PVI Industries M8414TM-COM, M8416TM-COM Operation & Maintenance Manual

Operation & Maintenance Manual
AquaSolve
®
Anti-Scale Systems Chemical-Free, Salt-Free Scale Prevention
M8414TM-COM (50 GPM) M8416TM-COM (75 GPM)
Important: Read this Manual BEFORE using this equipment. Failure to read and follow all safety and use information can result in death, serious personal injury, property damage, or damage to the equipment. Keep this Manual for future reference.
IOM-ASM1465TM_M1665TM
Manufacturing ASME Commercial Water Heaters Since 1961
USA: T: (817) 335-9531 • Toll Free: (800) 784-8326 • PVI.com
Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
© 2019 PVI
Operation & Maintenance Manual
AquaSolve
®
INTRODUCTION
The PVI AquaSolve Anti-Scale System provides pro­tection from scale formation on internal plumbing surfaces. The AquaSolve system can be installed at the point of entry to a building to treat both hot and cold water, or it can be located directly before a water heater, boiler, or other water using device that requires protection from hard water.
AquaSolve prevents scale by transforming the normal dissolved hardness minerals into undissolved crys­tal microparticles. These crystals stay suspended in the water and have a greatly reduced ability to react and attach to surfaces like dissolved hardness does. Therefore the problem of internal buildup of scale in pipes, water heaters and on fixtures and glass is greatly reduced.
AquaSolve is not a water softener or a chemical additive (like antiscalants or sequestrants). It is a scale prevention device with proven third party lab­oratory test data and years of successful residential and commercial installation. AquaSolve is the one water treatment device that effectively provides scale protection and is a great saltfree alternative to water softening (ion exchange) or scale sequestering chem­icals. Laundry and warewashing chemistry will like­wise require adjustments.
• Compatible with all on-site and community wastewater treatment systems
• Perfect system for towns or communities where water softeners are banned or restricted
• For high-flow applications, install multiple tanks in parallel
• AquaSolve does not remove minerals or add sodium to the water supply
• AquaSolve can be installed as pre-treatment to commercial reverse osmosis systems (contact your PVI representative for further details)
**For hot water applications where feed water temperature is 100° - 140°F (38° - 60°C), please contact PVI Technical Support at 1-800-433-5654.
WARNING
Do not use with water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after the system.
Systems are certied through WQA against NSF/ ANSI Standard 372 for Lead Free compliance.
AquaSolve Benefits
• Chemical-free scale prevention and protection – converts hardness minerals to harmless, inactive microscopic crystals making AquaSolve an effec­tive alternative technology to a water softener for the prevention of scale due to water hard-ness
• Virtually maintenance free – no control valve
• Uses environmentally friendly technology by using no salt or other chemicals to constantly add, no electricity and no wastewater
• Improves efficiency of all water using appliances – both hot** and cold
• Simple sizing and installation – all you need to know is pipe size and the peak flow rate
• Safe for landscaping and lawn watering, no need for costly bypass plumbing.
IOM-ASM1465TM_M1665TM Page 2 of 7Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
Operation & Maintenance Manual
AquaSolve
®
Specifications
AquaSolve scale prevention system shall be installed on the main water service pipe just after it enters the building, but after other whole building water safety devices (backflow preventers or pressure reducing valves), to effectively address water hardness con­cerns. A system may also be installed further down­stream to protect specific equipment or areas within a plumbing system. The system shall be plumbed with a bypass valve to allow isolation of tank(s) and to allow the bypass of untreated water in the event that service or media replacement be necessary. The installation area should be suitable in size for the tank(s) to be serviced without encumbrance and sit upright on a flat level surface.
The system must operate in an upflow manner and does not require additional water to backwash, flush, or regenerate once put into service. The system does not require any chemical additives and does not require electricity for operation.
Multi-tank systems shall be installed in parallel with PVC/CPVC manifold to meet peak flow rate require­ments – see image below.
Standards
Independent scientific testing has confirmed Template Assisted Crystallization (TAC) technology provides scale reduction of over 95+%. Testing was conducted under protocol based on DVGW W512 test to access control of scale formation.
NOTICE
Spotting may occur on external plumbing surfaces.
AquaSolve media systems perform best in single pass pota­ble water applications with NO additional chemical additives. Depending on hardness, soft scale spotting may occur. Soft scale spots in most cases can be easily wiped down with a damp cloth and will not form hard scale deposits. A Point of Use (POU) Water Softener should be used on mandatory spot-free applications (e.g. glass stemware, dishware).
CAUTION
• Not for use on closed loop systems.
• Do not let the system freeze. Damage to the tank may result.
• System must be operated in a vertical position. Do not lay it down during operation. The system may be placed in any position for shipping and installation but must be operated in the vertical position.
• Place the system on a smooth, level surface. Because the sys­tem operates in an upflow, fluidized bed mode, having a level surface is more important than with a softener or media filter.
• A bypass valve should be installed on every system to facili­tate installation and service.
• Observe all local plumbing and building codes when installing the system.
WARNING
Using AquaSolve with other water treatment equipment.
Due to the unique properties of AquaSolve, there are some unique requirements for using AquaSolve in conjunction with other forms of water treatment:
1. AquaSolve must be the last stage in the treatment chain. Do not install any filters after AquaSolve or before any devices for which scale prevention is required. POU filters, e.g. carbon, RO or Ultraviolet (UV) are exempt from this requirement.
2. Do not apply phosphate or any other antiscalant before or after AquaSolve.
3. The addition of soaps, chemicals, or cleaners, before or after AquaSolve treatment, may reverse its anti-scale treatment effects and/or create water with a heavy residue or spotting potential. Any adverse conditions caused by the addition of soaps, chemicals, or cleaners are the sole responsibility of the end user.
4. AquaSolve is not a water softener and does not softener the water - water treatment chemistry (e.g. antiscalants, seque trants, soaps, chemicals or cleaners etc.) will most likely have to be changed to be compatible with AquaSolve treated water. Laundry and ware-washing chemistry will likewise require adjustments.
IOM-ASM1465TM_M1665TM Page 3 of 7Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST