Protherm Leopard 24 BTV, Leopard 24 BOV User And Installation Instructions Manual

Leopard
User and Installation Instructions
24 BTV / v.17 24 BOV / v.17
XXXX
Wallhung gas boiler
Power 9 - 24kW
1
Mandatory warning for CEE countries
Warning: This appliance is designed, approved and inspected to meet the
requirements of the market. The identificationplate located on the inside of the
appliance certifies the origin where the product was manufactured and the country
for which it is intended.
If you see any exception to this rule, please contact your nearest dealer.
Thank you in advance for your assistance.
CE Mark
This boiler meets the requirements of Statutory Instrument No. 3083 The boiler
(Efficiency) Regulations, and therefore is deemed to meet the requirements of Directive
92/42/EEC on the efficiency requirements for new hotwater boilers fired with liquid or
gaseous fuels.
Type test for purposes of Regulation 5 certified by: Notified body 1015.
Product/production certified by: Notified body 1015.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to the electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
24 BTV/BOV
Table of contents
Introduction ...........................................2
Important notes ......................................2
Safety of life and property ......................3
User instruction
Control and signaling .............................4
Boiler indication ......................................5
Water temperature setting ......................5
Fault messages ......................................6
Boiler Start and Switch-Off .....................7
Boiler Regulation ....................................7
Protective features of the boiler ..............8
Servicing and maintenance ....................9
Note: The boiler serial number is marked on the data label attached to the fascia
behind the front panel. Refer to the ‘Introduction’ section for a description of the basic
functions of the boiler. The ‘User’ section describes how to safely operate the boiler.
The "Installation " is meant for workers of specialized companies..
Warranty conditions .............................10
Technical parameters ...........................11
Boiler schematic ...................................13
Dimensions and pressure available .....14
Installation instruction
Introduction ..........................................15
Boiler installation ..................................18
Flue gas and air ducts ..........................22
Example of horizontal duct flue ............25
Example of vertical duct flue ................22
Electrical part .......................................27
Electrical diagrams ...............................28
Conversion to LPG ...............................30
2
workshops, of fic es, etc. and as a flow heater of domestic hot water (DHW).
We believe it will serve you to your full satisfaction – certain minimum requirements must be fulfilled to that end. That is why we are asking you to study and follow these instructions carefully.
You have become an owner of a wall­hung combination boiler, for natural gas or LPG. The boiler 24BTV 17 with forced flue gas removal and 24BOV 17 with flue gas removal by means open chimney draught are designed for heating up the heating circuit water (CH) in central heating systems in flats, family houses,
Please, keep the following rules in mind:
• The boiler and all accessories must be installed and used in compliance with the design, the applicable laws, technical regulations and the manufacturer’s instructions.
• The boiler can only be installed in the type of environment for which it is designed.
• Only service centers authorized by the manufacturer are allowed to put the boiler into operation after in stal la tion.
• In case of defects, call a service centre authorised by the manufacturer – incompetent intervention can damage the boiler (and/or the accessories)!
• The service centre’s employee who initiates the boiler operation after installation shall instruct the user about the boiler, its parts and operation.
• Check completeness of the delivery.
• Check to make sure the supplied boiler type complies with the expected manner of use.
• If you feel uncertain about any activities related to the boiler operation, look up and study all relevant information in these instructions, and follow the recommended procedure.
• Do not remove or damage any labels or markings on the boiler.
• It is not allowed to tamper with inner fitting and wiring or make changes. In case of reparation, all parts must be approved by producer of boiler.
• If the boiler is going to be switched off for a longer time, it is recommended to disconnect boiler from the electricity source and close gas valve. This recommendation is valid with reference to condition in these Instruction (e.g. the anti-freeze protection
is inactivated then)
• When the life cycle of the boiler, or its parts, has expired, they should be disposed of in an environmentally friendly manner.
• Producer do not provide warranty and do not answer for damage due to infringement of:
- conditions mentioned in these Instructions
- valid Regulations and Standards
- correct installation and use
- conditions mentioned in Guarantee Certificate and Service Booklet
Dear Customer
Important notes
3
• Boilers as products are checked for compliance with the following documents: EN 483, EN 437, EN 625, EN 50 165, EN 60 335-1:1997.
• The installation of this boiler must be carried out by a competent person in accordance with the relevant requirements of the current issue of:
- the Gas Safety (Installation and Use) Regulations,
- the Building Regulations,
- the local water company Bylaws,
- the Building Standards Regulation,
- the Health and Safety at Work Act
• Besides the requirements as expressed in the above-cited documents, these Instructions for Use and the boiler documentation provided by the manufacturer are to be followed. During use, no children, drug-intoxicated or legally irresponsible persons should be allowed to tamper with the boiler.
Abbreviations used:
CH – heating circuit water, DHW – domestic hot water.
Safety of life and property
In practice, situations may occur in which the users must apply necessary precautions:
• Preventing the boiler from switching on (also accidental) when inspecting the chimney, flue-gas duct, water and gas piping – i.e., electricity supply to the boiler must be stopped (e.g., by unplugging) in addition to using the boiler switch;
• Stopping the boiler whenever flammable or explosive vapours appear (even if temporarily) – such as vapours of flooring glue, paints when surface finishing, gas leaks, etc.);
• If it is necessary to discharge water from the heating system, it must not be dangerously hot;
• If water has leaked from the boiler exchanger, or if the exchanger is filled with ice, no attempts to start the boiler should be made until normal operating conditions prevail.
• If there is a (whether confirmed or suspected) gas leak or stoppage in the gas supply, switching off the boiler, shutting down the gas supply and calling gasworks or a specialised service centre
4
Main on/of switch
The main on/off switch (see fig.1) is on the bottom of the boiler, below the control panel.
Caution: Commencing and first start of the boiler operation may only be carried out by a specialised service centre! Only turned on boiler has activated all protective function (e.g. anti-freeze protection).
Control panel
It serves for indication of actual parameters and for setting or changing required values this parameters.
1 - heating system pressure LED
(indication of the heating water pressure)
2 - domestic hot water LED
(indication DHW taking or domestic hot water temperature setting)
3 - central heating LED
(indication of the heat requirement or heating temperature setting
4 - fault message LED
(indication of faults in boiler operation)
5 - decrease button (-)
(decrease the setting value of parameters)
6 - increasing button (+)
(increase the setting value of parameters)
7 - display
(showing of pressure, temperatures, service parameters and fault
messages)
8 - MODE button
(switches between setting modes and corfirms setting value of parameters)
Control and Signaling
USER INSTRUCTONS
g. 1
g. 2
5
Actual circuit heating water tem­perature indication in °C.
LED 3 under symbol lights continuously. The
actual temperature of he­ating water flowing from boiler is displayed.
Domestic hot water temperature indication in °C (required value).
Domestic hot water tap is open. LED 2 under sym­bol lights continuous­ly. DHW temperature co­rresponds with required value in certain DHW flow range.
Water pressure in central heating system in Bar.
LED 1 under symbol lights continuously. Re­commended range is 1 - 2 Bar. Pressure is displayed for 30 sec. after one pressing button.
Domestic hot water temperature setting in °C.
Temperature is displayed for 30 second after two pressing button, LED 2 under symbol flash.
Buttons set domestic water tem­perature to following values: 35, 37, 38, 39, 40, 41, 44, 47, 50, 55, 60°C. Setting symbol means no preparation do­mestic hot water.
Setting value are saved into memory after next pressing button (if it's not confirmed until 30 sec., the previous setting is saved again)
Circuit heating water temperature setting in °C.
Temperature is display­ed for 30 sec. after three pressing button, LED 3 under symbol flash.
Buttons set central heating water temperature to following values: 38, 40, 42, 45, 50, 55, 60, 65, 70, 75, 80°C. Set­ting symbol switches central heating off (SUMMER adjustment).
Setting value are saved into memory after next pressing button (if it's not confirmed until 30 sec., the previous setting is saved again).
Boiler indication during ordinary operation (display mode)
Water temperature setting
Warning on wrong pressure in he­ating system under value 1 Bar (or over 2,5 Bar).
Boiler still works. LED 1 under symbol flash. It is necessary to fill up (or drain) the heating sys­tem to pressure 1- 2 Bar soon.
6
Equithermal mode - curve slope
Press the button ­letter E with the characters (0) through to (9) attached will appear on the display.
By pressing the
but­tons, select the required equithermal curve. The cur-
ve´s slope grows with the growing number (E0 < E9) - see fig. 3.
By pressing the
.button, the selecti-
on is saved in the memory.
Note: Equithermal control requires an ex­ternal sensor to be connected to the boi­ler, which must not be set to the SUMMER mode.
Attention: Boiler does heating with maxi­mal power on one hour after installation of the outdoor sensor. All settings are igno­red in this time except room thermostat (if is connected).
Equithermal mode – paralel curve shift
If previous parameter E was confirmed by pres­sing the button
- letter P with the chara­cters (0) through to (9) attached will apear on display. By pressing the
buttons, select the required shift (see fig. 3, table 1). For beginning setting choose the parameter P5, which respond to outdoor temperature 15 °C (see table 1, fig. 3).
Note: If boiler reaches the reference tem­perature, then heats system by minimal temperature (38 °C) till outdoor tempe­rature increase at 3 °C, then is heating switched-off (see table 1 - switch-off tem­perature).
fig. 3
Equithermal curves
„P“ parameter 0 1 2 3 4 5 6 7 8 9
Reference temp. °C 6 7 9 11131517192123
Switch-off temp. °C 9 10 12 14 16 18 20 22 24 26
Table 1
7
Operation diagram
8
No flame - F1
Boiler is switched off, for example by reason of gas supply failure. LED 4 un­der symbol
flash. Bo­iler can be restarted by switching off and on (
from position „I” to position „0“ and again to po­sition „I“
by mains on/off switch). If fault is
frequent, call service centre.
Loss of circuit heating water - F0
Pressure is under 0,7 Bar. Boiler is switched off, LED 1 and LED 4 under symbols
and flashes. After filling system up to 1­2 Bar the boiler automati­cally starts. For filling can
be used refilling valve at the bottom of boiler (see fig. 4). If fault is frequent, call service centre.
Other boiler faults (from F2 to F8)
Boiler switched off itself. LED 4 under symbol flash. It is necessary to call service centre.
Fault messages
Boiler memory fault - F9
Boiler works, but possi­bility changes in setting exists. LED 3 under sym­bol
lights continuously. Switch the boiler off and on (
from position „I” to
position „0“ and again to position „I“
by mains on/off switch). Then check boiler parameters (see Water temperature set­ting). Let check the boiler setting by ser­vice centre occasionally.
Note: The preparation for and commencing of the boiler operation may only be carried out by a specialised service centre!
Before starting the boiler when it has been put into operation, check the following facts:
• The power cord must be plugged into the socket.
• The gas valve that feeds the boiler must be open.
• The water pressure in the heating system should be between 1 and 2 bar Now the boiler is ready to be started.
Boiler start
Set the mains on/off switch to the “on” posi­tion (“I”). Display light up.
Note: In case of safety switch-off due to extinction of flame or the flue thermostat reaction (version 24 BOV) LED 4 under symbol
starts flash.
Boiler can be un-
blocking by switching the boiler off and on
Boiler Start and Switch-Off
(
from position „I” to position „0“ and again
to position „I
by mains on/off switch).
In case of
safety switch-off due to overheat
thermostat Led 4 under symbol
flash too, but boiler can be unblocking only by service centre and this act is not guarantee repair. Warning: The boiler must not be oper­ated if the safety elements (e.g. overheat thermostat, flue termostat) are dis abled or re placed with elements different from those specified by the manufacturer.
Boiler switch-off
Set the mains on/off switch to the “off” position (“0”).
If the boiler is going to be switched off for a longer time, it is recommended to dis­connect boiler from the electricity source and close gas valve. This must be done with reference to ambient temperature, because there is the risk of freezing boiler and system in frost weather.
9
Setting SUMMER mode (only DHW)
• Start the boiler;
• Select “– –” for CH temperature as de­scribed under Control and Signalling (CH temperature setting);
• Activate the basic state by MODE button.
Operation without a room thermo­stat
Boiler keeps CH temperature on setting value. The room thermostat is not con­nected; its contacts must be interconnected (by utilizing a jumper).
• Set the desired temperature value as de­scribed under Control and Signalling (CH temperature setting);
Operation with a room thermostat
Boiler keeps CH temperature on setting value, with breaks in operation dependent upon the temperature in the room in which the thermostat is installed. The radiator in that room must not be equipped with a thermostatic valve head. The settings are the same as the operation without the room thermostat, but the jumper is removed and the room thermostat is connected to the contacts.
Running the Boiler with Equithermal Control
The boiler changes heating water (HeW) temperature according to the changing outdoor temperature. Important: The boiler must have an out­door temperature sensor connected! The outdoor temperature sensor is installed on the coldest wall of the building (nor­th of north-west), about 2.5 – 3 m above ground. The sensor must not be exposed to any external sources of heat such as open windows or ventilation shafts or sun­shine. When selecting a heating curve, a rule applies that curves of a lower number are suitable for buildings with good thermal insulation and steeper thermal gradient,
and vice versa. The heating curve diagram provided is used as a primary guideline. More accu­rate setting is achieved by monitoring both outdoor and indoor temperatures for se­veral days. In the first setting select the E5 curve. When doing the setting, all radiator valves must be completely opened, thermostatic valves must be set to maximum tempe­rature and doors and windows must be closed. Change the curve gradient or reference temperature in small steps, and after each new setting wait about 2 hours and then assess the change. When trying to find the right setting, it is better to do so when the outdoor temperature fluctuations are greater, and the final setting should be done when the outdoor temperature is be­low the freezing point. The boiler is set in the following procedu­re: 1. Select the “HeW temperature” mode and make sure that the function “SUM­MER” is not activated. (symbol --). Set the temperature to a concrete value (it will have no effect on the equithermal mode).
2. Select “Equithermal mode – curve gra­dient” and set it to symbol E5 – see page
7.
3. Select “Equithermal mode –reference temperature shift “ and set it to (P5). 4. Put the boiler into the ready state. After seve­ral days of operation (when the premises have been heated up), change the curve gradient as necessary.
5. If the indoor temperature does not no­ticeably change with a changing outdoor temperature, the selected curve is the co­rrect one. The temperature can be set to
Boiler Regulation
Setting WINTER mode (CH + DHW)
• Start the boiler;
• Select the CH temperature instead of “– –” as described under Control and Signalling (CH temperature setting);
• Activate the basic state by MODE button
10
Anti-freeze protection of the system
The boiler has build-in protection against freezing water in boiler (no in whole heating system or DHW pipes). The boiler is always started if the CH temperature is below 4°C and works until CH temperature reaches 8°C. This protection is independent on room thermostat or SUMMER mode (CH water temperature setting – – )
Pump protection
The pump is automatically switched on for a short time (approximately 30 sec.) if it has not been operated for 24 hours – thus clogging by sludge sedimentation in the pump’s bearings is prevented.
Anti-cycling function
This function restrict too repeated starts of boiler to heating system and it is use­ful especially in smaller heating system, when required heating power is smaller than minimal boiler's thermal power output.
Next start is delayed in range from 1min 30 sec to 5 min.
Overheating protection
If the CH temperature is higher than the pre-set value of 80°C, the pump is always switched on and continuously operated. If temperature further increases, safety ther­mostat shut boiler down, and thermostat must be unblocked by service centre. In case water loss the boiler shut down too, but it will be reactivated automatically when the pressure increases again.
Disconnected boiler from el. source
Should the boiler be disconnected from the electricity source for a long time (continu­ously for one month or longer), it should be regularly reconnected and switched on (at least once a month). If the pump is blocked, always call a specialised service centre. Repairs of the pump caused by impurities in the heating system are not covered by
Protective features of the boiler
a higher or a lower value by shifting the reference temperature – see the section “Controls and signals – equithermal mode – reference temperature shift”. Please note: If with a decreasing outdoor temperature the indoor temperature noti­ceably increases, select a heating curve of a lower number, and if it decreases, with a higher number.
Running the Boiler with Equithermal Control and Room Control Unit
The room control units augments the equi­thermal control, allowing time setting and economy heating mode (e.g. at night).
How to set the boiler: • set the equithermal control as explained above;
• connect the room control unit to the boi­ler (remove the terminal jumper) and then set the required temperature during the comfort period on the control unit to a va­lue about 5°C higher then the temperature reached with equithermal control. Set the required temperature during the economy
period (at night, when absent) on the con­trol unit to the actually required value – it must always be at least 3°C lower than the actual comfort temperature.
Please note: Room control unit must be installed by a specialist service organisa­tion. Example: Select curve E5. With the out­door temperature -10°C, the boiler sup­plies water to the heating system of about 70°C. If you at the same time select the P5 reference temperature shift parame­ter, when the outdoor temperature rises by 15°C, the boiler should supply water to the heating system of 38°C. When the outdoor temperature rises to 18°C, the heating water heating is turned off.
Heating power setting
Boiler's power factory setting is 15 kW to heating system. The maximal power 23 kW is always available for preparing DHW. Only service centre authorized by manufacturer can change heating power in accordance with requirement of heating system.
Loading...
+ 23 hidden pages