Protherm Gepard, 23 MTV, 23 MOV Installation Manual

Page 1
23 MTV v.19
23 MOV v.19
Wall-hang non-condensing boiler
Power 8,5 - 23,3 kW
Flow heating HW
Gepard
version
EN
Page 2
- 1 -
CONTENTS
INTRODUCTION
Manual1
Product documentation1.1 ..............................................................3
Relevant documents1.2 ..................................................................3
Explanation of symbols1.3 ..............................................................3
Descriction device2
Safety regulation2.1 .......................................................................3
Data plate2.2 ...................................................................................3
Type of gas2.3 .................................................................................3
Regulations and legal provisions2.4 ...............................................3
Hydraulic scheme2.5 ......................................................................5
Safety instructions and regulations3
Safety instructions3.1 ......................................................................7
INSTALLATION
Location of equipment4
Location4.1 ......................................................................................8
Clearance4.2 ...................................................................................8
Boiler installation5
Contents of delivery5.1 ...................................................................8
Recommendations before you install5.2 .........................................8
Dimensions5.3 ................................................................................9
Mounting the boiler5.4 ..................................................................10
Hydraulic connection6 Air and exhaust lines7
Regulations7.1 .............................................................................14
Description exhausting kits7.2 ......................................................14
Connecting the boiler to the electricity supply8
Entrance to BMU8.1 ......................................................................17
BMU8.2 .........................................................................................18
Boiler wiring diagram8.3 ................................................................19
External accessories8.4 ................................................................20
Putting into operation9
Filling the heating system9.1 .........................................................20
Re-fi lling of the boiler9.2 ...............................................................20
First ignition9.3 ..............................................................................20
Testing the heating system9.4 .......................................................20
Specifi c settings10
Status of the appliance10.1 .............................................................21
Technical settings and a list of equipment parameters10.2 ............21
Re-check and restart10.3 ................................................................24
Informations for user11
Page 3
- 2 -
CONTENTS
ÚDRŽBA
Search and trouble-shooting12
Diagnosing faults12.1 ......................................................................25
Fault codes12.2 ...............................................................................25
Gas conversion13
Settings13.1 ....................................................................................26
Discharging water14
Heating system14.1 .......................................................................27
Servising15
Function check15.1 ........................................................................27
Replacement parts16
Spare parts17 Techni18 cal parameters
Page 4
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 3 -
INTRODUCTION
INTRODUCTION
Manual1
Product documentation1.1
Instructions are included with the device and after the installation must be handed to the user in accordance with applicable regulations.
Study the handbook carefully to ensure a safe installation, • safe use and proper service. W
e are not responsible for any damage resulting from failure to follow the instructions presented in this handbook.
Relevant documents1.2
Contents of the boiler is the following documentation: user manual, warranty card, a list of service centers, service
book
Explanation of symbols1.3
a
DANGER: Risk of injury.
e
DANGER: Risk of electric shock.
b
CAUTION: Risk of damage to the equipment or its edge parts.
i
IMPORTANT: Useful information.
Description of the device2
Safety regulations 2.1
The following regulations and safety instructions must be observed:
Never tamper with the safety devices.• Do not modify the equipment or its immediate surroundings,
as this could affect the safe use of the boiler. Do not under any circumstances destroy or remove the
sealing from any of the parts. Never carry out alone any maintenance or repairs to the
equipment. Only qualifi ed technicians may work with the equipment.
Be careful not to allow children to play with the boiler.• Do not plug or obstruct the ventilation system.
Some home “improvements” may signifi cantly affect the functioning of the boiler. Before carrying out any such intervention you must consult with the installer.
Do not site the equipment in excessive dampness.• Do not use and do not store explosive or fl ammable
materials (e.g. gasoline/petrol, aerosols, thinners, chlorine­based cleaning agents, paints, glues etc.) in the same space as the boiler. Under certain conditions these materials may be corrosive.
Do not touch the equipment surfaces - e.g. the ventilation • pipes, hydraulic connectors and so on — even after the boiler has been turned off, as these surfaces may be hot. Touching these surfaces may lead to burns or scalding.
Be prudent when using the hot water tap. Water coming out • of this tap may be scalding.
This equipment contains metal parts (components). In working with it and in cleaning it, particularly its corners, you must be careful.
If water leaks from the unit you must immediately turn off • the cold water intake and the leak must be repaired by a qualifi ed technician.
Do not store any objects on top of the equipment.
Product label2.2
Type the label indicates the country where the equipment was manufactured and the country where the equipment may be installed.
Location of the manufacturing label: Production label is located on the back of the electrical box. It is
accessible by tipping the entire electrical box. On the label is the type of boiler designation, serial number, the
appliance category, type and inlet gas pressure, CH maximum pressure, DHW maximum pressure, the maximum temperature in the boiler, DHW maximum fl ow, distribution, thermal output, thermal consumption, effciency, electrical casing and coverage certifi cation marks.
a
The device can be connected only to the type referred to the gas to the manufacturing label.
Type of gas2.3
This boiler is for natural gas but can be converted into propane. Natural gas: G25
Regulations and legal provisions2.4
CE mark 2.4.1
The boiler (as well as all its optional accessories) complies with the requirements of European Directive 90/396/EEC on gas-fuelled appliances and European Directive 92/42/ EEC on effi ciency, the European Directive 2006/95/EC on electrical means of operation for use in certain voltage ranges
Page 5
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 4 -
INTRODUCTION
and the European Directive 89/336/EEC on electromagnetic compatibility.
The appliance is also approved according to the European norms EN 677, EN 625, EN 60335-01, EN 50165, EN 55014, EN 61000-3-2 and EN 61000-3-3.
In order to operate and handle the boiler in accordance with the purpose for which it is designed in actual conditions of use (hereafter referred to only as use), it is necessary to abide also by additional conditions – the most essential of which (i.e. those which must not be omitted) are found in the following regulatory documents:
- in the design area: STN 06 0310 and STN 06 0830;
- in the fi re safety area: STN 92 0300;
- for installation and fi tting (and repairs): STN EN 1755 or STN 38 6460, as applicable STN 38 6462, Decree no. 48/1982 Coll. (as amended by the later prescriptions) and the binding occupational health regulations;
- in time of running and operation: STN 38 6405;
- in the area of discharge of combustion gases and air infl ow STN EN 483, company material – “catalogue of dual piping for discharge of combustion gases and infl ow of combustion air designated for type C gas appliances, i.e. in closed “TURBO” version.
Local Regulation2.4.2
The boiler is designated for operation within the normal AA5/ AB5 environment in compliance with STN 33 2000-3 and STN 33 2000-5-51 (i.e. a temperature range of 5 – 40°C, temperature-dependent humidity to a max. of 85%).
PANTHER boilers are suitable for the conditions of zones 1, 2 and 3, in rooms with a bath or shower and in washing areas as set out in STN 33 2000-7-701; they may not be installed in zone 0 (Fig.8). Before installation in the areas mentioned, protection against electric shocks must be provided for according to the same norms.
The boiler complies with Ministry of Health Decree No 13/1977 Coll., i.e. on noise, for installation in residential and public areas.
The boilers are built to operate with heating water, in compliance with STN 07 7401. (Above all, the water must never be acidic, i.e. its pH must be higher than 7 and it should have minimal carbonate hardness.)
The requirements regarding the characteristics of domestic water are set out in STN 83 0616 (potable water STN 75
7111). With regards to water with total material concentrations of calcium and magnesium greater than 1.8 mmol/l, further “non-chemical“ measures against scale deposits (e.g. operation of magnetic water treatments in combination with settling equipment) are advisable.
Silting up of the boiler with contaminants from the heating system or the settling of boiler scale on these disturbances, or on induced disturbances (e.g. silting up of the exchanger, pump breakdowns) are not covered by the boiler warranty.
The distance from fl ammable materials (e.g. PVC, fi breboard, polyurethane, synthetic fi bres, rubber etc.) must be suffi cient to keep the surface temperature of these materials below 80°C.
The minimum working (unhindered) space in close proximity to the boiler must be such that the boiler can be worked with easily and safely with bare hands and with the usual hand tools; we recommend a minimum distance of 300 mm from up and under, 10 mm from side and a minimum of 600 mm in front of the boiler.
CH (heating) + HW (hot water) -
The GEPARD boiler (model MTV and MOV) supplies both central heating and hot water for the home.
Non-condensing boiler with exhaust vented to a chimney -
Model MOV must be
tted to a ventilation system (chimney). The boiler comes equipped with a safety device that shuts off the gas feed if the chimney becomes blocked.
Non-condensing boiler with forced extraction of exhaust. -
The MTV model is gas models
tted with a ventilation system for the intake of air and the venting of exhaust. Thanks to this ventilation system, the heater can be installed in any space.
If the ventilator fails or if the chimney becomes blocked, the pressure switch shuts down the heater.
The boiler must be installed and commissioned by a qualifi ed technician. This ensures proper installation and operation in compliance with valid norms. If any maintenance, repair or adjustments concerning the gas are needed, a qualifi ed technician must be called.
Page 6
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 5 -
INTRODUCTION
Hydraulic scheme 2.5
23 MOV2.5.1
1
ABCDE
1
2
3
4
5
6
7
8
9
10
20
19
17 18
16
14
13
12
15
11
Legend 1 Safety valve 2 Gas valve 3 HW exchanger 4 Discharge valve 5 Burner 6 Ignition electrodes 7 NTC CH water intake temperature sensor 8 Combustion chamber 9 CH exchanger 10 Exhaust gas collector 11 Combustion thermostat 12 NTC CH return water temperature sensor 13 Expansion tank 14 Ionising electrode 15 Pump 16 CH pressure sensor 17 3–way motor valve 18 HW fl ow sensor 19 HW fi lter 20 Inlet valve A CH outlet B HW outlet C Gas inlet D HW inlet E CH inlet
Page 7
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 6 -
INTRODUCTION
23 MTV2.5.2
1
2
3
4
5
6
7
8
9
10
11
ABCDE
21
20
18 19
17
15
14
13
16
12
Legend 1 Safety valve 2 Gas valve 3 HW exchanger 4 Discharge valve 5 Burner 6 Ignition electrodes 7 NTC CH water intake temperature sensor 8 Combustion chamber 9 CH exchanger 10 Exhaust gas collector 11 Ventilator 12 Air manostat 13 NTC CH return water temperature sensor 14 Expansion tank 15 Ionising electrode 16 Pump 17 CH pressure sensor 18 3–way motor valve 19 HW fl ow sensor 20 HW fi lter 21 Inlet valve A CH outlet B HW outlet C Gas inlet D HW inlet E CH inlet
Page 8
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 7 -
INTRODUCTION
Safety instructions and regulations3
Safety instructions3.1
When gas pressure exceeds the limit specifi ed input device, the device may not start.
e
Incorrect installation can cause electric shock or damage to equipment.
Never disconnect safety devices and do not try to edit them.• Follow these steps and ways of handling:• Hold the device in its lower part ­Wear appropriate protective equipment, eg. gloves, safety -
shoes. Ensure that you adhere to proper lifting practices:• Have settled back. ­Do not rotate in the belt. ­Do not bend the upper body. ­Always take plant palms. ­Use for handles. ­Hold the load close to the body. ­If necessary, always ask for help. ­The user may not under any circumstances, interfere with
the installation of closed or edit. When engaging the right set seals to prevent leakage of gas
or water. This device contains metal parts (components) and when
handling and cleaning them, especially the corners, you have to be careful.
Before performing maintenance or replacement of a spare part must be carried out basic precautions:
Turn off the device.• Disconnect the device from the tension.• Close the valve to supply gas to the facility.• Hydraulic disconnect device by isolating valves, if they were
delivered. If you replace the hydraulic components that allow the device
off. While working with the device, protect all the electrical parts
from contact with water. Use only original spare parts.• Use only new O-rings and gaskets.• Upon completion of work on gas or water components of
check seal.
After the intervention, test the equipment to service and • safety check.
Page 9
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 8 -
INSTALATION
INSTALLATION
Location of equipment4
Location4.1
Instructions4.1.1
Before you choose a location for placement of equipment, carefully consult safety warnings and instructions in the user manual and installation guide.
Make sure the wall on which you installed the device, a • suffi ciently strong structure to hold the weight of equipment.
Ensure that the area in which the device installed, big • enough for its installation and that was around him a large enough space. This allows access and control of water mains, gas and ventilation (see Chapter clearance).
Explain the requirements of the user equipment.
Clearance4.2
The minimum working (unhindered) space in close proximity to the boiler must be such that the boiler can be worked with easily and safely with bare hands and with the usual hand tools; we recommend a minimum distance of 300 mm from up and under, 10 mm from side and a minimum of 600 mm in front of the boiler.
Boiler installation 5
Contents of delivery5.1
Contents of delivery
1 boiler 2 draw bar 3 exhaust gas diffuser (only for 23 MTV) 4 sealing 5 template 6 butt-end of water intake 7 butt-end of outlet valve 8 service manual 9 warranty
Check the contents of the packaging.
Recommendations before you install5.2
Nominal pipe internal diameter is chosen in the usual way, using the pump characteristic. Distribution pipes are designed according to the requirements for the system performance, not according to the boiler’s maximum output. However, measures must be taken in order to ensure suffi cient fl ow so that the water temperature difference in the supply and the return pipe is less than or equal to 20˚C. Minimum fl ow must be 400 l/h.
The piping system construction must prevent air bubbles from developing, making permanent bleeding of the system easier.
Bleeding valves should be situated on all high points of the system and on all radiators.
It is recommended to install upstream the boiler a set of heating water, hot water and gas isolation valves.
It is recommended to install upstream the boiler a set of heating water, hot water and gas isolation valves.
At the lowest point of the heating system we recommend installation of an exhaust valve, which shall also serve for fi lling of the heating system.
Before fi nal installation of the boiler, the heating distribution system pipes must be fl ushed a few times with pressurised water. In old, already used systems, the fl ushing must be done in the direction opposite to the fl owing heating water.
Important: Before connecting the boiler to the heating system, remove the plastic plugs located inside all connection outlets.
Before installing a new boiler, it is essential to clean the system thoroughly. In old systems it is necessary to remove all sludge settled at the bottom of radiators (predominantly gravity system).
In new systems it is necessary to remove all conservation material used by majority of radiator manufacturers.
It is recommended to install upstream the boiler (i.e. on the heating water return pipe) a sludge separator. The sludge separator should be constructed in such a way that it is easy to empty at regular time intervals without the necessity to drain a large quantity of water from the heating system. The separator can be combined with a fi lter, but a fi lter with a sieve alone is not suffi cient protection. The fi lter and sludge separator must be checked and cleaned regularly.
During reconstructions, in adverse building arrangements and so on, the boiler may be connected to the CH heating system, the HW system and the gas inlet with fl exible elements (hoses), but only those designated for this purpose. If fl exible elements are used, these should be as short as possible and must be protected from mechanical and chemical stresses and damages. It must also be ensured that before the end of their life cycle or reliability in maintaining their parameters (according to their manufacturers’ data) they are always replaced by new ones.
Note: The boiler includes fi lter which is situated below the HW ow sensor. You have to take out the HW fl ow sensor with fi lter to clean up the lter.
Page 10
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 9 -
INSTALATION
Dimensions5.3
Gepard 23 MOV5.3.1
311
410
742
179
205
Ø125
Gepard 23 MTV5.3.2
311
410
Ø39
742
184
205
82
65
116
65
82
205
26
160
134
Page 11
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 10 -
INSTALATION
Mounting the boiler 5.4
When mounting the boiler on the wall, proceed in accordance with the installation design conditions (e.g. wall load bearing properties, chimney inlet, pipe inlet and outlet connections).
The mounting procedure:
Take the paper template and attach it (for instance by ­adhesive tape) to the place of installation. When positioning the template, user a plumb line or a spirit level.
Using the marked points on the template, drill all necessary ­holes (mounting bar, connecting ramp).
If combustion gas discharge is to be directly via the building’s ­façade, project and mark a point for a pass of the concentric ducting.
Remove paper template. ­Drill the required holes, respecting the diameters shown in -
the template. Insert wall plugs into the holes for the mounting bar and then -
fasten the bar properly with the screws provided. Hang the boiler on the mounting bar. ­Install the combustion gases removal ducting onto the boiler. -
Fill-in the gaps between the ducting and the wall opening with a non-fl ammable material.
Remove the plastic plugs from the boiler outlets. ­Install the protective fi lter to the heating water inlet (not part -
of delivery). Mount isolation valves on all outlets from the boiler (not part -
of delivery). Connect heating water, hot water and gas distribution pipes -
to the isolation valves. Install lever for topping up water into the heating system. ­Fill boiler with water. ­Perform check of tightness of all connections. -
Page 12
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 11 -
INSTALATION
Hydraulic connection6
The boiler connection terminals may not be placed under undue pressure from the piping system for the CH circuit, the HW circuit or from the gas intake. This assumes a precise observance of the dimensions of the endings of all connecting pipes, with regard to height as well as distance from walls and separation distances of the interconnected individual intakes and outlets.
The heating system circuit should be connected to the boiler in such a way that during repairs to the boiler the heating water need be released only from the boiler.
1
2
3
4
5
6
Legend 1 gas valve 2 safety valve 3 plate to plate heat exchanger - 12 plates 4 auto air vent 5 WILO AC pump with two automatic speeds 6 fi lling loop
Page 13
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 12 -
INSTALATION
Air and exhaust lines7
1
3
4
2
5
6
Legend 1 chimney - 110 mm pre 12 kW, 125 mm pre 25 kW 2 over-fl ow safety device 3 draught diverter 4 heat exchanger 5 combustion chamber 6 burner - 13 blades
Page 14
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 13 -
INSTALATION
1
3 4
2
5
6
Legenda 1 fan 2 air pressure switch 3 draught diverter 4 heat exchanger 5 combustion chamber 6 burner - 13 blades
Page 15
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 14 -
INSTALATION
Regulations 7.1
The type MOV is designed for combustion gases to be removed and discharged into a chimney (through a chimney inlet) with a minimum stabilised thrust of 2 Pa. The boiler is connected to the chimney inlet by a fl ue of a diameter corresponding to the size of the boiler’s gas exhaust outlet. It is forbidden to place inside the combustion gases exhaust ducting any objects which impair the combustion gases fl ow (e.g. various types of heat exchangers to utilise their residual heat). The combustion gases exhaust ducting is not part of the boiler accessories.
Construction of the combustion gases exhaust ducting as well as that of the chimney must comply with relevant requirements. Compliance with the requirements specifi ed by these standards will prevent undesirable phenomena from occurring, such as excessive cooling of the combustion gases, penetration of dampness into brickwork and fl uctuations in the chimney thrust, and thus prevent undesirable effects on the boiler’s functioning.
The boiler takes combustion air from the space in which it is installed. Air must be supplied in suffi cient quantity in accordance with applicable regulations.
Venting of exhaust and drawing in of combustion air for the MTV type is done only through designated pipes.
The level sections of the piping slope at a gradient suffi cient to let the condensation drain towards an outside area or towards a receptacle designed to draw off condensation. To achieve this, the elbow joint may be gently bent away from the straight section. The upright sections of the piping are always fi tted with devices to draw off condensate. The devices for drawing off the condensate are installed where possible close to the passage where the exhaust exits the boiler. Breakdowns caused by leaking condensate are not covered by the boiler warranty.
Description exhausting kits7.2
Methods of air and fl ue gas ducting 7.2.1 (according to STN EN 483) and permitted piping lengths
If not described otherwise for the individual following methods of placing coaxial pipe routes and their drainages, the piping lengths (from connection at the boiler to the drainage) can be set as in the following cases.
Note: One Em is considered as either a 1 m direct section or one 90° joint.
Caution: If the lengths described for individual types are exceeded, the exhaust diffuser (orifi ce) must be removed from the ventilator drain.
The following methods of air intake and exhaust venting are recommended for the boiler:
The C7.2.2
12
method (MTV)
Level routes and level venting into an open area. Length of fume ducting (23 MTV):
60 / 100: min. 0.3 m (with one 90° joint), max. 3 m (with one ­90° joint).If the total fume ducting length is more than 0.5 m, the diffuser with a diameter of 39 mm must be removed.
80 / 125: min. 0.5 m (with one 90° joint), max. 9 m (with one ­90° joint).If the total fume ducting length is more than 1 m, the diffuser with a diameter of 39 mm must be removed.
An example of a level coaxial pipe route: version C
12
(complies
with STN EN 483)
The C7.2.3
32
method (MTV)
Vertical routes and vertical venting into an open space. Length of fume ducting (23 MTV):
60 / 100: min. 1 m (with one 90° joint), max. 4 m (with one ­90° joint). If the total fume ducting length is more than 1.5 m, the diffuser with a diameter of 39 mm must be removed.
80 / 125: min. 1 m (with one 90° joint), max. 10 m (with one ­90° joint). If the total fume ducting length is more than 1.5 m, the diffuser with a diameter of 39 mm must be removed.
An example of a vertical coaxial pipe route: version C
32
(complies with STN EN 483)
The C7.2.4
42
method (MTV)
Connecting to a double shared chimney. Double piping from independent boilers (independent routes)
can feed into shared chimneys; the transport capacity of the chimney is judged according to the manufacturer’s data on the chimney. If the pipes are set into the chimney in two directions and vertically aligned, there must be a vertical separation between the outlets of at least 0.45 m. Where two outlets vent towards each other, they must be separated by a minimum vertical distance of 0.6 m. The exhaust piping into the shared
Page 16
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 15 -
INSTALATION
double chimney never has terminal elements — the same as with pipes that vent into open areas!
Both components of the route — external (air) and internal (exhaust gas) — must safely feed into the relevant chimney duct but not protrude so deeply that they create blockages in the exhaust or air ducts.
Length of fume ducting (23 MTV):
60 / 100: min. 0.3 m (with one 90° joint), max. 3 m (with one ­90° joint). If the total fume ducting length is more than 0.5 m, the diffuser with a diameter of 39 mm must be removed.
The C7.2.5
52
method (MTV)
Separate double piping and venting into different areas (with different parameters, mainly of pressure)
For venting exhaust and bringing in air for combustion, separate piping may be used. The separate piping may not be routed on opposing walls of the building.
Length of fume ducting (23 MTV):
80 / 80: min. 2 x 0.5 m, max. 2 x 18 m. If the total fume ­ducting length is more than 2 x 2 m, the diffuser with a diameter of 39 mm must be removed.
The C7.2.6
82
method (MTV)
Using piping in cases where the air is drawn in from an open area and the exhaust vents into a shared chimney.
Length of fume ducting (23 MTV):
80 / 80: min. 2 x 0.5 m, max. 2 x 18 m. If the total fume ­ducting length is more than 2 x 2 m, the diffuser with a diameter of 39 mm must be removed.
Air may in the same way be brought in from an open space (or a space well supplied with air) and exhaust extracted into a common chimney (or, again, into a space with common venting of exhaust gases). The special case of B22 also belongs in this category. (See following text.)
The B7.2.7
22
method (MTV)
Extraction of exhaust (also in separate piping) into an open area and intake of combustion air from an internal space in the building in close proximity to the boiler (in coaxial piping with the perforation of its outer part).
Length of fume ducting (23 MTV):
80 / 80: min. 2 m, max. 2 m. The diffuser must be removed. -
When drawing in air for combustion from internal areas of the building, a suffi cient quantity of that air must be ensured. No other appliance may be connected to the exhaust duct (whether chimney or pipe), and when drawing in air at least 1.2 m3 of air/ hour per kW of boiler output must be available.
Page 17
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 16 -
INSTALATION
Piping gradient7.2.8
The layout of the piping must permit a down-gradient of the exhaust piping towards the boiler at a nominal gradient of 3 percent. A device for drawing off condensate must be placed on the piping as close as possible to the boiler.
Safety measures7.2.9
The distance of fl ammable materials from the exhaust component of the separate piping must be enough to ensure that the temperature at the surface of these materials is no higher than 80°C.
Exhaust may not be vented in areas:
where a danger of explosion is present (as set forth in STN • 33 2320)
that are interior areas of a building (lofts, halls, stairwells • etc.)
closeable, i.e. passages or gateways etc.• that descend underground (even if these remain open to
the surroundings and free of obstructions), e.g. tunnels, underpasses etc.
These basic injunctions for venting exhaust must always take adequate account of where independent air intakes are sited.
Wall apertures for coaxial piping for drawing in air and venting exhaust are cut to the appropriate size (approx. 120 to 150 mm) and sealed (with building construction methods) following the installation. Non-fl ammable materials (with Degree A of fl ammability according to STN 73 0823) must be used for sealing, e.g., masonry mortar, plaster etc. Openings in combustible walls or roofs must be made according to the fi rst section of this part.
Page 18
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 17 -
INSTALATION
Connecting the boiler to the electricity 8 supply
e
Incorrect installation can cause electric shock or damage to equipment. Electrical connection device can be performed only by a qualifi ed technician.
The device must be plugged directly into an accessible electrical plugs fi tted involved.
External leadership must be grounded with the right polarity and in accordance with current standards.
The manufacturer assumes no liability for personal injury or other damage caused by improper grounding of equipment. This applies also non-applicable standards.
Hooking up the boiler to the mains voltage is done through a triple-wire plug with a fl exible cord. The socket for connecting the boiler to the electrical network must comply with STN 33
2000-4-46. It must always have the protective ground (pin) reliably connected with the PE or PEN wire (a combination of green and yellow colours). The boiler must always be connected through its main to the ground and must always be installed in a way that allows access to the socket and plug. The use of a variety of “adaptors”, “extension cords” etc. is not permitted.
Caution: The preparation of plugs and sockets as well as room regulator connections that extend into the interior electrical components of the boiler must under all circumstances be carried only by a person with electrotechnical qualifi cations as set forth in Decree No. 50/1978 Coll. In the same way, servicing of the electrotechnical components may be carried out only by a person with the above-mentioned professional qualifi cations. Before servicing the electrotechnical elements the boiler must be disconnected from the current by pulling the mains lead from the socket!
The main body of the boiler is protected by a tube fuse (T 2A / 250 V), which is located on the boiler control board.
Entrance to BMU8.1
BMU is accessible when the front cover of the boiler and unloading ebox. Bellow the back cover is BMU, the composition of which it is possible to select the BMU.
1
Legenda 1 plastic clips
Page 19
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 18 -
INSTALATION
BMU8.2
1
Legend 1 Removable connector for 24V & Ebus room thermostats & outdoor sensor
Page 20
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 19 -
INSTALATION
Boiler wiring diagram8.3
1102113124135146157168179
18
1059483726
1
12 34
10987654321
1920 18 17 16 15 14 13 12 11
M
D TT
NTC
Ebus
24 V
X2
X30
X90
X32
X40
X51
X31
X25
X21
X13
230 VAC
LN
X12
X101
X15
FUS
X14
X20
X16
X17
X17
123
14253
6
10987654321
1920 18 17 16 15 14 13 12 11
423
1
3421
X2
12 1 11 1
1102113124135146157168179
18
X20
12 34
1
12
1
X21
18 17 16 15
2
1
3
4
5
9
7
6
8
10
11
12
14
X11
13
Legend 1 Regulation connector 2 Exalink connector 3 NTC solar connector 4 Alternative 24V connection 5 User interface 6 Hydraulic connector 7 Gas valve 8 Ventilator 9 Fuse 10 230 V connection 11 Pump 12 Electrodes 13 NTC CH water intake temperature sensor 14 NTC CH return water temperature sensor 15 Thermal fuse 16 NTC CH fl ow sensor 17 NTC HW fl ow sensor 18 3–way motor valve 19 CH pressure sensor
Page 21
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 20 -
INSTALATION
External accessories8.4
For regulating the boiler from a room regulator, only a regulator that has a no-voltage input, i.e. that does not send any external voltage into the boiler, may be used.
Load carrying capacity of the regulator with a relay switch is 24V / 0.1 A.
The room regulator must be connected to the boiler with a two-wire plug. The recommended cross-section for the room regulator connection (copper lead) is 1.5 mm
2
.
Leads for connecting the room regulator may not be coaxial with the mains voltage leads.
The terminal for hooking up the room regulator with the relay switch is supplied by the manufacturer with a connector and is located in the frame of the boiler control panel.
Room regulators may be connected to the GEPARD boiler via eBUS communication. For this type of equipment, however, we recommend installing only Protherm Thermolink B, Thermolink P or Thermolink RC regulators. Only in this way can the manufacturer guarantee the optimal functioning of the boiler.
The room regulator leads are connected to the terminal board of the boiler.
By means of the above-mentioned regulators the isothermal regulation function can be activated. All settings for isothermal curves are carried out with the aid of the room regulator.
Note: To activate the isothermal regulation the external temperature sensor must be installed. The external sensor lead is connected to the terminal board of the boiler.
The external sensor is placed on the coldest wall of the property (most often the northern wall).
Caution: The room regulator lead and the external sensor may not be coaxial with power cables (230 V current etc.).
Putting into operation 9
Filling the heating system9.1
Filling of water to the heating system using an external valve which is recommended when installing a heating system located on the distribution of heating water.
Note: In order to meet the heating system use fi lling loop, which is located in the boiler. This only serves to replenish the water system at a pressure drop heating water.
Re-fi lling of the boiler9.2
Bringing water into the heating system (small quantities only) can be done via the inlet valve on the boiler.
When fi lling the boiler the following conditions must be observed:
The water pressure on entry into the boiler must always be ­higher than the water pressure in the CH circuit.
Water is drawn into the boiler strictly in a cold state (CH ­temperature in the boiler up to 30°C).
The recommended water pressure in the cold boiler (up to ­30°C) is between 1 – 2 bar.
The pressure in the expansion tank is checked and if ­necessary adjusted to the correct value (see technical parameters on end of this manual).
First ignition9.3
Boiler switch on / off button on the control panel. When you turn to run the internal test control panel, then the boiler starts to respond to the requirements of the system. Before starting the rst check whether the gas inlet is open, all inputs and outputs of the heating system and whether it is in a desired system pressure.
Testing the heating system9.4
By activating these various test modes, you can enable special functions on the appliance.
Press the on/off button to switch off the appliance.• While keeping the button MODE pressed for more than 5
seconds, press the on/off button. The screen displays the fi rst test mode "P01".
Press button + or - to choose the test mode that you wish to • launch.
Press MODE to launch the test mode.• The number of the "PX" test mode and !On" fl ash on the screen.
The test mode will be automatically stop after 15 minutes.• When you have fi nished, press the On/Off button to exit the
test modes.
Page 22
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 21 -
INSTALATION
Code Parameter Description
P.01
Forcing the adjustable power burner when heating
The appliance functions at power adjustable from Pmin. to 100% by using buttons + or - on the right side after successful ignition.
P.02
Forcing the burner to heating ignition power
The appliance functions at ignition power after successful ignition.
P.03
Forcing the burner to heating Pmax
The appliance functions at its maximum power after successful ignition.
P.05 Filling the appliance
The 3 way valve is in the central position, the pump and the burner stop so that the appliance can be lled.
P.06 Venting the installation
The function is activated for a period of 5 minutes on the heating circuit. Make sure that the air vent is open.
P.07 Venting the appliance
The function is activated for a period of 5 minutes on the short circuit. Make sure that the air vent is open.
Specifi c settings10
Status of the appliance10.1
Press button "-" for more 3 seconds to learn the current state • of functioning of the appliance. The screen displays the state of the appliance "S.XX".
Press button MODE for more than 3 seconds to exit this • menu.
Status Heating mode
S.00 No request for heating S.01 Pre-run fan S.02 Pre- run pump S.03 Ignition S.04 Burner lit S.05 Post run pump/fan S.06 Post run fan S.07 Post run pump S.08 Time delay anti short-cycles after heating
Status Domestic hot water heating
S.10 Request for domestic hot water S.11 Pre-run fan S.13 Ignition S.14 Burner lit S.15 Post run pump/fan S.16 Post run fan S.17 Post run pump
Status Specifi c messages
S.30
Default status, no request for heating or domestic water. If an EBUS controller is connected to the boiler, check that a wiring link is present on terminals 3 and 4 of the boiler´s main board.
S.31 "Hot water only" mode
S.32
Control cycle: the speed of the fan in the function phase
is outside tolerance. S.34 "Frost protection" mode S.39 Underfl oor heating contact open S.40 Heating mode activated S.41 Water pressure too high
S.53
Waiting cycle: temperature differantial between heating
ow and return is too high. If T > 30, forcing to Pmin. S.54
Waiting cycle: lack of water in the installation/temperature
rise between heating fl ow and return is too high. S.96 Test temperature sensor for heating return
S.98
Test temperature sensors for heating fl ow and return, or
the appliance has a fault.
Technical settings and a list of equipment 10.2 parameters
Access to the installation and service mode is made as follows: Press and hold the MODE button pressed until the symbol
appears on the display "0". Use "+" and "-" to set to display the number "96" for the setup mode or the number "35" for the service mode and confi rm the MODE button. Now we are in mode, the display is shown of the parameter code and the parameter value. Use "+" and "-" on the control panel we choose the parameter and using the buttons "+" and "-" on the control panel changing the value of the parameter. When changing the value of the parameter number will display fl ash, set the desired value, and wait until the value stops fl ashing. This is automatically set to the value stored in memory.
The service climb mode, press and hold "MODE" to display the basic display. Where a service mode for some time not doing anything, the boiler itself automatically terminates service mode.
Page 23
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 22 -
INSTALATION
Code Description Manufacturing
setting
Minimum value
Maximum value
00 Heating part load, adjustable values in kW following power range 01 Central Heating Pump Overrun (min) 5 2 60 02 Maximum off period after central heating operation (min) 20 2 60 03 Domestic hot water fl ow temperature (°C) 04 Tank or micro-accumulation temperature (°C)
Only displayed when tank NTC connected
09 Nominal fl ow temperature from external eBus control (°C)
Only displayed if an eBus control is connected
10 Internal pump:
1 = on 0 = off
11 External pump:
1 = on 0 = off
12 Cylinder storage pump:
1 = on 0 = off
13 Circulation pump:
1…100 = on 0 = off
16 24V room thermostat
0 = open (no heating),
1 = closed (heating mode) 17 Type of temperature regulation: fl ow / return 0 0 1 18 Pump mode (post-run)
0= with burner
1= with RT
2= winter mode
102
19 Function mode of 2 speed pump mode setting:
0: burner mode = stage 2,
pre/post-run = stage 1;
1: CH + post-run = stage 1, DHW = stage 2,
2: automatic in CH, pre/post-run = stage 1,
DHW : stage 2
3: always stage 2
details see functional description
203
20 Maximum set value of the DHW setpoint (°C) 60 50 60 21 Warmstart function enabled and allowed
1 warmstart function enabled and allowed
0 warmstart function disabled or not allowed
01
22 DHW demand active (tank or tapping) :
1=on
0=off 23 Release of central heating
1 = CH release
0 = CH not released 24 air pressure switch
1: closed
0: open 25 Tank heating state
1=tank heating enable
0=tank heating disabled 27 Switching option relay 1 1 1 10 28 Switching option relay 2 2 1 10 31 Filling loop mode
0. manual
1. Semi-automatic
2. Full automatic
002
35 Position setpoint of the TWV
100 = DHW
0 = heating
40 = middle position
Page 24
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 23 -
INSTALATION
Code Description Manufacturing
setting
Minimum value
Maximum value
36 DHW waterfl ow sensor (l/min) 40 Flow temperature (°C) 41 Return temperature (°C) 43 Heating curve
Displayed only when outdoor T° sensor connected and no ebus control (sending a valid
CH setpoint) connected
1,2 0,2 4
44 Digitalized ionisation voltage (V) 45 Heating curve - base point adjustment
Displayed only when outdoor T° sensor connected and no ebus control (sending a valid
CH setpoint) connected
20 15 25
47 Outside temperature (°C)
Displayed only when outdoor T° sensor connected to the BMU 52 Offset for minimum steppermotor position (1 means 2 steps for motor with 480 steps) 45 0 99 53 Offset for maximum steppermotor position (1 means 2 steps for motor with 480 steps) -25 -99 0 62 Night/Day offset 0030 64 Average ignition time (s) 65 Maximum ignition time (s) 66 Disable warmstart function
0 : Warmstart disabled
1 : Warmstart enabled
101
67 Remaining burner blocking time (min) 68 Number of unsuccessfull ignitions at fi rst attempt 69 Number of unsuccessfull ignitions at second attempt 70 Three way valve working mode
0 : TWV in normal mode (heating position for heating and DHW position for DHW)
1 : TWV in permanent middle position
2 : TWV in permanent heating position
Only displayed and adjustable on system boilers
002
71 Maximum nominal value of fl ow temperature (°C) 75 45 80 77 Part load hot water in (kW)
Only displayed and adjustable on system boilers
závisí od výkonového rozsahu kotla
80 Operating hours in heating mode (h) 81 Operating hours in domestic hot water mode (h) 82 Number of burner starts in heating mode 83 Number of burner starts in DHW mode 85 Minimum power of the appliance (kW) závisí od výkonového rozsahu kotla 90 Digital control recognized:
1 = yes
0 = no 93 Adjustment of Device Specifi c Number
G20
0: 12 KOO
1: 12 KTO
2: 25 KOO
3: 25 KOV
4: 25 KTO
5: 25 KTV
6: 30 KTV
G31
1: 12 KTO
4: 25 KTO
5: 25 KTV
6: 30 KTV
7: 12 KOO
8: 25 KOO
9: 25 KOV
09
94 Reset fault codes list 0 0 1 95 Software Version of PeBus participiants
1. BMU
2. AI
Page 25
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 24 -
INSTALATION
Code Description Manufacturing
setting
Minimum value
Maximum value
96 Reset adjustable parameters to the factory settings 0 0 1
Re-check and restart10.3
After installing equipment, equipment check.• Start the installation to check that the settings are correct
and make sure equipment is working safely.
Informations for user11
On completion of installation the installer must:
user to explain how the equipment functions and safety ­devices, and if necessary running equipment and bring the user to answer questions;
user-submitted all necessary documentation; ­complete documents, where necessary; ­alert the user of the measures necessary to prevent damage -
to the system, equipment and buildings; user recalled that each year the device service. -
Page 26
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 25 -
MAINTENANCE
MAINTENANCE
Search and trouble-shooting 12
Diagnosing faults12.1
When displaying an error code the letter F will fl ash on the display together with the relevant error code.
During the normal course of operation of the device the ten most recent error alarms can be displayed by simultaneously pressing for seven seconds both keys for setting the CH temperature.
Fault codes12.2
i
Faults described in this chapter shall be removed by a qualifi ed technician and if necessary after-sales service.
Code Description
F0 Failure of NTC CH intake water temperature sensor F1 Failure of NTC CH water return temperature sensor F2 Failure of NTC HW sensor F3 Failure of NTC accumulator F4 Disruption of NTC collector F5 Failure of air supply sensor F6 Failure of draw sensor F7 Disruption of NTC HW return from solar sensor F8 Failure of NTC accumulator sensor ground F9 Failure of NTC exhaust hood sensor F10 Short circuit in NTC CH intake water temperature sensor F11 Short circuit in NTC CH return water temperature sensor
F12
Short circuit in NTC accumulator sensor ground
Short circuit in NTC CH sensor F13 Short circuit in NTC accumulator sensor F14 Short circuit in NTC collector sensor F15 Short circuit in air supply sensor F16 Short circuit in draw sensor F17 Short circuit in NTC HW return from solar sensor F18 Short circuit in NTC accumulator sensor ground F19 Short circuit in NTC exhaust hood sensor F20 Safe temperature limiter is active: Cut off due to overheating F21 Boiler locked out – threshold values exceeded F22 Low water in boiler – pump locked out
F23
Low water level: high temperature difference between outlet
and inlet NTC F24 Low water level: rapid temperature rise F25 High fl ow temperature F26 Incorrect fl ow value from stepmotor gas valve
F27
Flame sensing error – ionisation signal contrary to closed
gas valve F28 Failure to light burner at fi rst attempt F29 Loss of fl ame during burner operation
Code Description
F30 Failure of lock-out sensor F31 Short circuit in lock-out sensor
F32
Anti-freeze protection valve is active: ventilator rotations are outside tolerance limits
F33
Anti-freeze protection valve is active: Pressure sensor is not on
Pressure sensor is not off (when the ventilator is not running) F35 Flue system error F36 Draft detected (chimney version only) F37 Ventilator rpms during operation are outside tolerance limits F38 Measured frequency limit is outside tolerance limits F39 Error in boiler auto-detection F41 Incorrect gas regulation F42 Problem with coding resistor F43 Incorrect value for boiler variant F49 Low eBus voltage F55 Error in CO sensor F58 No feedback from preheater F60 Error gas valve + F61 Error gas valve ­F62 Error – gas valve turned off F63 EEPROM error F64 ADC error F65 High electronics temperature F66 Error in IIC collectors
F67
Flame signal from ASIC is unreliable
Detected fl ame input signal is outside range (0 or 5V) F70 Incorrect DSN F71 Flow sensor permanent failure
F72
Lengthy interval between fl ow sensor and NTC CH return
water sensor F73 CH pressure sensor not connected or short circuited F74 CH pressure sensor has electrical fault (or damaged cable)
F75
Permanent failure CH pressure sensor. No rise in pressure
detected following pump start F76 Thermal fuse failure in primary exchanger F80 Error in SHE entry sensor F81 Error in charger pump F82 Error in anode tester F90 Not connected to APC module F91 Error in APC module sensor
Page 27
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 26 -
MAINTENANCE
Gas conversion13
The Panther boilers are in their basic versions designed to use natural gas as fuel. The modifi cations required to switch to a different fuel must be carried out by an authorised technician with a valid manufacturer’s certifi cate.
For conversion to propane use the conversion kit for switching from natural gas to propane gas. The kit contains all necessary parts and instructions on how to perform the conversion.
Settings13.1
setting is performed electronically by setting on the control • panel
pressure is measured using the U-manometer (against • atmosphere) or other appropriate pressure gauge
before commencing setting, release the closing screw of the • measuring point of outlet gas pressure (1) and slide on the hose of the U-manometer
1
in the following steps proceed precisely according to the • service guide in the chapter “Setting minimum and maximum boiler output”, which is used upon exchange of gas valve
when setting minimum and maximum pressure use the • relevant values (see table)
After completing setting the boiler shuts down, the hose of the U-manometer is removed and the closing screw of the measuring point is tightened as appropriate. The boiler is started up and an air tightness test of the measuring points on the gas armature is performed.
Important:
during conversion the original parts supplied by the • manufacturer or person authorised thereby are used
setting of all elements is secured (e.g. by drop of paint)• type of fuel for which the boiler is heretofore designated is -
indicated in appropriate manner directly on boiler conversion, date and person performing conversion is -
recorded in the accompanying technical documentation of the boiler
23 kW
G20
20 mbar
G31
37 mbar
MTV MOV MTV MOV
Jet diameter (mm) 1,2 1,2 0,77 0,73 Pmin (mbar) 2,5 2,2 5,2 5,2 Pmin (mm H2O) 25,49 22,43 53 53 Pmax (mbar) 13,0 12,0 28,0 29,6 Pmax (mm H
2
O) 132,6 122,4 288,5 301,8
Shut down boiler using main switch.
Press (menu) button and also press the main switch of the • boiler.
Hold down the (menu) button. A point fl ashes on the display The parameter P00 OFF will appear on the display within
approx. 10 seconds Select the parameter P01 using the (+) or (-) button Use the MODE button to confi rm the data. After a brief period
the boiler burns at minimum output. Press MODE and hold for 10 seconds, with button (+) go to
service mode 35, confi rm with MODE, then with button (+) go to point 52
The number 50 appears on the boiler display (possible • setting 0 – 99)
Attach U-manometer and check that the minimum gas • pressure value corresponds to the prescribed value stated in the table.
In the case of deviation change the minimum boiler output • using the (+) and (–) buttons. Proceed in short steps and always wait for the level of the water column by the U-manometer to stabilise. The measured value most be identical to the value stated in the table.
After setting fi nished, hold MODE for 10 seconds to confi rm. The P01 appears on display. Using buttons (+) or (-) set
value 100 (maximum power). After a brief period the boiler burns at minimum output.
Press MODE and hold for 10 seconds, with button (+) go to • service mode 35, confi rm with MODE, then with button (+) go to point 53
The number 20 appears on the boiler display (possible • setting 0 – 99)
Attach U-manometer and check that the maximum gas • pressure value corresponds to the prescribed value stated in the table.
In the case of deviation change the maximum boiler output • using the (+) and (–) buttons. Proceed in short steps and always wait for the level of the water column by the U-manometer to stabilise. The measured value most be identical to the value stated in the table.
After setting fi nished, hold MODE for 10 seconds to confi rm and press MODE to fi nish the program mode.
Press the RESET button to slip to normal mode.
Important: The value stated on the display does not represent the value in mm/H2O.
Page 28
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 27 -
MAINTENANCE
Discharging water 14
The outlet valve is designated primarily for lowering the water pressure in the boiler during repairs. Only a partial discharge of water from the boiler is possible through this outlet.
A complete draining of water from only the boiler or the heating circuit and repeat fi lling must be carried out at inlet/outlet valves at appropriate locations in the heating circuit.
Discharging and fi lling of water into the heating circuit and the subsequent operations (air venting, regulating the expansion tank) are not covered by the boiler warranty.
If the HW in the boiler and piping is threatened with freezing, appropriate measures must be taken to avoid this entirely.
Note: The release valve is located on the right side of the boiler at the pump.
Heating system14.1
Release of water from the heating circuit follow through the discharge outlet, which should be placed on the outside of the boiler heating system. Valve on the boiler is used only for removing water from the boiler.
Servising 15
Serviced boiler shall only person with due authorization and properly trained equipment manufacturer. Serviced should be carried out at regular intervals in accordance with the warranty conditions.
Function check15.1
After putting into operation, it is necessary to carry out a functional check of the boiler and heating system throughout, as well as the external devices connected to the boiler.
Page 29
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 28 -
MAINTENANCE
Replacement parts 16
Burner16.1
Fan16.2
Page 30
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 29 -
MAINTENANCE
Air pressure switch16.3
Page 31
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 30 -
MAINTENANCE
Over - fl ow safety device16.4
Return heating NTC sensor16.5
Flow heating NTC sensor16.6
Page 32
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 31 -
MAINTENANCE
Pressure sensor16.7
Ignition transformator16.8
Page 33
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 32 -
MAINTENANCE
Plate to plate exchanger16.9
Page 34
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 33 -
MAINTENANCE
Gas valve16.10
Page 35
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 34 -
MAINTENANCE
DHW fl ow sensor16.11
Page 36
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 35 -
MAINTENANCE
Expansion vessel16.12
Page 37
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 36 -
MAINTENANCE
Spare parts17
To ensure safe operation and long life product, you must use only original parts from the manufacturer.
i
This product has the CE marking of conformity. Use only new original parts from the manufacturer.
Check the spare parts installed in the correct position and • in the right direction. After installation of the spare parts or servicing the equipment must be tested for safe operation.
Page 38
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 37 -
MAINTENANCE
Techniccal parameters18
Description Units GEPARD 23 MOV
Gas category II2H3P Distribution B11BS Ignition electronic
Power / fuel natural gas propane
Maximum thermal consumption kW 25,8 Minimum thermal consumption kW 10,4 Maximum thermal output kW 23,3 Minimum thermal output kW 9,0 Effi ciency % 89,9 Maximum gas consumption m
3
/h 2,73
Minimum gas consumption m
3
/h 1,10 Maximum gas consumption kg/h 2,64 Minimum gas consumption kg/h 1,13 NO
x
classifi cation 3
Gas pressure
Inlet pressure mbar 20 37 Membrane diameter mm 5,8 4,4 Maximum pressure in discharge nozzles mbar 11,4 27,8 Minimum pressure in discharge nozzles mbar 2,2 5,0 Discharge nozzle diameter mm 1,20 0,73
Heating
Maximum working pressure bar 3 Minimum working pressure bar 0,5 Recommended operating pressure bar 1 - 2 Temperature range °C 38 - 80 Expansion tank l 5 Maximum pressure in the expansion tank mbar 3
Hot water
Maximum pressure bar 10 Minimum pressure bar 0,5 Minimum HW fl ow l/min 1,7 Quantity of HW drawn (at T 30°C) l/min 11,1 Temperature range °C 38 - 60
Electrical data
Voltage / frequency V/Hz 230/50 Consumption W 92 Electrical casings IPX4D Current A 0,4
Exhaust venting method chimney
Fume ducting diameter mm 126 Exhaust gas temperature °C 110 Quantity of exhaust gas produced g/s 21,0 Noise dB < 50
Dimensions: height / width / depth mm 740 / 410 / 298 Weight without water kg 31
Page 39
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10 - protherm
- 38 -
MAINTENANCE
Description Units GEPARD 23 MTV
Gas category II2H3P Distribution C12, C32, C42, C52, C82, B22 Ignition electronic
Power / fuel natural gas propane
Maximum thermal consumption kW 25,0 Minimum thermal consumption kW 10,7 Maximum thermal output kW 23,3 Minimum thermal output kW 8,5 Effi ciency % 93 Maximum gas consumption m
3
/h 2,64 Minimum gas consumption m
3
/h 1,13 Maximum gas consumption kg/h 1,9 Minimum gas consumption kg/h 0,8 NO
x
classifi cation 3
Gas pressure
Inlet pressure mbar 20 37 Membrane diameter mm 5,95 4,20 Maximum pressure in discharge nozzles mbar 12,2 28,1 Minimum pressure in discharge nozzles mbar 2,4 5,1 Discharge nozzle diameter mm 1,20 0,73
Heating
Maximum working pressure bar 3 Minimum working pressure bar 0,5 Recommended operating pressure bar 1 - 2 Temperature range °C 38 - 80 Expansion tank l 5 Maximum pressure in the expansion tank mbar 3
Hot water
Maximum pressure bar 10 Minimum pressure bar 0,5 Minimum HW fl ow l/min 1,7 Quantity of HW drawn (at T 30°C) l/min 11,1 Temperature range °C 38 - 60
Electrical data
Voltage / frequency V/Hz 230/50 Consumption W 147 Electrical casings IPX4D Current A 0,4
Exhaust venting method turbo
Fume ducting diameter mm 60 / 100 , 80 / 125 , 80 / 80 Exhaust gas temperature °C 122 Quantity of exhaust gas produced g/s 13,4 Noise dB < 50
Dimensions: height / width / depth mm 740 / 410 / 298 Weight without water kg 34
Page 40
Page 41
www.protherm.eu
P2_GEPARD_installer manual_ work basis_EN_02 - 03/10
Insert the bar code
Protherm spol. s r.o. Pplk. Pľjušťa 45 909 01 Skalica Tel.: 034 6966 101 fax: 034 6966 111
Loading...