For your health and the protection of your pool equipment, it is essential that your
water be chemically balanced. The following levels must be used as a guide for balanced water.
Total Alkalinity (PPM)120 to 150120 to 15080 to 120
Calcium Hardness (PPM)200 to 300150 to 200200 to 400
Salt (PPM)4500 MAXIMUM4500 MAXIMUM4500 MAXIMUM
Free Chlorine (PPM)*2 to 32 to 32 to 3
Total Dissolved Solids (PPM) 3000 MAXIMUM** 3000 MAXIMUM**3000 MAXIMUM**
* Free Chlorine MUST NOT EXCEED 5 PPM!
** In salt water chlorinated pools, the total TDS can be as high as 6000 ppm.
• Occasional chemical shock dosing of the pool or spa water should not damage the
heater providing the water is balanced.
• Automatic chemical dosing devices and salt chlorinators are usually more efficient
in heated water, unless controlled, they can lead to excessive chlorine level whichcan damage your heater, and which is not covered under warranty. A check
valve should be installed between the heater outlet and a chlorinator or other chemical dosing device.
• Further advice should be obtained from your pool or spa builder, accredited pool
shop, or chemical supplier for the correct levels for your water.
Rev. 5 reflects the following:
Changes to: “Wiring Diagram” on page 32, “Illustrated Parts List” on page 44-46.
Additions: None
Deletions: None
2
CONTENTS
2Water Chemistry
4WARNINGS
4Pay Attention to These Terms
5PART ONE
OWNER'S OPERATING INSTRUCTIONS
5SECTION 1
START-UP PROCEDURES
6SECTION 2
CAUTION
6SECTION 3
MAINTENANCE & CARE PROCEDURES
7Lighting & Shutdown Instructions
8Pool & Spa Water Chemistry
8Automatic Chlorinators & Chemical Feeders
8Cold Weather Operation
8Winterizing the Pool & Spa Heater
9PART TWO
INSTALLATION & SERVICE INSTRUCTIONS
9SECTION 1
RECEIVING EQUIPMENT
10SECTION 2
GENERAL SPECIFICATIONS
10SECTION 3
INSTALLATION INSTRUCTIONS
10Code Requirements
11Clearances
11Outdoor Heater Installation
13Florida Building Code
14Indoor Heater Installation
14Specifications and Dimensions
16Combustion and Ventilation Air
16Direct Vent
17Venting
18Support of Vent Stack
18Vent Terminal Location
19Venting Installation Tips
19Venting Configurations
19Natural Draft Vertical Venting (Category I)
21Horizontal Through-the-Wall Direct Venting
33General Location of Controls
34Control Adjustments
34Control Panel Removal
35Thermostat Operation - Direct Spark Board
37Status and Diagnostics
38Remote Control Installation and Operation
38Remote Operation
38Activating the Remote
39Remote Control Wiring
392-Wire Remote Control
393-Wire Remote Control
40Time Clock / Fireman’s Switch
40High Limits
40Flow Switch
40Air Pressure & Blocked Vent Switches
41Visual Inspection
41Electrical
41Orifice Removal
41Igniter Removal
42SECTION 5
TROUBLESHOOTING
42Mechanical
43Control Logic - Flow Chart
44SECTION 6
REPLACEMENT PARTS
44Illustrated Parts List
45Part Numbers
47Important Instructions for the
Commonwealth of Massachusetts
3
WARNINGS—Pay Attention to These Terms
DANGER:
WARNING:
CAUTION:
NOTE:
DANGER: Failure to install the draft hood on indoor
installations and properly vent the heater to the
outdoors as outlined in the Venting section of this
manual can result in unsafe operation of the heater.
To avoid the risk of fire, explosion, or asphyxiation
from carbon monoxide, never operate this heater
unless it is properly vented and has an adequate air
supply for proper operation. Be sure to inspect the
vent system for proper installation at initial start-up;
and at least annually thereafter. Refer to the
Maintenance section of this manual for more
information regarding vent system inspections.
DANGER: Make sure the gas on which the heater
will operate is the same type as that specified on the
heater rating plate.
DANGER: When servicing or replacing components
that are in direct contact with the water, be certain
that:
• There is no pressure in the heater. (Pull the release
on the relief valve. Do not depend on the pressure
gauge reading).
• The heater water is not hot.
• The electrical power is off.
WARNING: All venting types must be of the same
material or product throughout the entire exhaust
installation to ensure proper securing and sealing.
Indicates the presence of immediate hazards which will cause severe
personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause
severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause
minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which
are important but not related to personal injury hazards.
WARNING: Both natural gas and propane have an
odorant added to aid in detecting a gas leak. Some
people may not physically be able to smell or
recognize this odorant. If you are unsure or
unfamiliar with the smell of natural gas or propane,
ask your local gas supplier. Other conditions, such
as "odorant fade," which causes the odorant to
diminish in intensity, can also hide, camouflage, or
otherwise make detecting a gas leak by smell more
difficult.
WARNING: UL recognized fuel gas detectors are
recommended in all enclosed propane and natural
gas applications wherein there is a potential for an
explosive mixture of fuel gas to accumulate and their
installation should be in accordance with the
detector manufacturer's recommendations and/or
local laws, rules, regulations, or customs.
WARNING - CALIFORNIA PROPOSITION
65: This product contains chemicals known to the
State of California to cause cancer, birth defects or
other reproductive harm.
WARNING: This product must be installed by a
licensed plumber or gas fitter when installed within
the Commonwealth of Massachusetts.
WARNING: Altering any Raypak pressure vessel
by installing replacement heat exchangers, tube
bundle headers, or any ASME parts not
manufactured and/or approved by Raypak will
instantly void the ASME and/or CSA ratings of the
vessel and any Raypak warranty on the vessel.
Altering the ASME and/or CSA ratings of the vessel
also violates national, state, and local approval
codes.
WARNING: Do not install within 3 feet of a heat
pump or an outdoor condensing unit. Strong air
intake from this type of equipment can disturb the
combustion process and cause damage or personal
injury.
WARNING: Do not use this heater if any part has
been under water. Immediately call a qualified
service technician to inspect the heater and to
replace any part of the control system and any gas
control which has been under water.
4
PART ONE
OFF
ON
OWNER'S OPERATING INSTRUCTIONS
FOR YOUR SAFETY - READ BEFORE OPERATING
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY
RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
INTRODUCTION
Your pool/spa heater has been designed for years of safe and reliable pool/spa water heating. It is available with
electronic ignition. This manual provides installation, operation, maintenance, and service information for these
heaters.
If your heater has been installed correctly, operating the heater is an easy task. The upper front panel of the
heater contains the control center that allows you to turn the heater On or Off and adjust the temperature settings for the pool or spa. The temperature range is factory set from 50°F (18°C) to 104°F (40°C). See figure
above for location of toggle switch to turn the heater On and Off. Section 4 of this manual contains more details
about the use of the controls in the Control Adjustments subsection (page 34).
SECTION 1 - START-UP PROCEDURE
1. Clean air louvers of dust, lint and debris.
2. Keep heater area clear and free from com-
bustibles, flammable liquids and chemicals.
3. Verify that the flow of combustion and ventilation
air is not obstructed.
4. Water must be flowing through the heater during
operation. Ensure that the system is filled with
water and the pump is operating. Double check
for any water leaks.
5. Purge air from the gas line. Insufficient purging
may keep the heater from lighting on the first try.
8. The unit comes wired for 240V/1ph/60Hz power. If
the supply voltage is nominally 120V/1ph/60Hz,
switch the blower harness located inside the cabinet (see wiring diagram).
9. If installed indoors, make sure flue gases are vent-
ed properly, and that combustion and makeup air
openings are adequate.
10. Locate and turn the gas valve ON.
11. Locate the plugged bleedle valve off the right side
of the gas valve.
12. Remove the bleedle plug and connect a manome-
ter to the valve.
13. Locate and flip the display lid upwards.
14. Turn the heater on, by pressing the ON/OFF tog-
gle switch on the front display.
15. Set the mode to either SPA or POOL.
16. If the set point is higher than the current temperature, the heater will begin its startup sequence.
17. The ignition control will verify that the blower air
switch is open before starting the blower. Once
proven open, the blower will be powered to start
the ignition sequence. Verify suction pressure
matches the table below, Blower Suction
Pressure, for your model heater during the prepurge period.
18. Once the blower air switch proves, a 45 second
pre-purge period will begin to purge residual
gases from the combustion chamber.
ModelElevationBlower Suction
0-2000 ft.-3.5 to -3.8 "WC
259
409
5
2000-5000 ft.-3.1 to -3.6 "WC
5000-7000 ft.-2.8 to -3.2 "WC
0-2000 ft.-3.7 to -4.0 "WC
2000-5000 ft.-3.3 to -3.8 "WC
5000-7000 ft.-3.0 to -3.4 "WC
Blower Suction Pressure
19. Once the pre-purge period ends, the igniter will
begin to spark just prior to the gas valve opening.
The gas valve will open for a 4 second trial for ignition. If flame is proven, the heater will operate to
meet heat demand. If flame is not proven, the
heater will enter a post-purge period and then retry
the ignition cycle or lockout, depending on the
heater configuration.
20. Once gas is flowing, the manometer reading will
drop to -0.40” +/- .1” WC. See the instructions on
page 40 for adjusting the valve manifold pressure
if the reading is not within tolerance.
21. Visually check through the sight glass that the
heater is on and heating. A yellowish glow coming
from the refractory indicates that the heater is running. The flame should be a blueish color.
22. Remove the manometer and replace with bleedle
plug.
23. Reinstall front door panel and knurled screw holding the door in place.
24. Feel the inlet and outlet pipes. Outlet pipe should
be only slightly warmer than the inlet. It should not
be hot.
SECTION 2 - CAUTION
Elevated water temperature can be hazardous. The
U.S. Consumer Product Safety Commission has these
guidelines:
1. Spa water temperatures should never exceed
104°F (40°C). A temperature of 100°F (38°C) is
considered safe for a healthy adult. Special caution
is suggested for young children.
5. Persons with a medical history of heart disease, circulatory problems, diabetes, or blood pressure
problems should obtain a physician's advice before
using pools or hot tubs.
6. Persons taking medications which induce drowsiness, such as tranquilizers, antihistamines, or anticoagulants, should not use spas or hot tubs.
SECTION 3 - MAINTENANCE AND
CARE PROCEDURES
WARNING: Check the heater for possible rodent
nests after long periods of non-use.
To be followed one month after start-up and then semiannually.
1. Inspect and operate all controls, gas valve and
pressure relief valve.
2. On indoor heaters, clean room intake openings to
ensure adequate flow of combustion and ventilation air.
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage
the heater and void the warranty.
3. Keep area around heater clear and free from com-
bustible materials, gasoline and other flammable
and corrosive vapors and liquids.
IF HEATER WILL NOT FIRE:
2. Drinking of alcoholic beverages before or during
spa or hot tub use can cause drowsiness which
could lead to unconsciousness and subsequently
result in drowning.
3. Pregnant Women Beware! Soaking in water over
102°F (39°C) can cause fetal damage during the
first three months of pregnancy resulting in the birth
of a brain-damaged or deformed child. Pregnant
women should stick to the 100°F (38°C) maximum
rule.
4. Before entering the spa or hot tub, users should
check the water temperature with an accurate thermometer; spa or hot tub thermostats may err in regulating water temperatures by as much as 4°F
(2.2°C).
If you have no electrical power, it may be that your
"circuit breaker" has tripped. Try re-setting it.
If you have electrical power but the heater will not fire
check the following or see Troubleshooting section:
1. The time clock must be in the "ON" position.
2. Your pump strainer basket may be full. If so
remove debris.
3. Your filter may be dirty. If so, backwash or clean
filter. (To tell if your filter is dirty, look to see if the
filter pressure will be higher than usual).
4. The pump may have lost its prime and be running
dry. Check the pressure on the filter. If there is no
pressure; then you are not moving water (or your
gauge is broken). Try to get the pump to run at its
normal flow rate.
6
WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control to the
heater.
CAUTION: Propane gas is heavier than air and will settle on the ground. Since propane can accumulate in
confined areas, extra care should be exercised when lighting propane heaters.
7
POOL & SPA WATER CHEMISTRY
Chemical imbalance can cause severe damage to
your heater and associated equipment. Maintain
your water chemistry according to the chart on page 2.
If the mineral content and dissolved solids in the water
become too high, scale forms inside the heat exchanger tube, reducing heater efficiency and damaging the
heater. If the pH drops below 7.2, this will cause corrosion of the heat exchanger and severely damage the
heater. Heat exchanger damage resulting from
chemical imbalance is not covered by the warranty.
COLD CLIMATE: Prolonged operation with water
temperatures below 50°F is not recommended.
When starting the heater with water temperatures
below 50°F, operate the heater continuously until
higher temperatures are reached. Operating the
heater for prolonged periods with pool water below
50°F can seriously damage the heater, and is not covered by the warranty.
For cold climate areas, please follow the winterizing
procedures listed.
WINTERIZING THE POOL & SPA HEATER
AUTOMATIC CHLORINATORS AND
CHEMICAL FEEDERS
All chemicals must be introduced and completely diluted into the pool or spa water before being circulated
through the heater. Do not place sanitizing chemicals
in the skimmer. High chemical concentrations will
result when the pump is not running (e.g. overnight).
Chlorinators must feed downstream of the heater and
have an anti-siphoning device to prevent chemical
back-up into the heater when the pump is shut off. A
check valve should be installed between the heater
outlet and the chlorinator.
See plumbing diagrams on page 30 and 31.
NOTE: High chemical concentrates from feeders and
chlorinators that are out of adjustment will cause rapid
corrosion to the heat exchanger. Such damage is not
covered under the warranty.
COLD WEATHER OPERATION
IMPORTANT FREEZE INFORMATION
Heaters installed outdoors in freezing climate areas
may be shut down for the winter. Observe the following procedure for winterizing the heater:
1. Turn off gas valve, manual gas valve, and electri-
cal supply to the heater.
2. Open the drain valve located on the inlet/outlet
header (at the lowest point). Pull the PRV handle
upwards to allow air in while the water drains
through the valve.
MODERATE CLIMATE: Heater operation can continue during short-term cold spells. When temperatures
are between 0°F and 32°F, flow (continuous pump
operation) must be maintained.
CAUTION: Do not use the heater to maintain water
temperatures just above freezing or for freeze protection. When heater is used during freezing weather,
care must be taken to avoid freeze-ups. Continuous
pump operation is a must. Additional protection may
be required. The heater is not warranted against
freeze-ups.
8
PART TWO
LABEL ON CARTON
SERIAL NUMBER
The Model & Serial No.
can also be found inside
the bezel above the display
Model & Serial No.
Located on Rating
Plate
O-RING
SLIP
2” TAIL PIECE
2” RING NUT
VINYL GROMMET
CPVC NIPPLE
2” RING NUT
SLIP
2” TAIL PIECE
O-RING
BUTTRESS
TAIL PIECE
INSTALLATION AND SERVICE INSTRUCTIONS
SECTION 1 - RECEIVING EQUIPMENT
The manufacturer recommends that this manual be reviewed thoroughly before installing your pool/spa heater.
If there are any questions that this manual does not answer, please contact the factory or your local representative.
On receipt of your equipment it is suggested that you visually check for external damage to the carton. If the
carton is damaged, a note should be made on the Bill of Lading when signing for the equipment. Remove the
heater from the carton. If it is damaged, report the damage to the carrier immediately. Save the carton.
These items are shipped inside a box in the carton with the heater:
STANDARD UNIT
1. Plastic pipe finish flange for gas line6. (2) 2” CPVC Ring Nuts
2. Bonding lug with mounting screw 7. (2) “O” rings
Be sure that you receive the number of packages indicated on the Bill of Lading.
When ordering parts, you must specify the model and serial numbers of the heater. See below for location of
serial number. When ordering under warranty conditions, you must also specify date of installation.
9
SECTION 2 - GENERAL SPECIFICATIONS
These heaters are design-certified and tested under the latest requirements of the ANSI Z21.56 / CSA 4.7
Standard for Gas-Fired Pool Heaters. All heaters can be used either indoor or outdoors.
Ambient Temperature Rating of Heater Components
Electronic Ignition Heater*-32°F to + 175°F
*Requires 120 or 240VAC Single-Phase 60 Hertz Power Supply
Rated inputs are suitable for up to 2,000 feet elevation. The input will be reduced by approximately 4% for each
1,000 feet above 2,000 feet, as high elevation reduces gas and air density.
SECTION 3 - INSTALLATION INSTRUCTIONS
CALIFORNIA PROPOSITION 65 WARNING: This product contains chemicals known to the State of California
to cause cancer, birth defects or other reproductive harm.
WARNING: This unit contains refractory ceramic fiber (RCF) insulation in the combustion chamber. RCF, as
manufactured, does not contain respirable crystalline silica. However, following sustained exposure to very
high temperatures (>2192°F), the RCF can transform into crystalline silica (cristabolite). The International
Agency for Research on Cancer (IARC) has classified the inhalation of crystalline silica (cristabolite) as carcinogenic to humans.
When removing the burner or heat exchanger, take precautions to avoid creating airborne dust and avoid
inhaling airborne fibers. When cleaning spills, use wet sweeping or High Efficiency Particulate Air (HEPA)
filtered vacuum to minimize airborne dust. Use feasible engineering controls such as local exhaust ventilation
or dust collecting systems to minimize airborne dust. Wear appropriate personal protective equipment
including gloves, safety glasses with side shields, and appropriate NIOSH certified respiratory protection, to
avoid inhalation of airborne dust and airborne fiber particles.
IMPORTANT NOTICE
These instructions are intended only for the use by qualified personnel, specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation
and service personnel may be required by some states to be licensed. If your state is such, be sure your contractor bears the appropriate license. Persons not qualified shall not attempt to fix this equipment nor attempt
repairs according to these instructions.
WARNING: Improper installation, adjustment, alteration, service or maintenance may damage the equip-
ment, create a hazard resulting in asphyxiation, explosion or fire, and will void the warranty.
CODE REQUIREMENTS
NOTE: The heater should not be located in an area where possible water leakage will result in damage to the
area adjacent to the heater or to the structure. When such locations cannot be avoided, it is recommended that
a suitable drain pan, with adequate drainage, be installed under the heater. The pan must not restrict combustion air flow.
Installation must be in accordance with local codes, or, in the absence of local codes, with the latest edition of
the National Fuel Gas Code, ANSI Z223.1/NFPA54 and National Electrical Code, ANSI/NFPA 70, and for
Canada, the latest edition of CAN/CSA-B149 Installation Codes, and Canadian Electrical Code, CSA C22.1
Part1 and Part 2.
10
CLEARANCES
ALL HEATERS
For clearances from combustible surfaces, see the
chart below.
CLEARANCE FROM
COMBUSTIBLE CONSTRUCTION
When installed according to the listed minimum clearances from combustible construction, the pool heater
can still be serviced without removing permanent
construction around the heater.
INDOOR INSTALLATIONS:
Top* - 30” Back - 1”
Front - Alcove (Open) Right Side - 1”
Vent - 1”Left Side - 1”
Floor** - 0”
OUTDOOR INSTALLATION - TOP EXHAUST
Top* - Unobstructed (Outdoor Stack)
Floor - 0”Right Side - 8”
Back - 6”Left Side - 8”
OUTDOOR INSTALLATION - REAR EXHAUST
Top* - Unobstructed
Floor - 0”Right Side - 8”
Back - 12”Left Side - 8”
*Clearance from top of vent terminal.
**Do not install on carpeting.
OUTDOOR HEATER INSTALLATION
These heaters are design-certified for outdoor installation, when equipped with the approved tops designated for
outdoor use.
However, for ease of servicing, Raypak recom-
mends a clearance of at least 24” in the front and
at least 18" on the water connection side. This will
enable the heater to be serviced in its installed location, that is, without movement or removal of the
heater.
The heater must be installed in a manner that will
enable the heater to be serviced without removing any
structure around the heater.
FLOORING: This heater can be installed on combustible flooring.
WARNING: The heater shall not be located in an area where water sprinklers, or other devices, may cause
water to spray through the cabinet louvers and into the heater. This could cause internal rusting or damage
electrical components, and void the warranty.
WARNING: Do not install within 3 feet of a heat pump or an outdoor condensing unit. Strong air intake from
this type of equipment can disturb the combustion process and cause damage or personal injury.
11
Heaters must not be installed under an overhang of less than three 3 ft from the top of the heater. Three sides
4 ft
Minimum
4 ft
Minimum
1 ft
Minimum
4 ft
Minimum
3 ft
Minimum
10 ft
Minimum
Forced Air Inlet
must be open in the area under the overhang. Roof water drainage must be diverted away from the heaters
installed under overhangs with the use of gutters.
For U.S. installations, the point from where the flue products exit the heater must be a minimum of 4 ft below,
4 ft horizontally from, or 1 ft above any door, window or gravity inlet into any building. The top surface of the
heater shall be at least 3 ft above any forced air inlet, or intake ducts located within 10 ft horizontally.
For installations in Canada, pool heaters shall not be installed with the top of the vent assembly within 10 ft
below, or to either side, of any opening into the building. Refer to the latest revisions of CAN/CSA-B149.
For installations in Florida and Texas, that must comply with the Florida or Texas Building Code, follow the
directions on page 13 for the installation of hurricane tie-down method for all models.
12
13
INDOOR HEATER INSTALLATION
ELECTRICAL REQUIREMENTS:
120V/1ph/60Hz 6A
240V/1ph/60Hz 3A
Locate the heater as close as is practical to a chimney or gas vent. The heater must always be vented to the
outside. See the Venting section (beginning on page 17) for details. Minimum allowable clearance is shown on
the nameplate, and in the “Clearances” section on page 11. Adequate combustion and ventilation air must be
provided. See page 16 for details.
SPECIFICATIONS AND DIMENSIONS
Dimensions (in.)
Shipping
Flue
Heater
Model
BR-259250.06”4”25125193
BR-409399.06”4”40125205
Notes:
1.The model number prefix indicates: (B=Bronze header), (R=Raypak) Model number suffix indicates: pilot
type (E = digital) and fuel type (P = propane, N = natural gas) fin tubing (X=Cupro-Nickel, C= Copper).
Example: Model number BR-409-EN-X indicates a unit with digital (IID) ignition using natural gas with
bronze headers and cupro-nickel tubes.
2.Ratings are for natural gas and elevations up to 2,000 feet above sea level. For elevations over 2,000 feet,
consult the factory.
3.Flue gases must be properly vented with CAT I vertical venting or CAT III horizontal venting. Non-metallic
venting not acceptable. Inlet air can be ducted with 4” metal or PVC pipe. See the venting section of this
manual for complete venting details.
MBTU
Input
Diameter
(B)
Air Inlet
(C)
Minimum
Flow
(gpm)
Maximum
Flow
(gpm)
Weight (lbs)
w/ Stackless
Top
14
U.S. Installations
1
Canadian Installations
2
A
Clearance above grade, veranda, porch,
deck, or balcony
1 ft (30 cm) 1 ft (30 cm)
B
Clearance to window or door that may be
opened
4 ft (1.2m) below or to side
of opening; 1 foot (30 cm)
above opening
3 ft (91 cm)
C Clearance to permanently closed window * *
D
Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance of 2 ft (61cm) from the centerline of the
terminal
5 ft (1.5m) *
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner 6 ft (1.83m) *
H
Clearance to each side of center line extended above meter/regulator assembly
*
I Clearance to service regulator vent outlet * 3 ft (91cm)
J
Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any
other appliance
4 ft (1.2m) below or to side
of opening; 1 ft (30 cm)
above opening
3 ft (91 cm)
K Clearance to mechanical air supply inlet
3 ft (91 cm) above if within
10 ft (3m) horizontally
6 ft (1.83m)
L
Clearance above paved sidewalk or paved
driveway located on public property
7 ft (2.13m) 7 ft (2.13m) t
M
Clearance under veranda, porch, deck or
balcony
* 12 in. (30 cm) TT
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code
2
In accordance with the current CAN/CSA-B149 Installation Codes
t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that se rves
both dwellings
TT Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of term inal and
underside of veranda, porch, deck or balcony is greater than 1 ft (30cm)
* Clearances in accordance with local installation codes and the requirements of the gas supplier
3 ft (91 cm) within a
height 15 ft above the
meter/regulator assembly
Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations
Vent/Air Inlet Termination Clearances
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.