Rain Bird ESP-LXIVM Troubleshooting Guide

ESP-LXIVM Controller
Troubleshooting Guide
For product manuals, instructional videos and FAQs, please visit: www.rainbird.com/esplxivm
For free professional support for programming and troubleshooting, please call: 1-866-544-1406

Local Rain Bird Contact Information

Distributor Mgr:
Email:
Phone:
Area Specification Mgr
Public Agency Manager:
Email:
Phone:
Contractor Account Mgr:
Email:
Phone:
Water Conservation Mgr:
Email:
Phone:
2 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Contents
Local Rain Bird Contact Information ..................................... 2
Tools ..................................................................... 4
Recommended ............................................................................. 4
Useful ............................................................................................... 5
LX-IVM Compatible Valves .................................5
Controller Features ............................................. 6
Front Panel .....................................................................................6
2-Wire Settings .............................................................................7
Diagnostics .................................................................................... 7
Cabinet Components ................................................................. 8
Basic Programming ............................................9
Troubleshooting Flow Charts .............................10
Getting Started ...........................................................................10
2-Wire Mapping .........................................................................11
No Water Days, No Run Times, … ........................................13
Shorted Paths ..............................................................................14
Shorted Path (Manual Method) .........................................15
Duplicate Address .....................................................................19
Flow Alarm ...................................................................................20
Ping Valve / Sensor (Ping Test) ..............................................22
Field Wiring Diagnostics ...................................23
Tools and Equipment ...............................................................23
Total System Milliamp Draw ..................................................23
3 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Field Wiring Issues .....................................................................23
Broken Wire (Open Circuit) List Not Responding .........24
Short Circuit ..............................................................................25
Ground Fault .............................................................................26
Relay Wiring .................................................................................27
IVM Power Filter Connection .................................................29
Controller Diagnostics ...................................... 30
IVM Interface Module ....................................... 37
LED Indicators .............................................................................37
LED Status ....................................................................................38
Module Status ..........................................................................38
2-Wire Path Status ...................................................................38
Individual Path Status ............................................................38

Tools

Recommended

MAXI Cable 2-Wire communications cable.
Rain Bird WC20 splice kits for ALL electrical wiring connections.
Rain Bird genuine Wire Stripper For video showing proper wire splice instructions and other installation tips, please visit:
www.rainbird.com/esplxivm
NOTE: If installing or repairing
communications wiring for IQ Software, do not install the communications cables in the same conduit as the 2-Wire path wiring.
Rain Bird
Wire Stripper
4 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

Useful

Milliamp Meter Recommended Model: Armada Pro 93
As-Built Drawing If you don’t have it, make it using a cable locator
LX-IVM Troubleshooting Tools
A list of ESP-LXIVM Controller Troubleshooting Videos can be found here:
https://www.rainbird.com/esplxivm

LX-IVM Compatible Valves

Videos for ESP-LXIVM compatible valves ,connecting and troubleshooting can be found here:
PGA Series
https://www.rainbird.com/products/pga-series
PEB Series
https://www.rainbird.com/products/pebpesb-series
EFB-CP Series
https://www.rainbird.com/products/efb-cp-series
BPE Series
https://www.rainbird.com/products/300-bpes
NOTE: Rain Bird HV, DV, and JTV Series residential valves are not
compatible with IVM-SOL. Use only Rain Bird commercial series valves for ESP-LXIVM installations:
NOTE: Physical intereference on any valves can be addressed
through “clocking” to avoid being “in-line” with IVM-SOL or removing the component (e.g. Flow Control).
5 ESP-LXIVM Controller Troubleshooting Guide
Milliamp
Meter
Table of
Contents

Controller Features

Front Panel

PROGRAMMING
DIAL
BACK BUTTON
PROGRAM
SELECT BUTTON
DISPLAY
PROGRAMMING
KEYS
ALARM
LIGHT
LANGUAGE
SELECT BUTTON
INFORMATION
BUTTON
6 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

2-Wire Settings

Diagnostics

7 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

Cabinet Components

IVM 2WIRE INTERFACE MODULE
JUNCTION
BOX
TRANSFORMER
8 ESP-LXIVM Controller Troubleshooting Guide
CONNECTOR
Table of
Contents

Basic Programming

The ESP-LXIVM Controller has 2-Wire Settings to help get you started and guide you through each step of the installation and hardware setup process.
It’s most effective to use the 2-Wire Settings in the order they appear in the
2-Wire Settings menu, as follows:
1. Master Valves
2. Weather Sensors (if present)
3. Station Setup
4. Flow Sensors (if present)
Installation, Programming & Operation Guide
For more information see the LX-IVM Field Device Installation Guide that came with the LX-IVM Controller.
Or download the LX-IVM User Manual at:
www.rainbird.com/esplxivm
9 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

Troubleshooting Flow Charts

What does the screen
display?
Is the LX-IVM
front panel
Alarm Light on?
Is the LX-IVM
front panel
Alarm Light
still on?

Getting Started

YES NO
Turn the dial to AUTO and press the Alarm button
No Water Days No Run Times No Start Times No PGM will... More Exit
Shorted Paths
Duplicate Address
Flow Alarm
Device Not Responding
Go to
page
13
Call the ESP-LX SeriesHOTLINE at
+1-866-544­1406
10 ESP-LXIVM Controller Troubleshooting Guide
Go to
page
14
Go to
page
19
YES NO
Go to
page
20
Go to
page
22
Go to
page
23
END - Job Well Done!
Table of
Contents

2-Wire Mapping

Next
Next
Next
Start
2-Wire Mapping “maps” or records information on the wire-path of any connected IVM devices. A total of 4 wire paths are available in a LX-IVM Controller.
NOTE: While this information is helpful for diagnostics, not doing
2-wire mapping WILL NOT affect irrigation functions. But if 2-wire mapping is NOT done, it will raise an alarm at the controller.
To initiate 2-wire mapping, follow the steps below:
Turn the Dial to 2-Wire Settings
1. At the Advanced Station Settings screen, press the Down Arrow key to select 2-Wire Mapping, then press Next.
2. At the 2-Wire Device Mapping screen, press the + and – keys to set the desired hour (from 0 to 23), then press the Right Arrow key.
Advanced Station Settings
Cycle & Soak Inter-Station Delay SimulStations Station Sequencing
2-Wire Mapping
2-Wire Device Mapping
Start Device Mapping In
00 00:
HH:MM
3. Press the + and – keys to set the desired minute (from 1 to 59), then press Next.
4. At the confirmation screen, press Start to begin Device Mapping.
NOTE: All irrigation is disrupted during the mapping process.
2-Wire Device Mapping
Start Device Mapping In
01
05:
HH:MM
11 ESP-LXIVM Controller Troubleshooting Guide
Attention
Device Mapping will interrupt all irrigation
and could take several
minutes
Table of
Contents
5. A confirmation screen shows the process is set to run.
Done
Cancel
Ping
Ping
Mapping
Mapping will begin
In 1 Hrs and 5
Mins.
The following pictures show the List Not responding screen without and with 2-wire mapping done.
Without 2-wire mapping With 2-wire mapping
LIST NOT RESPONDING
AT 01/01/18 Type
STA STA STA008 --­STA010 ---
002 004#---
12 : 00 PM Path
---
LIST NOT RESPONDING
AT 01/01/18 Type
STA STA STA008 2 STA010 2
002 004#2
12 : 00 PM Path 2
12 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

No Water Days, No Run Times, …

Is the
LX-IVM system
working?
Turn the dial to Date/Time and ensure time and date are correct
Turn the dial to Start Times, Run Times and Water Days and follow programming directions in the User Manual
Test LX-IVM system using Manual Watering or Auto
Check the display
for Alarms, see
page 10
Troubleshooting
NO
YES
END - Job Well Done!
13 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

Shorted Paths

The controller has automatically entered Short Finding Mode to protect itself against a short on the 2-wire path
Turn the dial to Diagnostics and select Diagnostics from the menu, then press Next
Press the Down Arrow button to select Test Shorted Paths, then press Next
Press the Down Arrow button to select the Path (1-4) to test, then press Next
Trouble Shoot in the Field using a milliamp meter. A sharp increase in current should be observed right before the Short Condition in 2-wire Path.
NOTE: Shorted Path will
display “Fault”.
Press and hold the Yes button to energize the selected path Note: Irrigation will be disabled
If issue cannot be resolved using the Shorted Paths Test, refer to the Shorted Path (Manual Method) on the next page.
Next Page
14 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

Shorted Path (Manual Method)

Did the
controller exit Short
Finding Mode and are
both Indicator Lights
illuminated?
Open the front panel and check the two indicator lights on the IVM 2-Wire Interface Module.
The top indicator light should be green and the bottom indicator light should be dark. This indicates that the controller put the module in Short Finding Mode
If there are more than one 2-wire paths connected, disconnect the first 2-wire path
Disconnect the second/ third/fourth 2-wire path
NO YES
NOTE: In “looped”
systems, cut the loop in the middle to create two independent paths.
Reconnect the Maxi-Cable to verify the controller goes back into Short Finding Mode
15 ESP-LXIVM Controller Troubleshooting Guide
Next Page
Table of
Contents
Wires
damaged, or found
repairs of the
Maxi-Cable?
What does
the display
show?
Shorted Path (Manual Method) cont.
Repair damaged Maxi-Cable using Maxi Cable and DRB/Y connectors
YES
Go to an IVM device approx. 50% the length of the 2-wire path. Disconnect the IVM device 2-wire splice to disconnect the second half of the 2-wire path.
Reconnect the Maxi-Cable to verify the controller goes back into Short Finding Mode
Walk the length of the 2-wire path and look for signs of recent constructions (trenching, new fence, sign, tree, etc.)
NO
Connect all 2-wire paths at
NO
the controller and observe screen
Go back to
Troubleshooting,
page 10
NOTE: Instead of
physically disconnecting the 2-wire path, you could instead use a clamp meter. See
page 18.
16 ESP-LXIVM Controller Troubleshooting Guide
Next Page
Table of
Contents
Check the
controller display to
see if it has exited
Short Finding
Mode
Shorted Path (Manual Method) cont.
YES NO
The problem is downstream between this point and the end of the 2-wire path
Re-connect the 2-wire path and go to an IVM device approx. 50% between this point and the end of the 2-wire path. Disconnect the 2-wire splice to disconnect the second half of the 2-wire path.
NOTE: Once a small section 2-wire path is identified as having an
issue, use “Energize Path for Testing” and Milliamp Meter to track for a sharp increase in test current before the location of the short.
For video instructions on Automatic Short
Finding Mode, please visit:
www.rainbird.com/esplxivm
17 ESP-LXIVM Controller Troubleshooting Guide
The problem is upstream between this point and the controller
Re-connect the 2-wire path and go to an IVM device approx. 50% between this point and the controller. Disconnect the 2-wire splice to disconnect the second half of the 2-wire path.
Next Page
Table of
Contents
Shorted Path (Manual Method) cont.
Alternatively you can measure current draw in your system using Diagnostics/ Diagnostics/Controller Output:
NOTE: Before measuring the amperage, calculate the approximate
current that the 2-wire path is consuming.
System Amperage Calculation
Quantity of IVM-SOL X 0.67 mA
Quantity of IVM-OUT X 0.67 mA
+
Quantity of other IVM-SEN X 6 mA
+
Approximate total system amperage in mA
=
If there is a mismatch, follow a process similar to page 10 to disconnect 50% of devices and redo calculation above. Continue todisconnect 50% of devices until you identify section of 2-wire Path with issues.
NOTE: Self-healing: Note that IVM Controller tracks the health
of the 2-wire Path to see if shorts are resolved and then automatically resumes irrigation. You do not need go back to the Controller to reset or restart.
For video instructions on Locating a Short
on the Two-Wire Path, please visit:
www.rainbird.com/esplxivm
18 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

Duplicate Address

Is the
LX-IVM system
working?
The controller will Alarm if duplicate device addresses are entered for one or more of IVM-SOL, IVM-SEN and IVM-OUT.
Turn the dial to 2-Wire Settings
Press the Down Arrow button to select Station Setup, then press Next
Use the + and - buttons to cycle through all the stations. Verify that all 2-wire addresses are correct and there are no duplicates.
NOTE: Only the first two
duplicates will be shown, so you may need to repeat this process until all of the duplicates have been addressed.
Test LX-IVM system using Manual Run or Auto Run
Check the display
for Alarms,
see page 10
Trouble-
shooting
19 ESP-LXIVM Controller Troubleshooting Guide
NO YES
END - Job Well Done!
Table of
Contents

Flow Alarm

Go Back and select FloZone Flow Alarms
Alarms are issued when flow conditions exceed your High or Low Flow settings.
Turn the dial to Alarms/History
Press the Down Arrow button to select Flow Alarms, then press Next
Press the Down Arrow button to select Station Flow Alarms, then press Next
Troubleshoot and fix any station that shows an alarm
CONTINUED
FROM NEXT PAGE (21)
Troubleshoot and fix any FloZone that shows an alarm
Next Page
20 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Flow Alarms cont.
Alarm is
cleared on
the display
After fixing any station or FloZone issues, go Back and select Clear Flow Alarms
Run all zones manually
Check the Alarms screen to see if previous alarm cleared
NO YES
GO BACK
TO PREVIOUS PAGE (20)
21 ESP-LXIVM Controller Troubleshooting Guide
END - Job Well Done!
Table of
Contents

Ping Valve / Sensor (Ping Test)

Assumption: A valve or sensor may not be working
Turn the dial to Diagnostics
Press the Down Arrow button to select Ping Valve/Sensor then press Next
Press the + and - buttons to select the type of device to test (Station, Master Valve, Flow Sensor, Weather Sensor, etc.)
Press the <> button to select the number of the device to test, then press Ping
The controller will ping the selected device and report a voltage reading if the device responds
Interpreting Ping Results
If the device does not respond verify the address and check the wire splices. The voltage reading is a measurement of the charge of the device capacitors.
If the voltage is low, wait a minute then ping again.
If the voltage is still low (below 23 volts), disconnect the device from the 2-wire path and connect directly to an unused wire path at Controller and repeat Ping Test. If the voltage is fine, the issue is with 2-wire path / splicing. If the voltage is still bad, replace the device.
22 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

Field Wiring Diagnostics

The ESP-LXIVM Controller includes multiple diagnostic functions to help you determine the cause of a field wiring issue.

Tools and Equipment

• An accurate “as-built” showing wire path and 2-wire device locations, the number and type of the 2-wire devices on each wire path, and 2-wire addresses
• Filled out LX-IVM Controller Programming Guide with 2-wire addresses and station/MV/sensor assignments
• A Volt/Ohm Meter (multi-meter) capable of reading 0 to 50 volts AC/ DC and resistance from 0 to 1,000,000 Ohms
• A Clamp Meter for measuring AC current with a precision of 1.0 mA (milliamp)
• Wire tracing and fault finding equipment
• Spare system components and tools including: spare IVM-SOL, IVM­SEN device, WC20 Splice Kits and wire strippers

Total System Milliamp Draw

Before troubleshooting a field wiring issue, calculate the expected total system draw in milliamp (mA). This value can be compared to actual readings during troubleshooting.
• Each IVM-SOL, IVM-OUT draws 0.67mA
• IVM-SEN draws 6 mA
• Add up the total devices of each type for each wire path and calculate the wire path mA draw
• Add the mA for each wire path together for the total system mA draw

Field Wiring Issues

Field wiring issues are typically caused by a broken wire, a short circuit or a ground fault in the 2-wire path. Refer to the section that best describes the observed symptoms to troubleshoot.
• Broken Wire (Open Circuit)
• Short Circuit
• Ground Fault
Next Page
23 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
NOTE: A majority of field wiring issues are caused by poor wire
splices. Use only WC20 Splice Kits. All splices should be made in splice boxes.
NOTE: If the 2-wire path is Looped, disconnect the loop half way
out before troubleshooting.

Broken Wire (Open Circuit) List Not Responding

If there is a broken wire causing an open circuit in the 2-wire path, you will notice one or more stations are not running even though they are programmed to operate. If the system is using flow sensing, you will receive a low (zero) flow alarm for each disconnected 2-wire station.
Controller Diagnostics
1. Turn the dial to Test All Stations / Check System. Select 2-Wire Diagnostics.
2. Select the List Not Responding. The results will indicate that one or more devices have an open circuit and you will be prompted to Check Wiring. Go to the location of the 2-wire devices that are not responding and check all wire splices.
2-Wire Path Diagnostics
1. Note the “List Not Responding” displays and corresponding wire paths. If you notice that all the 2-wire devices that are not responding are in a single leg of the 2-wire path, the open circuit exists between the last working 2-wire device and the first non-working 2-wire device. Check the splices at that location first. Also look for signs of recent construction/digging between the working and non-working 2-wire devices.
NOTE: If 2-Wire mapping is not done, the wire path column will
not include any information.
2. Turn the controller dial to 2-Wire Diagnostics; Select Short Finding; Turn Short Finding Mode On. Use a Clamp Meter to measure the Amp Draw of the 2-wire path cable conductors at the last working device and the first non-working device. Note any discrepancies in the readings. You must know the number and type of each device downstream to know what the mA reading up should be reading (see the Total System Milliamp Draw section for more information).
24 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

Short Circuit

If there is a short circuit (can be caused by crossed red and black wires) in the 2-wire path, the controller Alarm light will be illuminated and the alarm will inform you the controller has switched to Short Finding Mode. You must fix the short circuit before the controller will switch back to normal irrigation mode.
2-Wire Path Diagnostics
1. Disconnect each 2-wire path cable one at a time from the controller IVM 2-Wire Interface Module until the controller exits Short Finding Mode. Reconnect that 2-wire path cable, and if the Short Finding Mode returns you know the short is on that leg of the 2-Wire path.
2. Refer to the as-built to see the location of the 2-wire path. Walk the route of the 2-wire path cable and check for signs of recent construction/digging.
3. Find a device location about half-way down the 2-wire path cable. Disconnect the splices. See if the controller is still in Short Finding Mode. If the Short Finding Mode has cleared, the problem is downstream of this location. If the controller is still in Short Finding Mode, the problem is between this location and the controller. Keep disconnecting segments of the 2-wire path until you isolate the problem.
4. Use a Clamp Meter to measure the Amp Draw of the 2-wire path cable conductors at the last working device and the first non-working device. Note any discrepancy in the readings. You must know the number and type of each device downstream to know what the mA reading up should be reading (see the Total System Milliamp Draw section for more information).
5. The problem may be caused by a device that was damaged by a lightning power surge. The controller will exit Short Finding Mode when the damaged device is disconnected from the 2-wire path.
25 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

Ground Fault

A ground (earth) fault can be caused when a 2-wire path conductor is leaking to ground, possibly due to a bad wire splice, or a nicked or damaged cable. This issue may come and go depending on the soil moisture level. When the soil is very wet the problem will be worse than when the soil is dry.
Controller Diagnostics
1. Turn dial to Diagnostics / Diagnostics / Control Output.
2. Select Controller. Note the Milliamp (mA) reading. The mA
reading will be higher than normal when current is leaking to ground. You must know the number and type of each device in the system to know what the mA reading should be reading (see the Total System Milliamp Draw section for more information).
3. Disconnect each 2-wire path cable one at a time from the controller IVM 2-Wire Interface Module. Recheck the Control Output to isolate which segment of the 2-wire path has the ground fault.
4. Find a device location about half-way down the 2-wire path cable. Disconnect the splices.
5. Check the Control Output to see if the ground fault has been isolated. If the Control Output is normal, the problem is downstream of this location. If the Control Output still shows the ground fault, the problem is between this location and the controller. Keep disconnecting segments of the 2-wire path until you isolate the problem.
2-Wire Path Diagnostics
1. Turn the controller dial to Diagnostics / Diagnostics / Test Shorted Path.
2. Use a Clamp Meter to measure the Amp Draw of the 2-wire path cable conductors at various splice locations. Note any discrepancy in the readings. You must know the number and type of each device downstream to know what the mA reading up should be reading (see the Total System Milliamp Draw section for more information).
26 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

Relay Wiring

For valves without compatible latching solenoids.
IVM-SOL device can be used to connect any Rain Bird Commercial Valve to the LX-IVM Controller. For Non-Rain Bird Valve, use IVM-OUT device in conjunction with a compatible DC latching solenoid to connect to a LX-IVM controller. In the event, a compatible DC latching solenoid is not available, you can use the Rain Bird Pump Start Relay with following modifications to power the AC Solenoid.
1. Connect 110V relay to the + or - 24VAC terminals at the controller’s IVM 2-wire Interface Module.
NOTE: Do not connect 2-wire path to the 110V relay terminals.
2. Unplug PSR relay coil wires and output to AC Solenoid.
NOTE: Feed the solenoid wires through bottom of the PSR
enclosure.
27 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
3. Connect the red and white IVM-OUT wire to the red wire of the DC Latching Relay. Connect the black and white IVM-OUT wire to the black wire of the DC Latching Relay.
4. Connect the red IVM-OUT wire to the red wire on the 2-Wire path. Then connect the black IVM-OUT wire to the black wire on the 2-Wire path.
Input Power
from 24VAC
Out Terminal
at Controller
IVM-OUT
AC Solenoid
Model Nos.
PSR110-IVM
and PSR220-IVM
Allow 3 ft. (1 m)
Extra Cable
Length
28 ESP-LXIVM Controller Troubleshooting Guide
AC Solenoid
Table of
Contents

IVM Power Filter Connection

Electrical Noise in the input power can cause undesirable behavior of the LXIVM Controllers. Sources of Electrical Noise include VFD Pump and other Electrical Equipment.
Rain Bird recommends the GSP-IVM Filter to filter the noise from the input power and ensure normal operation of the Controller. Symptoms can include inconsistent operation of the stations (stations not running as programmed) and inability read flow from a compatible flow sensor.
Rain Bird recommends the following modification to the controller to “filter out” the noise and ensuring normal operations of the Controller.
Choke: Schaffner P/N: RD5122-6-9M6
Terminal Block
on LX-IVM
ORANGE
YELLOW
ORANGE
YELLOW
GREEN or GREEN YEL. (not connected)
(24VAC IN)
BLUE
BROWN
GROUND
LX-IVM Transformer
(26.5VAC Out)
NOTE: IVM Filter Kit can be sourced from Rain Bird GSP via the
online services store (link below).
https://servicesstore.rainbird.com/ivm-filter.html
29 ESP-LXIVM Controller Troubleshooting Guide
Capacitor, Kemet P/N: C274ACF5100SA0J
Table of
Contents

Controller Diagnostics

Use this table to troubleshoot issues using the built-in diagnostic features of the ESP-LXIVM controller.
Category Issue Potential Cause Solution
Controller Alarms
Red alarm light on the controller front panel is illuminated.
Controller alarm; No 2-Wire Module.
Controller alarm; 2-Wire path Off.
Controller alarm; Duplicate Device Address.
Controller alarm; Short Finding Mode.
Controller alarm; No Device Addresses.
The controller is reporting an alarm condition.
The IVM 2-Wire Interface Module is not properly attached to the controller module slots.
Someone has manually turned the 2-wire path Off.
Duplicate Device addresses have been entered.
2-wire path is shorted and the controller has automatically switched to the Short Finding Mode. The lower left status light on the controller is dark.
Device addresses have not been entered for any stations.
Turn dial to Auto, press the Alarm button, review the alarm conditions, and address the issue(s).
Check the upper status light on the IVM 2-Wire Interface Module. It should be solid green if it is properly connected to the controller. Remove and reinstall the module making sure it is fully seated in the module slots.
Turn dial to Off, press the 2-Wire Path button, and turn the 2-wire path On.
Note the duplicate Device Addresses posted in the alarm screen, verify and enter the correct Device addresses.
Disconnect the 2-wire cables from the IVM 2-Wire Interface Module one at a time until the alarm condition clears. The lower left status light on the controller will alternate between red and green when the wire path with the short is removed.
Trace the path of this 2-wire cable and look for source of issue (disturbed soil, new tree or fence post, etc).
Disconnect the 2-wire cable halfway between the controller and end of cable and check to see if the alarm clears to help identify short location on the cable.
Use a volt/ohm and clamp meter to identify which devices are receiving power.
Fix the short and check that the alarm is cleared.
Turn dial to 2-Wire Settings / Station Setup. Enter the address (see label on each Device) for each station. Addresses are also required for Master Valves, Weather Sensors and Flow Sensor.
30 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Category Issue Potential Cause Solution
Controller Alarms
Controller alarm; Zero Learned Flow.
Controller alarm; Flow Alarm.
The Learn Flow Utility has recorded a zero (0) flow rate for one or more station.
FloWatch (flow sensing utility) has detected a high or low flow condition.
Turn dial to Flow Sensor / Set Flow Rates / View Flow Rates / View Station Rates. Check for stations that have a 0 flow rate and are labeled Learned.
• If all stations have learned a 0 flow check flow sensor/ input connections, Flow Sensor config­uration, FloZone assignments, etc.
• If only one or a few stations have learned a 0 flow rate check the valve operation (flow control stem position, solenoid, wiring, etc.).
• If just small flow rate valves/stations (like drip zones) have learned a 0 flow rate the flow sensor may be too large for the lower flow rates. Check the product technical specs for the minimum flow rate of the flow sensor.
Turn dial to Alarms / History / Flow Alarms, and review the posted Station and/or FloZone (mainline) flow alarms. Note the station(s) or FloZone(s) that were identified. If you configured FloWatch to Diagnose & Eliminate or Alarm & Shut Down, the problem station(s) or FloZone(s) will be quarantined. Clear the Flow Alarms and test the system.
• Station flow alarms – Manually turn on the station. Turn dial to Flow Sensor / View Current Flow. The current and expected flow rates will be listed. Check the valve & sprinklers to identify the issue and correct it. If sprinklers or nozzles have been replaced, relearn the station flow rate.
• FloZone alarms - Manually start a program. Turn dial to Flow Sensor, View Current Flow. The current and expected flow rates will be listed. Check the water source(s) and mainline to identify the issues and correct it.
• If FloZone high flow alarms are being triggered by manual watering (QCV, manually bleeding valves, etc.) consider using the MV Water Window located under the Manual Watering dial position. Configure window open and close times, days of the week, MV(s) you want open, and the expected additional flow rate to allow for the manual watering.
31 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Category Issue Potential Cause Solution
Controller Alarms
2-Wire Path Issues
Controller alarm; Invalid Module Config.
Controller alarm; No PGM will Auto Run.
Controller Alarm; No Power – Irrigation Functions are Disabled.
Communication with 2-wire devices is intermittent.
Controller loses connection to 2-wire devices after a heavy irrigation or rainfall event.
A non-compatible module has been inserted into one of the controller module slots.
Incomplete programming.
No primary power to the controller transformer
Front panel ribbon cable is disconnected
2-wire cable or splices are leaking to ground or between conductors.
Communication signal and power leaks to ground.
Remove any recently added modules, one at a time, until the alarm condition clears.
• ESP-LXME/-LXMEF Controller 4-, 8-, & 12-Station Modules, FSM Flow Smart Modules, M50 and SM75 Modules are not compatible.
Turn dial to Diagnostics / Confirm Programs / Program Summary. Missing programming parameters are identified by an N. For programs to automatically run you need to program Start Days, Start Times, and Station Run Times.
Check the power input to the controller transformer. The display is being powered by the 9v backup battery.
Check both ends of the ribbon cable to make sure it is firmly connected to the backplane and front panel.
Turn dial to Diagnostics / Control Output. The controller voltage output and 2-wire path milliamp draw will be displayed.
• If there are no issues you will see Current Limit OK, Current Overload OK.
• If the 2-wire cable leaks are drawing a high amount of current you will see Current Limit Not OK, Current Overload OK. Use the troubleshooting tips above to find and fix the 2-wire cable/splice issues.
• If the 2-wire cable leaks are drawing a high amount of current you will see Current Limit Not OK, Current Overload Not OK. The controller will have automatically switched to Fault Finding Mode. Use the troubleshooting tips above to find and fix the 2-wire cable/splice issues.
• Single-jacketed cable and/or incorrect wires splices were used. When incorrect cable/splices become submerged it can create leakage to ground. Double- jacketed 14-2UF Maxi 2-Wire Cable and WC20 Splice Kits are required.
32 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Category Issue Potential
IVM-SEN/ Sensor
Programs Programs
Station Sequencing
The controller is not getting data from a flow or weather sensor connected to a IVM-SEN/ Sensor on the 2-wire path.
are running at random times.
Stations are not running in station number sequence
Cause
Sensor wiring polarity is reversed.
Flow sensor output pulse rate is not compatible with the LX-IVM Controller.
Weather sensor type is not compatible.
Multiple start times have been programmed unintentionally.
Water Windows have been configured so programs are paused and resume later.
Station Sequencing set to Sequence by Station Priority
Solution
Many sensor including flow sensors require wires to be connected with correct polarity (+ / -). If the sensor has colored or labeled wires, connect as follows:
• Sensor red (+) wire to the IVM-SEN Sensor red wire.
• Sensor black (-) wire to the IVM-SEN Sensor black wire.
The LX
-IVM Controller requires a minimum input of 2 pulses per 10 seconds for the smallest station flow rate. Pulse rates of less than 2 pulses per 10 seconds will not be registered. compatible flow sensor.
The LX-IVM Controller is not compatible with 4-20 mA or 0-5V weather sensors (discrete switched sensors only).
Turn dial to Diagnostics / Confirm Programs / Review Program. Review each program using the Program Button to select the program. Check for multiple start times on an individual program. In some cases users’ mix-up start times and stations and can inadvertently program the system to start multiple times per day.
Turn dial to Delay Watering / Water Window. Use the Programs Button to select a program 1 - 40. Water Windows control the hours of the day a program is allowed to operate. If a program starts outside a Water Window it is paused until the window opens. If the program is still running when the Water Window closes the program is paused and will automatically start the next time the window opens. Adjust the Water Window open and close times to allow the program to complete.
The LX-IVM offers 2 station sequencing modes:
• Sequence by Station Numbers (default) – Sta-
tion selection criteria: a) Non-Irrigation Priority; b) Station number low to high; c) Program assignment 1 - 40.
• Sequence by Station Priority (automatically
used if FloManager is On) – Station selection criteria: a) Station Priority Non-Irrigation, High, Medium, Low; b) Station Run Time longest to shortest; c) Station number low to high; d) Program Assignment 1 - 40.
To change Station Sequencing mode turn dial to 2-Wire Settings / Advanced / Station Sequencing. Use the +/- softkeys to change the selection.
Change to a
33 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Category Issue Potential Cause S olution
Station Valves
Station Valves
Master Valves
A station valve is not operating.
A station valve is not operating.
The Master Valve will not open when stations are operating.
Valve is manually closed or solenoid is damaged.
Station does not have run time for a program with start days and a start time.
IVM-SOL or valve wires are not spliced correctly.
Incorrect address. Check the address of the station (label on the IVM
Incorrect Valve Type
2-wire path from the controller is not connected to this area.
MV is assigned to a different FloZone than the stations.
MV is Normally Open but has been configured as a Normally Closed MV.
Station not configured to open Master Valve.
MV Address is incorrect.
Turn dial to Manual Watering / Start Station. Select the station making sure it has a run time and press run. Check to see if the valve is operating and if it isn’t, address the valve issue.
Turn dial to Run Time. Note which programs the station has run times programmed. Use Program Summary to make sure that program has start days and start times.
Turn dial to Diagnostics / Diagnostics / Ping List not Responding. If the ping test fails check the device and valve wire splices and repeat the ping test.
device that is connected to the valve) and verify the address is entered correctly. Turn dial to 2-wire Setting / Station Setup to access Station Address.
Turn Dial to 2-wire Setting / Station Setup / Valve Types. Valve types configure the decoder inrush amps and duration for opening a valve solenoid. The LX-IVM Valve Types are preconfigured for Rain Bird commercial valve models. Information for configuring Valve Types to work with other valves can be found in the controller manual. Note: Rain Bird residential valves (DV, JTV, HV) are not compatible with the LX-IVM system or IVM-SOL.
Ping other valves on the same 2-wire path leg. If these pings are also unsuccessful, check for an open wire connections on the 2-wire path.
Turn dial to 2-Wire Settings / Master Valves. Press Next to advance to FloZone (FZ) Setup screen. MV needs to be assigned to the same FloZone as the stations that receive water from this water source.
If the MV valve is Normally Open (powered to close) it needs to be configured as Normally Open. Turn dial to 2Wire Settings / MV Setup. Change MV from Normally Closed (default) to Normally Open.
Go to 2-Wire Settings / Station Setup to make sure the station is configured as requiring a Master Valve.
Check the address of the MV (label on the IVM device that is connected to the MV) and verify the address is entered correctly. Turn dial to Setup Wizards / Master Valves to access MV Address.
Diagnostics / Confirm Program
/ Station
34 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Category Issue Potential Cause Solution
Master Valves
IVM 2-Wire Interface Module
Pump Start Relays
Controller LCD Display
The Master Valve will not open when stations are operating.
No output from the module.
The controller cannot close the pump start relay that is connected to a IVM-OUT.
The controller display is either too light or too dark.
Controller display is blank.
2-wire device or valve wires are not spliced correctly.
IVM-Device is not functioning or damaged.
Fuses in the module have blown due to short or secondary power connected to the 2-wire path.
Module is in Automatic Short Finding Mode due to short or secondary power connected to the 2-wire path.
Amp draw of the pump start relay is more than the Device can provide.
The display contrast needs to be adjusted.
Controller LCD display is damaged.
Primary power to the controller has been lost or turned off.
Controller ribbon cable is not connected or damaged.
Turn dial to Diagnostics / Diagnostics /
MV and ping the MV address. If the ping
Ping test fails
check the decoder and valve wire splices and repeat the ping test.
Turn dial to Valve or Sensor, then ping the MV address. If the ping test fails swap the device, enter the new address and repeat the ping test.
Find the source of the short or power connected to the 2-wire path and address the problem. A replacement 2-wire Module is available for purchase.
Find the source of the short or power connected to the 2-wire path and address the problem.
Use a Rain Bird PSR-Series Pump Start Relay that incorporates an ice-cube relay, double relay system. You can also add an ice -cube relay to the existing pump start relay. Contact Rain Bird Technical Services or Global Support Plan for relay model and wiring diagram.
Turn dial to Off, press Contrast +/- buttons to adjust display contrast.
Plug in a 9V battery into the battery slot on the back of the controller front panel. If information is now visible on the display it is not damaged and working correctly. See other potential causes. If no information is displayed, remove the 2-wire module. If the alarm light on the front panel turns on after 1 minute but no information is in the display, the LCD is damaged and the front panel should be replaced. A replacement panel is available for purchase.
This can be verified by checking the status lights on the 2-wire module. If both status lights on the module are dark the primary power is likely off. Find primary power source to the controller and turn it on. If the power breaker is tripped or fuse is blown, find source of problem, fix the issue, and turn the power back on.
Check to make sure the ribbon cable is securely connected to both the controller backplane and the front panel. If the cable has broken wires or connectors, replace it.
Diagnostics / Diagnostics /
Select
Ping
35 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Category Issue Potential
Simul Stations (Simul­taneous Station Operation)
Weather Sensors
Controller Knock­outs
Too many or too few stations are operating simultaneously when program(s) operate.
Weather sensor is not preventing controller manual operation.
Wireless weather sensor is not providing input to the controller.
I am having trouble removing the knock-outs on the ESP-LX Series Controller plastic cabinet.
Cause
LX-IVM (Controller) SimulStations are configured incorrectly.
PGM (Program) SimulStations are configured incorrectly.
This is by design.
Sensor receiver is not wired to the controller module correctly.
Unlike knock­outs on a metal enclosure, these plastic knock-outs are designed to be removed by applying force to the center at the dimple.
Solution
Turn dial to 2-wire Setting / Advanced / SimulStations. Select LX-IVM SimulStations and adjust the maximum number of simultaneous irrigation stations you want to allow to operate across all programs at any time. Non- Irrigation SimulStations control stations with Non-Irr Priority.
Turn dial to 2-wire Setting / Advanced SimulStations. Select PGM SimulStations and adjust the maximum number of simultaneous irrigation stations you want to allow to operate simultaneously within the currently selected program. Move the Program Button to select the other programs 1 - 40.
Manual station, program or test program operation (from the front panel or a remote) is allowed regardless of the weather sensor state. To see the current state of a weather sensor, turn the dial to Weather Sensors. The status of each sensor is displayed.
The IVM 2-Wire Interface Module includes 4 terminals for wireless weather sensor connections. Wiring connections should be made as follows:
• Sensor receiver power wires to + and – terminals.
• Sensor receiver sensor wires to Sen and C terminals.
Prior to installing the cabinet, place on a flat surface with the knock-out facing up. Locate the dimple in the center of the knock-out you wish to remove. Place the tip of a large Phillips screwdriver in the dimple. Use a rubber or wooden mallet to firmly strike the top of the screwdriver. The knock-out should pop out in a single piece. If it breaks, use pliers to remove the pieces. Do not use a flat-bladed screwdriver around the outside of the knock-out as this could crack the case.
36 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

IVM Interface Module

This section explains the LED Status indicators on the IVM 2-Wire Interface Module.

LED Indicators

MODULE STATUS
2WIRE PATH
STATUS
1
2 3 4
INDIVIDUAL PATHS
37 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents

LED Status

Module Status

Module State Description LED Light
POWER OFF Power off or module is held in reset. Dark
POWER UP During initial power up or after reset Briefly lights GREEN
ENUMERATION or ERROR Waiting for enumeration. Flashing RED
CONFIGURATION After enumeration, while receiving
NORMAL After configuration download is
SHORT ADDRESS CONFIGURATION
device addresses and configuration from the front panel
complete (from front panel and setting all IVM-SEN to either flow or weather).
This is the Normal up and running state.
During the Normal state, there are devices in the field that have not yet been programmed with short addresses.
All other normal communication to field devices still function while in this state.

2-Wire Path Status

Module State Description LED Light
POWER OFF Power off or module is held in reset. Dark
2-wire ON Normal state with 2-Wire path powered
2-wire OFF 2-Wire path powered down. Dark
on.

Individual Path Status

to indicate power applied
Flashing ORANGE
Solid GREEN
Flashing GREEN
Blinking GREEN
Module State Description LED Light
POWER OFF Power off or module is held in reset. Dark
Individual path enabled Path connected (2-Wire path may be
Individual path disabled Path disconnected (2-wire path may be
on or off).
on or off).
Solid GREEN
Solid RED
38 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Rain Bird Corporation
6991 E. Southpoint Road
Tucson, AZ 85756
Phone: (520) 741-6100
Questions?
Call the Rain Bird Professional Support Line at
+1-866-544-1406
or else visit our web site at
www.rainbird.com/esplxseries
Rain Bird Rewards:
www.rainbird.com/rewards
Phone - 1-888-370-1814
Global Service Plan:
www.rainbird.com/gsp
Phone: 866-GSP-XPRT (477-9778)
Registered trademark of Rain Bird Corporation
2020 Rain Bird Corporation 23DE20
Loading...