PVI Industries PV 6126b User Manual

SPECIFICATION FOR DOMESTIC WATER HEATERS
Atmospheric Combustion, Gas-Fired Water Heaters
with Nickel-Plated Storage Tanks
Furnish and install atmospheric gas water heater(s) as manufactured by PVI Industries, L.L.C. of Fort Worth, Texas. Supply quantities and model numbers as indicated on the plumbing schedule.
Gas and Electrical Consumption
Pressure Vessel and Heating Surfaces
The water heater will be a vertical fire tube design that is constructed and stamped in acco rdance with Section IV, Part HLW of the ASME code. Both the storage and heating sections of the water heater will be National Board Registered for a working pressure of 150 psi and will be pressure tested at 1-1/2 times working pressure. The fireside of the heating surfaces will be of boiler-grade steel. The waterside of the heating tubes will be sealed in copper. The heating tubes will be rolled, beaded, and seal welded into the tube sheets. The combustion side of the tube sh eet will be insulated by a layer of ceramic fiber that will protect the tube sheet from both thermal stresses and failure that can result from the accumulation of scale and precipitants.
Tank Lining
The tank will be a plated with electroless nickel (EN). Plating will occur after the pressure vessel is completely fabricated and all welding is completed. The EN plating will be a high-phosphorus (10%) and nonporous composition suitable for submersion service (ASTM B733 standard ma y be used as a guideline). The finished lining will not req uire sacrificial anode rods. For additional protection against galvanic corrosion, which ma y occur within the potable water system, the EN plating may have a high-dielectric-strength polymer overcoat.
Burner and Venting
Combustion will be provided by an atmospheric burner with a gas train meeting the following agency requirement for the input specified:
___ UL (standard) ____ FM ___ IRI ___ Other ______________________ Water heater will be a category 1, non-condensing appliance. It will be UL-listed for use with non-pressurized, type
B venting material.
(continued)
PV 6126b 6/01 1
SPECIFICATION FOR DOMESTIC WATER HEATERS
Atmospheric Combustion, Gas-Fired Water Heaters
with Nickel-Plated Storage Tanks
(continued)
Safety Controls
As a minimum
electronic flame monitoring
two immersion operating thermostats
an immersion temperature limiting device
an _____ ASME- or _____ AGA-rated temperature and pressure relief valve
and options selected on form PV 6070
The burner and all heater parts will have a one-year warranty. Storage tank, heating surfaces, and combustion chamber will have a ten-year warranty covering manufacturing or material defects, leaks, and/or the production of rusty water. Tank and heating surfaces will have a three-year warranty against failure d ue to scale buildup with no provisions for periodic cleaning. The heater will have a _____ first year or ____ long-life service policy, which will cover replacement labor and freight costs under certain conditions. Initiation and /or continuation of warranty coverage will not dependent upon annual inspections, regular replacement of anode rods, or water chemistry. Complete copies of all warranties and service policies, including all exclusions and conditions, will be presented to the owner as part of the submittal package. These summaries are not warranties. Consult warranty and policies for full details.
The storage and heating sections will be completely factory packaged, requiring only job site hookup to utilities, venting, and plumbing. The heater will be insulated, jacketed with enameled steel panels, and mounted on heavy-duty channel skids. The heater will fit properly in the space provided and installation will conform to all local, state, and national codes.
Start up on the unit will be performed by factory trained and authorized personnel. A copy of the start up report will be provided to the owner.
The heater will be have an independent test laboratory listing to safety standard UL 795 or ANSI Z21.10.3. The water heaters will be manufactured by a company that has achieved certification to the ISO 9001 International Qualit y System.
, the heater will be equipped with the following:
Warranty Summary
be
Finishing
Start Up
Quality Certification and Safety Standards
PV 6126b 6/01 2
Loading...