Quantech QTC4 STYLE A Installation Operation & Maintenance

Page 1
AIR-COOLED SCREW
LIQUID CHILLERS
INSTALLATION, OPERATION, MAINTENANCE
MODEL QTC4 STYLE A
AIR-COOLED SCREW LIQUID CHILLERS WITH
VARIABLE SPEED DRIVE

Supersedes: QTC4-NM1 (318) Form QTC4-NM1 (418)

035-24497-000
150 - 500 TONS
525 - 1750 KW
60 HZ
HFC-134A
Issue Date:
April 2, 2018
LD18970
Page 2
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
This equipment is a relatively complicated apparatus. During rigging, installation, operation, maintenance, or service, individuals may be exposed to certain com­ponents or conditions including, but not limited to: heavy objects, refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of rigging, instal­lation, and operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in
which it is situated, as well as severe personal injury or death to themselves and people at the site.
This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This in­dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken.
Identies a hazard which could lead to
damage to the machine, damage to other equipment and/or environmental pollu­tion if proper care is not taken or instruc­tions and are not followed.
Indicates a potentially hazardous situa­tion which will result in possible injuries or damage to equipment if proper care is not taken.
External wiring, unless specied as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specications and must be performed only by a qualied
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2
Highlights additional information useful to the technician in completing the work being performed properly.
QUANTECH
Page 3
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
CHANGEABILITY OF THIS DOCUMENT
In complying with Johnson Controls’ policy for con­tinuous product improvement, the information con­tained in this document is subject to change without notice. Johnson Controls makes no commitment to update or provide current information automatically to the manual or product owner. Updated manuals, if applicable, can be obtained by contacting the nearest Johnson Controls Service office or accessing the John­son Controls QuickLIT website at http://cgproducts.
johnsoncontrols.com.
It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these
The Control/VSD Cabinet contains lethal high AC and DC voltages. Before per­forming service inside the cabinet, remove the AC supply feeding the chiller and verify using a non-contact voltage sensor.
The DC voltage on the VSD DC Bus will take 5 minutes to bleed off, after AC power is removed. Always check the DC Bus Voltage with a Voltmeter to assure the capacitor charge has bled off before working on the system.
NEVER short out the DC Bus to dis-
charge the lter capacitors.
NEVER place loose tools, debris, or any objects inside the Control Panel/VSD Cabinet.
documents to the equipment. If there is any question regarding the applicability of these documents, rig­ging, lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chiller.
CHANGE BARS
Revisions made to this document are indicated with a line along the left or right hand column in the area the revision was made. These revisions are to technical in­formation and any other changes in spelling, grammar or formatting are not included.
NEVER allow the Control Panel VSD Cabinet doors to remain open if there is a potential for rain to enter the panel.
Keep doors closed and assure all latches 
are engaged on each door unless the unit is being serviced.
ALWAYS lockout the disconnect supply­ing AC to the chiller.
The 1L Line Inductor will reach operating temperatures of over 150°C (300°F.). DO NOT open panel doors during operation. Assure the inductor is cool whenever working near the inductor with power OFF.
ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
Equipment Pre-Startup and Startup Checklist QTC4-CL2
QTC4 Parts Guide QTC4-RP1
Equipment Standard Limited Warranty QTC-NM2
QUANTECH
3
Page 4
LD23520
UNIT NOMENCLATURE
Base Product Type
Q = Quantech T = Variable Speed Screw C4 = Air Cooled Design Series
Model Number
Configuration
S = Condenser Code X = Evaporator Code X = Compressor Code X = Condenser Fan & Sound Kit Code
-
QTC4 SXXX 46 AA
210
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
Level / Refrigerant
A = Refrigerant R134a B = Refrigerant R513A
Voltage
17 = 200 / 3 / 60 28 = 230 / 3 / 60 40 = 380 / 3 / 60 42 = 400 / 3 / 60 46 = 460 / 3 / 60 50 = 380-415 / 3 / 50 58 = 575 / 3 / 60
4
QUANTECH
Page 5
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE OF CONTENTS
SECTION 1 - GENERAL CHILLER INFORMATION AND SAFETY ...................................................................... 11
Introduction ..................................................................................................................................................... 11
Warranty ......................................................................................................................................................... 11
Quality Assurance and Safety ........................................................................................................................ 11
Fluorinated Greenhouse Gases .....................................................................................................................12
Responsibility for Safety ................................................................................................................................. 12
About This Manual..........................................................................................................................................12
Misuse of Equipment ...................................................................................................................................... 12
Suitability for Application ....................................................................................................................... 12
Structural Support .................................................................................................................................12
Mechanical Strength .............................................................................................................................12
General Access .....................................................................................................................................12
Pressure Systems .................................................................................................................................12
Electrical ................................................................................................................................................ 12
Rotating Parts ........................................................................................................................................13
Sharp Edges ..........................................................................................................................................13
Refrigerants and Oils .............................................................................................................................13
High Temperature and Pressure Cleaning ............................................................................................13
Emergency Shutdown ...........................................................................................................................14
Safety Labels .........................................................................................................................................14
SECTION 2 - PRODUCT DESCRIPTION ............................................................................................................... 15
General System Description ........................................................................................................................... 15
Semi-Hermetic Quantech Twin-Screw Compressors .....................................................................................17
Evaporator ...................................................................................................................................................... 17
Condenser ...................................................................................................................................................... 17
Refrigerant Circuit ..........................................................................................................................................17
Electrical ......................................................................................................................................................... 17
Building Automation System Capabilities ....................................................................................................... 18
Microcomputer Control Center .......................................................................................................................18
Display Data .......................................................................................................................................... 18
Programmable Setpoints ...................................................................................................................... 18
Accessories and Options ................................................................................................................................ 19
Sound Attenuation ................................................................................................................................. 19
Fan Options .................................................................................................................................................... 19
Condenser Coils ............................................................................................................................................. 19
Condenser Coil Protection ....................................................................................................................19
Protective Chiller Panels .......................................................................................................................19
Evaporator Options ...............................................................................................................................20
Controls Options ....................................................................................................................................20
General Options ....................................................................................................................................20
Vibration Isolation .................................................................................................................................. 21
SECTION 3 - RIGGING, HANDLING AND STORAGE ..........................................................................................23
Lifting Weights ................................................................................................................................................ 23
Delivery and Storage ...................................................................................................................................... 23
Inspection ....................................................................................................................................................... 23
Moving the Chiller ........................................................................................................................................... 24
Unit Removal From Shipping Container ......................................................................................................... 24
Lifting Using Shackles .................................................................................................................................... 24
Lifting Using Lugs ........................................................................................................................................... 24
QUANTECH
5
Page 6
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
TABLE OF CONTENTS (CONT'D)
SECTION 4 - INSTALLATION ................................................................................................................................ 35
Location Requirements ..................................................................................................................................35
Outdoor Installations ......................................................................................................................................35
Location Clearances ....................................................................................................................................... 35
Recommended Minimum Clearances ...................................................................................................36
Vibration Isolators ........................................................................................................................................... 37
Installation .............................................................................................................................................37
Shipping Braces .............................................................................................................................................37
Chilled Liquid Piping ....................................................................................................................................... 37
General Requirements ..........................................................................................................................37
Water Treatment ............................................................................................................................................. 38
Pipework Arrangement ................................................................................................................................... 38
Minimum Water Volume ................................................................................................................................. 38
Leaving Water Temperature Out of Range ..................................................................................................... 38
Flow Rate Out of Range ................................................................................................................................. 39
Variable Primary Flow ....................................................................................................................................40
Connection Types and Sizes .......................................................................................................................... 40
Evaporator Connections ................................................................................................................................. 40
Option Flanges ...................................................................................................................................... 41
Refrigerant Relief Valve Piping ....................................................................................................................... 41
Electrical Connection ...................................................................................................................................... 41
Power Wiring .................................................................................................................................................. 41
Power Supply Wiring ...................................................................................................................................... 42
115VAC Control Supply Transformer ..............................................................................................................42
Control Wiring ................................................................................................................................................. 42
Volts Free Contacts ........................................................................................................................................ 42
Chilled Liquid Pump Starter ...................................................................................................................42
Run Contact ..........................................................................................................................................42
Alarm Contacts ...................................................................................................................................... 42
System Inputs ................................................................................................................................................. 42
Flow Switch ...........................................................................................................................................42
Remote Run / Stop ................................................................................................................................ 43
Remote Print .........................................................................................................................................43
Optional Remote Setpoint Offset – Temperature...................................................................................43
Optional Remote Setpoint Offset – Current ........................................................................................... 43
Optional Remote Setpoint Offset – Sound Limiting ............................................................................... 43
Power Supply Wiring ...................................................................................................................................... 44
Single Point Wiring ................................................................................................................................ 44
Voltage Utilization Range ......................................................................................................................44
Dual Point Wiring ...................................................................................................................................45
Customer Control Wiring ................................................................................................................................ 46
SECTION 5 - TECHNICAL DATA ...........................................................................................................................57
Elastomeric Isolator Installation ...................................................................................................................... 84
Elastomeric Isolator Specifications ................................................................................................................. 85
One Inch Deflection Isolator Installation ......................................................................................................... 86
One Inch Deflection Spring Isolator Specifications ........................................................................................87
Two Inch Deflection Isolator Installation And Adjustment ............................................................................... 88
Two Inch Deflection, Restrained Spring Isolator Specifications .....................................................................89
6
QUANTECH
Page 7
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE OF CONTENTS (CONT'D)
SECTION 6 - COMMISSIONING ............................................................................................................................91
Preparation ..................................................................................................................................................... 91
Inspection ............................................................................................................................................. 91
Refrigerant Charge ................................................................................................................................ 91
Correct System Refrigerant Charge ...................................................................................................... 91
Service and Oil Line Valves ................................................................................................................... 91
Compressor Oil .....................................................................................................................................91
Fans .....................................................................................................................................................92
Isolation / Protection .............................................................................................................................. 92
Control Panel .........................................................................................................................................92
Power Connections ...............................................................................................................................92
Grounding ..............................................................................................................................................92
Water System ........................................................................................................................................92
Flow Switch ...........................................................................................................................................92
Temperature Sensor(s) .......................................................................................................................... 92
Programmed Options ............................................................................................................................92
Programmed Settings ...........................................................................................................................92
Date and Time ....................................................................................................................................... 92
Start/Stop Schedule ..............................................................................................................................93
Setpoint and Remote Offset .................................................................................................................. 93
First Time Start Up .........................................................................................................................................93
Interlocks ............................................................................................................................................... 93
Unit Switch ............................................................................................................................................93
Startup ................................................................................................................................................... 93
Oil Pressure ...........................................................................................................................................93
Loading ..................................................................................................................................................93
Condenser and Fan Rotation ................................................................................................................93
System Charge ......................................................................................................................................93
General Operation ......................................................................................................................................... 93
Operation in Sub-freezing Conditions ...................................................................................................94
Unit Maintenance and Shutdown in Sub-freezing Conditions ..............................................................94
SECTION 7 - OPERATION .....................................................................................................................................95
Operating Controls .........................................................................................................................................95
Unit Switch ............................................................................................................................................95
Keypad ..................................................................................................................................................95
Keypad Data Entry Mode ......................................................................................................................96
Display ...................................................................................................................................................96
Anti-recycle Timer ..................................................................................................................................96
Evaporator Pump Control ...................................................................................................................... 96
Evaporator Heater Control ....................................................................................................................96
Alarms ...................................................................................................................................................97
Chiller Run Contact ...............................................................................................................................97
Flow Switch Control ...............................................................................................................................97
Remote Run / Stop ................................................................................................................................ 97
Basic Operating Sequence ............................................................................................................................. 97
Start Sequence and Loading ................................................................................................................. 97
Unit Warning ...................................................................................................................................................97
Unit Warning Operation .........................................................................................................................97
Low Battery Warning .............................................................................................................................97
QUANTECH
7
Page 8
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
TABLE OF CONTENTS (CONT'D)
Microboard (331-03478-xxx) ..........................................................................................................................98
Power Supplies and LEDs .....................................................................................................................98
Power Supply Test Points ......................................................................................................................98
Conguration Jumpers .........................................................................................................................98
Communication Ports .......................................................................................................................... 100
Building Automation System (BAS) Communications ..................................................................................100
Using Communications Protocol .........................................................................................................100
E-Link or SC-EQ Interface ............................................................................................................................ 101
SC-EQ or E-Link BAS Communications Card .............................................................................................. 103
E-Link ..................................................................................................................................................107
VSD ..................................................................................................................................................... 107
Program Update ........................................................................................................................................... 107
Data Logging ................................................................................................................................................ 107
Invalid Number of Compressors Warning............................................................................................108
Invalid Serial Number Warning ............................................................................................................108
Unit Safeties ................................................................................................................................................. 109
Unit Safety Operation .......................................................................................................................... 109
High Ambient Temp Fault .................................................................................................................... 109
Low Ambient Temp Fault ..................................................................................................................... 109
Low Leaving Chilled Liquid Temp Fault ............................................................................................... 109
VSD Communications Failure Fault ....................................................................................................109
System Safeties (Faults) .............................................................................................................................. 110
System Safety (Fault) Operation ......................................................................................................... 110
High Discharge Pressure Cutout (Software) Fault .............................................................................. 110
High Discharge Pressure Cutout (HPCO) (Hardware) Fault .............................................................. 111
Low Suction Pressure Cutout (Software) Fault ................................................................................... 111
Low Motor Current Cutout Fault .......................................................................................................... 111
High Differential Oil Pressure Cutout Fault ......................................................................................... 111
Low Differential Oil Pressure Cutout Fault .......................................................................................... 112
High Discharge Temperature Cutout Fault .......................................................................................... 11 2
Low Discharge Superheat Cutout Fault .............................................................................................. 112
Discharge Pressure Load Limiting/Unloading ..................................................................................... 112
Suction Pressure Load Limiting/Unloading ......................................................................................... 113
Sensor Failure Cutout Fault ................................................................................................................ 113
High Motor Temperature Cutout Fault ................................................................................................. 114
System Control Voltage Cutout Fault .................................................................................................. 114
Eductor Clog Fault ............................................................................................................................... 114
SECTION 8 - MICROPANEL ................................................................................................................................ 115
Unit Data Key ............................................................................................................................................... 118
System Data Keys 1 Through 4....................................................................................................................120
VSD Data Key ..............................................................................................................................................123
Operating Hours / Start Counter Key ...........................................................................................................124
History Key ................................................................................................................................................... 125
Setpoints Key ...............................................................................................................................................132
Program Key ................................................................................................................................................134
Options Key .................................................................................................................................................. 137
Date/Time and Schedule Keys .....................................................................................................................140
Manual Override Key .................................................................................................................................... 143
Print Key ....................................................................................................................................................... 144
System Switches Key ................................................................................................................................... 147
8
QUANTECH
Page 9
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE OF CONTENTS (CONT'D)
SECTION 9 - MAINTENANCE .............................................................................................................................. 149
General Requirements .................................................................................................................................149
Weekly Maintenance ...........................................................................................................................149
Unit Status ........................................................................................................................................... 149
Refrigerant Leaks ................................................................................................................................ 149
Operating Conditions ...........................................................................................................................149
Compressor Oil Level .......................................................................................................................... 149
Refrigerant Charge .............................................................................................................................. 149
Adding Charge to a System ................................................................................................................149
Refrigerant Removal, Evacuation and Charging a QTC4 Chiller ................................................................150
Refrigerant Removal ...........................................................................................................................150
Evacuating a System ...........................................................................................................................150
Charging Refrigerant into a System ....................................................................................................151
Microchannel Coil Cleaning .......................................................................................................................... 151
Scheduled Maintenance ...................................................................................................................... 151
Maintenance Requirements for QTC4 Chillers ............................................................................................. 152
SECTION 10 - DECOMMISSIONING, DISMANTLING AND DISPOSAL ............................................................161
General ......................................................................................................................................................... 161
Temperature ................................................................................................................................................. 162
QUANTECH
9
Page 10
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
LIST OF FIGURES
FIGURE 1 - QTC4 Air-Cooled Screw Liquid Chiller with Variable Speed Drive ...................................................... 15
FIGURE 2 - Chiller Control System ......................................................................................................................... 16
FIGURE 3 - View of Control Center User Interface ................................................................................................. 18
FIGURE 4 - Lift Lug to remove unit from shipping container ................................................................................... 24
FIGURE 5 - Accessory Lifting lugs ..........................................................................................................................24
FIGURE 6 - Acceptable Minimum Clearances Around / Between Unit(S) ............................................................... 36
FIGURE 7 - Pipework Arrangement ........................................................................................................................ 38
FIGURE 8 - Leaving Water Temperature Out of Range Suggested Layout ............................................................ 39
FIGURE 9 - Suggested Layout For Applications With Flow Rates Less Than The Evaporator
Minimum Allowable Flow Rate .............................................................................................................39
FIGURE 10 - Suggested Layout For Applications With A Flow Rate Greater Than The Evaporator
Maximum Allowable Flow Rate ..........................................................................................................39
FIGURE 11 - Victaulic Groove ................................................................................................................................. 40
FIGURE 12 - Flange Attachment ............................................................................................................................. 41
FIGURE 13 - Single Point Power Wiring .................................................................................................................44
FIGURE 14 - Dual Point Power Wiring .................................................................................................................... 45
FIGURE 15 - Customer Control Connections .........................................................................................................46
FIGURE 16 - QTC4 Dimensions .............................................................................................................................76
FIGURE 17 - Keyboard and Display........................................................................................................................95
FIGURE 18 - New 331-03478-xxx Microboard ........................................................................................................ 99
FIGURE 19 - Control Board Connections for BAS Communications ....................................................................103
LIST OF TABLES
TABLE 1 - Unit Rigging ........................................................................................................................................... 26
TABLE 2 - Minimum Evaporator Tube Removal Clearance ....................................................................................36
TABLE 3 - Evaporator Connections Dimensions ....................................................................................................40
TABLE 4 - Electrical Lug Data ................................................................................................................................47
TABLE 5 - Physical Data - Microchannel Coil ......................................................................................................... 58
TABLE 6 - Physical Data - Round Tube Coil ..........................................................................................................62
TABLE 7 - Optional One-Pass Evaporator ..............................................................................................................64
TABLE 8 - Standard Two-Pass, Rear Inlet/Outlet Evaporator ................................................................................ 68
TABLE 9 - Optional Three-Pass Rear Inlet/Front Outlet Evaporator ......................................................................72
TABLE 10 - Isolator Selection and Mounting Locations .......................................................................................... 78
TABLE 11 - Values Required for BAS Communication ......................................................................................... 102
TABLE 12 - Real Time Error Numbers For BAS, SC-EQ or E-Link Communications Card ..................................102
TABLE 13 - Native Communications Data Map .................................................................................................... 104
TABLE 13 - Native Communications Data Map (CONT'D) ...................................................................................105
TABLE 14 - Operational and Fault / Inhibit Codes ................................................................................................ 106
TABLE 15 - Flash Card Update Error XXXXX ......................................................................................................107
TABLE 16 - Data Logging ....................................................................................................................................108
TABLE 17 - Low Differential Oil Pressure Cutout ................................................................................................. 112
TABLE 18 - Discharge Pressure Load Limiting/Unloading ...................................................................................11 3
TABLE 19 - Suction Pressure Load Limiting/Unloading ........................................................................................113
TABLE 20 - Start Inhibit Sensor Thresholds ......................................................................................................... 114
TABLE 21 - Sensor Min/Max Outputs ................................................................................................................... 122
TABLE 22 - Setpoint Limits ................................................................................................................................... 133
TABLE 23 - Programmable Operating Parameters ...............................................................................................136
TABLE 24 - Printout Types ....................................................................................................................................144
TABLE 25 - Troubleshooting Guide ......................................................................................................................153
TABLE 26 - Temperature Input Voltage Sensor (Measured Signal To Shield at the Sensor) ...............................156
TABLE 27 - Outside Air Temperature Sensor Input Voltage (Measured Signal To Shield at the Sensor) ............. 157
TABLE 28 - Pressure Transducer Output Voltage (Measured Signal To Return At The Transducer) ................... 158
TABLE 29 - Motor Temperature Sensor Resistance (Check At The Motor) ..........................................................159
TABLE 30 - SI Metric Conversion .........................................................................................................................162
10
QUANTECH
Page 11
FORM QTC4-NM1 ISSUE DATE: 4/2/2018

SECTION 1 - GENERAL CHILLER INFORMATION AND SAFETY

INTRODUCTION

Quantech QTC4 chillers are manufactured to the highest design and construction standards ensuring high performance, reliability and adaptability with all types of air conditioning installations.
The unit is intended for cooling water or glycol solu­tions and is not suitable for purposes other than those specified in this manual.
Rigging and lifting should only be done by a profes­sional rigger in accordance with a written rigging and lifting plan. The most appropriate rigging and lifting method will depend on job specific factors, such as the rigging equipment available and site needs. Therefore, a professional rigger must determine the rigging and lifting method to be used, and it is beyond the scope of this manual to specify rigging and lifting details.
The rigger should locate the center of gravity through trial lifts to account possible variations in unit configu­rations. Contact your nearest Quan­tech sales office for weight data. See SECTION 3 - RIGGING, HANDLING AND STORAGE for more details.
This manual contains all the information required for correct installation and commissioning of the unit, together with operating and maintenance instructions. The manual should be read thoroughly before attempt­ing to operate or service the unit.
All procedures detailed in the manual, including in­stallation, commissioning and maintenance tasks must only be performed by suitable, trained and qualified personnel.
The manufacturer will not be liable for any injury or damage caused by incorrect installation, commission­ing, operation or maintenance resulting from a failure to follow the procedures and instructions detailed in the manual.

WARRANTY

Quantech warrants all equipment and materials against defects in workmanship and materials for a period of eighteen months from date of shipment or 12 months from date of startup, whichever comes first, unless labor or extended warranty has been purchased as part of the contract.
1
The warranty is limited to parts only replacement and shipping of any faulty part, or sub-assembly, which has failed due to poor quality or manufacturing errors. All claims must be supported by evidence that the failure has occurred within the warranty period, and that the unit has been operated within the designed parameters specified.
All warranty claims must specify the unit model, serial number, order number and run hours/starts. Model and serial number information is printed on the unit identi­fication plate.
The unit warranty will be void if any modification to the unit is carried out without prior written approval from Quantech. For warranty purposes, the following conditions must be satisfied:
• The initial start of the unit must be carried out by trained personnel from an authorized Quantech Service Center. Refer to SECTION 6 - COMMIS- SIONING for more information.
• Only genuine Quantech approved spare parts, oils, coolants, and refrigerants must be used.
• All the scheduled maintenance operations detailed
in this manual must be performed at the specied times by suitably trained and qualied personnel.
See SECTION 9 - MAINTENANCE for more in­formation.
• Failure to satisfy any of these conditions will automatically void the warranty. Refer to Form QTC4-NM2 for complete details.

QUALITY ASSURANCE AND SAFETY

QTC4 chillers are designed within EN ISO 9001 and built within an EN ISO 9002 accredited manufacturing organization.
ETL/ASME marked units conform to the following standards:
• ANSI/ASHRAE 15 – Safety Code for Mechanical Refrigeration.
• ANSI/ASHRAE 34 – Number Designation and
Safety Classication of Refrigerants.
• ANSI/NFPA 70 – National Electrical Code (N.E.C.).
• ASME Boiler and Pressure Vessel Code, Section VIII, Division 1.
QUANTECH
11
Page 12
SECTION 1 - GENERAL CHILLER INFORMATION AND SAFETY
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

FLUORINATED GREENHOUSE GASES

• This equipment contains uorinated greenhouse gases covered by the Kyoto Protocol.
• The global warming potential of the refrigerant (HFC-134a) used in this unit is 1300.
• The refrigerant quantity is stated in Table 5 on Page 58 of this document.
• The uorinated greenhouse gases in this equip­ment may not be vented to the atmosphere.
• This equipment should only be serviced by quali-
ed technicians.

RESPONSIBILITY FOR SAFETY

Every care has been taken in the design and manufacturing of the unit to ensure compliance with the safety requirements listed above. However, the individual rigging, lifting, maintaining, operating or working on any machinery is primarily responsible for:
• Personal safety, safety of other personnel, and the machinery.
• Correct utilization of the machinery in accordance with the procedures detailed in the manual.

Structural Support

Structural support of the unit must be provided as in­dicated in these instructions. Failure to provide proper support may result in injury to the operator, or damage to the equipment and/or building.

Mechanical Strength

The unit is not designed to withstand loads or stress­es from adjacent equipment, pipework or structures. Additional components must not be mounted on the unit. Any such extraneous loads may cause structur­al failure and may result in injury to the operator, or damage to the equipment.

General Access

There are a number of areas and features, which may be a hazard and potentially cause injury when working on the unit unless suitable safety precautions are taken. It is important to ensure access to the unit is restricted to suitably qualified persons who are familiar with the potential hazards and precautions necessary for safe operation and maintenance of equipment containing high temperatures, pressures and voltages.

Pressure Systems

ABOUT THIS MANUAL

The contents of this manual include suggested best working practices and procedures. These are issued for guidance only, and they do not take precedence over the above stated individual responsibility and/or local safety regulations.
This manual and any other document supplied with the unit are the property of Quantech which reserves all rights. They may not be reproduced, in whole or in part, without prior written authorization from an authorized Quantech Sales Representative.

MISUSE OF EQUIPMENT

Suitability for Application

The unit is intended for cooling water or glycol solu­tions and is not suitable for purposes other than those specified in these instructions. Any use of the equip­ment other than its intended use, or operation of the equipment contrary to the relevant procedures may result in injury to the operator, or damage to the equipment.
The unit contains refrigerant vapor and liquid under pressure, release of which can be a danger and cause in­jury. The user should ensure that care is taken during in­stallation, operation and maintenance to avoid damage to the pressure system. No attempt should be made to gain access to the component parts of the pressure system other than by suitably trained and qualified personnel.

Electrical

The unit must be grounded. No installation or main­tenance work should be attempted on the electri­cal equipment without first switching power OFF, isolating and locking-off the power supply. Servic­ing and maintenance on live equipment must not be attempted. No attempt should be made to gain access to the control panel or electrical enclosures during normal operation of the unit.
The unit must not be operated outside the design parameters specified in this manual.
12
QUANTECH
Page 13
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 1 - GENERAL CHILLER INFORMATION AND SAFETY
This equipment (Class A, Group 1) is designed and manufactured for use in an industrial environment, in accordance with EN 61000-6-2:2005 and EN 61000-6 4:2007 (with EN 55011:2007 limits). It is not intended to be used on a low-voltage public network which supplies domestic premises. Radio frequency interference may occur if it is used on a low voltage public network.
This equipment equipped with VSD, may generate conducted and radiated disturbances, which may inter­fere with or damage susceptible connected apparatus.
Generally accepted engineering standards and practic­es should be followed to ensure trouble-free and EMC compliant electrical installation. Installations must be supervised or completed by a competent person in accordance with EN 13313.
Special considerations depending on the application:
• Industry standard grounding or “earthing” prac­tices for the equipment and installation
• Use of shielded or special cables (power and/or control)
• Use of metallic conduit and/or cable trays for power and control cables connected to equipment
• Cable segregation (in order to avoid the risk of crosstalk or cross interference to signal cables, the power cables shall be segregated from signal cables)
• Dedicated isolation transformer
• Use of additional EMC lters
It is the responsibility of a designated System Integra­tor to take proper steps assuring the Electromagnetic Compatibility of both equipment and installation as a system.

Rotating Parts

1
Fan guards must be fitted at all times and not removed unless the power supply has been isolated. If ductwork is to be fitted, requiring the wire fan guards to be re­moved, alternative safety measures must be taken to protect against the risk of injury from rotating fans.

Sharp Edges

The fins on the air-cooled condenser coils have sharp metal edges. Reasonable care should be taken when working in contact with the coils to avoid the risk of minor abrasions and lacerations. The use of gloves is recommended.
Frame rails, brakes, and other components may also have sharp edges. Reasonable care should be taken when working in contact with any components to avoid risk of minor abrasions and lacerations.

Refrigerants and Oils

Refrigerants and oils used in the unit are generally non­toxic, non-flammable and non-corrosive, and pose no special safety hazards. Use of gloves and safety glass­es is, however, recommended when working on the unit. The buildup of refrigerant vapor, from a leak for example, does pose a risk of asphyxiation in confined or enclosed spaces and attention should be given to good ventilation.
Use only the refrigerant specifically designated for the unit. Any other type of refrigerant may cause damage to the equipment and will void the warranty.

High Temperature and Pressure Cleaning

High temperature and pressure cleaning methods (for example, steam cleaning) should not be used on any part of the pressure system as this may cause operation of the pressure relief device(s). Detergents and solvents, which may cause corrosion, should also be avoided.
QUANTECH
13
Page 14
SECTION 1 - GENERAL CHILLER INFORMATION AND SAFETY

Emergency Shutdown

In case of emergency , the control panel is fitted with an incoming supply circuit breaker with a red and yel­low handle which can be used as the emergency stop device. When operated it removes the electrical supply to the inverter, fans, and control circuit thus shutting down the unit.

Safety Labels

White symbol on blue background. For safe operation, read the Instructions first.
Black symbol on yellow background. Warning: This machine may start auto­matically without prior warning
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
Black symbol on yellow background. Warning: Hot surface.
Black symbol on yellow background. Warning: Safety relief valve may dis­charge gas or liquid without prior warning.
Black symbol on yellow background. Warning: Isolate all electrical sources of supply before opening or removing the cover, as lethal voltages may exist.
Black symbol on yellow background. General attention symbol.
Black symbol on yellow background. Warning: On isolating the supply it may take up to 300 seconds for the capacitor voltage to fall below 50 volts.
14
QUANTECH
Page 15
FORM QTC4-NM1 ISSUE DATE: 4/2/2018

SECTION 2 - PRODUCT DESCRIPTION

Quantech QTC4 chillers are designed for water or glycol cooling. All units are designed to be located outside on the roof of a building or at ground level.
The units are completely assembled with all intercon­necting refrigerant piping and internal wiring, ready for field installation.
Prior to delivery, the unit is pressure tested, evacuated, and fully charged with refrigerant and oil in each of the two independent refrigerant circuits. After assembly, an operational test is performed with water flowing through the evaporator to ensure that each refrigerant circuit operates correctly.
The unit structure is manufactured from heavy gauge, galvanized steel. Many external structural parts are coated with “Champagne” baked-on enamel powder paint.
All exposed power wiring is routed through liquid-tight, non-metallic conduit.

GENERAL SYSTEM DESCRIPTION

The QTC4 chiller combines the best of modern screw compressor design with the latest technology in variable speed drives. The result is superior control and efficiency in real world conditions. The VSD enables slowing the speed of the compressor to match the load on the system resulting in precise chilled liquid con­trol, minimized sound, maximum energy efficiency, and reduced cost of ownership. The VSD also pro­vides soft starts with no electrical inrush. The lack of heat build-up on start also enables required off time between starts to be reduced to a period of two minutes.
The QTC4 Air-Cooled Screw Chiller utilizes many components, which are the same or nearly the same as a standard screw chiller of a similar size. This includes modular frame rails, condenser, fans, compressors and evaporator.
The chiller consists of two screw compressors in a corresponding number of separate refrigerant circuits, a hybrid falling film evaporator, an air-cooled condens­er, receiver/flash tanks, feed valves, oil separators, and compressor mufflers.
2

FIGURE 1 - QTC4 AIR-COOLED SCREW LIQUID CHILLER WITH VARIABLE SPEED DRIVE

QUANTECH
LD15045
15
Page 16
SECTION 2 - PRODUCT DESCRIPTION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
INPUTS Pressure Transducers Temperature Sensors Switches
Liquid Flow High Pressure Start/Stop Level
Customer Supplied Contacts
COMMUNICATIONS
Building Automation
Printer Modem
3 Phase Power Line
CONTROL
PANEL
Chiller Control
Board)
Microprocessor
User Interface
Display and
Keypad
DISPLAY
KEYPAD
OUTPUTS
Relay Output Board)
Solenoids
Contactors
Alarm Pump
Compressor Heater
Run Status
Evaporator Heater
VSD
VSD Logic Board
SCR Trigger Board
Power Components
PWM (Speed Control)
MOTOR
LD15028
AC/DC Rectier
Rectier Controller
SCR Trigger Board
Rectier
VSD Logic Board
Signal From Main Control Panel

FIGURE 2 - CHILLER CONTROL SYSTEM

Oil separators utilize no moving parts. Oil cooling is accomplished by refrigerant leaving the eductor flash­ing in the suction line which cools the oil, motor and compressor.
An integral liquid cooled, transistorized, PWM, Variable Speed Drive (VSD) is controlled by the chiller microprocessor control panel to start/stop, select com­pressors to run, and select compressor speed. Displace­ment Power Factor is 0. 95 at part or full load.
Compressor 1
Power Driver
(IGBT)
Compressor 2
IGBT Gate Driver
Inverter
PWM Signal
LD15158
The chiller microprocessor communicates with the VSD Logic Board via a 3-wire RS-485 opto coupled data link. The VSD Logic Board runs the number of compressors required to meet the load and the com­pressors to the speed requested by the chiller micro­processor.
The basic system control and VSD system architecture is shown in Figure 2 on Page 16.
16
QUANTECH
Page 17
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 2 - PRODUCT DESCRIPTION

SEMI-HERMETIC QUANTECH TWIN-SCREW COMPRESSORS

Compressors are direct drive, semi-hermetic, rotary twin-screw type, including: muffler, temperature actu­ated ‘off-cycle’ heater, IP55 terminal board and preci­sion machined cast iron housing.
Reliable suction gas cooled, high efficiency, accessible hermetic compressor motor, full suction gas flow through mesh screen filter, with inherent internal thermal overload protection and external current over­load on all three phases.
Continuous function, microprocessor controlled, Variable Speed Drive (VSD) shall provide valve-less, smooth capacity control from 100% down to 10% of chiller capacity.
In addition, elimination of the slide valve and asso­ciated unloading components has resulted in a 50% reduction in compressor moving parts.

EVAPORATOR

The evaporator is a shell and tube, hybrid falling film type heat exchanger. It contains a balance of flooded and falling film technology to optimize efficiency, min­imize refrigerant charge, and maintain reliable control. A specifically designed distribution system provides uniform refrigerant flow for optimum performance.
Fan motors are Totally Enclosed Air-Over (TEAO), squirrel-cage type and current protected. The direct drive motors feature double-sealed and permanently lubricated ball bearings, cutting down on maintenance cost over the life of the unit.

REFRIGERANT CIRCUIT

An independent refrigerant circuit is provided per compressor. Each circuit uses copper refrigerant pipe formed on computer controlled bending machines to reduce the number of brazed joints resulting in a reli­able and leak resistant system.
• Discharge lines are provided with a manual com­pressor shutoff service valve (See Accessories and Options on Page 19 for suction line service valve).
• The external oil separators, with no moving parts and designed for minimum oil carry-over, are mounted in the discharge line of the compressor.
• Liquid line components include: high absorp-
tion removable core lter-drier, sight glasses with
moisture indicators, manual shut-off valve with
charging port, orice and electronic expansion
valve.
• An economizer (ash) tank is located in each re-
frigerant circuit to increase the system efciency.
2

CONDENSER

The QTC4 introduces micro-channel coil to the Quantech screw compressor chiller line. The micro­channel maximizes condenser heat transfer, resulting in a smaller footprint, and reduces refrigerant charge by as much as 50%.
Each condenser coil is a single piece all aluminum construction including headers, tubes and fins to avoid galvanic corrosion due to dissimilar metals. Coils and headers are brazed as one piece. Integral sub-cooling is included. The design working pressure is 375 PSIG (25.9 barg).
Multiple, standard low sound, high efficiency, TEAO motor driven fans move air through the coils. They are dynamically and statically balanced, direct drive with corrosion-resistant glass fiber reinforced composite blades molded into low-noise, full airfoil cross sec­tions, providing vertical air discharge from extended orifices for efficiency and low sound.

ELECTRICAL

Quantech has years of experience designing Variable Speed Drives (VSDs) specifically for chiller applica­tions. The result is an extremely reliable air-cooled chiller system that offers industry leading efficiency at real world operating conditions, valve-less compres­sor loading/unloading, excellent capacity control, high power factor and soft start.
Incoming single point power is standard utilizing a lockable circuit breaker, 115VAC control transformer, VSD, fan contactors, ON/OFF unit switch, microcom­puter keypad and display, Chiller Control and VSD Logic boards, and relay boards.
Standard design includes IP55 rating, powder painted steel cabinet with hinged, latched, and gasket sealed outer doors equipped with wind struts for safer servic­ing. The panel includes a control display access door so that display and control features can be accessed with­out opening main cabinet doors. All exposed power wiring is routed through liquid-tight, UV-stabilized, non-metallic conduit.
QUANTECH
17
Page 18
SECTION 2 - PRODUCT DESCRIPTION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

BUILDING AUTOMATION SYSTEM CAPABILITIES

The E-Link Gateway provides an economical and versatile connection between Quantech equipment and open/standard protocols. It efficiently man­ages the communication protocols currently used by Quantech equipment, exposing the data in a consistent, organized, and defined fashion. The E-Link Gateway is available as a field-installed option on QTC4. A simple switch selection allows configuration of the required equipment profile and output protocol, which reduces equipment connectivity startup time.

MICROCOMPUTER CONTROL CENTER

The microcomputer control center (see Figure 3 on Page 18) provides automatic control of chiller
operation including compressor start/ stop and load/ unload anti-recycle timers, condenser fans, evapora­tor pump, evaporator heater, unit alarm contacts and run signal contacts. The microcomputer control cen­ter comes online as soon as the main power switch on the unit is switched on; immediately, the microcom­puter control center will begin to check all variables with a frequency ranging from 30 seconds to almost continuous monitoring.
The microprocessor controls the unit’s capac­ity by matching the actual leaving chilled water temperature (LCWT) to the user-defined setpoint. Factors that may cause the system’s actual LCWT to fluctuate are changes in ambient temperature, loop flow rate, load, and loop volume. The control system reacts to such changes by adjusting the number of com­pressors that are on and the loading of each compressor in order to keep the LCWT at the setpoint.
• Compressor Run Hours
• Compressor Number of Starts
• Oil Pressure and Temperature (per Compressor)
• Evaporator Pump Status
• Evaporator Heater Status
• History Data for Last Twenty Normal Shutdowns
• History Data for Last Ten Shutdown Faults

Programmable Setpoints

• Chiller On/Off
• Chilled Liquid (Water or Glycol)
• Local or Remote Control
• Units of Measure (Imperial or SI)
• System Lead / Lag
• Remote Temperature Reset
• Remote Current Limit
• Leaving Chilled Liquid Temperature Setpoint and Range
Quantech’ systems or another vendor’s systems can incorporate these setpoints and data outputs to give the customer a complete understanding of how the system is running through a Building Automation System.
The control system logic monitors the rate at which the LCWT is approaching the setpoint to ramp up or down compressor capacity as required. The variable frequency drive allows the compressor capacity to match the load.

Display Data

• Leaving Chilled Liquid Temperature
• Returning Liquid Temperature
• Ambient Temperature
• Lead System
• Compressor Capacity (% of Full Load Amps)
• VSD Output Frequency / Compressor Speed
18
FIGURE 3 - VIEW OF CONTROL CENTER USER
INTERFACE
QUANTECH
Page 19
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 2 - PRODUCT DESCRIPTION
Extreme Conditions – During extreme or unusual conditions (i.e. blocked condenser coils, ambient above scheduled maximum, etc.) the chiller control system will avoid shutdown by varying capacity. By monitor­ing motor current and suction and discharge pressures, the chiller can maintain maximum available cooling output without shutting down.
Unit Safeties are provided for the chiller to perform auto-reset shut down for the following conditions:
• Ambient temperature above or below allowable range
• Out of range leaving chilled liquid temperature
• Under voltage
• Flow switch operation

ACCESSORIES AND OPTIONS

All options factory mounted unless otherwise noted.

Sound Attenuation

Low Noise Kits – The standard chiller configuration is equipped with low sound fans and acoustic treatments on the refrig erant lines and compressors. There are several sound attenuation options available to further reduce sound at its source thereby meeting local sound level regulations.
SilentNight™ – Due to time of day based sound regu­lations in some locations it may be desirable to force the chiller to a lower sound level on demand. The SilentNight control option provides a control input to limit sound output of the chiller based on time of day. This feature is programmable at the chiller panel or can be controlled remotely via a signal (4-20mA or 0-10VDC) from a BAS system.

FAN OPTIONS

Ultra Quiet Fans – The chiller is equipped with specially designed fans and motors to provide lower sound levels yet retain appropriate airflow. The result is reduced fan generated sound with minimal effect on the chiller capacity or efficiency.
High Static Fans – The chiller is equipped with condenser fans with higher power motors suitable for high external static pressure, up to 100 Pa (0.4 in. wa­ter), across condenser coils. This option should be se­lected if additional airflow resistance may be present due to flow restrictions such as field installed ducts, filters, sound enclosures etc. Please contact your local Quantech Sales Representative for more information.
High Airflow Fans – The chiller is equipped with con­denser fans with airfoil type blades and high power mo­tors providing extra airflow across coils. In some chiller configurations, this option can provide an increase in chiller capacity at high ambient. The high airflow fans are also available with variable speed control. Please contact your local Quantech Sales Representative for more infor­mation.

CONDENSER COILS

Fin and tub condenser coils of seamless, internally-en­hanced, high-condensing-coefficient, corrosion resis­tant copper tubes are arranged in staggered rows. The tubes are mechanically expanded into aluminum fins. Integral subcooling is included. The design working pressure of the coils is 350 PSIG (24 barg).

Condenser Coil Protection

The aluminum alloys used in the QTC4 micro­channel condenser have been carefully selected and tested for high corrosion resistance. However, all met­als can corrode in harsh conditions. Consider protect­ing coils from corrosive environments such as coastal, marine, urban and industrial.
Post-Coated Epoxy Dipped Condenser – Micro­channel condenser coils applied with electro-deposited and baked flexible epoxy coating that is finished with a polyurethane UV resistant top-coat suitable for highly corrosive applications.

Protective Chiller Panels

Wire Panels – UV stabilized black polyvinyl chloride coated, heavy gauge, welded wire mesh guards mounted on the exterior of the full unit. Protects condenser coil faces and prevents unauthorized access to refrigerant components (compressors, pipes, evaporator, etc.), yet provides free air flow. This can cut installation cost by eliminating the need for separate, expensive fencing.
Louvered Panels – Louvered panels, painted the same color as the unit, enclose the unit to visually screen and protect the coils as well as preventing unauthor­ized access to internal components. Also available as a condenser-only option.
Louvered/Wire Panels Combination – Louvered pan­els, painted the same color as the unit, are mounted on external condenser coil faces. Heavy gauge, welded wire-mesh panels, coated to resist corrosion, are mounted around base of machine to restrict unauthorized access.
2
QUANTECH
19
Page 20
SECTION 2 - PRODUCT DESCRIPTION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
End Hail Guard – Louvered panels, painted the same color as the unit, are installed on the rear of the unit (opposite end of the control panel) to protect the ex­posed condenser from flying debris or hail.
V-Guard Panels – Solid panels, painted the same col­or as the unit, are installed along the sides of the units to cover exposed piping within the condenser section without impacting airflow. These guard panels can be combined with End Hail Guard option for additional protection from debris.

Evaporator Options

38 mm insulation – Double thickness insulation provided.
Flange Kit – Provides contractor with the couplings best suited to tie into the chilled water piping. All flanges are PN10.
Connection Location – The standard unit configura­tion is available with fluid inlet connections at rear (opposite control panel end) of unit. Option available for front fluid inlet on select configurations.
Water Box Heater – The standard unit comes with evaporator shell heaters and water pump control soft­ware. Optional water box heaters are required for storage below 0°F (-17°C). Refer to the "Refrigerant
Valve - Off: Close the water valves, close flash tank drain valves, close the suction service valves and leave power to the chiller for evaporator heater mat and wa­terbox heater operation. For units without a suction service valve, close the discharge and compressor oil valves." on page 94 for more information on freeze protection.

Controls Options

High Ambient Operation – This provides special control logic coupled with high airflow fans to permit high ambient up to 52°C (125°F) operation. Fans are airfoil type blades with high power motors. This option may also allow for increased machine capacity, allow­ing the selection of a smaller chassis to meet specific capacity requirements.
setpoint can be positively offset upwards up to 22.2°C (40°F). This option is useful for ice storage or process applications or for periods where higher chilled liquid temperatures are adequate for low loads. Available alone or in combination with BAS Load Limit.
Building Automation System Interface (Load Lim­it) – Factory installed option to accept a 4 to 20mA or
a 0 to 10VDC input to allow remote reset of the Load Limit Setpoint. The setpoint can limit system demand from 30-100%. Available alone or in combination with BAS Temperature Reset.
E-Link – The optional E-Link gateway provides com­munication between the equipment and Building Auto­mation Systems, including BACnet (MS/TP), Modbus, LON and N2.
Thermal Storage – Provides special control logic and modifications to produce leaving chilled brine temper­atures below 4.4°C (40°F) primarily at times of low ambient temperatures (night time). Option can be used to produce ice to supplement cooling and significantly decrease energy costs. The capability of the chiller is enhanced by using both ice and chilled water simulta­neously during times of peak cooling needs.

General Options

Flow Switch Accessory – Vapor proof SPDT, NEMA 3R switch, 10.3 barg (150 PSIG) DWP, -29°C to 121°C (-20°F to 250°F) with 1" NPT (IPS) connection for up­right mounting in horizontal pipe. This flow switch or equivalent must be furnished with each unit. Field
mounted.
Differential Pressure Switch – This 0.2-3 barg (3-45
PSIG) range switch, with 1/4" NPTE pressure connec­tions, is an alternative to the paddle-type flow switch.
Field mounted.
Service Isolation Valve – Service suction isolation
valve added to unit for each refrigerant circuit.
Dual Pressure Relief Valve – Two safety relief valves are mounted in parallel; one is always operational to assist in valve replacement during maintenance.
Building Automation System Interface (Tempera­ture) – Factory installed option to accept a 4 to 20mA
or a 0 to 10VDC input to allow remote reset of the Leaving Chilled Liquid Temperature Setpoint. The
20
QUANTECH
Page 21
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 2 - PRODUCT DESCRIPTION
Terminal Block [not available for CE marked units] Terminal Block connections shall be provided
at the point of incoming single point connection for field connection and interconnecting wiring to the compressors. Separate external protection must be supplied, by others, in the incoming power wiring, which must comply with local codes.
Circuit Breaker – A unit-mounted circuit breaker with external lockable handle will be supplied to isolate the single point power voltage for servicing. The circuit breaker is sized to provide motor branch circuit protec­tion, short circuit protection and ground fault protec­tion for the motor branch-circuit conductors, the motor control apparatus and the motors.
Non-Fused Disconnect Switch – Unit-mounted disconnect switch with external lockable handle can be supplied to isolate the unit power voltage for servicing. Separate external fusing must be supplied by the power wiring, which must comply with local codes.

Vibration Isolation

Elastomeric Isolation – This option is recommend­ed for normal installations. It provides very good performance in most applications for the least cost.
Field mounted.
25 mm (1") Spring Isolators – Spring and cage type
isolators for mounting under the unit base rails are available to support unit. They are level adjustable. 25 mm (1") nominal deflection may vary slightly by application. Field mounted.
50 mm (2") Restrained Spring Isolators – Restrained Spring-Flex Mounting isolators incorporate a rugged welded steel housing with vertical and horizontal limit stops. Housings designed to withstand a minimum 1.0g accelerated force in all directions up to 51 mm (2"). The deflection may vary slightly by application. They are level adjustable. Field mounted.
2
QUANTECH
21
Page 22
FORM QTC4-NM1
ISSUE DATE: 03/07/2018
THIS PAGE INTENTIONALLY LEFT BLANK
22
QUANTECH
Page 23
FORM QTC4-NM1 ISSUE DATE: 4/2/2018

SECTION 3 - RIGGING, HANDLING AND STORAGE

3
Rigging and lifting should only be done by a professional rigger in accordance with a written rig-
ging and lifting plan. The most appropriate rigging and lifting method will depend on job specic
factors, such as the rigging equipment available and site needs. Therefore, a professional rigger must determine the rigging and lifting method to be used, and it is beyond the scope of this manual to specify rigging and lifting details.

LIFTING WEIGHTS

Refer to the unit nameplate for unit shipping weight. Note that weight may vary depending on unit con­figuration at the time of lifting. Refer to the Physical Data tables within this manual for further information regarding shipping and operating weights.

DELIVERY AND STORAGE

To ensure consistent quality and maximum reliabil­ity, all units are tested and inspected before leaving the factory. Units are shipped completely assembled and containing refrigerant under pressure. Units are shipped without export crating unless crating has been specified on the Sales Order.
If the unit is to be put into storage, prior to installation, the following precautions should be observed:
• The chiller must be “blocked” so that the base is not permitted to sag or bow.
• Ensure that all openings, such as water connec­tions, are securely capped.
• Do not store where exposed to high ambient air temperatures that may exceed relief valve settings.
LD19197
Refer to Long-Term Storage Requirement - Field Preparation (Form 50.20-NM7).
• The condensers should be covered to protect the
coils and ns from potential damage and corrosion,
particularly where building work is in progress.
• The unit should be stored in a location where there is minimal activity in order to limit the risk of accidental physical damage.
• To prevent inadvertent operation of the pressure relief devices the unit must not be steam cleaned.
• It is recommended that the unit is periodically in­spected during storage.

INSPECTION

Remove any transit packing and inspect the unit to en­sure that all components have been delivered and that no damage has occurred during transit. If any damage is evident, it should be noted on the carrier’s freight bill and a claim entered in accordance with the instructions given on the advice note.
Major damage must be reported immediately to your local Quantech Representative.
QUANTECH
23
Page 24
SECTION 3 - RIGGING, HANDLING AND STORAGE
LOCKING PIN
LUG
FLANGE
LIFTING HOLE IN BASE FRAME
CORRECT
LOCKING PIN
LUG
LIFTING HOLE IN BASE FRAME
FLANGE
INCORRECT
LOCKING PIN
FLANGE
LUG
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

MOVING THE CHILLER

Prior to moving the unit, ensure that the installation site is suitable for installing the unit and is easily capable of supporting the weight of the unit and all as­sociated services. Care should be taken to avoid dam­aging the condenser cooling fins when moving the unit.
The unit must only be lifted by the base frame using all lift points provided. Never move the unit on rollers, or lift the unit using a forklift truck.

UNIT REMOVAL FROM SHIPPING CONTAINER

1. Place a clevis pin into the holes provided at the end of each base rail on the unit. Attach chains or nylon straps through the clevis pins and hook onto a suitable lift truck for pulling the unit out of the container.
2. Slowly place tension on the chains or straps until the unit begins to move and then slowly pull the unit from the container. Be sure to pull straight so the sides do not scrape the container.
3. Place a lifting xture on the forks of the lift truck and reattach the chain or strap. Slightly lift the front of the unit to remove some weight from the
oor of the container. Continue pulling the unit
with an operator on each side to guide the lift truck operator.
4. Pull the unit until the lifting locations are outside of the container. Place 4 X 4 blocks of wood under the base rails of the unit. Gently rest the unit on the blocks and remove the chains and lift truck.
Rigging and lifting should only be done by a professional rigger in accordance with a written rigging and lifting plan. The most appropriate rigging and lifting method
will depend on job specic factors, such as
the rigging equipment available and site needs. Therefore, a professional rigger must determine the rigging and lifting method to be used, and it is beyond the scope of this manual to specify rigging and lifting details.

LIFTING USING SHACKLES

The shackles should be inserted into the respective holes in the base frame and secured from the inside. Use spreader bars to avoid lifting chains hitting the chiller. Various methods of spreader bar arrangements may be used, keeping in mind the intent is to keep the unit stable and to keep the chains from hitting the chiller and causing damage. Never lift the chiller using a forklift or by hooking to the top rails. Use only the lifting holes provided. Lifting Instructions are placed on a label on the chiller and on the shipping bag.

LIFTING USING LUGS

Units are provided with lifting holes in the base frame which accept the accessory lifting lug set as shown in the figure below. The lugs (RH and LH) should be inserted into the respective holes in the base frame and turned so that the spring loaded pin engages into the hole and the flanges on the lug lock behind the hole. The lugs should be attached to the cables/chains using shackles or safety hooks.
5. Once the unit is completely removed from the container, follow the professional written rigging plan to lift the unit.

FIGURE 4 - LIFT LUG TO REMOVE UNIT FROM SHIPPING CONTAINER

24
LD19197a
LD19197b

FIGURE 5 - ACCESSORY LIFTING LUGS

QUANTECH
Page 25
FORM QTC4-NM1 ISSUE DATE: 03/07/2018
SECTION 3 - RIGGING, HANDLING AND STORAGE
THIS PAGE INTENTIONALLY LEFT BLANK
QUANTECH
25
Page 26
SECTION 3 - RIGGING, HANDLING AND STORAGE

TABLE 1 - UNIT RIGGING

FORM QTC4-NM1
ISSUE DATE: 4/2/2018
LD18582
QTC4 MODEL
DESCRIPTION UNITS
RIGGING HOLES
MODEL COND EVAP A B C D E F G H
150 S B
165 H B
175 P C
185 S A
185 H A
185 P B
175 C C
210 S A
210 H C
210 P C
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
inches 18 60 116 192
mm 464 1512 2937 4866
inches 18 60 137 214
mm 464 1533 3482 5435
inches 12 73 144 197 260
mm 314 1845 3654 5012 6593
inches 18 60 143 220
mm 464 1533 3636 5598
inches 18 60 143 227 272
mm 464 1533 3636 5761 6920
inches 18 60 137 215 302
mm 464 1533 3484 5455 7670
inches 18 60 131 214
mm. 464 1518 3332 5430
inches 18 60 143 227 272
mm 464 1533 3637 5761 6920
inches 12 73 144 197 260
mm 314 1845 3654 5012 6593
inches 12 73 163 254 324
mm 314 1845 4144 6443 8218
NOTE: Rigging and lifting the unit must be done by a professional rigger safely, as discussed in this section. The rigger should locate the center
of gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Quantech Sales Ofce for weight data.
26
QUANTECH
Page 27
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 1 - UNIT RIGGING (CONT'D)
SECTION 3 - RIGGING, HANDLING AND STORAGE
3
LD18582
QTC4 MODEL
DESCRIPTION UNITS
RIGGING HOLES
MODEL COND EVAP I J K L M N O P
150 S B
165 H B
175 P C
185 S A
185 H A
185 P B
175 C C
210 S A
210 H C
210 P C
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
inches 18 60 116 192
mm 464 1511 2937 4866
inches 18 60 137 214
mm 464 1533 3485 5435
inches 12 73 144 197 260
mm 314 1845 3654 5012 6593
inches 18 60 143 220
mm 464 1533 3636 5598
inches 18 60 143 227 272
mm 464 1533 3636 5761 6920
inches 18 60 137 215 302
mm 464 1533 3484 5455 7670
inches 60 131 214
mm 1518 3332 5430
inches 18 60 143 227 272
mm 464 1533 3637 5761 6920
inches 12 73 144 197 260
mm 314 1845 3654 5012 6593
inches 12 73 163 254 324
mm 314 1845 4144 6443 8218
NOTE: Rigging and lifting the unit must be done by a professional rigger safely, as discussed in this section. The rigger should locate the center
of gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Quantech Sales Ofce for weight data.
QUANTECH
27
Page 28
SECTION 3 - RIGGING, HANDLING AND STORAGE
TABLE 1 - UNIT RIGGING (CONT'D)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
LD18582
QTC4 MODEL
DESCRIPTION UNITS
RIGGING HOLES
MODEL COND EVAP A B C D E F G H
230 S B
240 H C
240 P C
260 S B
270 S D
270 H E
270 P E
290 H E
300 S C
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
inches 18 60 137 215 272
mm 464 1533 3485 5456 6919
inches 18 60 149 240 324
mm 464 1533 3789 6088 8218
inches 12 73 163 254 347
mm 314 1845 4144 6443 8825
inches 18 60 137 215 302
mm 464 1533 3484 5455 7670
inches 12 73 121 181 264 324
mm 314 1845 3073 4601 6717 8217
inches 12 73 121 181 264 324
mm 314 1845 3073 4601 6717 8218
inches 12 73 121 181 243 347
mm 314 1845 3073 4601 6169 8825
inches 12 73 179 290 347
mm 314 1845 4551 7358 8825
inches 12 73 161 254 347
mm 314 1845 4092 6443 8825
NOTE: Rigging and lifting the unit must be done by a professional rigger safely, as discussed in this section. The rigger should locate the center
of gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Quantech Sales Ofce for weight data.
28
QUANTECH
Page 29
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 1 - UNIT RIGGING (CONT'D)
SECTION 3 - RIGGING, HANDLING AND STORAGE
3
LD18582
QTC4 MODEL
DESCRIPTION UNITS
RIGGING HOLES
MODEL COND EVAP I J K L M N O P
230 S B
240 H C
240 P C
260 S B
270 S D
270 H E
270 P E
290 H E
300 S C
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
inches 18 60 137 215 272
mm 464 1533 3485 5456 6919
inches 18 60 149 240 324
mm 464 1533 3789 6088 8218
inches 12 73 163 254 347
mm 314 1845 4144 6443 8825
inches 18 60 137 215 302
mm 464 1533 3484 5455 7670
inches 12 73 121 181 264 324
mm 314 1845 3073 4601 6717 8218
inches 12 73 121 181 264 324
mm 314 1845 3073 4601 6717 8218
inches 12 73 121 181 243 347
mm 314 1845 3073 4601 6169 8825
inches 12 73 179 290 347
mm 314 1845 4551 7358 8825
inches 12 73 161 254 347
mm 314 1845 4092 6443 8825
NOTE: Rigging and lifting the unit must be done by a professional rigger safely, as discussed in this section. The rigger should locate the center
of gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Quantech Sales Ofce for weight data.
QUANTECH
29
Page 30
SECTION 3 - RIGGING, HANDLING AND STORAGE
TABLE 1 - UNIT RIGGING (CONT'D)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
LD18582
QTC4 MODEL
DESCRIPTION UNITS
RIGGING HOLES
MODEL COND EVAP A B C D E F G H
300 H C
310 P E
315 P E
320 S E
330 S C
340 S E
340 H E
370 P J
370 S F
370 H J
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
inches 12 73 161 254 306 391
mm 314 1845 4092 6443 7763 9941
inches 12 73 121 179 243 296 391
mm 314 1845 3072 4549 6169 7508 9942
inches 12 73 121 179 243 353 435
mm 314 1845 3072 4549 6169 8962 11059
inches 12 73 121 181 243 347
mm 314 1845 3073 4601 6169 8825
inches 12 73 163 254 306 391
mm 314 1845 4144 6443 7765 9942
inches 12 73 121 181 243 296 391
mm 314 1845 3073 4602 6170 7511 9942
inches 12 73 121 181 243 353 435
mm 314 1845 3073 4602 6170 8961 11059
inches 12 73 181 238 302 392 434 501
mm 314 1845 4602 6039 7662 9957 11024 12725
inches 12 73 181 238 302 435
mm 314 1845 4602 6039 7662 11059
inches 12 73 181 238 302 435
mm 314 1845 4602 6039 7662 11059
NOTE: Rigging and lifting the unit must be done by a professional rigger safely, as discussed in this section. The rigger should locate the center
of gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Quantech Sales Ofce for weight data.
30
QUANTECH
Page 31
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 1 - UNIT RIGGING (CONT'D)
SECTION 3 - RIGGING, HANDLING AND STORAGE
3
LD18582
QTC4 MODEL
DESCRIPTION UNITS
RIGGING HOLES
MODEL COND EVAP I J K L M N O P
300 H C
310 P E
315 P E
320 S E
330 S C
340 S E
340 H E
370 P J
370 S F
370 H J
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
inches 12 73 161 254 306 391
mm 314 1845 4092 6443 7763 9941
inches 12 73 121 179 243 296 391
mm 314 1845 3072 4549 6169 7508 9942
inches 12 73 121 179 243 353 435
mm 314 1845 3072 4549 6169 8962 11059
inches 12 73 121 181 243 347
mm 314 1845 3073 4601 6169 347
inches 12 73 163 254 306 391
mm 314 1845 4144 6443 7765 9942
inches 12 73 121 181 243 296 391
mm 314 1845 3073 4602 6170 7511 9942
inches 12 73 121 181 243 353 435
mm 314 1845 3073 4602 6170 8961 11059
inches 12 73 181 238 302 392 434 501
mm 314 1845 4602 6039 7662 9957 11024 12725
inches 12 73 181 238 302 435
mm 314 1845 4602 6039 7662 11059
inches 12 73 181 238 302 435
mm 314 1845 4602 6039 7662 11059
NOTE: Rigging and lifting the unit must be done by a professional rigger safely, as discussed in this section. The rigger should locate the center
of gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Quantech Sales Ofce for weight data.
QUANTECH
31
Page 32
SECTION 3 - RIGGING, HANDLING AND STORAGE
TABLE 1 - UNIT RIGGING (CONT'D)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
LD18582
QTC4 MODEL
DESCRIPTION UNITS
RIGGING HOLES
MODEL COND EVAP A B C D E F G H
400 P J
405 S H
410 H H
410 P J
450 S G
490 H J
460 S G
470 C K
480 C J
500 S J
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
inches 12 73 181 238 302 435 478 545
mm 314 1845 4602 6039 7358 11059 12135 13835
inches 12 73 181 238 302 435
mm 314 1845 4601 6039 7662 11059
inches 12 73 181 238 302 435 478 545
mm 314 1845 4602 6039 7358 11059 12135 13835
inches 12 73 181 238 302 435 494 572
mm 314 1845 4602 6039 7358 11059 12546 14541
inches 12 73 181 238 290 435 478 545
mm 314 1845 4602 6039 7662 11059 12135 13835
inches 12 73 181 238 290 435 494 572
mm 314 1845 4602 6039 7358 11059 12546 14541
inches 12 73 181 238 290 435 494 572
mm 314 1845 4602 6039 7358 11059 12546 14529
inches 12 73 181 238 290 435
mm 305 1854 4597 6045 7366 11049
inches 12 73 181 238 290 435 572
mm 305 1854 4597 6045 7366 11049 14529
inches 12 73 181 238 290 435 494 572
mm 305 1854 4597 6045 7366 11049 12548 14529
NOTE: Rigging and lifting the unit must be done by a professional rigger safely, as discussed in this section. The rigger should locate the center
of gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Quantech Sales Ofce for weight data.
32
QUANTECH
Page 33
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 1 - UNIT RIGGING (CONT'D)
SECTION 3 - RIGGING, HANDLING AND STORAGE
3
LD18582
QTC4 MODEL
DESCRIPTION UNITS
RIGGING HOLES
MODEL COND EVAP I J K L M N O P
400 P J
405 S H
410 H H
410 P J
450 S G
490 H J
460 S G
470 C K
480 C J
500 S J
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
Rigging Hole
Location
inches 12 73 181 238 302 435 478 545
mm 314 1845 4602 6039 7358 11059 12135 13835
inches 12 73 181 238 302 435
mm 314 1845 4601 6039 7662 11059
inches 12 73 181 238 302 435 478 545
mm 314 1845 4602 6039 7358 11059 12135 13835
inches 12 73 181 238 302 435 494 572
mm 314 1845 4602 6039 7358 11059 12546 14541
inches 12 73 181 238 290 435 478 545
mm 314 1845 4602 6039 7358 11059 12135 13835
inches 12 73 181 238 290 435 494 572
mm 314 1845 4602 6039 7358 11059 12546 14541
inches 12 73 181 238 290 435
mm 305 1854 4597 6045 7366 11049
inches 12 73 181 238 290 435
mm 305 1854 4597 6045 7366 11049
inches 12 73 181 238 290 435
mm 305 1854 4597 6045 7366 11049
inches 12 73 181 238 290 435 494 572
mm 305 1854 4597 6045 7366 11049 12548 14529
NOTE: Rigging and lifting the unit must be done by a professional rigger safely, as discussed in this section. The rigger should locate the center
of gravity through trial lifts to account for possible variations in unit conguration. Contact your nearest Quantech Sales Ofce for weight data.
QUANTECH
33
Page 34
FORM QTC4-NM1
ISSUE DATE: 03/07/2018
THIS PAGE INTENTIONALLY LEFT BLANK
34
QUANTECH
Page 35
FORM QTC4-NM1 ISSUE DATE: 4/2/2018

SECTION 4 - INSTALLATION

LOCATION REQUIREMENTS

For optimum performance and trouble-free service, it is essential that the installation site meets the location and space requirements for the model being installed.
Ensure to preserve minimum service access space for cleaning and maintenance purposes.

OUTDOOR INSTALLATIONS

The units are designed for outdoor installation and can be installed at ground level on a suitable flat level foundation easily capable of supporting the weight of the unit, or on a suitable rooftop location. In both cases an adequate supply of air is required. Avoid locations where the sound output and air discharge from the unit may be objectionable.
The selected location must have minimum sun exposure and must be away from boiler flues and other sources of airborne chemicals that could attack the condenser coils and steel parts of the unit.
If located in an area accessible to unauthorized persons, steps must be taken to prevent access to the unit by means of a protective fence. This will help to prevent the possibility of vandalism, accidental damage, or possible harm caused by unauthorized removal of protective guards or opening panels to expose rotating or high voltage components.
For ground level locations, the unit must be installed on a suitable flat and level concrete base that extends to fully support the two side channels of the unit base frame. A one-piece concrete slab, with footings extending below the frost line is recommended. To avoid noise and vibration transmission, the unit should not be secured to the building foundation.
On rooftop locations, choose a place with adequate structural strength to safely support the entire operating weight of the unit and service personnel. The unit can be mounted on a concrete slab, similar to ground floor locations, or on steel channels of suitable strength. The channels should be spaced with the same centers as the unit side and front base rails. This will allow vibration isolators to be fitted if required. Isolators are recom­mended for rooftop locations.
Mounting holes (5/8”) are provided in the base rails for bolting the unit to its foundation. Refer to Table 10 on Page 78 for location of the mounting holes.
Any ductwork or attenuators fitted to the unit must not have a total static pressure resistance, at full unit airflow, exceeding the capability of the fans installed in the unit.
The condenser fans are propeller-type and are not recommended for use with ductwork, filters or other impediments to airflow in the condenser air stream.
When it is desirable to surround the unit(s) in addition to whatever optional louver package is selected, it is recommended that the screening be able to pass the required chiller CFM without exceeding
0.1"w.g. (24.9084 pa) external static pressure.
Protection against corrosive environments is available by ordering the units with cured epoxy-coat­ing on the microchannel condenser coil. Epoxy-coated coils should be used with any units being installed at the seashore where salt spray / mist may hit the units, or where acid rain is prevalent.
On installations where winter operation is intended and snow accumulations are expected, additional elevation must be provided to insure normal condenser air flow.
Avoid locations near windows or structures where normal operating sounds may be objectionable.

LOCATION CLEARANCES

Adequate clearances around the unit(s) are required for the unrestricted airflow for the air-cooled condenser coils and to prevent re-circulation of warm discharge air back onto the coils. If clearances given are not maintained, airflow restriction or re-circulation will cause a loss of unit performance, an increase in power consumption, and may cause the unit to malfunction. Consideration should also be given to the possibility of down drafts, caused by adjacent buildings, which may cause re-circulation or uneven unit airflow.
For locations where significant cross winds are expected, such as exposed roof tops, an enclosure of solid or louver type is recommended to prevent wind turbulence interfering with the unit airflow.
When units are installed in an enclosure, the enclo­sure height should not exceed the height of the unit on more than one side. If the enclosure is of louvered construction, the same requirement of static pressure loss applies as for ducts and attenuators stated above.
4
QUANTECH
35
Page 36
SECTION 4 - INSTALLATION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

Recommended Minimum Clearances

Recommended clearances for the QTC4 units are:
• Side to wall – 6' (1.8 m)
• Rear to wall – 6' (1.8 m)
• Control panel end to wall – 4' (1.2 m)
• Top – no obstructions whatsoever
• Distance between adjacent units – 10' (3 m)
Clearance dimensions provided in Figure 6 on page 36below and Table 2 on Page 36, are necessary to maintain good
airow and ensure correct unit operation.
It is also necessary to consider access requirements for safe operation and maintenance of the unit and power and control panels. Local health and safety regulations, or practical considerations for service replacement of large compo­nents, may require larger clearances than those recommended.
A
Tube Removal
Clearance Area
B
1.8 m (6') Minimum
1.2 m (4') Minimum
C
A
3 m (10') Minimum
Control Panel

FIGURE 6 - ACCEPTABLE MINIMUM CLEARANCES AROUND / BETWEEN UNIT(S)

Tube Removal
Clearance Area
TABLE 2 - MINIMUM EVAPORATOR TUBE REMOV­AL CLEARANCE
TUBE REMOVAL
MODEL QTC4
FRAME COND EVAP IN. MM IN. MM IN. MM
150 S B 26 663 36 914 132 3353
165 H B 26 663 36 914 132 3353
175 P C 26 663 36 914 156 3962
185 S A 26 663 36 914 144 3658
185 H A 26 663 36 914 144 3658
185 P B 26 663 36 914 144 3658
175 C C 26 663 36 914 156 3962
210 S A 26 663 36 914 156 3962
210 H C 26 663 36 914 156 3962
210 P C 26 663 36 914 156 3962
230 S B 26 663 36 914 132 3353
240 H C 26 663 36 914 156 3962
240 P C 26 663 36 914 156 3962
260 S B 26 663 36 914 132 3353
270 C D 26 663 36 914 192 4877
270 S D 26 663 36 914 192 4877
270 H E 26 663 36 914 192 4877
270 P E 26 663 36 914 192 4877
290 H E 26 663 36 914 192 4877
300 S C 26 663 36 914 156 3962
300 H E 26 663 36 914 156 3962
310 P E 26 663 36 914 156 3962
315 P E 26 663 36 914 192 4877
320 S E 26 663 36 914 192 4877
330 S C 26 663 36 914 156 3962
340 S E 26 663 36 914 192 4877
340 H E 26 663 36 914 192 4877
370 P J 26 663 36 914 192 4877
370 S F 26 663 36 914 144 3658
370 H J 26 663 36 914 192 4877
400 P J 26 663 36 914 192 4877
405 S H 26 663 36 914 192 4877
410 H H 26 663 36 914 144 3658
410 P J 26 663 36 914 192 4877
450 S G 26 663 36 914 144 3658
490 H J 26 663 36 914 192 4877
460 S G 26 663 36 914 144 3658
470 C K 26 663 36 914 192 4877
480 C J 26 663 36 914 192 4877 500 S J 26 663 36 914 192 4877
CLEARANCE DIMENSIONS
A B C
36
QUANTECH
Page 37
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 4 - INSTALLATION

VIBRATION ISOLATORS

Optional sets of vibration isolators can be supplied loose with each unit.
Using the Isolator tables shipped with the unit in the information pack. Identify each mount and its correct location on the unit.

Installation

Place each mount in its correct position and lower the unit carefully onto the mounts ensuring the mount engages in the mounting holes in the unit base frame.
On adjustable mounts, transfer the unit weight even­ly to the springs by turning the mount adjusting nuts (located just below the top plate of the mount) counter­clockwise to raise and clockwise to lower. This should be done two turns at a time until the top plates of all mounts are between 1/4" (6 mm) and 1/2" (12 mm) clear of top of their housing and the unit base is level.

SHIPPING BRACES

The chiller’s modular design does not require shipping braces.

CHILLED LIQUID PIPING

General Requirements

The following piping recommendations are intended to ensure satisfactory operation of the unit(s). Failure to follow these recommendations could cause damage to the unit, or loss of performance, and may invalidate the warranty.
The maximum ow rate and pressure drop
for the evaporator must not be exceeded at any time. Refer to SECTION 5 - TECHNI­CAL DATE on page 57 for details.
The Maximum acceptable Chilled Liquid pressure in the inlet of Evaporator is same as the statement in "Maximum Tube Side Pressure" of Pressure Vessel Name Plate for QTC4 with Falling Film Evaporator.
There should be a straight run of piping of at least 5 pipe diameters on either side. The flow switch should be wired to Terminals 2 and 13 on the 1TB terminal block. A flow switch is required to prevent damage to the evaporator caused by the unit operating without ad­equate liquid flow.
The flow switch used must have gold plated contacts for low voltage/current operation. Paddle type flow switches suitable for 10 barg (150 PSIG) working pres­sure and having a 1" N.P.T. connection can be obtained from Quantech as an accessory for the unit. Alterna­tively, a differential pressure switch fitted across an orifice plate may be used, preferably of the high/low limit type.
The chilled liquid pump(s) installed in the piping system(s) should discharge directly into the unit evap­orator section of the system. The pump(s) may be con­trolled by the chiller controls or external to the unit.
Pipework and fittings must be separately supported to prevent any loading on the evaporator. Flexible con­nections are recommended which will also minimize transmission of vibrations to the building. Flexible connections must be used if the unit is mounted on anti-vibration mounts, as some movement of the unit can be expected in normal operation.
Piping and fittings immediately next to the evaporator should be readily de-mountable to enable cleaning be­fore operation, and to facilitate visual inspection of the exchanger nozzles.
The evaporator must be protected by a
strainer, preferably of 16 mesh, tted as
close as possible to the liquid inlet con­nection, and provided with a means of local isolation.
The evaporator must not be exposed to flushing velocities or debris released during flushing. It is recommended that a suitably sized bypass and valve arrangement is installed to allow flushing of the piping system. The bypass can be used during maintenance to isolate the heat exchanger without disrupting flow to other units.
4
QUANTECH
The liquid must enter evaporator at the inlet connection. The standard inlet con­nection is opposite the control panel end
of the evaporator. A ow switch must be
installed in the customer piping at the outlet of the evaporator and wired back to the control panel using shielded cable.
Thermometer and pressure gauge connections should be provided on the inlet and outlet connections of each evaporator. Gauges and thermometers are not provided with the unit and are to be furnished by others.
Drain and air vent connections should be provided at all low and high points in the piping to permit drainage of the system and to vent any air in the pipes.
37
Page 38
SECTION 4 - INSTALLATION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
Liquid system lines at risk of freezing, due to low am­bient temperatures should be protected using insula­tion and heater tape and/or a suitable glycol solution. The liquid pump(s) may also be used to ensure liquid is circulated when the ambient temperature approaches freezing point.
Insulation should also be installed around the evapora­tor nozzles. Heater tape of 21 Watts per meter under the insulation is recommended, supplied independently and controlled by an ambient temperature thermostat set to switch ON at approximately 2.2°C (4°F), above the freezing temperature of the chilled liquid.
Evaporator heater mats are installed under the insula­tion, and are powered from the chiller's control panel. In sub-freezing conditions, unless the evaporator has been drained or an appropriate water-to-glycol concen­tration is maintained, high voltage power to the chill­er must be kept on to ensure the heater mats assist in evaporator freeze protection. If there is a potential for power loss, Quantech recommends that the evaporator is drained or that water in the chilled water circuit be replaced with an appropriate water-to-glycol concen­tration.
Any debris left in the water piping be­tween the strainer and evaporator could cause serious damage to the tubes in the evaporator and must be avoided. Be sure the piping is clean before connecting it to the evaporator. Keep evaporator nozzles and chilled liquid piping capped prior to installation to assure construction debris is not allowed to enter.
The installer/user must also ensure that the quality of the water in circulation is adequate, without any dissolved gases, which can cause oxidation of steel or cop­per parts within the evaporator.

WATER TREATMENT

The unit performance provided in the Design Guide is based on a fouling factor of 0.018m2/hr °C/kW (0.0001 ft2hr°F/Btu). Dirt, scale, grease and certain types of wa­ter treatment will adversely affect the heat exchanger surfaces and therefore the unit performance. Foreign matter in the water system(s) can increase the heat ex­changer pressure drop, reducing the flow rate and caus­ing potential damage to the heat exchanger tubes. Aer­ated, brackish or salt water is not recommended for use in the water system(s).
Quantech recommends that a water treatment specialist should be consulted to determine whether the proposed water composition will adversely affect the evaporator materials of carbon steel and copper. The pH value of the water flowing through the evaporator must be kept in a range between 7 and 8.5.

PIPEWORK ARRANGEMENT

The following is a suggested piping arrangement for single unit installations.
-Isolating Valve - Normally Open
-Isolating Valve - Normally Closed
-Flow Regulating Valve
-Flow Measurement Device
-Strainer
-Pressure Tapping
-Flow Switch
-Flanged Connection
-Pipework

FIGURE 7 - PIPEWORK ARRANGEMENT

LD15151

MINIMUM WATER VOLUME

It is good practice to include as much water volume as possible in a chilled water loop. This increases the ther­mal mass and “Flywheel” effect within the system (that is: the more; the better) which in turn promotes stable water temperature control and increases reliability by reducing compressor cycling.
For air conditioning applications, a minimum of 3 gal­lons/ton is required. It is preferred that the gallon/ton ratio be within the 5 to 8 range. For process applica­tions, a minimum of 6 gallons/ton ratio is required with preference towards a range of 7 to 11. Install a tank or increase pipe sizes to provide sufficient water volume.

LEAVING WATER TEMPERATURE OUT OF RANGE

The QTC4 chiller line has a maximum leaving water temperature of 15.6°C (60°F). Where process applica­tions require a chilled water temperature higher than what the chiller provides, a simple piping change can remove the problem. By using a mixture of chiller­cooled water and returning process water, the chilled
38
QUANTECH
Page 39
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 4 - INSTALLATION
water entering the process can be held at the desired temperature. A tank can also be used to meet high leav­ing water temperature requirements.
RECIRCULATION
SUPPLY TO LOAD
RETURN FROM LOAD
LOAD
LD15049
FIGURE 8 - LEAVING WATER TEMPERATURE OUT
OF RANGE SUGGESTED LAYOUT

FLOW RATE OUT OF RANGE

Each QTC4 evaporator has a minimum and maximum flow rate. Some process applications require a flow rate that is out of range for the evaporator. In those ap­plications, a piping change can remove the problem.
In applications where the required flow rate is less than the evaporator’s minimum allowable, the chilled water can be recirculated to the chiller.
In applications where the required flow rate is greater than the evaporator’s maximum allowable, the chilled water can be recirculated to the load.
THERMAL STORAGE
Thermal storage is the practice of storing cooling ener­gy during a period of little or no load and/or low energy costs for use during periods of high load and/or energy costs. Conventional cooling systems produce cooling when it is needed which is commonly during times of peak demand. Thermal storage allows generation of cooling capacity to occur during off-peak periods and store that capacity to meet future cooling requirements. Using thermal storage can result in smaller equipment sizes, thereby reducing capital cost, and also can result in significant energy cost savings
The QTC4 has special control logic to be able to pro­duce chilled leaving brine temperatures below 4.4°C (40°F) so as to supply a storage tank with chilled liq­uid during times of low demand. QTC4 chillers selected for thermal storage operation can also be selected to efficiently provide chilled fluid at nominal cooling loads.
4
BYPASS
SUPPLY TO LOAD
RETURN FROM LOAD
LOAD
LD15050

FIGURE 9 - SUGGESTED LAYOUT FOR APPLICATIONS WITH FLOW RATES LESS THAN THE EVAPORATOR MINIMUM ALLOWABLE FLOW RATE

QUANTECH
BYPASS
SUPPLY TO LOAD
LOAD
LD15051

FIGURE 10 - SUGGESTED LAYOUT FOR APPLICATIONS WITH A FLOW RATE GREATER THAN THE EVAPORATOR MAXIMUM ALLOWABLE FLOW RATE

39
Page 40
SECTION 4 - INSTALLATION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

VARIABLE PRIMARY FLOW

Quantech recommends a maximum 10% per minute flow rate of change, based on design flow, for variable primary flow applications. Provide 8 to 10 gallons per chiller ton (8.6 to 10.8 liter per cooling KW) system wa­ter volume. Insufficient system volume and rapid flow changes can cause control problems or can even cause chiller shutdowns. There are many other design issues to evaluate with variable primary flow systems. Consult your Quantech Sales Representative for more informa­tion about successfully applying QTC4 chillers.

CONNECTION TYPES AND SIZES

For connection sizes relevant to individual models, re­fer to SECTION 5 - TECHNICAL DATA.

EVAPORATOR CONNECTIONS

Standard chilled liquid connections on evaporators are of the Victaulic Groove type.
LD10494

FIGURE 11 - VICTAULIC GROOVE

TABLE 3 - EVAPORATOR CONNECTIONS DIMEN-
SIONS
VICTAULIC
FRAME COND. EVAP.
150 S B 6" DN150 165 H B 6" DN150 175 P C 6" DN150 185 S A 6" DN150 185 H A 6" DN150 185 P B 6" DN150 175 C C 6" DN150 210 S A 6" DN150 210 H C 6" DN150 210 P C 6" DN150 230 S B 6" DN150 240 H C 6" DN150 240 P C 6" DN150 260 S B 6" DN150 270 C D 6" DN150 270 S D 6" DN150 270 H E 8" DN200 270 P E 8" DN200 290 H E 8" DN200 300 S C 6" DN150 300 H C 6" DN150 310 P E 8" DN200 315 P E 8" DN200 320 S E 8" DN200 330 S C 6" DN150 340 S E 8" DN200 340 H E 8" DN200 370 P J 8" DN200 370 S F 8" DN200 370 H J 8" DN200 400 P J 8" DN200 405 S H 8" DN200 410 H H 8" DN200 410 P J 8" DN200 450 S G 8" DN200 490 H J 8" DN200 460 S G 8" DN200 470 C K 8" DN200 480 C J 8" DN200 500 S J 8" DN200
* Reference Figure 12 on Page 41 for ange dimensions.
CONNECTIONS
SIZE
NOMINAL
DIAMETER
40
QUANTECH
Page 41
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 4 - INSTALLATION

Option Flanges

One of two types of flanges may be fitted depending on the customer or local pressure vessel code require­ments. These are Victaulic-Adapter flanges, normally supplied loose, or weld flanges, which may be sup­plied loose or ready-fitted. Victaulic-Adapter and weld flange dimensions are to ISO 7005 - NP10.
WELD FLANGE VICTAULIC ADAPTER
LD10495

FIGURE 12 - FLANGE ATTACHMENT

If relief piping is common to more than one valve, its cross-sectional area must be at least the total required by each valve. Valve types should not be mixed on a common pipe. Precautions should be taken to ensure the outlets of relief valves or relief valve vent pipes remain clear of obstructions at all times.

ELECTRICAL CONNECTION

The following connection recommendations are intended to ensure safe and satisfactory operation of the unit. Failure to follow these recommendations could cause harm to persons or damage the unit, and may invalidate the warranty.
No additional controls (relays, etc.) should be mounted in the control panel. Power and control wiring not connected to the control panel should not be run through the control panel. If these pre­cautions are not followed it could lead to a risk of electrocution. In addition, elec­trical noise could cause malfunctions or damage the unit and its controls.
4

REFRIGERANT RELIEF VALVE PIPING

The evaporator is protected against internal refrigerant overpressure by refrigerant relief valves. A pressure relief valve is mounted on each of the main refrigerant lines connecting the evaporator to the compressors.
A piece of pipe is fitted to each valve and directed so that when the valve is activated the release of high pressure gas and liquid cannot be a danger or cause injury. For indoor installations (not recommended), pressure relief valves should be piped to the exterior of the building.
The size of any piping attached to a relief valve must be of sufficient diameter so as not to cause resistance to the operation of the valve. Unless otherwise specified by local regulations. Internal diameter depends on the length of pipe required and is given by the following formula:
D5 = 1.447 x L
Where:
• D = minimum pipe internal diameter in cm
• L = length of pipe in meters
After power wiring connection, do not switch on mains power to the unit. Some internal components are live when the mains are switched on and this must only be done by “Authorized” persons familiar with starting, operating, and troubleshooting this type of equipment.

POWER WIRING

All electrical wiring should be carried out in accor­dance with local regulations. Route properly sized cables to cable entries on the unit.
In accordance with local codes, NEC codes, U.L. and C.E. standards, it is the responsibility of the user to install over current protection devices between the supply conductors and the power supply terminals on the unit.
To ensure that no eddy currents are set up in the power panel, the cables forming the 3-phase power supply must enter via the same cable entry.
All sources of supply to the unit must be taken via a common point of isolation (not supplied by Quantech).
QUANTECH
41
Page 42
SECTION 4 - INSTALLATION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
Copper power wiring only should be used for supply­ing power to the chiller. This is recommended to avoid safety and reliability issues resulting from connection failure at the power connections to the chiller. Alumi­num wiring is not recommended due to thermal char­acteristics that may cause loose terminations result­ing from the contraction and expansion of the wiring. Aluminum oxide may also build up at the termination causing hot spots and eventual failure. If aluminum wiring is used to supply power to the chiller, AL-CU compression fittings should be used to transition from aluminum to copper. This transition should be done in an external box separate to the power panel. Copper conductors can then be run from the box to the chiller.
Caulk power and control wiring conduit entering the power panel to assure moist air from the building cannot enter the panel.

POWER SUPPLY WIRING

Units require only one 3-phase supply, plus earth.
Connect the 3-phase supplies to the circuit breaker located in the panel (See Table 4 on Page 47).
Connect a suitably sized earth wire to the PE terminal in the panel.

CONTROL WIRING

All control wiring utilizing contact closures to the con­trol panel terminal block is nominal 115VAC and must be run in shielded cable, with the shield grounded at the panel end only, and run in water tight conduit. Run shielded cable separately from mains cable to avoid electrical noise pick-up. Use the control panel cable entry to avoid the power cables.
Voltage free contacts connected to the panel must be suitable for 115VAC10 ma (gold contacts recommend­ed). If the voltage free contacts form part of a relay or contactor, the coil of the device must be suppressed using a standard R/C suppressor. The above precautions must be taken to avoid electrical noise, which could cause a malfunction or damage to the unit and its controls.

VOLTS FREE CONTACTS

Chilled Liquid Pump Starter

Terminals 23 and 24 on 1TB close to start the chilled liquid pump. This contact can be used as a master start/ stop for the pump in conjunction with the daily start/ stop schedule. Cycle the pumps from the unit panel if the unit will be operational or shut-down during sub­freezing conditions. Refer to the Evaporator Pump Control on Page 96 for more information on testing the pumps.

115VAC CONTROL SUPPLY TRANSFORMER

A 3-wire high voltage to 115VAC supply transformer is standard in the chiller. This transformer is mounted in the cabinet and steps down the high voltage supply to 115VAC to be used by the Controls, VSD, Feed and Drain Valve Controller, Valves, Solenoids, Heaters, etc.
The high voltage for the transformer primary is taken from the chiller input. Fusing is provided for the transformer.
Removing high voltage power to the chiller will remove the 115VAC supply voltage to the control panel circuitry and the evaporator heater mat. In sub­freezing weather, this could cause serious damage to the chiller due to evaporator freeze-up. Do not remove power unless alternate means are taken to ensure op­eration of the control panel, evaporator heater mat, and waterbox heaters.

Run Contact

Terminals 21 and 22 on 1TB close to indicate that a system is running.

Alarm Contacts

Each system has a single voltage-free contact, which will operate to signal an alarm condition whenever any system locks out, or there is a power failure. To obtain system alarm signal, connect the alarm circuit to volt free Terminals 25 & 26 (Sys 1), Terminals 27 and 28 (Sys 2) of 1TB.

SYSTEM INPUTS

Flow Switch

A chilled liquid flow switch of suitable type MUST be connected between Terminals 2 and 13 of 1TB to pro­vide protection against loss of liquid flow, which will cause evaporator freeze-up if the chiller is permitted to run. The flow switch circuitry is a 115VAC circuit. Contacts must be rated for low current (5mA). Gold contacts should be used.
42
QUANTECH
Page 43
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 4 - INSTALLATION

Remote Run / Stop

A Remote Run/Stop input is available for each systems. These inputs require a dry contact to start and stop the system. System 1 remote dry contacts are connected between Terminals 2 and 15 of 1TB and System 2 dry contacts are connected between Terminals 2 and 16 of 1TB. If remote start/stop is not utilized, a jumper must be paced across the terminals to allow the system to run. The remote run/stop circuitry is a 115VAC circuit. Contacts must be rated for low current (5mA). Gold contacts should be used.

Remote Print

Closure of suitable contacts connected to Terminals 2 and 14 of 1TB will cause a hard copy printout of Operating Data/Fault History to be made if an optional printer is connected to the RS-232 port. The remote print circuitry is a 115VAC circuit. Contacts must be rated for low current (5mA). Gold contacts should be used.

Optional Remote Setpoint Offset – Temperature

A voltage signal connected to Terminals 17 and 18 of 1TB will provide a remote offset function of the chilled liquid setpoint, if required.

Optional Remote Setpoint Offset – Current

A voltage signal connected to Terminals 19 and 20 of 1TB will provide a remote setting of current limit setpoint, if required.

Optional Remote Setpoint Offset – Sound Limiting

A voltage signal connected to Terminals 40 and 41 of 1TB will provide remote setting of sound limit setpoint, if required.
4
QUANTECH
43
Page 44
SECTION 4 - INSTALLATION

POWER SUPPLY WIRING

FORM QTC4-NM1
ISSUE DATE: 4/2/2018

Single Point Wiring

Minimum Circuit Ampacity (MCA), Minimum/Maximum Fuse Size and Minimum/Maximum Circuit Breaker size varies on chillers based upon model and options ordered. Consult YorkWorks or the chiller data plate for electrical data
on a specic chiller.

FIGURE 13 - SINGLE POINT POWER WIRING

44

Voltage Utilization Range

RATED
VOLTAGE
200/60/3 180-220
230/60/3 208-254
380/60/3 342-402
400/60/3 360-440
460/60/3 414-508
575/60/3 520-635
400/50/3 360-440
UTILIZATION RANGE
LD18588
QUANTECH
Page 45
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 4 - INSTALLATION

Dual Point Wiring

4
2

FIGURE 14 - DUAL POINT POWER WIRING

QUANTECH
LD18589
45
Page 46
SECTION 4 - INSTALLATION
SYS. No. 1
ALARM
CONTACTS
SYS. No. 2
ALARM
CONTACTS
CHILLER
RUN
EVAP. PUMP
START
SIGNAL
SYS. No. 1 RUN PERM
SYS. No. 2 RUN PERM
FLOW SWITCH (-SF)
PRINT (PNT)
LEGEND
TERMINAL BLOCK FOR CUSTOMER CONNECTIONS
TERMINAL BLOCK FOR QUANTECH CONNECTIONS
WIRING AND COMPONENTS BY QUANTECH
OPTIONAL EQUIPMENT
WIRING AND/OR COMPONENTS BY OTHERS
RELAY
BOARD
No. 2
RELAY
BOARD
No. 1
CONTROL
BOARD
+ SIGNAL INPUT
+ SIGNAL INPUT
+ SIGNAL INPUT
- SIGNAL INPUT (GND)
- SIGNAL INPUT (GND)
- SIGNAL INPUT (GND)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

CUSTOMER CONTROL WIRING

FIGURE 15 - CUSTOMER CONTROL CONNECTIONS

46
QUANTECH
Page 47
FORM QTC4-NM1 ISSUE DATE: 4/2/2018

TABLE 4 - ELECTRICAL LUG DATA

FIELD WIRING LUGS
QTC4 MODEL
MODEL COND EVAP
150 S B
165 H B
175 P C
185 S A
185 H A
185 P B
175 C C
210 S A
210 H C
INPUT
VOLTS
INPUT
FREQ
200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil 400 50 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil 400 50 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil 400 50 2 #2 - 600 kcmil 2 #2/0 ~ 500 kcmil 2 #2 - 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 - 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
STANDARD & ULTRA QUIET CONDENSER FANS
TERMINAL
BLOCK
WIRES
PER
PHASE
SINGLE POINT WIRING
LUG
WIRE
RANGE
WIRES
PER
PHASE
CIRCUIT
BREAKER
LUG
WIRE
RANGE
SECTION 4 - INSTALLATION
NON-FUSED
DISCONNECT SWITCH
WIRES
PER
PHASE
LUG
WIRE
RANGE
4
QUANTECH
47
Page 48
SECTION 4 - INSTALLATION
TABLE 4 - ELECTRICAL LUG DATA (CONT'D)
FIELD WIRING LUGS
QTC4 MODEL
MODEL COND EVAP
150 S B
165 H B
175 P C
185 S A
185 H A
185 P B
175 C C
210 S A
210 H C
INPUT
VOLTS
INPUT
FREQ
200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
WIRE
PER
PHASE
HIGH AIRFLOW/HIGH STATIC CONDENSER FANS
TERMINAL
BLOCK
LUG
WIRE
RANGE
PHASE
BREAKER
WIRES
PER
CIRCUIT
LUG
WIRE
RANGE
SINGLE POINT WIRING
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
NON-FUSED
DISCONNECT SWITCH
WIRES
PER
PHASE
LUG
WIRE
RANGE
48
QUANTECH
Page 49
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 4 - ELECTRICAL LUG DATA (CONT'D)
FIELD WIRING LUGS
QTC4 MODEL
MODEL COND EVAP
210 P C
230 S B
240 H C
240 P C
260 S B
270 C D
270 S D
270 H E
270 P E
INPUT
VOLTS
INPUT FREQ
200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 400 50 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 - 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #2 - 600 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil
WIRES
PER
PHASE
STANDARD & ULTRA QUIET CONDENSER FANS
TERMINAL
BLOCK
LUG
WIRE
RANGE
SINGLE POINT WIRING
PHASE
WIRES
PER
CIRCUIT
BREAKER
LUG
WIRE
RANGE
SECTION 4 - INSTALLATION
NON-FUSED
DISCONNECT SWITCH
WIRES
PER
PHASE
LUG
WIRE
RANGE
4
QUANTECH
49
Page 50
SECTION 4 - INSTALLATION
TABLE 4 - ELECTRICAL LUG DATA (CONT'D)
FIELD WIRING LUGS
QTC4 MODEL
MODEL COND EVAP
210 P C
230 S B
240 H C
240 P C
260 S B
270 C D
270 S D
270 H E
270 P E
INPUT
VOLTS
INPUT
FREQ
200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 - 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 - 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 - 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 - 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 - 500 kcmil 2 #2 ~ 600 kcmil 200 60 4 #1/0 ~ 700 kcmil 230 60 4 #2 - 600 kcmil 4 4/0 ~ 500 kcmil 380 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 400 50 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 2 #2 - 600 kcmil 2 #1 - 500 kcmil 2 #2 ~ 600 kcmil
WIRE
PER
PHASE
HIGH AIRFLOW/HIGH STATIC CONDENSER FANS
TERMINAL
BLOCK
LUG
WIRE
RANGE
WIRES
PHASE
PER
CIRCUIT
BREAKER
LUG
WIRE
RANGE
SINGLE POINT WIRING
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
NON-FUSED
DISCONNECT SWITCH
WIRES
PER
PHASE
LUG
WIRE
RANGE
50
QUANTECH
Page 51
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 4 - ELECTRICAL LUG DATA (CONT'D)
FIELD WIRING LUGS
QTC4 MODEL
MODEL COND EVAP
290 H E
300 S C
300 H C
310 P E
315 P E
320 S E
330 S C
340 S E
340 H E
INPUT
VOLTS
INPUT
FREQ
200 60 230 60 380 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 ~ 600 kcmil 460 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 ~ 600 kcmil
WIRES
PER
PHASE
STANDARD & ULTRA QUIET CONDENSER FANS
TERMINAL
BLOCK
LUG
WIRE
RANGE
SINGLE POINT WIRING
WIRES
PER
PHASE
CIRCUIT
BREAKER
LUG
WIRE
RANGE
SECTION 4 - INSTALLATION
NON-FUSED
DISCONNECT SWITCH
WIRES
PER
PHASE
LUG
WIRE
RANGE
4
QUANTECH
51
Page 52
SECTION 4 - INSTALLATION
TABLE 4 - ELECTRICAL LUG DATA (CONT'D)
FIELD WIRING LUGS
QTC4 MODEL
MODEL COND EVAP
290 H E
300 S C
300 H C
310 P E
315 P E
320 S E
330 S C
340 S E
340 H E
INPUT
VOLTS
INPUT
FREQ
200 60 230 60 380 60 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 460 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 - 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 - 600 kcmil 200 60 230 60 380 60 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 460 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 - 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 - 600 kcmil 200 60 230 60 380 60 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 460 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 - 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 - 600 kcmil 200 60 230 60 380 60 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 460 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 - 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 - 600 kcmil 200 60 230 60 380 60 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 460 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 - 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 - 600 kcmil 200 60 230 60 380 60 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 460 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 - 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 - 600 kcmil 200 60 230 60 380 60 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 460 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 - 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 - 600 kcmil 200 60 230 60 380 60 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 460 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 - 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 - 600 kcmil 200 60 230 60 380 60 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 400 50 4 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 4* #2 - 600 kcmil 460 60 3 #2 - 600 kcmil 4 #4/0 ~ 500 kcmil 3 #2 - 600 kcmil 575 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #2 - 600 kcmil
WIRE
PER
PHASE
HIGH AIRFLOW/HIGH STATIC CONDENSER FANS
TERMINAL
BLOCK
LUG
WIRES
WIRE
RANGE
PHASE
SINGLE POINT WIRING
PER
CIRCUIT
BREAKER
LUG
WIRE
RANGE
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
NON-FUSED
DISCONNECT SWITCH
WIRES
PER
PHASE
LUG
WIRE
RANGE
52
QUANTECH
Page 53
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 4 - ELECTRICAL LUG DATA (CONT'D)
FIELD WIRING LUGS
QTC4 MODEL
MODEL COND EVAP
370 P J
370 S F
370 H J
400 P J
405 S H
410 H H
410 P J
450 S G
490 H J
INPUT
VOLTS
INPUT FREQ
200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil
WIRES
PER
PHASE
STANDARD & ULTRA QUIET CONDENSER FANS
TERMINAL
BLOCK
LUG
WIRE
RANGE
DUAL POINT WIRING
WIRES
PER
PHASE
CIRCUIT
BREAKER
LUG
WIRE
RANGE
SECTION 4 - INSTALLATION
NON-FUSED
DISCONNECT SWITCH
WIRES
PER
PHASE
LUG
WIRE
RANGE
4
QUANTECH
53
Page 54
SECTION 4 - INSTALLATION
TABLE 4 - ELECTRICAL LUG DATA (CONT'D)
FIELD WIRING LUGS
QTC4 MODEL
MODEL COND EVAP
370 P J
370 S F
370 H J
400 P J
405 S H
410 H H
410 P J
450 S G
490 H J
INPUT
VOLTS
INPUT
FREQ
200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil
TERMINAL
WIRE
PER
PHASE
HIGH AIRFLOW/HIGH STATIC CONDENSER FANS
CIRCUIT
BLOCK
LUG
WIRE
RANGE
WIRES
PER
PHASE
BREAKER
LUG
WIRE
RANGE
DUAL POINT WIRING
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
NON-FUSED
DISCONNECT SWITCH
WIRES
PER
PHASE
LUG
WIRE
RANGE
54
QUANTECH
Page 55
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 4 - ELECTRICAL LUG DATA (CONT'D)
FIELD WIRING LUGS
QTC4 MODEL
MODEL COND EVAP
460 S G
470 C K
480 C J
500 S J
INPUT
VOLTS
INPUT
FREQ
200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 200 60 230 60 380 60 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 400 50 3 #2 - 600 kcmil 3 #3/0 ~ 400 kcmil 3 #3/0 ~ 400 kcmil 460 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil 575 60 2 #2 - 600 kcmil 2 #1 ~ 500 kcmil 2 #1 ~ 500 kcmil
WIRE
PER
PHASE
STANDARD & ULTRA QUIET CONDENSER FANS
TERMINAL
BLOCK
LUG
WIRE
RANGE
DUAL POINT WIRING
WIRES
PER
PHASE
CIRCUIT
BREAKER
LUG
WIRE
RANGE
SECTION 4 - INSTALLATION
NON-FUSED
DISCONNECT SWITCH
WIRES
PER
PHASE
LUG
WIRE
RANGE
4
QUANTECH
55
Page 56
FORM QTC4-NM1
ISSUE DATE: 03/07/2018
THIS PAGE INTENTIONALLY LEFT BLANK
56
QUANTECH
Page 57
FORM QTC4-NM1 ISSUE DATE: 4/2/2018

SECTION 5 - TECHNICAL DATA

The data shown in all the tables of this section, is ap­plicable to selected typical configurations. Other con­figurations are available through our configuration/ selection software.
Please contact your nearest Quantech Sales Represen­tative for the chiller configuration that best matches your specific needs.
5
QUANTECH
57
Page 58
SECTION 5 - TECHNICAL DATA
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

TABLE 5 - PHYSICAL DATA - MICROCHANNEL COIL

UNIT FRAME 150 165 175 185 185 185 175 210 210 210 UNIT FRAME 230 240 240 260 270 270 270 270 290 300 CONDENSER CODE S H P S H P C S H P CONDENSER CODE S H P S C S H P H S EVAPORATOR CODE B B C A A B C A C C EVAPORATOR CODE B C C B D D E E E C GENERAL UNIT DATA GENERAL UNIT DATA
Number of Independent Refrigerant Circuits
Refrigerant Charge, R-134a, R-513A, Ckt.-1/ Ckt.-2, lbs (kg)
Oil Charge, Ckt.-1/Ckt.-2, gal (liters)
175/175
(79/79)
2.1/2.0 (8.0/
7.7)
190/190
(86/86)
2.2/2.2 (8.5/
8.5)
225/225
(102/102)
2.5/2.5 (9.3/
9.3)
175/155
(79/70)
2.4/2.0 (9.2/
7.7)
190/170
(86/77)
2.6/2.1
Minimum Load (%) 10% Minimum Load (%) 10% Chassis Dimensions -
Length, inches (mm) Chassis Dimensions -
Width, inches (mm)
Chassis Dimensions ­Height, inches (mm)
203.3
(5163)
88.3
(2242)
94.6
(2403)
247.2
(6280)
88.3
(2242)
94.6
(2403)
291.2
(7397)
88.3
(2242)
94.6
(2403)
247
(6274)
88.3
(2242)
94.6
(2403)
291.2
(7397)
(2242)
(2403)
COMPRESSORS, SEMI-HERMETIC SCREW COMPRESSORS, SEMI-HERMETIC SCREW
Qty per Chiller 2 Qty per Chiller 2
CONDENSER FANS CONDENSER FANS
Number Ckt-1/Ckt-2 4/4 5/5 6/6 6/4 7/5 8/6 4/4 6/6 6/6 7/7 Number Ckt-1/Ckt-2 7/5 8/6 8/8 7/7 6/6 7/7 7/7 8/8 9/7 9/7 Air on Condenser
(Min/Max), °F (°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM
Water Volume, gal (liters)
58
(220)
58
(220)
71 (269)
2
48
(182)
Leaving Water Temperature (Min/Max), °F (°C) 3
Maximum Water Side Pressure, psig (barg)
Maximum Refrigerant Side Pressure, psig (barg)
Evap Drain Connection, inches (mm)
Minimum Chilled Water Flow Rate, gpm (l/sec)
Maximum Chilled Water Flow Rate, gpm (l/sec)
Inlet and Outlet Water Connections, in
250
(15.8)
950
(59.9)
6 6 6 6 6 6 6 6
250
(15.8)
950
(59.9)
300
(18.9)
1150
(72.6)
200
(12.6)
750
(47.3)
(12.6)
(47.3)
(9.7/
8.0)
88.3
94.6
(-17.8/55)
48
(182)
(4.4/15.6)
200
750
2
220/195
(100/88)
2.7/2.2 (10.4/
335.2
(8514)
(2242)
(2403)
0/131
58 (220)
40/60
150
(10.3)
235
(16.2)
3/4
(15.8)
(59.9)
8.5)
88.3
94.6
250
950
205/205
(93/93)
2.6/2.6 (10.0/
10.0)
226
(5741)
88.3
(2242)
94.6
(2403)
71
(269)
300
(18.9)
1150
(72.6)
175/175
(79/79)
2.5/2.5 (9.3/
9.3)
291.2
(7397)
88.3
(2242)
94.6
(2403)
48
(182)
200
(12.6)
750
(47.3)
225/225
(102/102)
2.8/2.8 (10.5/
10.5)
291.2
(7397)
88.3
(2242)
94.6
(2403)
240/240
(109/109)
2.9/2.9 (10.8/
10.8)
335.2
(8514)
88.3
(2242)
94.6
(2403)
71 (269) 71(269) Water Volume, gal (liters) 58(220) 71(269) 71(269) 58(220) 82(310) 82(310) 113(428) 113(428) 113(428) 71(269)
300
(18.9)
1150
(72.6)
300
(18.9)
1150
(72.6)
6 6
NOTES:
1. Shipping and operating weights shown are for base unit; selected options may add weight to unit. Contact your nearest Quantech Sales Represenative for weight data.
2. For leaving liquid temperature below 40°F(4.4°C) or above 60°F (15.6°C). Contact your nearest Quantech Sales Representative for application requirements.
58
QUANTECH
Page 59
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 5 - PHYSICAL DATA - MICROCHANNEL COIL (CONT'D)
SECTION 5 - TECHNICAL DATA
Number of Independent Refrigerant Circuits
Refrigerant Charge, R-134a, R-513A, Ckt.-1/ Ckt.-2, lbs (kg)
Oil Charge, Ckt.-1/Ckt.-2, gal (liters)
Chassis Dimensions ­Length, inches (mm)
Chassis Dimensions ­Width, inches (mm)
Chassis Dimensions ­Height, inches (mm)
210/190
(95/86)
2.7/2.6 (10.1/
9.7)
291.2
(7397)
88.3
(2242)
94.6
(2403)
250/225
(113/102)
2.9/2.8 (11.1/
10.5)
335.2
(8514)
88.3
(2242)
94.6
(2403)
250/250
(113/113)
2.9/2.9 (11.1/
11.1)
379.1
(9631)
88.3
(2242)
94.6
(2403)
210/210
(95/95)
2.7/2.7
Air on Condenser (Min/Max), °F (°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM
Leaving Water Temperature (Min/Max), °F (°C) 3
Maximum Water Side Pressure, psig (barg)
Maximum Refrigerant Side Pressure, psig (barg)
Evap Drain Connection, inches (mm)
Minimum Chilled Water Flow Rate, gpm (l/sec)
Maximum Chilled Water Flow Rate, gpm (l/sec)
Inlet and Outlet Water Connections, in
250
(15.8)
950
(59.9)
6 6 6 6 6 6 8 8 8 6
300
(18.9)
1150
(72.6)
300
(18.9)
1150
(72.6)
(10.1/
10.1)
335.2
(8514)
88.3
(2242)
94.6
(2403)
2
250
(15.8)
950
(59.9)
250/250
(114/114)
3.0/3.0 (11.4/
11.4)
291.2
(7397)
88.3
(2242)
94.6
(2403)
(-17.8/55)
(4.4/15.6)
300
(18.9)
1150
(72.6)
2
265/265
(120/120)
3.0/3.0 (11.4/
11.4)
335.2
(8514)
88.3
(2242)
94.6
(2403)
0/131
40/60
150
(10.3)
235
(16.2)
3/4
300
(18.9)
1150
(72.6)
265/265
(120/120)
3.0/3.0 (11.4/
11.4)
335.2
(8514)
88.3
(2242)
94.6
(2403)
400
(25.2)
1500
(94.7)
270/270
(122/122)
3.1/3.1 (11.6/
11.6)
379.2
(9631)
88.3
(2242)
94.6
(2403)
400
(25.2)
1500
(94.7)
310/265
(141/120)
3.8/3.1 (14.4/
11.7)
379.2
(9631)
88.3
(2242)
94.6
(2403)
400
(25.2)
1500
(94.7)
290/245
(132/111)
3.7/3.0 (14.0/
11.4)
379.2
(9631)
88.3
(2242)
94.6
(2403)
300
(18.9)
1150
(72.6)
5
NOTES:
1. Shipping and operating weights shown are for base unit; selected options may add weight to unit. Contact your nearest Quantech Sales Representative for weight data.
2. For leaving liquid temperature below 40°F(4.4°C) or above 60°F (15.6°C), Contact your nearest Quantech Sales Representative for application requirements.
QUANTECH
59
Page 60
SECTION 5 - TECHNICAL DATA
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
TABLE 5 - PHYSICAL DATA - MICROCHANNEL COIL (CONT'D)
UNIT FRAME 300 310 315 320 330 340 340 370 370 UNIT FRAME 370 400 405 410 410 450 490 460 470 480 500
CONDENSER CODE H P P S S S H P S CONDENSER CODE H P S H P S H S C C S
EVAPORATOR CODE C E E E C E E J F EVAPORATOR CODE J J H H J G J G K J J
GENERAL UNIT DATA GENERAL UNIT DATA
Number of Independent Refrigerant Circuits
Refrigerant Charge, R-134a, R-513A, Ckt.-1/Ckt.-2, lbs (kg)
Oil Charge, Ckt.-1/Ckt.-2, gal (liters)
Minimum Load (%) 10% Minimum Load (%) 10%
Chassis Dimensions ­Length, inches (mm)
Chassis Dimensions ­Width, inches (mm)
Chassis Dimensions ­Height, inches (mm)
COMPRESSORS, SEMI-HERMETIC SCREW COMPRESSORS, SEMI-HERMETIC SCREW
Qty per Chiller 2 Qty per Chiller 2
CONDENSER FANS CONDENSER FANS
Number Ckt-1/Ckt-2 10/8 10/8 8/8 8/8 9/9 9/9 10/10 14/8 13/7 Number Ckt-1/Ckt-2 13/7 14/10 12/8 14/10 14/12 12/12 13/13 13/13 10/10 10/10 13/13
Air on Condenser (Min/Max), °F (°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM
Water Volume, gal (liters) 71 (269) 113 (428) 113 (428) 113 (428) 71 (269) 113 (428) 113 (428) 147 (556) 96 (363) Water Volume, gal (liters) 147(556) 147(556) 130(492) 130(492) 147(556) 96(363) 147(556) 96(363) 130 (492) 147(556) 147(556)
Leaving Water Temperature (Min/Max), °F
2
(°C)
Maximum Water Side Pressure, psig (barg)
Maximum Refrigerant Side Pressure, psig (barg)
Evap Drain Connection, inches (mm)
Minimum Chilled Water Flow Rate, gpm (l/sec)
Maximum Chilled Water Flow Rate, gpm (l/sec)
Inlet and Outlet Water Connections, in
295/250
(134/114)
3.7/3.0
(14.0/ 11.4)
423.1
(10748)
88.3 (2242) 88.3 (2242) 88.3 (2242) 88.3 (2242) 88.3 (2242) 88.3 (2242) 88.3 (2242) 88.3 (2243) 88.3 (2243)
94.6 (2403) 94.6 (2403) 94.6 (2403) 94.6 (2403) 94.6 (2403) 94.6 (2403) 94.6 (2403) 94.7 (2405) 94.7 (2405)
300
(18.9)
1150
(72.6)
6
315/275
(143/125)
3.9/3.2
(14.8/ 12.1)
423.1
(10748)
400
(25.2)
1500
(94.7)
8 8 8
315/295
(143/134)
3.9/3.3
(14.8/ 12.5)
467.1
(11865)
2
400
(25.2)
1500
(94.7)
295/295
(134/134)
3.7/3.7
(14.0/ 14.0)
379.2
(9631)
400
(25.2)
1500
(94.7)
2
290/290
(132/132)
3.7/3.7
(14.0/ 14.0)
423.1
(10748)
0/125
(-17.8/51.7)
40/60
(4.4/15.6)
150
(10.3)
235
(16.2)
3/4
300
(18.9)
1150
(72.6)
6
310/310
(141/141)
3.8/3.8
(14.4/ 14.4)
423.1
(10748)
400
(25.2)
1500
(94.7)
8 8 8 8
315/315
(143/143)
3.9/3.9
(14.8/ 14.8)
467.1
(11865)
400
(25.2)
1500
(94.7)
475/320
(216/145)
4.1/4.0
(15.5/ 15.1)
511
(12979)
550
(34.1)
1880
(118.1)
420/245
(191/111)
4.0/2.9
(15.1/ 11.0)
467.1
(11864)
460
(29.0)
1540
(97.0)
NOTES:
1. Shipping and operating weights shown are for base unit; selected options may add weight to unit. Contact your nearest Quantech Sales Representative for weight data.
2. For leaving liquid temperature below 40°F(4.4°C) or above 60°F (15.6°C). Contact your nearest Quantech Sales Representative for application requirements.
60
QUANTECH
Page 61
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 5 - PHYSICAL DATA - MICROCHANNEL COIL (CONT'D)
SECTION 5 - TECHNICAL DATA
Number of Independent Refrigerant Circuits
Refrigerant Charge, R-134a, R-513A, Ckt.-1/Ckt.-2, lbs (kg)
Oil Charge, Ckt.-1/Ckt.-2, gal (liters)
Chassis Dimensions - Length, inches (mm)
Chassis Dimensions - Width, inches (mm)
Chassis Dimensions - Height, inches (mm)
Air on Condenser (Min/Max), °F (°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM
Leaving Water Temperature (Min/Max), °F
2
(°C)
Maximum Water Side Pressure, psig (barg)
Maximum Refrigerant Side Pressure, psig (barg)
Evap Drain Connection, inches (mm)
Minimum Chilled Water Flow Rate, gpm (l/sec)
Maximum Chilled Water Flow Rate, gpm (l/sec)
Inlet and Outlet Water Connections, in
470/310
(213/141)
4.1/3.8 (15.5/
14.4)
467.1
(11864)
(2243)
(2405)
(34.1)
1880
(118.1)
475/360
(216/163)
4.1/4.1 (15.5/
15.5)
555.3
(14104)
88.3 (2243)
94.7 (2405)
550
(34.1)
(118.1)
8 8 8 8 8 8 8 8 8 8 8
88.3
94.7
550
1880
460/345
(209/156)
4.0/4.0 (15.1/
15.1)
467.1
(11864)
88.3
(2243)
94.7
(2405)
520
(33.0)
1700
(107.0)
480/365
(218/166)
4.1/4.1 (15.5/
15.5)
555.3
(14104)
88.3
(2243)
94.7
(2405)
2
520
(33.0)
1700
(107.0)
475/385
(215/175)
4.1/4.1 (15.5/
15.5)
599.3
(15222)
88.3
(2243)
94.7
(2405)
550
(34.1)
1880
(118.1)
2
370/370
(168/168)
4.0/4.0 (15.1/
15.1)
555.3
(14104)
88.3
(2243)
94.7
(2405)
0/125
40/60
(4.4/15.6)
150
(10.3)
235
(16.2)
3/4
460
(29.0)
1540
(97.0)
445/445
(202/202)
4.2/4.2 (15.9/
15.9)
599.3
(15222)
88.3
(2243)
94.7
(2405)
550
(34.1)
1880
(118.1)
385/385
(175/175)
4.0/4.0 (15.1/
15.1)
599.3
(15222)
88.4
(2244)
94.7
(2405)
460
(29.0)
1540
(97.0)
390/390
(179/179)
4.0/4.0 (15.1/
15.1)
467.1
(11864)
88.3
(2242)
94.6
(2403)
470 (30)
1870
(118)
405/405
(184/184)
4.0/4.0 (15.1/
15.1)
467.1
(11865)
88.3
(2243)
94.7
(2405)
550
(34.1)
1880
(118.1)
445/445
(202/202)
4.2/4.2 (15.9/
15.9)
599.3
(15222)
88.3
(2243)
94.7
(2405)
550
(34.1)
1880
(118.1)
5
NOTES:
1. Shipping and operating weights shown are for base unit; selected options may add weight to unit. Contact your nearest Quantech Sales Representative for weight data.
2. For leaving liquid temperature below 40°F(4.4°C) or above 60°F (15.6°C). Contact your nearest Quantech Sales Representative for application requirements.
QUANTECH
61
Page 62
SECTION 5 - TECHNICAL DATA
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

TABLE 6 - PHYSICAL DATA - ROUND TUBE COIL

UNIT FRAME 150 185 175 210 230 260 270 270 300 CONDENSER CODE S S C S S S C S S EVAPORATOR CODE B A C A B B D D C GENERAL UNIT DATA
Number of Independent Refrigerant Circuits
Refrigerant Charge, R-134a, R-513A, Ckt.-1/Ckt.-2, lbs (kg)
Oil Charge, Ckt.-1/Ckt.-2, gal (liters)
Minimum Load (%) 10%
Chassis Dimensions - Length, inches (mm)
Chassis Dimensions - Width, inches (mm)
Chassis Dimensions - Height, inches (mm)
COMPRESSORS, SEMI-HERMETIC SCREW
Qty per Chiller 2
CONDENSER FANS
Number Ckt-1/Ckt-2 4/4 6/4 4/4 6/6 7/5 7/7 6/6 7/7 9/7
Air on Condenser (Min/Max), °F (°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM
Water Volume, gal (liters) 58 (220) 48 (182) 71 (269) 48 (182) 58 (220) 58 (220) 82 (310) 82 (310) 71 (269)
Leaving Water Temperature (Min/Max), °F (°C)
Maximum Water Side Pressure, psig (barg)
Maximum Refrigerant Side Pressure, psig (barg)
Evap Drain Connection, inches (mm)
Minimum Chilled Water Flow Rate, gpm (l/sec)
Maximum Chilled Water Flow Rate, gpm (l/sec)
Inlet and Outlet Water Connections, in
2
211/211
(96/96)
2.1/2.0
(8.0/7.7)
203.3
(5163)
88.3
(2242)
94.6
(2403)
250
(15.8)
950
(59.9)
229/191 (104/87)
2.4/2.0
(9.2/7.7)
247
(6274)
88.3
(2242)
94.6
(2403)
200
(12.6)
750
(47.3)
6 6 6 6 6 6 6 6 6
241/241
(109/109)
2.6/2.6
(9.9/9.9)
226
(5740)
88.3
(2242)
94.6
(2403)
300
(18.9)
1150
(72.6)
229/229
(104/104)
2.5/2.5
(9.5/9.5)
291.2
(7397)
88.3
(2242)
94.6
(2403)
200
(12.6)
750
(47.3)
2
273/235
(124/107)
2.7/2.6
(10.3/9.9)
291.2
(7397)
88.3
(2242)
94.6
(2403)
0/125
(-17.8/51.7)
40/60
(4.4/15.6)
150
(10.3)
235
(16.2)
3/4
250
(15.8)
950
(59.9)
273/273
(124/124)
2.7/2.7
(10.3/10.3)
335.2
(8514)
88.3
(2242)
94.6
(2403)
250
(15.8)
950
(59.9)
304/304
(138/138)
3.0/3.0
(11.4/11.4)
291.2
(7397)
88.3
(2242)
94.6
(2403)
300
(18.9)
1150
(72.6)
328/328
(149/149)
3.0/3.0
(11.4/11.4)
335.2
(8514)
88.3
(2242)
94.6
(2403)
300
(18.9)
1150
(72.6)
371/308
(168/140)
3.7/3.0
(14.0/11.4)
(9631)
(2242)
(2403)
379.2
88.3
94.6
300
(18.9)
1150
(72.6)
NOTES:
1. Shipping and operating weights shown are for base unit; selected options may add weight to unit. Contact your nearest Quantech Sales Representative for weight data.
2. For leaving liquid temperature below 40°F(4.4°C) or above 60°F (15.6°C). Contact your nearest Quantech Sales Representative for applica­tion requirements.
62
QUANTECH
Page 63
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 5 - TECHNICAL DATA
TABLE 6 - PHYSICAL DATA - ROUND TUBE COIL (CONT'D)
UNIT FRAME 320 330 340 370 405 450 460 470 480 500 CONDENSER CODE S S S S S S S C C S EVAPORATOR CODE E C E F H G G K J J GENERAL UNIT DATA
Number of Independent Refrigerant Circuits
Refrigerant Charge, R-134a, R-513A, Ckt.-1/Ckt.-2, lbs (kg)
Oil Charge, Ckt.-1/Ckt.-2, gal (liters)
Minimum Load (%) 10%
Chassis Dimensions - Length, inches (mm)
Chassis Dimensions - Width, inches (mm)
Chassis Dimensions - Height, inches (mm)
COMPRESSORS, SEMI-HERMETIC SCREW
Qty per Chiller 2
CONDENSER FANS
Number Ckt-1/Ckt-2 8/8 9/9 9/9 13/7 12/8 12/12 13/13 10/10 10/10 13/13
Air on Condenser (Min/Max), °F (°C)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM
Water Volume, gal (liters) 113 (428) 71 (269) 113 (428) 96 (363) 130 (492) 96 (363) 96 (363) 130 (492) 147 (556) 147 (556)
Leaving Water Temperature (Min/Max), °F (°C)
Maximum Water Side Pressure, psig (barg)
Maximum Refrigerant Side Pressure, psig (barg)
Evap Drain Connection, inches (mm)
Minimum Chilled Water Flow Rate, gpm (l/sec)
Maximum Chilled Water Flow Rate, gpm (l/sec)
Inlet and Outlet Water Connections, in
2
367/367
(166/166)
3.7/3.7 (14.0/
14.0)
379.2
(9631)
88.3
(2242)
94.6
(2403)
400
(25.2)
1500
(94.7)
371/371
(168/168)
3.7/3.7 (14.0/
14.0)
423.1
(10748)
88.3
(2242)
94.6
(2403)
(18.9)
1150
(72.6)
8 6 8 8 8 8 8 8 8 8
300
391/391
(177/177)
3.8/3.8 (14.4/
14.4)
423.1
(10748)
88.3
(2242)
94.6
(2403)
400
(25.2)
1500
(94.7)
537/308
(244/140)
4.0/2.9 (15.1/
11.0)
467.1
(11864)
88.3
(2243)
94.7
(2405)
460
(29.0)
1540
(97.0)
568/417
(258/189)
(11864)
4.0/4.0 (15.1/
15.1)
467.1
88.3
(2243)
94.7
(2405)
0/125
(-17.8/51.7)
40/60
(4.4/15.6)
(10.3)
(16.2)
520
(33.0)
1700
(107.0)
2
478/478
(217/217)
4.0/4.0 (15.1/
15.1)
555.3
(14104)
(2243)
(2405)
150
235
3/4
(29.0)
1540
(97.0)
88.3
94.7
460
502/502
(228/228)
4.0/4.0 (15.1/
15.1)
599.3
(15222)
88.4
(2244)
94.7
(2405)
460
(29.0)
1540
(97.0)
480/480
(218/218)
4.0/4.0 (15.1/
15.1)
467.1
(11864)
88.3
(2242)
94.6
(2403)
470 (30)
1870 (118)
495/495
(224/224)
4.0/4.0 (15.1/
15.1)
467.1
(11864)
88.4
(2244)
94.7
(2405)
550
(34.1)
1880
(118.1)
562/562
(255/255)
4.2/4.2
(15222)
(118.1)
(15.9/
15.9)
599.3
88.3
(2243)
94.7
(2405)
550
(34.1)
1880
5
NOTES:
1. Shipping and operating weights shown are for base unit; selected options may add weight to unit. Contact your nearest Quantech Sales Representative for weight data.
2. For leaving liquid temperature below 40°F(4.4°C) or above 60°F (15.6°C). Contact your nearest Quantech Sales Representative for applica­tion requirements.
QUANTECH
63
Page 64
SECTION 5 - TECHNICAL DATA

TABLE 7 - OPTIONAL ONE-PASS EVAPORATOR

ALL DIMENSIONS - INCHES (MM)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
QTC4
MODEL
150 S
165 H
175 P
185 S
185 H
185 P
175 C
210 S
210 H
210 P
A,B C D
COND.
20.8
(528)
20.8
(528)
20.8
(528)
19.8
(503)
19.8
(503)
21
(533)
20.8
(528)
19.8
(503)
20.8
(528)
21
(533)
6.8
(173)
29.2
(742)
34.9
(886)
17.7
(450)
61.5
(1562)
117.3
(2979)
1.7
(43)
61.7
(1567)
34.9
(886)
78.9
(2044)
34.5
(876)
56.1
(1425)
70
(1778)
56.8
(1443)
56.7
(1425)
56.1
(1425)
38.1
(968)
56.8
(1443)
70
(1778)
70
(1778)
E
NOZZLE
SIZE
8
8
8
6
6
8
8
6
8
8
WATER
VOLUME.
GALLONS
(LITERS)
58
(220)
58
(220)
71
(269)
48
(182)
48
(182)
56
(220)
71
(269)
48
(182)
71
(269)
71
(269)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
500 (32)
500 (32)
590 (37)
400 (25)
400 (25)
500 (32)
590 (37)
400 (25)
590 (37)
590 (37)
MAXIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
1970
(124)
1970
(124)
2190
(138)
1230
(77)
1230
(77)
1970
(124)
2190
(138)
1230
(77)
2190
(138)
2190
(138)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted. Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
64
QUANTECH
Page 65
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 7 - OPTIONAL ONE-PASS EVAPORATOR (CONT'D)
ALL DIMENSIONS - INCHES (MM)
SECTION 5 - TECHNICAL DATA
5
QTC4
MODEL
230 S
240 H
240 P
260 S
270 C
270 S
270 H
270 P
290 H
300 S
A,B C D
COND.
20.8
(528)
21
(533)
21
(533)
21
(533)
21
(533)
21
(533)
22.5
(572)
22.5
(572)
22.5
(572)
21
(533)
73.2
(1859)
92.9
(2360)
122.9
(3122)
117.1
(2974)
16.8
(427)
42.9
(1090)
44.7
(1135)
88.3
(2243)
88.6
(2250)
122.9
(3122)
56.1
(1425)
56.1
(1425)
70
(1778)
56.1
(1425)
51.9
(1318)
70
(1778)
71.8
(1824)
71.8
(1824)
71.8
(1824)
70
(1778)
E
NOZZLE
SIZE
8
8
8
8
8
8
10
10
10
8
WATER
VOLUME.
GALLONS
(LITERS)
58
(220)
71
(269)
71
(269)
58
(220)
82
(310)
82
(310)
113
(428)
113
(428)
113
(428)
71
(269)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
500 (32)
590 (37)
590 (37)
500 (32)
590 (37)
590 (37)
810 (51)
810 (51)
810 (51)
590 (37)
MAXIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
1970
(124)
2190 (138)
2190 (138)
1970 (124)
2190 (138)
2190 (138)
3200 (202)
3200 (202)
3200 (202)
2190 (138)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted. Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
QUANTECH
65
Page 66
SECTION 5 - TECHNICAL DATA
TABLE 7 - OPTIONAL ONE-PASS EVAPORATOR (CONT'D)
ALL DIMENSIONS - INCHES (MM)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
QTC4
MODEL
300 H
310 P
315 P
320 S
330 S
340 S
340 H
370 P
370 S
370 H
A,B C D
COND.
21
(533)
22.5
(572)
22.5
(572)
22.5
(572)
21
(533)
22.5
(572)
22.5
(572)
23.3
(592)
22.3
(566)
23.3
(592)
166.9
(4239)
132.2
(3358)
176.6
(4486)
88.6
(2250)
166.9
(4239)
132.6
(3368)
176.21 (4476)
208.6
(5298)
180.9
(4595)
164.3
(4173)
70
(1778)
71.8
(1824)
71.8
(1824)
71.8
(1824)
70
(1778)
71.8
(1824)
71.8
(1824)
83.5
(2121)
112.2
(2850)
83.4
(2118)
E
NOZZLE
SIZE
8
10
10
10
8
10
10
10
10
10
WATER
VOLUME.
GALLONS
(LITERS)
71
(269)
113
(428)
113
(428)
113
(428)
71
(269)
113
(428)
113
(428)
147
(556)
96
(363)
147
(556)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
590
(37)
810
(51)
810
(51)
810
(51)
590
(37)
810
(51)
810
(51)
1090
(69)
840
(53)
1090
(69)
MAXIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
2190 (138)
3200 (202)
3200 (202)
3200 (202)
2190 (138)
3200 (202)
3200 (202)
3420 (215)
3320 (209)
3420 (215)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted. Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
66
QUANTECH
Page 67
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 7 - OPTIONAL ONE-PASS EVAPORATOR (CONT'D)
ALL DIMENSIONS - INCHES (MM)
SECTION 5 - TECHNICAL DATA
5
QTC4
MODEL
400 P
405 S
410 H
410 P
450 S
490 H
460 S
470 C
480 C
500 S
A,B C D
COND.
23.3
(592)
22.5
(572)
22.5
(572)
23.3
(592)
22.3
(566)
23.3
(592)
22.3
(566)
22.5
(571)
23.3
(592)
23.3
(592)
252.5
(6414)
164.6
(4181)
252.6
(6416)
296.5
(7531)
287.1
(7292)
308.4
(7833)
331.2
(8412)
176.5
(4482)
176.2
(4475)
308.4
(7833)
83.5
(2121)
83.8
(2129)
83.8
(2129)
83.5
(2121)
94.2
(2393)
71.5
(1816)
94.2
(2393)
71.7
(1820)
71.5
(1816)
71.5
(1816)
E
NOZZLE
SIZE
10
10
10
10
10
10
10
10
10
10
WATER
VOLUME.
GALLONS
(LITERS)
147
(556)
130
(492)
130
(492)
147
(556)
96
(363)
147
(556)
96
(363)
130
(492)
147
(556)
147
(556)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
1090
(69)
940 (59)
940 (59)
1090
(69)
840 (53)
1090
(69)
840 (53)
940 (59)
1090
(69)
1090
(69)
MAXIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
3420 (215)
3420 (215)
3420 (215)
3420 (215)
3320 (209)
3420 (215)
3320 (209)
3420 (215)
3420 (215)
3420 (215)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted. Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
QUANTECH
67
Page 68
SECTION 5 - TECHNICAL DATA

TABLE 8 - STANDARD TWO-PASS, REAR INLET/OUTLET EVAPORATOR

ALL DIMENSIONS - INCHES (MM)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
QTC4
MODEL
150 S
165 H
175 P
185 S
185 H
185 P
175 C
210 S
210 H
210 P
A B C DE NOZZLE
COND.
15.1
(384)
15.1
(384)
15.1
(384)
14.1
(358)
14.1
(358)
15.3
(389)
15.1
(384)
14.1
(358)
15.1
(384)
15.3
(389)
11.4
(290)
11.4
(290)
11.4
(290)
11.4
(290)
11.4
(290)
11.4
(290)
11.4
(290)
11.4
(290)
11.4
(290)
11.4
(290)
6.8
(173)
29.4
(747)
34.9
(886)
17.7
(450)
61.5
(1562)
117.3
(2979)
1.7
(43)
61.7
(1567)
29.9
(759)
78.9
(2004)
– 6
– 6
– 6
– 6
– 6
– 6
– 6
– 6
– 6
– 6
SIZE
F G
34.5
(876)
56.1
(1425)
70
(1778)
56.8
(1443)
56.7
(1440)
56.1
(1425)
38.1
(968)
58.8
(1494)
70
(1778)
70.3
(1786)
–
–
–
–
–
–
–
–
–
–
WATER
VOLUME
GALLONS
(LITERS)
58
(220)
58
(220)
71
(269)
48
(182)
48
(182)
58
(220)
71
(269)
48
(182)
71
(269)
71
(269)
MINIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
250 (16)
250 (16)
300 (19)
200 (13)
200 (13)
250 (16)
300 (19)
200 (13)
300 (19)
300 (19)
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
980
(62)
980
(62)
1170
(74)
790
(50)
790
(50)
980
(62)
1170
(74)
790
(50)
1170
(74)
1170
(74)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted. Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
68
QUANTECH
Page 69
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 8 - STANDARD TWO-PASS, REAR INLET/OUTLET EVAPORATOR (CONT'D)
ALL DIMENSIONS - INCHES (MM)
SECTION 5 - TECHNICAL DATA
5
QTC4
MODEL
230 S
240 H
240 P
260 S
270 C
270 S
270 H
270 P
290 H
300 S
A B C D
COND.
15.1
(384)
15.3
(389)
15.3
(389)
15.3
(389)
15.3
(388)
15.3
(389)
15.5
(394)
15
(381)
15.5
(394)
15.3
(389)
11.4
(290)
11.4
(290)
11.4
(290)
11.4
(290)
11.4
(290)
11.4
(290)
14
(356)
14
(356)
14
(356)
11.4
(290)
73.3
(1862)
29.9
(759)
122.9
(3122)
117.3
(2979)
16.8
(427)
42.9
(1090)
44.3
(1125)
88.3
(2243)
88.3
(2243)
122.9
(3122)
NOZZLE
SIZE
– 6
– 6
– 6
– 6
– 6
– 6
– 8
– 8
– 8
– 6
E
F G
56.1
(1425)
56.1
(1425)
70
(1778)
56.1
(1425)
51.9
(1318)
70
(1778)
71.8
(1824)
71.8
(1824)
71.8
(1824)
70
(1778)
–
–
–
–
–
–
–
–
–
–
WATER
VOLUME
GALLONS
(LITERS)
58
(220)
71
(269)
71
(269)
58
(220)
82
(310)
82
(310)
113
(428)
113
(428)
113
(428)
71
(269)
MINIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
250 (16) 980 (62)
300 (19) 1170 (74)
300 (19) 1170 (74)
250 (16) 980 (62)
300 (19) 1170 (74)
300 (19) 1170 (74)
410 (26) 1600 (101)
410 (26) 1600 (101)
410 (26) 1600 (101)
300 (19) 1170 (74)
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted.
Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
QUANTECH
69
Page 70
SECTION 5 - TECHNICAL DATA
TABLE 8 - STANDARD TWO-PASS, REAR INLET/OUTLET EVAPORATOR (CONT'D)
ALL DIMENSIONS - INCHES (MM)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
QTC4
MODEL
300 H
310 P
315 P
320 S
330 S
340 S
340 H
370 P
370 S
370 H
A B C DE NOZZLE
COND.
15.3
(389)
15.5
(394)
15.5
(394)
15.5
(394)
15.3
(389)
15.5
(394)
15.5
(394)
16.3
(414)
15.8
(401)
16.3
(414)
11.4
(290)
14
(356)
14
(356)
14
(356)
11.4
(290)
14
(356)
14
(356)
14
(356)
13
(330)
14
(356)
166.8
(4237)
132.2
(3358)
176.21 (4476)
88.6
(2250)
166.9
(4239)
132.2
(3358)
176.2
(4475)
208.5
(5296)
180.9
(4595)
164.4
(4176)
– 6
– 8
– 8
– 8
– 6
– 8
– 8
– 8
176.4
(4480)
– 8
SIZE
8
F G
70
(1778)
83.4
(2118)
83.4
(2118)
83.4
(2118)
83.4
(2118)
83.4
(2118)
83.4
(2118)
83.4
(2118)
112.2
(2850)
83.4
(2118)
–
–
–
–
–
–
–
–
107.7
(2735)
–
WATER
VOLUME
GALLONS
(LITERS)
71
(269)
113
(428)
113
(428)
113
(428)
71
(269)
113
(428)
113
(428)
147
(556)
96
(363)
147
(556)
MINIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
300 (19) 1170 (74)
410 (26) 1600 (101)
410 (26) 1600 (101)
410 (26) 1600 (101)
300 (19) 1170 (74)
410 (26) 1600 (101)
410 (26) 1600 (101)
550 (35) 2160 (136)
420 (26) 1660 (105)
550 (35) 2160 (136)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted. Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
70
QUANTECH
Page 71
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 8 - STANDARD TWO-PASS, REAR INLET/OUTLET EVAPORATOR (CONT'D)
ALL DIMENSIONS - INCHES (MM)
SECTION 5 - TECHNICAL DATA
5
QTC4
MODEL
400 P
405 S
410 H
410 P
450 S
490 H
460 S
470 C
480 C
500 S
A B C D
COND.
16.3
(414)
15.5
(394)
15.5
(394)
16.3
(414)
15.8
(401)
16.3
(414)
15.8
(401)
15.5
(394)
16.3
(414)
16.3
(414)
14
(356)
14
(356)
14
(356)
14
(356)
13
(330)
14
(356)
13
(330)
14
(355)
14
(356)
14
(356)
252.5
(6414)
164.6
(4181)
252.6
(6416)
296.5
(7531)
287.1
(7292)
308.4
(7833)
331.2
(8412)
176.5
(4482)
176.2
(4475)
308.4
(7833)
– 8
– 8
– 8
– 8
282.5
(7177)
– 8
326.6
(8296)
– 8
– 8
– 8
E
NOZZLE
SIZE
8
8
F G
83.5
(2121)
83.8
(2129)
83.8
(2129)
83.5
(2121)
94.2
(2393)
71.5
(1816)
94.2
(2393)
71.7
(1820)
71.5
(1816)
71.5
(1816)
–
–
–
–
89.7
(2278)
–
89.7
(2278)
–
–
–
WATER
VOLUME
GALLONS
(LITERS)
147
(556)
130
(492)
130
(492)
147
(556)
96
(363)
147
(556)
96
(363)
130
(492)
147
(556)
147
(556)
MINIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
550 (35) 2160 (136)
470 (30) 1870 (118)
470 (30) 1870 (118)
550 (35) 2160 (136)
420 (26) 1660 (105)
550 (35) 2160 (136)
420 (26) 1660 (105)
470 (30) 1870 (118)
550 (35) 2160 (136)
550 (35) 2160 (136)
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted.
Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
QUANTECH
71
Page 72
SECTION 5 - TECHNICAL DATA

TABLE 9 - OPTIONAL THREE-PASS REAR INLET/FRONT OUTLET EVAPORATOR

ALL DIMENSIONS - INCHES (MM)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
QTC4
MODEL
150 S
165 H
175 P
185 S
185 H
185 P
175 C
210 S
210 H
210 P
COND.
A B C D
15.1
(384)
15.1
(384)
15.1
(384)
25.5
(648)
14.1
(358)
15.3
(389)
15.1
(384)
14.1
(358)
15.1
(384)
15.3
(389)
26.5
(673)
26.5
(673)
26.5
(673)
25.5
(648)
25.5
(648)
26.7
(678)
26.53 (674)
25.5
(648)
26.5
(673)
26.7
(678)
6.8
(173)
29.2
(742)
34.9
(886)
17.7
(450)
61.5
(1562)
117.3
(2979)
1.7
(43)
61.6
(1565)
34.9
(886)
78.9
(2004)
34.5
(876)
56.1
(1425)
70
(1778)
56.8
(1443)
56.7
(1440)
56.1
(1425)
38.1
(968)
58.8
(1494)
70
(1778)
70.3
(1786)
E
NOZZLE
SIZE
5
5
6
5
5
5
6
5
6
6
WATER
VOLUME
GALLONS
(LITERS)
58
(220)
58
(220)
71
(269)
48
(182)
48
(182)
58
(220)
71
(269)
48
(182)
71
(269)
71
(269)
MINIMUM
CHILLED
MAXIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
FLOW RATE
GPM (L/S)
170 (11) 650 (41)
170 (11) 650 (41)
200 (13) 780 (49)
130 (8) 520 (33)
130 (8) 520 (33)
170 (11) 650 (41)
200 (13) 780 (49)
130 (8) 520 (33)
200 (13) 780 (49)
200 (13) 780 (49)
WATER
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted.
Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
72
QUANTECH
Page 73
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 5 - TECHNICAL DATA
TABLE 9 - OPTIONAL THREE-PASS REAR INLET/FRONT OUTLET EVAPORATOR (CONT'D)
ALL DIMENSIONS - INCHES (MM)
QTC4
MODEL
230 S
240 H
240 P
260 S
270 C
270 S
270 H
270
290 H
300 S
COND.
P
A B C D
14.1
(358)
15.3
(389)
15.3
(389)
15.3
(389)
15.3
(388)
15.3
(389)
15.5
(394)
15.5
(394)
15.5
(394)
15.3
(389)
25.5
(648)
26.7
(678)
26.7
(678)
26.7
(678)
26.7
(678)
26.7
(678)
29.5
(749)
29.5
(749)
29.5
(749)
26.7
(678)
73.2
(1859)
29.9
(759)
122.9
(3122)
117.1
(2974)
16.8
(427)
42.9
(1090)
88.6
(2250)
88.3
(2243)
88.6
(2250)
122.9
(3122)
56.1
(1425)
56.1
(1425)
70
(1778)
56.1
(1425)
51.9
(1318)
70
(1778)
71.8
(1824)
71.8
(1824)
71.8
(1824)
70
(1778)
E
NOZZLE
SIZE
5
6
6
5
6
6
6
6
6
6
WATER
VOLUME
GALLONS
(LITERS)
58
(220)
71
(269)
71
(269)
58
(220)
82
(310)
82
(310)
113
(428)
113
(428)
113
(428)
71
(269)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
170 (11) 650 (41)
200 (13) 780 (49)
200 (13) 780 (49)
170 (11) 650 (41)
200 (13) 780 (49)
200 (13) 780 (49)
270 (17) 1060 (67)
270 (17) 1060 (67)
270 (17) 1060 (67)
200 (13) 780 (49)
5
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted.
Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
QUANTECH
73
Page 74
SECTION 5 - TECHNICAL DATA
TABLE 9 - OPTIONAL THREE-PASS REAR INLET/FRONT OUTLET EVAPORATOR (CONT'D)
ALL DIMENSIONS - INCHES (MM)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
QTC4
MODEL
300 H
310 P
315 P
320 S
330 S
340 S
340 H
370 P
370 S
370 H
COND.
A B C D
15.3
(389)
15
(381)
15
(381)
15.5
(394)
15.3
(389)
15.5
(394)
15.5
(394)
16.3
(414)
15.8
(401)
16.3
(414)
26.7
(678)
30.3
(770)
29.5
(749)
29.5
(749)
26.7
(678)
29.5
(749)
29.5
(749)
30.3
(770)
28.8
(732)
30.3
(770)
166.9
(4239)
132.2
(3358)
176.6
(4486)
88.6
(2250)
166.9
(4239)
132.6
(3368)
176.2
(4475)
208.6
(5298)
180.9
(4595)
164.3
(4173)
70
(1778)
71.8
(1824)
71.8
(1824)
71.8
(1824)
70
(1778)
71.8
(1824)
71.8
(1824)
83.5
(2121)
112.2
(2850)
83.4
(2118)
E
NOZZLE
SIZE
6
6
6
6
6
6
6
8
6
8
WATER
VOLUME
GALLONS
(LITERS)
71
(269)
113
(428)
113
(428)
113
(428)
71
(269)
113
(428)
113
(428)
147
(556)
94
(356)
147
(556)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
200 (13) 780 (49)
270 (17) 1060 (67)
270 (17) 1060 (67)
270 (17) 1060 (67)
200 (13) 780 (49)
270 (17) 1060 (67)
270 (17) 1060 (67)
370 (23) 1440 (91)
280 (18) 1100 (69)
370 (23) 1440 (91)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted. Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
74
QUANTECH
Page 75
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 5 - TECHNICAL DATA
TABLE 9 - OPTIONAL THREE-PASS REAR INLET/FRONT OUTLET EVAPORATOR (CONT'D)
ALL DIMENSIONS - INCHES (MM)
QTC4
MODEL
400 P
405 S
410 H
410 P
450 S
490 H
460 S
470 C
480 C
500 S
COND.
A B C D
16.3
(414)
15.5
(394)
15.5
(394)
16.3
(414)
15.8
(401)
16.3
(414)
15.8
(401)
15.5
(394)
16.3
(414)
16.3
(414)
30.3
(770)
29.5
(749)
29.5
(749)
30.3
(770)
28.8
(732)
30.3
(770)
28.8
(732)
29.5
(749)
30.3
(770)
30.3
(770)
252.5
(6414)
164.6
(4181)
252.6
(6416)
296.5
(7531)
287.1
(7292)
308.4
(7833)
331.2
(8412)
176.2
(4476)
176.2
(4475)
308.4
(7833)
83.5
(2121)
83.8
(2129)
83.8
(2129)
83.5
(2121)
94.2
(2393)
71.5
(1816)
94.2
(2393)
71.5
(1817)
71.5
(1816)
71.5
(1816)
E
NOZZLE
SIZE
8
6
6
8
6
8
6
6
8
8
WATER
VOLUME
GALLONS
(LITERS)
147
(556)
128
(485)
128
(485)
147
(556)
94
(356)
147
(556)
94
(356)
130
(492)
147
(556)
147
(556)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
370 (23) 1440 (91)
320 (20) 1230 (77)
320 (20) 1230 (77)
370 (23) 1440 (91)
280 (18) 1100 (69)
370 (23) 1440 (91)
280 (18) 1100 (69)
320 (20) 1230 (77)
370 (23) 1440 (91)
370 (23) 1440 (91)
5
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted.
Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.
QUANTECH
75
Page 76
SECTION 5 - TECHNICAL DATA
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
The data below is applicable to select configurations. Other configurations are available through our con­figuration/selection software.
94.6"
(2403 mm)
C
B
A" PIPE WATER OUTLET
120"
(305 mm)
VIEW A-A
A" PIPE WATER INLET
CONTROL ENTRY
3.0" (76 mm) WIDE X
11.5" (292 mm) HIGH
3.0"
(75 mm)
Please contact your nearest Quantech Sales Represen­tative for the chiller configuration that best matches your specific needs.
BB
LD16178
88.3" (2242 mm)
4.0"
(102 mm)
1.5"
(38 mm)
VIEW B-B
POWER ENTRY
10" (254 mm) WIDE X
13" (330 mm) HIGH
VSD / CONTROL PANEL

FIGURE 16 - QTC4 DIMENSIONS

60.0"
(1524 mm)
14.1"
(359 mm)
47.4"
(1204 mm)
76
QUANTECH
Page 77
FORM QTC4-NM1 ISSUE DATE: 03/07/2018
SECTION 5 - TECHNICAL DATA
THIS PAGE INTENTIONALLY LEFT BLANK
QUANTECH
77
Page 78
SECTION 5 - TECHNICAL DATA

TABLE 10 - ISOLATOR SELECTION AND MOUNTING LOCATIONS

QTC4 CONFIGURATION
MODEL COND EVAP
150 S B
165 H B
175 P C
185 S A
185 H A
185 P B
175 C C
210 S A
210 H C
210 P C
230 S B
DESCRIPTION 1 2 3 4 5 6 7 8
Isolator X-Dimension
10
(263)
73
(1852)
(3662)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
77
(1943)
(3000)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
(3779)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
76
(1943)
(3152)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(259)
76
(1939)
(2997)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
76
(1943)
(3000)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
76
(1943)
(3000)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
(3779)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
(3779)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
(3779)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
76
(1943)
(2999)
Isolator Y-Dimension 1 (34)
144
118
149
124
118
118
118
149
149
149
118
193
(4900)
157
(3985)
187
(4756)
163
(4137)
157
(3982)
157
(3985)
157
(3985)
187
(4756)
187
(4756)
187
(4756)
157
(3984)
220
(5589)
251
(6368)
210
(5323)
208
(5295)
209
(5299)
209
(5299)
251
(6368)
251
(6368)
235
(5968)
209
(5298)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
281
(7132)
308
(7823)
281
(7136)
301
(7653)
281
(7135)
NOTES:
1. Contact your nearest Quantech Sales Representative for weight data.
2. All isolator mounting holes are 19mm.
3. Dimensions are in inches (mm).
78
QUANTECH
Page 79
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 5 - TECHNICAL DATA
TABLE 10 - ISOLATOR SELECTION AND MOUNTING LOCATIONS (CONT'D)
QTC4 CONFIGURATION
MODEL COND EVAP
150 S B
165 H B
175 P C
185 S A
185 H A
185 P B
175 C C
210 S A
210 H C
210 P C
230 S B
DESCRIPTION 9 10 11 12 13 14 15 16
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
10
(263)
10
(263)
10
(263)
10
(263)
10
(259)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
73
(1852)
77
(1943)
81
(2057)
76
(1943)
76
(1939)
76
(1943)
76
(1943)
81
(2057)
81
(2057)
81
(2057)
76
(1943)
144
(3662)
118
(3000)
149
(3779)
124
(3152)
118
(2997)
118
(3000)
118
(3000)
149
(3779)
149
(3779)
149
(3779)
118
(2999)
193
(4900)
157
(3985)
187
(4756)
163
(4137)
157
(3982)
157
(3985)
157
(3985)
187
(4756)
187
(4756)
187
(4756)
157
(3984)
220
(5589)
251
(6368)
210
(5323)
208
(5295)
209
(5299)
209
(5299)
251
(6368)
251
(6368)
235
(5968)
209
(5298)
5
281
(7132)
308
(7823)
281
(7136)
301
(7653)
281
(7135)
NOTES:
1. Contact your nearest Quantech Sales Representative for weight data.
2. All isolator mounting holes are 19mm.
3. Dimensions are in inches (mm)..
QUANTECH
79
Page 80
SECTION 5 - TECHNICAL DATA
TABLE 10 - ISOLATOR SELECTION AND MOUNTING LOCATIONS (CONT'D)
QTC4 CONFIGURATION
MODEL COND EVAP
240 H C
240 P C
260 S B
270 C D
270 S D
270 H E
270 P E
290 H E
300 S C
300 H C
310 P E
315 P E
320 S E
330 S C
340 S E
DESCRIPTION 1 2 3 4 5 6 7 8
Isolator X-Dimension
10
(263)
76
(1943)
128
(3260)
173
(4391)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
143
(3638)
187
(4748)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
77
(1943)
118
(2999)
157
(3984)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
149
(3779)
187
(4756)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
161
(4084)
201
(5105)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
161
(4084)
201
(5105)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
161
(4095)
201
(5105)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
161
(4095)
201
(5105)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
143
(3638)
187
(4748)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(260)
81
(2057)
144
(3663)
187
(4755)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(260)
81
(2054)
161
(4081)
201
(5102)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
161
(4084)
201
(5105)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
161
(4084)
201
(5105)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
143
(3636)
188
(4781)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
161
(4084)
201
(5105)
Isolator Y-Dimension 1 (34)
220
(5579)
245
(6232)
209
(5298)
264
(6709)
301
(7654)
301
(7654)
298
(7582)
296
(7512)
245
(6232)
277
(7047)
298
(7579)
298
(7582)
298
(7582)
245
(6232)
298
(7582)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
301
(7654)
339
(8609)
308
(7823)
339
(8609)
339
(8609)
339
(8608)
383
(9726)
383
(9723)
427
(10843)
339
(8609)
383
(9726)
383
(9726)
NOTES:
1. Contact your nearest Quantech Sales Representative for weight data.
2. All isolator mounting holes are 19mm.
3. Dimensions are in inches (mm).
80
QUANTECH
Page 81
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 10 - ISOLATOR SELECTION AND MOUNTING LOCATIONS (CONT'D)
QTC4 CONFIGURATION
MODEL COND EVAP
240 H C
240 P C
260 S B
270 C D
270 S D
270 H E
270 P E
290 H E
300 S C
300 H C
310 P E
315 P E
320 S E
330 S C
DESCRIPTION 9 10 11 12 13 14 15 16
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
10
(260)
10
(260)
10
(263)
10
(263)
10
(263)
76
(1943)
81
(2057)
77
(1943)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2054)
81
(2057)
81
(2057)
81
(2057)
128
(3260)
143
(3638)
118
(2999)
149
(3779)
161
(4084)
161
(4084)
161
(4095)
161
(4095)
143
(3638)
144
(3663)
161
(4081)
161
(4084)
161
(4084)
143
(3636)
173
(4391)
187
(4748)
157
(3984)
187
(4756)
201
(5105)
201
(5105)
201
(5105)
201
(5105)
187
(4748)
187
(4755)
201
(5102)
201
(5105)
201
(5105)
188
(4781)
220
(5579)
245
(6232)
209
(5298)
264
(6709)
301
(7654)
301
(7654)
298
(7582)
296
(7512)
245
(6232)
277
(7047)
298
(7579)
298
(7582)
298
(7582)
245
(6232)
SECTION 5 - TECHNICAL DATA
301
(7654)
339
(8609)
308
(7823)
5
339
(8609)
339
(8609)
339
(8608)
383
(9726)
383
(9723)
427
(10843)
339
(8609)
383
(9726)
NOTES:
1. Contact your nearest Quantech Sales Representative for weight data.
2. All isolator mounting holes are 19mm.
3. Dimensions are in inches (mm)..
QUANTECH
81
Page 82
SECTION 5 - TECHNICAL DATA
TABLE 10 - ISOLATOR SELECTION AND MOUNTING LOCATIONS (CONT'D)
QTC4 CONFIGURATION
MODEL COND EVAP
340 H E
370 P J
370 S F
370 H J
400 P J
405 S H
410 H H
410 P J
450 S G
490 H J
460 S G
470 C K
480 C J
500 S J
DESCRIPTION 1 2 3 4 5 6 7 8
Isolator X-Dimension
10
(263)
81
(2057)
161
(4084)
201
(5105)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
145
(3680)
205
(5219)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
145
(3680)
206
(5219)
Isolator Y-Dimension
Isolator X-Dimension
10
(263)
81
(2057)
145
(3680)
206
(5219)
Isolator Y-Dimension
Isolator X-Dimension
10
(254)
81
(2057)
154
(3912)
206
(5232)
Isolator Y-Dimension
Isolator X-Dimension
10
(263)
81
(2057)
145
(3680)
205
(5219)
Isolator Y-Dimension
Isolator X-Dimension
10
(254)
81
(2057)
145
(3680)
206
(5219)
Isolator Y-Dimension
Isolator X-Dimension
10
(260)
81
(2054)
145
(3677)
205
(5216)
Isolator Y-Dimension
Isolator X-Dimension
10
(263)
81
(2057)
154
(3907)
206
(5219)
Isolator Y-Dimension
Isolator X-Dimension
10
(263)
81
(2057)
154
(3907)
206
(5219)
Isolator Y-Dimension
Isolator X-Dimension
10
(263)
81
(2057)
154
(3907)
206
(5219)
Isolator Y-Dimension
Isolator X-Dimension
10
(263)
81
(2057)
154
(3907)
205
(5219)
Isolator Y-Dimension
Isolator X-Dimension
10
(263)
81
(2057)
154
(2908)
205
(5219)
Isolator Y-Dimension 1 (34)
Isolator X-Dimension
10
(263)
81
(2057)
154
(3907)
206
(5219)
Isolator Y-Dimension 1 (34)
(7582)
(7218)
(7218)
1 (34)
(7218)
1 (34)
(7214)
1 (34)
(7218)
1 (34)
(7218)
1 (34)
(7215)
1 (34)
(7218)
1 (34)
(7218)
1 (34)
(7218)
1 (34)
(7218)
1 (34)
(7218)
(7218)
298
284
284
284
284
284
284
284
284
284
284
284
284
284
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
427
(10843)
383
(9725)
439
(11157)
427
(10842)
427
(10842)
427
(10846)
483
(12268)
427
(10843)
427
(10842)
427
(10839)
427
(10842)
427
(10842)
427
(10842)
483
(12274)
505
(12817)
483
(12274)
505
(12820)
505
(12820)
427
(10842)
427
(10843)
427
(10842)
505
(12820)
495
(12577)
539
(13691)
539
(13694)
562
(14262)
539
(13694)
562
(14265)
562
(14265)
562
(14265)
NOTES:
1. Contact your nearest Quantech Sales Representative for weight data.
2. All isolator mounting holes are 19mm.
3. Dimensions are in inches (mm).
82
QUANTECH
Page 83
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
TABLE 10 - ISOLATOR SELECTION AND MOUNTING LOCATIONS (CONT'D)
QTC4 CONFIGURATION
MODEL COND EVAP
340 S E
340 H E
370 P J
370 S F
370 H J
400 P J
405 S H
410 H H
410 P J
DESCRIPTION 9 10 11 12 13 14 15 16
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
10
(254)
10
(260)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2054)
161
(4084)
161
(4084)
145
(3680)
145
(3680)
145
(3680)
145
(3680)
145
(3680)
145
(3680)
145
(3677)
201
(5105)
201
(5105)
205
(5219)
206
(5219)
206
(5219)
206
(5219)
205
(5219)
206
(5219)
205
(5216)
298
(7582)
298
(7582)
284
(7218)
284
(7218)
284
(7218)
284
(7218)
284
(7218)
284
(7218)
284
(7215)
SECTION 5 - TECHNICAL DATA
383
(9726)
427
(10843)
383
(9725)
427
(10842)
427
(10842)
427
(10842)
427
(10843)
427
(10842)
427
(10839)
439
(11157)
483
(12274)
483
(12274)
505
(12817)
495
(12577)
539
(13694)
539
(13694)
562
(14262)
5
450 S G
490 H J
460 S G
470 C K
480 C J
500 S J
NOTES:
1. Contact your nearest Quantech Sales Representative for weight data.
2. All isolator mounting holes are 19mm.
3. Dimensions are in inches (mm).
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
Isolator X-Dimension
Isolator Y-Dimension 87 (2206)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
10
(263)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
81
(2057)
154
(3907)
154
(3907)
154
(3907)
154
(3907)
154
(2908)
154
(3907)
206
(5219)
206
(5219)
206
(5219)
205
(5219)
205
(5219)
206
(5219)
284
(7218)
284
(7218)
284
(7218)
284
(7218)
284
(7218)
284
(7218)
427
(10842)
427
(10842)
427
(10842)
427
(10842)
427
(10843)
427
(10842)
483
(12274)
505
(12820)
505
(12820)
505
(12820)
539
(13694)
562
(14265)
562
(14265)
562
(14265)
QUANTECH
83
Page 84
SECTION 5 - TECHNICAL DATA
SECTIOND-D

ELASTOMERIC ISOLATOR INSTALLATION

(B)
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
TOP BOLT
TOP WASHER
D
C
L
D
Read the following instructions before beginning installation.
1. Isolators are shipped fully assembled and are to be positioned in accordance with the submittal draw­ings or as otherwise recommended.
2. Set isolators on oor, housekeeping pad or sub­base, ensuring that all isolators lines match the equipment mounting holes. The VMC group rec­ommends that the isolator base (A) be installed on a level surface. Shim or grout as required, leveling all isolator bases to the same elevation (0.03125-inch maximum difference is tolerated).
(C)
(B)
C
L
SECTION D-D
(A)
LD13762C
3. Bolt or anchor all isolators to supporting structure utilizing base thru holes (B).
4. Remove top bolt and top washer. Place equip­ment on top of isolators so that mounting holes in equipment or base line up with threaded hole (C).
5. Reinstall top bolt and washer and tighten down.
84
QUANTECH
Page 85
FORM QTC4-NM1
LD17304
ISSUE DATE: 4/2/2018
SECTION 5 - TECHNICAL DATA

ELASTOMERIC ISOLATOR SPECIFICATIONS

HF
DW
CD
MOLDED
DURULENE
HF
Ø = AD Thru
Typ 2 Places
AL
L
BT
W
BT
AL
L
DW
CD
MOLDED
DURULENE
5
R = 0.280 Slot
Typ 2 Places
W
MOUNT
TYPE
L W HF AL AD BT CD DW
DIMENSION DATA (INCHES)
RD1-WR 3.13 1.75 1.25 2.38 0.34 0.19 5/16-18 UNC X 3/4 1.25 RD2-WR 3.88 2.38 1.75 3.00 0.34 0.22 3/8-16 UNC X 1 1.75 RD3-WR 5.50 3.38 2.88 4.13 0.56 0.25 1/2-13 UNC X 1 2.50 RD4-WR 6.25 4.63 2.75 5.00 0.56 0.38 1/2-13 UNC X 1 3.00
MODEL NUMBER ISOLATOR COLOR WEIGHT RANGE (LBS) WEIGHT RANGE (KGS)
RD-3-CHARCOAL-WR CHARCOAL Up thru 825 UP TO 374
RD-4-BRICK RED-WR BRICK RED 826 thru 1688 375 - 766
RD-4-CHARCOAL-WR CHARCOAL 1689 thru 4000 767 - 1814
QUANTECH
85
Page 86
SECTION 5 - TECHNICAL DATA
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

ONE INCH DEFLECTION ISOLATOR INSTALLATION

UPPER HOUSING
(D)
LOWER HOUSING
NON-SKID ELASTOMERIC PA D
POSITIONING PIN (H)
0.25” min - 0.5” max
Read the following instructions before beginning installation.
1. Isolators are shipped fully assembled and are to be positioned in accordance with the submittal draw­ings or as otherwise recommended.
EQUIPMENT BASE
(C)
(C)
(B)
4. Place equipment on top of isolators making sure that mounting holes of the equipment line up with isolator positioning pin (“H”).
5. Equipment or machine is at its full operating weight.
2. Set isolators on oor, housekeeping pad or sub­base, ensuring that all isolators centerlines match the equipment mounting holes. The VMC group recommends that the isolator base (“B”) be installed on a level surface. Shim or grout as required, leveling all isolator bases to the same elevation (0.25-inch maximum difference can be tolerated).
3. Bolt or anchor all isolators to supporting structure utilizing base slotted holes (“C”).
6. Adjust each isolator in sequence by turning spring adjusting bolt (“D”) one full counterclock­wise turn at a time. Repeat this procedure on all isolators, one at a time.
7. Continue adjusting each isolator until a minimum of 0.25” clearance is achieved between the low­er housing and upper housing. (See illustration above).
8. Fine adjust isolators to level equipment.
86
QUANTECH
Page 87
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 5 - TECHNICAL DATA

ONE INCH DEFLECTION SPRING ISOLATOR SPECIFICATIONS

CPX-X-


5



MOUNT
TYPE



DIMENSION DATA (INCHES)
W D L B C T H
CP 3 5/8 7-3/4 6-1/2 4-3/4 1/2 5-5/8
C2P 3 5/8 10-1/2 9-1/4 7-3/4 9/16 6
RATED CAPACITY (FOR UNITS WITH ALL LOAD POINTS
MODEL NUMBER COLOR CODE
LESS THAN 1785 LBS (810 KG)
(LBS.) (KG) PART NUMBER
CP-1D-510 BLACK Up thru 434 Up thru 197 029-25334-002
CP-1D-900 DARK GREEN 435 thru 765 198 thru 347 029-25334-003
CP-1D-1200 GRAY 766 thru 1020 348 thru 463 029-25334-004
CP-1D-1360 WHITE 1021 thru 1156 464 thru 524 029-25334-005
CP-1D-1785N GRAY/RED 1157 thru 1785 525 thru 810 029-25334-006
RATED CAPACITY (FOR UNITS WITH ANY LOAD POINT
MODEL NUMBER COLOR CODE
ABOVE 1518 LBS (689 KG)
(LBS.) (KG) PART NUMBER
C2P-1D-1350 DARK PURPLE Up thru 1148 Up to 521 029-25334-008 C2P-1D-1800 DARK GREEN 1149 thru 1530 522 - 694 029-25334-009 C2P-1D-2400 GRAY 1531 thru 2040 695 - 925 029-25334-010 C2P-1D-2720 WHITE 2041 thru 2312 926 - 1049 029-25334-012
C2P-1D-3570N GRAY/RED 2313 thru 3570 1050 - 1619 029-25334-013
NOTES:
1. Use either all CP's or all CP2's at all locations on a unit.
2. Installation requires bolting or anchoring mount to support structure with a 2 x 0.625" diameter bolts or 2 x 0.5" diameter concrete anchors.
3. All springs are designed for 50% over-travel.
QUANTECH
87
Page 88
SECTION 5 - TECHNICAL DATA

TWO INCH DEFLECTION ISOLATOR INSTALLATION AND ADJUSTMENT

FORM QTC4-NM1
ISSUE DATE: 4/2/2018
("A")
("E")
("G")
C
L
("E")
Read the following instructions before beginning installation.
1. Isolators are shipped fully assembled and are to be positioned in accordance with the submittal draw­ings or as otherwise recommended.
2. Set isolators on oor, housekeeping pad, or sub- base, ensuring that all isolator centerlines match the equipment mounting holes. The VMC group recommends that the isolator base plates (“B”) be installed on a level surface. Shim or grout as required, levelling all isolator base plates to the same elevation (0.25-inch maximum difference can be tolerated).
GROMMET
1/4 - 3/8 GAP
WASHER
("F")
("C")
("B")
("A")
("F")
("C")
C
L
EQUIPMENT
("E")
Bolt equipment securely to top plate of isolator using a minimum of 2 x 0.625" UNC A325 GRADE 5 SAE bolts or weld equipment or bracket to the top plate (“A”) of isolator with a
minimum 0.375" fillet welds 2” long @ 3” O.C.
for a minimum total weld of 10”. (All sides of equipment or bracket resting on top plate (“A”) must be welded).
6. The adjustment process can only begin after the equipment or machine is at its full operating weight.
7. Back off each of the 4 limit stop lock nuts (“F”) on the isolators 0.5”.
3. Bolt or anchor all isolators to supporting structure utilizing base plate through holes (“C”) or weld base plate to supporting structure with 0.375"
llet weld 2” long @ 4” on center around entire base plate or as engineered for specic load and or eld conditions.
4. Isolators are shipped to the job site with (2) removable spacer shims (“E”) between the top plate and the housing. These shims must be in place when the equipment is positioned over the isolators.
5. With all shims (“E”) in place, position equipment on top of plate (“A”) of isolator.
88
8. Adjust each isolator in sequence by turning spring adjusting nuts (“G”) one full clockwise turn at a time. Repeat this procedure on all isolators, one at a time. Check the limit stop lock nuts (“F”) periodically to ensure that clearance between the washer and rubber grommet is maintained. Stop adjustment of isolator only when the top plate (“A”) has risen just above the shim (“E”).
9. Remove all spacer shims (“E”).
10. Fine adjust isolators to level equipment.
11. Adjust all limit stop lock nuts (“F”) per isolator, maintaining 0.25-to 0.375-inch gap. The limit stop nuts must be kept at this gap to ensure uni­form bolt loading during uplift (as the case when equipment is drained).
QUANTECH
Page 89
FORM QTC4-NM1 ISSUE DATE: 4/2/2018

TWO INCH DEFLECTION, RESTRAINED SPRING ISOLATOR SPECIFICATIONS

SECTION 5 - TECHNICAL DATA
Y2RS
12-1/4"
1-1/8"
2-3/4"
12"
5/8-11UNC TYP. (4)
3-1/2"
1/2" LIMIT STOP & NUT
5"
8-3/8"
OPER.
HEIGHT
3/8"
3/4"
7/8"
3/8" GAP
Ø3/4"
TYP.(4)
5/8"
5"
2-3/4"
14"
MODEL NUMBER WEIGHT RANGE (LBS) WEIGHT RANGE (KGS) QUANTECH P/N
Y2RSI-2D-460 Up thru 391 UP TO 177 029-25336-006
Y2RSI-2D-710 392 thru 604 178 - 274 029-25336-008
Y2RSI-2D-870 605 thru 740 275 - 336 029-25336-009
Y2RSI-2D-1200N 741 thru 1020 337 - 463 029-25336-010
Y2RSI-2D-1690 1021 thru 1437 464 - 652 029-25336-011
Y2RSI-2D-2640N 1438 thru 2244 653 - 1018 029-25336-012
Y2RSI-2D-2870N 2245 thru 2618 1019 - 1188 029-25336-013
Y2RSI-2D-3280N 2619 thru 3740 1189 - 1696 029-25336-014
5
NOTES:
1. All dimensions are in inches, interpret as per ANSI Y14
2. Equipment must be bolted or welded to the top plate to meet allowable seismic ratings.
3. All springs are designed for 50% overload capacity with exception of the 029-25336-013 and 029-25336-014.
4. Contact your nearest Quantech Sales Representative for concrete installation.
QUANTECH
89
Page 90
FORM QTC4-NM1
ISSUE DATE: 03/07/2018
THIS PAGE INTENTIONALLY LEFT BLANK
90
QUANTECH
Page 91
FORM QTC4-NM1 ISSUE DATE: 4/2/2018

SECTION 6 - COMMISSIONING

PREPARATION

Commissioning of this unit should only be carried out by Quantech Authorized personnel.
Commissioning personnel should be thoroughly familiar with the information contained in this docu­ment before starting the unit.
The following basic checks should be made with the customer power to the unit switched OFF.
Proper electrical lock out and tag out procedures must be followed.

Inspection

Correct System Refrigerant Charge

The charge on a system should always be checked when operating for several minutes at full speed with the system stable. Stable conditions are defined as operation without fan cycling, economizer cycling, VI solenoid cycling, or any other system transient condi­tions. Ideal refrigerant charge will be reached when the refrigerant level in the evaporator is near the middle of the evaporator sight glass.
Refrigerant should not be added or removed unless the level is at the bottom or the top of the glass. It is not necessary to weigh charge unless the entire charge has been lost. The ease of charging is possible since the microchannel coils hold only a small amount of refrigerant charge. A
charging valve is located between the xed orice and the evaporator for adjusting
charge. Charge should be added as liquid
with the pump ON and liquid owing
through the evaporator.
6
Inspect unit for installation damage. If found, take action and/or repair as appropriate.

Refrigerant Charge

Packaged units are normally shipped as standard with a full refrigerant operating charge. Check that refrig­erant pressure is present in both systems and that no leaks are apparent. If no pressure is present, a leak test must be undertaken, the leak(s) located and repaired.
Do not evacuate or liquid charge with static water in the evaporator. Turn the pump on. Take care to liq­uid charge slowly to avoid excessive thermal stress at the charging point and to assure the refrigerant temperature in the evaporator does not go below the freezing point with liquid refrigerant in the evapo­rator. Once the vacuum is broken, charge into the evaporator or flash tank with the Condenser Drain Valve (Flash Tank Feed) open and the chilled liquid pump ON to the full operating charge, as detailed in SECTION 5 - TECHNICAL DATA.

Service and Oil Line Valves

Open each compressor oil, economizer, and discharge ball or service valves. If valves are of the back-seat type, open them fully (counterclockwise) then close one turn of the stem to ensure operating pressure is fed to pressure transducers.

Compressor Oil

To add oil to a circuit - connect a hand oil pump (Part No. 470-10654-000) to the 1/4" (6.35 mm) oil charging valve on the oil separator piping with a length of clean hose or copper line, but do not tighten the flare nut. Using clean oil of the correct type (“L” oil), pump oil until all air has been purged from the hose then tighten the nut. Stroke the oil pump to add oil to the oil system. While the compressor is running at full speed, the oil level should be visible in the sight glass of the oil separator. Approximately 2 to 3.1 gallons (7.5 to
11.6 liters) are present in each refrigerant system.
QUANTECH
91
Page 92
SECTION 6 - COMMISSIONING
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
Avoid levels in either oil separator that are above the middle of the top sight glass. This may cause excessive oil carryover in the system. High oil concen­tration in the system may cause nuisance trips resulting from incorrect readings on the level sensor and tem­perature sensors. Temperature sensor errors may result in poor liquid control which will result in liquid over­feed and subsequently damage the compressor. High oil carryover may also cause liquid to be returned to the compressor, which can damage the compressor.

Fans

Check that all fans are free to rotate and are not dam­aged. Ensure blades are at the same height when rotated. Ensure fan guards are securely fixed.
If condenser fans are manually operated in VFD mode, manually turn on all 4 fan digital outputs before enabling fan control voltage output. Damage to a fan contactor or fan VFD may occur if this instruction is not followed.
plugged air vent mounted on the top of the evaporator body.
Flow rates and pressure drops must be within the limits given in SECTION 5 - TECHNICAL DATA. Operation outside of these limits is undesirable and could cause damage.
If main power must be switched OFF for maintenance or shutdown, precautions must be taken. See Unit
Maintenance and Shutdown in Sub-freezing Conditions on Page 94. Before placing the unit back in service,
valves should be opened and power must be switched on (if power is removed for more than 8 hours) for at least 8 hours (24 hours if ambient temperature is below 86°F [30°C]) before the unit is restarted.

Flow Switch

Verify a chilled water flow switch is correctly fitted in the customer’s piping on the evaporator outlet, and wired into the control panel correctly using shielded cable.

Isolation / Protection

Verify all sources of electrical supply to the unit are taken from a single point of isolation. Check that the maximum fuse sizes recommended in SECTION 5 - TECHNICAL DATA has not been exceeded.

Control Panel

Check the panel to see that it is free of foreign materi­als (wire, metal chips, etc.) and clean out if required.

Power Connections

Check that the customer power cables are connected correctly to the terminal blocks or optional circuit breaker. Ensure that connections of power cables within the panels to the circuit breaker or terminal blocks are tight.

Grounding

Verify that the unit’s protective ground terminal(s) are properly connected to a suitable grounding point. En­sure that all unit internal ground connections are tight.

Water System

Verify the chilled liquid system has been installed cor­rectly, and has been commissioned with the correct di­rection of water flow through the evaporator. The inlet should be at the bottom connection on a two pass evapo­rator. Purge air from the top of the evaporator using the
There should be a straight run of at least five pipe diam­eters on either side of the flow switch. The flow switch should be connected to Terminals 2 and 13 in the panel.

Temperature Sensor(s)

Ensure the leaving liquid temperature sensor is coated with heat conductive compound (Part No. 013-00890-
000) and is inserted to the bottom of the water out­let sensor well in the evaporator. This sensor is part of the pump control freeze protection operation. It provides some freeze protection and must always be fully inserted in the water outlet sensor well.

Programmed Options

Verify that the options factory-programmed into the Micro Panel are in accordance with the customer’s order requirements by pressing the OPTIONS key on the keypad and reading the settings from the display.

Programmed Settings

Ensure the system cutout and operational settings are in accordance with the operating requirements by press­ing the PROGRAM key.

Date and Time

Program the date and time by first ensuring that the CLK jumper JP2 on the Chiller Control Board is in the ON position. Then press the DATE/TIME key and set the date and time (See Date/Time and Schedule Keys on
92
QUANTECH
Page 93
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 6 - COMMISSIONING
Page 140 for more details on programming the date and time).

Start/Stop Schedule

Program the daily and holiday start/stop by pressing the SCHEDULE key (See Date/Time and Schedule Keys on Page 140 for more details on programming the date and time).

Setpoint and Remote Offset

Set the required leaving chilled liquid temperature setpoint and Control Range under the SETPOINTS key. The chilled liquid temperature control settings need to be set according to the required operating conditions.
If remote temperature reset (offset) is to be used, the maximum reset required must be programmed by pressing the SETPOINTS key (See Setpoints Key on Page 132).

FIRST TIME START UP

During the commissioning period there should be sufficient heat load to run the unit under stable full load operation to enable the unit controls, and system operation to be set up correctly, and a commissioning log taken.
and display the nature of the fault.

Oil Pressure

When a compressor starts, press the relevant “System Pressures” key and verify that oil differential pressure (oil pressure-suction pressure) develops immediately. If oil pressure does not develop, the automatic con­trols will shut down the compressor. Under no circum­stances should a restart attempt be made on a compres­sor, which does not develop oil pressure immediately. Switch the UNIT switch to the OFF position.

Loading

Once the unit has been started, all operations are fully automatic. After an initial period at minimum capacity, the control system will adjust the unit load depending on the chilled liquid temperature and rate of tempera­ture change. If a high heat load is present, the control­ler will increase the speed of the compressor(s).

Condenser and Fan Rotation

Once a compressor is running, discharge pressure rises as refrigerant is pumped into the air-cooled con­denser coils. This pressure is controlled by stages of fans to ensure maximum unit efficiency while main­taining sufficient pressure for correct operation of the condensers and the lubrication system.
6

Interlocks

Verify that liquid is flowing through the evaporator and that heat load is present. Ensure that any remote run interlocks are in the run position and that the Daily Schedule requires the unit to run or is overridden.

Unit Switch

Place the UNIT switch on the keypad to the ON position.

Startup

Press the SYSTEM SWITCHES key and place the system switch for System 1 to the ON position. There may be a few seconds delay before the first compres­sor starts because of the anti-recycle timer). Be ready when each compressor starts, to switch the UNIT switch OFF immediately, if any unusual noises or other adverse conditions develop.
When a compressor is running, the controller monitors oil pressure, motor current, and various other system parameters such as discharge pressure, chilled liquid temperature, etc. Should any problems occur; the con­trol system will immediately take appropriate action
As discharge pressure rises, the condenser fans operate in stages or ramp up in speed to control the pressure. Verify that the fans operate in the correct direction of rotation and operation is correct for the type of unit.

System Charge

Check system charge at steady full compressor load only. It is important that all fans are running for the system. The refrigerant level in the evaporator should be about in the middle of the sight glass. Unless levels are at the bottom or the top of the sight glass, they should not cause concern or require adding or removing charge.

GENERAL OPERATION

After completion of the above checks for System 1, switch OFF the SYS 1 switch on the keypad and repeat the process for each subsequent system. When all run correctly, stop the unit, switch all applicable switches to the ‘ON’ position and restart the unit.
Assure all checks are completed in the Equipment Pre - Startup and Startup Checklist. The chiller is then ready to be placed into operation.
QUANTECH
93
Page 94
SECTION 6 - COMMISSIONING
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

Operation in Sub-freezing Conditions

The QTC4 may be operated in sub-freezing conditions if the following freeze protections are taken:
A. A suction service valve electric actuator is
installed. Chiller software will operate the actuator in order to protect against freezing due to evaporator refrigerant migration.
-or-
B. No suction service valve is installed but the water
circuit valves are kept open, there is continuous power to the chiller and pump for chilled water pump control, and the pump will operate and cir­culate water through the evaporator whenever commanded by the chiller.
The above operation is only advised if uninterrupted power can be ensured. Unforeseen power interruptions can damage the evaporator in a very short time frame if the temperature falls below freezing.
Unit Maintenance and Shutdown in Sub­freezing Conditions
If the QTC4 is maintained or shut down and will be subjected to sub-freezing conditions, it is critical to protect against evaporator and waterbox freeze dam­age. Quantech recommends the following options (in order of freeze protection level) be performed on each circuit.
A. Glycol: Replace water with an appropriate water
to glycol concentration of antifreeze.
-or-
B. Drain: Remove power to the waterbox heaters.
Close the water valves, drain the evaporator, and leave the evaporator drain valves open.
-or-
C. Refrigerant Valve - Off: Close the water valves,
close ash tank drain valves, close the suction
service valves and leave power to the chiller for evaporator heater mat and waterbox heater op­eration. For units without a suction service valve, close the discharge and compressor oil valves.
If there is potential for power loss, Quantech recom­mends the water in the chilled water circuit be replaced with an appropriate water-to-glycol concentration.
Failure to follow Quantech freeze pro­tection recommendations can void the warranty.
-or-
D. Pump Control: Keep power to the chiller in or-
der to have control over chilled water pumps and heater operation and leave the water circuit valves open. This will enable water to circulate through the evaporator to avoid freezing.
Options A and B are the recommended processes for unit maintenance and shutdown. Unforeseen power interrup­tions can damage the evaporator in a very short time frame if the temperature falls below freezing.
94
QUANTECH
Page 95
FORM QTC4-NM1 ISSUE DATE: 4/2/2018

SECTION 7 - OPERATION

OPERATING CONTROLS

DISPLAY

KEYPAD

FIGURE 17 - KEYBOARD AND DISPLAY

UNIT
SWITCH
LD21850
The keypad also contains keys in the center section for data entry in the various program modes. These keys are listed below:
• 0-9 Keys NUMERIC KEYPAD
• PERIOD/DECIMAL
• +/- PLUS/MINUS
• ENTER
• CANCEL
• ▲ UP ARROW
• ▼ DOWN ARROW
• ◄ LEFT ARROW
• ► RIGHT ARROW
The numeric keys allow keying numeric values into memory.
The • (PERIOD/DECIMAL) key allows keying a decimal point into numeric values.
7

Unit Switch

A double pole single throw ON/OFF rocker switch on the front of the control panel is used to turn the entire chiller ON and OFF. When the switch is placed in the OFF position, the entire unit shuts down immediately and all systems will be disabled. One pole of the UNIT switch contacts is wired to the Run Signal input and the Chiller Control Board “UNIT switch X” digital input (X equals System 1 or 2). Separate System Fuses are also wired in series with each set of UNIT switch con­tacts. If either fuse is pulled or blown, only the system with the good fuse (Input is high) will run. When both inputs are high, the entire chiller will be enabled to run. When both inputs are low, the chiller will be disabled as a UNIT switch OFF Shutdown.
Keypad
An operator keypad allows complete control of the sys­tem from a central location. The keypad offers a multi­tude of command keys on the left and right side of the keypad to access displays, program setpoints, history data, and initiate system commands. Most keys have multiple displays that can be accessed by repetitively
pressing the key or by pressing the ▲,▼,◄, and ►
(ARROW) keys. The keypad utilizes an overlay to convert the keypad to various languages.
The +/- (PLUS/MINUS) key allows making numeric values negative.
The (ENTER) key stores program changes into memory.
The X (CANCEL) key is used to cancel the data en­try operation and returns the programmed value to the original value, before any programming changes were made, when an error is made.
The ▲ (UP ARROW) and ▼ (DOWN ARROW) keys allow scrolling backward (▲) and forward (▼)
through items to be programmed under keys such as the PROGRAM or OPTIONS key.
The ▲ (UP ARROW) and ▼ (DOWN ARROW) keys also allow scrolling forward (▼) or backwards (▲) through data display keys that have multiple
displays under keys such as UNIT DATA, SYSTEM DATA, HISTORY, PROGRAM, OPTIONS, etc. The arrow keys can be used instead of repeatedly pressing the data key to see the multiple displays under a key.
Once the ▲ ▼ (ARROW) keys are pressed and used
for scrolling, pressing the original data key will return to the first display message displayed under the data (UNIT DATA, SYSTEM DATA, etc.) keys.
QUANTECH
95
Page 96
SECTION 7 - OPERATION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
The ◄ ► (LEFT and RIGHT ARROW) keys allow
scrolling between non-numeric program choices under the OPTION, DATE/TIME, and SCHEDULE keys.
The ◄ (LEFT ARROW) key allows programming the
default value when programming numeric values. For
changing numeric values, the ► (RIGHT ARROW)
key has no function.
The ◄ ► (ARROW) keys also allow scrolling side­ways between the same displays on different systems.
For example, pressing the ► (RIGHT ARROW) key
while viewing the system #1 suction pressure moves the display to system #2 suction pressure.
Pressing the ◄ (LEFT ARROW) key moves the opposite direction. The arrow keys also allow fast scrolling through data under keys such as HISTORY by enabling the operator to move between subgroups of data such as Unit, System, and VSD data.

Keypad Data Entry Mode

For numeric programmable items, the data entry mode is entered by pressing any of the number keys, the deci­mal point key, or the +/- key. When the data entry mode is entered, the data from the key press will be entered and the cursor will appear under the position where the data is being entered.
For non-numeric programmable items, data entry
mode is entered by pressing the ◄ or ► (ARROW)
keys. When the data entry mode is entered, the cursor will appear under the first position of the non-numeric string. The programmable choice may be changed by
pressing the ◄ or ► (ARROW) keys.
To exit the data entry mode and store the programmed value, the(ENTER) key must be pressed. When the (ENTER) key is pressed, the cursor will disappear.
The data entry mode may also be exited by pressing the X (CANCEL) key. The programmed data will be returned to its original value when the X (CANCEL) key is pressed.
When the data entry mode is exited, the cursor will dis­appear. If any other key is pressed while in the Data Entry Mode, the following display will appear for 2 seconds indicating the user must choose between accepting or canceling the change:
XXXXXXXXXXX PRESS TO ACCEPT VALUE OR
X TO CANCEL DATA ENTRY
If the (ENTER) key was pressed from the data en­try mode and the numeric value entered was out of range, the following message will appear for 2 seconds followed by the original data display.
XXXXXXXXXXX OUT OF RANGE TRY AGAIN!
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX

Display

The 80 character (2 lines of 40 characters per line) display is a Liquid Crystal Display (LCD) used for displaying unit parameters, system parameters, and operator messages. The display has an LED backlight background for night viewing and is viewable in direct sunlight.

Anti-recycle Timer

On power-up of the control panel, the anti-recycle tim­er for each system will be set to 120 seconds and must time out before a compressor is allowed to start.
Whenever a system starts, the anti-recycle timer for all systems will be set to 120 seconds and will count down from the time the motor starts. The timer must time out before another compressor is allowed to start.
Whenever a system shuts down, the anti-recycle timer for that system will be set to 120 seconds. The timer must time out before the system is allowed to restart.

Evaporator Pump Control

The evaporator pump dry contacts are energized when any of the following conditions are true:
• If a Low Leaving Chilled Liquid Fault occurs.
• Whenever a compressor is running.
• The Daily Schedule is ON and the UNIT switch is ON.
Even if one of above is true, the pump will not run if the panel has been powered up for less than 30 seconds or if the pump has run in the last 30 seconds to prevent pump motor overheating.

Evaporator Heater Control

The evaporator heater is controlled by ambient air temperature. If no systems are running and the ambient temperature drops below 4.4 °C (40°F), the heater is turned ON. If no systems are running and the temperature rises above 7.2°C (45°F) the heater is turned OFF. Whenever a system is running, the evapo­rator heater is turned OFF.
96
QUANTECH
Page 97
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 7 - OPERATION
Both evaporator heater outputs will always be turned ON and OFF together. An under voltage condition will keep the heater OFF until full voltage is restored to the system.
Compressor Heater Control
Each compressor has its own heater. The purpose of the heater is to assure refrigerant does not condense in the compressor. There is no oil sump, but refriger­ant could possibly condense in the rotors or the motor housing. The heater will be OFF whenever the respec­tive compressor is running. As soon as the compressor shuts OFF, the heater will turn ON as long as all motor temperature sensors in the compressor read less than 70°C (158°F). The heater will turn OFF, if any internal compressor motor temperature sensor reads more than
71.1°C (160°F).

Alarms

Each system has its own alarm. The Alarm output is ON (dry contact closed) when no fault condition is pres­ent and OFF (dry contact open) to indicate an alarm situation. The Alarm will be activated (contacts open), if any of the following are true.
• A System is faulted or inhibited from starting for more than 5 seconds.
• The Unit is faulted or inhibited from starting for more than 5 seconds.
• A System is locked out.
• The Unit is locked out.
• Power is removed from the chiller.

Chiller Run Contact

The Chiller Run dry contact is closed whenever any sys­tem is running. It is open when all systems are shut OFF.

Flow Switch Control

A chilled liquid flow switch of suitable type MUST be connected between Terminals 2 and 13 of 1TB to provide protection against loss of liquid flow, which will cause evaporator freeze-up if the chiller is permit­ted to run.

Remote Run / Stop

A Remote Run/Stop input is available for each system.

BASIC OPERATING SEQUENCE

Start Sequence and Loading

To initiate the start sequence of the chiller, the follow­ing conditions must be satisfied before the precharge of the DC Bus will take place:
• UNIT SWITCH must be ON.
• At least one System Switch is ON
• Run permissive inputs (Remote Cycling Contacts) must be closed.
• No unit faults exist.
• No unit start inhibits exist.
• At least one system not faulted or inhibited.
• The Daily Schedule is calling for the chiller to run.
• The Flow Switch is closed.
• Leaving Chilled Liquid Setpoint is above the Setpoint plus CR (Setpoint High Limit).
Once the precharge takes place, if the anti-recycle tim­er is timed out the chiller control system on the Chiller Control Board will select the number of compressors to start and begin operation of the compressors. The compressor(s) speed will be ramped to the minimum start frequency and increase speed as needed in an ef­fort to regulate the leaving chilled liquid temperature to meet the desired Setpoint. Unit Warnings

UNIT WARNING

Unit Warning Operation

Unit warnings are caused when a condition is pres­ent requiring operator intervention to restart the unit. All setpoints, program values, and options should be checked before operating the unit. Warnings are not logged to the history buffer. If a unit warning is in effect, the message will be displayed to the operator when the STATUS key is pressed.

Low Battery Warning

The LOW BATTERY WARNING can only occur at unit power-up. On micropanel power-up, the RTC bat­tery is checked to see if it is still operational. If it is, normal unit operation is allowed. If the battery volt­age is determined to be low, the following warning message is displayed indefinitely.
7
QUANTECH
UNIT WARNING: !! LOW BATTERY !!
CHECK SETPOINTS/PROGRAM/OPTIONS/TIME
97
Page 98
SECTION 7 - OPERATION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
If a low battery condition exists, all programmed setpoints, program values, time, schedule, and history buffers will have been lost. These values will all be reset to their default values, which may not be the desired operating values. Once a bad battery is detect­ed, the unit will be prevented from running until the MANUAL OVERRIDE key is pressed. Once the MANUAL OVERRIDE key is pressed, the anti recycle timers will be set to the programmed default anti recycle time to allow the operator sufficient time to check setpoints, program values, etc.
If a low battery is detected, it should be replaced as soon as possible. The programmed values will all be lost and the unit will be prevented from running on the next power interruption.

MICROBOARD (331-03478-XXX)

The 331-03478-xxx microboard was developed as a direct replacement for the 031-02478-xxx line of microboards. No adapter harness is required when replacing a 02478 with the new 03478. The 03478 microboard uses the IPUII processor card and provides new features for the chillers, that the 02478 did not have.
The 03478 program resides in flash memory instead of EPROM. Program updates are accomplished by loading the new program from an SD card inserted into the SD card reader/writer. This same SD card reader/ writer also allows the user to datalog the operating parameters to an SD card every 5 seconds. This information is invaluable when troubleshooting unit and system problems since it allows the service technician to view operating parameters prior to a unit fault.
Details on the new datalogging capability are explained in the OPTIONS Key area of this manual. A Real Time Clock/BRAM keeps time and setpoints during power outages.
Refer to Figure 18 on Page 99, to locate the follow­ing ports of the 03478 microboard.
POWER – On solid indicates that the base board +12V and +5V power supplies are operational.
TX1 – Red LED flashes when transmitting data out Port 1 TB3 (Future native communications BAS port).
RX1 – Green LED flashes when receiving data in Port 1 TB3 (Future native communications BAS port).
TX2 – Red LED that flashes when transmitting data out Port 2 (E-Link TB2 or printer TB1).
RX2 – Green LED that flashes when receiving data in Port 2 (E-Link TB2 or printer TB1).
VSD_TX – Red LED that flashes when transmitting data out Port 3 to the VSD Logic board.
VSD_RX – Green LED that flashes when receiving data in Port 3 from the VSD Logic board.

Power Supply Test Points

24VAC power is applied to the 331-03478-xxx microboard connector J12 and is used to create vari­ous DC power sources required by the microboard circuitry. If the chiller control is malfunctioning, the power supply test points should be measured to determine the status of the microboard.
TP1 GND (Measure TP2, TP3, TP4 and TP5 in refer­ence to this Test Point)
TP2 +3.3V [3.2 to 3.4VDC] provides power to the processors
TP3 +5V [4.8 to 5.2VDC] power communication ports 2,3 and 4 and analog sensors
TP4 +12V [11.64 to 12.36VDC] powers the display and backlight and is regulated to become the +5V
TP5 +15V [11.3 to 16.6VDC] powers the analog out­puts to the EEV valves

Configuration Jumpers

The same configuration jumpers that existed on the 02478 are provided on the 03478.

Power Supplies and LEDs

The 03478 has LEDs to indicate various states of operation of the microboard.
STATUS – Flashes every ½ second to indicate that the base board processor is running its program.
98
JP4 Remote Temp Reset jumper position Pins 1 to 2 (left) = 4-20 mA, Pins 2 to 3 (right) = 0-10 VDC.
JP5 Remote Current Limit jumper position Pins 1 to 2 (left) = 4-20 mA, Pins 2 to 3 (right) = 0-10 VDC.
JP6 Remote Sound Limit jumper position (Pins 1 to 2 (left) = 4-20 mA, Pins 2 to 3 (right) = 0-10 VDC.
QUANTECH
Page 99
FORM QTC4-NM1 ISSUE DATE: 4/2/2018
SECTION 7 - OPERATION
20
19
18
17
16
1
15
2
14
7
3
13
12
11
10
4
ITEM DESCRIPTION ITEM DESCRIPTION ITEM DESCRIPTION ITEM DESCRIPTION
1
2
3
4
5
TP3 +5V
TP2 +3.3V
SD Card
JP4, JP5, JP6
Remote Setpoint
Jumpers
U5 RTC/BRAM
6
7
8
9
10
5
Power LED 11
Status LED 12
Power LED 13
Port 2
RS485 to E-Link/
SC-EQ or Modbus
U23 Port 2
RS-485 Driver
6
14
15
7
Port 2
RX2, TX2
PORT 2 RS-232
Printer or Modbus
VSD RX VSD-TX
U18 VSD
RS-485 Driver
U26 PORT 1
RS-485 Driver
8
9
LD19331
16
17 TP1 GND
18 TP4+12V
19 TP5 + 15V
20 TP10 + 24V
Port 1
Native BAS

FIGURE 18 - NEW 331-03478-XXX MICROBOARD

QUANTECH
99
Page 100
SECTION 7 - OPERATION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018

Communication Ports

The 03478 microboard has the following native communication ports.
TB3 Port 1 Native BAS RS-485.
SW1 RS-485 Biasing Switch for Port. Set to ON if
Chiller is in an End Of Line position on the network.
U26 is the Port 1 RS-485 Driver Chip. It is socketed to allow field replacement. RX1 and TX1 LEDs illuminate to indicate Port 1 communications activity.

BUILDING AUTOMATION SYSTEM (BAS) COMMUNICATIONS

There are three different ways the chiller communi­cates to the BAS.
• Via board Native Communication protocol
• Using an E-Link Gateway
• Using an SC-EQ Communication Card
To access the Port communication parameters:
1. Press the PROGRAM key once.
2. Enter password 5255.
3. Press the (ENTER) key to display the Port 1
(P1) settings.
Set the following parameters:
1. DE Modier Address (number entered is multiplied by 100): set as required by network.
2. DE Modier Offset (number entered is added to DE Modier Address): set as required by net­work (see NOTE below).
3. P1 Protocol: set to BACNET (Default Setting).
4. P1 Manual MAC Address: set to 1 (Default Setting).
5. P1 Baud rate: set as required by network. If not known, set to AUTO.
6. P1 Parity: set to NONE (Default Setting).

Using Communications Protocol

TB3 Port 1 Native BAS RS-485.
SW1 RS-485 Biasing Switch for Port. Set to ON if
chiller is in an End of Line position on the network.
U26 is the Port 1 RS-485 Driver Chip. It is sock­eted to allow field replacement. RX1 and TX1 LEDs illuminate to indicate Port 1 communications activity.
QTC4 Native Communication Setup
Native communication is applicable to three types of protocols, they are BACnet, N2 and Modbus RTU. It requires IPU II Microboard (331-03478-101) and software version Y.ACS.20.02 or later.
BACnet MS/TP Setup Port 1 (TB3)
To setup the BACNET MS/TP Port 1, follow the steps below:
1. Connect the BACnet MS/TP Network to Port 1 on the IPU II I/O Board.
2. Set up the QTC4 Port 1 (P1) for BACnet Communications as shown in Figure 18 on Page
99.
7. P1 Stop Bits: set to 1 (Default Setting).
The BACnet DE Instance (Device Instance) is determined by adding the [DE MODIFIER AD­DRESS x 100] with the DE MODIFIER OFFSET. For example, if the desired DE Instance address is 5023, set the DE Modifier Address to 50, and then set the DE Modifier Offset to 23 (50 X 100 + 23 = 5023). DE Instances must be limited to values between 1 and 4,194,303 and every device in the network must have a unique device Instance.
N2 Metasys Setup Port 1 (TB3)
1. Connect the N2 Network to Port 1 on the IPU II I/O Board as shown in Figure 18 on Page 99.
2. Set up the QTC4 Port 1 (P1) for N2 Communica­tions.
To access the Communication parameters:
You must always cycle power to the microboard following port setting changes.
100
QUANTECH
Loading...