PVI Industries PV 413A User Manual

START-UP OF POWER VT
®
WATER HEATERS OR BOILERS
**FOR DETAILED INFORMATION SEE INSTALLATION & MAINTENANCE MANUAL **
1. Check the water heater tank to make sure it is full of water. (Remove air through T&P valve)
2. Remove enclosure panel cover on the water heater to expose control circuit. A wiring diagram, included in this packet, will show the controls used in our circuitry.
3. Visually check that all components are intact and no damage has occurred during transit.
4. Check all connections within the control cabinet. A loose connection could cause intermittent shutdowns.
5. Check flue gases with an electronic flue analyzer to make final settings of gas pressure regulator.
6. The readings need to be taken from a hole in the vent several inches downstream of the fan outlet connection.
7. Insert 0-6" W.C. manometer into the test opening in the vent. Pressure in stack should not exceed 2" W.C.
8. When water in tank is above 120°F, insert analyzer or O
9. Increase manifold gas pressure at the main gas pressure regulator taking O regulator until optimum O where the greatest reading is achieved.
10. CO should not exceed 200 ppm. A reading greater than 200 ppm indicates lack of air. Reduce manifold gas pressure slightly and take readings until CO is within proper range. Optimum reading is no CO.
11. If manifold pressure was changed during startup, take a final CO and O
12. Record CO
13. Insert vent temperature gauge in test opening and read gross vent temperature; maximum gross stack is to be 250°F. If an excessively high gross vent temperature is recorded, consult the factory.
14. Check each operating and limit control to be sure they function properly by lowering and raising the temperature setting on each of the controls, causing burner to cycle on and off.
15. NOTE: During the initial firing of the burner, smoke that is not related to the burner will be emitted from the heater. This is normal during "burn in" and could possibly continue for several hours.
16. Complete the attached startup report.
and NOx if applicable. (See I&M if NOx measurement is required).
2
% (5-7%) is reached. If O2% decreases, reduce the gas pressure to last reading
2
testing in test opening; take O2 reading in percentage.
2
reading at each adjustment of gas
2
reading.
2
Important – Contact PVI Customer Service, 800-433-5654, if any recommended setpoint or analysis reading falls outside of the recommended ranges before completing startup.
PV 413A 8/05
START-UP REPORT
POWER VT
Warning: Startup must be performed by a qualified service installer, service agency or the gas supplier.
Model Number:
®
WATER HEATERS OR BOILERS
Serial Number: Job Name: Address:
GENERAL INFORMATION
Restart? Yes No Installation is: New Replacement/Renovation Indoor Outdoor Primary operating voltage supply: VAC Voltage from neutral to earth ground: (should be zero) Thermostat Setting: °F Thermostat Setting: °F Hi-Limit Setting °F Is the T & P Relief Valve plumbed to a suitable drain? Yes No
BOILER INSTALLATIONS (Closed Loop Heating System)
Boiler water supply and return piping size Is there a Primary (boiler bypass) loop? Yes No Primary (boiler bypass) loop contains: Modulating 3-way valve Manual valve No valve What is the horsepower of the primary (boiler loop) circulator pump? VFD? Yes No What is the location of the primary circulator pump? Downstream from boiler Upstream from boiler Is there a balancing valve (circuit setter) in the primary loop? Yes No Supply water temperature: °F Return water temperature: °F What is the horsepower of the secondary (main heating loop) circulator pump? VFD? Yes No What is the location of the secondary circulator pump? Downstream from boiler Upstream from boiler Is there a balancing valve (circuit setter) in the secondary loop? Yes No
WATER HEATER INSTALLATIONS
Type of piping connected to heater: Copper Brass Galvanized Is there a check valve in the supply water piping? Yes No Is there a water softener on the cold water supply? Yes No Operational? Yes No Is there a mixing valve on the hot water supply? If yes; temperature setting: °F No Is there expansion relief in the cold water supply? If yes, what type: tank valve No Is there a recirculation loop? Yes Circulating pump horsepower: No Is there a floor drain in the room? Yes No
PV 413 8/05 817-335-9531 800-433-5654 FAX 800-880-2019 www.pvi.com
Page 1 of 2
Loading...
+ 1 hidden pages