Proline T1000, T3000, T2000 User Manual

USER MANUAL
ON LINE UPS
UPS T1000 / 2000 / 3000
Uninterruptible Power Supply
www.pinnacle.co.za
CONTENT
1.SAFETY AND EMC INSTRUCTIONS..........................................................................
1.1 I
NSTALLATION
.........................................................................................................
1.2 O
PERATION
............................................................................................................
1.3 M
AINTENANCE, SERVICING AND FAULTS
......................................................................
1.4 T
RANSPORT
...........................................................................................................
1.5 S
TORAGE
...............................................................................................................
1.6 S
TANDARDS
...........................................................................................................
2. DESCRIPTION OF COMMONLY USED NOTATIONS ................................................
3. INTRODUCTION .......................................................................................................
3. INTRODUCTION .......................................................................................................
4. SYSTEM DESCRIPTION ...........................................................................................
5. CONNECTION AND OPERATION .............................................................................
5.1 C
ONNECTION AND OPERATION
...................................................................................
6. TROUBLE SHOOTING..........................................................................................
7. MAINTENANCE ....................................................................................................
7.1 O
PERATION
........................................................................................................
13
7.2 S
TORAGE
...........................................................................................................
13
8. TECHNICAL DATA................................................................................................
8.1 E
LECTRICAL SPECIFICATIONS
................................................................................
14
8.2 O
PERATING ENVIRONMENT
...................................................................................
14
8.3 T
YPICAL STORED ENERGY TIME (TYPICAL VALUES AT
25°C
IN MINUTES
:)......................
14
8.4 D
IMENSIONS AND WEIGHTS
...................................................................................
15
9. BATTERY MAINTENANCE....................................................................................
10. NOTES FOR BATTERY DISPOSAL AND BATTERY REPLACEMENT.................
11. OPERATING MODE.............................................................................................
11.1 U
TILITY POWER MODE
........................................................................................
18
11.2 B
ATTERY MODE
.................................................................................................
18
11.3 B
YPASS MODE
...................................................................................................
19
11.4 A
BNORMALITY MODE
..........................................................................................
19
12. COMMUNICATION PORT....................................................................................
12.1 RS232 I
NTERFACE
............................................................................................
20
12.2 AS400 I
NTERFACE(OPTION
) ...............................................................................
20
13. SOFTWARE ........................................................................................................
F
REE SOFTWARE DOWNLOAD – WINPOWER
................................................................
21
APPENDIX 1
BACK PANEL ...................................................................................
1.Safety and EMC instructions
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit!
1.1 Installation
Condensation may occur if the UPS is moved directly from a cold to a warm
environment. The UPS must be absolutely dry before being installed. Please allow
an acclimatization time of at least two hours.
Do not install the UPS near water or in damp environment.
Do not install the UPS where it would be exposed to direct sunlight or near heat.
Do not block ventilation openings in the UPS’s housing.
Place cables in such a way that no one can step on or trip over them.
For UPS T1000/2000/3000
Socket-outlets and socket of batteries are earthed by the input power cord, please
insert the power cord into mains socket before using of UPS.
Connect the UPS only to an earthed shockproof socket outlet.
The building wiring socket outlet (shockproof socket outlet) must be easily accessible
to close to the UPS.
This is operator installable .
1.2 Operation
Do not disconnect the earth conductor cable on the UPS or the building wiring
socket (grounded shockproof socket) during operation as this would remove the
ground to the UPS and of all connected loads.
The UPS output socket or output terminal block may be electrically lived even if the
UPS system is not connected to the building wiring terminal.
In order to fully disconnect the UPS, first press the Standby button, then disconnect
the mains lead.
Ensure that no liquid or other foreign objects can enter the UPS.
The UPS can be operated by any individuals with no previous experience.
1.3 Maintenance, servicing and faults
The UPS operates with hazardous voltages. Repairs may be carried out only by
qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
power supply (building wiring socket), components inside the UPS are still connected to the battery which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries.
Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals.
Batteries must be replaced only by qualified personnel.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the ground. Verify that no voltage is present before servicing!
Batteries have a high short-circuit current and pose a risk of shock. Take all
precautionary measures specified below and any other measures necessary when working with batteries:
remove all jewellery, wristwatches, rings and other metal objects
use only tools with insulated grips and handles.
When changing batteries, replace with the same quantity and the same type of
batteries.
Do not attempt to dispose of batteries by burning them. It could cause explosion.
Do not open or destroy batteries. Effluent electrolyte can cause injury to the skin and
eyes. It may be toxic.
Please replace the fuse only by a fuse of the same type and of the same amperage
in order to avoid fire hazards.
Do not dismantle the UPS, except the qualified maintenance personnel.
1.4 Transport
Please transport the UPS only in the original packaging (to protect against shock
and impact).
1.5 Storage
The UPS must be stockpiled in the room where it is ventilated and dry.
1.6 Standards
* Safety
IEC/EN 62040-1-1
* EMI
Conducted Emission....................................:IEC/EN 62040-2 Category C1
Radiated Emission.......................................:IEC/EN 62040-2 Category C1
Harmonic Current....................................:IEC/EN 61000-3-2 (Input Current≤16A)
Voltage Fluctuation and Flicker...............:IEC/EN 61000-3-3 (Input Current≤16A)
*EMS
ESD..........................................................:IEC/EN 61000-4-2 Level 4
RS........................................................ ....:IEC/EN 61000-4-3 Level 3
EFT........................................................... :IEC/EN 61000-4-4 Level 4
SURGE.................................................... :IEC/EN 61000-4-5 Level 4
CS............................................................ :IEC/EN 61000-4-6 Level 3
Power-frequency Magnetic field............... :IEC/EN 61000-4-8 Level 3
Low Frequency Signals.............................:IEC/EN 61000-2-2
2. Description of commonly used notations
Some or all of the following Notations may be used in this manual and may appear in your application process. Therefore, all users should be familiar with them and understand their explanations.
3. Introduction
This On-Line-Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically for Novell, Windows NT and UNIX servers.
The double-converter principle eliminates all mains power disturbances. A rectifier
converts the alternating current from the socket outlet to direct current. This direct current charges the batteries and powers the inverter. On the basis of this DC voltage, the inverter generates a sinusoidal AC voltage, which permanently supplies the loads.
Computers and periphery are thus powered entirely by the mains voltage. In the event of power failure, the maintenance-free batteries power the inverter.
This manual covers the UPS listed as follows. Please confirm whether it is the model you intend to purchase by performing a visual inspection of the Model No. on the rear panel of the UPS.
“S” Model: Long backup time
Model No. Type Model No. Type
UPS T1000 UPS T1000S UPS T2000 UPS T2000S UPS T3000
Standard
UPS T3000S
Long backup time
4. System Description
Figure 1: Display Panel
Switch Function
ON - Switch
Turn on UPS system:
By pressing the ON-Switch “I” the UPS system is turned on.
Deactivate acoustic alarm:
By pressing this switch an acoustic alarm can be deactivated.
OFF-Switch
When mains power is normal, the UPS system switches to Standby mode by pressing OFF-Switch “ “. It is then switched to Bypass and the inverter is off. At this moment, the output sockets are supplied with voltage via the bypass if the mains power is available.
Display Function
LINE LED
The green LINE LED lights up if mains voltage is applied to the UPS input.
LINE LED blinks when the phase and neutral conductor have been reversed at the input of the UPS system.
If LINE LED and BATTERY-LED light up, the mains power supply is out of tolerance.
BATTERY LED
The orange-coloured BATTERY-LED lights up when the mains power has failed and the inverter is being powered by the batteries.
BYPASS LED
The orange-coloured BYPASS LED lights up when the UPS system is supplying voltage provided by the mains power via the bypass.
INVERTER
LED
The green-coloured INVERTER LED lights up if the UPS system is supplying voltage provided by the mains power via the inverter.
FAULT LED
The red FAULT LED lights up and an acoustic warning signal is issued continuously when the UPS system is in fault condition. Press the Standby switch in order to turn off the warning tone.
Loading...
+ 18 hidden pages