PVI Industries TempTrac User Manual

Page 1
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Installation and interface must be performed by a qualified controls technician.
IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND
CONFIGURATION OF THIS EQUIPMENT. READ AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL OTHER PROVIDED INSTRUCTIONS, LABELS AND MARKINGS BEFORE INSTALLING, OPERATING OR SERVICING THIS UNIT.
Contents
OVERVIEW OF INTERFACE METHODS: ................................................................................................. 2
TEMPTRAC PROTOCOL ........................................................................................................................... 4
ITEMS REQUIRED FOR GATEWAY INTERFACE: ................................................................................... 4
ITEMS REQUIRED FOR MODBUS DIRECT INTERACE: ......................................................................... 4
IDENTIFY EQUIPMENT: ............................................................................................................................. 5
WIRING BAS TO GATEWAY AND THEN GATEWAY TO TEMPTRAC: .................................................. 6
WIRING OF TEMPTRAC TO BAS (Direct, no Gateway): ........................................................................... 7
GATEWAY CONFIGURATION CONNECTION: ........................................................................................ 7
CONFIGURE GATEWAY DIP SWITCHES: ............................................................................................... 8
CONFIGURE THE GATEWAY USING THE HTML INTERFACE: ............................................................. 9
CONFIRM OPERATION: ........................................................................................................................... 10
TROUBLESHOOTING GATEWAY: .......................................................................................................... 10
HOOKUP OVERVIEW: .............................................................................................................................. 11
APPLICATION SPECIFICS: ...................................................................................................................... 12
POINTS LIST: ............................................................................................................................................ 16
TYPICAL POINTS: ..................................................................................................................................... 16
ALL POINTS INCLUDING ADVANCED: ................................................................................................... 18
ADVANCED MODBUS LIST: .................................................................................................................... 25
TO THE INSTALLER / CONTROLS INTEGRATOR: After installation and integration, these instructions must be given to the equipment user or left near the appliance.
SPECIAL INSTRUCTIONS TO THE OWNER: Retain this manual for future reference. These instructions contain important integration information that will help you in maintaining and operating this appliance.
PVI INDUSTRIES, LLC - Fort Worth, Texas 76111 - Web www.pvi.com - Phone 1-800-433-5654
Page 1 of 30 PV7069-T 03 /17
Part number 129209
Page 2
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Other equipment
GATEWAY
PVI WATER HEATERS
BAS
Other equipment
PVI WATER HEATERS
BAS
OVERVIEW OF INTERFACE METHODS:
This document is a quick reference for connecting the TempTrac water heater / boiler control to a Building Automation System (BAS). Direct connection via MODBUS RTU or using a gateway to interface to protocols other than MODBUS RTU are the methods covered in this manual.
BAS to Heaters direct, using MODBUS RTU:
Building Automation System (BAS) connecting directly to water heaters using MODBUS RTU twisted pair wire. (Wiring is RS-485 physical layer.)
BAS to heaters using a Protocol Gateway:
Building Automation System (BAS) connecting to a PVI gateway. This can provide interface to BACNET MSTP, BACNET IP, LONWORKS, and MODBUS TCP. (Wiring from gateway to heaters is RS-485 physical layer. Wiring from BAS to gateway will depend on Protocol.)
BAS to heaters using discrete connections:
This is simply control of the heater using the external ENABLE/DISABLE contacts, remote equipment contacts and the alarm contacts. See wiring diagram of equipment for details.
Page 2 of 30 PV7069-T 03 /17
Part number 129209
Page 3
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
TempTrac Heater MODBUS fixed settings:
Most of the MODBUS RTU and Port settings are not adjustable Baud Rate: 9600bps (Not adjustable) Data Length: 8 bit (Not adjustable) Parity: None (Not adjustable) Stop Bits: 1 (Not adjustable) Start/Stop: Silent interval of 3 characters minimum Minimum Time Between Retry: 500 msec. Maximum read command is 5 words
Steps to change the TempTrac MODBUS address:
Editing parameters should be done without any device trying to communicate through the MODBUS port. To avoid interference from a gateway or BAS, you should unplug the MODBUS adapter port on the back of the TempTrac at the white header, while making changes to the TempTrac parameters. The first step to interfacing with a TempTrac or group of TempTracs will be the assignment of the address number for each boiler. The default for TempTrac is Address #1. You can assign any number in the range of 1-247. This is the limitations of the MODBUS RTU standard. The MODBUS address is the Adr parameter, and it is in the Pr2 menu.
Enter the Programming mode by pressing the SET and DOWN key for more than 3 seconds. (Lead with the SET key.)
Pressing the DOWN key, parameters will display in top, and value in bottom. Select Pr2 / PAS (parameter / value), and press the SET key. The lower display will show the value 0 - - with a flashing zero.
Use UP or DOWN keys to input the security code in the flashing digit; confirm each digit by pressing SET. The security code is 321. After hitting SET on the last digit, you will be in the Pr2 menu. Once you have entered the Pr2 menu press the DOWN key to move through the parameters until the Adr parameter appears on the top display.
Now press the SET key once and the value number will begin to blink. Use the arrow key to set the address and then hit the SET key. After hitting the SET, it will automatically go to the next parameter. Let it time out, or cycle power to the TempTrac. Each TempTrac on a RS-485 network must have a unique MODBUS address.
The TempTrac MODBUS adapter port:
The MODBUS adapter is an orange dongle with 2 green screw terminals attached to an 8 inch cable that plugs into the back of the TempTrac at a white header. This can be an option installed on heater, or it may be a separate line item part. When the option is available, it is MBUSC option code. As a standalone part, it is PN: 11807.
Page 3 of 30 PV7069-T 03 /17
Part number 129209
Page 4
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
TEMPTRAC PROTOCOL
The MODBUS RTU protocol is well established industry protocol and technical references for this are readily available on the Internet.
Data Types Used
The TempTrac only uses one data type Holding Registers (40001 – 49999) Read/Write
Other data types such as Coils are not implemented in the TempTrac control. Only the data points in the POINTS LIST should be accessed.
Physical Layer RS-485
MODBUS RTU uses the physical layer RS-485. RS-485 (EIA-485): A 2 wire (twisted pair) multi drop network. Each device can send data by holding positive and negative voltage on the line and reversing polarity on the 2 wires. When no devices are transmitting, the line will be tristate. The recommended arrangement of the wires is as a connected series of point-to ­point (multi-dropped) nodes, i.e. a line or bus, not a star, ring, or multiply connected network. The number of devices that can be connected to a single line is defined in the RS-485 standard by the input impedance of 32 UNIT LOADs. The wire and circuits interfacing on this 2 wire connection is considered the PHYSICAL LAYER. (RS-485 is the same physical layer as used with BACNET MSTP.)
No provisions for biasing resistors or termination resistors are provided on the control. If required, this will need to be provided externally. The PVI gateway does provide optional biasing (default) and can provide a termination resistor, if required.
ITEMS REQUIRED FOR GATEWAY INTERFACE:
One or more water heaters with a TempTrac control (red/orange LED display with 6 tactile buttons) including the RS-485 adapter.
Protonode Gateway with Power supply adapter (when ordering, please specify what protocol is required; BACNET MSTP, BACNET IP, LONWORKS or MODBUS TCP).
Protonode Gateway Manual (Covers general information for the gateway). PV7069-T.PDF Interface manual that covers specifics for interfacing with the TempTrac system. Also
includes the points list for the TempTrac control system. (This document). 120VAC power outlet for the power supply. Computer with web browser and Ethernet connection capability to configure gateway.
ITEMS REQUIRED FOR MODBUS DIRECT INTERACE:
One or more water heaters with a TempTrac control (red/orange LED display with 6 tactile buttons) including the RS-485 adapter.
PV7069-T.PDF Interface manual that covers specifics for interfacing with the TempTrac system. Also includes the points list for the TempTrac control system. (This document).
Page 4 of 30 PV7069-T 03 /17
Part number 129209
Page 5
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Protocol Gateway
TempTrac Front and side view
TempTrac back, showing adapter dongle.
IDENTIFY EQUIPMENT:
The equipment should have a TempTrac mounted on the control panel. The RS-485 adapter may be installed or may ship lose. The gateway and power supply ship lose. The gateway is a grey module that has a wall wart style power supply.
TempTrac is mounted on the control panel of the equipment. On the back side of the TempTrac is a white header. The RS-485 adapter plugs into this with a 8 inch cable. The orange adapter has 2 green terminals labeled (+) & (-).
The Protocol Gateway, if supplied, comes with a power supply and ships as a loose item.
Page 5 of 30 PV7069-T 03 /17
Part number 129209
Page 6
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Gateway
6 Pos. terminal
TempTrac
Orange adapter
TempTrac #2
Orange adapter
Tx/+ (+) (+)
Rx/- (-) (-)
GND
BAS protocol
Connection Port on Gateway
Labeled
BACNET MSTP
3 TERMINAL CONNECTOR
FIELD
BACNET IP
ETHERNET PORT
ETHERNET
LONWORKS
2 TERMINAL CONNECTOR
LonWorks
MODBUS TCP
ETHERNET PORT
ETHERNET
WIRING BAS TO GATEWAY AND THEN GATEWAY TO TEMPTRAC:
Each gateway has 3 connection points. The 6 position terminal block contains connection for power and MODBUS RTU (going to heaters). The Ethernet port is for configuration, BACNET IP, or MODBUS TCP. The 3 or 2 pin terminal is for the BAS interface: BACNET MSTP, or LONWORKS.
Power Connection:
Gateway power supply, 6 position terminal +PWR, -PWR. Use supplied wall wart style power supply. 15VDC. Do not power other devices with same power supply. If power adapter has not already been connected, cut and discard the connector on the end, strip and terminate the power adapter in the proper terminals. Verify polarity. If another supply is to be used, it must be isolated. Do not use 24VAC power from heater.
Gateway Connection to Heaters:
Wiring from Gateway to the heaters, use twisted pair wire. Connector on the orange dongle adapter that is on the end of a 8” cable plugged into the back of the TempTrac.
The wiring is standard 2 wire RS-485 wiring. You will connect all devices together in a daisy chain. We recommend the gateway to be at the start of this connection.
Building Automation Connection:
Page 6 of 30 PV7069-T 03 /17
Part number 129209
Page 7
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Field connection
for BAS
TempTrac
Orange adapter
TempTrac #2
Orange adapter
Testing
VDC
Results for proper
hookup
RS 485 +
(+) (+)
Positive
lead
+ 0.100
To
+ 5.500
RS R85 -
(-) (-)
Negative
lead
GND
WIRING OF TEMPTRAC TO BAS (Direct, no Gateway):
The back side of the TempTrac has a white header with an 8 inch cable, connecting to an orange adapter module with 2 green terminals labeled (+) & (-). This is the RS-485 Modbus connection point.
Ensure the proper polarity, check with a Digital Volt Meter set to Volts DC. Take a reading at the orange adapter from the (-) Terminal to the (+) Terminal. The (+) should be the positive lead when connected.
GATEWAY CONFIGURATION CONNECTION:
Both the LONWORKS and BACNET gateway have an Ethernet port. Connect the computer using a patch cable or cross-over cable to establish a direct connection to the gateway. Older units may require a cross­over cable or two patch cables with an Ethernet switch. If using BACNET IP or MODBUS TCP interface, connect the BAS Ethernet cable to the gateway when configuration is complete.
At this point, each heater and the gateway should all be powered, and have all wiring finished. The RUN LED will toggle every second to indicate the gateway is running.
Page 7 of 30 PV7069-T 03 /17
Part number 129209
Page 8
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Protocol
S0
S1
S2
S3
BACNET IP
OFF
OFF
OFF
OFF
BACNET MSTP
ON
OFF
OFF
OFF
MODBUS TCP
OFF
ON
OFF
OFF
MODBUS RTU
ON
ON
OFF
OFF
Baud
B0
B1
B2
B3
9600
ON
ON
ON
OFF
19200
OFF
OFF
OFF
ON
38400 *
ON
ON
OFF
ON
57600
OFF
OFF
ON
ON
76800
ON
OFF
ON
ON
1 2 4 8 16
32
64 <-sum for address
A0
A1
A2
A3
A4
A5
A6
A7
Address
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF 0 Invalid
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF 1
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF 2
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
3 *
Default
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF 4
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF 5
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF 6
ON
ON
ON
OFF
OFF
OFF
OFF
OFF 7
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF 8
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF 9
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
10 … … … … … … … … … ON
ON
ON
ON
ON
ON
ON
OFF
127
CONFIGURE GATEWAY DIP SWITCHES:
The ON position is toward the center of the module, and OFF is toward the edge of the module. Only the BACNET gateway requires dip switch settings. The BACNET gateway is used for MODBUS TPC also.
DIP SWITCHES S0-3 PROTOCOL
Set Protocol (BACNET and MODBUS gateway only): The gateway protocol is determined on power up by looking at the “S” dip switches. If the protocol is changed, the configuration/profiles must be cleared and reconfigured. This is done with the HTML interface. MODBUS RTU does not require a gateway. LONWORKS: Configured in hardware, no need to adjust dip switches.
DIP SWITCHES B0-4 BAUD
3PIN CONNECTOR TO BAS, Configure BAUD: Default is 38400. Configures the Baud rate for the 3 position terminal block. This is the connection that will connect to the Building Automation System (BAS). This is used only when the protocol is BACNET MSTP.
A0-7 (BACNET MSTP) MAC ADDRESS:
Default is MAC address 3. Configure the MAC address for the BACNET Gateway by
summing the “A” dip switches
that are ON. MAC address range: 1 – 127
Page 8 of 30 PV7069-T 03 /17
Part number 129209
Page 9
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
CONFIGURE THE GATEWAY USING THE HTML INTERFACE:
This section will provide the parameters required for the TempTrac control. For more details of the gateway, consult the gateway manual. Connect your computer’s Ethernet port to the Ethernet port of the gateway. Using a web browser, browse to the gateway at IP address: 192.168.1.24 default (If you have changed the IP address, go to the appropriate address.). If the device IP address has been changed and is not known, a utility is available from Feildserver.com. Contact Fieldserver for more information.
Menu options vary depending on if you are configuring a LONWORKS gateway, BACNET Gateway set for BACNET IP, a BACNET gateway set for BACNET MSTP, or a BACNET gateway set for MODBUS TCP.
Using your browser, set the following and SUBMIT after each change.
MODBUS RTU Baud Rate: 9600 MODBUS RTU Parity: NONE MODBUS RTU Data Bits: 8 MODBUS RTU Stop Bits: 1
(BACNET options)
BACNET Network Number: Must be unique network number on BACNET network BACNET Node Offset: This will be used to create the DEVICE INSTANCE. Sum the device
MODBUS Address and this number. Example 50000 Node Offset + MODBUS address 1 = 50001 Device Instance. Each MODBUS device will have its own Device Instance number. (BACNET MSTP option) BACNET MSTP Max Master: 127 (BACNET IP option)
BACNET IP Port: 47808 (Default) BACNET COV: COV Disable
(BACNET MSTP option)
BACNET BBMD: - (Default “-, enabling this is an advanced feature, not recommended) BACNET Router: NO for 1 water heater, YES for multiple water heaters
SELECT THE DEVICE TYPE (BACNET & LONWORKS):
Press the ADD button, under Node ID enter the MODBUS address of the first heater. Typically you will have the nearest heater setup as MODBUS address 1, and the next heater MODBUS address 2. All heaters ship from factory with MODBUS Address set to 1. Each heater must have a unique MODBUS address. (See previous section Setup heater MODBUS address) Under Current profile, select the proper interface for the TempTrac control. For BACNET Gateway: Select
BAC_IP Temptrac for BACNET IP BAC_MSTP Temptrac for BACNET MSTP
For LONWORKS Gateway: Select LON TempTrac Water Heater Press the Submit button.
Add additional devices as required. After adding all devices, restart the gateway by clicking the SYSTEM RESTART button.
Page 9 of 30 PV7069-T 03 /17
Part number 129209
Page 10
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Pos. (red)
Probe
Neg. (black)
Probe
Min
Max
Actual
Reading
Gateway 6 pin terminal block
+PWR
-PWR
+9.0VDC
+30VDC
Tx/+
Rx/-
+0.1VDC
+5.5VDC
Gateway 3 pin terminal block (BACNET MSTP only)
RS 485 +
RS 485 -
+0.1VDC
+5.5VDC
TempTrac orange dongle (Each heater)
(+)
(-)
+0.1VDC
+5.5VDC
(+)
(-)
+0.1VDC
+5.5VDC
(+)
(-)
+0.1VDC
+5.5VDC
(+)
(-)
+0.1VDC
+5.5VDC
(+)
(-)
+0.1VDC
+5.5VDC
CONFIRM OPERATION:
Heater Communication:
Communication between gateway and heaters is evident by rapid flashing of the TX and RX LEDs on the gateway. If only the TX is flashing (may be as slow as 30 seconds between flashes), that will indicate no response from the heaters.
Building Automation System Communication:
Using the HTML interface, you can confirm some operations and under USER MESSAGES, confirm there are no errors messages. At this point, the BAS will need to discover the gateway and implement the points into its integration.
TROUBLESHOOTING GATEWAY:
ERR Red LED on
o Gateway is reporting an error. o Connect to gateway with HTML interface to view error messages
PWR LED not on
o Confirm power on +PWR and –PWR
TX & RX not flashing
o Confirm connections to heaters and MODBUS addressing o Confirm gateway has been configured
TX flashing, RX not flashing
o Gateway is talking to TempTrac, but not getting response from TempTrac. Confirm wiring,
confirm TempTrac is configured to proper address, Baud, Parity, Stop bits.
Verify polarity of all connections:
Set a Digital Volt Meter to read DC Volts. (Capable of reading less than 1.0VDC)
For advance gateway troubleshooting, reference the gateway manual.
Page 10 of 30 PV7069-T 03 /17
Part number 129209
Page 11
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
BACNET MSTP
LONWORKS
To heaters with
TempTrac
Power Adapter
BACNET IP
MODBUS TCP
To heaters with
TempTrac
Power Adapter
MODBUS RTU
To heaters with
TempTrac
HOOKUP OVERVIEW:
BACNET MSTP or LONWORKS
BACNET IP or MODBUS TCP
OR
OR
MODBUS RTU Direct Connect
Page 11 of 30 PV7069-T 03 /17
Part number 129209
Page 12
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
APPLICATION SPECIFICS:
Each product that uses the TempTrac control may have subtle differences. The following products address the important information regarding each device.
Conquest 100 Gallon (199 – 299) & 130 gallon 399: (Smaller Conquest)
Model Numbers: 20 L 100A-GCL, 25 L 100A-GCL, 30 L 100A-GCL, 40 L 130A-GCL
Probe 1: Is in the top of the tank, and controls the burner Probe 2: Is in the mid-section and controls the agitator pump using Relay3 Probe 3: Is in the flue Alarm_AL2: Alarm on any failure Burner_Relay1: Burner Relay2: Alarm dry contact Relay3: Agitator pump
Discrete connections: External Enable: Terminals R1 – R2, Jumper to enable. Heater ships with jumper on this. An external
enable/disable can be attached to this. This is a low current, low voltage contact. It is advised to use a contact with gold plating. If not available, use 2 contacts in parallel.
Alarm: A1 & A2 (Output from Heater) Closed = ALARM. Remote Proving: C1 & C2. Ships with factory jumper. Open will prevent burner from operating. Keeping
this open will create a lockout condition that will require user intervention. Remote Equipment / Burner ON: Contact that will close P1 – P2 during a heating cycle. Open, the heater is not calling for heat. No Setpoint Input: There is not a discreet method to send a setpoint signal to the Conquest.
Conquest 130 Gallon (500 – 800): (Larger Modulating Conquest)
Model Numbers: 50 L 130A-GCML, 60 L 130A-GCML, 70 L 130A-GCML, 80 L 130A-GCML Same as the smaller Conquest with the addition of modulation.
Modulation Rate: Modulation rate, Low fire = 0, High Fire = 100 Discrete connections:
Same as the smaller Conquest with the following notes: No Modulation Input: There is not discreet way for a building automation system to control the modulation (firing rate) of the Conquest.
Page 12 of 30 PV7069-T 03 /17
Part number 129209
Page 13
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Centauri Boiler, Centauri Plus Boiler, VT3 Boiler:
Model Numbers: All Centauri, Centauri Plus and VT3 Boilers Probe 1: This temperature is displayed in yellow in the lower section of the display.
With SSBCO option, this probe is located in the top of the boiler. Without this option, the probe is shipped uninstalled and should be installed in the BHWR piping to read the temperature of the water entering the boiler. Probe 2: This temperature is displayed in red in the upper section of the display. With SSBCO option, this probe is shipped uninstalled and is intended to be installed in the field in the boiler’s HWR piping. Without the SSBCO option, this probe is installed in the top of the boiler providing the outlet water temperature. Probe 3: Is an Auxiliary probe that can be used for outdoor temperature or other temperature readings. This is optional and not standard.
Alarm_AL3: Alarm on any failure Burner_Relay1: Burner Relay2: Not used Relay3: Isolation Valve control when the OnTrac boiler management system is controlling. Modulation Rate: Modulation rate, Low fire = 0, High Fire = 100
Discrete connections: Ext Enable: Terminals R1 – R2, Jumper to enable. Heater ships with jumper on this. An external
enable/disable can be attached to this. (Recommend relay at boiler, min 10A at 24VAC.) Remote Equipment: P1 & P2, this is a contact that is driven any time a call for heat is present. Note this is only provided if the Remote Equipment or Louver options are present. Alarm: A1 & A2 provide a 3 min alarm signal that is present after a failure to ignite burner for 4 minutes. This output will be active for 3 minute and then the communication alarm will become active dropping the call for heat and dropping this signal. It is possible to get this alarm and the alarm condition that caused this alarm can be corrected before the 3 minutes, removing the alarm and not having a lockout or alarm condition over communication. (3 min signal of alarm condition and potential lockout.)
Page 13 of 30 PV7069-T 03 /17
Part number 129209
Page 14
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
M3 Boiler
Probe 1: Is in the top of the tank, and controls the burner. Provides outlet temperature. Probe 2: Is wired but lose and field installed in the boiler HWR piping. Probe 3: Is in the flue. Alarm_AL2: Alarm on any failure. Burner_Relay1: Burner Relay2: Alarm dry contact, goes to terminals A1 & A2. Relay3: Isolation Valve control, used with OnTrac group control. Terminals labeled
CIRCULATOR 1 & 2.
Modulation Rate: Modulation rate, Low fire = 0, High Fire = 100. Discrete connections:
External Enable: Terminals R1 – R2, Jumper to enable. Heater ships with jumper on
this. An external enable/disable can be attached to this. This is a low current, low voltage contact. It is advised to use a contact with gold plating. If not available, use 2 contacts in parallel.
Alarm: A1 & A2 (Output from Heater) Closed = ALARM. Remote Proving: C1 & C2. Ships with factory jumper. Open will prevent burner from operating. Keeping
this open will create a lockout condition that will require user intervention. Remote Equipment / Burner ON: Contact that will close P1 – P2 during a heating cycle. Open, the heater is not calling for heat.
No Setpoint Input: There is not a discreet method to send a setpoint signal to the M3 boiler. No Modulation Input: There is not discreet way for a building automation system to control the modulation
(firing rate) of the Conquest.
Quickdraw Steam to Water Storage
Probe 1: Lower Sensor Probe 2: Upper Sensor Relay1: Control valve
Reference wiring diagram for more details. Options vary greatly on this product.
Discrete connections: External Enable: Terminals Remote Equipment / Heating: E1 & E2 terminals are closed when heating, and open when not. This is
an option REMEQ. Alarm: A1 & A2 terminals are closed when in Alarm. This is an option REMAL.
Quickdraw Steam to Water Instantaneous
Probe 1: Lower Sensor Probe 2: Upper Sensor Relay1: Control valve
Reference wiring diagram for more details. Options may vary on this product.
Discrete connections: External Enable: Terminals Remote Equipment / Heating: E1 & E2 terminals are closed when heating, and open when not. This is
an option REMEQ.
Alarm: A1 & A2 terminals are closed when in Alarm. This is an option REMAL.
Page 14 of 30 PV7069-T 03 /17
Part number 129209
Page 15
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Other Equipment and Equipment Custom features:
Reference supplied wiring diagram and the I & O Manual. Contact PVI for additional information. Below is a list of other products that can use the TempTrac controller:
Quickdraw Water to water Storage EZ PLATE STORAGE TURBOPOWER 99 TURBOPOWER POWER VT PLUS TRICON MAXIM 3 DURAWATT (With TTRAC option) MAXIM (With TTRAC option) COBREX STORAGE
Page 15 of 30 PV7069-T 03 /17
Part number 129209
Page 16
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Point Name
Read/Write
Short Description
MODBUS
Register Type
Address Offset
MODBUS Address
BACNET
BACNET Name
Object Instance
BACNET Units
LONWORKS
Lon Read name_#
Lon Write name_#
Lon Units
NOTES
TYPICAL POINTS:
Control_CNT
Write
Enable Heater 257=on 1 = off
MODBUS
Holding Register
1280
41281
BACNET
Enable
128100
LONWORKS
nvoCtrl_CNT_#
This can be used to prevent the heater from heating via communication. 257 or 0X0101 = on, 1 or 0x0000 = off The resister cannot be read. The register should only be written to with the values 257 and 1, as it has other undocumented functions.
Setpoint_St1
Read/Write
System Setpoint
MODBUS
Holding Register
768
40769
BACNET
Setpoint_St1
76900
Deg-F
LONWORKS
nvoSP_St1_#
nviSP_St1_#
Deg_F
This is the setpoint for the heater.
Probe 1
Read Only
Controlling Probe Degrees F
MODBUS
Holding Register
256
40257
BACNET
Probe1
25700
Deg-F
LONWORKS
nvoProbe1_#
Deg_F
Probe that provides control of heating. Location can vary depending on equipment and application. See section that discussed the various equipment to determine actual location of probe. Connection on TempTrac is green screw terminals 14 and common 17.
POINTS LIST:
The gateway will provide a full points list, including typical points and advanced points. Normal interface will only require the TYPICAL POINTS. Many points are provided as ADVANCED POINTS and not advised to be used in normal integration. The Advanced Points are present for the purpose of future development and custom applications. Please consult factory if any points not in the TYPICAL POINTS are required.
Key:
LONWORKS shows multiple devices connected with a device number suffix, (#) represent the device. MODBUS address with “:” to designate single bit usage of register. Number following colon represents bit location, 0 is the least significant bit.
TYPICAL POINTS:
The points that are typically used to interface with the heater. Most integrations only require points from this list.
Page 16 of 30 PV7069-T 03 /17
Part number 129209
Page 17
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
TYPICAL POINTS:
Probe 2
Read Only
Probe 2 in degrees F
MODBUS
Holding Register
258
40259
BACNET
Probe2
25900
Deg-F
LONWORKS
nvoProbe2_#
Deg_F
Optional probe on some devices, usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 15 and common 17.
Probe 3
Read Only
Probe 3 in degrees F
MODBUS
Holding Register
260
40261
BACNET
Probe3
26100
Deg-F
LONWORKS
nvoProbe3_#
Deg_F
Optional probe on some devices, not usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 16 and common 17.
Burner Runtime
Read/Write
Burner Runtime Hours 0-65535
MODBUS
Holding Register
848
40849
BACNET
BURNER_HOURS_ou1
84900
Hours
LONWORKS
nvoBrnHr_ou1_ #
nviBrnHr_ou1_#
Hours
NOTE: Number of hours the burner has been enabled. Once it reaches 9999. This can be written to, as a way to reset it.
Modulation Rate
Read Only
Monitor the modulation signal
MODBUS
Holding Register
262
40263
BACNET
Modulation_FR
26300
LONWORKS
nvoMod_FR_#
Modulation rate on the analog output 4-20ma is represented as 0-100. This feature was introduced in Firmware
0.5 (5) and is not available from older TempTrac modules already in the field.
Burner_Relay1
Read Only
Status of burner, Relay1 (Output 1)
MODBUS
Holding Register
2049
42050:0
BACNET
Burner_Relay1
205050
LONWORKS
nvoBrn_Rel1_#
This is Bit 0 of the Relay status word. It is the relay that controls the main heating output. Typically the Burner Status. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0001, if result = 0, relay is off. If result = 1, relay is on.
Alarm_AL2
Read Only
Status of digital input #2 Alarm
MODBUS
Holding Register
3328
43329:11
BACNET
Alarm_AL2
332961
LONWORKS
nvoAlarm_AL2_#
Digital Input #2 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 11 of the ALARM STATUS ALL word. Flashes ‘AL2’ or ‘LP’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x0800 = 0x0800 Alarm is active. = 0x0000 Alarm is not active.
Page 17 of 30 PV7069-T 03 /17
Part number 129209
Page 18
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
TYPICAL POINTS:
Alarm_AL3
Read Only
Status of digital input #3 Alarm
MODBUS
Holding Register
3328
43329:12
BACNET
Alarm_AL3
332962
LONWORKS
nvoAlarm_AL3_#
Digital Input #3 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 12 of the ALARM STATUS ALL word. Flashes ‘AL3’ or ‘HP’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x1000 = 0x1000 Alarm is active. = 0x0000 Alarm is not active.
Com Status
Read Only
Communication Status bit
MODBUS
Input Register
NA
NA
BACNET
Gateway_TT_Com_OK
200
LONWORKS
nvoGwyTTCmOK_#
NOTE: This point is not generated by the heater; it is generated internally by the gateway. It is a status of the communication connection between the gateway and the heater. If active (GOOD), the gateway is talking to the heater. If inactive (NOT_PRESENT) then the gateway does not have good communication with the heater. This point may take up to 3 minutes to register properly after communication is established or interrupted. If this value if reading NOT_PRESENT, then no all over values are suspect, as the device is not communicating. Generally the Gateway will hold the last value received. The only way to ensure you have the current values from the heater is to verify this point is ACTIVE as well.
ALL POINTS INCLUDING ADVANCE:
Control_CNT
Write
Enable Heater 257=on 1 = off
MODBUS
Holding Register
1280
41281
BACNET
Enable
128100
LONWORKS
nvoCtrl_CNT_#
This can be used to prevent the heater from heating via communication. 257 or 0X0101 = on, 1 or 0x0000 = off The resister cannot be read. The register should only be written to with the values 257 and 1, as it has other undocumented functions.
Setpoint_St1
Read/Write
System Setpoint
MODBUS
Holding Register
768
40769
BACNET
Setpoint_St1
76900
Deg-F
LONWORKS
nvoSP_St1_#
nviSP_St1_#
Deg_F
This is the setpoint for the heater.
Setpoint_St1 C
Read/Write
System Setpoint
MODBUS
BACNET
Setpoint_St1_C
76900
Deg-C
LONWORKS
Special BACNET point that converts the Setpoint value to degrees C in the gateway. Not available in LONWORKS or MODBUS.
ALL POINTS INCLUDING ADVANCED:
Points listed below that are not in the TYPICAL POINTS are provided for advanced interface and for custom applications. Contact factory for additional information.
Page 18 of 30 PV7069-T 03 /17
Part number 129209
Page 19
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Hy1
Read
Setpoint Differential
MODBUS
Holding Register
772
40773
BACNET
Hy1
77300
delta-degrees-Fahrenheit
LONWORKS
nvoHy1_#
Differential. (if Hy1 is negative) The heater will begin heating when Probe #1 must fall this far below St1 setpoint, and stay on until the heater reaches St1 setpoint. (If Hy1 is positive) The heater will come on when Probe #1 falls to or below St1 setpoint, and will not turn off until it has reached this far above St1 Setpoint. BACNET and LONWORKS, this point is configured as a read only, with MODBUS, there is no protection from changing this value.
St4
Read Only
Modulation Start
MODBUS
Holding Register
792
40793
BACNET
St4
79300
No Units
LONWORKS
nvoSt4_#
Starting point of modulation. Related to the St1 setpoint. If Probe 1 is above St1 + St4, then Modulation signal will be low fire. If Probe 1 falls below (St1 + St4) then the analog output signal will modulate based on the setting in the SR register. This is set to No Units in BACNET because it can relative to St1 or is can be independent value. Typically it is configured as relative to St1. BACNET and LONWORKS, this point is configured as a read only, with MODBUS, there is no protection from changing this value.
SR
Read
Modulation bandwidth
MODBUS
Holding Register
793
40794
BACNET
SR
79400
delta-degrees-Fahrenheit
LONWORKS
nvoSR_#
Normally this is a negative number. Number of degrees of change in Probe 1 that will modulate from 0 to 100%. St1 + St4 = low fire, St1 + St4 + SR = High Fire. Temperatures above low fire will be low fire, temperatures below high fire will be high fire. In-between, the output will modulate from 4-20mA (0-100%) BACNET and LONWORKS, this point is configured as a read only, with MODBUS, there is no protection from changing this value.
Probe 1
Read Only
Controlling Probe Degrees F
MODBUS
Holding Register
256
40257
BACNET
Probe1
25700
Deg-F
LONWORKS
nvoProbe1_#
Deg_F
Probe that provides control of heating. Location can vary depending on equipment and application. See section that discussed the various equipment to determine actual location of probe. Connection on TempTrac is green screw terminals 14 and common 17.
Probe 2
Read Only
Probe 2 in degrees F
MODBUS
Holding Register
258
40259
BACNET
Probe2
25900
Deg-F
LONWORKS
nvoProbe2_#
Deg_F
Optional probe on some devices, usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 15 and common 17.
Probe 3
Read Only
Probe 3 in degrees F
MODBUS
Holding Register
260
40261
BACNET
Probe3
26100
Deg-F
LONWORKS
nvoProbe3_#
Deg_F
Optional probe on some devices, not usually installed on most devices. If installed and enabled, returns the temperature of the probe in degrees F. Connection on TempTrac is green screw terminals 16 and common 17.
Page 19 of 30 PV7069-T 03 /17
Part number 129209
Page 20
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Probe 1 C
Read Only
Controlling Probe Degrees C
MODBUS
BACNET
Probe1_C
25790
Deg-C
LONWORKS
Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in LONWORKS or MODBUS.
Probe 2 C
Read Only
Probe 2 in degrees C
MODBUS
BACNET
Probe2_C
25990
Deg-C
LONWORKS
Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in LONWORKS or MODBUS.
Probe 3 C
Read Only
Probe 3 in degrees C
MODBUS
BACNET
Probe3_C
26190
Deg-C
LONWORKS
Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in LONWORKS or MODBUS.
Manual Modulation
Read/Write
Force modulation to a level
MODBUS
Holding Register
797
40798
BACNET
PS4
79800
LONWORKS
NvoPS4_#
NviPS4_#
Used to force a modulation rate. Typically used by service tech to make combustion adjustments at a particular firing rate. Normal setting is 101 = Auto. This allows the heater to modulate ad the load requires. If you put a value 0-100, it will force the heater to that firing rate when operating. 0=Low Fire, 100=High Fire Use with caution. Advise allowing the heater do control its own modulation.
ALL
Read/Write
Minimum Temperature Alarm
MODBUS
Holding Register
814
40815
BACNET
ALL
81500
Deg-F
LONWORKS
nvoALL_#
nviALL_#
Deg_F
Minimum temperature for Probe 1. Alarm will be activated if Probe 1 falls below this temperature. See Alarm points.
ALU
Read/Write
Flame Current for proof of flame
MODBUS
Holding Register
815
40816
BACNET
ALU
81600
Deg-F
LONWORKS
nvoALU_#
nviALU_#
Deg_F
Maximum temperature for Probe 1. Alarm will be activated if Probe 1 rises above this temperature. See Alarm points.
Burner Runtime
Read/Write
Burner Runtime Hours 0-65535
MODBUS
Holding Register
848
40849
BACNET
BURNER_HOURS_ou1
84900
Hours
LONWORKS
nvoBrnHr_ou1_ #
nviBrnHr_ou1_#
Hours
NOTE: Number of hours the burner has been enabled. Once it reaches 9999. This can be written to, as a way to reset it.
Page 20 of 30 PV7069-T 03 /17
Part number 129209
Page 21
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Maintenance Reminder
Read/Write
Number of burner cycles 0-9999
MODBUS
Holding Register
851
40852
BACNET
oP1
85200
LONWORKS
nvooP1_#
nvioP1_#
Maintenance feature, set the value to 0.
Output #2 Mode
Read/Write
Output #2 mode, ON, OFF, AUTO
MODBUS
Holding Register
855
40856
BACNET
TT_2on
85600
LONWORKS
nvoTT_2on_ #
nviTT_2on_#
TempTrac relay output spade 6 & 7. 0= Force relay off, 1=Force relay ON, 2= Auto (operates from thermostat functions).
Output #3 Mode
Read/Write
Output #2 mode, ON, OFF, AUTO
MODBUS
Holding Register
856
40857
BACNET
TT_3on
85700
LONWORKS
nvoTT_3on_#
nviTT_3on_#
TempTrac relay output spade 8 & 9. 0= Force relay off, 1=Force relay ON, 2= Auto (operates from thermostat functions).
Software Version
Read Only
Firmware revision
MODBUS
Holding Register
859
40860
BACNET
VERSION_rEL
86000
LONWORKS
nvoVer_rEL_#
Software/Firmware revision number. At time of this manual, current version is 0.5 read as 5.
Modulation Rate
Read Only
Monitor the modulation signal
MODBUS
Holding Register
262
40263
BACNET
Modulation_FR
26300
LONWORKS
nvoMod_FR_#
Modulation rate on the analog output 4-20ma is represented as 0-100. This feature was introduced in Firmware
0.5 (5) and is not available from older TempTrac modules already in the field.
RELAYS Status ALL
Read Only
Shows the current state of the 3 output relays
MODBUS
Holding Register
2049
42050:0,1,2
BACNET
RELAYS
205000
LONWORKS
nvoRELAYS_#
This register contains the relay status for all 3 relays. Bit 0 = relay 1 (4&5), Bit 1 = relay 2 (6&7), Bit 2 = relay 3 (8&9). See below breakout of each relay.
Burner_Relay1
Read Only
Status of burner, Relay1 (Output 1)
MODBUS
Holding Register
2049
42050:0
BACNET
Burner_Relay1
205050
LONWORKS
nvoBrn_Rel1_#
This is Bit 0 of the Relay status word. It is the relay that controls the main heating output. Typically the Burner Status. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0001, if result = 0, relay is off. If result = 1, relay is on.
Page 21 of 30 PV7069-T 03 /17
Part number 129209
Page 22
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Relay2
Read Only
Status of Relay2 (Output 3)
MODBUS
Holding Register
2049
42050:1
BACNET
Relay2
205051
LONWORKS
nvoRelay2_#
This is Bit 1 of the Relay status word. It is the output #2 relay. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0002, if result = 0, relay is off. If result = 2, relay is on.
Relay3
Read Only
Status of Relay3 (Output 3)
MODBUS
Holding Register
2049
42050:2
BACNET
Relay3
205052
LONWORKS
nvoRelay3_#
This is Bit 2 of the Relay status word. It is the output #3 relay. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break it out yourself. Read value, BITWISE AND with 0x0004, if result = 0, relay is off. If result = 4, relay is on.
ALARM STATUS ALL
Read Only
ALL ALARMS STATUS
MODBUS
Holding Register
3328
43329
BACNET
DIA
332900
LONWORKS
nvoDIA_#
Alarm word, each bit represent separate alarms.
Alarm_LA
Read Only
Status of low temperature Alarm
MODBUS
Holding Register
3328
43329:0
BACNET
Alarm_LA
332950
LONWORKS
nvoAlarm_LA_#
Low water temperature alarm. Probe 1 is lower than temperature in ALL point. This is Bit 0 of the ALARM STATUS ALL word. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x0001 = 0x0001 Alarm is active. = 0x0000 Alarm is not active.
Alarm_HA
Read Only
Status of high temperature Alarm
MODBUS
Holding Register
3328
43329:1
BACNET
Alarm_HA
332951
LONWORKS
nvoAlarm_HA_#
High water temperature alarm. Probe 1 is higher than temperature in ALU point. This is Bit 1 of the ALARM STATUS ALL word. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x0002 = 0x0002 Alarm is active. = 0x0000 Alarm is not active.
Alarm_P1
Read Only
Status of Probe 1 Alarm
MODBUS
Holding Register
3328
43329:2
BACNET
Alarm_P1
332952
LONWORKS
nvoAlarm_P1_#
Probe 1 alarm. This can be a disconnected, open or shorted probe. This will shut down heating operation. This
is Bit 2 of the ALARM STATUS ALL word. Flashes ‘P1’ on TempTrac display. In BACNET and LONWORKS,
this is broken out into a state logic point. For MODBUS ALARMS && 0x0004 = 0x0004 Alarm is active. = 0x0000 Alarm is not active.
Page 22 of 30 PV7069-T 03 /17
Part number 129209
Page 23
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Alarm_P2
Read Only
Status of Probe 1 Alarm
MODBUS
Holding Register
3328
43329:8
BACNET
Alarm_P2
332958
LONWORKS
nvoAlarm_P2_#
Probe 2 alarm. This can be a disconnected, open or shorted probe. This is Bit 8 of the ALARM STATUS ALL
word. Flashes ‘P2’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic
point. For MODBUS ALARMS && 0x0100 = 0x0100 Alarm is active. = 0x0000 Alarm is not active.
Alarm_P3
Read Only
Status of Probe 1 Alarm
MODBUS
Holding Register
3328
43329:9
BACNET
Alarm_P3
332959
LONWORKS
nvoAlarm_P3_#
Probe 3 alarm. This can be a disconnected, open or shorted probe. This is Bit 9 of the ALARM STATUS ALL word. Flashes ‘P3’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x0200 = 0x0200 Alarm is active. = 0x0000 Alarm is not active.
Alarm_AL1
Read Only
Status of digital input #1 Alarm
MODBUS
Holding Register
3328
43329:10
BACNET
Alarm_AL1
332960
LONWORKS
nvoAlarm_AL1_#
Digital Input #1 alarm. This is typically not implemented. Refer to product specific details for information on this alarm. This is Bit 10 of the ALARM STATUS ALL word. Flashes ‘AL1’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x0400 = 0x0400 Alarm is active. = 0x0000 Alarm is not active.
Alarm_AL2
Read Only
Status of digital input #2 Alarm
MODBUS
Holding Register
3328
43329:11
BACNET
Alarm_AL2
332961
LONWORKS
nvoAlarm_AL2_#
Digital Input #2 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 11 of the ALARM STATUS ALL word. Flashes ‘AL2’ or ‘LP’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x0800 = 0x0800 Alarm is active. = 0x0000 Alarm is not active.
Alarm_AL3
Read Only
Status of digital input #3 Alarm
MODBUS
Holding Register
3328
43329:12
BACNET
Alarm_AL3
332962
LONWORKS
nvoAlarm_AL3_#
Digital Input #3 alarm. On some products, this is a general failure to operate alarm. See product specific information. This is Bit 12 of the ALARM STATUS ALL word. Flashes ‘AL3’ or ‘HP’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x1000 = 0x1000 Alarm is active. = 0x0000 Alarm is not active.
Page 23 of 30 PV7069-T 03 /17
Part number 129209
Page 24
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
ALL POINTS INCLUDING ADVANCE:
Alarm_Nn1
Read Only
Maintenance Alarm for output #1
MODBUS
Holding Register
3328
43329:13
BACNET
Alarm_Nn1
332963
LONWORKS
nvoAlarm_Nn1_#
Maintenance Alarm. This is enabled when the time on ou1 is greater than the value in oP1. Flashes ‘Nn1’ on
TempTrac display. Bit #13 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x2000 = 0x2000 Alarm is active. = 0x0000 Alarm is not active.
Alarm_Nn2
Read Only
Maintenance Alarm for output #2
MODBUS
Holding Register
3328
43329:14
BACNET
Alarm_Nn2
332963
LONWORKS
nvoAlarm_Nn2_#
Maintenance Alarm. This is enabled when the time on ou2 is greater than the value in oP2. Flashes ‘Nn2’ on
TempTrac display. Bit #14 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x4000 = 0x4000 Alarm is active. = 0x0000 Alarm is not active.
Alarm_Nn3
Read Only
Maintenance Alarm for output #3
MODBUS
Holding Register
3328
43329:15
BACNET
Alarm_Nn3
332963
LONWORKS
nvoAlarm_Nn3_#
Maintenance Alarm. This is enabled when the time on ou3 is greater than the value in oP3. Flashes ‘Nn3’ on TempTrac display. Bit #15 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point. For MODBUS ALARMS && 0x8000 = 0x8000 Alarm is active. = 0x0000 Alarm is not active.
Com Status
Read Only
Communication Status bit
MODBUS
Input Register
NA
NA
BACNET
Gateway_TT_Com_OK
200
LONWORKS
nvoGwyTTCmOK_#
NOTE: This point is not generated by the heater; it is generated internally by the gateway. It is a status of the communication connection between the gateway and the heater. If active (GOOD), the gateway is talking to the heater. If inactive (NOT_PRESENT) then the gateway does not have good communication with the heater. This point may take up to 3 minutes to register properly after communication is established or interrupted. If this value if reading NOT_PRESENT, then no all over values are suspect, as the device is not communicating. Generally the Gateway will hold the last value received. The only way to ensure you have the current values from the heater is to verify this point is ACTIVE as well.
Page 24 of 30 PV7069-T 03 /17
Part number 129209
Page 25
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
ADVANCED MODBUS LIST:
The following is the direct MODBUS interface addresses. Descriptions of most to the MODBUS parameters are listed in the correlating TYPICAL POINTS defined previously. Many MODBUS parameters are not supported in the gateway interface. This is a complete reference list and contains advanced parameters. All MODBUS points normally required for interface are represented in the TYPICAL POINTS section. If there is a need for interfacing using other parameters, consult factory to confirm proper use.
Page 25 of 30 PV7069-T 01/05/16
Part number 129209
Page 26
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
Label
Firm
Description
Range
Rev
0.3
Rev
0.5
Hex Add Modbus
Register
Version
X÷Y
Level
Level
base 0
40000+
St1
0.3 & 0.5
Set point1 LS1÷US1
Pr1
Pr1
0x300
769
St2
0.3 & 0.5
Set point2 LS2÷US2
Pr1
Pr1
0x301
770
St3
0.3 & 0.5
Set point3 LS3÷US3
Pr1
Pr1
0x302
771
St5
0.3 & 0.5
Set point5 Set point 3 alternate
-20÷70°F
Pr1
Pr1
0x303
772
HY1
0.3 & 0.5
Differential for St1
-22÷22°F
Pr2
Pr2
0x304
773
LS1
0.3 & 0.5
Minimum set point1
-40°F÷SET
Pr2
Pr2
0x305
774
US1
0.3 & 0.5
Maximum set point1 SET ÷ 230°F
Pr2
Pr2
0x306
775
AC1
0.3 & 0.5
Anti-short cycle delay for output 1 0÷30 min.
Pr2
Pr2
0x307
776
S2c
0.3 & 0.5
Configuration of St2: dependent on St1 or independent
diP; ind
Pr3
Pr2
0x308
777
HY2
0.3 & 0.5
Differential for St2
-22÷22°F
Pr2
Pr2
0x309
778
LS2
0.3 & 0.5
Minimum set point2
-40°F÷St2
Pr2
Pr2
0x30A
779
uS2
0.3 & 0.5
Maximum set point2 St2 ÷ 230°F
Pr2
Pr2
0x30B
780
AC2
0.3 & 0.5
Anti-short cycle delay for output 2 0÷30 min.
Pr2
Pr2
0x30C
781
S3c
0.3 & 0.5
Configuration of St3: dependent on St1 or independent
diP; ind
Pr2
Pr2
0x30D
782
HY3
0.3 & 0.5
Differential for set point 3 St3
-22÷22°F
Pr2
Pr2
0x30E
783
LS3
0.3 & 0.5
Minimum set point 3 St3
-40°F÷St3
Pr2
Pr2
0x30F
784
uS3
0.3 & 0.5
Maximum set point 3 St3 St3 ÷ 230°F
Pr2
Pr2
0x310
785
AC3
0.3 & 0.5
Anti-short cycle delay for output 3 0÷30 min.
Pr2
Pr2
0x311
786
o3P
0.3 & 0.5
Probe selection for output 3 Pb1 / Pb2
Pr2
Pr2
0x312
787
SSE
0.3 & 0.5
Set point shift for output 3 enable disable No; Yes
Pr2
Pr2
0x313
788
HY5
0.3 & 0.5
Differential for set point 5
-22÷22°F
Pr2
Pr2
0x314
789
Ac5
0.3 & 0.5
Anti-short cycle delay for output 3 alternate set point 0÷30 min.
Pr2
Pr2
0x315
790
AcA
0.3 & 0.5
Time delay between the St3 to St5 set point shift 0÷15 min.
Pr2
Pr2
0x316
791
ANALOGUE OUTPUT 4÷20mA (output 4)
S4c
0.3 & 0.5
Configuration of St4: dependent on St1 or independent
diP; ind
Pr3
Pr2
0x317
792
St4
0.3 & 0.5
Analogue output set point
-100÷100°F
Pr2
Pr2
0x318
793
SR
0.3 & 0.5
Analogue output band width
-100÷100°F
Pr2
Pr2
0x319
794
Th4
0.3 & 0.5
Outlet temperature threshold for forcing to 4ma the analog output
-40°F ÷ 230°F
Pr2
Pr2
0x31A
795
HY4
0.3 & 0.5
Differential for restart working of analog output
-45 ÷ -1 °F
Pr2
Pr2
0x31B
796
Ac4
0.3 & 0.5
Anti-short cycle delay for output 4 0÷30 min.
Pr2
Pr2
0x31C
797
PS4
0.3 & 0.5
Analog output percentage (nu=101) 0÷100, nu
Pr2
Pr2
0x31D
798
PP4
0.3 & 0.5
Analog output percentage with fault probe 1 (nu=101)
0÷100, nu
Pr3
Pr2
0x31E
799
DYNAMIC RESET
tt
0.3 & 0.5
Outdoor temperature threshold for dynamic reset of St1
-40÷230°F
Pr2
Pr2
0x31F
800
rr2
0.3 & 0.5
Outdoor temperature band width
-100÷100°F
Pr2
Pr2
0x320
801
Page 26 of 30 PV7069-T 01/05/16
Part number 129209
Page 27
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
rr1
0.3 & 0.5
Maximum shift of St1
-100÷100°F
Pr2
Pr2
0x321
802
tt2
0.3 & 0.5
Outdoor temperature threshold to open all the loads
-40÷230°F
Pr2
Pr2
0x322
803
Ht2
0.3 & 0.5
Differential for restart working of controller
-45 ÷ -1 °F
Pr2
Pr2
0x323
804
DIGITAL INPUTS
i1P
0.3 & 0.5
Digital input 1 polarity CL÷OP
Pr3
Pr2
0x324
805
i2P
0.3 & 0.5
Digital input 2 polarity CL÷OP
Pr2
Pr2
0x325
806
i2d
0.3 & 0.5
Digital input 2 alarm delay 0÷255 min.
Pr3
Pr2
0x326
807
i3P
0.3 & 0.5
Digital input 3 polarity CL÷OP
Pr2
Pr2
0x327
808
i3d
0.3 & 0.5
Digital input 3 alarm delay 0÷255 min.
Pr3
Pr2
0x328
809
DISPLAY
cF
0.3 & 0.5
Temperature measurement unit °C ÷ °F
Pr3
Pr2
0x329
810
rES
0.3 & 0.5
Resolution (integer/decimal point) only for °C in ÷ de
Pr3
Pr2
0x32A
811
dS2
0.3
Default showing for display #2 Top (red) Pb2, Pb3
Pr2
0x32B
812
dS2
0.5
Default showing for display #2 Top (red) Pb3 will display yellow EXT, Ani will display yellow Valve/M Pb1,Pb2,Pb3,AnI
Pr2
0x32B
812
dS1
0.3
Default showing for display #1 Bottom (Yellow) Pb1; tiM
Pr2
0x32C
813
dS1
0.5
Default showing for display #1 Bottom (Yellow) Pb3 will display yellow EXT, Ani will display yellow Valve/M Pb1,Pb2,Pb3,AnI, TiM
Pr2
0x32C
813
ALARMS
Alc
0.3 & 0.5
Temperature alarms configuration: dependent on St1 or independent rE÷Ab
Pr3
Pr2
0x32D
814
ALL
0.3
minimum temperature alarm for Pb1 (Alarm LA flash only)
-40÷230°F
Pr2
Pr2
0x32E
815
ALL
0.5
minimum temperature alarm for Pb1 (Alarm LA flash and signal on 3329)
-40÷230°F
Pr2
Pr2
0x32E
815
Alu
0.3
MAXIMUM temperature alarm for Pb1 (Alarm HA flash only)
-40÷230°F
Pr3
Pr2
0x32F
816
Alu
0.5
MAXIMUM temperature alarm for Pb1 (Alarm HA flash and signal on 3329)
-40÷230°F
Pr3
Pr2
0x32F
816
AFH
0.3 & 0.5
Differential for temperature alarm recovery 1÷45°F
Pr2
Pr2
0x330
817
ALd
0.3 & 0.5
Temperature alarm delay 0÷255 min.
Pr2
Pr2
0x331
818
dAo
0.3 & 0.5
Delay of temperature alarm at start up 1 = 10 min disp 0.1
0 ÷ 23h 50 min.
Pr2
Pr2
0x332
819
ANALOGUE INPUTS
oF1
0.3 & 0.5
First probe calibration
-21÷21°F
Pr3
Pr2
0x333
820
P2P
0.3 & 0.5
Second probe presence No; Yes
Pr2
Pr2
0x334
821
oF2
0.3 & 0.5
Second probe calibration
-21÷21°F
Pr3
Pr2
0x335
822
P3P
0.3 & 0.5
Third probe presence No; Yes
Pr2
Pr2
0x336
823
oF3
0.3 & 0.5
Third probe calibration
-21÷21°F
Pr3
Pr2
0x337
824
TIME AND DATE
Page 27 of 30 PV7069-T 01/05/16
Part number 129209
Page 28
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
Hur
0.3 & 0.5
Current hour 0 ÷ 23
Pr2
Pr2
0x338
825
Min
0.3 & 0.5
Current minute 0 ÷ 59
Pr2
Pr2
0x339
826
dAY
0.3 & 0.5
Current day Sun ÷ SAt
Pr2
Pr2
0x33A
827
ENERGY SAVING TIMES
E1
0.3 & 0.5
Energy saving start on Sunday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x33B
828
S1
0.3 & 0.5
Energy saving stop on Sunday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x33C
829
Sb1
0.3 & 0.5
Set back temperature on Sunday
-40÷40°F
Pr2
Pr2
0x33D
830
E2
0.3 & 0.5
Energy saving start on Monday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x33E
831
S2
0.3 & 0.5
Energy saving stop on Monday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x33F
832
Sb2
0.3 & 0.5
Set back temperature on Monday
-40÷40°F
Pr2
Pr2
0x340
833
E3
0.3 & 0.5
Energy saving start on Tuesday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x341
834
S3
0.3 & 0.5
Energy saving stop on Tuesday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x342
835
Sb3
0.3 & 0.5
Set back temperature on Tuesday
-40÷40°F
Pr2
Pr2
0x343
836
E4
0.3 & 0.5
Energy saving start on Wednesday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x344
837
S4
0.3 & 0.5
Energy saving stop on Wednesday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x345
838
Sb4
0.3 & 0.5
Set back temperature on Wednesday
-40÷40°F
Pr2
Pr2
0x346
839
E5
0.3 & 0.5
Energy saving start on Thursday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x347
840
S5
0.3 & 0.5
Energy saving stop on Thursday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x348
841
Sb5
0.3 & 0.5
Set back temperature on Thursday
-40÷40°F
Pr2
Pr2
0x349
842
E6
0.3 & 0.5
Energy saving start on Friday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x34A
843
S6
0.3 & 0.5
Energy saving stop on Friday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x34B
844
Sb6
0.3 & 0.5
Set back temperature on Friday
-40÷40°F
Pr2
Pr2
0x34C
845
E7
0.3 & 0.5
Energy saving start on Saturday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x34D
846
S7
0.3 & 0.5
Energy saving stop on Saturday 0 ÷ 23h 50 min. - nu
Pr2
Pr2
0x34E
847
Sb7
0.3 & 0.5
Set back temperature on Saturday
-40÷40°F
Pr2
Pr2
0x34F
848
WORKING HOURS
ou1
0.3 & 0.5
working hours actual of relay 1 0÷9999 Hours
Pr1
Pr2
0x350
849
ou2
0.3 & 0.5
working hours actual of relay 2 0÷9999 Hours
Pr1
Pr2
0x351
850
ou3
0.3 & 0.5
working hours actual of relay 3 0÷9999 Hours
Pr2
Pr2
0x352
851
oP1
0.3 & 0.5
working hours limit of relay 1, Nn1 Alarm when reached
0÷9999, 0=disabled
Pr2
Pr2
0x353
852
oP2
0.3 & 0.5
working hours limit of relay 2, Nn2 Alarm when reached
0÷9999, 0=disabled
Pr2
Pr2
0x354
853
oP3
0.3 & 0.5
working hours limit of relay 3, Nn3 Alarm when reached
0÷9999, 0=disabled
Pr2
Pr2
0x355
854
OUTPUTS SETTING
1on
0.3 & 0.5
The output 1 force ON / OFF or Temperature regulation
rEG=2; on=1; oFF=0
Pr2
Pr2
0x356
855
2on
0.3 & 0.5
The output 2 force ON / OFF or Temperature regulation
rEG=2; on=1; oFF=0
Pr2
Pr2
0x357
856
3on
0.3 & 0.5
The output 3 force ON / OFF or Temperature regulation
rEG=2; on=1; oFF=0
Pr2
Pr2
0x358
857
OTHER
Page 28 of 30 PV7069-T 01/05/16
Part number 129209
Page 29
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
Adr
0.3 & 0.5
Serial address 0÷247
Pr2
Pr2
0x359
858
Ptb
0.3 & 0.5
Parameter map code always = 1 readable only
Pr2
Pr2
0x35A
859
rEL
0.3 & 0.5
Software release 5 = V0.5, 3 = V0.3 readable only
Pr2
Pr2
0x35B
860
i1S
0.5
Analog output when Digital Input 1 is activated 4-20mA Pr2
0x35C
861
i1t
0.5
Analog output at i1S extra time if Digital Input 1 is not activated 0÷30 sec.
Pr2
0x35D
862
i1d
0.5
Digital Input 1 Alarm Delay 0÷255 min.
Pr2
0x35E
863
i1F
0.5
If Yes, Digital Input 1 will function as Alarm. Operating only when trying to call for output 1 and Input 1 is active, subject to i1d timer
No; Yes Pr2
0x35F
864
i2F
0.5
Digital Input 2 will function only when Output 1 is energized
No; Yes Pr2
0x360
865
i3F
0.5
Digital Input 3 will function only when Output 1 is energized, When Edi is selected, Output 1 will open when digital input 3 is activated
No; Yes; Edi
Pr2
0x361
866
oS2
0.5
Output 2 function: either temp relay or alarm relay Std; AL Pr2
0x362
867
(TP1)
0.3 & 0.5
Probe 1 temperature Degrees F/C
Pr2
0x100
257
0.3
Probe 1 Information/Status Normal=512 or 0x0200, Fault=515 or 0x0203. Fault will, drop call for heat, buz, Flash Yellow P1, light yellow valve/M
bit (0,1 on) probe failure
Pr2
0x101
258
(TP2)
0.3 & 0.5
Probe 2 temperature Degrees F/C
Pr2
0x102
259
0.3
Probe 2 Information/Status Normal=512 or 0x0200, Fault=515 or 0x0203. Fault will buz, Flash Red P2 bit (0,1 on) probe failure
Pr2
0x103
260
(TP3)
0.3 & 0.5
Probe 3 temperature Degrees F/C
Pr2
0x104
261
0.3
Probe 3 Information/Status Normal=512 or 0x0200, Fault=515 or 0x0203. Fault will buz, Flash Red P3 bit (0,1 on) probe failure
Pr2
0x105
262
0.5
Modulation rate output (4 to 20mA) 0÷100% Pr2
0x106
263
0.3 & 0.5
Statas of Relay 1,2&3 bit 0,1,2 Pr2
0x801
2050
0.3
Input 3 Alarm, buz, ALMMB, Flashes HP= 4096 or 0x0800
bit # 12 or 13th bit
Pr2
0xD00
3329
0.3
Input 2 Alarm, buz, Flashes LP= 4096 or 0x0800 bit # 12 or 13th bit
Pr2
0xD00
3329
0.3
Input 2 & 3, buz, Flashed HP & LP= 4096 or 0X0800 bit # 12 or 13th bit
Pr2
0xD00
3329
0.5
Low Temperature Alarm, beep, Flash Yellow LA= 1 or 0x0001
bit # 0 or 1st bit
Pr2
0xD00
3329
0.5
High Temperature Alarm, beep, Flash yellow HA= 2 or 0x0002
bit # 1 or 2nd bit
Pr2
0xD00
3329
0.5
Probe 1 error, open or shorted, Drops call for heat, yel valve/M on, Flash Yellow P1=4 or 0x0004 bit # 2 or 3rd bit
Pr2
0xD00
3329
0.5
Probe 2 error, open or shorted, Flashing red P2=256 or 0x0100
bit # 8 or 9th bit
Pr2
0xD00
3329
0.5
Probe 3 error, open or shorted, Flashing red P3=512 or 0x0200
bit # 9 or 10th bit
Pr2
0xD00
3329
0.5
ALARM 1 (stops heating) Input 1, beep, Flash AL1 = 1024 or 0x0400. Will recover if Input 1 goes away, or need for call for heat goes away
bit # 10 or 11th bit
Pr2
0xD00
3329
Page 29 of 30 PV7069-T 01/05/16
Part number 129209
Page 30
TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
0.5
ALARM 2 (Lockout, stops heating) Input 2, Flash AL2 & Lguage & valve= 2048 or 0x1000 bit # 11 or 12th bit
Pr2
0xD00
3329
0.5
ALARM 3 (Lockout, stops heating) Input 3/ALMMB/ALOAF, beep, Flash AL3 & Hguage & valve (This is ALARM ON ANY FAILURE)= 4096 or 0x0800
bit # 12 or 13th bit
Pr2
0xD00
3329
0.5
Maintenance Relay1, beep, Flash Nn1 & wrench=8192 or 0x2000 You must reset hours ou1 or set oP1=0
bit # 13 or 14th bit
Pr2
0xD00
3329
0.5
Maintenance Relay2, beep, Flash Nn2 & wrench=16384 or 0x4000 You must reset hours ou2 or set oP2=0
bit # 14 or 15th bit
Pr2
0xD00
3329
0.5
Maintenance Relay3, beep, Flash Nn3 & wrench=32768 or 0x8000 You must reset hours ou3 or set oP3=0
bit # 15 or 16th bit
Pr2
0xD00
3329
0.3 & 0.5
On/Off On=257 or 0x0101, Off=1 or 0x0001 Can be used to reset ALMMB alarm by cycling OFF, wait 30 sec , ON
Low byte is mask, Hi byte is command. Bit # 0 & #8
Pr2
0x500
1281
0.3 & 0.5
Keyboard Lock Lock=2056 or 0x0808, Unlock=8 or 0x0008. If locked PoF is displayed when keypad edit is attempted
Low byte is mask, Hi byte is command. Bit # 3 & #11 Pr2
0x500
1281
0.3 & 0.5
Reset audible alarm when condition is corrected, 4112 or 0x1010 does not reset alarm, just stops the beeping
Low byte is mask, Hi byte is command. Bit # 3 & #12 Pr2
0x500
1281
Energy Savings Registers are enumerated 0 to 145 w/145=n/u
10 min each with 145=nu
All other enumerations start at 0 and count up
Page 30 of 30 PV7069-T 01/05/16
Part number 129209
Loading...