WARNING: If the information in these instructions
are not followed exactly, a fire or explosion may
result causing property damage, personal injury or
death.
les instructions données dans cette notice pour
réduire au minimum le risqué d’incendie ou
d’explosion ou pour éviter tout dommage matériel,
toute blessure ou la mort.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids or other
combustible materials in the vicinity of this or any
other appliance. To do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.•
Do not touch any electrical switch; do not use•
any phone in your building.
Immediately call your gas supplier from a•
neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the•
fire department.
Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
Ne pas entreposer ni utilizer d’essence ou ni
d’autres vapeurs ou liquids inflammables à proimité de cet appareil ou de tout autre appareil.
CE FAIRE SI VOUS SENTEZ UNE ODEUR
DE GAS:
Ne pas tenter d’allumer d’appareil. •
Ne touchez á aucun interrupteur; ne pas vous•
server des téléphones se trouvant dans la
bâtiment.
Appelez immédiatement votre fournisseur de•
gaz depuis un voisin. Suivre les instructions
du fournisseur.
Si vous ne pouvez rejoinder le fournisseur,•
appelez le service es incendies.
L’installation et l’entretien doivent être assurés par
un installeur qualifié ou par le fournisseur de gaz.
Rev. 3 reflects the following:
Changes to: Minor changes to pages 8, 17, 22, 29, 37, 38, 39, 40, 52, 55, 58, 59, 66 and 67. Updated Wiring Diagram
on page 47.
Additions: Information under Condensate Management on page 37.
Deletions: Information under Ignition Control Functions on page 39.
2
Page 3
CONTENTS
WARNINGS 4
Pay Attention to These Terms4
BEFORE INSTALLATION 5
Product Receipt5
Model Identification6
Ratings and Certifications6
Installations at Elevation6
Component Locations7
General Information7
BOILER DIMENSIONS 8
Time/Temperature Relationships
in Scalds9
INSTALLATION 9
Installation Codes9
Equipment Room10
Clearances10
Combustion and Ventilation Air11
Direct Vent14
Conventional Combustion Air Supply14
Water Piping15
Hydronic Heating16
System Sensor Installation16
Applications and Modes17
Heater Flow Rates and Pressure Drops17
MODE 1 Water Plumbing18
MODE 2 Water Plumbing19
MODE 3 Water Plumbing20
Gas Supply21
Gas Supply Connection21
Equivalent Pipe Length21
Gas Supply Pressure22
Electrical Power Connections22
Making the Electrical Connections23
Field Wiring Connections24
Heating System Sensor Installation25
Venting28
Venting Installation Tips31
Venting Configurations31
Condensate Management37
Freeze Protection38
Controls39
Outdoor Reset Concept45
WIRING DIAGRAM 47
Converting Natural to Propane Gas48
Gas Valve & Combustion Settings49
START-UP 50
Pre Start-up51
Pre Start-up Check51
Initial Start-up51
Preparation51
Start-Up52
Lighting Instructions54
To Turn Off Gas to Appliance54
TROUBLESHOOTING 55
XPak FT Error Codes55
Heater Errors55
Heater Faults55
Sensor Resistance Values55
XPak FT Fault Text56
Inside Air Contamination61
Important Instructions for the
Commonwealth of Massachusetts62
WARRANTY 63
START-UP CHECKLIST 64
ILLUSTRATED PARTS LIST 65
3
Page 4
WARNINGS
Pay Attention to These Terms
ndicates the presence of immediate hazards which will cause severe
DANGER:
I
personal injury, death or substantial property damage if ignored.
WARNING:
CAUTION:
NOTE:
DANGER: Make sure the gas on which the boiler
will operate is the same type as that specified on the
boiler rating plate.
WARNING: Should overheating occur or the gas
supply valve fail to shut, do not turn off or disconnect
the electrical supply to the boiler. Instead, shut off
the gas supply at a location external to the boiler.
WARNING: Do not use this boiler if any part has
been under water. Immediately call a qualified
service technician to inspect the boiler and to
replace any part of the control system and any gas
control which has been under water.
WARNING: To minimize the possibility of improper
operation, serious personal injury, fire, or damage to
the boiler:
Indicates the presence of hazards or unsafe practices which could cause
severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause
minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which
are important but not related to personal injury hazards.
WARNING: Both natural gas and propane have an
odorant added to aid in detecting a gas leak. Some
people may not physically be able to smell or
recognize this odorant. If you are unsure or
unfamiliar with the smell of natural gas or propane,
ask your local gas supplier. Other conditions, such
as "odorant fade," which causes the odorant to
diminish in intensity, can also hide, camouflage, or
otherwise make detecting a gas leak by smell more
difficult.
WARNING: UL-recognized fuel gas detectors are
recommended in all enclosed propane and natural
gas applications wherein there is a potential for an
explosive mixture of fuel gas to accumulate and their
installation should be in accordance with the
detector manufacturer's recommendations and/or
local laws, rules, regulations, or customs.
•Always keep the area around the boiler free of
combustible materials, gasoline, and other
flammable liquids and vapors.
•Boiler should never be covered or have any
blockage to the flow of fresh air to the boiler.
WARNING: Vent connectors serving any other
appliances shall not be connected into any portion of
mechanical draft systems operating under a positive
pressure. If an XPak FT
an existing unit, the vent system MUST be verified to
be of the correct size and of one of the Category IV
vent materials identified in this manual. If it is NOT,
it MUST be replaced.
®
boiler is installed to replace
WARNING - CALIFORNIA PROPOSITION
65: This product contains chemicals known to the
State of California to cause cancer, birth defects or
other reproductive harm.
WARNING: This appliance produces condensate
from the flue products that is acidic and highly
corrosive. Raypak recommends the use of a
condensate neutralizer kit to avoid long-term
damage to the drainage system and to meet local
code requirements.
WARNING: Risk of electrical shock. More than one
disconnect switch may be required to de-energize
the equipment before servicing.
4
Page 5
CAUTION: This boiler requires forced water
circulation when the burner is operating. See
minimum and maximum flow rates. Severe damage
will occur if the boiler is operated without proper
water flow circulation.
OTE: When the boiler has been filled for the first
N
time or the system has been drained and refilled, it
will be necessary to release any air that may have
become trapped within the appliance heat
exchanger. Open the bleedle valve until all air is
purged.
AVERTISSEMENT: N’utilisez pas cette Chaudière
si une partie de celle-ci s’est retrouvée sous l’eau.
Appelez immédiatement un technician de service
qualifié pour inspecter la Chaudière et pour
remplacer toute partie du système de contrôle et
toute commande de gaz s’étant retrouvée sous
l’eau.
OTE: Minimum 18 AWG, 105°C, stranded wire
N
must be used for all low voltage (less than 30 Volts)
xternal connections to the unit. Solid conductors
e
should not be used because they can cause
xcessive tension on contact points. Install conduit
e
as appropriate. All high voltage wires must be the
same size (105°C, stranded wire) as the ones on the
unit or larger.
AVERTISSEMENT: En cas de surchauffe ou de
non fermeture de la vanne d’alimentation en gaz,
n’éteignez ou ne débranchez pas l’alimentation électrique de la chaudière. Coupez plutôt l’alimentation
en gaz á l’extérieur de la chaudière.
BEFORE INSTALLATION
Raypak strongly recommends that this manual be reviewed thoroughly before installing your XPak FT boiler.
Please review the General Safety information before installing the unit. Factory warranty does not apply to units
that have been improperly installed or operated. (Refer to the warranty at the back of this manual.) Installation
and service must be performed by a qualified installer, service agency or gas supplier. If, after reviewing this
manual, you still have questions which this manual does not answer, please contact your local Raypak representative or visit our website at www.raypak.com.
Thank you for purchasing a Raypak product. We hope you will be satisfied with the high quality and durability of
our equipment.
Product Receipt
On receipt of your unit it is suggested that you visually check for external damage to the shipping carton. If the
carton is damaged, make a note to that effect on the Bill of Lading when signing for the shipment. Next, remove
the boiler from the carton. Report any damage to the carrier immediately.
On occasion, items are shipped loose. Be sure that you receive the correct number of packages as indicated on
the Bill of Lading.
Claims for shortages and damages must be filed with the carrier by consignee. Permission to return goods must
be received from the factory prior to shipping. Goods returned to the factory without an authorized Returned
Goods Receipt number will not be accepted. All returned goods are subject to a restocking charge.
When ordering parts, you must specify the model and serial number of the boiler. When ordering under warranty
conditions, you must also specify the date of installation.
Purchased parts are subject to replacement only under the manufacturer’s warranty. Debits for defective
replacement parts will not be accepted. Parts will be replaced in kind only per Raypak’s standard warranties.
5
Page 6
Model Identification
he model identification number and boiler serial num-
T
ber are found on the rating plate located on the inside
upper right panel and also on inlet air decal. The
model number has the form H7-198AR or similar
epending on the unit size and configuration. The let-
d
ter in the first group of characters identifies the
application (H = Hydronic Heating). The number which
follows identifies the firing mode (7 = electronic modulation). The second group of characters identifies the
size of the unit (three numbers representing the
approximate MBTUH input), and, where applicable, a
letter indicating the manufacturing series.
Ratings and Certifications
Standards:
•ANSI Z21.13 · CSA 4.9 - latest edition, GasFired Hot Water Boilers
•SCAQMD Rule 1146.2
All units are National Board Registered, and designcertified and tested by the Canadian Standards
Association (CSA) for the U.S. and Canada. Each boiler is constructed in accordance with Section IV of the
American Society of Mechanical Engineers (ASME)
Boiler and Pressure Vessel Code and bears the ASME
“H” stamp. This boiler also complies with the latest edition of the ASHRAE 90.1 Standard.
by installing replacement heat exchangers or any
ASME parts not manufactured and/or approved by
Raypak will instantly void the ASME and CSA ratings
of the vessel and any Raypak warranty on the
vessel. Altering the ASME or CSA ratings of the
vessel also violates national, state, and local
approval codes.
Rated inputs are suitable for up to 2,000 ft elevation
without de-rating. Consult your local representative or
the factory for installations at altitudes over 2,000 ft
above sea level. No hardware changes are required
to the boilers for installations up to 10,000 ft (adjustments may be required).
6
Page 7
Component Location
General Information
AFUE Rating
Model
.
No
88AR17.0859512.01”½”½”2”/3”**2”/3”**
108AR22.01109513.01”½”½”3”3”
198AR39.81999528.41-1/4”¾”¾”3”3”
278AR55.02759536.61-1/4”¾”¾”3”3”
398A39.939996*39.91-1/2”¾”¾”3”/4”***3”/4”***
*Model 398A value is a Thermal Efficiency.
**Model 88AR has a 3" standard vent size, but can be reduced to 2" with a shorter run. (See page 31 for details)
***Model 398A has a 4" standard vent size, but can be reduced to 3" with a shorter run. (See page 31 for details)
use by individuals directly. A heat exchanger must
be used in conjunction with this boiler to meet DHW
needs.
Time/Temperature
Relationships in Scalds
The following chart details the relationship of water
temperature and time with regard to scald injury and
may be used as a guide in determining the safest
water temperature for your applications.
INSTALLATION
Installation Codes
Installations must follow these codes:
Local, state, provincial, and national codes, laws,•
regulations and ordinances
National Fuel Gas Code, ANSI Z223.1/NFPA 54 –•
atest edition (NFGC)
l
National Electrical Code, ANSI/NFPA 70 - latest•
edition (NEC)
Standard for Controls and Safety Devices for•
Automatically Fired Boilers, ANSI/ASME CSD-1,
(CSD-1) when required
For Canada only: CAN/CSA B149 Natural Gas•
and Propane Installation Code and CSA C22.1
C.E.C. Part 1 (C22.1)
CAUTION: This boiler should be located in an area
where water leakage will not result in damage to the
area adjacent to the appliances or to the structure.
When such locations cannot be avoided, it is
recommended that a suitable catch pan, adequately
drained, be installed under the appliance. The pan
must not restrict air flow.
Water Temp.
Time to Produce
Serious Burn
120°FMore than 5 minutes
125°F1-1/2 to 2 minutes
130°FAbout 30 seconds
135°FAbout 10 seconds
140°FLess than 5 seconds
145°FLess than 3 seconds
150°FAbout 1-1/2 seconds
155°FAbout 1 second
Table courtesy of The Shriners Burn Institute
Table D: Time to Produce Serious Burn
9
Page 10
Fig 4: Wall Mount Installation
Equipment Room
Install CO detectors per local regulations. Boiler
requires yearly maintenance, see chapter “Checks,
adjustments and fault finding”.
Operating Limits of the boiler:
Max. Boiler Outlet Temperature: 200°F (99°C)
Max. Operating Pressure: 80 psi (5.5 bar)
The hot water distribution system must comply with all
applicable codes and regulations. When replacing an
existing boiler, it is important to check the condition of
the entire hot water distribution system to ensure safe
operation.
In addition, the unit shall be installed such that the gas
ignition system components are protected from water
(dripping, spraying, rain, etc.) during appliance operation or service.
NOTE: Use of this boiler in construction areas
where fine particulate matter, such as concrete or
dry-wall dust, is present may result in damage to the
boiler that is not covered by the warranty. If operated
in a construction environment, a clean source of
combustion air must be provided directly to the
boiler.
Clearances
Indoor Installations
When installed according to the listed minimum clearances from combustible construction, these boilers
can be serviced without removing permanent structural construction around the unit. However, for ease of
servicing, we recommend a clearance of at least 24 in.
in front, on the rear and 24 in. above the top of the boiler. This will allow the unit to be serviced in its installed
location without movement or removal of the heater.
Service clearances less than the minimum may
require removal of the unit to service either the heat
exchanger or the burner components. In either case,
the boiler must be installed in a manner that will enable
the unit to be serviced without removing any structure
around the boiler.
Min.
Boiler Side
Clearances
from
Combustible
Minimum
Service
Clearances
Surfaces
Right Side0”1”
Left Side0”1”
Top0”24”
FrontOpen24”
Vent1”1”
Bottom6”12”
Table E: Clearances — Indoor Installations
10
Page 11
ombust
C
it
n
u
is
Th
t
n
o
c
-
n
o
n
ip
u
q
e
d
n
a
c
ia
v
d
lie
p
o
r
f
n
w
a
r
d
ia
v
r
o
,
r
e
r
f
ly
t
c
e
ir
d
u
q
e
r
e
h
t
a
d
a
n
a
C
(
T
AU
C
min
a
t
n
o
c
ma
a
d
n
a
c
p
p
A
e
h
t
TE: It
NO
ed
insulat
and
ion
p
p
u
s
e
b
t
s
mu
t
ir
a
d
e
t
a
min
a
t
ila
t
n
e
v
t
n
me
l me
a
n
io
t
n
e
v
n
o
imme
a
e
r
a
e
h
t
m
w
,
t
n
e
v
t
c
e
ir
d
A
.
e
id
s
t
u
o
m
o
f
o
s
t
n
me
e
ir
l c
a
c
ll lo
a
d
n
a
,
)
mb
o
C
:
N
O
I
r
o
c
y
b
d
e
t
a
ile
o
b
e
h
t
e
g
)
.
ix
d
n
e
is reco
in cold climates t
mmended that the in
Vent
h
it
w
d
lie
o
p
p
u
s
o
mb
o
C
.
n
io
w
s
n
a
e
t
ia
d
o
c
e
r
e
h
lla
a
t
s
in
ll
FG
N
e
h
t
.
s
e
d
o
a
n
io
t
s
u
c
e
iv
s
o
r
o
v
d
n
a
r
o minimize swe
s
h
ly
t
h
t
r
u
e
mb
io
e
id
u
s
ir
ic
f
f
r
p
io
t
s
c
e
r
r
r
u
s
u
s
n
C
mu
mic
e
h
t
ila
ie
p
o
a
n
o
u
o
io
t
mu
U
(
l
a
w
t
n
e
mb
n
n
s
S.
.
f
a
r
ir
s
t
ion
t
a
u
q
o
c
a
c
s
u
g
in
d
is
ir
a
mp
o
c
t
)
n
t
me
u
n
a
r
r
ke ven
a
ating.
n
mb
b
n
io
t
t
r
o
s
t
o
y.
t
h
it
n
d
A
ie
s
u
s
e
a
e
r
ly
B1
b
t
w
(
s
t
ir
b
a
w
h
S
be
t
ir
f
o
n
io
-
p
u
is
-
il
o
n
w
h
it
9
4
e
h
ic
e
e
Venting not shown for clarity. Boiler must be vented per
instructions in this manual
Fig. 5: Minimum Clearances from Combustible
Surfaces
Fig 6: Indoor Air Duct
11
Page 12
Fig 7: Two Vertical Air Ducts - Floor
Fig 8: Single Air Duct
Fig 9: Two Vertical air Ducts - Ceiling
Fig 10: Two Horizontal Air Ducts
12
Page 13
U.S. Installations
1
Canadian Installations
2
A
Clearance above grade, veranda, porch,
deck, or balcony
1 ft (30 cm) 1 ft (30 cm)
B
Clearance to window or door that may be
opened
4 ft (1.2 m) below or to side
of opening; 1 foot (30 cm)
above opening
3 ft (91 cm)
C Clearance to permanently closed window * *
D
Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance of 2 ft (61cm) from the centerline of the
terminal
5 ft (1.5 m)*
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner 6 ft (1.83 m)*
H
Clearance to each side of center line extended above meter/regulator assembly
*
3 ft (91 cm) within a height
15 ft above the me-
ter/regulator assembly
I Clearance to service regulator vent outlet * 6 ft (1.83 m)
J
Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any
other appliance
4 ft (1.2 m) below or to side
of opening; 1 ft (30 cm)
above opening
3 ft (91 cm)
K Clearance to mechanical air supply inlet
3 ft (91 cm) above if within
10 ft (3 m) horizontally
6 ft (1.83 m)
L
Clearance above paved sidewalk or paved
driveway located on public property
7 ft (2.13 m)
7 ft (2.13 m) t
M
Clearance under veranda, porch, deck or
balcony
* 12 in. (30 cm) TT
1
In accordance with the current ANSI Z223.1/NFPA 54 N ational Fuel Gas Code
2
In accordance with the current CAN/CSA-B149 Installation Codes
t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single-family dwellings that serves
both dwellings
TT Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of term inal and
underside of veranda, porch, deck or balcony is greater than 1 ft (30 cm)
* Clearances in accordance with local installation codes and the requirements of the gas supplier
Fig. 11: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations
Table F: Vent/Air Inlet Termination Clearances
13
Page 14
Direct Vent
If outside air is drawn through the intake pipe directly
o the unit for combustion:
t
1. Install the combustion air ducting kit.
. Install combustion air direct vent in accordance
2
with Fig. 24 (horizontal) or Fig. 26 (vertical) of this
manual.
3. Ventilation of the space occupied by the boiler(s)
is recommended and can be provided by an opening(s) for ventilation air at the highest practical
point communicating with the outdoors. The total
cross-sectional area should be at least 1 in² of free
area per 20,000 BTUH (111 mm² per kW) of total
input rating of all equipment in the room when the
opening is communicating directly with the outdoors or through vertical duct(s). The total
cross-sectional area should be at least 1 in² of free
area per 10,000 BTUH (222 mm² per kW) of total
input rating of all equipment in the room when the
opening is communicating with the outdoors
through horizontal duct(s). Damage to the equipment due to inadequate ventilation of the space is
not a warrantable failure.
4. In cold climates, and to mitigate potential freezeup, Raypak highly recommends the installation of
a motorized sealed damper on the air intake to
prevent the circulation of cold air through the boiler
during non-operating hours.
Conventional Combustion Air
Supply
U.S. Installations
All Air from Inside the Building
The confined space shall be provided with TWO permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for a
room large in comparison (NFGC). The total input of all
gas utilization equipment installed in the combined
space shall be considered in making this determination. Each opening shall have a minimum free area
of 1 in.2 per 1,000 BTUH (2,225 mm2 per kW) of the
total input rating of all gas utilization equipment in the
con- fined space, but not less than 100 in.2 (645 cm2).
One opening shall commence within 12 in. (305 mm)
of the top, and one opening shall commence within 12
in. (305 mm) of the bottom of the enclosure. The minimum dimension of air openings shall be not less than
3 in. (76 mm) in any direction.
ll Air from Outdoors
A
The confined space shall communicate with the out-
oors in accordance with one of the methods below.
d
The minimum dimension of air openings shall not be
less than 3 in. (76 mm) in any direction. Where ducts
are used, they shall be of the same cross-sectional
rea as the net free area of the openings to which they
a
connect.
1. Two permanent openings, one commencing
within 12 in. (305 mm) of the top, and one commencing within 12 in. (305 mm) of the bottom of
the enclosure, shall be provided. The openings
shall communicate directly, or by ducts, with the
outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
a. Where directly communicating with the out-
doors or where communicating to the
outdoors through vertical ducts, each open-ing shall have a minimum free area of 1 in.
per 4,000 BTUH (550 mm2per kW) of total
input rating of all equipment in the enclosure.
b. Where communicating with the outdoors
through horizontal ducts, each opening shall
have a minimum free area of 1 in.2per 2,000
BTUH (1,100 mm2per kW) of total input rating of all equipment in the enclosure.
2. One permanent opening, commencing within 12
in. (305 mm) of the top of the enclosure, shall be
permitted where the equipment has clearances of
at least 1 in. (25 mm) from the sides, top and bottom and 6 in. (152 mm) from the front of the
appliance. The opening shall directly communicate with the outdoors or shall communicate
through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the
outdoors, and shall have a minimum free area of:
a. 1 in.2per 3,000 BTUH (740 mm2per kW) of
the total input rating of all equipment located in
the enclosure, and
b. Not less than the sum of the areas of all vent
connectors in the confined space.
WARNING: Do not use the “one permanent
opening” method if the equipment room is under
negative-pressure conditions.
2
14
Page 15
Canadian Installations
. Ventilation of the space occupied by the boiler
1
shall be provided by an opening(s) for ventilation
air at the highest practical point communicating
with the outdoors. The total cross-sectional area of
uch an opening(s) shall be at least 10% of the
s
area required in 2. and 3. (below), but in no case
shall the cross-sectional area be less than 10 in.2
(65 cm2).
CAUTION: All combustion air must be drawn from
the air outside of the building; the mechanical equipment room must communicate directly with the
outdoors.
2. For boilers using a barometric damper in the vent
system, there shall be a permanent air supply
opening(s) having a cross section area of not less
than 1 in.
to and including 1 million BTUH, plus 1 in.2per
14,000 BTUH (160 mm2per kW) in excess of 1
million BTUH. This opening(s) shall be either
located at or ducted to a point not more than 18 in.
(450 mm) nor less than 6 in. (152 mm) above the
floor level. The duct can also “goose neck” through
the roof. The duct is preferred to be straight down
and terminated 18 in. (450 mm) from the floor, but
not near piping. This air supply opening requirement shall be in addition to the air opening for
ventilation air required in 1. (above).
3. For heaters when air supply is provided by natural
air flow from outdoors for a power burner and
there is no draft regulator, drafthood or similar flue
gas dilution device installed in the same space, in
addition to the opening for ventilation air required
in 1., there shall be a permanent air supply opening(s) having a total cross-sectional area of not
less than 1 in.2for each 30,000 BTUH (74 mm2per
kW) of total rated input of the burner(s), and the
location of the opening(s) shall not interfere with
the intended purpose of the opening(s) for ventilation air referred to in 1. This opening(s) can be
ducted to a point not more than 18 in. (450 mm)
nor less than 6 in. (152 mm) above the floor level.
The duct can also “goose neck” through the roof.
The duct is preferred to be straight down 18 in.
(450 mm) from the floor, but not near piping.
WARNING: Care must be taken to ensure that the
equipment room is not under negative pressure
conditions.
2
per 7,000 BTUH (320 mm2per kW) up
Water Piping
NOTE: Refer to the VERSA IC®Applications Guide
(Catalog #5000.72) for detailed instructions regarding the various applications supported by the
ERSA IC control system.
V
General
The boiler should be located so that any water leaks
will not cause damage to the adjacent area or structures.
CAUTION: This boiler requires forced water
circulation when the burner is operating. See Table H
for minimum and maximum flow rates. The pump
must be interlocked with the boiler to prevent heater
operation without water circulation.
WARNING: Pressure relief valve discharge piping
must be piped near the floor and close to a drain to
eliminate the potential of severe burns. Do not pipe
to any area where freezing could occur. Refer to
local codes.
Relief Valve Installation and Piping
The boiler is supplied with a Section IV “H” stamped
relief valve sized for the full input of the unit. Relief
valve discharge piping shall provide no less than the
cross-sectional area of the relief valve outlet and must
be routed to a safe point of discharge. Installation must
comply with all national, state and local codes.
Temperature & Pressure Gauge
The temperature and pressure gauge is shipped loose
for field installation and must be installed within 12
inches of the boiler outlet (if possible) in an easily
readable location. Installation must comply with ASME
Section IV as well as all applicable national, state and
local codes.
Hydrostatic Test
Unlike many types of heaters, this boiler does not require hydrostatic testing prior to being placed in operation. The heat exchanger is ASME certified for 80 PSI
maximum working pressure. However, Raypak does
recommend hydrostatic testing of the piping connections to the unit and the rest of the system prior to
operation. This is particularly true for hydronic systems using expensive glycol-based anti-freeze.
Raypak recommends conducting the hydrostatic test
before connecting gas piping or electrical supply.
4. Refer to the B149 Installation Code for additional
information.
15
Page 16
eaks must be repaired at once to prevent damage to
L
the heater. NEVER use petroleum-based stop-leak
compounds.
o perform hydrostatic test:
T
. Connect fill water supply. With bleed valve open,
1
fill boiler with water. When water flows from bleed
valve, shut off water. Close bleed valve. Carefully
fill the rest of the system, making sure to eliminate
any entrapped air by using high-point vents. Close
feed valve. Test at standard operating pressure for
at least 24 hours.
2. Make sure constant gauge pressure has been
maintained throughout test.
3. Check for leaks. Repair if found.
Hydronic Heating
Pump Selection
In order to ensure proper performance of your boiler
system, you must install a correctly-sized pump. Raypak recommends designing for a ∆T within the range
of 20°F to 60°F (8°C to 19°C). See Table H for acceptable flow rates for each model (∆T is the temperature
difference between the inlet and outlet water when the
heater is firing at full rate).
System Sensor Installation
The System Sensor (S3) is required for all selectable
modes unless the unit’s firing rate will be controlled by
an external source such as our Temp Tracker MOD+
Hybrid sequencer. Proper placement and method of
installation are critical for proper operation of the system. (See Fig. 12) The sensor must be installed in a
drywell in conjunction with heat conductive compound
as shown in the following images. The drywell must be
installed no more than 5 equivalent feet of pipe/tubing
downstream of the de-coupler and installed in such a
way that ensures the sensor bulb is in the flow path.
CAUTION: Be careful when installing the drywell
not to over-tighten the well as this can damage the
well and may prevent the sensor from fitting properly.
NPT
Fitting
Thermal
Paste
Drywell
System
Sensor (S3)
Boiler
Model
Standard Boiler Pump*
PumpHP
H7-88ARTACO 0071/25
H7-108ARTACO 0071/25
H7-198ARTACO 0101/8
H7-278ARTACO 0121/8
H7-398ATACO 0121/8
* Pump selection based on 30° ∆T with up to 50 eq. ft. of tubing.
Table G: Pump Selection
NOTE: The 50 eq. feet of tubing typically represents
25 linear feet of tubing and 25 eq. feet of fittings.
Fig 12: System Sensor Installation
Three-Way Valves
Three-way valves intended to regulate system water
temperatures by reducing flow in the boiler should not
be used.
16
Page 17
Applications & Modes
The VERSA IC Control system is designed for a wide
range of applications. The installer/design engineer
should refer to the following Modes to determine which
best fits the intended application and functionality for
he unit being installed.
t
The XPak FT has three modes available to them to
address the various applications the units can be
applied to.
Mode 1
This mode is for hydronic heating systems with single
or multiple boilers (Maximum 4 boilers) in primary/secondary piping configuration with or without Outdoor Air
Reset (S4). The system temperature is controlled by
the System sensor (S3). The Boiler Pump (P1) runs
during any call for heat. The System Pump (P2) runs
whenever the system is enabled for heating and the
outdoor air temperature is lower than the warm weather shut down (WWSD) temperature setting (if utilized).
The Boiler Pump and System Pump are delayed “off”
as user-defined in the ADJUST menu. See Fig. 13 for
piping example.
Mode 2
This mode is for hydronic heating systems with single
or multiple boilers (Maximum 4 boilers) in primary/secondary piping configuration with or without Outdoor Air
Reset (S4) with indirect DHW on the system loop (with
or without priority). The system temperature is controlled by the System sensor (S3). The Indirect DHW
sensor (S5) determines the indirect call/tank setpoint.
The system temperature is boosted to Target Max
when using the Indirect DHW sensor (S5) during an
indirect call for heat. Priority mode toggles off the
System Pump (P2) when an indirect call for heat is
present. The Boiler Pump (P1) runs during any call for
heat. The Indirect DHW Pump (P3) runs during an
indirect call for heat with no “off” delay. The boiler
ump (P1) and System Pump (P2) delay “off” as user-
P
defined in the ADJUST menu. The System Pump (P2)
runs whenever the system is enabled for heating and
the outdoor air temperature is lower than the WWSD
emperature setting (if utilized) unless an indirect call
t
for heat is present with priority. See Fig. 14 for piping
xample.
e
Mode 3
This mode is for hydronic heating systems with single
or multiple boilers (Maximum 4 boilers) in primary/secondary piping configuration with or without Outdoor Air
Reset (S4) with indirect DHW on the boiler loop (with
priority). The system temperature is controlled by the
Supply sensor (S3) whenever the indirect call for heat
is not active. The DHW Supply sensor (S5) determines
the indirect call/tank setpoint. During an indirect call for
heat the boiler firing rate is determined by the water
temperature at the Indirect Supply sensor (S6) and the
Target Max setting when using the Indirect DHW sensor (S5).
The Boiler Pump (P1) runs during all heat calls regardless of priority. The Indirect DHW Pump (P3) runs
during an indirect call for heat with no “off” delay. The
Boiler Pump (P1) and System Pump (P2) delay “off” as
user-defined in the ADJUST menu. The system pump
(P2) runs whenever the system is enabled for heating
and the outdoor air temperature is lower than the
WWSD temperature setting (if utilized) unless an indirect call for heat is present. See Fig. 15 for piping
example.
WARNING: All potable water heating with this
boiler must be by an indirect heat exchanger. Only
non-potable water will go through the boiler.
System flow must exceed 120% of boiler flow.
Model
No.
H7-88A8.15.4205.43.34.02.33.21.82.71.460
H7-108A10.57.4207.04.55.23.24.22.43.52.060
H7-198A18.911.62012.66.29.54.37.63.56.33.060
H7-278A26.120.32017.410.113.16.510.54.98.74.060
H7-398A38.314.12025.57.419.25.015.34.012.83.460
Notes: Basis for minimum flow is ∆T . Basis for maximum flow is GPM.
Fig 13: MODE 1 - Single Boiler - Primary/Secondary Piping
18
Page 19
Fig 14: MODE 2 - Single Boiler - Primary/Secondary Piping
with Indirect DHW on System Loop
19
Page 20
Fig 15: MODE 3 - Single Boiler - Primary/Secondary Piping
with Indirect DHW on Boiler Loop
20
Page 21
Gas Supply
ANGER: Make sure the gas on which the unit will
D
operate is the same type as specified on the rating
plate.
Gas piping must have a sediment trap ahead of the
boiler gas controls, and a manual shut-off valve located outside the boiler jacket. It is recommended that
a union be installed in the gas supply piping adjacent
to the boiler for servicing. Refer to Table J for maximum pipe lengths.
Gas Supply Connection
CAUTION: The boiler must be disconnected from
the gas supply during any pressure testing of the gas
supply system at test pressures in excess of 1/2 PSI
(3.45 kPa).
The boiler must be isolated from the gas supply piping system by closing the upstream manual shut-off
valve during any pressure testing of the gas supply
piping system at test pressures equal to or greater
than 1/2 PSI (3.45 kPa). Relieve test pressure in the
gas supply line prior to re-connecting the boiler and its
manual shut-off valve to the gas supply line. FAIL-
URE TO FOLLOW THIS PROCEDURE MAY
DAMAGE THE GAS VALVE. Over-pressurized gas
valves are not covered by warranty. The boiler and its
gas connections shall be leak-tested before placing
the appliance in operation. Use soapy water for leak
test. DO NOT use an open flame.
Fig. 16: Gas Supply Connection
CAUTION: Do not use Teflon tape on gas line pipe
thread. A pipe compound rated for use with natural
and propane gases is recommended. Apply
sparingly only on male pipe ends, leaving the two
end threads bare.
CAUTION: Support gas supply piping with
hangers, not by the boiler or its accessories. Make
sure the gas piping is protected from physical
damage and freezing, where required.
N: Natural Gas 1000 BTU/FT٨3 .60 Specific Gravity @ 0.5” WC pressure Drop
P: Propane Gas 2500 BTU/FT٨3 1.53 Specific Gravity @ 0.5” WC pressure Drop
Model
88AR
108AR
198AR
278AR
398A
Input
(KBTU)
883575135305440990
1102050902052907201045
19915306595220365880830
275153550120205460425980
399202560100230220485
1/2”3/4”1”1-1/4”1-1/2”
NPNPNPNPNP
Maximum Equivalent Pipe Length
Table J: Maximum Equivalent Pipe Length
21
Page 22
Gas Supply Pressure
minimum of 4.5 in. WC upstream gas pressure
A
under full load and a maximum gas supply pressure
setpoint of 10.5 in. WC under load and no-load conditions for natural gas. A minimum of 8.0 in. WC
pstream gas pressure under full load and a maximum
u
gas supply pressure setpoint of 13.5 in. WC is required
or propane gas. The gas pressure regulator(s) sup-
f
plied on the boiler is for low-pressure service. If
upstream pressure exceeds 1/2 PSI at any time, an
intermediate gas pressure regulator, of the lockup
type, must be installed. This regulator should be
placed a minimum distance of 10 times the pipe diameter upstream of the boiler gas controls.
When connecting additional gas utilization equipment
to the gas piping system, the existing piping must be
checked to determine if it has adequate capacity for
the combined load. The gas valve pressure regulator
on the boiler is nominally preset as noted in Table K.
During normal operation, carbon dioxide should be 8.8
to 10.5% at full fire for natural gas and between 10.2
and 10.8% for propane gas. Carbon monoxide should
be ‹200 ppm.
Manifold Pressure (in. WC)
Model
No.
88AR-.1” WC-.1” WC
108AR-.1” WC-.1” WC
198AR-2.0” WC-1.4” WC
278AR-2.1” WC-2.0” WC
398A-3.4” WC-3.0” WC
Table K: Manifold Gas Pressure Settings
CAUTION: For proper operation, no more than a
30% drop in gas supply pressure from no-load to fullload conditions is acceptable. Under no
circumstances should the pressure be outside the
listed operational range.
Natural GasPropane Gas
HighHigh
Electrical Power Connections
Installations must follow these codes:
•National Electrical Code and any other national,
state, provincial or local codes or regulations having jurisdiction.
•Safety wiring must be NEC Class 1.
•Heater must be electrically grounded as required
by the NEC.
•In Canada, CSA C22. 1 C.E.C. Part 1.
The XPak FT 88AR-398A boilers are wired for 120
VAC single-phase 60 Hz power. Consult the wiring diagram shipped with the unit. Before starting the boiler,
check to ensure proper voltage to the boiler and
pump(s).
The expected current draw for the boiler is less than 5
amps. The pump load is additional.
The boiler pump (up to ¼ HP) and the indirect DHW
pump (up to ¼ HP) get their power supply directly from
the boiler power supply. The system pump relay is
rated for pilot duty only. An indirect DHW pump larger
than ¼ HP or 5A must use a separate power supply
and run the power through an external field-supplied
pump contactor. Use appropriately-sized wire as
defined by NEC, CSA and/or local codes. All primary
wiring should be 125% of minimum rating. The indirect and system pumps outputs are fuse-protected.
If any of the original wire as supplied with the boiler
must be replaced, it must be replaced with 105°C wire
or its equivalent.
All 120VAC field wiring connections to the XPak FT are
made inside the rear wiring box as shown in Fig. 17.
Low-voltage wiring is connected to the VERSA control
board and the Platform Ignition Module (PIM) at the
front of the unit. Sensors, enable/disable contacts,
(optional) 0-10 VDC control wiring, and cas- cade connections are wired into the VERSA and PIM field wiring
plugs. See the wiring diagram on page 47.
22
Page 23
Check the Power Source
CG
(12 AWG)
BW
(12 AWG)
ABK
(12 AWG)
NOTE: Minimum 18 AWG, 105°C, stranded wire
must be used for all low voltage (less than 30 volts)
external connections to the unit. Solid conductors
should not be used because they can cause
excessive tension on contact points. Install conduit
s appropriate. All high voltage wires must be the
a
same size (105°C, stranded wire) as the ones on the
unit or larger.
Fig. 18: Multi-meter
Making the Electrical Connections
Refer to Fig. 17–25.
1. Verify that circuit breaker is properly sized by
referring to the boiler’s rating plate. A dedicated
circuit breaker should be provided and sized for
the boiler and all pumps powered through it.
NOTE: Current draw noted on rating plate does not
include pump current.
Fig. 17: Wiring Connections
WARNING: Using a multi-meter, check the
following voltages at the circuit breaker panel prior to
connecting any equipment. Make sure proper
polarity is followed and house ground is proven.
(See Fig. 17.)
Check the power source:
AC = 108 VAC Minimum, 132 VAC MAX
AB = 108 VAC Minimum, 132 VAC MAX
BC = <1 VAC Maximum
2. Turn off all power to the boiler. Verify that power
has been turned off by testing with a multi-meter
prior to working with any electrical connections or
components at the J-box inside the unit.
3. Observe proper wire colors while making electrical connections. Many electronic controls are
polarity sensitive. Components damaged by improper electrical installation are not covered by
warranty.
4. Provide overload protection and a disconnect
means for equipment serviceability as required by
local and state code.
5. Install boiler controls, thermostats, or building
management systems in accordance with the
applicable manufacturers’ instructions.
6. Conduit must not be used as the earth ground.
NOTE: A grounding electrode conductor shall be
used to connect the equipment grounding
conductors, the equipment enclosures, and the
grounded service conductor to the grounding
electrode.
23
Page 24
Field Wiring Connections
DANGER: SHOCK HAZARD
Make sure electrical power to the boiler is disconnect-
d to avoid potential serious injury or damage to
e
components.
CAUTION: Wiring errors can cause improper and
dangerous operation. See the wiring diagram in this
manual. Verify proper operation after servicing.
Fig. 19: Electrical Wiring
Wiring the Thermostat
Connect the Enable/Disable terminals to the PIM (shown in Fig. 20). Alternately, any dry contact closure (including a remote thermostat) across these terminals will enable the XPak FT unit to run. Caution should be used to
ensure neither of the terminals becomes connected to ground.
Fig. 20: XPak FT Single Boiler Control
24
Page 25
Heating Sensor Installation
1. Only use the System sensor provided with the
unit.
2. The sensor wires can be extended up to 500'
sing a shielded 2-conductor cable.
u
3. Do not run sensor wires in conduit with line voltage
wiring.
4. Install a 3/8" ID 1/2 NPT immersion well.
5. If installing the system sensor on the supply, insert
the sensor in a well with heat paste no more than
5' feet past the boiler loop outlet on the common
supply header but before any major takeoffs. The
sensor must be located where it sees the output of
all the boiler stages. If a boiler is piped so that the
sensor does not see its output, the VERSA IC will
not sequence the boilers correctly.
Heating
System
Sensor
Sensor
Probe
Immersion Well
3/8” ID 1/2 NPT
Fig 21: System Sensor (S3)
Common
Supply Pipe
3. Use a minimum 18 AWG wire for runs of up to 150
feet.
4. Mount the outdoor sensor on an exterior surface of
he building, preferably on the north side in an
t
area that will not be affected by direct sunlight and
that will be exposed to varying weather conditions.
Wiring the Indirect Sensor (S5)
1. There is no indirect sensor connection required if
an indirect water heater is not used in the installation.
2. When the Indirect DHW call for heat is active, the
PIM communicates this to the VERSA. The
VERSA calculates the optimal operation and
sends the firing rate and pump output requests to
the PIM so it can activate the Indirect DHW pump
and Boiler pump if needed.
NOTE: Alternately, a thermostat contact closure can
be used in lieu of the sensor for indirect operation.
Connect the thermostat to the terminals marked IND
REMOTE THERMOSTAT.
CAUTION: Sensor and control wiring must NOT be
run in conduit or chases with line voltage.
If an optional Indirect DHW sensor is connected to
J2-1 and J2-2 the PIM will pass this signal to the
VERSA. This allows the VERSA to optimize the
Indirect DHW demand to maintain the Indirect
DHW setpoint. The Indirect DHW thermostat
switch closure is not required when using the
Indirect DHW sensor. If a VERSA is not present
the PIM shall activate the Indirect DHW pump
whenever the Indirect DHW call is active. The
Boiler pump may also be activated based on the
Indirect DHW piping configuration setting.
NOTE: If the System Sensor (S3) can not sense the
correct water temperature, the VERSA IC will not
provide comfortable heat levels.
WARNING: Use only the System and Outdoor Air
sensors included with the control.
Wiring the Outdoor Sensor (S4)
1. There is no connection required if an outdoor sensor is not used in this installation.
2. If using an Outdoor Sensor, connect the sensor
wires to the terminals marked OUTDOOR SENSOR (see wiring diagram). Caution should be
used to ensure neither of these terminals
becomes connected to ground.
3. Connect the indirect tank sensor to the terminals
marked INDIRECT DHW SENSOR (see wiring
diagram). Caution should be used to ensure neither of these terminals becomes connected to
ground.
Wiring the Optional 0–10 Volt
Building Control Signal
1. A signal from an energy management system may
be connected to the XPak FT boiler. This signal
should be a 0-10 volt positive DC signal, and an
energy management system can be used to control either the setpoint temperature or the firing
rate of the XPak FT boiler.
25
Page 26
VERSA
MASTER
Fig. 22: XPak FT Cascade System Wiring
2. To enable this remote control function, set dip
switch 5 to the UP position on the PIM. Dip switch
5 Toggles between an EMS (UP) signal or a
demand signal from the VERSA (DOWN). Dip
switch 2 on the PIM toggles between a Direct
Drive (UP) input and a Target Temperature
(DOWN) setpoint.
3. For a 4-20 mA application, refer to the VERSA IC
Applications Guide.
4. Connect an Energy Management system or other
auxiliary control signal to the terminals marked 010V (+ /-) on the PIM (see Fig. 20). Caution should
be used to ensure that the +0-10V connection
does not create a short to ground.
Wiring the Cascade System
Communication Bus
1. Designate the primary boiler as the master
boiler/boiler1 by leaving DIP switch 2 on the
VERSA in the ON position. All other VERSA controls require DIP switch 2 to be toggled OFF,
designating them as followers. Follower VERSA’s
are ignored by their corresponding PIM’s. Use
standard 18 AWG wire to connect the master
VERSA to the PIM on the followers. A total of 3 followers can be connected to the VERSA on the
master. For systems requiring more than 4 connected boilers, an external sequencer such as the
Raypak Temp-Tracker Mod+ Hybrid can be used.
2. It is recommended that the shortest length cable
possible be used to reach between the boilers. Do
not run unprotected cables across the floor or
where they will become wet or damaged. Do not
run communication cables parallel with, or close to
or against, high voltage (120 volt or greater)
wiring. Raypak recommends that the total maximum length of each set of communication bus
cables not exceed 200 feet.
3. Route the FT_BUS wires from the front along the
right rail and out the bottom of the cabinets.
4. Connect the FT_BUS wires to the PIM by pressing
down on the slots with a small screwdriver and
then inserting the wires into the holes. See Fig.
23.
Fig. 23: FT_BUS Wire Connection
26
Page 27
G
(12 AWG)
W
(12 AWG)
BK
G
W
BK
G
W
BK
G
W
BK
(12 AWG)
Fig. 24: XPak FT Cascade Master Pumps
G
(12 AWG)
W
(12 AWG)
BK
(12 AWG)
G
W
BK
-
Cascade System Pump and
Sensor Wiring
1. On the boiler designated as the Master, connect
the system pump wiring to the terminal block at the
rear of the unit. Connect to terminals 10, 11, and
12 (See Fig. 24). The output is rated for pilot duty
only (2A maximum).
Cascade Follower Pump
and Sensor Wiring
. Once the primary boiler has been identified, addi-
1
tional boilers will be designated as follower boilers.
Ensure DIP switch 2 on each follower VERSA is
set to the OFF/Down position (See Fig. 25)
2. For each follower boiler, connect the boiler pump
wires to the terminal block at the rear of each unit.
Connect to terminals 4, 5, and 6 as shown in Fig.
24.
2. Connect the boiler pump wires to the terminal
block at the rear of their unit. Connect to terminals
4, 5, and 6 (See Fig. 24).
3. Connect the system supply sensor to terminals 3
Fig. 25: VERSA Follower
and 4 on the J2 connector located on the Master
PIM (See Fig. 20).
Modbus BMS Communication
The VERSA IC control is equipped as standard with a
communications port for connectivity to building
automation via Modbus protocol. Refer to the VERSA
IC Applications Guide (Catalog No. 5000.72) for fur-
4. Connect the Outdoor sensor (if used) to terminals
5 and 6 on the J2 connector located on the Master
PIM (See Fig. 20).
ther information.
5. Connect the Enable/Disable wiring to terminals 9
and 10 on the J1 connector located on the Master
PIM (See Fig. 20). This connection must be provided through dry contacts closure.
NOTE: This dry contacts closure can come from a
room thermostat or a remote relay. No power of any
kind should be applied to either of these terminals.
27
Page 28
Alarm Connection
The Alarm Contacts are 3A rated dry contacts on a
normally-open relay that close during fault or lockout
conditions, and the maximum voltage across the contacts is 30 VAC or 30 VDC. Connections are made at
he supplied alarm contacts (spade terminals).
t
In a cascade system, the alarm output of the master
boiler will be active if either the master boiler or follower(s) have a lockout condition. The alarm output of
the follower boilers will only energize if a lockout condition occurs on that specific boiler.
Venting
CAUTION: Proper installation of flue venting is
critical for the safe and efficient operation of the
boiler.
WARNING: Contact the manufacturer of the vent
aterial if there is any question about the appliance
m
categorization and suitability of a vent material for
application on a Category IV vent system. Using
improper venting materials can result in personal
injury, death or property damage.
se only PVC or CPVC vent material (in Canada,
U
ULC-S636 approved plastic material must be used) or
special gas vent pipes listed for use with Category IV
gas burning heaters, such as the AL29-4C stainless
steel vents offered by Heat Fab Inc. (800-772-0739),
Protech System, Inc. (800-766-3473), Z-Flex (800654-5600) or American Metal Product (800-423-4270).
Pipe joints must be positively sealed. Follow the vent
manufacturer’s installation instructions carefully.
®
DuraVent
approved to be used on XPak FT products.
polypropylene vent material is also
General
Appliance Categories
Heaters are divided into four categories based on the
pressure produced in the exhaust and the likelihood of
condensate production in the vent.
Category I – A heater which operates with a non-positive vent static pressure and with a vent gas
temperature that avoids excessive condensate production in the vent.
Category II – A heater which operates with a non-positive vent static pressure and with a vent gas
temperature that may cause excessive condensate
production in the vent.
Category III – A heater which operates with a positive
vent pressure and with a vent gas temperature that
avoids excessive condensate production in the vent.
Category IV – A heater which operates with a positive
vent pressure and with a vent gas temperature that
may cause excessive condensate production in the
vent.
See Table M for appliance category requirements.
NOTE: For additional information on appliance
categorization, see the ANSI Z21.13 Standard and
the NFGC (U.S.), or B149 (Canada), or applicable
provisions of local building codes.
Vent installation shall be in accordance with Part 7,
Venting of Equipment, of the NFGC, ANSI
Z223.1/NFPA 54, Section 7, Venting Systems and Air
Supply for Appliances, of the B149 Code, or applicable
provisions of the local building codes.
WARNING: Do not use foam core or cellular core
PVC/CPVC pipe for venting.
WARNING: DO NOT insulate PVC or CPVC vent
pipe.
CAUTION: When using stainless steel vent in a climate where freezing may occur, a double wall vent
pipe must be used.
CAUTION: The inlet water temperature to the XPak
FT must not exceed 170ºF at any firing rate to use
the PVC venting option. The venting system must
conform to local codes and/or the current National
Fuel Gas Code ANSI Z223.1/NFPA 54. The system
setpoint must not exceed 180°F.
Support of Vent Stack
The weight of the vent stack or chimney must not rest
on the heater vent connection. Support must be provided in compliance with applicable codes. The vent
should also be installed to maintain proper clearances
from combustible materials. Use insulated vent pipe
spacers where the vent passes through combustible
roofs and walls.
28
Page 29
ombustion
COMBUSTIONCOMCOMBUCOMBUSCOMBUSTCOMBUSTICOMBUSTIOCOMBUSTION
TEST PORT
COMBUSTION
TEST PO
COMBUSTION
TEST PORT
3 O-RING
COMBUSTION
TEST PORT
3 O-RING
GASKETS
COMBUSTION
TEST PORT
3 O-RING
GASKETS
C
Air Supply
xhaust
E
Configuration
Heater
Venting
Category
Vertical Venting
From Inside Building
(Non-Direct Venting)
Horizontal Through-
the-Wall Venting
Vertical Venting
From Outside Building
(Direct Venting)
Horizontal Through-
the-Wall Venting
* Only Duravent®polypropylene is approved for the XPak FT product.
Table L: Venting Category Requirements
IV
ertified Vent
C
Materials
(Canada Only: ULC-
636 PVC and CPVC)
S
Stainless Steel,
AL29-4C,
Sch 40 PVC or CPVC
Polypropylene*
Combustion
Air Inlet
Material
Galvanized Steel,
PVC, ABS,
CPVC
WARNING: Condensate is acidic and highly
corrosive. The drain line must not be allowed to
freeze. Take appropriate measures.
NOTE: During winter months check the vent cap
and make sure no blockage occurs from build-up of
snow or ice.
Vent Terminal Location
1. Condensate can freeze on the vent cap. Frozen
condensate on the vent cap can result in a blocked
flue condition.
2. Give special attention to the location of the vent
termination to avoid possibility of property damage or personal injury.
3. Gases may form a white vapor plume in winter.
The plume could obstruct a window view if the termination is installed near windows.
4. The bottom of the vent terminal and the air intake
shall be located at least 12 in. above grade, including normal snow line.
5. Single-wall Category IV metal vent pipe shall not
be used outdoors in cold climates for venting gasfired equipment without insulation.
6. Through-the-wall vents for Category IV appliances shall not terminate over public walkways or
over an area where condensate or vapor could
create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or
other equipment.
Fig. 26: 3 in 1 Multi-Vent Connector
The Multi-vent connector is capable of using stainless
steel (SST), Polypropylene or PVC/CPVC pipe. Before
installing vent pipe, verify which o-ring gasket will be
used and dispose of the other two.
6. Locate and guard vent termination to prevent accidental contact by people or pets.
7. DO NOT terminate vent in window well, stairwell,
alcove, courtyard or other recessed area.
9. DO NOT terminate above any door, window, or
gravity air intake. Condensate can freeze, causing
ice formations.
10. Locate or guard vent to prevent condensate from
damaging exterior finishes. Use a 300-series
stainless steel backing plate against brick or
masonry surfaces.
29
Page 30
11. DO NOT extend exposed vent pipe outside of
VENT CAPS STACKED VERTICALLY
FLUE GASES MOVING IN PARALLEL
VENT CAPS ALL AT SAME ELEVATION
FLUE GASES MOVING TOWARD EACH OTHER
VENT CAPS AT STAGGERED ELEVATIONS
FLUE GASES MOVING TOWARD EACH OTHER
1” MINIMUM (TYP)
2” MINIMUM (TYP)
1” MINIMUM (TYP)
DISCHARGE
4’-0” MIN.
(TYP)
4’-0” MIN.
(TYP)
DISCHARGE
uilding beyond the minimum distance required
b
for the vent termination. Condensate could freeze
and block vent pipe.
.S. Installations
U
Refer to the latest edition of the National Fuel Gas
ode.
C
Vent termination requirements are as follows:
1. Vent must terminate at least 4 ft below, 4 ft horizontally from or 1 ft above any door, window or
gravity air inlet to the building.
2. The vent must not be less than 7 ft above grade
when located adjacent to public walkways.
3. Terminate vent at least 3 ft above any forced air
inlet located within 10 ft.
4. Vent must terminate at least 4 ft horizontally, and
in no case above or below unless 4 ft horizontal
distance is maintained, from electric meters, gas.
5. Terminate vent at least 6 ft away from adjacent
walls.
6. DO NOT terminate vent closer than 5 ft below roof
overhang.
7. The vent terminal requires a 12 in. vent terminal
clearance from the wall.
8. Terminate vent at least 1 ft above grade, including
normal snow line.
9. Multiple direct vent installations require a 4 ft
clearance between the ends of vent caps located
on the same horizontal plane.
Installations in Canada
Refer to latest edition of the B149 Installation Code.
A vent shall not terminate:
1. Directly above a paved sidewalk or driveway
which is located between two single-family dwellings and serves both dwellings.
2. Less than 7 ft (2.13 m) above a paved sidewalk or
paved driveway located on public property.
3. Within 6 ft (1.8 m) of a mechanical air supply inlet
to any building.
4. Above a meter/regulator assembly within 3 ft (915
mm) horizontally of the vertical centerline of the
regulator.
WARNING: The Commonwealth of Massachusetts
requires that sidewall-vented heaters, installed in
every dwelling, building or structure used in whole or
in part for residential purposes, be installed using
special provisions as outlined on page 62 of this
manual.
5. Within 6 ft (1.8 m) of any gas service regulator
vent outlet.
Fig. 26: Vent Cap Configurations
6. Less than 1 ft (305 mm) above grade level.
7. Within 3 ft (915 mm) of a window or door which
can be opened in any building, any non-mechanical air supply inlet to any building or the
combustion air inlet of any other appliance.
8. Underneath a verandah, porch or deck, unless the
verandah, porch or deck is fully open on a minimum of two sides beneath the floor, and the
distance between the top of the vent termination
and the underside of the verandah, porch or deck
is greater than 1 ft (305 mm).
30
Page 31
M
odel
No.
ertified Vent
C
Material
Vent and
ntake Air
I
Vent Size
(in.)
Vertical Vent Height1 (ft)
Min.Max.
Combustion
ir Intake
A
Pipe
Material
Vertical Air
Inlet Max.
Length* (ft)
88AR
(Canada Only:
ULC-S636 PVC
2
0
5
and CPVC)
108AR
198AR
278AR
Stainless Steel,
AL29-4C,
ANSI/ASTM D1785
Sch 40 PVC,
3100100
Galvanized
5
PVC, ABS,
ANSI/ASTM F441
398A
1
Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details.
* Subtract 10 ft per elbow. Max. 7 elbows.
** Only Duravent polypropylene is approved for the XPak FT product.
Model No.
Sch 40 CPVC
Polypropylene**
Table M: Category IV Vertical Vent & Vertical Direct Vent
Size
(in.)
36060
4100100
Approved
Intakes
Approved Plastic
Terminals
Approved SS Terminals
88AR
3" PVC/CPVC Elbow
108AR
198AR
278AR
398A4
3
PVC 90° Elbow,
Sch 40
Galvanized 90°
Elbow,
SS 90° Elbow,
ABS 90° Elbow
Sch 40*,
Duravent
Polypropylene
4" PVC/CPVC Tee
Sch 40*,
Duravent
FasNSeal®FSTT 3
FasNSeal®FSTT 4
Polypropylene
Steel,
CPVC
0
5
*Must be ULC-S636 materials in Canada.
Table N: Horizontal Vent and Air Intake Terminals
Venting Installation Tips
Support piping:
• Horizontal runs—At least every 5 ft (1.5 m)
• Vertical runs—Use braces
• Under or near elbows
NOTE: Ensure adequate clearances to allow annual
inspection of the venting system.
Venting Configurations
For heaters connected to gas vents or chimneys, vent
installations shall be in accordance with the NFGC
(U.S.), or B149 (Canada), or applicable provisions of
local building codes.
CAUTION: This venting system requires the
installation of a condensate drain in the vent piping
per the vent manufacturer’s instructions. Failure to
install a condensate drain in the venting system will
void all warranties on this boiler. Condensate is
acidic and highly corrosive. The drain line must not
be allowed to freeze. Take appropriate measures.
Vertical Venting (Category IV)
Installation
The maximum and minimum venting length for this
Category IV appliance shall be determined per the
NFGC (U.S.) or B149 (Canada).
31
Page 32
The minimum flue pipe diameter for conventional venting is: 3 in. (76 mm) for Models 88AR (2” optional),
108AR, 198AR and 278AR, and 4 in. (102 mm) for
Models 398A (3” optional).
The connection from the appliance vent to the stack
must be as direct as possible and shall be the same
diameter as the vent outlet. The horizontal breaching
of a vent must have an upward slope of not less than
1/4 inch per linear foot from the heater to the vent terminal. The horizontal portions of the vent shall also be
supported for the design and weight of the material
employed to maintain clearances and to prevent physical damage or separation of joints.
The vent terminal should be vertical and should terminate outside the building at least 2 ft above the highest
point of the roof that is within 8 ft. The vent cap should
have a minimum clearance of 4 ft horizontally from and
in no case above or below (unless a 4 ft hori-zontal
distance is maintained) electric meters, gas meters,
regulators and relief equipment.
WARNING: Vent connectors serving any other
appliances shall not be connected into any portion of
mechanical draft systems operating under a positive
pressure. If an XPak FT boiler is installed to replace
an existing boiler, the vent system MUST be verified
o be of the correct size and of Category IV AL29-4C
t
vent material, approved PVC/CPVC construction, or
DuraVent
®
polypropylene (in Canada, ULC- S636
approved plastic materials must be used). If it is
NOT, it MUST be replaced..
NOTE: For extractor sizing, typical CO2 levels are
9.0% for natural gas and 10.5% for propane gas and
flue temperatures of less than 180°F.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances remaining connected to the common venting system are not
in operation:
The distance of the vent terminal from adjacent public
walkways, adjacent buildings, open windows and
building openings must be consistent with the NFGC
(U.S.) or B149 (Canada). Vents supported only by
flashing and extending above the roof more than 5 ft
should be securely guyed or braced to withstand snow
and wind loads.
Common Venting
The NFGC does not address sizing guidelines for the
common venting of multiple Category IV heaters. This
is covered in the NFGC under “Engineered Vent Systems”. Table O provides volumes of flue products at
full fire for the calculation of appropriate vent and
extractor sizing for common venting.
CAUTION: A listed vent cap terminal suitable for
connection to the Cat IV vent materials, adequately
sized, must be used to evacuate the flue products
from the boilers.
WARNING: An extractor is required when multiple
heaters are vented through a common vent pipe.
The extractor must operate when one or more units
are firing.
(a) Seal any unused openings in the common venting
system.
(b) Visually inspect the venting system for proper size
and horizontal pitch and make sure there is no
blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe
condition.
(c) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat
so appliance will operate continuously.
NOTE: Vent and intake piping must be supported so
that the weight of the venting is not transfered to the
unit. Horizontal runs of vent and intake piping must
be supported to prevent sagging.
NOTE: While a drain connection is required in the
vent of all XPak FT installations, the drain can be accomplished in several different ways. The figures in
this manual show the drain in a vent tee, however,
this can also be accomplished using an inline collector for condensing stacks or an inline vertical or
horizontal collector available from several of the
listed vent manufacturers.
WARNING: Condensate is acidic and highly
corrosive.
32
Page 33
CAUTION: This venting system requires the
installation of a condensate drain in the vent piping
per the vent manufacturer’s instructions. Failure to
install a condensate drain in the venting system will
oid all warranties on this boiler. The drain line must
v
not be allowed to freeze. Take appropriate
measures.
Installation
These installations utilize the heater-mounted blower
to draw combustion air and to vent the combustion
products to the outdoors. The combustion air intake
and the vent are installed horizontally through the wall
to the outdoors. Adequate ventilation air must be supplied to the equipment room in accordance with the
NFGC (U.S.) or B149 (Canada).
The total length of the horizontal through-the-wall
direct vent system should not exceed 200 equivalent ft
in length. If combined vent/intake run exceeds 200
equivalent ft, an appropriately sized variable-speed
extractor must be used. Each elbow used is equal to
10 ft of straight pipe with a maximum of 4 elbows each
on the air intake and vent.
ermination
T
The vent cap MUST be mounted on the exterior of the
uilding. The vent cap cannot be installed in a well or
b
below grade. The vent cap must be installed at least 1
ft above ground level and above normal snow levels.
Only Raypak-approved vent caps may be used. The
ent terminal must be located NO CLOSER than 12”
v
off the wall.
WARNING: No substitutions of flue pipe or vent
cap material are allowed. Such substitutions would
jeopardize the safety and health of inhabitants.
The vent cap is not considered in the overall length of
the venting system.
The vent must be installed to prevent flue gas leakage.
Care must be taken during assembly to ensure that all
joints are sealed properly and are airtight. The vent
must be installed to prevent the potential accumulation
of condensate in the vent pipes. It is required that:
1. The vent must be installed with condensate drains
as directed by the vent manufacturer.
2. The vent must be installed with a slight upward
slope of not less than 1/4 inch per foot of horizontal run to the vent terminal.
33
Page 34
Horizontal Through-the-Wall Direct
Venting (Category IV)
Fig. 27: Horizontal Through-the-Wall Venting
Fig. 28: Horizontal Through-the-Wall Direct
Venting
Fig. 29: Horizontal Through-the-Wall Venting w/ Single Termination
These installations utilize the heater-mounted blower
to draw combustion air from outdoors and vent combustion products to the outdoors.
The total length of air supply pipe cannot exceed the
distances listed in Table M. Each elbow used is equal
to 10 ft of straight pipe. This will allow installation in
any arrangement that does not exceed the lengths
shown in Table M.
The vent cap is not considered in the overall length of
the venting system.
Care must be taken during assembly that all joints are
sealed properly and are airtight.
Combustion air supplied from outdoors must be free of
articulate and chemical contaminants. To avoid a
p
blocked flue condition, keep the vent cap clear of
snow, ice, leaves, debris, etc.
Condensate Management
he condensate must be drained properly to protect
T
the appliance and drainage system. The condensate
from the boiler is acidic. Its pH is between 3.2 and 4.5.
Raypak recommends treating the condensate with a
Condensate Treatment kit (Z-12). The treatment kit is
connected to the drain system and contains limestone
(calcium carbonate) chips to raise the pH level of the
condensate. The kit may be added to avoid long-term
damage to the drainage system and to meet local
code requirements. The pH level of the effluent entering a sanitary drain must be 5.0 or higher.
The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is
required that:
1. The vent must be installed with a condensate
drain as directed by the vent manufacturer.
2. The vent must be installed with a slight upward
slope of not more than 1/4 inch per foot of horizontal run to the vent terminal.
CAUTION: This venting system requires the
installation of a condensate drain in the vent piping
per the vent manufacturer’s instructions. Failure to
install a condensate drain in the venting system will
void all warranties on this boiler. Note that the
condensate is acidic and highly corrosive.
Termination
The vent cap MUST be installed on the exterior of the
building. The vent cap cannot be installed in a well or
below grade. The vent cap must be installed at least 1
ft above ground level and above normal snow levels.
Vent pipe condensate drains are also required for
installation of the XPak FT. Follow vent manufacturer
instructions for location of condensate drains in the
vent. The vent condensate should also be routed
through a treatment kit, as required by local code
requirements.
The treatment kit must be sized to the condensate
generated by the appliance and the vent.
The condensate drain line must not be allowed to
freeze. Take appropriate measures.
The vent cap MUST NOT be installed with any combustion air inlet directly above a vent cap. This vertical
spacing would allow the flue products from the vent
cap to be pulled into the combustion air intake installed
above.
This type of installation can cause non-warrantable
problems with components and poor operation of the
boiler due to the recirculation of flue products. Multiple vent caps installed in the same horizontal plane
must have a 4 ft clearance from the side of one vent
cap to the side of the adjacent vent cap(s).
37
Page 38
Freeze Protection
o enable freeze protection, DIP switch position 7 (on
T
the PIM) must be turned on (UP position). This is the
default position.
f the water temperature drops below 45˚F on the
I
Outlet or Inlet sensors, the Boiler pump is enabled.
The pump is turned off when both the Inlet and Outlet
temperatures rise above 50˚F.
If either the Outlet or Inlet temperature drops below
38°F, the VERSA starts the burner at the minimum firing rate. The burner cycle will terminate when both the
Inlet and Outlet temperatures rise above 42°F.
CAUTION: In general, the condensate piping from
the appliance must have a downward slope of ¼” per
horizontal foot. Condensate drain traps must be
primed with water to prevent gas flue leaks.
reatment kits should be checked at least once per
T
year, to ensure that the pH of the effluent is 5.0 or
higher, and the chips should be replenished as necessary. When replacing the chips, they should be no
smaller than ¾” to avoid blockage in the condensate
piping. Fig. 38 is a visual guide only. Follow the manufacturer’s instructions for the installation of the
treatment kit and condensate drains.
WARNING: Installation, adjustment and service of
controls, including timing of various operating functions, must be performed by a qualified installer,
service agency or the gas supplier. Failure to do so
may result in control damage, malfunction, property
damage, personal injury, or death.
CAUTION: This appliance has provisions to be
connected to more than one supply source. To
reduce the risk of electric shock, disconnect all such
connections before servicing.
CAUTION: Risk of electric shock: More than one
disconnect switch may be required to de-energize
the equipment before servicing.
Fig. 38: Visual Guide for Condensate Piping
38
Page 39
Controls
Ignition Control Functions
When there is a call for heat, and all safeties are
losed, then the combustion air blower starts to purge
c
air from the combustion chamber. After the pre-purge,
he igniter is energized. The ignition module will lock-
t
out after failing to light 3 times during a call for heat. To
reset the lockout, press and release the RESET button
located on the user interface. The con- trol will automatically reset after 1 hour. When in lockout the
control will run the blower through a post- purge cycle.
NOTE: Ignition modules are common for all model
sizes. However, model-specific operating parameters are defined by their respective ID cards.
High Limit — Manual Reset
he heater is equipped with a fixed-setting manual-
T
reset high limit temperature device as standard, set at
200ºF, and it may have an additional optional
adjustable manual reset high temperature device.
Standard
The fixed-setting manual-reset high limit is built into
the PIM, and utilizes a dual element sensor located on
the outlet. To reset a high limit lock-out, press and
release the RESET button located on the user interface.
Optional
The optional adjustable-setting manual-reset high limit
is located behind the front panel. To reset a high limit
lockout, press the reset button on the adjustable manual reset limit as well as the reset button located on the
user interface.
Flue Temperature Limit
The heater is equipped with a fixed-setting manualreset high limit temperature device on the vent, for use
with non-metallic vent material. The high temperature
limit is located inside the unit near the vent adapter.
The VERSA monitors the limit and displays any fault
associated with the limit on the user interface. To reset
the limit, access it and press down on the red button.
The unit is provided with a limit rated for PVC vent
material. A higher-rated limit is provided when using
DuraVent®polypropylene venting. The limit is
removed when using Category IV stainless steel venting.
Fig. 39: Flue Temperature Limit
39
Page 40
Test/Reset
PRESSPRESS
TO START
PRESS
T
PRESS
TO ST
PRESS
TO STAR
PRESS
TO START
Low Water Cut-Off (Model 398A
Only)
The standard low water cut-off automatically shuts
own the burner whenever water level drops below the
d
level of the sensing probe. A 5-second time delay prevents premature lockout due to temporary conditions
such as power fluctuations or air pockets. Manual
reset is required to restore operation
Fig. 40: Low Water Cut-Off
All-In-One Low Water Cut-Off
(Models 88AR-278AR)
The standard low water cut-off automatically shuts
down the burner whenever water level drops below the
level of the sensing probe.
This device will automatically reset once the correct
water level is restored. The VERSA control will continue to maintain lockout for 15 minutes (soft lockout).
During that time, press ‘RESET’ to restart the unit.
pressure drops below the factory setting of 3.0 in. WC
for natural gas or propane gas.
The high gas pressure switch connection mounts
downstream of the gas valve. Special ports are located on the backside of the gas valve and are accessible
from the front or top of the boiler (to reset the gas pressure switch), as necessary. If the gas pressure
regulator in the valve fails, the high gas pressure
switch automatically shuts down the burner.
The High gas pressure switch shuts down the boiler if
the gas supply pressure rises above the factory setting
of 3.0” WC for either natural or propane gas.
Fig. 42: High/Low Gas Pressure Switch
Operation of either the High or Low Gas Pressure
Switch will turn on an LED inside the switch housing.
Push the top of the plastic switch housing as shown in
Fig. 42 to reset a tripped pressure switch. The LED will
go out when the switch is reset.
These safety devices can emit small amounts of fuel
gas, and must be piped to a safe discharge location
outdoors, per local code requirements.
Fig. 41: Low Water Cut-Off
High & Low Gas Pressure Switches
(Field Add-On)
The low gas pressure switch connection mounts
upstream of the gas valve (on the inlet flange to the
gas valve) and is accessible through the removable
access panels on the front of the boiler to reset the gas
pressure switch, as necessary. It is used to ensure that
sufficient gas pressure is present for proper valve/regulator performance. The low gas pressure switch
automatically shuts down the boiler if the gas supply
Blocked Vent Switch
The heater is equipped with a blocked vent pressure
switch to prevent the operation of the boiler when a
significant amount of air flow is blocked at the vent.
The switch is located at the left rear of the unit.
Fig. 43: Blocked Vent Switch
40
Page 41
User Interface
The user interface consists of several Menu options.
Press the MENU button to scroll through the different
menus in the interface. Press the ITEM button to scroll
through available items within a selected menu. And,
he UP and DOWN buttons allow for setting changes
t
to items in the ADJUST menu. Refer to Fig. 44 for display and key locations.
View Menu
The VIEW menu is the default menu. See Table P. It
displays sensor temperatures, the modulation rate of
the blower, heater cascade status, pump operation
nd CFH information. Some of the items displayed are
a
mode-specific and are only observable when its corresponding mode is active.
For detailed descriptions of the various screens, consult the VERSA IC Control Applications Guide (Catalog
No. 5000.72).
Adjusting the XPak FT Setpoint
To adjust the setpoint on the XPak FT:
Use the MENU key to scroll to the ADJUST menu,
then use the ITEM key to scroll to the SETPOINT item.
Adjust the Setpoint using the UP and DOWN arrow
keys. Minimum is 50°F, Maximum is 192°F, and the
default is 180°F for H models.
Setup Menu
To change settings use the MENU key to scroll to the
ADJUST menu. The ADJUST menu allows the
installer to make adjustments to items shown in
Table Q.
Refer to the VERSA IC Control Applications Guide
(Catalog #5000.72) for detailed setup instructions.
ItemApplicationDescription
OUTDOORMODE 1, 2, 3Outdoor air temperature, available when TARGET = RSET in ADJUST menu.
TargetMODE 1, 2, 3
SUPPLYMODE 1, 2, 3Current system supply temperature
IND SUPPLYMODE 3Current temperature being supplied to the indirect system
Boil OUTLETAllCurrent boiler outlet temperature
Boil INLETAllCurrent boiler inlet temperature
Boil ΔTAllCurrent temperature difference between boiler outlet and boiler inlet
DHW SUPPLYMODE 2, 3Current indirect DHW supply temperature
BOILER STATUSAllIDLE, PREP, IGN, MOD RATE %, POST, SOFT
Fig. 44: User Interface
Current target temperature, available when TARGET = SETP in ADJUST
menu (Defautl), (EMS /MODB)
MODEMODE 1, 2, 31, 2, 3Piping and application configuration.1
SETPOINTMODE 1, 2, 350°F to 192°F
OUT START MODE 1, 2, 335°F to 85°FOutdoor starting temperature - outdoor reset70°F
OUT DESIGN MODE 1, 2, 3-60°F to 45°FOutdoor design temperature - outdoor reset10°F
Boil START MODE 1, 2, 335°F to 150°F
Boil DESIGN MODE 1, 2, 370°F to 200°F
TARGET MAX MODE 1, 2, 3100°F to 192°FMaximum target system temperature192°F
TARGET MIN MODE 1, 2, 3OFF, 50°F to 190°FMinimum target system temperature50°F
TARGET DIFF MODE 1, 2, 32°F to 42°FDifferential for target system temperature10°F
IND SENSOR MODE 1, 2, 3OFF <> ON
IND SETPMODE 2, 3OFF, 50°F to 180°F
DHW DIFFMODE 2, 32°F to 10°F
IND SUPPLYMODE 2, 3OFF, 50°F to PIM value*
Boiler target temperature while a heat
demand is present for setpoint operation
Starting boiler target temperature when the
outdoor temperature is at outdoor start out-
door reset
Design boiler target temperature when the
outdoor temperature is at outdoor design
outdoor reset
Selects whether a DHW sensor is used for
indirect DHW tank
Target Indirect DHW Tempererature (IND
Sensor = ON, to enable this setting)
Differential for the target indirect DHW tank
temperature, Requires IND Sensor = ON
Target boiler temperature for the DHW heat
exchanger during indirect DHW operation,
requires IND Sensor = OFF
180°F
70°F
180°F
OFF
140F
6°F
180°F
DHW
PRIORITY
PRI OVRMODE 2, 3Au, 0:10hr to 2:00hr
SYS PURGEAllOFF, 0:20min to 20:00min
MIX TYPEAllH (BOIL <> PLNT)
MIX TARGETAll50°F TO 140°FInlet Target Temperature120F
MIX LOCKAllON <>OFF
MIX TRIMAll-5 to 5
MIX SPEEDAllFAST <> MED <> SLOWThis setting defines speed of response.MED
MIX INVAllON <>OFF
WWSDMODE 1, 2, 340°F to 100°F
UNITSAlldeg F <> deg CShow units using icons in displaydeg F
MODBUSAllOFF<>MNTR<>TEMP<>RATE
ADDRESSAll1 to 247ModBus slave address1
DATA TYPEAllRTU <> ASCIModbus data typeRTU
BAUD RATEAll2400<>9600<>19K2<>57K6<>115K19K2
PARITYAll NONE<>EVEN<>ODDEVEN
* Fixed values based on the ID card.
MODE 2OFF <> ON
Selects whether or not Indirect DHW priority
is active during indirect DHW operation
Sets the length of the indirect DHW priority
override time
Sets the length of the system pump post
purge
Selects the type of control depending on
pipe configuration for CWP
The equipment will trigger a warning when
“MIX Target” is not reached within 7 min-
utes. MIX LOCK = ON Alarm and lockout,
MIX LOCK = OFF Alarm only
This adjustment is for various types and
sizes of units as well as various actuator
motor speeds and types supplied by Raypak
This option is related to the use of spring
return actuators with a proportional valve
The system warm weather shutdown tem-
perature outdoor reset, requires TARGET =
REST
ModBus Operating Mode: Off, Monitor, Temp
Control, Rate Control
OFF
1:00hr
20
seconds
H BOIL
OFF
OFF
70°F
OFF
Table Q: Adjust Menu
0
42
Page 43
Boiler View Menu
The Boiler View displays various items regarding ignition, temperature monitoring, and modulation rates. As well
as software and hardware information
ItemApplication
BOILER 1ALLEnables Boiler for operation
BOILER 2CASCADEEnables Boiler for cascade operation
BOILER 3CASCADEEnables Boiler for cascade operation
BOILER 4CASCADEEnables Boiler for cascade operation
IDLE=no CFH PREP=pre-purge or inter-purge between trials for ignition IGN=trial for
ignition BURN=burner operating POST=post purge HARD=a hard lockout fault has
occurred requiring manual reset (Ignition Lockout or manual high limit) and SOFT=a
IGNITIONALL
LIMIT TEMPALLCurrent Outlet -Limit temperatureN/A
EMS VdcALLCurrent EMS signal in Volts DCN/A
FIRE RATEALLPIMN/A
SPEEDX 1000ALLBlower speed in revolutions per minute (rpm) x 1000N/A
OUTLET MAXMode 1, 2, 3
OPERATORALLOperator Potentiometer setting on PIMN/A
DIFFALLCurrent auto differential – Fixed by PIMN/A
Pump PostALLSets the length of the boiler pump purgeN/A
FLAME CURALLFlame current in micro-amps (µA)N/A
soft lockout fault has occurred which interrupts the heating cycle (any safety other
than ignition or manual high limit).
The CFH will resume after the soft lockout fault has been corrected and a 15 min.
Defines Max Outlet temperature offset above Target Setpoint (Press and hold up and
down arrows for 3 seconds to enable adjustment), see Versa IC manual, catalog
DescriptionUser
N/A
waiting period has expired.
5000.72.
MASSALLThermal mass recovery, see Versa IC manual, catalog 5000.72.
IDENTITYALLIdentifies the unit as boiler, water heater or pool heaterN/A
IGN TYPEALLPIM Board typeN/A
ID CARDALLIdentifies Raypak Identity CardN/A
SW IDALLPIM Software identification numberN/A
ERROR CODEALLCurrent Error CodeN/A
Table R: Boiler View Menu
43
Page 44
Monitor Menu
he Monitor Menu records and displays critical Boiler information, such as, Cycle times, Run times, and
T
Maximum/Minimum temperature readings depending on the setup.
ItemApplicationDescription
RUN TIME Burner 1AllBurner run time (hours). Press UP/DOWN for 1 sec to clear.
Cycles BurnerAllNumber of burner cycles. Press UP/DOWN for 1 sec to clear.
RUN TIME Boiler pumpAllBoiler pump run time (hours). Press UP/DOWN for 1 sec to clear.
RUN TIME System pumpAllSystem pump run time (hours). Press UP/DOWN for 1 sec to clear.
RUN TIME DHW pumpMODE 2, 3DHW pump run time (hours). Press UP/DOWN for 1 sec to clear.
OUTLET HIAll
OUTLET LOAll
INLET HIAll
INLET LOAll
DELTA TAll
OUTDOOR HIMODE 1, 2, 3
OUTDOOR LOMODE 1, 2, 3
SYSTEM HIAll
SYSTEM LOAll
IND HIMODE 1, 2, 3
IND LOMODE 1, 2, 3
Records the highest boiler outlet temperature. Press UP/DOWN for 1 sec
to clear.
Records the lowest boiler outlet temperature. Press UP/DOWN for 1 sec to
clear.
Records the highest boiler inlet temperature. Press UP/DOWN for 1 sec to
clear.
Records the lowest boiler outlet temperature. Press UP/DOWN for 1 sec to
clear.
Captures the highest Delta T Temperature recorded Press UP & DOWN
buttons for 3 sec to clear this entry
Records the highest outdoor temperature. Press UP/DOWN for 1 sec to
clear.
Records the lowest outdoor temperature. Press UP/DOWN for 1 sec to
clear.
Records the highest supply temperature. Press UP/DOWN for 1 sec to
clear.
Records the lowest supply temperature. Press UP/DOWN for 1 sec to
clear.
Records the highest Indirect supply temperature. Press UP/DOWN for 1
sec to clear.
Records the lowest Indirect supply temperature. Press UP/DOWN for 1
sec to clear.
Table S: Monitor Menu
44
Page 45
Toolbox Menu
he Toolbox Menu logs all error codes from the VERSA and PIM, as well as other functions. Up to 15 error codes
T
can be logged for a maximum of 24 days.
tem
I
Lookup Active ErrorLook up and display the active error info.
USER TEST
MAX HEAT
P/N 104901Software number of the Raypak VERSA
DEFAULTS
HISTORY
lookup logged error
Select ON to start the function. The setting returns to default after the test is run.
(See Page 52 for details.)
Select ON to start the function. The setting will time out to OFF after 24 hours or can
be set to OFF again by the user. (See VERSA IC Applications Guide for details.)
Resets to factory settings. Press UP and DOWN for 1 second to show CLR and load
factory defaults to all settings. This will also clear all history.
Displayed when an error code is present. 1 indicates the most recent error code.
Press UP and DOWN for 1 second to clear the error logs.
Table T: Toolbox Menu
Outdoor Reset Concept
The Temperature controller can change the System
Set Point based on outdoor temperature (Outdoor
Reset). The temperature controller varies the temperature of the circulating heating water in response to
changes in the outdoor temperature. The heating
water temperature is controlled through the modulation and/or sequencing of the cascade.
The Temperature controller can also control the system circulating pump with an adjustable Outdoor
Cutoff. When the outdoor temperature is above the
Outdoor Cutoff, the pump is turned off and no heating
water is circulated through the system. When the outdoor temperature drops below the Outdoor Cutoff, the
system pump relay is activated and the heating water
circulates through the system. The temperature of the
heating water is controlled by the Reset Ratio, Water
Offset, and changes with the outdoor temperature.
Reset Ratio/Outdoor Reset
When a building is being heated, heat escapes
through the walls, doors, and windows to the colder
outside air. The colder the outside temperature, the
more heat escapes. If you can input heat into the building at the same rate that it is lost out of the building,
then the building temperatures will remain constant.
The Reset Ratio is an adjustment that lets you achieve
this equilibrium between heat input and heat loss.
escription
D
The starting point for most systems is the 1.00
(OD):1.00 (SYS) (Outdoor Temperature: Heating
Water Temperature) ratio. This means that for every
degree the outdoor temperature drops, the temperature of the heating water will increase one degree.
With the VERSA, both ends of the slope are
adjustable. It is factory-set at 70°F water temperature
(Boil START) at 70°F outdoor air (OUT START), and
180°F water temperature (Boil DESIGN) at 10°F outdoor air (OUT DESIGN).
Each building has different heat loss characteristics. A
very well insulated building will not lose much heat to
the outside air, and may need a Reset Ratio of 2.00
(OD):1.00 (SYS) (Outdoor: Water). This means the
outdoor temperature would have to drop 2 degrees to
increase the water temperature 1 degree. On the other
hand, a poorly insulated building may need a Reset
Ratio of 1.00 (OD):2.00 (SYS). This means that for
each degree the outdoor temperature dropped the
water temperature will increase 2 degrees. The
VERSA control Reset Ratio allows for full customization to match any building’s heat loss characteristics.
A heating curve that relies not only on Outdoor temperature but also on the type of radiation will improve heat
comfort. The user can fine-tune these adjustments
based on the specific building need.
45
Page 46
RESET RATIO
The control uses the four following settings to determine the reset ratio:
Boiler Start (Boil START)
T
he Bo il START temp er ature is the theo re tical bo iler s upply water t em perat ure that th e heat in g system re qu ires whe n the out door air
temperature equals the OUT START temperature setting. The Boil START is typically set to the desired building temperature.
O
utdoor Start (OUT START)
The OUT START temperature is the outdoor air temperature at which the control provides the Boil START water temperature to
the system. The OUT START is typically set to the desired building temperature.
Outdoor Design (OUT DESIGN)
The OUT DESIGN is the outdoor air temperature that is the typical coldest annual temperature where the building is located. This
temperature is used when completing heat loss calculations for the building.
Boiler Design (Boil DESIGN)
The Boil DESIGN temperature is the water temperature required to heat the boiler zones when the outdoor air is as cold as the
OUT DESIGN temperature.
Warm Weather Shut Down (WWSD)
When the outdoor air temperature rises above the WWSD setting, the
co ntrol tu rns on the WWSD se gment in the display. Wh en the co ntrol is in
Warm Weather Shut Down, the Dem 1 segment is displayed if there is a
heat demand. However, the control does not operate the boiler to satisfy
this demand. The control continues to respond to DHW demands.
Decreasing Outdoor Temperature
Increasing Water Temperature
Boil
START
OUT
DESIGN
Boil DESIGN
START
OUT
RESET RATIO =
(OUTDOOR START – OUTDOOR DESIGN)
(BOILER DESIGN – BOILER START)
Reset Ratio
The controller uses the following four settings to calculate the Reset Ratio (RR):
For example, when using the default values, the RR
is:
RR = (70 - 10) / (180 - 70) = 0.55
Therefore, the RR is 0.55:1 (Outdoor:Water).
Fig. 45: Reset Ratio
46
Page 47
WIRING
DIAGRAM
Fig. 46: Wiring Diagram
47
Page 48
CONVERTING NATURAL TO
ROTATERROTROTAROTATROTATE
TO OFF
ROTATETROTATE
TO OFF
RUBBERRRUBBER
GROMMET
RUBBERGRUBBER
GRO
RUBBER
GROM
RUBBER
GROMM
RUBBER
GROMME
RUBBER
GROMMET
PROPANEPPROPROPPROPAPROPA NPROPAN E
ORIFICE
PROPANE
ORIFICE
ASSEMBLEDASSEMBLED
ORIFICE IN
ASSEMBLED
ORIFICE IN
GROMMET
ASSEMBLED
ORIFICE IN
G
ASSEMBLED
ORIFICE IN
GRO
ASSEMBLED
ORIFICE IN
GROM
ASSEMBLED
ORIFICE IN
GROMM
ASSEMBLED
ORIFICE IN
GROMME
ASSEMBLED
ORIFICE IN
GROMMET
GASGAS
VALV E
GASVGAS
VAL
GAS
VALV E
PROPANEPPROPROPPROPAPROPANPROPAN E
ORIFICE
PROPANE
ORIFICE
RUBBERRRUBBER
GROMMET
RUBBERGRUBBER
GRO
RUBBER
GROM
RUBBER
GROMM
RUBBER
GROMME
RUBBER
GROMMET
ALLEN
RUBBER
GROMMET
ALLEN
SCREWS
RUBBER
GROMMET
ALLEN
SCREWS
BLOWER/
RUBBER
GROMMET
ALLEN
SCREWS
B
RUBBER
GROMMET
ALLEN
SCREWS
BLO
RUBBER
GROMMET
ALLEN
SCREWS
BLOW
RUBBER
GROMMET
ALLEN
SCREWS
BLOWE
RUBBER
GROMMET
ALLEN
SCREWS
BLOWER
RUBBER
GROMMET
ALLEN
SCREWS
BLOWER/
VENTURI
RUBBER
GROMMET
ALLEN
SCREWS
BLOWER/
VENTURI
ROTATERROTROTAROTATROTATE
TO OFF
ROTATE
T
ROTATE
TO OFF
V
ENTURIVENTURI
UNION
VENTUR
I
UNION
GAS VALVEGAS GAS VAGAS VALVGAS VALVE
ASSEMBLY
GAS VALVE
ASSEMB
GAS VALVE
ASSEMBLY
BLOWER
GAS VALVE
ASSEMBLY
B
GAS VALVE
ASSEMBLY
BLO
GAS VALVE
ASSEMBLY
BLOW
GAS VALVE
ASSEMBLY
BLOWE
GAS VALVE
ASSEMBLY
BLOWER
SCREW
GAS VALVE
ASSEMBLY
BLOWER
SCREW
SCREW
GAS VALVE
ASSEMBLY
BLOWER
SCREW
SCREW
VENTURIVENTURI
PROPANE GAS
These instructions are intended for boilers manufactured for Natural Gas. The instructions must be
ollowed by a trained qualified technician or manufac-
f
turing representative.
1. Turn power OFF to the boiler.
2. Remove screws holding top panel in place (located above boiler).
3. Turn Supply Gas OFF and/or turn the Manual
Valve to the OFF position (see Fig 47).
Fig. 49: Rubber Seal & Propane Orifice
10. Re-install grommet in between Venturi and Valve
assembly.
11. Re-install Allen screws to secure Gas Valve
assembly.
12. Tighten union to secure supply line to Gas valve.
13. Turn manual valve back on.
14. See “Gas Valve Adjustment” before running boiler.
For Models 198AR thru 398A
6. Loosen the Venturi union from the Manifold nipple
(see Fig 50).
Fig. 47: Shut-Off Valve & Venturi Location
88AR thru 108AR
4. Disconnect Gas Valve power harness.
5. Loosen union above Manual Valve.
For Models 88AR & 108AR (orifice supplied)
6. Remove the two Allen screws holding the Gas
Valve to the Venturi/Blower assembly (see Fig 48).
Fig. 48: Gas Train Assembly 88AR thru 108AR
7. Remove the Gas Valve assembly. This will reveal
the rubber grommet between the Gas Valve and
Venturi assembly.
8. Remove the rubber grommet.
9. Insert the Propane orifice inside this grommet.
There is a thin slot allocated for the orifice to slip
into. (see Fig 49).
Fig. 50: Shut-off Valve & Venturi Location
198AR thru 398A
7. Remove the Gas Valve assembly and set aside.
8. Remove the (3) screws holding the Natural Gas
Venturi to the Blower (see Fig 51).
Fig. 51: Gas Train Assembly 198AR thru 398A
48
Page 49
9. Replace the Natural Gas Venturi with the Propane
BLOWERBBLOBLOWBLOWEBLOWER
SCREW
BLOWER
SCREW
SCREW
BLOWER
SCREW
SCREW
VENTURIVENTURI
HI FIRE THROTTLEHI FIRE THHI FIRE THROHI FIRE THROTHI FIRE THROTTHI FIRE THROTTLHI FIRE THROTTLE
(
FLAT SCREWDRIVER)
HI FIRE THROTTLE
(FL
HI FIRE THROTTLE
(FLA
HI FIRE THROTTLE
(FL
AT SCREWDRIVER)
LO FIRE OFFSET
HI FIRE THROTTLE
(FL
AT SCREWDRIVER)
L
HI FIRE THROTTLE
(FL
AT SCREWDRIVER)
LO FIRE OFFSET
(
ALLEN WRENCH)
HI FIRE THROTTLE
(FL
AT SCREWDRIVER)
LO FIRE OFFSET
(ALLEN WRENCH)
GAS VALVEGAS GAS VAGAS VALVGAS VALVE
Venturi (see Fig 52).
Fig. 53: Setting Hi Fire Throttle / LO Fire Offset
Fig. 52: Propane Venturi
10. Re-install (3) screws to secure the Propane
Venturi to Blower.
11. Re-install Gas Valve assembly to Venturi by securing the union between them.
12. Tighten union to secure supply line to Gas valve.
13. Turn manual valve back on.
14. See “Gas Valve Adjustment” before running boiler.
GAS VALVE ADJUSTMENT
A Gas Valve adjustment is required to attain optimal
performance from the boiler when replacing one or
converting gas. These instructions must be followed
by a trained qualified technician or manufacturing
representative.
Valve adjustment throttle locations are indicated on
Figure 53.
CAUTION: Adjust the proper throttle on Hi Fire
and/or Offset on LO Fire. Adjustment of the LO fire
offset while the heater is running on Hi Fire may
cause the valve to work improperly and vice versa.
Setting Hi Fire Throttle:
1. Turn the needle down (clockwise) until the needle
bottoms out.
2. Follow Table U below for the number of 360°
counter-clockwise turns needed for each model
and Gas Type.
3. Once adjustment is made, turn heater on.
4. Adjust 0-10 VDC SIGNAL to 10 VDC.
5. Wait until “FIRE RATE” reaches 100%.
6. Adjust Hi Fire Throttle (see Fig. 53)) to get within
the combustion range required.
Setting LO Fire Offset (while heater is running on
LO Fire):
1. Adjust 0-10 VDC signal to 1 VDC.
2. Wait until Blower RPM reaches 1300 RPM.
3. Using an Allen wrench turn the Offset slightly
clockwise to increase CO2values (see Fig. 53).
4. Adjust 0-10 VDC signal back to 10 VDC.
5. Verify combustion is still within range given in
Table U. Adjust if necessary.
tandard options. Refer to the large wiring diagram
s
provided with your boiler for options installed on your
specific unit(s).
START-UP
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
Pre Start-up
•If you cannot reach your gas supplier, call the fire
epartment.
d
•Use only your hand to close the gas supply shutoff
valve inside the boiler. Never use tools. If the knob
will not turn by hand, do not try to repair it, call a
ualified service technician. Forced or attempted
q
repair may result in a fire or explosion.
Do not use this appliance if any part has been
•
under water. Immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas control
which has been under water.
•Check around unit for debris and remove com-
bustible products, i.e. gasoline, etc.
Filling System (Heating Boilers)
Fill system with water. Purge all air from the system.
Lower system pressure. Open valves for normal system operation, and fill system through feed pressure.
Manually open air vent on the compression tank until
water appears, then close vent.
Venting System Inspection
1. Check all vent pipe connections and flue pipe material.
2. Make sure vent terminations are installed per code
and are clear of all debris or blockage.
For Your Safety
This appliance has a direct spark igniter. It is equipped
with an ignition device which automatically lights the
burners. Do not try to light the burners by hand.
BEFORE OPERATING, smell all around the appliance
area for gas. Be sure to smell near the floor because
some gas is heavier than air and will settle on the floor.
Pre Start-up Check
1. Verify the boiler is filled with water.
2. Check system piping for leaks. If found, repair
immediately.
3. Vent air from system. Air in system can interfere
with water circulation.
4. Purge air from gas line to boiler.
Initial Start-up
Required tools
•(1) 12-0-12 (24” scale) U-tube manometer
•(2) 6-0-6 (12” scale) U-tube manometer
•Screwdrivers (assorted sizes and shapes)
•(1) Crescent wrench (8” or 10”)
•(1) Multi-meter
(Metric Allen wrenches will be required for servicing
the gas valve, but not during start-up)
NOTE: Digital manometers are not recommended.
WHAT TO DO IF YOU SMELL GAS:
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any
telephone in your building.
•Immediately call your gas supplier from a neighbor’s telephone. Follow the gas supplier’s
instructions.
50
Page 51
Preparation
WARNING: Do not turn on gas at this time.
Check Power Supply
ith multi-meter at incoming power, check voltage
W
between:
Hot - Common (≈120 VAC)
Hot - Ground (≈120 VAC)
Common - Ground (< 1 VAC)
WARNING: If Common - Ground is > 1 VAC,
STOP: Contact electrician to correct ground failure.
Failure to do this may burn out 120V-24V
transformer, or may cause other safety control
damage or failure.
NOTE: While attaching manometers, any cap or
bleedle valves removed should be retained for
reinstallation later.
ttach Manometers to Measure Pressures
A
1. Turn off main gas shutoff valve.
. Attach a 24” scale manometer to the supply pres-
2
sure test port on the gas valve to the heater (see
Fig. 54).
. Attach a 12” scale manometer to the offset pres-
3
sure testport for Models 88AR-108AR. For Models
198AR-398A attach manometer to manifold pressure tap (see Fig. 54).
Check Gas Supply Pressure
1. Slowly turn on main gas shut-off valve.
2. Read the gas supply pressure from the manome-
ter; minimum supply pressure for natural gas is 4.5
in. WC, recommended supply is 7.0 in. WC, minimum supply pressure for propane gas is 8.0 in.
WC, recommended supply is 11.0 in. WC (dynamic readings, full fire input).
3. If the gas pressure is greater than 14.0 in. WC,
turn off the main gas shut-off valve.
Fig. 54: Gas Pressure Measurement Locations
51
Page 52
Start-Up
. Turn power on.
1
2. Turn on the boiler, approximately 45 seconds after
the blower starts, the igniter should start to spark.
3. The boiler ignites at 3000 RPM (as indicated on the
LCD display of the user interface).
4. This boiler is equipped with a three-try ignition
module, it will try for ignition up to three times
before going into lockout.
5. Wait until the controller indicates a percentage on
the firing rate display screen. This may take several minutes.
Manifold Check
1. Check manifold gas pressure at the manifold pressure tap. This pressure should read per the values
in Table U, on page 49.
User Test
Set DIP #1 on the VERSA IC control to “ON”. Set
•
USER TEST = ON in the 'ToolBox' Menu to start
he user test function.
t
• USER TEST is displayed in the Title Field.
•UP keystrokes are used to advance through the
user test.
•The Boil MIN/MAX steps for burner operation are
only run for enabled boilers.
•Local Heat/DHW/EMS demands must be present
for burner operation.
•On the first press of the Up button, the test step is
held and "HOLD" is flashed at 1Hz.
•On the second press of the Up button, the test
step is incremented.
•If boiler outlet temperature reaches the PIM HiLimit, the boiler will be ramped down to keep the
temperature in a safe range.
•Press of the Up button from Boiler Max will End
the User Test function.
2. Valves should be within the specified ranges given
on Table U, on page 49.
Number
Field
SYSSystem Pump relay turns on.
DHWDHW Pump relay turns on.
PMP 1System and Boiler Pump relays turn on.
Boil 1Ignite Boiler Burner.
Min 1Hold Boiler at Min Fire.
Max 1Ramp Boiler to Max Fire and hold.
Output Action
Table V: User Test Fields
52
Page 53
Safety Inspection
1. Check all thermostats and high limit settings.
2. During the following safety checks leave manometers hooked up, check and record.
. If other gas-fired appliances in the room are on the
3
same gas main, check all pressures on the XPak
FT with all other equipment running.
4. Check thermostats for ON-OFF operation.
5. Check high limits for ON-OFF operation.
6. While in operation, check flow switch operation (if
equipped).
7. Check the low gas pressure switch (if provided).
(For proper adjustment, use the attached
manometers, if available, to set pressure. The
scales on the switch are approximate only.) Low
gas pressure switch (if provided) must be set at
3.0 in. WC for natural gas and propane gas.
8. Make sure that the high gas pressure switch (optional) is set to 3.0 in. WC for both natural gas and
propane gas.
Post Start-Up Check
. Verify that the boiler and heat distribution units or
1
2. Confirm that the manual air vent was opened duing
3. Verify that air has been purged from the system.
4. Verify that air has been purged from the gas pip-
5. Confirm that the proper start-up procedures were
6.Inspect burner to verify flame.
7. Test safety controls: If boiler is equipped with a low
8. Check to see that the high limit control is set
Finishing
Record all data on the “Start-up Checklist” located at
the back of this manual.
2. Disconnect the manometers and reconnect the
cap on the air intake and reinsert or close the sealing screws into the bleedle valves.
3. Start-up is complete and the boiler should be operating properly.
9. Check that the boiler is cycled with the thermostat.
10. Observe several operating cycles for proper oper-
storage tank are filled with water.
the venting procedure.
ing, and that the piping has been checked for
leaks.
followed.
water cut-off or additional safety controls, test for
operation as outlined by manufacturer. Burner
should be operating and should go off when controls are tested. When safety devices are restored,
burners should re-ignite after pre-purge time
delay.
above the design temperature requirements of the
system. For multiple zones: Check to make sure
the flow is adjusted as required in each zone.
Raise the setting on the thermostat to the highest
setting and verify that the boiler goes through the
normal start-up cycle. Reduce to the lowest setting and verify that the boiler goes off.
ation.
Follow-Up
Safety checks must be recorded as performed. Turn
boiler on. After main burner ignition:
1. Cycle unit several times and re-check readings.
2. Remove all manometers and replace caps and
screws.
3. Check for gas leaks.
11. Set the boiler thermostat to desired temperature.
12. Review all instructions shipped with this boiler with
owner or maintenance person, return to envelope
and give to owner or place the instructions inside
front panel on boiler.
53
Page 54
Fig. 55: Boiler Lighting Shut Off Instructions
54
Page 55
TROUBLESHOOTING
XPak FT Error Codes
f any of the sensors detect an abnormal condition or
I
an internal component fails during the operation of the
XPak FT, the display may show an error code. This
code may either be the result of a temporary condition
n which case the display will revert to its normal read-
i
out when the condition is corrected, or it may be the
result of a condition that the controller has evaluated
as not safe to restart the unit. In this case, the unit control will be locked out, requiring the maintenance
person to manually reset the control by pressing and
releasing the RESET key.
WARNING: When servicing or replacing any
components of this unit be certain that:
• The gas is off.
• All electrical power is disconnected.
Sensor Resistance Values
Water Sensor / Outdoor Sensor
Water Temperature
(°F)
3232550
4125340
Resistance (ohms)
Heater Errors
When an error condition occurs, the controller will display an error code on the display module. These error
codes and several suggested corrective actions are
included in the XPak FT Fault Text section on the following page.
Heater Faults
1. When a fault condition occurs, the controller will
flash a red light on the PIM and display the error
code on the user interface. The alarm output will
also be activated. Most fault conditions will also
cause the boiler pump to run in an attempt to cool
the unit.
2. Note the error code, either through the flash code
on the PIM and/or from the Toolbox menu on the
user interface, and reference the explanation of
the fault along with troubleshooting steps in the
XPak FT fault text section.
3. Press and release the RESET key to clear the
fault on the user interface and resume operation.
Be sure to observe the operation of the unit for a
period of time to ensure correct operation and no
reoccurrence of fault code(s).
5019870
5915700
6812490
7710000
868059
956535
1045330
1134372
1223605
1312989
1402490
1492084
1581753
1671481
1761256
1851070
194915
203786
DANGER: When servicing or replacing components
that are in direct contact with the water, be certain
that:
• There is no pressure in the boiler. (Pull the release
on the relief valve. Do not depend on the pressure
gauge reading).
• The boiler water is not hot.
• The electrical power is off.
212667
Table W: Sensor Resistance Values
55
Page 56
3/16”
WARNING: Do not use this appliance if any part
has been under water. Improper or dangerous
operation may result. Contact a qualified service
echnician to inspect the boiler and to repair or
t
replace any part of the boiler that has been under
water prior to placing the boiler back in operation.
CAUTION: Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing. See wiring diagram.
CAUTION: If overheating occurs or the gas supply
fails to shut off, do not turn off electrical power to the
circulating pump. This may aggravate the problem
and increase the likelihood of boiler damage.
Instead, shut off the gas supply to the boiler at the
gas service valve.
XPak FT Fault Text
Error Display
If there is an active error, then it is displayed as the first
item in the Toolbox Menu and it is the default display
for the control until the error is resolved.
NOTE: If receiving a NO FLAME, check the gap spacing between
points on the electrode by holding two quarters together and sliding
them through the gap. There should be no resistance.
Fig. 56: Direct Spark Igniter
Error ItemDescription and Troubleshooting
OUTLET SENCheck the outlet water sensor and its wiring.
LIMIT SENCheck the high limit sensor and its wiring.
INLET SENCheck the inlet sensor and its wiring.
GAS PRESSCheck PIM wiring.
IGNITIONReset control, push and release RESET button
LIMIT TRIPBoiler temperature tripped the high limit.
FLAMEFalse flame detected. Shut off gas supply, recycle power.
ID CARDIdentity card, check ID card and wiring.
IGN CTRLInternal control fault. Reset power, replace control.
DELTA T
Temperature difference between the inlet and outlet exceeded the set
point. Check water flow.
LOW 24VACLow 24 VAC power. Check power supply wiring and transformer.
BLOW SPEEDBlower speed out of range. Check blower wiring and blower.
Table X: Error Display
56
Page 57
LED Error Code Listing
ctive errors detected are indicated by LED lights on the PIM.
A
LED CodeError ModeRecommended Troubleshooting
OffNormal Operation
Red LED
steady ON,
Green Power
ID Card Fault
LED OFF
Steady ONInternal Control Failure Perform a power and system reset. If fault remains, replace PIM.
1 flashN/AN/A
2 flashesFalse Flame ErrorCheck for proper gas valve closure. Clean burner and electrodes.
3 flashesIgnition Lockout FaultCheck the gas supply. See table for more information.
4 flashesN/AN/A
Check that the proper ID card is securely connected. Perform a
power and system restart.
5 flashesLow Voltage Fault
Check the 24 VAC input voltage. The voltage must be above 18.0
VAC.
6 flashesN/AN/A
7 flashesHi-Limit FaultCheck for proper water flow. Check hi-limit and outlet sensor.
8 flashesSensor FaultSee VERSA for fault identification. Check sensor wiring.
9 flashesN/AN/A
10 flashesN/AN/A
11 flashesBlower Speed FaultVerify tachometer signal and connection on J5.
12 flashesN/AN/A
13 flashes
14 flashes
Hi-Temperature Delta
Fault
Ft-Bus
Communications Fault
15 flashesSafety Circuit Open
Check pump operation. Confirm proper water flow across heat
exchanger.
Verify VERSA is connected and operating. Check the cable between
the VERSA and PIM.
Confirm all safeties are functioning normally. Check continuity at the
PIM at J8 plug, pins 5 and 6.
Table Y: PIM LED Error Codes
57
Page 58
MAINTENANCE
Suggested Minimum
Maintenance Schedule
Regular service by a qualified service agency and
maintenance must be performed to ensure maximum
operating efficiency.
Maintenance as outlined below may be performed by
the owner.
Daily
1. Check that the area where the boiler is installed is
free from combustible materials, gasoline, and
other flammable vapors and liquids.
2. Check for and remove any obstruction to the flow
of combustion or ventilation air to boiler.
.Check that area is free from combustible materi-
3
als, gasoline, and other flammable vapors and liquids.
. Check for and remove any obstruction to the flow
4
of combustion or ventilation air to boiler.
5. Follow pre-start-up check in the Start-up section.
6.Visually inspect burner flame. It should be light
blue at full input. Remove and visually inspect
direct spark igniter and sensor for damage, cracking or debris build-up.
7. Check operation of safety devices. Refer to manu-
facturers’ instructions.
8. Follow oil-lubricating instructions on pump (if re-
quired). Over-oiling will damage pump.
Water-lubricated circulators do not need oiling.
Monthly
1.Check for piping leaks around pumps, mixing
valves, relief valves, and other fittings. If found,
repair at once. DO NOT use petroleum-based
stop-leak compounds.
2.Visually inspect burner flame.
3.Visually inspect venting system for proper function, deterioration or leakage.
4. Visually inspect for proper operation of the con-
densate drains in the venting, and the internal condensate trap. Clean trap as necessary. If leaks are
observed, repair at once.
5. Check air vents for leakage.
Yearly (Beginning Of Each Heating
Season)
Schedule annual service call by qualified service
agency.
1.Visually check top of vent for soot. Call service
person to clean. Some sediment at bottom of vent
is normal.
2.Visually inspect venting system for proper func-
tion, deterioration or leakage. Ensure that condensate drain is inspected and ensure that
condensate is being directed to appropriate condensate management system or drain, as
required by local codes.
9. To avoid potential of severe burn, DO NOT REST
HANDS ON OR GRASP PIPES. Use a light touch;
return piping will heat up quickly.
10. Check blower and blower motor.
11. Check for piping leaks around pumps, relief valves
and other fittings. Repair, if found. DO NOT use
petroleum-based stop-leak.
Periodically
1.Check relief valve. Refer to manufacturer’s
instructions on valve.
2. Test low water cut-off (if equipped). Refer to manufacturer’s instructions.
Preventive Maintenance
Schedule
The following procedures are recommended and are
good practice for all XPak FT installations.
Daily
1. Check gauges, monitors and indicators.
2. Check instrument and equipment settings. (See
“Post Start-Up Check”.)
3. Check burner flame. (Should see light blue flame
at full input rate).
58
Page 59
Monthly
. Check flue, vent, stack, or dampers.
1
2. Check drip leg and gas strainers.
.Test high and low gas pressure interlocks (if
2
equipped). (See “Safety Inspection”.)
Semi-Annually
1. Recalibrate all indicating and recording gauges.
2. Check flame failure detection system components.
3. Check firing rate control by checking the manifold
pressure. (See “Manifold Check”.)
4. Check piping and wiring of all interlocks and shutoff valves.
Annually
1. Test flame failure detection system.
2. Test high limit and operating temperature. (See
“Post Start-Up Check”.)
3. Check flame sensor.
4. Refer to Table U for gas valve combustion readings.
3. Check flame failure detection system. (See “Post
Start-Up Check”.) Verify high and low fire flame
signal, compare to start-up data.
4. Check igniter. Clean and verify spark gap (see
Fig. 56).
5. Check fan speed and manifold pressure. (See
“Blower Check” and “Manifold Check”.)
6. Test safety/safety relief valves in accordance with
ASME Heater and Pressure Vessel Code Section
IV.
5. Check valve coil for 60-cycle hum or buzz. Check
for leaks at all valve fittings using a soapy water
solution (while unit is operating). Test other operating parts of all safety shut-off and control valves
and increase or decrease settings (depending on
the type of control) until the safety circuit opens.
Reset to original setting after each device is tested.
6. Perform leakage test on gas valves, if required by
local codes.
7. Inspect and clean burner using shop air.
8. Clean the combustion chamber coil, using the procedure on the following page.
As Required
1. Recondition or replace low water cut-off device (if
equipped).
59
Page 60
WARNING:
The combustion chamber insulation in this product
contains ceramic fiber material. Ceramic fibers can
e converted to cristobalite in very high temperature
b
applications. The International Agency for Research
n Cancer (IARC) has concluded that “Crystalline
o
silica inhaled in the form of quartz or cristobalite from
occupational sources is carcinogenic to humans
(Group1).”:
Combustion Chamber Cleaning
Instructions
Before beginning this procedure, you must have on
hand the following items:
a nylon, stainless steel or brass brush (not steel)
–
– “Rydlyme” (recommended for best results) or
“CLR”
– Gloves, eye protection
Avoid breathing dust and contact with skin and •
eyes.
Use NIOSH certified dust respirator (N95).•
This type of respirator is based on the OSHA
requirements for cristobalite at the time this
document was written. Other types of respirators
may be needed depending on the job site
conditions. Current NIOSH recommendations
can be found on the NIOSH website at
http://www.cdc.gov/niosh/homepage.html.
NIOSH approved respirators, manufacturers,
and phone numbers are also listed on this
website.
Wash potentially contaminated clothes•
separately from other clothing. Rinse clothes
washer thoroughly.
NIOSH stated First Aid:
Eye: Irrigate immediately
Breathing: Fresh air.
1. Shut down the XPak FT boiler by using the following steps:
a. Close the gas valve, shut down the unit and
wait for the unit to be cool to the touch.
b. Disconnect the condensate piping from the out-
side connection, (not from the XPak FT boiler
side), so the flow from condensate reservoir
can be observed.
c. Disconnect electrical connections from the gas
valve, spark electrode and flame rectification
probe and combustion blower.
d. Disconnect the gas line by loosening union
above the shut-off valve.
e. Disconnect the wiring connected to the com-
bustion blower motor.
f. Remove the 10mm nuts from the burner plate
assembly.
g. Remove the valve/blower/burner assembly
with refractory from the heat exchanger.
2. Using a spray bottle filled with the recommended
product “RYDLYME” or “CLR”, spray liberally on the
heat exchanger, making sure the solution penetrates and funnels down through the condensate
system. If the condensate system is blocked, let the
chemical penetrate for at least 15 minutes or until it
drains.
3. Use the nylon, stainless steel or brass brush (do not
use steel) to scrub heat exchanger to remove any
buildup, then vacuum the debris from the heat
exchanger.
4. Spray the heat exchanger with clear water, making
sure to confine the spray to the area being cleaned.
Flush the combustion chamber with fresh water
until clear water runs from the condensate drain. At
this point, the XPak FT should be ready to be reassembled.
a. Inspect gaskets.
b. Re-install the burner assembly.
60
Page 61
2. You want to reduce infiltration into your building
3. You are using AL29-4C stainless steel vent pipe,
which is more corrosion-resistant than standard
metallic vent pipe. In extremely contaminated ar-
as, this may also experience deterioration.
e
Products causing contaminated combustion air:
• spray cans containing chloro/fluorocarbons
• permanent wave solutions
• chlorinated waxes/cleaners
• chlorine-based swimming pool chemicals
• calcium chloride used for thawing
• sodium chloride used for water softening
• refrigerant leaks
• paint or varnish removers
• hydrochloric acid/muriatic acid
• cements and glues
• antistatic fabric softeners used in clothes dryers
•chloride-type bleaches, detergents, and cleaning
solvents found in household laundry rooms
• adhesives used to fasten building products
• similar products
Fig. 57: Heat Exchanger Components Removal
APPENDIX
Inside Air Contamination
Combustion air can be contaminated by certain vapors
in the air which raise the acidity of the condensate.
Higher acidity levels attack many materials including
stainless steel, which is commonly used in high efficiency systems. The boiler can be supplied with corrosion-resistant, non-metallic intake air vent material.
You may, however, choose to use outside combustion
air for one or more of these reasons:
Areas where contaminated combustion air commonly
exists:
•dry cleaning/laundry areas
•metal fabrication plants
•beauty shops
•refrigeration repair shops
•photo processing plants
•auto body shops
•plastic manufacturing plants
•furniture refinishing areas and establishments
•new building construction
•remodeling areas
•open pit skimmers
Check for areas and products listed above before installing boiler. If found:
•remove products permanently, OR
•install TruSeal direct vent.
1. Installation is in an area containing contaminants
listed below which will induce acidic condensation.
61
Page 62
Important Instructions for the Commonwealth of Massachusetts
The Commonwealth of Massachusetts requires compliance
with regulation 248 CMR 4.00 and 5.00 for installation of
hrough – the – wall vented gas appliances as follows:
t
(a) For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but
not limited to decks and porches, the following requirements
shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gasfitter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the floor level
where the gas equipment is to be installed. In addition, the
installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an
alarm is installed on each additional level of the dwelling,
building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the
property owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon
monoxide detectors
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the
hard wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the
above requirements; provided, however, that during said
thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each
carbon monoxide detector as required in accordance with
the above provisions shall comply with NFPA 720 and be
ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with
the exhaust vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The sign shall read,
in print size no less than one-half (1/2) inch in size, "GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
(b) EXEMPTIONS: The following equipment is exempt from
248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment
Not Required To Be Vented" in the most current edition of
NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally
vented gas equipment provides a venting system design or
venting system components with the equipment, the instructions provided by the manufacturer for installation of the
equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the
manufacturer of a Product Approved side wall horizontally
vented gas fueled equipment does not provide the parts for
venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the
manufacturer:
1. The referenced "special venting system" instructions shall
be included with the appliance or equipment installation
instructions; and
2. The "special venting systems" shall be Product Approved
by the Board, and the instructions for that system shall
include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting
instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion of
the installation.
4. INSPECTION. The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
62
Page 63
LIMITED PARTS WARRANTY XPak FT®– TYPE H
MODELS 88AR-398A
COPE
S
Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this heater which are actually manufactured by Raypak will be free from failure under
ormal use and service for the specified warranty periods and subject to the conditions set forth in this Warranty. Labor charges and other costs for parts
n
emoval or reinstallation, shipping and transportation are not covered by this Warranty but are the owner’s responsibility.
r
HEAT EXCHANGER WARRANTY
pace Heating (Closed Loop System)
S
en (10) year limited warranty from date of heater installation. This warranty applies only to boilers utilized in closed loop heating systems and hot water sup-
T
ply boilers that have been properly installed based upon manufacturer’s installation instructions.
ear of Claim0-56789
Y
Percentage to be paid
by purchaser0 %20%40%60%80%
Thermal Shock Warranty
wenty (20) years from date of heater installation against “Thermal Shock” (excluded, however, if caused by heater operation at large changes exceeding
T
150°F between the water temperature at intake and heater temperature, or operating at heater temperatures exceeding 215°F).
ANY OTHER PART MANUFACTURED BY RAYPAK
ne (1) year warranty from date of heater installation, or eighteen (18) months from date of factory shipment based on Raypak’s records, whichever comes
O
first.
SATISFACTORY PROOF OF INSTALLATION DATE, SUCH AS INSTALLER INVOICE, IS REQUIRED. THIS WARRANTY
WILL BE VOID IF THE HEATER RATING PLATE IS ALTERED OR REMOVED.
ADDITIONAL WARRANTY EXCLUSIONS
This warranty does not cover failures or malfunctions resulting from:
1. Failure to properly install, operate or maintain the heater in accordance with our printed instructions provided;
. Abuse, alteration, accident, fire, flood and the like;
2
3. Sediment or lime build-up, freezing, or other conditions causing inadequate water circulation;
4. High velocity flow exceeding heater design rates;
5. Failure of connected system devices, such as pump or controller;
6. Use of non-factory authorized accessories or other components in conjunction with the heater system;
7. Failing to eliminate air from, or replenish water in, the connected water system;
8. Chemical contamination of combustion air or use of chemical additives to water.
PARTS REPLACEMENT
Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if requested, with transportation
charges prepaid, and all applicable warranty conditions found satisfied. The replacement part will be warranted for only the unexpired portion of the original
warranty. Raypak makes no warranty whatsoever on parts not manufactured by it, but Raypak will apply any such warranty as may be provided to it by the
parts manufacturer.
TO MAKE WARRANTY CLAIM
Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and description of the problem. The installer must
then notify his Raypak distributor for instructions regarding the claim. If either is not available, contact Service Manager, Raypak, Inc.,
2151 Eastman Avenue, Oxnard, CA 93030 or call (805) 278-5300. In all cases proper authorization must first be received from Raypak before
replacement of any part.
EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY
This is the only warranty given by Raypak. No one is authorized to make any other warranties on Raypak’s behalf. THIS WARRANTY IS IN LIEU OF ALL
OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE. RAYPAK’S SOLE LIABILITY AND THE SOLE REMEDY AGAINST RAYPAK WITH RESPECT TO DEFECTIVE PARTS SHALL
BE AS PROVIDED IN THIS WARRANTY. IT IS AGREED THAT RAYPAK SHALL HAVE NO LIABILITY, WHETHER UNDER THIS WARRANTY, OR IN
CONTRACT, TORT, NEGLIGENCE OR OTHERWISE, FOR ANY SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGE, INCLUDING DAMAGE
FROM WATER LEAKAGE. Some states do not allow limitations on how long an implied warranty lasts, or for the exclusion of incidental or consequential
damages. So the above limitation or exclusion may not apply to you.
This Limited Warranty gives you specific legal rights. You may also have other rights which may vary from state to state. We suggest that you complete the
information below and retain this certificate in the event warranty service is needed. Reasonable proof of the effective date of the warranty (date of installation) must be presented; otherwise, the effective date will be based on the date of manufacture plus thirty (30) days.
This start-up checklist is to be completely filled out by the service technician starting up the Raypak Boiler or Heater
for the first time. All information may be used for warranty purposes and to ensure that the installation is correct.
Additionally this form will be used to record all equipment operation functions and required settings.
GAS SUPPLY DATA CLEARANCES
Regulator Model & Size _________ / ______CFH Front Clearance _______________In.
G
as Line Size (in room) ________________In. NPT Right Side Clearance _______________In.
Length of Gas Line ________________Eq Ft Left Side Clearance _______________In.
Low Gas Pressure Setting ________________In. WC Rear Clearance _______________In.
High Gas Pressure Setting ________________In. WC Overhead Clearance _______________In.
Gas Shut-Off Valve Type ________________
( Ball, Lube cock)
ELECTRICAL
S
ediment Trap ________________Y/N Voltage Supply (VAC) No Load______ Load_____
Port _______Std______Full Voltage -24 VAC _______________VAC
Voltage Com to Ground _______________VAC
VISUAL INSPECTION OF COMPONENTS
Verify inspection was done and condition of components are in
good working order with a “yes”
Auto High Limit Setting
Manual Reset High Limit Setting
_______________deg F
_______________deg F
Wiring Harness _________________ Y/N Operating Control Setting _______________deg F
Burner/s (flame) _________________ Y/N
Refractory (visual) _________________ Y/N Sketch plumbing on reverse side
Remote fla me sense _________________ Y/N
WATER SUPPLY
Covers in place for outdoor _________________ Y/N Flow Rate in GPM or De lta T _______________If Avail
Measure flow rate at full fire
VENTING
Pump Off Delay setting _______________Minutes
Vent Size: _____________ Stack Height:_______ Low Water Cutoff _______________Test
Category: _________ sketch vent on reverse side ***Number of Tanks and Size Qty____ _______Gallons
Vent Material: __________________ Plumbing Size _______________
Vent Termination Type: __________________ Pump Size: _________(boiler) Pump HP: ______
Combustion Air Openings: Low __________ in2 Impeller trim____________ Pump Model___________
Ventilation air High __________ in2 Louvers __________________ Screens________________
EMISSIONS SETTINGS AND TEST INFORMATIONNominal Factory Recommended Settings
Air Intake Pressure _________________In. WC See manual or card tag
Supply Gas Pressure
Verify stable pressure static &
_________________In. WC
dynamic condition
See manual or card tag
Manifold Gas Pressure _________________In. WC See manual or card tag
The following measurements must be obtained with a Combustion Analyzer.
NOX _________________PPM Less than 20 PPM (If required by Certifying Agency)
CO _________________PPM Less than 150 PPM
CO2 _________________% See manual
Model Number: ______________________________ Serial Number: _______________________________
*** Note: draw venting with details, such as extractors,
barometric dampers, blast dampers or draft inducers
Site Altitude Above Sea Level __________________Ft.
Job Name _______________________________________________________________________________________