Raypak B-21, B-23, B-26, B-27 User Manual

Job: Engineer: Contractor: Prepared By: Date:
TempTracker is designed to sequence multiple boilers up to four total stages, whether it’s one to four on/off boilers, two two-stage boilers, or one boiler with up to four stages. It is available factory-mounted or loose on Hi Delta boilers, and loose on Raytherm boilers. This control can be used for space heating and hot water supply with six application-specific modes to meet various applications, including outdoor reset for heating systems. It monitors and displays inlet and outlet temperatures on all applications as well as monitors outdoor temperature when an outdoor reset mode is utilized.
Features
1-4 boilers/stages
Selectable P or PID logic
LCD display
NEMA 1 enclosure
Boiler-in and boiler-out water sensors
System water sensor
Outdoor air sensor
(Models B-27 and B-23)
Alarm ready (pilot duty)
24 VAC, 60 Hz, 3 VA Supply Power
Relay Ratings
Stage 1: 5A @ 120 VAC Stages 2 to 4: 3A @ 120 VAC
TempTracker
2- and 4-Stage Controllers
For Hi Delta® and Raytherm
Boilers & Water Heaters
Programmable Functions
6 programming modes
Adjustable outdoor reset
Min. system water temperature (70 °F)
Max. system water temperature
o Heating – 220 °F o DHW – 190 °F
Temperature differential (2 to 42 °F)
Boiler target (70 to 220 °F)
Outdoor cutoff (35 to 85 °F)
Boiler mass (low, med, high)
Stage-on delay (P mode)
(10 sec. to 8 min.)
System pump-off delay (0 to 20 min.)
Temperature measurement (°F or °C)
Model Information
B-26 2-stage setpoint B-27 2-stage outdoor reset B-21 4-stage setpoint B-23 4-stage outdoor reset
®
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (800) 872-9725 www.raypak.com
Catalog No.: 5100.30A Effective: 2-1-08 Replaces: 8-1-07