governor – Polymer
To test the operation of the Unitherm Governor, place in
hot water (over 110°F [43°C]) and watch for movement
against spring. If there is no movement, replace unit.
UG/BYPASS ASSY
Figure 57. Refractory Panels
WARNING: When removing the burners or heat
AA
exchangers, take precautions to avoid creating airborne
dust and avoid inhaling airborne bers. When cleaning
spills, use wet sweeping or High Eciency Particulate
Air (HEPA) ltered vacuum to minimize airborne dust.
Use feasible engineering controls such as local exhaust
ventilation or dust collecting systems to minimize
airborne dust. Wear appropriate personal protective
equipment including gloves, safety glasses with side
shields, and appropriate NIOSH certied respiratory
protection, to avoid inhalation of airborne dust and
airborne ber particles.
NOTE: The U.G. on ASME models (brass headers)
can only be replaced by replacing the entire Unitherm
Governor/Bypass Valve Assembly.
31
8. OPERATING
OFF
INSTRUCTIONS
Before Start-Up
Visual Inspection
Flames can be observed through the opening below the
plenum. Flame color is blue and evenly spread on the top
surface of the burner. At least every three months a visual
inspection should be made of the burners.
Burners
Keep heater area clear and free from combustibles,
ammable liquids and chemicals. Do not obstruct the ow
of combustion and ventilation air.
Water
Water must be owing through the heater during operation.
Ensure that the system is lled with water and that the
pump is operating.
Start-Up Procedures
Your pool/spa heater has been designed for years of safe
and reliable pool/spa water heating. It is available with only
electronic ignition. ASME-certied units typically used in
commercial applications, are also available. This manual
provides installation, operation, maintenance, and service
information for these heaters.
TEMP ADJUST BUTTONS
MODE BUTTON
Water Pressure Switch
A water pressure switch is provided in the heater to shut
o the burners in the event that water supply is interrupted.
It is very important to verify that the switch electrically
opens and shuts o the gas valve when water ow to the
heater is interrupted. Otherwise rapid and severe damage
will likely occur to the heater.
The water pressure switch should be checked and adjusted
for proper operation by a qualied service person at the
time of installation and periodically checked thereafter.
Refer to "Water Pressure Switch Adjustment" on page
28.
TEMP
LCD DISPLAY
Figure 60. Heater Control Toggle Switch
MODE
ON
If your digital heater has been installed correctly, operating
the heater is an easy task. The upper front panel of the
heater contains the control center that allows you to turn
the heater On or O and adjust the temperature settings
for the pool or spa. The temperature range is factory set
from 65°F (18°C) to 104°F (40°C). See Figure 60 for
location of toggle switch to turn the heater On and O.
See Section 7 for additional details about the use of the
controls in the Control Adjustments subsection.
After Start-Up
Feel the inlet and outlet pipes. Outlet pipe should be only
slightly warmer than the inlet. It should not be hot.
WARNING: Should overheating occur or the gas
AA
supply fail to shut o, turn o the manual gas control to
the appliance.
F10671
Figure 61. Water Pressure Switch
WARNING: Operation of the heater without water
AA
circulation will cause rapid and severe damage to the
heater, and will void the warranty.
Blower Adjustment
This heater is equipped with a combustion air plate (bae)
mounted on the air intake to the combustion air blower.
The bae has a hole that is utilized to control the air inlet
to the blower.
When the combustion air setting is proper, there will be
some lifting of the ames on some areas of the burner
deck under cold-start conditions. After about ve minutes
of operation, the ames should settle down and blue
tips should become visible. Lifting of ames beyond ve
minutes would indicate too much combustion air.
32
OPERATING INSTRUCTIONS AND SHUT-OFF PROCEDURES
ELECTRONIC IGNITION DIGITAL MODELS
(AUTOMATICALLY–LIGHTED PILOT)
FOR YOUR SAFETY READ BEFORE LIGHTING
A. This appliance is equipped with an ignition de-
vice which automatically lights the pilot. Do not
try to light the pilot by hand.
B. BEFORE OPERATING, smell all around the ap-
pliance area for gas. Be sure to smell near the
oor because some gas is heavier than air and
will settle on the oor.
WHAT TO DO IF YOU SMELL GAS:
*Do not try to light any appliance.
*Do not touch any electric switch; do not use any
phone in your building.
*Immediately call your gas supplier from a neigh-
bor’s phone. Follow the gas supplier’s instructions.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn o all electrical power to the appliance.
4. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light
the pilot by hand.
5. Remove heater door panel.
6. Turn gas control knob clockwise to "OFF".
7. Wait 5 minutes to clear out any gas. If you
then smell gas, STOP! Follow “B" in the safety
information above. If you don’t smell gas, go to the
next step.
8. Turn gas control knob counter-clockwise to "ON."
9. Replace heater door panel.
10. Turn on all electrical power to the appliance.
*If you cannot reach your gas supplier, call the
re department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, do not try to repair
it. Call a qualied service technician. Force or
attempted repair may result in a re or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualied service technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the
instructions “To Turn O Gas To Appliance”
and call your service technician or gas
supplier.
HONEYWELL VR8340 GAS
VALVE IID
GAS
INLET
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat at the lowest setting.
2. Turn o all the electrical power to the appliance if
service is to be performed.
3. Remove heater door panel.
4. Turn gas control knob clockwise to "OFF".
Make sure knob rests against stop.
5. Replace heater door panel.
33
9. MAINTENANCE AND CARE
F10673
Cold Weather Operation
WARNING: Check the heater for possible rodent
AA
nests after long periods of non-use.
To be followed one month after start-up and then semiannually.
1. Inspect top of heater and drafthood for soot, a sticky
black substance around finned tubes and “V” baffles,
and open flue gas passageways. Any visible soot
should be cleaned for proper operation.
CAUTION: Soot may be combustible. Wet sooted
AA
surfaces completely prior to cleaning. Do not use steel
wire brush.
2. The Low NOx burners and orifice areas should be
inspected annually. Dirt and debris can affect the
operation of the heater and could damage the burners
or prevent the heater from firing. DO NOT clean the
burners with a wire brush.
3. Inspect and operate all controls, gas valve and
pressure relief valve (if equipped).
4. Make visual check of the burner and pilot flames.
Flame color is blue and evenly spread on the top
surface of the burner.
5. On indoor heaters, clean room intake openings to
ensure adequate flow of combustion and ventilation
air.
CAUTION: Combustion air must not be contaminated
AA
by corrosive chemical fumes which can damage the
heater and void the warranty.
6. Keep area around heater clear and free from
combustible materials, gasoline and other flammable
and corrosive vapors and liquids.
Important Freeze Information
MODERATE CLIMATE: Heater operation can continue
during short-term cold spells. When temperatures are
between 0°F (-18°C) and 32°F (0°C), ow (continuous
pump operation) must be maintained.
CAUTION: Do not use the heater to maintain
AA
water temperatures just above freezing or for freeze
protection. When heater is used during freezing weather,
care must be taken to avoid freeze-ups. Continuous
pump operation is a must. Additional protection may be
required. The heater is not warranted against freeze-ups.
COLD CLIMATE: Prolonged operation with water
temperatures below 50°F (10°C) is not recommended.
When starting the heater with water temperatures below
50°F (10°C), operate the heater continuously until higher
temperatures are reached. Operating the heater for
prolonged periods with pool water below 50°F (10°C)
can seriously damage the heater, and is not covered by
the warranty. For cold climate areas, please follow the
winterizing procedures listed below.
Winterizing the Pool and Spa Heater
Heaters installed outdoors in freezing climate areas may be
shut down for the winter. Observe the following procedure
for winterizing the heater:
1. Turn off gas valve, manual gas valve, and electrical
supply to the heater.
2. Remove the ProTek Shield Assy located in the inlet/
outlet header, (under water pipes). Remove the heat
exchanger inspection panel on the side opposite
water piping to gain access to the drain plug on the
return header. Open drain plug on return header. See
Figure 62 and Figure 63.
If Heater Will Not Fire:
If you have no electrical power, it may be that your “circuit
breaker” has tripped. Try re-setting it.
If you have electrical power but the heater will not re
check the following or see "TROUBLESHOOTING" on page 35:
1. The time clock must be in the ON position.
2. Your pump strainer basket may be full. If so remove
debris.
3. Your filter may be dirty. If so, backwash or clean
filter. (To tell if your filter is dirty, look to see if the filter
pressure is higher than usual).
4. The pump may have lost its prime and be running
dry. Check the pressure on the filter. If there is no
pressure; then you are not moving water (or your
gauge is broken). Try to get the pump to run at its
normal flow rate.
34
DRAIN PLUG
Figure 62. Return Header Drain Plug, Polymer
("P" Prex Model)
DRAIN PLUG
Figure 63. Return Header Drain Valve, Brass
("B" Prex Models)
O RING
F10672
10. TROUBLESHOOTING
IMPORTANT NOTICE: These instructions are intended for the use of qualied personnel who are specically trained
and experienced in the installation of this type of heating equipment and related system components. Installation and
service personnel may be required by some states to be licensed. Persons not qualied shall not attempt to install this
equipment nor attempt repairs according to these instructions.
ProblemPossible CauseCorrective Action
Harmonics, or whining noiseUnitherm governor inoperative ................Check movement by putting in hot water (110°F [40°C] or
*Debris or restriction in system ...............Locate the restriction and remove. Flush system and clean
*Debris in gas line...................................Remove debris or blow out gas line
Low ow..................................................Scale forming in heat exchanger - clean heat exchanger and
Heater going on and o
continuously
Liming or scale forming in
exchanger
SootingHigh ow rates ........................................Reduce by adding manual bypass valve
Pilot outage or “Weak Flame”
signal
Yellow lazy ameLow gas pressure ...................................Adjust gas pressure
Outer jacket very hot (paint
blistered)
Takes too long to heat pool or
spa
Leaking at heat exchangerOveracid .................................................Replace heat exchanger and maintain proper water chemistry
Gasket brittle and leaking (overheated)
Combustion fan not running
"Fan 5 min Delay" signal or
"Fan Lockout" signal
* Indicates symptom which usually occurs on initial start-up.
Dirty lter ................................................Clean or replace lter
Low water level in pool ...........................Raise water level
Sooted heater .........................................Determine cause of sooting and correct
Fan relay.................................................Replace fan relay
Fan .........................................................Loose connection or failed motor
Burned motor ..........................................Incorrect wiring, replace blower
Air pressure switch .................................Replace air switch
higher)
check pool pH and total alkalinity
Adjust manual bypass valve until heater outlet water temp is
between 105°F and 110°F (40°C and 43°C)
higher). If no movement, replace
Calculate heating capacity of heater
Htr. output (BTUH)
Pool gallonage x 8.33
or refer to heater sizing chart
This does not take into account heat loss due to weather
35
Digital - Flow Chart
START
TURN GAS SUPPLY OFF.
TURN THERMOSTAT
(CONTROLLER) TO CALL
FOR HEAT
POWER TO PC BOARD?
(24 V NOMINAL)
YES
SPARK ACROSS
IGNITER/SENSOR GAP?
YES
WARNING: HIGH VOLTAGE
AA
For qualied technicians ONLY
NOTE: Some heaters may be equipped with an ignition
module that shuts o pilot gas if pilot fails to light. To
reset, interrupt power to heater.
NOTE: Before troubleshooting, familiarize yourself with the start-up and check-out
procedure.
Check line voltage power, low voltage transformer, limit controller, thermostat
NO
NO
(controller) and wiring. Make sure that the line voltage is NOT 208 VAC.
Pull ignition lead and check spark at PC board.
Spark Okay?
YES NO
• Check ignition cable, ground wiring, ceramic insulator and gap, and correct.
• Check boot of the ignition cable for signs of melting or buckling. Take protective
action to shield cable and boot from excessive temperatures.
Replace the PC board.
TURN GAS SUPPLY ON
PILOT BURNER LIGHTS?
YES
MAIN BURNER LIGHTS?
YES
SYSTEM RUNS UNTIL
CALL FOR HEAT ENDS?
YES
CALL FOR HEAT ENDS
SYSTEM SHUTS OFF?
YES
NO
NO
NO
NO
• Check that all manual gas valves are open, supply tubing and pressures are
good, and pilot burner orice is not blocked.
• Check electrical connections between PC board and pilot operator on gas control.
• Check for 24 VAC across PV-MV/PV terminals on PC board. If voltage is okay,
replace gas control; if not, replace PC board.
NOTE: If PC board goes into lockout, reset system. Lockout is used on L.P.G.
models.
• Check for 24 VAC across MV-MV/PV terminals. If no voltage, replace module.
• Check electrical connections between PC board and gas control. If okay, replace
gas valve or gas control operator, i.e. pilot gas valve, etc.
NOTE: IF PC board goes into lockout, reset system.
• Check continuity of ignition cable and ground wire.
NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though
operation is normal at the time of checkout.
• Check that pilot ame covers ame rod and is steady and blue.
• If checks are okay, replace PC board.
• Check for proper thermostat (controller) operation.
• Remove MV lead at module; if valve closes, recheck temperature controller and
wiring; if not, replace gas valve.
TROUBLESHOOTING
36
ENDS
Control Logic - Flow Chart
Power On
Is the water
temperature displayed?
YES
NO
• Check On/Off switch (under lid on control panel)
• Check for 120/240 volts to the transformer
(time clock, circuit breaker, wire connections)
• Check for 24 volts to Circuit Board (P6 connector)
Push MODE
switch to select
"Pool" or "Spa"
Push Temp
arrow to scroll to
desired temperature
Water temperature
and set
temperature
displayed?
YES
“Heating” will
display briefly
“Spark”
Flame icon displayed
and flashing?
OR
Water temp displayed?
(pilot lit and rectified)
YES
NO
NO
“Remote” and Water Temperature displayed
(a remote control is controlling the heater)
Note: Disconnect the remote by turning the
remote function off. See page 28 for instructions.
NO
Is a fault code displayed and flashing?
YES
Diagnostic Readouts
“Sensor Failure,” “Sensor Open” or “Sensor Short” -
Temperature sensor out of range (replace sensor)
Sensor Failure
Inspect thermister, wires, and connector at Terminal P1
Check resistance value of the thermister. Reference to chart below.
Replace thermister if not within 10% of values shown below.
If okay, replace Circuit Board.
“Water Sw Open” Pressure switch. Verify water flow and pressureCLEAN FILTER / STRAINER - backwash if neccessary.
“Hi Limit 1 Fault” High limit switch. Verify water flow. Inspect internal
“Hi Limit 2 Fault” Thermostat (Unitherm Governor) and bypass valve.
Press manual button on HL1 fault on brass (ASME) models.
“Rollout Sw Open” Rollout Sensor - Check for blocked heat exchanger and soot. Press manual reset button.
“Clock/Fireman Sw” Fireman or Remote switch connected to safety loop is in theOFF mode.
“Vent/Field Sw #1” Vent switch open. Check connections to the board.If extractor installed, troubleshoot extractor.
“Ignition Lockout” Ignition lockout. Check power at pilot valve. Check spark (bad
ignition circuit or hi-tension wire). Verify clean pilot orifice and
clearance from igniter to ground rod.
“Ignition Failure” Ignition failure. Verify gas to the heater. Verify valve operation(gas present at tube fitting).
Heater Fired?
YES
END
NO
Verify power at MV on P-4 Terminal on digital circuit board.
Verify power to valve MV voltage. (Replace valve.)
37
11. REPLACEMENT PARTS
NOTE: To supply you with the correct part, it is important
that you supply the heater model number, serial number
and type of gas when applicable.
Any part returned for replacement under standard
company warranties must be properly tagged with a return
parts tag, completely lled in with the heater serial number,
model number, etc., and shipped to the Company freight
prepaid.
If determined defective by the Company and within
warranty, a like part or equal substitution will be returned,
freight collect. Credit will not be issued.
MANUFACTURER:
2151 Eastman Avenue
Oxnard, Ca 93030
38
12. ILLUSTRATED PARTS LIST
9-M
3-V
I-S
I3-S
8-S
2-J
8-C
6-M
1-V
5-C
4-C
11-S
17-HM
3-J
4-V
2-V
I5-HP
3-HP
4-S
9-M
6-HP
6-S
3-R
4-HP
2-S
5-HP
7-HP
6-HP
I2-S
20-HP
7-S
2-R
3-S
14-S
8-M
7-M
1-G
4-B
15-M
3-B
10-S
2-M
2-B
1-B
8-B
25 -M
5-B
7-C
6-B
13-M
10-M
12-M
5-S
4-S
1-R
12-M
1-J
39
1-M
3-HM
7-HM
5-HM
5-HM
2-S
16-M (OPTIONAL)
6-C
6-HM
4-HM
1-M
17-M
2-HM
4-S
8-HP
18-M
FOR UNITS WITH ASME BRASS HEADERS FROM 12/2019
2-S
6-HM
6-C
14-HM
13-HM
19-HM
2-HM
9-S
21-HM
17-HP
15-HM
26-HM
20-HP
16-HM
27-HM
18-HP
1-C
9-C
28-HM
(OPTIONAL)
11-HM
6-M
6-M
2-C
17-HM
40
7-HM
3-HM
3-C
4-HM
4-S
19-HM
20-HM
18-HM
FOR UNITS WITH ASME CAST IRON HEADERS PRIOR TO 12/2019
*FOR INSTALLATIONS AT OVER 5,000 FEET ABOVE SEA LEVEL, CONSULT THE FACTORY
**WARNING: The Hydraulic conditions or water chemistry that caused the tube bundle to fail have very likely also damaged the bypass valve and
Unitherm Governor. We recommend you replace the Unitherm Governor and inspect the bypass assembly. Failure to do so could cause premature
failure of this replacement part.
***Replacement burner trays are built for sea level, natural gas applications unless otherwise specified at the time the order is placed.
42
CALL OUTDESCRIPTION207A267A337A407A
failure of this replacement part.
HMHEAT EXCHANGER - METAL
1-HMHeat Exchanger Assy.Copper ASME
2-HMInlet/Outlet Header ASME Complete
15-HMInlet & Outlet Flange (Complete) - prior to 12/2019003766F003766F003766F003766F
20-HM Inlet & Outlet Flange - prior to 12/2019016166F016166F016166F016166F
21-HM Flange Bolts - prior to 12/2019016167F016167F016167F016167F
16-HM Flange Gasket 1 1/2" Connections - prior to 12/2019062236B062236B062236B062236B
12-HMDrain Valve013793F013793F013793F013793F
13-HMSensor Well003765F003765F003765F003765F
14-HMWell Retaining Clip300203300203300203300203
17-HMRear Drain Plug & Cover005264F005264F005264F005264F
19-HMAdapter CPVC 2"005393F005393F005393F005393F
26-HMAdapter - ProTek Shield (Includes 27-HM)018006F018006F018006F018006F
27-HMNut - ProTek Shield Adapter - 2-Pc018007F018007F018007F018007F
28-HMU.G./Bypass Assembly017958F017958F017962F017962F
**WARNING: The Hydraulic conditions or water chemistry that caused the tube bundle to fail have very likely also damaged the bypass valve and
Unitherm Governor. We recommend you replace the Unitherm Governor and inspect the bypass assembly. Failure to do so could cause premature
Units manufactured from 12/2019 (Brass)017983F017984F017985F017986F
Units manufactured prior to 12/2019 (Cast Iron)010051F016193F010053F010054F
Heat Exchanger Assy.Cupronickel ASME
Units manufactured from 12/2019 (Brass)017987F017988F017989F017990F
Units manufactured prior to 12/2019 (Cast Iron)010360F010361F010362F010363F
Units manufactured from 12/2019 (Brass)017961F017961F017992F017992F
Units manufactured prior to 12/2019 (Cast Iron)006730F006730F006730F006730F
Inlet/Outlet Header ASME
Units manufactured from 12/2019 (Brass)017966F017966F017966F017966F
Units manufactured prior to 12/2019 (Cast Iron)012319F012319F012319F012319F
Flange Gasket 2" Connections - prior to 12/2019800080B800080B800080B800080B
Units manufactured from 12/2019 (Brass)017973F017973F017973F017973F
Units manufactured prior to 12/2019 (Cast Iron)006731F006731F006731F006731F
Units manufactured from 12/2019017974F017975F017976F017977F
Units manufactured prior to 12/2019010055F006733F010057F010058F
Tube Bundle Cupronickel ASME **
Units manufactured from 12/2019017978F017979F017980F017981F
Units manufactured prior to 12/2019010368F010369F010370F010371F
Stud Bolt Kit
Units manufactured from 12/2019017982F017982F017982F017982F
Units manufactured prior to 12/2019007870F007870F007870F007870F
Units with Plastic Bypass Valve
Units with Brass Bypass Valve (Units manufactured to 3/5/17)013794F013794F013794F013794F
1-RRefractory Common (Left & Right) 010079F010079F010079F010079F2-RRefractory Uncommon (Front and Rear)010080F010081F010082F010083F3-RRefractory Retainer Kit 010262F010263F010264F010265F
SSHEETMETAL
1-SJacket Top (Louvered)010047F010048F010049F010050F2-SFlue Collector (Units with Polymer Header)010063F010064F010065F010066F
Flue Collector (Units with Metal Header)010067F010068F010069F010070F
3-SDoor Assy.
Raypak Cool Dark & Warm Dark Gray013871F013872F013873F013874F Green010267F010268F010269F010270F Rheem Cool Dark & Warm Dark Gray013875F013876F013877F013878F Green010271F010272F010273F010274F Ruud Cool Dark & Warm Dark Gray (Units mfd after to 9/2012)013871F013872F013873F013874F Warm Dark Gray (Units manufactured prior to 9/2012)013879F013880F013881F013882F Green010271F010272F010273F010274F JacuzziN/A016700FN/A016701F
14-SScrew & Retainer006744F006744F006744F006744F
4-SAccess Panel Set (3 Pcs. Units with Polymer Header)010311F010311F010311F010311F
Access Panel Set -ASME Access Panel Set (3 Pcs. for BR Header)017967F017967F017967F017967F
Access Panel Set (3 Pcs. for CI Header) - prior to 12/2019010312F010312F010312F010312F5-SJacket Side Panel Right010313F010313F010313F010313F6-SJacket Side Panel Left010314F010314F010314F010314F7-SJacket Rear Panel (2 Pcs.)010315F010316F010317F010318F8-SPoolstat Cover/Lock0095050095050095050095059-SHigh Limit Cover010319F010319F010319F010319F10-SBase Heat Shield - prior to 10/2019010320F010320F010320F010320F11-SUp Front Control Panel
Green010321F010322F010323F010324F
Cool Dark Gray013887F013888F013889F013890F
Warm Dark Gray013891F013892F013893F013894F12-SHigh Limit Shield010342F010342F010342F010342F13-SWeather Shield010325F010326F010327F010328F