Protherm 65, 85, 100, 130, Grizzly 150 KLO EKO Manual For Instruction And Use

...
Floorstanding cast iron boiler
Cascade conection possible
Output up to 150 kW
Grizzly
EN
verzion
XXXX - v.2 4/2005
and use of boiler
65, 85, 100, 130, 150 KLO
Protherm spol. s r.o. Jurkovičova 45 909 01 Skalica Tel.: 034 6966 101 Fax: 043 6644 017
www.protherm.sk
2
3
Dear Client,
You have just become an owner of a KLO /
KLO EKO (Grizzly) natural gas or propa­ne gas fired cast iron boiler. We are con­fident that you will be satisfied with the service this boiler will give you. Howe­ver, you’ll have to comply with at least minimum requirements when running the equipment. Therefore please read these Operating Instructions carefully and comply with their guidelines.
Please pay careful attention to the following
important information:
1. The boiler with all its accessories must be installed and used in accordance with an installation design, all applicable legal regulations, technical standards and manufacturer’s instructions.
2. The boiler may be installed only in the environment for which it has been de­signed and only in a correctly ventilated room.
3. After installation, the boiler must be put into operation by a service organisation authorised by the manufacturer.
4. Please also contact authorised service if you are experiencing any problems with the equipment – unauthorised re­pairs may damage the boiler (as well as the connected equipment!).
5. The service technician when putting the boiler into operation for the fist time must demonstrate its controls and show you its various parts and how to control them.
6. Check whether the boiler is complete.
7. Check whether it is the model you have ordered.
8. Whenever you have any doubts how to operate the boiler, find and study the relevant information in these Operating Instructions and proceed in accordance with them.
In practice, situations might occur when the
following essential measures have to be taken:
– prevent the boiler from being (even
accidentally) switched on while in­specting the fumes exhaust and gas and water distribution routes, by dis­connecting the boiler from power supply by another means than just with the boiler’s switch (e.g. by pul­ling the power cord plug out of the socket),
– shut the boiler down every time when
flammable or explosive vapours are present (even temporarily) inside the premises from which combusti­on air is supplied to the boiler,
– if it is inevitable to drain water from
the boiler or the heating system, the water must not be dangerously hot,
– when water leaks from the boiler’s
heat exchanger or when the exchan­ger is clogged with ice, do not try to switch the boiler on until normal run­ning conditions have been restored,
– during (even suspected) gas leaks or
after gas supply failure, switch the boiler and the gas supply off and call the gas company or authorised ser­vice.
Regulations and Directives
The PROTHERM KLO boiler may be put into operation only by an authorised service organisation in accordance with UBP SR Notice No. 74/1996. Installations, putting the boiler into operation, warranty and post-warranty service are performed by a network of the manufacturer’s con­tractual service organisations, which meet the above-specified requirements. Instal­lations must be carried out in accordance with a design prepared in compliance with applicable regulations detailed below.
9. When repairing the boiler, only original parts must be always used. Internal wi­ring and factory settings must not be changed or interfered with.
10. Do not remove or damage any signs and labels on the boiler.
11. The boiler meets regulations applicable in Slovakia. For use in other countries, any potential differences must be identi­fied and resolved.
12. At the end of life of the boiler’s parts and components (or of the entire boiler), the­ir disposal must be carried out ecologi­cally – metal parts must be delivered to a metal scrap yard, plastics, seals, and insulation materials must be sorted out as required, or a special disposal tech­nology used, engaging the services of companies authorised for such operati­ons.
13. Before a protracted shutdown we re­commend to turn off the gas supply and disconnect the boiler from power supply. This recommendation is part of general conditions defined in this Operating In­structions.
15. The manufacturer shall not be held li­able for any damages caused by the user’s failure to:
– abide by the conditions defined in
these Operating Instructions,
– abide by applicable regulations and
standards,
– abide by installation and operating in-
structions.
– abide by the regulations specified in
the Warranty Certificate and Service Book.
Such damages are not covered by the pro-
duct warranty.
a ) Heating systems:
STN 06 0310 – Central heating, design and installations STN 06 0830 – Safety equipment for cen­tral heating and hot water heating sys­tems. STN 07 7401 – Water and steam for heat energy equipment of operating pressure up to 8 MPa
b ) Gas distribution systems:
STN 38 6420 – Industrial gas pipelines. STN EN 1775 – Gas supply – Gas pipe­lines in buildings – Maximum operating pressure below 5 bar STN 38 6413 – Steel gas pipelines and connections STN 07 0703 – Gas-fired boilers STN 38 6405 – Gas equipment. Operating principles. Act No. 222/94 Coll. on business condi­tions and public service supervision in the energy industry and on state energy inspection.
c ) Electrical installation:
STN 33 2180 – Wiring of electrical instru­ments and appliances. STN 33 2000-3 – Electrical installation in buildings. Part 3: Definition of basic char­acteristics. STN 33 2000-7-701 – Electrical installa­tion in buildings. Part 7: Requirements on special installations or premises. Section
701. Rooms with a bath-tub… STN 33 2130 – Electrical engineering reg­ulations. Interior electrical installations. STN 33 0160 – Electrical engineering regulations. Labelling terminals of electri­cal objects. Execution regulations. STN 33 0165 – Electrical engineering regulations. Colour marking or numbering of wires. Execution regulations. STN 33 2350 – Regulations for electrical equipment in difficult climatic conditions.
4
5
STN 34 0350 – STN electrical engineer­ing regulations. Regulations for loose ca­bles and cords. STN 33 1500 – Instructions for electrical equipment. STN EN 60 335-1 – Safety of household and similar electrical appliances. Part 1 – General requirements.
d ) Chimney:
STN 73 4210 – Construction of chimneys and fume exhausts and connecting fuel appliances to them. STN 73 4201 – Designing chimneys and fume exhaust flues. STN 06 1610 – Fume exhaust parts of household appliances. STN EN 297 – Gas-fired central heating boilers. Boilers Type B11 and B11BS with atmospheric burners and nominal thermal output up to 70 KW.
e ) Fire protection regulations:
STN 92 0300 – Fire safety of local appli­ances and sources of heat. STN 73 0823 – Fire technical properties of materials. Degrees of flammability of building materials.
f ) Utility hot water heating systems:
STN 06 0320 – Heating of utility hot wa­ter. STN 06 0830 – Safety devices for central heating and utility hot water heating sys­tems. STN 73 6660 – Internal water distribution systems. STN 83 0616 – Utility hot water quality.
Safety of Persons and Equipment
As products, boilers are verified for com­pliance with the following documents:
STN EN 437, STN EN 50165, STN EN 60335-1+A11, Act No. 513/1991 Commer­cial Code, Act No. 634/1992 and Ministry of Health Public Notice No. 13/1977.
Boiler Features
The PROTHERM KLO / KLO EKO station­ary, cast iron boiler is designed for heating water for heating purposes and, if com­bined with an indirectly heated reservoir, also for heating utility hot water. It is avail­able in the following series of size:
a) 65, 85, 100, 130, 150 KLO b) 65, 85, 100, 130, 150 KLO EKO
The boilers use as fuel natural gas and both series have a dual-stage design (low and high output).
Models 65 – 85 KLO/KLO EKO are sin­gle-stage and designed to run on propane gas.
Both model series can be fitted with a Sie­mens Albatros RVA 43.222 equithermal control unit. By combining it with other RVA 43.222 control units, a cascade sys­tem can be created with multiple sources of heat.
The central heating system water pump is controlled by a thermostat and turned on only when the heating water temperature reaches a set value. This reduces the time required to heat the water inside the boil­er after a protracted break in the boiler’s function. The heating water pump is part of the delivery.
The boiler can work in conjunction with an indirectly heated utility water tank. The standard boiler configuration allows the tank to be connected easily to the boiler’s terminal box.
To guarantee correct functioning of the system, we recommend using a PRO­THERM reservoir heater of 95- to 200-litre volume, equipped with a thermostat and a switching contact. Using the RVA 43.222 control unit will allow water in the reservoir to be topped up by a pump.
Important: For combined heaters (with water heated also by electricity), it is es­sential to prevent the supply of alien volt-
The boiler (as well as its accessories) complies with the type which has been tested and certified by the Technical Test­ing Institute in Piešťany, SKTC-104, au­thorised to verify the compliance with the requirements of the Slovak Bureau for Standardisation, Metrology and Testing, and the compliance with the technical re­quirements specified by Government De­crees Nos. 392/99, 393/99 and 393/99 as set forth in Act No. 264/1999.
Hence the boilers (and their accessories) meet the requirements of applicable tech­nical and legal standards, a fact confirmed in a “Certificate of Compliance” issued by the manufacturer. Pursuant to applica­ble legislation, the Certificate is kept for inspection and supervision authorities, and for distribution purposes sufficient is a written confirmation that the Certificate has been issued.
When installing and using the boilers and their accessories, other generally applica­ble documents must taken into account, which also define requirements in addition to those on the product itself, namely:
– in the areas of design and installation
(and maintenance and repairs): STN 06 0310, STN 06 0830, STN 07 0703, STN EN 1775, STN 38 6413 and STN 38 6460, STN 73 4201and STN 73 4210, and Public Notice No. 48/1982 (in the wording of later regulations) and binding work safety and health at work regulations;
– . during transportation and operation:
STN 38 6405, Public Notice No. 718/
2002.
In addition to abiding with the require­ments of these documents, it is neces­sary to proceed when using the boiler in accordance with these Operating Instruc­tions and other manufacturer’s documen­tation supplied with the boiler.
age to the boiler – i.e. the thermostat con­tacts must be separated from the heater’s internal electrical wiring!!!
Utility hot water heating has priority before heating water. This means that water in the central heating (CH) system is heated only after the utility hot water (UHW) has been heated to the required temperature. Setting this value above usual tempera­ture (50-60°C) will result in longer heating times and hence longer breaks in heat­ing the building. The heating time will be longer also when the boiler is set to low output, or when the CH water temperature is set too low.
Important: The boiler must not be used for any other purposes than those described in these Operating Instructions.
6
7
The PROTHERM KLO boiler consists of the following components:
1. cast iron body of the boiler with thermal insulation and water connection pipe sec­tion;
2. burner plate with gas connection route and ignition device;
3. collector of combustion fumes with a chimney thrust detector and SKKT ther­mostat.
4. boiler covers with control panel and boiler terminal box;
5. boiler base. The cast iron boiler body is made of seg-
ments and serves as a combustion cham­ber (including combustion fumes routes), and also as a water reservoir (including water routes). The segments are lateral (right and left) and central (one kind). The boiler body of the required size (including combustion chamber and water reservoir) is constructed by assembling and joining together the segments. The assembled boiler body is fitted with pipe sections for water connection and is insulated against heat loss and heat radiation. It also has
960
850
52
544
92
125
370
605
720
1195
A
B
75
111
Æ G 6/4"
G
1"
Æ G 6/4"
C
Æ D
770
objemový prùtok vody V (m /h)
3
tlaková ztráta p (Pa)
20000
18000
20
0
4681012
16000
14000
12000
10000
8000
6000
4000
2000
65, 85 KLO / KLO EKO
100 KLO / KLO EKO
130 KLO / KLO EKO
150 KLO / KLO EKO
Model 65 KLO /
KLO EKO
85 KLO /
KLO EKO
100 KLO /
KLO EKO
130 KLO /
KLO EKO
150 KLO /
KLO EKO
A 850 1010 1170 1410 1570
B 460,5 540,5 620,5 740, 5 820,5
C 860,3 850,3 840,3 825,3 825,3
D 180 200 220 250 250
brackets for fitting thermostat sensors and a thermometer, and lugs on feet for con­necting the body to the boiler base. The KLO EKO series boilers use low-emission burner tubes, the KLO series boilers use standard tubes. Depending on the output, the boiler has 7 to 16 burner tubes and a complete gas route.
The burner plate is fitted with a gas dis­tribution section, the actual burner tubes and an ignition device. The gas route consists of a gas supply pipe section ter­minated with a combined gas valve. The combined gas valve controls the supply of gas into the boiler depending on the required and reached operating states of the whole system (i.e. the boiler combined with the heating system); its outlet is al­ready the gas distribution section of the of the burner plate, terminated with 7 to 15 jets (one for each burner tube).
Igniting the burner and watching that it is running is done by a Polidoro low-emis­sion ignition burner. When a request is sent to ignite the main burner, after waiting time T
w
= 10 seconds, the ignition burner
Accessories
Pressure loss (Pa)
Fig. 1
Basic and Connecting Dimensions
Pressure loss of the boiler´s body
Fig. 2
Flow of water volume V (m3/h)
8
9
is automatically ignited. It is ignited by an ignition spark and its flame is detected by an ionisation electrode. After the ignition burner has steadied up and the ionisation circuit closed, the main gas supply valve to the main burner opens. If the ignition burner does not ignite within a safety time T
s
= 25 seconds, the gas supply to the main burner and to the ignition burner is automatically shut off. If the flame during normal boiler operation goes out, the au­tomatic ignition system will repeat the igni­tion cycle of the ignition burner. If the loss of ionisation prevails, the boiler will switch to a fault status (the light of the “Unlock automatic fault signalling system” button on the control panel lights up). After a waiting time of approximately 10 seconds, the fault status can be manually cancelled by pressing the RESET button.
The ignition burner remains on while the main burner is on.
In the event of power supply failure, the gas supply to the burner is automatically shut off. When power supply is restored, the boiler will automatically restart itself.
KLO
1
2
3
4
5
6
7
8
10
9
11131415
16
18
22
20
21
19
2
3
4
5
6
7
8
10
9
12131415
16
18
19
20
1
21
22
11
17
17
1. Main control panel
2. Chimney thrust detec­tor system cover
3. Fume exhaust
4. Chimney thrust detector
5. Fume thermostat
6. Heating water outlet
7. Gas supply
8. Cast iron body seg­ments
9. Heating water inlet
10. Combustion chamber
11. Secondary air supply
12. Supply burning air
13. Burner
14. Supply burning air
15. Jet
16. Combining pipeline gas
17. Operator burner
18. Gas armatures*
19. Boiler covering
20. Case for sensors
21. Main control panel
22. Automotive ignition automatics
* For models 130-150 KLO / KLO EKO is used only 1 gas armature.
KLO EKO
KLO
The combustion fumes collector is con­nected to a chimney thrust detector and behind it is terminated in a boiler exhaust outlet (on a fumes flue connection). The collector is equipped with a removable cleaning lid, which is accessible after re­moving the top boiler’s cover.
The chimney thrust detector system (SKKT) works on the principle of monitor­ing the combustion fumes temperature inside the collector. A thermostat situated inside the collector reacts to an increase of the combustion fumes temperature caused by a reduced chimney effect will shut the boiler down (by shutting off gas supply to the burner).
The boiler has covers, which are rigidly fixed to the rear and side-wall, a remov­able wall and a removable top cover. The boiler’s control panel is located in the top section.
The boiler body base is a single steel­base on which the body of the boiler and the covers are mounted.
Boiler Installation Guidelines
The PROTHERM KLO / KLO EKO boil­ers can be put into operation only by an authorised service organisation in accord­ance with UBP SR Public Notice No. 74/
1996. Installations, putting into operation, warranty and post-warranty service are done by a network of manufacturer’s con­tractual service organisations, which meet the requirements specified above.
Connecting the boiler to gas supply
The PROTHERM Series KLO - ZP / KLO EKO – ZP boilers are designed to run on natural gas with nominal pressure in the distribution network 1.8 kPa (18 mbar) and a calorific value usually claimed between
9 and 10 kWh/cum. The internal gas dis­tribution system as well as the gas meter must be of sufficient size, taking into ac­count also other user’s gas appliances. The gas supply pipe must have an internal diameter of at least the same size as the gas connection pipe on the boiler (which depends on the boiler size), but preferably one size bigger.
The PROTHERM Series 65 – 85 KLO - P / 65 - 85 KLO EKO - P boilers are designed to run on propane gas. Propane gas calo­rific value is given between 12.8 and 13 kWh/kg. Because supplying boilers from pressure cylinders is problematic, particu­larly from the capacity and handling point
Fig. 3
Schematic operation diagram
10
11
of view, it is recommended that a reservoir is installed near the building to be heated, and refilled by an authorised organisa­tion.
Adequately sized propane supply from the reservoir to the boiler and to other gas appliances will then be part of the design and delivery of the reservoir. When install­ing a propane gas-fired boiler, an accurate nominal pressure of 3.0 kPa (30 mbar) must be secured by installing a reduction valve (station) before the boiler.
Supply of combustion air
Ventilation must guarantee that sufficient quantity of combustion air is supplied to the boiler and that the maximum permis­sible concentrations of harmful gases in the boiler’s vicinity are not exceeded and that an acceptable temperature is maintained there (all in accordance with Ministry of Environment Public Notice No. 706/2002).
The stationary cast iron PROTHERM KLO/KLO EKO boilers draw combustion air from the space in which they are in­stalled. The combustion air supplied to the boiler must be free of dust and corrosive and flammable substances (vapours, sol­vents, paints, adhesives, etc.). The sup­ply of adequate quantity of combustion air must meet the requirements of STN 070703 “Gas-fired boiler rooms”. Gas ap­pliances connected to combustion fumes flue must not be located in places where negative pressure can be created by ven­tilation fans.
Combustion fumes exhaust
The boiler is designed for combustion fumes to be removed into a chimney (via a chimney connection point) with a stabi­lised thrust of at least 2 Pa. The boiler is connected to the chimney by a flue of a diameter corresponding to the flue diam-
quired by the water composition. Depend­ing on the anticipated amount of sludge trapped; is recommended to desludge the boiler approximately a week after it has been put into operation. Functional defects caused by mechanical dirt are not covered by the manufacturer’s overall warranty (re­fer to Warranty Terms and Conditions).
Important: When filling the boiler with water, all air in the boiler as well as in the heating system has to be thoroughly bled.
Using antifreeze liquid
KLO and KLO EKO boilers may be filled with an antifreeze liquid, namely product called ALYCOL TERMO, produced by Slovnaft Moravia. Using other antifreeze products will invalidate the manufacturer’s warranty on parts and related costs.
Properties of the heating system and filling the system with water
The boiler must be connected to the heat­ing system distribution pipes (G6/4”) and to the gas supply pipe (G 1”) in such a way that the connection end pieces are not stressed by forces imposed by the heat­ing system distribution pipes or by the gas supply pipe. The connection end pieces have an external thread.
We recommend equipping the connection
eter of the flue connection point (depends on the boiler size). The flue is part of the delivery.
It is forbidden to put inside the flue objects obstructing the flow of combustion fumes (e.g. various types of heat exchangers to increase utilisation of the heat).
Construction of the flue and the chimney must comply with STN 06 1610, STN 73 420 and STN 73 4201 standards.
By complying with requirements of these standards, we prevent undesirable phe­nomena from occurring, such as exces­sive cooling of the fumes, penetration of dampness into walls, fluctuations in the chimney effect (thrust) and thus undesir­able effects on the boiler’s functioning.
Requirements on heating water quality
The PROTHERM KLO / KLO EKO boilers are designed for heating water of up to 400 kPa (4 bar) gauge pressure, which is in compliance with STN 07 7401.
The first fill as well as top up water must be clear and colourless, and be free of suspended substances; oil and chemi­cally corrosive additives, under no circum­stances may be acidic (i.e. have pH factor greater than 7) and must have minimal carbonate hardness.
For softening the first fill water can be used trisodium phosphate or a one-off dose of chelating agent.
It is recommended to install before the boiler (i.e. to the return heating water pipe) a sludge trap. Its design should allow the device to be emptied in regular intervals without draining a great deal of heating water in the process. The sludge trap can be combined with a filter, but the filter itself would not provide adequate protection. Both the filter and the sludge trap must be checked regularly and cleaned, as re-
pipes with isolation valves, so that when repairing the boiler it is not necessary to drain water from the heating system.
The heating system should be designed in such a way that a permanent circulation of the heating water is possible at least through some radiators.
The boiler does not have an expansion vessel or a safety valve built in, therefore these devices can be connected only to an external system, designed in accord­ance with STN 06 0310 and safety fea­tures compliant with STN 06 0830.
The boiler can work in systems with both an open and closed (pressurised) expan­sion vessel. However, when using the boiler in systems with an open expansion vessel, it is necessary to harmonise the temperature setting of the emergency thermostat (98°C) and limit the operation range on the heating controls. This setting must be done by authorised service only.
In open expansion vessels, correct water level must be maintained (between the op­erating minimum and maximum). Closed expansion vessels when being filled up must be set according to the heating sys­tem.
For filling and draining purposes, the boiler is equipped with a filling (draining) valve. After being filled up, the system must be thoroughly bled.
After reconstructions, in unsuitable build­ing disposition, etc., the boiler may be connected to the heating system and to the gas supply by flexible hoses, but only those designed for this purpose. When us­ing flexible connections, these should be as short as possible, protected against mechanical and chemical stress and dam­age, and be always replaced before the end of their life or before their parameters deteriorate with new ones (as determined by their manufacturer).
Fig. 4
Loading...
+ 14 hidden pages