INSTALLATION & OPERATING
INSTRUCTIONS
Adds 4-20mA Setpoint capability to
TempTracker Mod+ Control System
4-20mA
EMS
Interface
4-20 mA EMS
4-20mA INPUT
Signal GND
+
2
1
3
RS485
EXTENSION
CONNECTORS
2
INTRODUCTION
The 4-20mA EMS Interface provides the TempTracker
Mod+ control with the capability of receiving an external Setpoint as a 4-20mA signal through Energy
Management or Building Management Systems
(EMS/BMS). The External Setpoint is a temperature
input and can also function as a Shutdown signal.
WIRING
Wiring the EMS Signal
• The signal must be a two-wire 4-20mA.
• A system sensor must be installed to the
TempTracker Mod+ control.
• The External Setpoint must be set up correctly
(See TempTracker Mod+ documentation). These
settings will allow the TempTracker Mod+ to read
and monitor the system temperature and also
monitor the 4-20mA input to remotely adjust the
setpoint to the desired value.
• If the EMS/BMS or other equipment signal provides the DC current, attach the (+) side of the
EMS/BMS signal to the 4-20mA EMS Interface terminal marked SIGNAL. Attach the (-) side of the
EMS/BMS signal to the 4-20mA EMS Interface terminal marked GND as shown in Fig. 1.
• The 4-20mA EMS Interface can provide the DC
current for the 4-20mA input signal. If using the 420mA EMS Interface to provide the power, attach
the (+) side of the EMS/BMS signal to the 4-20mA
EMS Interface terminal marked +. Attach the (-)
side of the EMS/BMS signal to the 4-20mA EMS
Interface terminal marked SIGNAL as shown in
Fig. 2.
Fig. 2: TempTracker Provides Current for 4-20 mA
Signal
Fig. 1: External Device (e.g. BMS) Provides Current for
4-20 mA Signal
4-20mA INPUT
Signal
GND
+
2
1
3
RS485
EXTENSION
CONNECTORS
(-)
EMS/BMS Input
(+)
4-20mA INPUT
GND
Signal
+
2
1
3
(-)
EMS/BMS Input
RS485
EXTENSION
CONNECTORS
(+)