PVI Industries Love 4C, Love 8C, Love 16C Programming Manual

Love 4C, 8C and 16C Microprocessor Based Temperature Process Control
Programming guide for PVI Industries EZ Plate Water Heater with Boiler Water Control Valve
INITIAL SETTING MENU (all parameters in this menu must be set before programming other values)
Press and hold the ENTER key for at least 3 seconds while at the Home Display in order to access the Initial Setting Menu. Pressing the INDEX key will cycle through the menu items. The parameter will be displayed in the top display, while its value will be displayed in the bottom display. The UP and DOWN arrows change the values of th e parameters. The ENTER key must be pressed after any changes.
INITIAL SETTING MENU
Parameter Description Value
REGULATION MENU
Press the ENTER key while at the Home Display in order to access the Regulation Menu. Pressing the INDEX key will cycle through the menu items. The parameter will be displayed in the top display, while its value will be displayed in the bottom display. The UP and DOWN arrows change the values of the parameters. The ENTER key must be pressed after any changes.
REGULATION MENU
Parameter Description Value
OPERATION MENU
Pressing the INDEX key will cycle through the below menu items. The parameter will be displayed in the top display, while its value will be displayed in the bottom display, except for the set point which is displayed in the bottom display on the Home Display. The UP and DOWN arrows change the values of the parameters. The ENTER key must be pressed after any changes.
OPERATION MENU
Parameter Description Value
After Setting to Loc1, the control will no longer allow changes to the settings without following the unlocking procedures in the “Security Settings” of this guide. See next page for reference information.
Input Selection. J2 Temperature Units. F Scale Height Limit. 752.0 Scale Low Limit. -4.0 Control Mode. PID Heat/Cool Selection. HEAT Alarm 1 Setting. 0 Alarm 2 Setting. 0 Communications protocol language. ASCII Communications Write Function Feature. Off Controller Address: Set from 1 to 247. 1 Baud Rate Setting. 9600 Communication Data Length. 7 Communication Parity Bit. Even Communication Stop Bit. 1
Auto Tune. Off Proportional Band Setting. 5 Integral time (reset time). 10 Derivative time (rate time). 0 Integral Deviation Offset Correction. 0 Process Temperature Offset. 0.0 Analog Output High Limit. 0 Analog Output Low Limit. 0
Select Run - Stop Output Control. Run Set front panel security lock. Loc1 Display the % output value for output 1. 0
FRONT KEY FUNCTIONS
Key functions are as follows:
INDEX: Pressing the INDEX key advances the display to the next menu item.
UP ARROW: Increments a value or changes a menu item. If pressed during the Operation Mode, the set point value will
be increased.
DOWN ARROW: Decrements a value or changes a menu item. If pressed during the Operation Mode, the set point
value will be decreased.
ENTER: Stores the value or item change. If not pressed, the previously stored value or item will be retained. When
pressed during the Operation Mode, the controller switches to the Regulation Mode. If held for more than 3 seconds during the Operation Mode, the controller switches to the Initial Setting Mode. If pressed during the Regulation Mode or Initial Setting Mode, the controller will return to the Operation Mode.
SECURITY FEATURES
The C series controller has two built in security lock settings to prevent unauthorized personn el from changing parameter settings. These parameters are set in the
Operation Mode
.
The LoC1 setting affects all parameters in the controller. If LoC1 setting is enabled, the operator will have to unlock the controller to make any changes to the controller’s parameters.
The LoC2 setting affects all parameters except the set point. If LoC2 setting is enabled, the only parameter that the operator will be able to change is the set point. In order to change any other parameters, the operator will have to unlock the control before making a change.
In order to unlock the control, the operator must depress the ENTER and INDEX key simultaneously.